User's Manual: Model EJA510A and EJA530A Absolute Pressure and Gauge Pressure Transmitters (Style: S2)
User's Manual: Model EJA510A and EJA530A Absolute Pressure and Gauge Pressure Transmitters (Style: S2)
User's Manual: Model EJA510A and EJA530A Absolute Pressure and Gauge Pressure Transmitters (Style: S2)
IM 01C21F01-01E
9th Edition
i
Contents
1. Introduction................................................................................................ 1-1
Regarding This Manual................................................................................................. 1-1
1.1 For Safe Use of Product ................................................................................... 1-2
1.2 Warranty.............................................................................................................. 1-3
1.3 ATEX Documentation........................................................................................ 1-4
2. Handling Cautions..................................................................................... 2-1
2.1 Model and Specifications Check...................................................................... 2-1
2.2 Unpacking........................................................................................................... 2-1
2.3 Storage................................................................................................................ 2-1
2.4 Selecting the Installation Location ................................................................. 2-1
2.5 Pressure Connection......................................................................................... 2-2
2.6 Waterproofing of Cable Conduit Connections............................................... 2-2
2.7 Restrictions on Use of Radio Transceiver...................................................... 2-2
2.8 Insulation Resistance and Dielectric Strength Test....................................... 2-2
2.9 Installation of Explosion Protected Type........................................................ 2-3
2.9.1 FM Approval........................................................................................ 2-3
2.9.2 CSA Certification................................................................................. 2-5
2.9.3 IECEx Certification.............................................................................. 2-7
2.9.4 ATEX Certification............................................................................... 2-8
2.10 EMC Conformity Standards............................................................................ 2-11
2.11 PED (Pressure Equipment Directive)............................................................ 2-11
2.12 Low Voltage Directive...................................................................................... 2-12
3. Component Names................................................................................... 3-1
4. Installation.................................................................................................. 4-1
4.1 Precautions ....................................................................................................... 4-1
4.2 Mounting ............................................................................................................ 4-1
4.3 Rotating Transmitter Section............................................................................ 4-2
4.4 Changing the Direction of Integral Indicator ................................................. 4-2
5. Installing Impulse Piping.......................................................................... 5-1
5.1 Impulse Piping Installation Precautions......................................................... 5-1
5.1.1 Connecting Impulse Piping to the Transmitter.................................... 5-1
5.1.2 Routing the Impulse Piping................................................................. 5-1
5.2 Impulse Piping Connection Examples............................................................ 5-2
IM 01C21F01-01E
iii
(8) Operation Mode Setup . ................................................................... 8-13
(9) Output Status Display/Setup when a CPU Failure .......................... 8-13
(10) Output Status Setup when a Hardware Error Occurs ..................... 8-13
(11) Range Change while Applying Actual Inputs ................................... 8-14
(12) Zero Point Adjustment ..................................................................... 8-14
(13) Span Adjustment............................................................................... 8-16
(14) Test Output Setup ............................................................................ 8-17
(15) User Memo Fields............................................................................. 8-17
8.4 Displaying Data Using the BT200................................................................... 8-17
8.4.1 Displaying Measured Data............................................................... 8-17
8.4.2 Display Transmitter Model and Specifications.................................. 8-17
8.5 Self-Diagnostics............................................................................................... 8-18
8.5.1 Checking for Problems..................................................................... 8-18
8.5.2 Errors and Countermeasures........................................................... 8-20
9. Maintenance............................................................................................... 9-1
9.1 Overview............................................................................................................. 9-1
9.2 Calibration Instruments Selection................................................................... 9-1
9.3 Calibration.......................................................................................................... 9-1
9.4 Disassembly and Reassembly......................................................................... 9-3
9.4.1 Replacing the Integral Indicator.......................................................... 9-3
9.4.2 Replacing the CPU Board Assembly.................................................. 9-4
9.4.3 Cleaning and Replacing the Capsule Assembly................................ 9-5
9.5 Troubleshooting................................................................................................. 9-6
9.5.1 Basic Troubleshooting........................................................................ 9-6
9.5.2 Troubleshooting Flow Charts.............................................................. 9-6
10. General Specifications........................................................................... 10-1
10.1 Standard Specifications.................................................................................. 10-1
10.2 Model and Suffix Codes.................................................................................. 10-3
10.3 Optional Specifications................................................................................... 10-4
10.4 Dimensions....................................................................................................... 10-6
Customer Maintenance Parts List
Model EJA510A and EJA530A
Absolute and Gauge Pressure Transmitter.................................... CMPL 01C21F01-01E
Revision Information
IM 01C21F01-01E
<1. Introduction> 1-1
1. Introduction
Thank you for purchasing the DPharp electronic
pressure transmitter. NOTE
The DPharp Pressure Transmitters are precisely For FOUNDATION FieldbusTM, PROFIBUS PA
calibrated at the factory before shipment. To ensure and HART protocol versions, please refer to
correct and efficient use of the instrument, please IM 01C22T02-01E, IM 01C22T03-00E and IM
read this manual thoroughly and fully understand 01C22T01-01E respectively, in addition to this
how to operate the instrument before operating it. manual.
IM 01C21F01-01E
<1. Introduction> 1-2
1.1 For Safe Use of Product (c) Operation
For the protection and safety of the operator • Wait 10 min. after power is turned off, before
and the instrument or the system including the opening the covers.
instrument, please be sure to follow the instructions
(d) Maintenance
on safety described in this manual when handling
this instrument. In case the instrument is handled in • Please do not carry out except being written
contradiction to these instructions, Yokogawa does to a maintenance descriptions. When these
not guarantee safety. Please give your attention to procedures are needed, please contact nearest
the followings. YOKOGAWA office.
• Care should be taken to prevent the build up of
(a) Installation
drift, dust or other material on the display glass
• The instrument must be installed by an expert and name plate. In case of its maintenance, soft
engineer or a skilled personnel. The procedures and dry cloth is used.
described about INSTALLATION are not
permitted for operators. (e) Explosion Protected Type Instrument
• In case of high process temperature, care • Users of explosion proof instruments should
should be taken not to burn yourself because refer first to section 2.9 (Installation of an
the surface of body and case reaches a high Explosion Protected Instrument) of this manual.
temperature. • The use of this instrument is restricted to those
• The instrument installed in the process is under who have received appropriate training in the
pressure. Never loosen the process connector device.
bolts to avoid the dangerous spouting of • Take care not to create sparks when accessing
process fluid. the instrument or peripheral devices in a
• During draining condensate from the hazardous location.
pressuredetector section, take appropriate care
to avoid contact with the skin, eyes or body, or (f) Modification
inhalation of vapors, if the accumulated process • Yokogawa will not be liable for malfunctions or
fluid may be toxic or otherwise harmful. damage resulting from any modification made
• When removing the instrument from hazardous to this instrument by the customer.
processes, avoid contact with the fluid and the
interior of the meter.
• All installation shall comply with local installation
requirement and local electrical code.
(b) Wiring
• The instrument must be installed by an expert
engineer or a skilled personnel. The procedures
described about WIRING are not permitted for
operators.
• Please confirm that voltages between the
power supply and the instrument before
connecting the power cables and that the
cables are not powered before connecting.
IM 01C21F01-01E
<1. Introduction> 1-3
1.2 Warranty
• The warranty shall cover the period noted on
the quotation presented to the purchaser at the
time of purchase. Problems occurred during the
warranty period shall basically be repaired free
of charge.
• In case of problems, the customer should
contact the Yokogawa representative from
which the instrument was purchased, or the
nearest Yokogawa office.
• If a problem arises with this instrument,
please inform us of the nature of the problem
and the circumstances under which it
developed, including the model specification
and serial number. Any diagrams, data and
other information you can include in your
communication will also be helpful.
• Responsible party for repair cost for the
problems shall be determined by Yokogawa
based on our investigation.
• The Purchaser shall bear the responsibility for
repair costs, even during the warranty period, if
the malfunction is due to:
- Improper and/or inadequate maintenance by
the purchaser.
- Failure or damage due to improper handling,
use or storage which is out of design
conditions.
- Use of the product in question in a location
not conforming to the standards specified by
Yokogawa, or due to improper maintenance
of the installation location.
- Failure or damage due to modification or
repair by any party except Yokogawa or an
approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after
delivery.
- Reason of force majeure such as fires,
earthquakes, storms/floods, thunder/
lightening, or other natural disasters, or
disturbances, riots, warfare, or radioactive
contamination.
IM 01C21F01-01E
<1. Introduction> 1-4
1.3 ATEX Documentation
This procedure is only applicable to the countries in European Union.
GB SK
CZ
DK
I LT
E LV
EST
NL
PL
SF
SLO
P
BG
RO
S
M
GR
IM 01C21F01-01E
<2. Handling Cautions> 2-1
2. Handling Cautions
This chapter describes important cautions 2.2 Unpacking
regarding how to handle the transmitter. Read
carefully before using the transmitter. When moving the transmitter to the installation site,
keep it in its original packaging. Then, unpack the
The EJA-A Series pressure transmitters are transmitter there to avoid damage on the way.
thoroughly tested at the factory before shipment.
When the transmitter is delivered, visually check
them to make sure that no damage occurred during 2.3 Storage
shipment. The following precautions must be observed when
Also check that all transmitter mounting hardware storing the instrument, especially for a long period.
shown in Figure 2.1 is included. If the transmitter (a) Select a storage area which meets the following
was ordered without the mounting bracket, the conditions:
transmitter mounting hardware is not included. After • It is not exposed to rain or water.
checking the transmitter, repack it in the way it was • It suffers minimum vibration and shock.
delivered until installation. • It has an ambient temperature and relative
Mounting bracket humidity within the following ranges.
U-bolt nut (S) (Flat type)
Plate Ambient temperature:
Adapter -40 to 85°C without integral indicator
-30 to 80°C with integral indicator
Relative humidity:
5% to 100% R.H. (at 40°C)
Preferred temperature and humidity:
approx. 25°C and 65% R.H.
(b) When storing the transmitter, repack it as nearly
U-bolt (L) as possible to the way it was packed when
delivered from the factory.
U-bolt (S)
(c) If storing a transmitter that has been used,
thoroughly clean the chambers inside the body,
U-bolt nut (L)
F0201.ai so that no measured fluid remains in it. Also
Figure 2.1 Transmitter Mounting Hardware make sure before storing that the transmitter
assemblies are securely mounted.
IM 01C21F01-01E
<2. Handling Cautions> 2-2
(b) Ambient Atmosphere 2.7 Restrictions on Use of Radio
Avoid installing the transmitter in a corrosive
atmosphere. If the transmitter must be installed
Transceiver
in a corrosive atmosphere, there must be
adequate ventilation as well as measures to
IMPORTANT
prevent intrusion or stagnation of rain water in Although the transmitter has been designed to
conduits. resist high frequency electrical noise, if a radio
(c) Shock and Vibration transceiver is used near the transmitter or its
Select an installation site suffering minimum external wiring, the transmitter may be affected
shock and vibration (although the transmitter is by high frequency noise pickup. To test for such
designed to be relatively resistant to shock and effects, bring the transceiver in use slowly from a
vibration). distance of several meters from the transmitter,
(d) Installation of Explosion-protected Transmitters and observe the measurement loop for noise
Explosion-protected transmitters can be effects. Thereafter, always use the transceiver
installed in hazardous areas according to the outside the area affected by noise.
types of gases for which they are certified.
See Subsection 2.9 “Installation of Explosion
Protected Type Transmitters.”
2.8 Insulation Resistance and
2.5 Pressure Connection Dielectric Strength Test
Since the transmitter has undergone insulation
WARNING resistance and dielectric strength tests at the
factory before shipment, normally these tests are
• Instrument installed in the process is not required. However, if required, observe the
under pressure. Never loosen the process following precautions in the test procedures.
connector bolts to avoid the dangerous
(a) Do not perform such tests more frequently than
spouting of process fluid.
is absolutely necessary. Even test voltages that
• During draining condensate from the
do not cause visible damage to the insulation
capsule assembly, take appropriate care to
may degrade the insulation and reduce safety
avoid contact with the skin, eyes or body,
margins.
or inhalation of vapors, if the accumulated
(b) Never apply a voltage exceeding 500 V DC
process fluid may be toxic or otherwise
(100 V DC with an internal lightning protector)
harmful.
for the insulation resistance test, nor a voltage
exceeding 500 V AC (100 V AC with an internal
The following precautions must be observed lightning protector) for the dielectric strength
in order to safely operate the transmitter under test.
pressure. (c) Before conducting these tests, disconnect
(a) Make sure that the process connection part is all signal lines from the transmitter terminals.
tightened firmly. Perform the tests in the following procedure:
(b) Make sure that there are no leaks in the impulse • Insulation Resistance Test
piping.
