AFC-1000 Manual
AFC-1000 Manual
AFC-1000 Manual
120VAC 50Hz~60Hz
240VAC 50Hz~60Hz
Connect to separate
unswitched AC circuit
120|240
+
I/O 4
-
120/240 VAC
+
Jumper Position
I/O 3
- +
I/O 2
-
E.O.L.
+
I/O 1
-
NAC 1 NAC 2 NAC 4 NAC 5 NAC 6 PLINK 1 PLINK 2 SLC
TO PLINK DEVICES
Battery connection (non-power limited).
Use two(2) 12V batteries connected in series.
DWG #641-1
2
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
The AC terminals are located in the upper left hand portion of the main board. The main board supervises the main
AC power and provides indication that the AC power is absent.
120VAC 50/60 Hz
240VAC 50/60 Hz
Connect to separate
Unswitched AC circuit
Black
White
Ground
B W G
DWG #593-6
AC POWER
AC120V/ AC230V,50/ 60Hz
Figure 2. Main Supply Circuit
The terminals are rated at 120 VAC/240 VAC 50/60 Hertz and are marked so accordingly on the board. The earth
ground connection is marked as “G” and is the furthest connection from the line voltage connection.
The battery charging circuit is provided on the main panel in the lower left portion of the board. Terminal
connections are provided to connect wire leads for battery connection. The battery must be a recognized or listed
sealed lead acid battery or equivalent.
The battery charging voltage is approximately 27.3 VDC and the circuit is supervised. The battery circuit is protected
with a non-replaceable 7 amp poly switch located on the main circuit board. The maximum battery charging circuit is
1.0 amp DC.
The battery circuit is rated for 8 to 55 AH batteries and the cabinet will house up to two 18 AH batteries. The
batteries will operate the panel for at least 24 hours and 5 minutes of alarm. In order to determine the minimum size
batteries for standby and alarm times desired, the installer must complete a battery calculation work sheet in order to
determine the minimum battery size for a particular application. For reference, the battery calculation work sheet is
attached as Appendix A. Complete standby battery calculations must be completed to ensure adequate battery sizes
are provided.
3
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
Panel
- + Connections
BATTERY
- + - +
12 V 12 V
Battery Battery
DWG #593-5
The main AC power connection is considered high-voltage and non-power limited. The phone line connections to the
DACT are high-voltage – power limited. Battery conductors, and the alarm, supervisory, and trouble relays are non-
power limited. All remaining circuits are low-voltage, power limited connections.
Proper separation must be maintained between the circuits listed above. All separations in the different wiring must
be maintained by at least 0.25 inches and the wire insulation must be for the higher voltage.
In the panel there are sufficient knock outs located around the periphery of the cabinet to allow the installer to
maintain power limited and non-power limited connections. The main AC power connection should be made on
the left side or top left of the cabinet. The DACT wiring connections should be made along the top right side of the
cabinet.
The panels are equipped with six NAC circuits and each are rated for a continuous 3 amps at 24 VDC. The outputs
are supervised and regulated. The NACs reverse polarity upon activation and the board and illustrations are marked
accordingly.
The panels can be programmable to allow for addition of a CA-6500 Class-A Expander. This expander allows for
Class A operation of the NACs. Each Class A circuit is rated for a continuous 3 amps at 24 VDC. The outputs are
supervised and regulated.
NAC circuits are power limited and the type of output is selectable. The NACs may be configured for strobe
synchronization with AMSECO, Wheelock, Gentex, or System Sensor strobe devices as shown compatible in this
document and the installation instructions.
The maximum impedance is a function of the load being applied to the circuit. In order to calculate the maximum
impedance as follows:
(Alarm Current of Notification Appliances) X (Wire Resistance) < 3 volts.
4
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
The panel has ground fault detection on the NAC circuits. The impedance to ground for ground fault detection is
0 ohms.
Notification
Appliance
5.1k EOL
Potter Part #3005013
DWG #602-4
Notification
Appliance
DWG #602-5
The end of line resistor is a 5.1K ohm resistor. The resistor assembly has been evaluated in past projects and is a
standard in the Potter panel product line. The Potter part number for the listed end of line assembly is 3005013 EOL
Resistor Assembly.
5
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
I/O Circuits
The panels are equipped with four I/O circuits. The I/O circuits can be configured as either an input or an output. The
I/O circuits can be used in Class B mode only.
The circuit is power limited and the type of output is selectable. I/O circuits may be configured for strobe
synchronization with AMSECO, Wheelock, Gentex, or System Sensor strobe devices as shown compatible in this
document and the installation instructions.
The maximum impedance is a function of the load being applied to the circuit. In order to calculate the maximum
impedance as follows
The panels have ground fault detection on the I/O circuits. The impedance to ground for ground fault detection is 0
ohms.
Normally Open
Notification Dry Contact
Appliance
The end of line resistor is a 5.1K ohm resistor. The resistor assembly has been evaluated in past projects and is a
standard in the Potter panel product line. The Potter part number for the listed end of line assembly is 3005013 EOL
Resistor Assembly.
6
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
The panels are equipped with one built-in SLC loop supporting a maximum of 127 devices. Up to 9 additional SLC
loops are supported by adding the PAD100-SLCE or the SLCE-127 loop expander modules. The PAD100-SLCE
supports the PAD protocol and the SLCE-127 supports the Nohmi protocol.