1) Short-circuit the + and – SUPPLY terminals in
(c) Never apply a pressure higher than the
the terminal box.
specified maximum working pressure.
2) Turn OFF the insulation tester. Then connect
the insulation tester plus (+) lead wire to the
2.6 Waterproofing of Cable shorted SUPPLY terminals and the minus (–)
Conduit Connections leadwire to the grounding terminal.
3) Turn ON the insulation tester power and
Apply a non-hardening sealant to the threads
measure the insulation resistance. The voltage
to waterproof the transmitter cable conduit
should be applied short as possible to verify
connections. (See Figure 6.7, 6.8 and 6.9.)
that the insulation resistance is at least 20 MΩ.
IM 01C21F01-01E
<2. Handling Cautions> 2-3
4) After completing the test and being very careful
not to touch exposed conductors disconnect the CAUTION
insulation tester and connect a 100 kΩ resistor
between the grounding terminal and the short- This instrument is tested and certified as
circuiting SUPPLY terminals. Leave this resistor intrinsically safe type or explosionproof
connected at least one second to discharge any type. Please note that the construction of
static potential. Do not touch the terminals while the instrument, installation, external wiring,
it is discharging. maintenance or repair is strictly restricted, and
non-observance or negligence of this restriction
• Dielectric Strength Test would result in dangerous condition.
1) Short-circuit the + and – SUPPLY terminals in
the terminal box.
2) Turn OFF the dielectric strength tester. Then WARNING
connect the tester between the shorted
SUPPLY terminals and the grounding terminal. To preserve the safety of explosionproof
Be sure to connect the grounding lead of the equipment requires great care during mounting,
dielectric strength tester to the ground terminal. wiring, and piping. Safety requirements also
3) Set the current limit on the dielectric strength place restrictions on maintenance and repair
tester to 10 mA, then turn ON the power and activities. Please read the following sections very
gradually increase the test voltage from ‘0’ to carefully.
the specified voltage.
4) When the specified voltage is reached, hold it
for one minute. 2.9.1 FM Approval
5) After completing this test, slowly decrease the
a. FM Intrinsically Safe Type
voltage to avoid any voltage surges.
Caution for FM intrinsically safe type. (Following
2.9 Installation of Explosion contents refer “DOC. No. IFM012-A12 P.1 and
2.”)
Protected Type
Note 1. Model EJA Series pressure transmitters
In this section, further requirements and differences with optional code /FS1 are applicable for
and for explosionproof type instrument are use in hazardous locations.
described. For explosionproof type instrument, • Applicable Standard: FM3600, FM3610,
the description in this chapter is prior to other FM3611, FM3810, ANSI/NEMA250
description in this users manual. • Intrinsically Safe for Class I, Division 1,
For the intrinsically safe equipment and Groups A, B, C & D. Class II, Division 1,
explosionproof equipment, in case the instrument Groups E, F & G and Class III, Division 1
is not restored to its original condition after any Hazardous Locations.
repair or modification undertaken by the customer, • Nonincendive for Class I, Division 2, Groups
intrinsically safe construction or explosionproof A, B, C & D. Class II, Division 2, Groups E,
construction is damaged and may cause dangerous F & G and Class III, Division 1 Hazardous
condition. Please contact Yokogawa for any repair Locations.
or modification required to the instrument. • Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T4
NOTE • Ambient temperature: –40 to 60°C
Note 2. Entity Parameters
For FOUNDATION Fieldbus and PROFIBUS
• Intrinsically Safe Apparatus Parameters
PA explosion protected type, please refer to
[Groups A, B, C, D, E, F and G]
IM 01C22T02-01E and IM 01C22T03-00E
respectively. Vmax = 30 V Ci = 22.5 nF
Imax = 165 mA Li = 730 µH
Pmax = 0.9 W
IM 01C21F01-01E
<2. Handling Cautions> 2-4
* Associated Apparatus Parameters Note 4. Maintenance and Repair
(FM approved barriers) • The instrument modification or parts
Voc ≤ 30 V Ca > 22.5 nF replacement by other than authorized
Isc ≤ 165 mA La > 730 µH representative of Yokogawa Electric
Pmax ≤ 0.9W Corporation is prohibited and will void
Factory Mutual Intrinsically safe and
• Intrinsically Safe Apparatus Parameters
Nonincendive Approval.
[Groups C, D, E, F and G]
[Intrinsically Safe]
Vmax = 30 V Ci = 22.5 nF
Hazardous Location Nonhazardous Location
Imax = 225 mA Li = 730 µH
Class I, II, III, Division 1,
Pmax = 0.9 W Groups A, B, C, D, E, F, G General
* Associated Apparatus Parameters EJA Series Pressure Purpose
Transmitters Safety Barrier Equipment
(FM approved barriers) + + + +
Voc ≤ 30 V Ca > 22.5 nF – – – –
Supply
Isc ≤ 225 mA La > 730 µH
Pmax ≤ 0.9 W
• Entity Installation Requirements
[Nonincendive]
Vmax ≥ Voc or Vt, Imax ≥ Isc or It,
Hazardous Location Nonhazardous Location
Pmax (IS Apparatus) ≥ Pmax (Barrier)
Class I, II, Division 2,
Ca ≥ Ci + Ccable, La ≥ Li + Lcable Groups A, B, C, D, E, F, G
Class III, Division 1. General
Note 3. Installation
EJA Series Pressure Purpose
• Barrier must be installed in an enclosure that Transmitters Equipment
meets the requirements of ANSI/ISA S82.01. + +
• Control equipment connected to barrier must Supply – –
not use or generate more than 250 V rms or Not Use
V dc. Safety Barrier
F0203.ai
IM 01C21F01-01E
<2. Handling Cautions> 2-5
Note 2. Wiring 2.9.2 CSA Certification
• All wiring shall comply with National Electrical
Code ANSI/NEPA70 and Local Electrical a. CSA Intrinsically Safe Type
Codes. Caution for CSA Intrinsically safe type.
• When installed in Division 1, “FACTORY (Following contents refer to “DOC No. ICS003-
SEALED, CONDUIT SEAL NOT A12 P.1-1 and P.1-2.”)
REQUIRED.”
Note 1. Model EJA Series differential, gauge,
Note 3. Operation and absolute pressure transmitters with
• Keep the “CAUTION” nameplate attached to optional code /CS1 are applicable for use
the transmitter. in hazardous locations
CAUTION: OPEN CIRCUIT BEFORE Certificate: 1053843
REMOVING COVER. SEAL ALL CONDUITS • Applicable Standard: C22.2 No.0, No.0.4,
WITHIN 18 INCHES. WHEN INSTALLED No.25, No.30, No.94, No.142, No.157,
IN DIV.1, “FACTORY SEALED, CONDUIT No.213
SEAL NOT REQUIRED.” INSTALL IN • Intrinsically Safe for Class I, Division 1,
ACCORDANCE WITH THE INSTRUCTION Groups A, B, C & D. Class II, Division 1,
MANUAL IM 1C22. Groups E, F & G and Class III, Division 1
• Take care not to generate mechanical Hazardous Locations.
sparking when accessing to the instrument • Nonincendive for Class I, Division 2, Groups
and peripheral devices in a hazardous A, B, C & D, Class II, Division 2, Groups F &
location. G, and Class III, Hazardous Locations. (not
Note 4. Maintenance and Repair use Safety Barrier)
• The instrument modification or parts • Encl. “Type 4X”
replacement by other than authorized • Temperature Class: T4
representative of Yokogawa Electric • Ambient temperature: –40* to 60°C
Corporation is prohibited and will void * –15°C when /HE is specified.
Factory Mutual Explosionproof Approval. • Process Temperature: 120°C max.
c. FM Intrinsically Safe Type/FM Note 2. Entity Parameters
Explosionproof Type • Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax) = 30 V
Model EJA Series pressure transmitters with
Maximum Input Current (Imax) = 165 mA
optional code /FU1 can be selected the type
Maximum Input Power (Pmax) = 0.9 W
of protection (FM Intrinsically Safe or FM
Maximum Internal Capacitance (Ci) = 22.5nF
Explosionproof) for use in hazardous locations.
Maximum Internal Inductance (Li) = 730 µH
Note 1. For the installation of this transmitter, * Associated apparatus (CSA certified barriers)
once a particular type of protection is Maximum output voltage (Voc) ≤ 30 V
selected, any other type of protection Maximum output current (Isc) ≤ 165 mA
cannot be used. The installation must be in Maximum output power (Pmax) ≤ 0.9 W
accordance with the description about the
Note 3. Installation
type of protection in this instruction manual.
• All wiring shall comply with Canadian
Note 2. In order to avoid confusion, unnecessary Electrical Code Part I and Local Electrical
marking is crossed out on the label other Codes.
than the selected type of protection when • The instrument modification or parts
the transmitter is installed. replacement by other than authorized
representative of Yokogawa Electric
Corporation and Yokogawa Corporation
of America is prohibited and will void
Canadian Standards Intrinsically safe and
nonincendive Certification.
IM 01C21F01-01E
<2. Handling Cautions> 2-6
[Intrinsically Safe] • When installed in Division 2, “SEALS NOT
Hazardous Location Nonhazardous Location REQUIRED.”
Class I, II, III, Division 1, Note 3. Operation
Groups A, B, C, D, E, F, G General • Keep the “CAUTION” label attached to the
EJA Series Pressure Purpose
Transmitters Safety Barrier Equipment
transmitter.
+ + + + CAUTION: OPEN CIRCUIT BEFORE
Supply – – – – REMOVING COVER.
OUVRIR LE CIRCUIT AVANT D´NLEVER
LE COUVERCLE.
• Take care not to generate mechanical
[Nonincendive] sparking when accessing to the instrument
Hazardous Location Nonhazardous Location and peripheral devices in a hazardous
Class I, II, Division 2, location.
Groups A, B, C, D, E, F, G
Class III, Division 1. General Note 4. Maintenance and Repair
EJA Series Pressure Purpose
• The instrument modification or parts
Transmitters Equipment
replacement by other than authorized
+ +
representative of Yokogawa Electric
Supply – –
Not Use Corporation and Yokogawa Corporation of
Safety Barrier America is prohibited and will void Canadian
F0204.ai
Standards Explosionproof Certification.
b. CSA Explosionproof Type Non-Hazardous Hazardous Locations Division 1
Locations
Caution for CSA explosionproof type.
Non-hazardous
Note 1. Model EJA Series differential, gauge, Location
Equipment 50 cm Max.
and absolute pressure transmitters with
optional code /CF1 are applicable for use
in hazardous locations:
42 V DC Max. Conduit
Certificate: 1089598 4 to 20 mA DC Sealing Fitting
• Applicable Standard: C22.2 No.0, No.0.4, Signal
EJA Series
No.25, No.30, No.94, No.142
• Explosionproof for Class I, Division 1, Non-Hazardous Hazardous Locations Division 2
Locations
Groups B, C and D.
Non-hazardous
• Dust-ignitionproof for Class II/III, Division 1, Location
Groups E, F and G. Equipment
• Encl “Type 4X”
• Temperature Class: T6, T5, and T4
• Process Temperature: 42 V DC Max.
4 to 20 mA DC Sealing Fitting
85°C (T6),100°C (T5), and 120°C (T4) Signal
• Ambient Temperature: –40* to 80°C EJA Series
F0205.ai
* –15°C when /HE is specified.
• Supply Voltage: 42 V dc max. c. CSA Intrinsically Safe Type/CSA
• Output Signal: 4 to 20 mA Explosionproof Type
Note 2. Wiring Model EJA Series pressure transmitters with
• All wiring shall comply with Canadian optional code /CU1 can be selected the type
Electrical Code Part I and Local Electrical of protection (CSA Intrinsically Safe or CSA
Codes. Explosionproof) for use in hazardous locations.
• In hazardous location, wiring shall be in
conduit as shown in the figure. Note 1. For the installation of this transmitter,
CAUTION: SEAL ALL CONDUITS WITHIN once a particular type of protection is
50 cm OF THE ENCLOSURE. selected, any other type of protection
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À cannot be used. The installation must be in
MOINS DE 50 cm DU BîTIER. accordance with the description about the
type of protection in this instruction manual.
IM 01C21F01-01E
<2. Handling Cautions> 2-7
Note 2. In order to avoid confusion, unnecessary • Installation Requirements
marking is crossed out on the label other Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
than the selected type of protection when Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
the transmitter is installed. Uo, Io, Po, Co, and Lo are parameters of
barrier.
2.9.3 IECEx Certification
Note 3. Installation
Model EJA Series differential, gauge, and absolute
• In any safety barreir used output current
pressure transmitters with optional code /SU2
must be limited by a resistor 'R' such that
can be selected the type of protection (IECEx
Io=Uo/R.
Intrinsically Safe/type n or flameproof) for use in
• The safety barrier must be IECEx certified.
hazardous locations.
• Input voltage of the safety barrier must be
Note 1. For the installation of this transmitter, less than 250 Vrms/Vdc.
once a particular type of protection is • The instrument modification or parts
selected, any other type of protection replacement by other than authorized
cannot be used. The installation must be in representative of Yokogawa Electric
accordance with the description about the Corporation and will void IECEx Intrinsically
type of protection in this instruction manual. safe and type n certification.
• The cable entry devices and blanking
Note 2. In order to avoid confusion, unnecessary elements for type n shall be of a certified type
marking is crossed out on the label other providing a level of ingress protection of at
than the selected type of protection when least IP54, suitable for the conditions of use
the transmitter is installed. and correctly installed.
a. IECEx Intrinsically Safe Type / type n • Electrical Connection:
The type of electrical connection is stamped
Caution for IECEx Intrinsically safe and type n. near the electrical connection port according
Note 1. Model EJA Series differential, gauge, to the following marking.
and absolute pressure transmitters with
Screw Size Marking
optional code /SU2 are applicable for use
ISO M20 × 1.5 female M
in hazardous locations.
• No. IECEx KEM 06.0007X ANSI 1/2 NPT female A
• Applicable Standard: IEC 60079-0:2004,
IEC 60079-11:1999, IEC 60079-15:2005,
IEC 60079-26:2004
• Type of Protection and Marking Code:
Ex ia IIC T4, Ex nL IIC T4 Location of the marking
• Ambient Temperature: –40 to 60°C
• Max. Process Temp.: 120°C F0206.ai
• Enclosure: IP67
Note 4. Operation
Note 2. Entity Parameters • WARNING:
• Intrinsically safe ratings are as follows: WHEN AMBIENT TEMPERATURE ≥ 55°C,
Maximum Input Voltage (Ui) = 30 V USE THE HEAT-RESISTING CABLES ≥
Maximum Input Current (Ii) = 165 mA 90°C.
Maximum Input Power (Pi) = 0.9 W
Maximum Internal Capacitance (Ci) = 22.5nF Note 5. Special Conditions for Safe Use
Maximum Internal Inductance (Li) = 730 µH • WARNING:
• Type “n” ratings are as follows: IN THE CASE WHERE THE ENCLOSURE
Maximum Input Voltage (Ui) = 30 V OF THE PRESSURE TRANSMITTER IS
Maximum Internal Capacitance (Ci) = 22.5nF MADE OF ALUMINUM, IF IT IS MOUNTED
Maximum Internal Inductance (Li) = 730 µH IN AN AREA WHERE THE USE OF ZONE
0 IS REQUIRED, IT MUST BE INSTALLED
SUCH, THAT, EVEN IN THE EVENT OF
RARE INCIDENTS, IGNITION SOURCES
DUE TO IMPACT AND FRICTION SPARKS
ARE EXCLUDED.
IM 01C21F01-01E
<2. Handling Cautions> 2-8
[Intrinsically Safe] Note 3. Operation
Hazardous Location Nonhazardous Location • WARNING:
Group I/IIC, Zone 0 AFTER DE-ENERGIZING, DELAY 10
General MINUTES BEFORE OPENING.
EJA Series Pressure IECEx certified Purpose • WARNING:
Transmitters Safety Barrier Equipment WHEN AMBIENT TEMPERATURE ≥ 70°C,
+ + + +
USE THE HEAT-RESISTING CABLES ≥
Supply – – – –
90°C.
• Take care not to generate mechanical
sparking when accessing to the instrument
[type n] and peripheral devices in a hazardous
Hazardous Location Nonhazardous Location location.
Group IIC, Zone 2 Note 4. Maintenance and Repair
• The instrument modification or parts
EJA Series Pressure IECEx Certified
Transmitters Equipment [nL] replacement by other than authorized
+ + representative of Yokogawa Electric
Supply – – Corporation is prohibited and will void IECEx
Not Use Certification.
Safety Barrier
F0207.ai 2.9.4 ATEX Certification
b. IECEx Flameproof Type (1) Technical Data
Caution for IECEx flameproof type.
a. ATEX Intrinsically Safe Type
Note 1. Model EJA Series differential, gauge,
and absolute pressure transmitters with Caution for ATEX Intrinsically safe type.
optional code /SU2 are applicable for use Note 1. Model EJA Series differential, gauge,
in hazardous locations: and absolute pressure transmitters with
• No. IECEx KEM 06.0005 optional code /KS2 for potentially explosive
• Applicable Standard: IEC60079-0:2004, atmospheres:
IEC60079-1:2003 • No. KEMA 02ATEX1030 X
• Type of Protection and Marking Code: • Applicable Standard: EN 50014:1997,
Ex d IIC T6...T4 EN 50020:1994, EN 50284:1999
• Enclosure: IP67 • Type of Protection and Marking code:
• Maximum Process Temperature: EEx ia IIC T4
120°C (T4), 100°C (T5), 85°C (T6) • Temperature Class: T4
• Ambient Temperature: –40 to 75°C (T4), • Enclosure: IP67
–40 to 80°C (T5), –40 to 75°C (T6) • Process Temperature: 120°C max.
• Supply Voltage: 42 V dc max. • Ambient Temperature: –40 to 60°C
• Output Signal: 4 to 20 mA dc
Note 2. Electrical Data
Note 2. Wiring • In type of explosion protection intrinsic
• In hazardous locations, the cable entry safety EEx ia IIC only for connection to a
devices shall be of a certified flameproof certified intrinsically safe circuit with following
type, suitable for the conditions of use and maximum values:
correctly installed. Ui = 30 V
• Unused apertures shall be closed with Ii = 165 mA
suitable flameproof certified blanking Pi = 0.9 W
elements. (The plug attached is certificated Effective internal capacitance; Ci = 22.5 nF
as the flame proof IP67 as a part of this Effective internal inductance; Li = 730 µH
apparatus.)
• In case of ANSI 1/2 NPT plug, ANSI
hexagonal wrench should be applied to
screw in.
IM 01C21F01-01E
<2. Handling Cautions> 2-9
Note 3. Installation Note 2. Electrical Data
• All wiring shall comply with local installation • Supply voltage: 42 V dc max.
requirements. (Refer to the installation • Output signal: 4 to 20 mA
diagram)
Note 3. Installation
Note 4. Maintenance and Repair • All wiring shall comply with local installation
• The instrument modification or parts requirement.
replacement by other than authorized • The cable entry devices shall be of a certified
representative of Yokogawa Electric flameproof type, suitable for the conditions of
Corporation is prohibited and will void KEMA use.
Intrinsically safe Certification.
Note 4. Operation
Note 5. Special Conditions for Safe Use • Keep the “CAUTION” label to the transmitter.
• In the case where the enclosure of the CAUTION: AFTER DE-ENERGIZING,
Pressure Transmitter is made of aluminium, DELAY 10 MINUTES BEFORE OPENING.
if it is mounted in an area where the use of WHEN THE AMBIENT TEMP.≥70°C, USE
category 1 G apparatus is required, it must HEAT-RESISTING CABLES ≥ 90°C.
be installed such, that, even in the event of • Take care not to generate mechanical
rare incidents, ignition sources due to impact sparking when accessing to the instrument
and friction sparks are excluded. and peripheral devices in a hazardous
location.
[Installation Diagram]
IM 01C21F01-01E
<2. Handling Cautions> 2-10
(3) Installation (6) Name Plate
Name plate
WARNING
• All wiring shall comply with local installation
requirement and local electrical code.
• There is no need of the conduit seal for : Refer to USER'S MANUAL
(4) Operation
WARNING F0210.ai
IM 01C21F01-01E
<2. Handling Cautions> 2-11
2.10 EMC Conformity Standards Model
PS*1
V(L)
PS-V
Category*2
(bar) (bar-L)
EN 61326-1 Class A, Table 2 (For use in industrial Article 3, paragraph 3
EJA110A 160 0.01 1.6
locations) (SEP)
Article 3, paragraph 3
EN 61326-2-3 EJA120A 0.5 0.01 0.005
(SEP)
Article 3, paragraph 3
EN 61326-2-5 (for Fieldbus) EJA130A 420 0.01 4.2
(SEP)
EJA130A
420 0.01 4.2 III
CAUTION With code /PE3
Article 3, paragraph 3
EJA310A 160 0.01 1.6
(SEP)
This instrument is a Class A product, and it is
Article 3, paragraph 3
designed for use in the industrial environment. EJA430A 160 0.01 1.6
(SEP)
Please use this instrument in the industrial Article 3, paragraph 3
EJA440A 500 0.01 50
environment only. (SEP)
EJA440A
500 0.01 50 III
With code /PE3
Article 3, paragraph 3
EJA510A 500 0.01 50
(SEP)
NOTE EJA510A With
500 0.01 50 III
code /PE3
YOKOGAWA recommends customer to apply Article 3, paragraph 3
the Metal Conduit Wiring or to use the twisted EJA530A 500 0.01 50
(SEP)
pair Shield Cable for signal wiring to conform the EJA530A
500 0.01 50 III
requirement of EMC Regulation, when customer With code /PE3
installs the EJA Series Transmitters to the plant. *1: PS is maximum allowable pressure for vessel itself.
*2: Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 97/23/EC
(3) Operation
2.11 PED (Pressure Equipment
Directive) CAUTION
(1) General • The temperature and pressure of fluid should
• EJA series of pressure transmitters are be applied under the normal operating
categorized as pressure accessories under the condition.
vessel section of this directive 97/23/EC, which • The ambient temperature should be applied
corresponds to Article 3, Paragraph 3 of PED, under the normal operating condition.
denoted as Sound Engineering Practice (SEP).. • Please pay attention to prevent the
• EJA130A, EJA440A, EJA510A, and EJA530A excessive pressure like water hammer,
can be used above 200 bar and therefore etc. When water hammer is to be occurred,
considered as a part of a pressure retaining please take measures to prevent the
vessel where category lll, Module H applies. pressure from exceeding PS by setting the
These models with option code /PE3 conform safety valve, etc. at the system and the like.
to that category. • When external fire is to be occurred, please
take safety measures at the device or
(2) Technical Data
system not to influence the transmitters.
• Models without /PE3
Article 3, Paragraph 3 of PED, denoted as
Sound Engineering Practice (SEP) .
• Models with /PE3
Module: H
Type of Equipment: Pressure Accessory-Vessel
Type of Fluid: Liquid and Gas
Group of Fluid: 1 and 2
IM 01C21F01-01E
<2. Handling Cautions> 2-12
2.12 Low Voltage Directive
Applicable standard: EN 61010-1
IM 01C21F01-01E
<3. Component Names> 3-1
3. Component Names
External indicator Transmitter section
conduit connection (Note 1)
CPU assembly
Zero-adjustment screw
Integral
indicator (Note 1)
Mounting screw Pipe (Open to atmosphere)
(Note 3)
Range-setting
switch (Note 1)
(See Subsection 7.5)
Amplifier Cover
Setting Pin (CN4) Burn-Out Output at
Position (Note 2) Direction Burn-Out
H
110% or
HIGH higher
L
H
-5% or
LOW lower
L
F0301.ai
Note 1: See Subsection 10.2, “Model and Suffix Codes,” for details.
Note 2: Insert the pin (CN4) as shown in the figure above to set the burn-out direction. The pin is set to the H side for delivery (unless
option code /C1 is specified in the order).
The setting can be confirmed by calling up parameter D52 using the BRAIN TERMINAL. Refer to Subsection 8.3.3 (8).
Note 3: Applied to Model EJA530A with Measurement span code A, B, and C.
IM 01C21F01-01E
<4. Installation> 4-1
4. Installation
4.1 Precautions Vertical pipe mounting
Before installing the transmitter, read the cautionary
notes in Section 2.4, “Selecting the Installation
Adapter
Location.” For additional information on the ambient
conditions allowed at the installation location, refer
U-bolt (S) Plate
to Subsection 10.1 “Standard Specifications.”
U-bolt nut (S)
IMPORTANT
• When welding piping during construction,
take care not to allow welding currents to U-bolt nut (L)
flow through the transmitter.
• Do not step on this instrument after Mounting bracket
installation. 50 mm(2-inch) pipe U-bolt (L)
Gasket
F0402.ai
IM 01C21F01-01E
<4. Installation> 4-2
IMPORTANT IMPORTANT
Tighten the hexagonal nut part of the capsule Do not rotate the transmitter section more than
assembly. See Figure 4.3. 180°.