The addressable points may be any combination of smoke sensors, heat detectors, input modules or output modules.
The SLC provides power and communication to each of the sensors and modules connected. The SLC is fully
supervised in that the communication signal is sent and must be received from each device. The entire loop is polled
approximately every 4 seconds.
The voltage range for the SLC is 22-24 VDC. The power is a constant regulated connection with a maximum line
resistance of 50 ohms. The SLC has a maximum loop capacitance of 0.5 micro-farads. The maximum SLCE-127 fully
loaded loop current is 56.055 mA. The maximum PAD100-SLCE fully loaded loop current is 90.61 mA.
The panels have ground fault detection on the SLC circuits and addressable devices. The impedance to ground for
ground fault detection is 0 ohms.
If the Nohmi protocol SCI short circuit isolators are installed, a total of 8 devices must be deducted from the total
number of devices for each isolator installed.
Addresses for all PAD protocol devices are assigned via a dipswitch on the device.
Addresses for the Nohmi protocol devices are assigned by using the hand-held programmer (part # FZAW004-
-P/3610053).
For the PAD protocol, Class X requires a PAD100-IB to be installed for each sensor and/or PAD100-IM to be installed
on each side of each module. The maximum wiring resistance between a PAD100-IB/PAD100-IM and another
PAD100-IB/PAD100-IM shall be less than 10 ohms and the total resistance must be below 50 ohms. The maximum
wiring resistance shall be calculated based on 0.1 ohm per PAD100-IB/PAD100-IM.
For the Nohmi protocol, Class X requires one AIB to be installed for each sensor and/or SCI to be installed on each
side of each module. The maximum wiring resistance between an AIB/SCI shall be less than 10 ohms and the total
resistance must be below 50 ohms. The maximum wiring resistance shall be calculated based on 0.1 ohm per AIB/
SCI.
Note: Class X requires a close nipple or conduit connection to every module or sensor for both PAD and Nohmi
protocols.
7
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
SLC Loop
Isolation Module
SLC Loop
Isolation Module
SLC Loop
Isolation Module
-
+
-
+
AFC Series SLC Loop
SLC Loop Isolation Module
Class X
Wiring Diagram
DWG #641-2
8
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
-
+
-
+
AFC Series
SLC Loop
Class A
Wiring Diagram
DWG #641-3
-
+
AFC Series
SLC Loop
Class B
Wiring Diagram
DWG #641-4
9
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
Address No.
S-2 S+2 S-1 S+1 Address No. S- S+ Address No.
S-2 S+2 S-1 S+1
Potter Electric Signal Company Potter Electric Signal Company Potter Electric Signal Company
SIGNALING
SIGNALING
SIGNALING
LISTED
LISTED
LISTED
UL
UL
UL
Short Circuit Isolater Dual Contact Module Short Circuit Isolater
Model No. SCI Model No. DCM-4 Model No. SCI
Ser. No. xxxxxx Ser. No. xxxxxx Ser. No. xxxxxx
XXXX
XXXX
Document: TN51313e date:XX.XX.2009 Document: TN51316e date:XX.XX.2009 Document: TN51313e date:XX.XX.2009
NO2 NO1
Z2 (NC2) C2 Z1 (NC1) C1
Address No.
S-2 S+2 S-1 S+1 Address No.
24- 24+ S- S+ Address No.
S-2 S+2 S-1 S+1
Potter Electric Signal Company Potter Electric Signal Company Potter Electric Signal Company
SIGNALING
SIGNALING
SIGNALING
LISTED
LISTED
LISTED
UL
UL
UL
Short Circuit Isolater Conventional Initiating Zone Module Short Circuit Isolater
Model No. SCI Model No. CIZM-4 Model No. SCI
Ser. No. xxxxxx Ser. No. xxxxxx Ser. No. xxxxxx
FIRE ALARM EQUIPMENT
XXXX
XXXX
Document: TN51313e date:XX.XX.2009
Document: TN51313e date:XX.XX.2009 Compatibility Identifier: INTE01 Document: TN51313e date:XX.XX.2009
WARNING :
Power supply for terminals 24+ and 24- must
WARNING : be power limited WARNING :
All Terminals are power limited. All Terminals are power limited. All Terminals are power limited.
B- B+ A- A+
DWG #610-3
SCI 5.1kΩ
SCI
LISTED
LISTED
LISTED
SIGNALING
UL
UL
LISTED
XXXX
FIRE ALARM EQUIPMENT
XXXX
FIRE ALARM EQUIPMENT
XXXX
FIRE ALARM EQUIPMENT
5.1kΩ
7 24- 24+ S- S+
Address No.
NO
S- S+ C
LISTED
UL
5.1kΩ
DWG #610-2
10
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
Terminal Connections
7 24- 24+ S- S+
Address No.
SIGNALING
NO
S- S+ C
LISTED
UL
Conventional Initiating Zone Module
Model No. CIZM-4 (NC)
Ser. No. xxxxxx
Potter Electric Signal Company
5.1kΩ
DWG #610-1
All expansion devices are supervised via the RS-485 connection. Wiring is fully supervised and power limited. Any
connection to ground of 0 ohms will be annunciated as a ground fault.
The worst case P-Link current draw cannot exceed the 1 amp. P-Link wiring gauges and lengths are calculated using
the worst-case current draw values from the table below. The worst case current draw numbers are used only for
wiring calculations, refer to the battery calculation worksheet for normal standby and alarm currents.