Transmitter section
Rotate 90° or 180° segments
Capsule assembly
Conduit connection
Zero-adjustment screw
Gasket
Pipe
F0405.ai
IM 01C21F01-01E
<5. Installing Impulse Piping> 5-1
IM 01C21F01-01E
<5. Installing Impulse Piping> 5-2
(3) Impulse Piping Slope
Tap valve
The impulse piping must be routed with only an
upward or downward slope. Even for horizontal
routing, the impulse piping should have a slope of Union or flange
Stop valve
at least 1/10 to prevent condensate (or gases) from
accumulating in the pipes.
IM 01C21F01-01E
<6. Wiring> 6-1
6. Wiring
6.1 Wiring Precautions 6.3 Connections of External
Wiring to Terminal Box
IMPORTANT
• Lay wiring as far as possible from electrical
6.3.1 Power Supply Wiring Connection
noise sources such as large capacity Connect the power supply wiring to the SUPPLY +
transformers, motors, and power supplies. and – terminals.
• Remove electrical connection dust cap
Transmitter terminal box
before wiring. +
• All threaded parts must be treated with Power supply
waterproofing sealant. (A non-hardening –
and power cables through the same ducts. Figure 6.1 Power Supply Wiring Connection
• Explosion-protected instruments must
be wired in accordance with specific 6.3.2 External Indicator Connection
requirements (and, in certain countries,
legal regulations) in order to preserve the Connect wiring for external indicators to the CHECK
effectiveness of their explosionprotected + and – terminals.
features. (Note) Use a external indicator whose internal resistance is 10Ω
or less.
• The terminal box cover is locked by an Allen
head bolt (a shrouding bolt) on CENELEC External indicator
Power supply
and IECEx flameproof type transmitters. +
When the shrouding bolt is driven clockwise
–
by an Allen wrench, it is going in and cover
lock is released, and then the cover can
be opened by hand. See Subsection 9.4
Transmitter terminal box
“Disassembly and Reassembly” for details. F0602.ai
(a) Use stranded leadwires or cables which are Connect the BT200 to the SUPPLY + and
the same as or better than 600 V grade PVC – terminals (Use hooks). The communication line
insulated wire (JIS C3307) or equivalent. requires a reception resistor of 250 to 600Ω in
(b) Use shielded wires in areas that are susceptible series.
to electrical noise. Transmitter terminal box Power supply
(c) In areas with higher or lower ambient +
temperatures, use appropriate wires or cables. –
(d) In environment where oils, solvents, corrosive
Ignore the polarity
gases or liquids may be present, use wires or since the BT200 is
cables that are resistant to such substances. AC-coupled to the
BT200 terminal box.
(e) It is recommended that crimp-on solderless
F0603.ai
terminal lugs (for 4 mm screws) with insulating
Figure 6.3 BT200 Connection
sleeves be used for leadwire ends.
IM 01C21F01-01E
<6. Wiring> 6-2
6.3.4 Check Meter Connection (2) Intrinsically Safe Type
Connect the check meter to the CHECK + and For intrinsically safe type, a safety barrier must be
– terminals (use hooks). included in the loop.
• A 4 to 20 mA DC output signal from the CHECK Hazardous Location Nonhazardous Location
+ and – terminals.
(Note) Use a check meter whose internal resistance is 10Ω or Transmitter terminal box
less. Distributor
(Power supply unit)
Power supply
+ Receiver
instrument
– +
–
Check meter
Transmitter terminal box Safety barrier
F0604.ai F0606.ai
Figure 6.4 Check Meter Connection Figure 6.6 Connection between Transmitter and
Distributor
Tee
Transmitter terminal box
Distributor
(Power supply unit)
Drain plug
IM 01C21F01-01E
<6. Wiring> 6-3
(2) Flameproof Type 6.5 Grounding
Wire cables through a flameproof packing adapter, Grounding is always required for the proper
or using a flameproof metal conduit. operation of transmitters. Follow the domestic
■ Wiring cable through flameproof packing adapter. electrical requirements as regulated in each
• Apply a nonhardening sealant to the terminal country. For a transmitter with built-in lightning
box connection port and to the threads on the protector, grounding should satisfy ground
flameproof packing adapter for waterproofing. resistance of 10Ω or less.
Ground terminals are located on the inside and
Apply a non-hardening
sealant to the threads for outside of the terminal box. Either of these terminals
waterproofing. may be used.
Transmitter terminal box
Wiring metal
conduit
Ground terminal
(Inside)
Tee
Drain plug
Flexible metal conduit
600
Flameproof
heavy-gauge External E–10.5
steel conduit load R= Communication
0.0236
resistance applicable range
R (Ω) BRAIN and HART
Tee
Flameproof flexible
Drain plug
metal conduit 250
Seal fitting
After wiring, impregnate the fitting
with a compound to seal tubing.
F0609.ai
IM 01C21F01-01E
<7. Operation> 7-1
7. Operation
7.1 Preparation for Starting Confirming that Transmitter is Operating
Properly
Operation
This section describes the operation procedure for Using the BT200
measuring a pressure as shown in Figure 7.1.
• If the wiring system is faulty, ‘communication
error’ appears on the display.
NOTE • If the transmitter is faulty, ‘SELF CHECK
ERROR’ appears on the display.
Confirm that the process pressure tap valve,
drain valve, and stop valve are closed. PARAM
C60:SELF CHECK
ERROR
communication error
(a) Introduce a process fluid into the impulse piping
and then to the transmitter in the following
procedure: DATA DIAG PRNT ESC
1) Open the tap valve (main valve) to fill the Communication error Self-diagnostic error
(Faulty wiring) (Faulty transmitter)
impulse piping with process fluid. F0702.ai
Union or flange
Self-diagnostic error on
Vent plug (Fill plug) the integral indicator
(Faulty transmitter)
F0703.ai
Tap valve
NOTE
Stop valve If any of the error indications above appears on
the display of the integral indicator or BT200,
refer to Subsection 8.5.2 for corrective action.
Tee
Verify and Change Transmitter
Union or flange Parameter Setting and Values
Drain valve
The following parameters are the minimum settings
Drain plug required for operation. The transmitter has been
F0701.ai
shipped with these parameters. To confirm or
Figure 7.1 Liquid Flow Measurement (Gauge change the values, see Subsection 8.3.3.
Pressure Transmitters)
• Measuring range … See Subsection 8.3.3 (2)
• Operation mode … See Subsection 8.3.3 (7)
IM 01C21F01-01E
<7. Operation> 7-2
7.2 Zero Point Adjustment 7.2.1 When you can obtain Low Range
Value from actual measured value of
Adjust the zero point after operating preparation is
0% (0 kPa, atmospheric pressure);
completed.
For pressure measurement using gauge pressure
IMPORTANT transmitters, follow the step below before zero point
adjustment.
Do not turn off the power to the transmitter
1) Close the tap valve (main valve).
immediately after a zero adjustment. Powering
2) Loosen the fill plug so that the pressure applied
off within 30 seconds after a zero adjustment
to the transmitter is only the head of the seal
will return the adjustment back to the previous
liquid.
settings.
3) Adjust the zero point at this status.
4) After the adjustment, close the fill plug and then
The zero point adjustment can be made in either
gradually open the tap valve.
way: using the zero-adjustment screw of the
transmitter or the BT200 operation.
Using the Transmitter Zero-adjustment
For output signal checking, display the parameter Screw
A10: OUTPUT (%) in the BT200.
Before adjusting a screw, check that the parameter
BT200 J20: EXT ZERO ADJ displays ENABLE. See
PARAM Output signal (%)
Subsection 8.3.3 (11) for the setting procedure.
A10:OUTPUT(%)
display
0.0 %
A11:ENGR OUTPUT
Use a slotted screwdriver to turn the zero-
A20:AMP TEMP
adjustment screw. Turn the screw clockwise
to increase the output or counterclockwise to
DATA DIAG PRNT ESC decrease the output.
The zero point adjustment can be made with a
Zero-adjustment Screw resolution of 0.01% of the setting range. Since
the degree of zero adjustments varies with the
screw turning speed, turn the screw slowly for fine
adjustment and quickly for coarse adjustment.
IM 01C21F01-01E
<7. Operation> 7-3
7.2.2 When you cannot obtain Low Range 7.3 Starting Operation
Value from actual measured value of
After completing the zero point adjustment, follow
0%;
the procedure below to start operation.
Convert the actual measured value obtained by a
1) Confirm the operating status. If the output
digital manometer or a glass gauge into %.
signal exhibits wide fluctuations (hunting) due
[Example] to periodic variation in the process pressure,
use BT200 to dampen the transmitter output
The measuring range of 50 to 250 kPa; the actual signal. Confirm the hunting using a receiving
measured value of 130 kPa. instrument or the integral indicator, and set
130–50 the optimum damping time constant. See
Actual measured value= x 100=40.0% Subsection 8.3.3 (3), “Damping Time Constant
250–50
Setup.”
2) After confirming the operating status, perform
Using the Transmitter Zero-Adjustment the following.
Screw
Turn the screw to match the output signal to the IMPORTANT
actual measured value in %.
• Remove the BT200 from the terminal box,
Using the BT200 and confirm that none of the terminal screws
are loosened.
Select the parameter J10: ZERO ADJ. Change • Close the terminal box cover and the
the set point (%) displayed for the parameter to the amplifier cover. Screw each cover in tightly
actual measured value (%), and press the ENTER until it will not turn further.
key twice. See Subsection 8.3.3 (11) for operation • Two covers are required to be locked on
details. the CENELEC and IECEx Flameproof type
SET Display at J10 transmitters. An Allen head bolts (shrouding
J10:ZERO ADJ
-0.0 % bolts) are provided under edge of the
+ 000.0
each cover for locking. When a shrouding
bolts are driven counterclockwise by an
CLR ESC
Allen wrench, it is coming out and locks
up a cover. (See page 9-4) After locking,
the covers should be confirmed not to be
SET
J10:ZERO ADJ opened by hand.
-0.0 % Change setting to the actually
+ 040.0 • Tighten the zero-adjustment cover mounting
measured value (40.0%).
screw to fix the cover in position.
Press key twice
F0706.ai
7.4 Shutting Down Operation
Shut down the transmitter operation as follows.
1) Turn off the power.
2) Close the stop valve.
3) Close the tap valve.
NOTE
Whenever shutting down the transmitter for a
long period, remove any process fluid from the
transmitter pressure-detector section.
IM 01C21F01-01E
<7. Operation> 7-4
7.5 Setting the Range Using the IMPORTANT
Range-setting Switch
• Do not turn off the power to the transmitter
With actual pressure being applied to the immediately after completion of the change
transmitter, the range-setting switch (push-button) in the LRV and/or HRV setting(s). Note
located on the optional /E integral indicator plate that powering off within thirty seconds after
and the external zero-adjustment screw allow users setting will cause a return to the previous
to change (re-range) the low- and high-limit values settings.
for the measurement range (LRV and HRV) without • Changing LRV automatically changes HRV
using BT200. However, other changes in the to the following value.
display settings (scale range and engineering unit)
for the integral indicator requires BT200. HRV =
previous HRV + (new LRV – previous LRV)
Follow the procedure below to change the LRV and
HRV settings. • If the range-setting push-button and external
zero-adjustment screw are not touched
[Example] during a range-change operation, the
transmitter automatically switches back to
Rerange LRV to 0 and HRV to 3 MPa.
the normal operation mode.
1) Connect the transmitter and apparatus as
shown in Figure 9.1 and warm up for at least Integral indicator
five minutes.
2) Press the range-setting push-button. The Note : Use a thin bar which
has a blunt tip, e.g.,
integral indicator then displays “LSET.” a hexagonal wrench,
3) Apply a pressure of 0 kPa (atmospheric to press the range-
setting push-button
pressure) to the transmitter. (Note 1)
4) Turn the external zero-adjustment screw in the
desired direction. The integral indicator displays
Range-setting switch
the output signal in %. (Note 2) (Push-button)
5) Adjust the output signal to 0% (1 V DC) by F0707.ai
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-1
Power
supply
cc
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-2
8.2 BT200 Operating Procedures 8.2.2 Operating Key Functions
8.2.1 Key Layout and Screen Display (1) Alphanumeric Keys and Shift Keys
Figure 8.3 shows the arrangement of the operating You can use the alphanumeric keys in conjunction
keys on the BT200 keypad, and Figure 8.4 shows with the shift keys to enter symbols, as well as
the BT200 screen component. alphanumeric keys.