11
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
B
A
+
Panel
Connection Expansion
-
P-LINK 1 P-LINK 2 Device
- + A B - + A B
B
A
+
DWG #602-11
Expansion
-
Device
Panel
Connection
B
P-LINK 1 P-LINK 2
A
- + A B - + A B
+
CA-6500
Connection Expansion
-
P-LINK 1 P-LINK 2
Device
- + A B - + A B
B
A
+
DWG #602-12
Expansion
-
Device
12
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
PAD100-SLCE/SLCE-127
The panels can be programmed to support up to 9 PAD100-SLCE (PAD protocol) and/or SLCE-127 (Nohmi
protocol) loop expanders. The expansion card provides an additional SLC loop, supporting up to 127 addressable
points. The expansion cards support both Class B and Class A wiring.
UD-1000/UD-2000
The panels can be programmed to support the UD-1000/UD-2000 digital alarm communicator transmitter (DACT).
The DACT may be enabled, disabled or bypassed depending on the mode of operation. When the DACT is
disabled, the panels are not capable of transmitting any alarms off premises through the DACT.
The DACT provides for up to two phone lines for communication to a monitoring station. The DACT
communicates using the SIA-DCS or Ademco Contact ID protocols. When enabled, the DACT automatically
monitors each phone line or voltage and has the ability to seize the line and connect with a remote receiver. Once
the communication is complete, the DACT will hang up the phone line.
The UD-1000 is provided with an RJ-11 jack for each phone line. The UD-2000 is provided with terminal
blocks for each phone line connection. In order for the DACT to work properly, it must be installed on a plain
old telephone service (POTS) or equivalent as deemed by the authority having jurisdiction. The DACT must be
installed before any other equipment to ensure it can seize the line and disconnect any other lines.
Phone lines are high voltage and should be run in a separate conduit from other circuits. The wire conductors
connecting the DACT to the phone system should be 26 AWG or larger.
13
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
MC-1000 (Multi-Connect)
The panels support up to 31 MC-1000 modules. The MC-1000 allows multiple AFC series panels to report to the
central station through a shared phone line or Internet connection.
14
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
Note:
EOL Device shall be installed in the same
electrical enclosure as the releasing device.
DWG #602-6
Releasing
Device
The maximum current is 3 amps. The maximum line impedance is calculated using the following formula.
Rmax (ohm) = (24V-Vmin-0.95V)/I total
Vmin is the lowest voltage operation of the connected devices.
I total is the total current of the connected devices.
When a NAC is used as a releasing circuit, the End of Line Diode (EOLD) assembly must be installed. The EOLD
is Potter part number 3005012 and must be installed in accordance with the installation manual.
According to UL 10th Edition, the disabling of a releasing circuit shall be accomplished by a physical switch
activated without the use of the software. When a releasing circuit is disabled a supervisory signal will be
annunciated at the FACP.
15
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
Notes:
IO circuits and/or NAC Circuits can be used as Municipal box connection .
The EOL device shall be installed in the same electrical enclosure as the Municipal Box
. DWG #602-9
Figure 16. Municipal Box Wiring Example
Trip current = NAC1-NAC6 = 3 Amps, I/O1-I/O4 = 1 Amp
Max Voltage = 24 VDC
The panel has ground fault detection on municipal box connection circuits. The impedance to ground for ground fault
detection is 0 ohms.
+
Keltron
TTM-RPS
-
Only the I/O circuits on the panel can be programmed as reverse polarity circuits. The short circuit current is rated
at 24 VDC and 14 mA maximum.
When configured for reverse polarity, the panel will indicate alarm and trouble events to a remote site. Alarms will
override trouble conditions.
The panels have ground fault detection on reverse polarity circuits. The impedance to ground for ground fault
detection is 0 ohms.
The connection between the FACP and the remote device shall be limited to 20 feet and enclosed in conduit or
equivalently protected against mechanical injury.
16
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
Relay Outputs
DWG #593-26
Figure 18. Panel's Dedicated Relay Outputs
The panels have three dedicated common relays. The dedicated trouble relay is a failsafe trouble relay that
changes position anytime a trouble condition occurs.
The contact rating is 24VDC / 3.0A, 125VAC / 3A, Power Factor: 1.0. These outputs are non-power limited and
not supervised. However, they are power-limited if the power supply to the connected devices is power-limited.
The enclosure requires the use of power limited and non-power limited wiring on the main board as well as within
the enclosure. Power limited wiring is to remain separated from non-power limited by a minimum or 0.25 inches
and all cabling should be insulated to the higher voltage.
When the panel is installed, the National Electrical Code (NEC, NFPA 70) should be followed for the proper
installation and separation of power limited and non-power limited circuits. The mixing of power limited and
non-power limited should be avoided. Refer to the following figure for suggested wiring routing.
17
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
HIGH VOLTAGE
WIRING HIGH VOLTAGE
WIRING
POWER
LIMITED
WIRING
POWER
LIMITED
WIRING
NON-POWER
LIMITED WIRING
POWER
LIMITED
WIRING
18
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
2. Operation
System Type: Auxiliary
Central Station (Protected Premises Unit)
Proprietary (Protected Premises Unit)
Remote Station (Protected Premises Unit)
Local
System Service: Automatic Fire Alarm
Manual Fire Alarm
Sprinkler Supervisory
Waterflow Alarm
Releasing Service for Pre-Action, Deluge
System Signal: Radio Frequency
Digital Alarm Communicator (DAC)
March Time
Non-Coded
Reverse Polarity
Other Technologies
3. Functionality
The panel utilizes a signaling line circuit for communication to various sensors and modules. The system polls each
loop between every 4 to 5 seconds. The system is completely supervised and is designed to comply with UL 864. The
control panel uses a proprietary protocol to digitally communication with various sensors and modules to determine
the status of each. When the panel response from the sensor or module is within a pre-determined range or status, the
control will process the commands accordingly.
The control panel user interface requires the use of a key to open the outer door. Advanced features will require an
additional user code to be entered using a combination of numbers.
The panel is completely programmable through the use of a computer program. Remote programming is detailed
later in this section.
The control panel includes three relay contacts for additional monitoring or building functions.
The first relay is a failsafe, dedicated Trouble Relay. This relay changes state during any trouble condition. This
relay is not programmable and no additional mapping to this relay can take place.
The second relay is a dedicated Supervisory Relay. This relay changes state during any supervisory condition. This
relay is not programmable and no additional mapping to this relay can take place.
The third relay is a dedicated Alarm Relay. This relay changes state during any alarm condition. This relay is not
programmable and no additional mapping to this relay can take place.
The AFC-1000 has six NACs and four I/O circuits. Each NAC is rated for 3 amps at 24 VDC. Each I/O circuit is
configurable as a NAC rated for 1 amp at 24 VDC, or as a dry contact input. The NACs may be operated in Class A
with the addition of a CA-6500 Class A Expander.
NACs may be programmed to provide steady (constant) voltage, a cadence pattern, releasing service or synchronized
strobes. Full synchronization is maintained system-wide. The NACs may be programmed as silenceable or non-
silenceable. Anytime a NAC has been silenced, the condition will be indicated by the silenced LED. If a NAC that
is programmed as silenceable is silenced and another alarm event mapped to that NAC occurs, the NAC will resound
and the silenced LED will extinguish.
19
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
The Low AC report delay period is programmable from 30 minutes up to 30 hours. For UL installations and
applications the installer must set the time delay between 30 minutes and 90 minutes.
Supervisory Signal Operation – Zones programmed as supervisory zones can be programmed as latching or non-
latching.
Trouble Signal Operation – Any fault or off normal that would impair the system is annunciated as a trouble
condition. The trouble condition is specifically displayed on the LCD display so the trouble can be corrected. When
a trouble occurs the buzzer sounds every ten seconds for one second, the trouble LED illuminates and the trouble
relay changes state.
The panel transfers from AC to battery instantly upon AC failure or brownout. The trouble relay will indicate the low
AC condition after the Low AC Report Delay has elapsed.
The control panel can utilize an optional digital alarm communicator transmitter, (UD-1000/UD-2000). The UD-
1000/UD-2000 is a two line dialer with the capability to report in the Ademco Contact ID or the Security Industry
Association’s Digital Communications Standard (SIA-DCS).
When equipped with a UD-1000, the status changes of the panel are remotely communicated to a monitoring station.
Programming options allow for selecting separate accounts for alarm/trouble/supervisory/test events. When a UD-
1000/UD-2000 is not installed, the panel will operate as a local system.
The DACT will provide a daily test to a remote monitoring point daily. The daily test time is programmable. If
two phone lines are utilized, the DACT will alternate between lines on each daily call. If multiple accounts are
programmed, then multiple daily tests will be conducted alternating on each line.
The panels may be equipped with 31 PSN-1000 series intelligent power expanders. The PSN-1000/PSN-1000(E) is
a 10 amp notification power supply and P-Link (RS-485) repeater. The power supply connects to the P-Link bus from
the control panel and is operated and supervised from the panel.
The power supply has six (6) Class B or three (3) Class A power outputs. Each output is regulated and power limited
with a 3 Amp maximum rating. In addition, the PSN-1000s have two (2) programmable dry contact inputs. The dry
contact inputs are Class B, supervised inputs.
The power supply operates on either 120 or 220 VAC power and has a regulated 24 VDC output. In addition, the
panel can charge up to 55 AH batteries and will house 18 AH batteries.
The power supplies are programmed and controlled through the main control panel P-Link bus. The panel displays
any troubles or off normal conditions of the power supply and the events are stored in the panel history buffer.
20
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
120VAC 50Hz-60Hz
240VAC 50Hz-60Hz
Connect to separate
unswitched AC circuit
Non-power limited
relay connection
P-Link
Terminals
Non-power limited
battery connection
Power limited
wiring
DWG #608-23
Figure 20. PSN-1000 Wiring Example
The panels may be equipped with 9 additional PAD100-SLCE (PAD Protocol) and/or Nohmi Protocol SLCE-127
boards that utilize a signaling line circuit for communication to various sensors and modules. The system polls each
loop between every 4–5 seconds. The PAD100-SLCE and the SLCE-127 supports a maximum of 127 addressable
devices configured in any combination of smoke sensors, heat detectors, input modules or output modules.
The PAD100-SLCE and the SLCE-127 outputs are supervised and regulated. Circuits are low voltage and power
limited. All wiring must be separated by at least 0.25 inches and the wire insulation must be for the higher voltage.
Refer to Figure 19 for suggested wire routing.