LCD
(21 character × 8 lines) Alphanumeric keys
0.3
Alphanumeric keys
1 –9
F0806.ai
Figure 8.4 BT200 Screen Component Use the function key [F2] to select between
CAPS
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-3
Use the function key [F1] CODE to enter symbols.
The following symbols will appear in sequence, one
at a time, at the cursor each time you press [F1]
CODE:
/ . − , + * ) ( ’ & % $ # ” !
To enter characters next to these symbols, press [>]
to move the cursor.
symbol command
l/m
(I) (/) (m)
F0809.ai
Function keys
F0810.ai
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-4
8.2.3 Calling Up Menu Addresses Using the Operating Keys
PARAM
01:MODEL
EJA510A-DC
INITIAL 02:TAG NO. FUNC
DATA YOKOGAWA 1.MENU
SCREEN 03:SELF CHECK (ESC) 2.UPLOAD TO BT200
GOOD 3.DOWNLOAD TO INST
OK 4.PRINT ALL DATA
(SET) (ADJ)
(HOME MENU SCREEN) (SET MENU SCREEN) (ADJ MENU SCREEN)
MENU MENU MENU
A.DISPLAY C.SETTING J.ADJUST
B.SENSOR TYPE D.AUX SET 1 K.TEST
MENU E.AUX SET 2 M.MEMO
SCREEN H:AUTO SET P:RECORD
HOME SET ADJ ESC HOME SET ADJ ESC HOME SET ADJ ESC
PARAM PARAM
A60:SELF CHECK C60:SELF CHECK
GOOD GOOD
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-5
8.3 Setting Parameters Using the BT200
8.3.1 Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters EJA110A, EJA120A, and EJA130A
P: Pressure transmitters EJA310A, EJA430A, EJA440A, EJA510A, and EJA530A
L: Liquid level transmitters EJA210A and EJA220A
Applica-
Rewrita- bility
No. Item Description Remarks Default Value
bility
F P L
01 MODEL Model+capsule type –
02 TAG NO. Tag number – 16 alphanumerics
03 SELF CHECK Self-diagnostic result – GOOD/ERROR
A DISPLAY Measured data display – Menu name
A10 OUTPUT (%) Output (in %) – –5 to 110%*3
A11 ENGR. OUTPUT Output (in engineering units) – –19999 to 19999
A20 AMP TEMP Amplifier temperature – Unit specified in D30
A21 CAPSULE Capsule temperature – Unit specified in D30
TEMP
A30 STATIC PRESS Static pressure – Unit specified in D31*1 –
A40 INPUT Input (indicated as the value – –32000 to 32000
after zeroing)
A60 SELF CHECK Self-diagnostic messages – GOOD/ERROR, CAP MODULE FAULT, AMP
MODULE FAULT, OUT OF RANGE, OUT OF SP
RANGE*1, OVER TEMP (CAP), OVER TEMP (AMP),
OVER OUTPUT, OVER DISPLAY, ILLEGAL LRV,
ILLEGAL HRV, ILLEGAL SPAN, and ZERO ADJ OVER
B SENSOR TYPE Sensor type – Menu name
B10 MODEL Model+span – 16 uppercase alphanumerics
B11 STYLE NO. Style number –
B20 LRL Lower range-limit – –32000 to 32000
B21 URL Upper range-limit – –32000 to 32000
B30 MIN SPAN Minimum span – –32000 to 32000
B40 MAX STAT.P. Maximum static pressure*6 – –
B60 SELF CHECK Self-diagnostic messages – Same as A60
C SETTING Setting data – Menu name
C10 TAG. NO. Tag number 16 alphanumerics As specified when
ordered.
C20 PRESS UNIT Measurement range units Selected from mmH2O, As specified when
mmAq, mmWG, mmHg, Torr, ordered.
Pa, hPa, kPa, MPa, mbar, bar,
gf/cm2, kgf/cm2, inH2O, inHg,
ftH2O, psi, or atm
C21 LOW RANGE Measurement range, lower –32000 to 32000(but within As specified when
range value measurement range) ordered.
C22 HIGH RANGE Measurement range, higher –32000 to 32000(but within As specified when
range value measurement range) ordered.
C30 AMP DAMPING Damping time constant Selected from 0.2*2, 0.5, 1.0, 2.0 s
2.0, 4.0, 8.0, 16.0, 32.0, or
64.0 sec.
C40 OUTPUT MODE Output mode and integral Selected from OUT:LIN; DSP: As specified when – –
indicator mode LIN, OUT:LIN; DSP:SQR, ordered.
OUT:SQR; DSP:SQR If not specified, OUT:
LIN; DSP: LIN.
C60 SELF CHECK Self-diagnostic messages – Same as A60
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-6
Applica-
Rewrita- bility
No. Item Description Remarks Default Value
bility
F P L
D AUX SET 1 Auxiliary setting data 1 – Menu name
D10 LOW CUT Low cut 0.0 to 20.0% 10.0%
D11 LOW CUT Low cut mode LINEAR/ZERO LINEAR
MODE
D15 OUT LIMIT(L) Lower output range-limit –5.0 to 110.0% –5.0%*7
D16 OUT LIMIT(H) Upper output range-limit –5.0 to 110.0% 110.0%
D20 DISP SELECT Display selection NORMAL %/USER SET, As specified when
USER & %/INP PRES, PRES ordered.
&%
D21 DISP UNIT Engineering unit for display 8 uppercase alphanumerics
D22 DISP LRV Engineering range, lower –19999 to 19999 As specified when
range value ordered.
D23 DISP HRV Engineering range, higher –19999 to 19999 As specified when
range value ordered.
D30 TEMP UNIT Temperature setting units deg C/deg F deg C
D31 STAT. P. UNIT Static pressure setting units Selected from mmH2O, As specified when –
mmAq, mmWG, mmHg, Torr, ordered. If not
Pa, hPa, kPa, MPa, mbar, bar, specified, MPa.
gf/cm2, kgf/cm2, inH2O, inHg,
ftH2O, psi, or atm
D40 REV OUTPUT Output reversal NORMAL/REVERSE If not specified,
NORMAL.
D45 H/L SWAP Impulse piping accessing NORMAL/REVERSE*4 NORMAL – –
direction
D52 BURN OUT CPU error – HIGH/LOW, –5 to 110%*3 HIGH
D53 ERROR OUT Hardware error HOLD/HIGH/LOW, HIGH
–5 to 110%*3
D60 SELF CHECK Self-diagnostic messages – Same as A60
E AUX SET 2 Auxiliary setting data 2 – Menu name
E10 DFS MODE DFS mode OFF/ON*5 ON –
E14 TEMP SELECT Reference temperature AMP. TEMP/CAP. TEMP*5 CAP. TEMP –
sensor
E15 TEMP ZERO Zero shift conpensation ±10.00*5 0.00 –
setup
E30 BI DIRE MODE Bidirectional mode OFF/ON OFF – –
E50 AUTO Auto-recover from sensor OFF/ON ON
RECOVER error
E60 SELF CHECK Self-diagnostic messages – Same as A60
H AUTO SET Automatic setup – Menu name
H10 AUTO LRV Automatic measurement –32000 to 32000 Displays the same
range lower range value data as C21.
setup
H11 AUTO HRV Automatic measurement –32000 to 32000 Displays the same
range higher range value data as C22.
setup
H60 SELF CHECK Self-diagnostic messages – Same as A60
J ADJUST Adjustment data – Menu name
J10 ZERO ADJ Automatic zero adjustment –5 to 110.0%*3
J11 ZERO DEV. Manual zero adjustment
J15 SPAN ADJ Manual span adjustment –10.00 to 10.00% 0.00%
J20 EXT. ZERO ADJ External zero-adjustment ENABLE/INHIBIT
screw permission
J30 AOUTPUT 4mA 4mA adjustment –10.00 to 10.00% 0.00%
J31 OUTPUT 20mA 20mA adjustment –10.00 to 10.00% 0.00%
J60 ASELF CHECK Self-diagnostic messages – Same as A60
K TEST Tests – Menu name
K10 OUTPUT in % Test output % setting –5 to 110.0%*3 Displays
‘ACTIVE’ while executing
K60 SELF CHECK Self-diagnostic messages – Same as A60
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-7
Applica-
Rewrita- bility
No. Item Description Remarks Default Value
bility
F P L
M MEMO Memo – Menu name
M10 MEMO 1 Memo 8 uppercase alphanumerics
M20 MEMO 2 Memo 8 uppercase alphanumerics
M30 MEMO 3 Memo 8 uppercase alphanumerics
M40 MEMO 4 Memo 8 uppercase alphanumerics
M50 MEMO 5 Memo 8 uppercase alphanumerics
M60 SELF CHECK Self-diagnostic messages – Same as A60
P RECORD History of the errors –
P10 ERROR REC 1 Last error Display the error
P11 ERROR REC 2 One time before Display the error
P12 ERROR REC 3 Two time before Display the error
P13 ERROR REC 4 Three time before Display the error
P60 SELF CHECK Self-diagnostic messages – Same as A60
*1: In case of Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
*2: When Optional code /F1 is specified, substitute the value with 0.1.
*3: When Optional code /F1 is specified, substitute the value –5 with –2.5.
*4: Not applicable for Model EJA115.
*5: Applicable only for Model EJA118W, EJA118N, EJA118Y, EJA438W, and EJA438N.
*6: See MWP(max. working pressure) on the nameplate. B40 shows an approximate value of maximum pressure for the capsule.
*7: Unless otherwise specified by order. When optional code /F1 is specified, substitute the value –5 with –2.5.
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-8
8.3.2 Parameter Usage and Selection
IMPORTANT
Before describing the procedure for setting
parameters, we present the following table showing If the transmitter is turned off within 30 seconds
how the parameters are used and in what case. after parameters have been set, the set data
will not be stored and the terminal returns to
previous settings.
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-9
8.3.3 Setting Parameters SET Set TAG NO. and press the
C10:TAG NO.
Set or change the parameters as necessary. After YOKOGAWA key.
FIC-1a _
completing these, do not fail to use the “DIAG” key
to confirm that “GOOD” is displayed for the self- CODE caps CLE ESC
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-10
b. Setting Calibration Range Lower Range
Value and Higher Range Value • Example 2: With present settings of 0 to
(C21: LOW RANGE, C22: HIGH RANGE) 30 kPa, set the Higher range
value to10 kPa.
These range values are set as specified in the
order before the instrument is shipped. Follow the
SET
C22:HIGH RANGE
Set 10.
30 kPa Press the key twice
procedure below to change the range. + 10
to enter the setting.
• The measurement span is determined by DEL CLR ESC
the high and low range limit values. In this
SET Press the (OK) key.
instrument, changing the low range value also C22:HIGH RANGE
10 kPa
automatically changes the high range value,
keeping the span constant.
FEED NO OK
SET
C20:PRESS UNIT
The higher range value is • Example: Change from 2.0 sec to 4.0 sec.
kPa
C21:LOW RANGE changed while the span remains
SET
0.5 kPa
constant. C30:AMP DAMPING Use the or
C22:HIGH RANGE
2.0 sec
30.5 kPa
DATA DIAG PRNT ESC < 2.0 sec > key to select 4.0 sec.
< 4.0 sec >
< 8.0 sec > Press the key twice
(Span = Higher range value – Lower range value ) < 16.0 sec >
ESC to enter the setting.
F0814.ai
SET
C30:AMP DAMPING Press the (OK) key.
• Note, however, that changing the higher range 4.0 sec
2.0sec
any decimal point) for low or high range limits
within the range of −32000 to 32000. 4.0sec
8.0sec
16.0sec
32.0sec
64.0sec
F0816.ai
Note: The damping time constant set here is the damping time
constant for the amplifier assembly. The damping time
constant for the entire transmitter is the sum of the values
for the amplifier assembly and for the capsule assembly.
For the capsule assembly damping time constant (fixed),
see the “General Specifications” found at the end of this
manual. (See Chapter 10.)
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-11
(4) Output Signal Low Cut Mode Setup (5) Change Output Limits
(D10: LOW CUT, D11: LOW CUT MODE) (D15: OUT LIMIT(L), D16: OUT LIMIT(H))
Low cut mode can be used to stabilize the output The range of normal output is preset at factory from
signal near the zero point. The low cut point can be -5.0 to 110.0% unless otherwise specified, and the
set in a range from 0 to 20% of output. (Hysteresis output is limited with these upper and lower values.
of cut point: ±1%) This output range can be changed, for example, to
meet the requirements of NAMUR, etc. within the
LOW CUT at 10%
settable range. Set the lower limit with D15: OUT
50 LIMIT(L) and upper limit with D16: OUT LIMIT(H).
Settable range: −5.0 to 110.0 (%)
Output(%)
Lower limit < Upper limit
A40:INPUT
FEED NO OK
456 kPa
PARAM
D10:LOW CUT
PRES & % Indicates input pressure and %
10.0 % alternately in 3 second intervals.