The PAD100-SLCE and the SLCE-127 are supplied with a mounting bracket which allows it to be mounted into a
compatible fire enclosure. Please refer to the figures shown below:
Figure 21. PAD100-SLCE / Nohmi Protocol SLCE-127 Board & Shown Installed in AFC-1000 Cabinet
DETAIL G
SCALE 1 : 2
21
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
When the panels are equipped with a LED-16/LED-16(F) module, alarm/supervisory/trouble conditions display for up
to 16 zones. Blank zone labels are provided for use with the LED-16s. Zone names/identifiers can be typed or written
on the supplied card-stock, and then inserted into the LED-16/LED-16F as shown below.
Labels are inserted
here as needed
Zone labels
may be
inserted here
DWG #608-4
DWG #608-5
Figure 22. LED-16/LED-16(F) Module & Board
The LED-16s are controlled over the 4-wire P-Link connection. The higher current required for the LED outputs can
be provided by the panel, or from an auxiliary power source as shown below. The auxiliary power can be any fire
listed 24VDC source, and is fully supervised.
Example: Example:
Powered by Powered by
control panel aux supply
Figure 23. Examples of Wiring a LED-16/LED-16(F) Module to Control Panel or Auxiliary Power Supply
The panels may equipped with a DRV-50 (LED Driver) module, which can be individually mapped to any zone. The
DRV-50 is controlled over the 4-wire P-Link connection. The DRV-50 mounts in a mounting bracket as shown below.
This can then be mounted into any of the compatible fire enclosures, or the AE-2, AE-8 or AE-14 accessory cabinets.
DWG #608-7
22
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
The 50 programmable LED outputs are located on connectors P1-P5, each containing 10 LED outputs and two 5VDC
outputs. The system LEDs & PZT control outputs are located on connector P6. LEDs are wired as shown below,
no external resistor is required. All outputs are power limited. All connections to P1-P6 are limited to same room
installation.
LED1
TRB
SUP
ALR
SIL
EARTH
LED10 PWR
LED+ PZT-
LED+ LED+
The 4 programmable dry-contact inputs are located on connector P7. All input circuits are power limited and use UL
listed 5.1k EOL resistor (Potter part #3005013). The inputs can be programmed for any of the contact input functions
available for other input circuits available on the panel. Inputs I1-I4 are Class B dry contact inputs only. All contact
inputs are fully supervised. Ground fault detection impedance is 0 ohms.
P7
Maximum wiring resistance = 100 ohms
I4
5.1k
5.1k
5.1k
DWG #608-9
The higher current required for the DRV-50 outputs can be provided by the panel, or from an auxiliary power source
as shown below. The auxiliary power can be any fire listed 24VDC source, and is fully supervised. Output power
must be 16 VDC-33 VDC, and must be power limited.
Example: Example:
Powered by Powered by
control panel aux supply
Figure 27. Examples of Wiring DRV-50 from Control Panel or Auxiliary Power Supply
23
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
The panels may be equipped with a RLY-5 (Relay Board) module, which is controlled over the 4-wire P-Link
connection. The RLY-5 mounts in a mounting bracket as shown below. The RLY-5 can be mounted inside the panel
cabinet, or the AE-2, AE-8 or AE-14 accessory cabinets.
DWG #608-10
The RLY-5 higher current required for the relay outputs can be provided by the panel, or from an auxiliary power
source as shown below. The auxiliary power can be any fire listed 24VDC source, and is fully supervised. Output
power must be 16VDC-33VDC, and must be power limited.
• Relay contacts are rated for 120VAC/24VDC, 3 Amp (resistive).
• All connections to relay contacts shall be power limited.
• Not to be used for off-premise signaling.
Example: Example:
Powered by Powered by
control panel aux supply NC (Normally Closed)
C (Common)
NO (Normally Open)
Figure 29. RLY-5 Wiring to Control Panel / Auxiliary Power Supply & RLY-5 Normally Open / Normally Closed Contacts
When the FCB-1000 (Fire Communications Bridge) is added to the panel, a remotely-located IP connection is
provided into the panel. The FCB-1000 can be mounted inside the AE-2, AE-8 or AE-14 accessory enclosure. The
optional rack-mount kit (FCB-1000RM) includes a standard 19 inch rack-mount enclosure, which can then be
installed directly in an equipment rack.
Note: The Ethernet/IP connection is limited to same room installation. This connection shall be limited to 20 feet,
and enclosed in conduit or equivalently protected against mechanical injury.
24
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
When the panels are equipped with the FIB-1000 (Fiber Interface Bridge) optional board, the standard 4 wire P-Link
bus may be converted to/from the fiber optic cable.
The FIB-1000 can be mounted inside the AE-2, AE-8 or AE-14 accessory enclosure. The optional rack-mount
kit (FIB-1000RM) includes a standard 19 inch rack-mount enclosure, which can then be installed directly in an
equipment rack.
• Utilizes multimode 62.5/125 micron fiber optic cable (wave length = 820 nm)
• Tolerates up to 12 db of signal loss
An optional SPG-1000 serial/parallel gateway (printer driver) board can be mounted inside the AE-2, AE-8 or AE-14
accessory enclosure. A rack-mount kit (SPG-1000RM) includes a standard 19 inch rack-mount enclosure, which can
then be installed directly in an equipment rack.
Note: Serial/Parallel printer connection is limited to same room installation. This connection shall be limited to 20
feet, and enclosed in conduit or equivalently protected against mechanical injury.
25
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
When the AFC series panels are equipped with the MC-1000 (Multi-Connect Module) optional board, up to 63 panels
may be interconnected to report to the central station through a shared phone line or Internet connection.
DWG #641-6
DWG #641-8
Figure 33. MC-1000 Multi-Connect Board & MC-1000 Shown Installed in AFC-1000 Cabinet
The panel supports up to thirty one (31) IDC-6 modules. The IDC-6 is controlled over the 4 wire P-Link connection.
. It can be mounted in the large panel enclosure, the PSN-1000, or either of the AE-2, AE-8 or AE-14 accessory
cabinets..
+ - + - A B
IDC PWR P LINK
Dip Switch S1
Figure 34. IDC-6 Initiating Device Circuit Expander and IDC-6 Installation
The IDC-6 higher current required for the inputs can be provided by the panel, or from an auxiliary power source
as shown below. The auxiliary power can be any fire listed 24VDC source, and is fully supervised. IDC-6 operating
voltage range is 15VDC-28VDC, and must be power limited.
26
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
The control panel has an interface display for allowing users, technicians and installers the ability to recognize the
status and input changes to the control panel. The display consists of three parts — the 160 character LCD display, the
keypad and LEDs.
The keypad on the control panel is utilized for common user functions and system programming. The common user
function buttons the following:
27
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
28
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
4. Programming Options
The control panel is configured using a PC based programming tool. The panel stores the site specific configuration
data in non-volatile memory.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to
specific values or not used at all as indicated below.
29
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
30
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
31
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
32
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
IP-Reporting IP Based Central Y Alarm, Supervisory, Trouble & All Settings Allowed
Station Reporting Test Reports
5. Testing/Maintenance
The control panel has one fuse on the board for the AC power over current protection.
The AC fuse is rated at 8A 250VAC Time-Lag and screened onto the main board as F1.
The batteries are to be replaced at least once every four years. The batteries are required to be UL recognized
batteries with a date of manufacture permanently marked on the battery. The battery is to be tested at least annually
and if the battery is showing signs of failure, it is to be replaced.
The battery is to remain in the cabinet with nothing on or around the batteries. Only properly sized sealed lead acid
batteries are to be used with the control panel. Use of another battery or not providing the proper clearance may result
in a fire or an explosions.
The control panel is required to be installed in accordance with local and state building codes and NFPA 72 (National
Fire Alarm Code).
The control panel and related system is required to be inspected and tested in accordance with NFPA 72.
33
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
6. Compatibilities
NAC Appliances
Please refer to Potter document 5403592 NAC Compatibility Document.
SLC Devices
Nohmi Protocol PAD Protocol
PSA – Photoelectric Smoke Detector PAD100-PD – Photo Detector
PSHA – Photoelectric/Heat Smoke Detector PAD100-HD – Fixed Heat Detector
FHA – Fixed Temperature Heat Detector PAD100-CD – CO Detector
RHA – Rate of Rise/fixed Temperature Heat Detector PAD100-PHD – Combination Photo/Heat Detector
DSA – Photo Duct Detector PAD100-DUCT – Duct Detector
APS-SA/DA – Addressable Pull Station PAD100-DUCTR – Duct Detector w/Relay
(Single Action / Dual Action)
AIB – Addressable Isolator Base PAD100-DD – Duct Detector Sensor
ASB – Addressable Sounder Base PAD100-DRTS – Duct Detector Remote Test Switch
ARB – Addressable Relay Base MS-RA – DUCT Remote LED Indicator
MCM – Miniature Contact Module MS-KA/P/R – DUCT LED w/Test Switch
SCM-4 – Single Contact Module PAD100-MIM – Mini Input Module
DCM-4 – Dual Contact Module PAD100-SM – Speaker Module
TRM-4 – Twin Relay Module PAD100-PSSA – Pull Station Module Single Action
MOM-4 – Monitored Output Module PAD100-PSDA – Pull Station Module Dual Action
CIZM-4 – Conventional Input Zone Module PAD100-SB – Addressable Sounder Base
SCI – Short Circuit Isolator PAD100-RB – Addressable Relay Base
PAD100-IB – Addressable Isolator Base
PAD100-IM – Isolator Module
PAD100-RM – Relay Module
PAD100-NAC – Notification Appliance Circuit
PAD100-TRTI – Twin Relay-Twin Input
PAD100-DIM – Double Input Module
PAD100-OROI – One Relay-One Input
PAD100-ZM – Zone Module
PAD100-LED – Remote LED
PAD100-LEDK – Remote LED w/Key
PAD100-SIM – Single Input Module
PAD100-LFSB - Low Frequency Sounder Base
PAD100-SPKB - Speaker Base
34
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
DACT/DACR Compatibility
UD-1000/UD-2000 DACT
The DACT transmits in Ademco Contact ID and Security Industries Association’s Digital Communication Standards
(SIA-DCS). Each account may be configured for Contact ID or SIA-DCS independent of the other accounts setting.
Therefore some account(s) could be Contact ID and others could be SIA-DCS or vice versa. Similarly, accounts
could be the same reporting type.
Compatible Receivers
Silent Knight Model 9500/9800 (Ademco MX8000)
Sur-Gard System III
SG-DRL3 (POTS Line Card)
IP Reporting Compatibility
Sur-Gard System III
SG-DRL3-IPCA (Network Line Card)
Notes:
Where the fire alarm transmitter is sharing on-premises communications equipment, the shared equipment
shall be Listed.