D11:LOW CUT MODE
ZERO
D20:DISP SELECT A10:OUTPUT (%)
NORMAL %
DATA DIAG PRNT ESC 45.6 %
A40:INPUT
F0818.ai 456 kPa
F0819.ai
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-12
See (a.) through (c.) for each setting procedure. a. Display Selection (D20: DISP SELECT)
Follow the instructions given to the below to change
% indication and User-set engineering
the range of integral indication scales.
input pressure unit display
indication When USER SET is selected, the user set values
of integral indication and A11: ENGR. OUTPUT
D20: DISP SELECT D20: DISP SELECT
NORMAL % USER SET
parameter are indicated.
INP PRES USER & %
PRES & % • Example: Set the integral indicator scale to
engineering units display.
Set for user-set
engineering unit display. SET Use the or key
D20:DISP SELECT
NORMAL %
<NORMAL %> to select “USER SET.”
<USER SET>
Transmitter is set D21: DISP UNIT <USER & %> Press the key twice to
<INP PRES>
ESC enter the setting.
for “% display” when Set a unit to be
shipped. displayed on the BT200. SET
D20:DISP SELECT Press the (OK) key.
USER SET
FEED NO OK
F0822.ai
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-13
c. Lower and Higher Range Value Setup in (8) Operation Mode Setup
Engineering Unit (D40: REV OUTPUT)
(D22: DISP LRV, D23: DISP HRV)
This parameter allows the direction of the 4 to 20
These parameter items are used to set the lower mA output to be reversed with respect to input.
and higher range values for the engineering unit Follow the procedure below to make this change.
display.
• Example: Change 4 to 20 mA output to 20 to
When the instrument is shipped, these are set
4 mA output.
as specified in the order. Follow the procedure
below to change these settings. Note that these SET
D40:REV OUTPUT
Use the or key
NORMAL
parameters need not be set for % display. < NORMAL > to select REVERSE.
< REVERSE>
Press the key twice to
• Example: Set lower range value (LRV) to –50 ESC
enter the setting.
and higher range value (HRV) to 50.
F0825.ai
Setting LRV
SET
D22:DISP LRV
Set “–50.” (9) Output Status Display/Setup when a CPU
-
0M
50 Press the key twice to Failure
enter the setting. (D52: BURN OUT)
DEL CLR ESC
This parameter displays the status of 4 to 20 mA
Setting HRV DC output if a CPU failure occurs. In case of a
SET Set “50.” failure, communication is disabled.
D23:DISP HRV
100M
+ 50 Press the key twice to
Setting of HIGH or LOW is enabled. This is done
enter the setting.
DEL CLR ESC
with the pin (CN4) on the CPU assembly. See
Chapter 3 for details.
SET Press the (OK) key. Standard specifications
D23:DISP HRV
50M
The parameter is set to HIGH. If a failure, the
transmitter outputs the signal of 110% or higher.
FEED NO OK
The parameter D53: ERROR OUT is set to HIGH
PARAM from the factory.
D21:DISP UNT
M
D22:DISP
-
LRV
50M
Optional code/C1
D23:DISP HRV
DATA
50M
DIAG PRNT ESC The parameter is set to LOW. If a failure, output
which is −5% or lower is generated. The parameter
F0823.ai
D53: ERROR OUT is set to LOW from the factory.
(7) Unit Setup for Displayed Temperature
(D30: TEMP UNIT) • Example: Standard specifications
D52: BURN OUT pin (CN4) position: H
When the instrument is shipped, the temperature HIGH
• Example: Change the unit for the temperature (10) Output Status Setup when a Hardware
display. Error Occurs
(D53: ERROR OUT)
SET
D30:TEMP UNIT
Use the or key
deg C
< deg C > to select “deg F.” This parameter allows the setting of the output
< deg F >
Press the key twice to status when a hardware error occurs. The following
ESC
enter the setting. three selections are available.
F0824.ai
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-14
(a) HOLD; Outputs the last value held before the Note that changing the higher range value does not
error occurred. cause the lower range value to change but does
(b) HIGH; Outputs an output of 110% when an change the span.
error has occurred.
(c) LOW; Outputs an output of −5% when an error • Example 2: When the higher range value is to
has occurred. be changed to 10 kPa with the
Note: A hardware error means CAP MODULE FAULT of Er.01 present setting of 0 to 30 kPa, take
or AMP MODULE FAULT of Er. 02 which are shown in
8.5.2 “Errors and Countermeasures.”) the following action with an input
pressure of 10 kPa applied.
• Example: Set the output status to LOW when SET Press the key twice.
H11:AUTO HRV
a hardware error occurs. +
30 kPa
30 The higher range value is
SET
D53:ERROR OUT Use the or key changed to 10 kPa.
HIGH ESC
< HIGH> to select “LOW.”
< LOW>
< HOLD>
Press the key twice to
SET
H11:AUTO HRV
Press the (OK) key.
ESC 10.000 kPa
enter the setting.
F0827.ai
FEED NO OK
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-15
(a) Follow the procedure below when setting the (b)-2 Follow the procedure below to use J11:
present output to 0% (4 mA). ZERO DEV.
A10:OUTPUT (%)
Present output is 41.0%.
A10:OUTPUT (%) Output is 0.5%. 41.0 %
0.5 % Output error = 40.0–41.0 = –1.0%.
SET
SET
J11:ZERO DEV.
Since “J11: ZERO DEV.” contains
J10:ZERO ADJ Press the key twice. 2.50 %
0.0 % 0 the previous correction, obtain the
+ 000.0
correction value by adding –1.0%
ESC
CLR ESC to it. 2.50% + (–1.0%) = 1.50%
SET
J10:ZERO ADJ Zero adjustment is completed. SET
J11:ZERO DEV.
Set the correction value, 1.50.
0.0 % 2.50 %
Press the (OK) key. 1.50 Press the key twice.
FEED NO OK ECS
A10:OUTPUT (%) Output is 0%. A10:OUTPUT (%) The output is changed to 40%.
0.0 % 40.0 %
F0832.ai
F0830.ai
A10:OUTPUT (%) The output is changed to 40%. This is set to “ENABLE” when the instrument is
40.0 %
shipped.
F0831.ai
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-16
• Span adjustment value
• Example: Inhibiting zero adjustment by the
The span adjustment value is calculated as
external zero-adjustment screw
follows.
SET Use the or key P – A40 ×100
J20:EXIT ZERO ADJ Span adjustment value (%) = 1
ENABLE
< ENABLE > to select “INHIBIT.” P1
< INHIBIT>
Press the key twice to P1: Actual differential pressure/pressure value
ESC
enter the setting. A40: Input (indicated as the value after zeroing)
F0834.ai
Measurement pressure
• Zero point adjustment using external zero-
adjustment screw on the transmitter
A40
Turn the zero-adjustment screw on the outside of
the transmitter case using a slotted screwdriver.
Turn the screw to the right to increase the zero point Applied pressure
P1
or to the left to decrease the zero output; the zero 0
F0835.ai
adjusts in increments of 0.01% of the range setting.
Note that the amount of adjustment to the zero point • Example: For the range of 0 to 30 kPa.
changes according to the speed at which the screw A40: INPUT = 30.15 kPa
is turned. To make fine adjustments, turn the screw J15: SPAN ADJ = 0.15 %
slowly; to make coarse adjustments, turn the screw
Suppose that a standard pressure of 30 kPa is applied
quickly. and the value of the parameter of A40:INPUT is 30.15 kPa.
Note: When a zero point adjustment has been made, do not turn Firstly, obtain the slope error for the span as follows;
off the transmitter less than 30 seconds after adjustment.
P1 – A40
Span adjustment value (%) = ×100
(13) Span Adjustment P1
30.00 – 30.15
Each DPharp EJA series transmitter is factory = ×100 = −0.5 (%)
30.00
characterized according to the specification.
Mounting position effects or zero shifts caused by Add −0.5% to 0.15% of the current value to calculate the
static pressure are typically compensated by a zero accumulated span adjustment value.
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-17
(14) Test Output Setup 8.4 Displaying Data Using the
(K10: OUTPUT X%)
BT200
This feature can be used to output a fixed current
from 3.2 mA (−5%) to 21.6 mA (110%) for loop 8.4.1 Displaying Measured Data
checks.
The BT200 can be used to display measured data.
• Example: Output 12 mA (50%) fixed current. The measured data is updated automatically every
7 seconds. In addition, the display can be updated
SET
K10:OUTPUT X %
Set “50.0%.” to the present data value at any time by pressing
0.0 %
+ 050.0 Press the key twice to the [F1] (DATA) key. For parameters associated
output a fixed current at 50%. with the display of measured data, see Subsection
ESC
8.3.1, “Parameter Summary.”
SET “Active” is displayed while this is
K10:OUTPUT X %
50.0 % ACTIVE
being executed. • Example: Display output.
Press the (OK) key to cancel MENU
A:DISPLAY
FEED NO OK
the fixed current output. B:SENSOR TYPE
F0837.ai
HOME SET ADJ ESC
IMPORTANT PARAM
A10:OUTPUT (%)
Display “A10: OUTPUT (%).”
XX.X %
A11:ENGR.OUTPUT
1. Test output is held for approximately 10 YY.Y %
A20:AMP TEMP
minutes, and then released automatically ZZ deg C
DATA DIAG PRNT ESC
after the time has elapsed. Even if the Data is updated automatically
at 7-second intervals.
BT200 power supply is turned off or the PARAM
A10:OUTPUT (%)
communi
minutes.
2. Press the [F4] (OK) key to release test output
F0839.ai
immediately.
8.4.2 Display Transmitter Model and
(15) User Memo Fields Specifications
(M: MEMO) The BT200 can be used to display the model and
This feature provides 5 user memo fields, each specifications of the transmitter.
holding up to 8 alphanumeric characters. Up to 5
items such as inspection date, inspector, and other • Example: View transmitter model name.
information can be saved in these fields. MENU Press .
A:DISPLAY
B:SENSOR TYPE
• Example: Save an inspection date of January
30, 1995.
HOME SET ADJ ESC
PARAM
M10:MEMO 1
Set “95.1.30” in the order of year,
M20:MEMO 2 month, and day.
M30:MEMO 3 Press the key twice to
PARAM
DATA DIAG PRNT ESC
enter the setting. B10:MODEL For the associated
SET
EJA510A-DC parameters, see
B11:STYLE NO.
M10:MEMO 1
S1.01 Subsection 8.3.1,
95.1.30_ B20:LRL Parameter Summary.
- 98.07 kPa
DATA DIAG PRNT ESC
ESC
F0840.ai
F0838.ai
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-18
8.5 Self-Diagnostics • Example 3: Checking the history of the errors
8.5.1 Checking for Problems MENU
J:ADJUST
Connect the BT200 to the
K:TEST
M:MEMO
transmitter, and call item “P.”
(1) Identifying Problems with BT200 P:RECORD
The following four areas can be checked. HOME SET ADJ ESC
PARAM
(a) Whether connections are good. P10:ERROR REC 1
ERROR
(b) Whether BT200 was properly operated. P11:ERROR REC 2
ERROR
(c) Whether settings were properly entered. P12:ERROR REC 3
GOOD
DATA DIAG PRNT ESC
(d) History of the errors.
See examples below. P10: “ERROR REC 1” displays the last error.
P11: “ERROR REC 2” displays the error one time before
• Example 1: Connection errors the last error occurred.
P12: “ERROR REC 3” displays the error two times before
--WELCOME-- Press the key.
BRAIN TERMINAL
ID: BT200
the last error occurred.
When the panel shown on the left P13: “ERROR REC 4” displays the error three times
check connection
push ENTER key appears, press the key. before the last error occurred.
UTIL FEED
The history of up to four errors can be stored. When the
Since communications will be 5th error has occurred, it is stored in “P10”. The error
communication error unsuccessful if there is a problem stored in “P13” will be deleted, and then, the error in “P12”
in the connection to the BT200, will be copied to “P13”. In this sequence, the history of the
ESC the display at the left will appear. most previously occurred error will be removed from
memory.
Recheck the connection.
“GOOD” will be displayed if there was no previous error.
Press the (OK) key.
F0841.ai
SET Select P10: ERROR REC1 and
P10:ERROR REC 1
<
ERROR
ERROR >
press the key to
< ILLEGAL LRV > display the error message.