Secondary power shall be provided for all equipment necessary for the transmission and reception of alarm,
supervisory and trouble signals at the protected premises.
Secondary power shall be provided for all equipment necessary for the transmission and reception of alarm,
supervisory and trouble signals at the supervising station.
The connection between the FACP and on-premises communications equipment shall be limited to 20 feet and
enclosed in conduit or equivalently protected against mechanical injury.
RS-485 Devices
PAD100-SLCE Provides an additional PAD protocol SLC loop with a maximum of 127 addressable
points.
SLCE-127 Provides an additional Nohmi protocol SLC loop with a maximum of 127 addressable
points.
RA-6500R / RA-6500F 4x40 character LCD Remote Annunciator
RA-6075R 2x16 character LCD Remote Annunciator
PSN-1000/E 10 Amp Power Expander
LED-16 / LED-16F Device that displays alarm/supervisory/trouble conditions for up to 16 zones and five
(5) non-programmable system LEDs that annunciate system's overall conditions (Power,
Earth, Silenced, Alarm, Supervisory, & Troubles).
DRV-50 Device that provides 50 LED outputs can be individually mapped to any zone, four
(4) programmable supervised dry contact inputs, and five (5) non-programmable
system LEDs annunciate the overall system condition (Power, Earth, Silenced, Alarm,
Supervisory, & Troubles).
RLY-5 Device that provides five (5) Form-C relay outputs which can be individually mapped to
any zone.
FCB-1000 Device that provides remote IP connection.
FIB-1000 Device that converts the 4 wire P-Link bus to/from fiber optic cable.
MC-1000 Allows up to 63 AFC series panels to report to the central station through a shared phone
line or Internet connection.
IDC-6 Device that provides six (6) additional conventional Class B inputs or three (3) Class A
inputs that can be individually mapped to any zone.
35
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
Class A Expander
CA-6500 Class A Expander
Printers
Keltron 90 Series Fire Alarm printer or other UL Listed fire alarm printer (Ancillary).
7. System Configurations
AFC-1000 (4,064 Point System)
Model Description Local Releasing Auxiliary Remote Central Proprietary
Service Station Station
AFC-1000 Main Board/Panel Assembly Y Y Y Y Y Y
CA-6500 Class A Expander O O O O O O
UD-1000/UD- DACT N N N Y Y Y
2000
PAD100-SLCE PAD Protocol SLC Loop Expander O O O O O O
SLCE-127 Nohmi Protocol SLC Loop Expander O O O O O O
RA-6075R LCD type remote Annunciator O O O O O O
RA-6500R, LCD type remote Annunciator O O O O O O
RA-6500F
PSN-1000 Fire Power Expander O O O O O O
LED-16/LED-16F LED Annunciator O O O O O O
DRV-50 LED Driver O O O O O O
RLY-5 Relay Expander O O O O O O
FCB-1000 Fire Communications Bridge O O O O O O
FIB-1000 Fiber Interface Bridge O O O O O O
SPG-1000 Serial/Parallel Gateway O O O O O O
MC-1000 Multi-Connect Module O O O O O O
IDC-6 Initiating Device Circuit O O O O O O
3005013 End of line resistor Y Y Y Y Y Y
3005012 End of line resistor and diode N Y Y N N N
Y = Yes, required for applicable section.
N = No, not required for applicable section.
O = Optional, may or may not be used, has no affect on the applicable section.
36
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
8. System Power/Size
Rating
Panel # NACs SLC Power Notes Class
per NAC
AFC-1000 6 up to 10 if 3 Amp Maximum One built-in SLC SLC – Class A or B
all I/O circuits Load of Loop, up to 9 NAC – Class A or B
configured as 90.61 mA additional using P-Link – Class A or B
NACs PAD100-SLCE I/O – Class B only
and/or SLCE-127
Loop Expanders All are low voltage
and power limited
System Size
Accessories/subassemblies Maximum System Size
AFC-1000 1,270 maximum points any combination of detectors or
modules if 9 PAD100-SLCE and/or SLCE-127 SLC Loop
Expanders are added
6 notification circuits on the main board
4 I/O circuits
UD-1000/UD-2000 1 DACT
37
Fire Panel Operating Instructions
Normal Standby The green AC POWER LED will be illuminated and the user defined message on the LCD will be displayed. If
the AC power is removed for more than 5 seconds, the green AC power LED will extinguish.
Acknowledging Off normal events are acknowledged by pressing the ACK key while reviewing events. After all events have been
acknowledged, the buzzer will deactivate and the associated LED will stop flashing and remain on continuously.
During Positive Alarm Sequence operation the “ACK” key must be pressed within 15 seconds of the alarm
initiation to activate the investigation timer.
Alarm Condition The red ALARM LED will be illuminated anytime an alarm is occurring in the system. The LCD will display the
number of inputs in alarm, and the buzzer will be activated. The buzzer will remain active until all alarms have
been acknowledged, or until the Silence key is pressed.
Silencing Alarm When the system is in Alarm, the notification circuits (strobes and horns) can be shut off by pushing the SILENCE
button.
Resetting Alarm After the condition that caused the alarm has been identified and corrected, the system may be reset to the Normal
Standby by pressing the RESET button.
Supervisory Condition When a supervisory condition is detected, the amber SUPERVISORY LED will illuminate and the buzzer will
sound. The LCD display will indicate the number of supervisory events that are active. The local buzzer will
sound until all supervisory events have been acknowledged.
Restoring Supervisory If the Supervisory condition is non-latching, once the device is restored to the normal condition, the supervisory
Condition event will clear. If the supervisory condition is latching, the device that was activated must be restored and the
RESET pressed.
Trouble Condition When a fault condition occurs, the amber TROUBLE LED will illuminate and the local buzzer will sound
until the fault is removed or the ACK button is pressed acknowledging the trouble condition. If the buzzer is
acknowledged and the fault is not removed within 24 hours, the buzzer will resound.
Silencing Trouble(s) When a trouble is occurring, the local buzzer will sound until either all troubles have been acknowledged or the
SILENCE button is pressed.
Ground Fault When a conductor contacts and earth ground, the amber EARTH FAULT LED will illuminate and the LCD
display will provide further information of where the fault is located.
Pre-Release The amber Pre-Release LED will illuminate when the system is in a count down timer for an agent release.
(Releasing Panels Only) Additionally, pre-release events and countdown timers are displayed on the LCD.
Release The red Release LED will illuminate when a release condition is active. Additionally, release events will be
(Releasing Panels Only) displayed on the LCD.
Agent Release Abort If the system is being used as an agent releasing panel and a pre-discharge timer is programmed, the release
(Releasing Panels Only) may be aborted by pressing the abort switch. For ULI installations, pushing the Abort will allow the timer to
countdown until 10 seconds and then halt. Releasing and reactivating the Abort will set the timer to 10 seconds.
Testing and Test this system monthly or more frequently as required by the AHJ. Before conducting any testing contact
Maintenance the building personnel and the monitoring facility as applicable. When testing a system configured for
releasing, activate the releasing disconnect switch to prevent accidental discharge of a suppression system.
Test the circuits as outlined in the Installation Manual. Test in accordance with NFPA 72 Inspection, Testing
and Maintenance Chapter(s) and any local requirements. The batteries should be marked with the date of
installation and replaced every four years or sooner if battery trouble occurs. Batteries should be checked with
a tester acceptable to the AHJ such as a Stone Technologies model STC612A or equivalent. In case of a fuse
replacement, refer to the Installation Manual for the proper rating. Contact the agency below for service or
operational questions.
Name:
Company:
Frame and display instructions adjacent to the fire alarm panel. Address:
5409071–Rev B Telephone:
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
39
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
Total Total
Standby Alarm
Description Quantity Standby Alarm
(mA) (mA)
(mA) (mA)
Convert to Amps x 0.001 Convert to Amps x 0.001
(*Refer to maximum allowable standby current) Total A: Total A:
60 minutes per hour
Alarm time (minutes)
Multiply by standby hours x____ Example: ÷ ____
5 minute alarm: enter 12
10 minute alarm: enter 6
Total Standby AH Total Alarm AH
+Total Standby AH
Total AH
Efficiency Factor ÷ 0.80
Required AH
40
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
* Note 1: PAD100-ZM requires 24VDC power source. Standby Current = 15.0 mA. Alarm Current = 60.0 mA.
* Note 2: PAD100-NAC requires 24VDC power source. Standby Current = 3.0 mA. Alarm Current = 8.0 mA.
* Note 3: PAD100-SB requires 24VDC power source. Standby Current = 4.0 mA. Alarm Current = 30.0 mA.
* Note 4: PAD100-DUCTR requires 24VDC power source. Standby Current = 30.0 mA. Alarm Current = 60.0 mA.
* Note 5: When connecting the MS-RA/MS-KA/P/R power source, Standby Current = 45.0 mA. Alarm Current = 90 mA.
* Note 6: PAD100-LFSB requires 24VDC power source. Standby current = 4.1 mA. Alarm Current = 156.6 mA.
41
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
* Note 1: PAD100-ZM requires 24VDC power source. Standby Current = 15.0 mA. Alarm Current = 60.0 mA.
* Note 2: PAD100-NAC requires 24VDC power source. Standby Current = 3.0 mA. Alarm Current = 8.0 mA.
* Note 3: PAD100-SB requires 24VDC power source. Standby Current = 4.0 mA. Alarm Current = 30.0 mA.
* Note 4: PAD100-DUCTR requires 24VDC power source. Standby Current = 30.0 mA. Alarm Current = 60.0 mA.
* Note 5: When connecting the MS-RA/MS-KA/P/R power source, Standby Current = 45.0 mA. Alarm Current = 90.0 mA.
* Note 6: PAD100-LFSB requires 24VDC power source. Standby current = 4.1 mA. Alarm Current = 156.6 mA.
42
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
* Note 1: CIZM requires 24VDC power source. Standby Current Class A = 4.90 mA, Class B (8.5 mA). Alarm Current = 50.0 mA
* Note 2: MOM requires 24VDC power source. Standby Current = 1.60 mA. Alarm Current = 1.60 mA
* Note 3: ASB requires 24VDC power source. Standby Current = 5 mA. Alarm Current = 100 mA
* Note 4: ARB requires 24VDC power source. Standby Current = 5 mA. Alarm Current = 50 mA
43
AFC-1000 INSTALLATION MANUAL-5403649-REV B 10/17
Circuit board assembly is mounted in the cabinet using four (4) fasteners as shown in the illustration below.
DWG #641-7
44