< ILLEGAL HRV >
ESC
• Example 2: Setting entry errors
<(a) SETUP PANEL>
PARAM The initial data panel shows the
01:MODEL
EJA510A-DC For the details of the messages listed below, see Table
02:TAG NO. result of current transmitter
YOKOGAWA 8.5.1 Error Message Summary.
03:SELF CHECK diagnostics.
ERROR
OK CAP MODULE FAULT OVER TEMP (CAP) ILLEGAL LRV
AMP MODULE FAULT OVER TEMP (AMP) ILLEGAL HRV
PARAM
C20:PRESS UNIT
Press the (DIAG) key in the
kPa OUT OF RANGE OVER OUTPUT ILLEGAL SPAN
C21:LOW RANGE parameter panel to go to the
600 kPa OUT OF SP RANGE OVER DISPLAY ZERO ADJ OVER
C22:HIGH RANGE
600 kPa
diagnostics panel
DATA DIAG PRNT ESC
(C60: SELF CHECK). Note 1: Press the key twice in the setting panel
DIAG An error message is displayed (panel 1) to clear all error message (P10 to P13)
C60:SELF CHECK
ERROR information.
< ERROR > when an error occurs in the
< ILLEGAL LRV > Note 2: After two hours from when an error occurs, the
diagnostics panel.
error message of that error will be recorded.
FEED PRNT ESC
Therefore, if you switch off the transmitter within
F0842.ai two hours from when the error occurs, there is no
history of that error stored in the transmitter, and
this function is meaningless.
F0843.ai
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-19
(2) Checking with Integral Indicator
NOTE
If an error is detected in the self-diagnostic,
an error number is displayed on the integral
indicator. If there is more than one error, the error
number changes at two-second intervals. See
Table 8.2 regarding the error numbers.
F0844.ai
IM 01C21F01-01E
<8. BRAIN TERMINAL BT200 Operation> 8-20
8.5.2 Errors and Countermeasures
The table below shows a summary of error messages.
Table 8.2 Error Message Summary
Integral
Output Operation during
Indicator BT200 Display Cause Countermeasure
Error
Display
None GOOD
--- ERROR
Er.01 CAP MODULE FAULT Capsule problem.*1 Outputs the signal (Hold, Replace the capsule when
High, or Low) set with error keeps appearing even
parameter D53. after restart.*2
Er.02 AMP MODULE FAULT Amplifier problem. Outputs the signal (Hold, Replace amplifier.
High, or Low) set with
parameter D53.
Er.03 OUT OF RANGE Input is outside Outputs high range limit Check input.
measurement range value or low range limit
limit of capsule. value.
Er.04 OUT OF SP RANGE Static pressure exceeds Displays present output. Check line pressure (static
specified range.*3 pressure).
Er.05 OVER TEMP (CAP) Capsule temperature is Displays present output. Use heat insulation or make
outside range lagging to keep temperature
(–50 to 130°C). within range.
Er.06 OVER TEMP (AMP) Amplifier temperature is Displays present output. Use heat insulation or make
outside range lagging to keep temperature
(–50 to 95°C). within range.
Er.07 OVER OUTPUT Output is outside high or Outputs high or low range Check input and range
low range limit value. limit value. setting, and change them as
needed.
Er.08 OVER DISPLAY Displayed value is Displays high or low range Check input and display
outside high or low limit value. conditions and modify them
range limit value. as needed.
Er.09 ILLEGAL LRV LRV is outside setting Holds output immediately Check LRV and modify as
range. before error occurrence. needed.
Er.10 ILLEGAL HRV HRV is outside setting Holds output immediately Check HRV and modify as
range. before error occurrence. needed.
Er.11 ILLEGAL SPAN SPAN is outside setting Holds output immediately Check SPAN and change as
range. before error occurrence. needed.
Er.12 ZERO ADJ OVER Zero adjustment is too Displays present output. Readjust zero point
large.
*1: This error code appears at a capsule problem or when an illegal overpressure is applied to the pressure sensor.
*2: If the normal pressure is regained, the Er.01 will disappear according to the setting of the parameter of E50: AUTO RECOVER.
When the E50: AUTO RECOVER is set to ON(defalut setting), the Er.01 will disappear automatically. When the E50: AUTO
RECOVER is set to OFF, restart the transmitter to cancel Er.01. If no error code appears then, perform necessary adjustment such
as zero-adjustment to continue the operation. If the error code still exists, replace the capsule assembly.
*3: For Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
IM 01C21F01-01E
<9. Maintenance> 9-1
9. Maintenance
9.1 Overview 9.2 Calibration Instruments
Selection
WARNING Table 9.1 shows the instruments required for
Since the accumulated process fluid may be calibration. Select instruments that will enable
toxic or otherwise harmful, take appropriate care the transmitter to be calibrated or adjusted to the
to avoid contact with the body, or inhalation of required accuracy. The calibration instruments
vapors even after dismounting the instrument should be handled carefully so as to maintain the
from the process line for maintenance. specified accuracy.
IM 01C21F01-01E
<9. Maintenance> 9-2
Table 9.1 Instruments Required for Calibration
Name Yokogawa-recommended Instrument Remarks
Power supply Model SDBT or SDBS distributor 4 to 20 mA DC signal
Load resistor Model 2792 standard resistor [250 Ω ±0.005%, 3 W]
Load adjustment resistor [100 Ω ±1%, 1 W]
Voltmeter Model 2501 A digital multimeter
Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)
Digital Model MT220 precision digital manometer Select a manometer having a
manometer 1) For 10 kPa class pressure range close to that of
Accuracy: ± (0.015% of rdg + 0.015% of F.S.) · · for 0 to 10 kPa the transmitter.
± (0.2% of rdg + 0.1% of F.S.) · · · · · · for −10 to 0 kPa
2) For 130 kPa class
Accuracy: ± 0.02% of rdg · · · · · · · · · · · · · · · · · · for 25 to 130 kPa
± 5 digits · · · · · · · · · · · · · · · · · · · · · · · for 0 to 25 kPa
± (0.2% of rdg + 0.1% of F.S.) · · · · · · for −80 to 0 kPa
3) For 700 kPa class
Accuracy: ± (0.02% of rdg + 3 digits) · · · · · · · · · for 100 to 700 kPa
± 5 digits · · · · · · · · · · · · · · · · · · · · · · · for 0 to 100 kPa
± (0.2% of rdg + 0.1% of F.S.) · · · · · · for −80 to 0 kPa
4) For 3000 kPa class
Accuracy: ± (0.02% of rdg + 10 digits) · · · · · · · · for 0 to 3000 kPa
± (0.2% of rdg + 0.1% of F.S.) · · · · · · for −80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ± (0.03% of rdg + 6 digits) · · · · · · · · · for 0 to 130 kPa abs
Pressure Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, Requires air pressure supply.
generator 25 kPa {2500 mmH2O}
Accuracy: ± 0.05% of F.S.
Dead weight gauge tester 25 kPa {2500 mmH2O} Select the one having a
Accuracy: ±0.03% of setting pressure range close to that of
the transmitter.
Pressure Model 6919 pressure regulator (pressure pump) Prepare the vacuum pump for
source Pressure range: 0 to 133 kPa {1000 mmHg} negative pressure ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
level, there are difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa representatives
from which the instrument was purchased or the nearest Yokogawa office.
IM 01C21F01-01E
<9. Maintenance> 9-3
9.4 Disassembly and 9.4.1 Replacing the Integral Indicator
Reassembly
CAUTION
CAUTION Cautions for Flameproof Type Transmitters
Users are prohibited by law from modifying the
Precautions for CENELEC and IECEx
construction of a flameproof type transmitter.
Flameproof Type Transmitters
This would invalidate the agency approval and
• Flameproof type transmitters must be, as
the transmitter’s use in such rated area.
a rule, removed to a non-hazardous area
Thus the user is prohibited from using a
for maintenance and be disassembled and
flameproof type transmitter with its integral
reassembled to the original state.
indicator removed, or from adding an integral
• On the flameproof type transmitters the two
indicator to a transmitter. If such modification is
covers are locked, each by an Allen head
absolutely required, contact Yokogawa.
bolt (shrouding bolt). When a shrouding bolt
is driven clockwise by an Allen wrench, it is
This subsection describes the procedure for
going in and cover lock is released, and then
replacing an integral indicator. (See Figure 9.4)
the cover can be opened by hand.
When a cover is closed it should be locked by a Removing the Integral Indicator
shrouding bolt without fail. Tighten the shrouding
1) Remove the cover.
bolt to a torque of 0.7 N·m.
2) Supporting the integral indicator by hand,
loosen its two mounting screws.
This section describes procedures for disassembly
3) Dismount the LCD board assembly from the
and reassembly for maintenance and component
CPU assembly.
replacement.
When doing this, carefully pull the LCD board
Always turn OFF power and shut off and release assembly straight forward so as not to damage
pressures before disassembly. Use proper tools for the connector pins between it and the CPU
all operations. Table 9.2 shows the tools required. assembly.
Table 9.2 Tools for Disassembly and Reassembly Attaching the Integral Indicator
Tool Quantity Remarks Integral indicator can be installed in the following
Phillips 1 JIS B4633, No. 2 three directions.
screwdriver
Slotted 1
screwdriver
Allen wrenches 2 JIS B4648
One each, nominal 3 and
5 mm Allen wrenches
Wrench 1 Width across flats, 17 mm
Torque wrench 1 F0903.ai
Adjustable 1 Figure 9.3 Installation Direction of Indicator
wrench
Socket wrench 1 Width across flats, 16 mm
1) Align both the LCD board assembly and CPU
Socket driver 1 Width across flats, 5.5 mm
assembly connectors and engage them.
Tweezers 1
2) Insert and tighten the two mounting screws.
3) Replace the cover.
Shrouding Bolt
Shrouding Bolt
F0902.ai
IM 01C21F01-01E
<9. Maintenance> 9-4
NOTE
Be careful not to apply excessive force to the
CPU assembly when removing it.
IM 01C21F01-01E
<9. Maintenance> 9-5
9.4.3 Cleaning and Replacing the Capsule 1) Remove the CPU assembly as shown in
Assembly Subsection 9.4.2.
2) Remove the two Allen screws and the pipe
This subsection describes the procedures for
(shown in Figure 9.5) for the model EJA530A
cleaning and replacing the capsule assembly. (See
with Measurement span code A, B, and C,
Figure 9.5.)
which connect the transmitter section and
capsule assembly.
CAUTION 3) Separate the transmitter section and capsule
assembly.
Cautions for Flameproof Type Transmitters 4) Clean the capsule assembly or replace with a
Users are prohibited by law from modifying the new one.
construction of a flameproof type transmitter. If
Reassembling the Capsule Assembly
you wish to replace the capsule assembly with
one of a different measurement range, contact 1) Insert the capsule assembly to the transmitter
Yokogawa. section. For the model EJA530A with
The user is permitted, however, to replace a Measurement span code A, B, and C with the
capsule assembly with another of the same pipe (shown in Figure 9.5), insert the capsule
measurement range. When doing so, be sure to assembly in a way that the direction of the
observe the following. pipe screw thread matches to that of the zero-
• The replacement capsule assembly must adjustment screw of the transmitter section.
have the same part number as the one being 2) Tighten the two Allen screws to a torque of 5
replaced. N·m and the pipe with gasket if applied.
• The section connecting the transmitter and 3) Install the CPU assembly according to
capsule assembly is a critical element in Subsection 9.4.2.
preservation of flameproof performance, and 4) After completing reassembly, adjust the zero
must be checked to verify that it is free of point and check the parameters.
dents, scratches, and other defects. Transmitter section
• After completing maintenance, be sure to
securely tighten the Allen screws that fasten
the transmitter section and pressure-detector
section together.
Allen screw
Zero-adjustment
Removing the Capsule Assembly screw
Allen screw
IMPORTANT
Gasket
Exercise care as follows when cleaning the
capsule assembly. Capsule name plate Pipe
• Handle the capsule assembly with care, and
be especially careful not to damage or distort
Pipe screw thread
the diaphragms that contact the process
Capsule assembly
fluid.
• Do not use a chlorinated or acidic solution for F0905.ai
IM 01C21F01-01E
<9. Maintenance> 9-6
9.5 Troubleshooting 9.5.2 Troubleshooting Flow Charts
If any abnormality appears in the measured values, Symptoms: • There is no output signal.
• Output signal does not change although
use the troubleshooting flow chart below to isolate process variable is known to be varying.
and remedy the problem. Since some problems • Output value is inconsistent with value
inferred for process variable.
have complex causes, these flow charts may not
identify all.
If you have difficulty isolating or correcting a Connect BRAIN TERMINAL and check self-diagnostics.
problem, contact Yokogawa service personnel.
YES
Is there any pressure leak?
NO Is there
Inspect receiver. continuity through the NO
transmitter loop wiring?
Do the loop numbers
match?
Environmental conditions Transmitter itself
Find/correct broken conductor or
YES
wiring error.
Check/correct
Check transmitter.
environmental conditions. Contact Yokogawa service personnel.
Operating conditions F0907.ai
Check/correct operating
conditions.
F0906.ai
IM 01C21F01-01E
<9. Maintenance> 9-7
Connect BRAIN TERMINAL and check self-diagnostics. Connect BRAIN TERMINAL and check self-diagnostics.
Is impulse piping NO
Are valves opened or NO
connected correctly?
closed correctly?
F0909.ai
IM 01C21F01-01E
<10. General Specifications> 10-1
IM 01C21F01-01E
<10. General Specifications> 10-2
Installation Where:
L = length in meters or feet
Supply & Load Requirements “◊”: R = resistance in Ω (including barrier
* Safety approvals can affect electrical resistance)
requirements. C = cable capacitance in pF/m or pF/ft
See Section 6.6, ‘Power Supply Voltage and Cf = maximum shunt capacitance of
Load Resistance.’ receiving devices in pF/m or pF/ft
Supply Voltage “◊”:
Physical Specifications
10.5 to 42 V DC for general use and flameproof
type Wetted Parts Materials:
10.5 to 32 V DC for lightning protector (Optional Diaphragm and Process connector;
code /A) See ‘Model and Suffix Codes’
10.5 to 30 V DC for intrinsically safe, Type n,
nonincendive, or non-sparking type Non-wetted Parts Materials:
Minimum voltage limited at 16.4 V DC for digital Housing;
communications, BRAIN and HART Low copper cast-aluminum alloy with
polyurethane paint (Munsell 0.6GY3.1/2.0)
EMC Conformity Standards: Degrees of Protection
EN 61326-1 Class A, Table 2 (For use in IP67, NEMA4X
industrial locations) Cover O-rings;
EN 61326-2-3 Buna-N, Fluoro-rubber (option)
EN 61326-2-5 (for Fieldbus) Data plate and tag;
Immunity influence during the test SUS304 or SUS316(optional)
Differential pressure/pressure: Output shift is Fill Fluid;
specified within ±1% of 1/10 Max span. Silicone or Fluorinated oil (optional)
Communication Requirements “◊”: Weight:
BRAIN 1.6 kg (3.5 lb) without integral indicator and
Communication Distance; mounting bracket.
Up to 2 km (1.25 miles) when using CEV Connections:
polyethylene-insulated PVC-sheathed See ‘Model and Suffix Codes.’
cables.
Communication distance varies depending < Settings When Shipped > “◊”
on type of cable used.
Tag Number As specified in order *1
Load Capacitance; Output Mode ‘Linear’
0.22 μF or less (see note) Display Mode ‘Linear’
Load Inductance; ‘Normal’ unless otherwise
Operation Mode
3.3 mH or less (see note) specified in order
Input Impedance of communicating device; Damping Time
‘2 sec.’
10 kΩ or more at 2.4 kHz. Constant
Note: For general-use and Flameproof type. For Calibration Range
As specified in order
Intrinsically safe type, please refer to ‘Optional Lower Range Value
Specifications.’ Calibration Range
As specified in order
Higher Range Value
HART
Selected from mmH2O, mmAq,
Communication Distance; mmWG, mmHg, Torr, Pa, hPa,
Up to 1.5 km (1 mile) when using multiple Calibration Range kPa, MPa, mbar, bar, gf/cm2,
twisted pair cables. Communication distance Units kgf/cm2, inH2O, inHg, ftH2O, psi
or atm.
varies depending on type of cable used.
(Only one unit can be specified)
Use the following formula to determine cable
*1: If Tag No. is no more than 16 alphanumeric characters
length for specific applications: (including - and ·), it will be written into the tag plate and
65 x 106 (Cf + 10,000) amplifier memory settings.
L= −
(R x C) C
IM 01C21F01-01E
<10. General Specifications> 10-3
10.2 Model and Suffix Codes
IM 01C21F01-01E
<10. General Specifications> 10-4
10.3 Optional Specifications
For FOUNDATION Fieldbus explosion protected type, see IM 01C22T02-01E.
For PROFIBUS PA explosion protected type, see IM 01C22T03-00E.
Item Description Code
FM Explosionproof Approval *1
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
FF1
Hazardous (classified) locations, indoors and outdoors (NEMA 4X)
Temperature class: T6
Amb. Temp.: –40 to 60°C (–40 to 140°F)
FM Intrinsically safe Approval *1
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1 Hazardous Locations.
Factory Mutual (FM)
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
Groups E, F & G, and Class III, Division 1 Hazardous Locations.
Enclosure: “NEMA 4X”, Temp. Class: T4, Amb. Temp.: –40 to 60°C (–40 to 140°F) FS1
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 µH
[Groups C, D, E, F and G]
Vmax=30 V, Imax=225 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 µH
Combined FF1 and FS1 *1 FU1
ATEX Flameproof Approval *2
Certificate: KEMA 02ATEX2148
II 2G Exd IIC T4, T5, T6 KF21
Amb. Temp.: T5; –40 to 80°C (–40 to 176°F), T4 and T6; –40 to 75°C (–40 to 167°F)
ATEX Max. process Temp.: T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F)
ATEX Intrinsically safe Approval *2
Certificate: KEMA 02ATEX1030X
KS2
II 1G EEx ia IIC T4, Amb. Temp.: –40 to 60°C (–40 to 140°F)
Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 µH
CSA Explosionproof Approval *1
Certificate: 1089598
Explosionproof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
Division2 ‘SEALS NOT REQUIRED’ , Temp. Class: T4, T5, T6 Encl Type 4x
Max. Process Temp.: T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F) CF1
Amb. Temp.: –40 to 80°C (–40 to 176°F)
Process Sealing Certification
Dual seal certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required. Primary seal failure annunciation : at the zero-
adjustment screw
Canadian Standards
CSA Intrinsically safe Approval *1
Association (CSA)
Certificate: 1053843
Intrinsically Safe for Class I, Groups A, B, C and D Class II and III, Groups E, F and G
Nonincendive for Class I, Division 2, Groups A, B, C and D Class II, Division 2,
Groups F and G and Class III (not use Safety Barrier)
Encl Type 4x, Temp. Class: T4, Amb. Temp.: –40 to 60°C (–40 to 140°F) CS1
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 µH
Process Sealing Certification
Dual seal certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required. Primary seal failure annunciation : at the zero-
adjustment screw
Combined CF1 and CS1 *1 CU1
IM 01C21F01-01E
<10. General Specifications> 10-5
Item Description Code
IECEx Intrinsically safe, type n and Flameproof Approval *3
Intrinsically safe and type n
Certificate: IECEx KEM 06.0007X
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP67
Amb. Temp.: –40 to 60°C (–40 to 140°F), Max. Process Temp.: 120°C (248°F)
Electrical Parameters:
[Ex ia] Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 µH
IECEx Scheme SU2
[Ex nL] Ui=30 V, Ci=22.5 nF, Li=730 µH
Flameproof
Certificate: IECEx KEM 06.0005
Ex d IIC T6...T4 Enclosure: IP67
Max.Process Temp.: T4;120°C (248°F), T5;100°C (212°F), T6; 85°C (185°F)
Amb.Temp.: –40 to 75°C (–40 to 167°F) for T4, –40 to 80°C (–40 to 176°F) for T5,
–40 to 75°C (–40 to 167°F) for T6
*1: Applicable for Electrical connection code 2 and 7 (1/2 NPT female).
*2: Applicable for Electrical connection code 2, 4, 7 and 9 (1/2 NPT and M20 female).
*3: Applicable for Electrical connection code 2, 4 and 7 (1/2 NPT and M20 female).
IM 01C21F01-01E
<10. General Specifications> 10-6
10.4 Dimensions
Model EJA510A and EJA530A [Style: S2]
Conduit connection 12 45
(0.47) (1.77) Ground terminal
Shrouding bolt *2
(3.07)
Ø78
127(5.0)
111(4.37)
170(6.69)
LOCK ZERO LOCK
Zero adjustment
Adapter
124(4.88)
Pipe(Open to atmosphere)*1
44(1.73)
(1.85)
47
176(6.92)
Ø6(0.23)
5(0.19)
F1001.ai
IM 01C21F01-01E
Customer Model EJA510A and EJA530A
Maintenance Absolute and Gauge
Parts List Pressure Transmitter
2 5
4
11
A 10
12
13 1
2 2
1
14
A
6
7-2
7-1 5
8 9
18
17
15 15
16
15
Process connection
code 7
21
19
22
24
20 23
1 Bellow 2 Cover
F9341RA Cast-aluminum alloy
F9341RJ SCS14A stainless steel
2 F9341JP 2 O-ring
3 Below 1 Case Assembly (Note 1)
F9341AR SCS14A stainless steel for 1/2 NPT (two electrical connections)
4 F9341KA 1 Name Plate
5 Bellow 4 Screw
F9900RG For cast-aluminum alloy case assembly
F9900RR For SCS14A stainless steel case assembly
F9342AM For HART protocol version with write protection switch (Optional code /F1)
7-2 F9342BF 1 For FOUNDATION Fieldbus protocol version
F9342BG For FOUNDATION Fieldbus protocol version with PID/LM function (Optional code /LC1)
8 F9900RP 2 Cap Screw
9 Y9612YU 2 Screw
10 Below 1 Plug
F9340NW For Pg13.5
F9340NX For M20
G9330DK For G1/2
G9612EB For 1/2 NPT
22 Below 1 Bracket
F9270AX SECC carbon steel
F9300TN SECC carbon steel (for epoxy resin-baked coating)
F9300TE SUS304 Stainless Steel
23 F9385XW 1 U-bolt/Nut Assembly (S), SUS304 Stainless Steel
(Note 1) Applicable for BRAIN and HART protocol versions (Output signal code D and E).
For FOUNDATION Fieldbus protocol version (Output signal code F), consult Yokogawa local office.
(Note 2) In case of Degrease cleansing treatment (Optional code /K1), consult Yokogawa local office.
IM 01C21F01-01E
Edition Date Page Revised Item
6th Apr. 2006 1-2 1.1 Add (e) Explosion Protected Type Instrument and (f) Modification
1-3 1.3 Add “1.3 ATEX Document”
2-6 2.9.3 Add “IECEx Certification” and delete “SAA Certification”
2-11 2.12 Add Low Voltage Directive
10-4, 10-5 10.3 Add Certificate numbers and Applicable standards
10-5 Add option code /SU2 and delete option code /SU1
10-6 Add option code /PR
7th Jan. 2008 1-1 Add direct current symbol.
1-4 Add 11 European languages for ATEX documentation.
2-3+ 2.9.1 Add applicable standard and certificate number for appovals.
2-10 2.10 Add EMC caution note.
4-2 4.4 Add section of changing the direction of integral indicator.
8-14 8.3.3(11) Add figure for A40.
9-4 9.4.1 Add figure of integral indicator direction.
10-1+ 10.1, 10.2 Add PROFIBUS PA communication type.
10-4,10-5 10.3 Delete applicable standard from the table.
CMPL CMPL 01C21F01-01E 4th → 5th
Delete logo from the tag plate.
8th Oct. 2008 2-9 2.9.4 Change explosion protection marking for type n from EEx to Ex.
2-10 2.10 Update EMC conformity standards.
8-4 and 8-5 8.3.1 Add new parameters.
8-6 8.3.2 Add items in table 8.3.1.
8-9 and later 8.3.3 Add (5)Change Output Limits and (13)Span Adjustment.
Re-number the items.
8-18 8.5.2 Modify descriptions and notes for Er.01.
9-1 9.3 Add a note for calibration.
9-5 9.4.3 Add a note for cleaning.
10-3 10.2 Add new suffix codes.
10-5, 10-6 10.3 Add sealing statement for CSA standards. Add /HC.
CMPL CMPL 01C21F01-01E 7th → 8th
Change Part No. of items 5 and 8.
9th July 2015 2-5, 2-6 2.9.2 Add temperature limitation for /HE.
2-9 to 2-10 2.9.4 b Change /KF2 to /KF21 and modify descriptions. Delete c.
Replace tag plate.
2-11 2.10 Add standards.
2-12 2.12 Add (3) and (4).
8-1 8.1.1 Add note. 8.1.2 Add descriptions.
10-2 10.1 Add information to “EMC Conformity Standards”.
10-4 to 10-5 10.3 Delete codes KU2 and KF2. Add KF21. Add Codes HE and CA.
IM 01C21F01-01E