Marelli Motori Digital Avr: Functions and Key Features Inputs

The D-Vo is a digital voltage regulator developed by Marelli Motori that manages the electrical parameters of synchronous generators. It has various operating modes and protections. It can interface with a PC using Modbus communication protocols. The D-Vo is a standard feature for generators above 800 frames or high voltage generators, and is compatible with any Marelli Motori generator.

Uploaded by

Ashraf Irfan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
131 views2 pages

Marelli Motori Digital Avr: Functions and Key Features Inputs

The D-Vo is a digital voltage regulator developed by Marelli Motori that manages the electrical parameters of synchronous generators. It has various operating modes and protections. It can interface with a PC using Modbus communication protocols. The D-Vo is a standard feature for generators above 800 frames or high voltage generators, and is compatible with any Marelli Motori generator.

Uploaded by

Ashraf Irfan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

D-Vo

MARELLI MOTORI DIGITAL AVR

The new Digital Voltage Regulator D-Vo is an electronic


microprocessor-based device which manages the
operating electrical parameters of synchronous
generators. The power supply to the exciter is through a
PWM power stage.
The D-Vo AVR can be interfaced and programmed using the
standard Modbus communication protocol and a proprietary
PC application supplied by Marelli Motori.
The new D-Vo regulator is a standard feature of all
generators ≥800 frame size and all HV (std) generators,
it is also compatible with any Marelli Motori generator.

FUNCTIONS AND KEY FEATURES INPUTS


 4 Operating modes:  1-ph or 3-ph generator voltage sensing
 Automatic Voltage Regulation (AVR mode)  1-ph or 3-ph generator current sensing
 Power Factor Regulation (PF mode)
 1-ph grid voltage sensing
 Reactive Power Regulation (VAR mode)
 Field Current Regulation (FCR mode)  3 auxiliary analogue inputs for remote setpoint control
 Input for external potentiometer
 Stability parameters individually configurable (P.I.D.)
 9 digital contacts (8 programmable)
or pre-defined standard parameterization

 Soft start with adjustable ramp, in AVR mode

 Parallel function with similar generators operated with OUTPUTS


Reactive Droop Compensation
 PWM output max. 10A continuous, 20A forcing for 10s
 Generator protections:  3 configurable output relays for alarm and FRT
 Field over-voltage
 Field over-current
 Generator over-voltage
 Generator under-voltage FRT
 Generator over-current
 Loss of sensing The D-Vo is equipped with a Fault Ride Through (FRT)
 Diode monitoring function that allows to detect the Low Voltage Ride Through
(LVRT) or the High Voltage Ride Through (HVRT) and
 Excitation limiters (over- and under-excitation)
provides a dynamic support of reactive current
 Watchdog during the event.
FRT Management options available:
 Under-frequency limiter  Standard
 AVR mode
 FRT detection and management

 Certifications:
 CE
 UL
 Grid code: compliant with VDE-AR-N-4110

COMBROAVR002_= 02/2019
PRODUCT SPECIFICATION

POWER SUPPLY GENERATOR CURRENT SENSING


TECHNOLOGY Digital INPUTS 3 (6 terminals) for U-V-W phase sensing
Single phase
CONNECTION TYPE CURRENT RANGE
1Aac (50/60Hz)
Three phase OF EACH INPUT
Shunt
Auxiliary winding
POWER SOURCE PMG
REGULATION ACCURACY
Separate AC source
AVR MODE ±0.25% of rated voltage
Separate DC source
FCR MODE ±2% of rated exciter current
AC: up to 250Vac (50Hz to 400Hz)
±0.005PF
VOLTAGE RANGE DC: up to 300Vdc PF MODE
(with PF between 0.9 lagging and 0.9 leading)
Voltage build-up: 5Vac VAR MODE ±2% of rated power
VOLTAGE MATCHING ±2% of rated voltage
CONTROL SUPPLY
Single phase
CONNECTION TYPE
Three phase
ENVIRONMENTAL CONDITIONS
Shunt
OPERATING TEMPERATURE -30°C to +70°C
Auxiliary winding
STORAGE TEMPERATURE -40°C to +80°C
POWER SOURCE PMG
HUMIDITY <90%
Separate AC source
DIMENSIONS 335 x 190 x 60 (mm)
Separate DC source
AC: 24Vac to 250Vac (50Hz to 400Hz)
VOLTAGE RANGE
DC: 24Vdc to 300Vdc
EMC
IMMUNITY IEC 61000-6-2
GENERATOR VOLTAGE SENSING
EMISSIONS IEC 61000-6-4
Single phase
CONNECTION TYPE Burst: IEC 61000-4-4
Three phase
Surge: IEC 61000-4-4
VOLTAGE RANGE AC: 100Vac to 480Vac ±15%, at 50/60Hz
ESD: IEC 61000-4-2
Conducted immunities LF: IEC 60945
GRID VOLTAGE SENSING TESTED ACCORDING TO Conducted immunities HF: IEC 61000-4-6
THE FOLLOWING
CONNECTION TYPE Single phase STANDARDS Radiated immunities HF: IEC 61000-4-3
VOLTAGE RANGE AC: 100Vac to 480Vac ±15%, at 50/60Hz Radiated emissions: CISPR 16, CISPR 11
Single-phase Conducted emissions: CISPR 16, CISPR 11
VOLTAGE SENSING
220Vac to 480Vac at 50Hz/60Hz Power interruptions: IEC 61000-4-11
OF THE GRID
Frequency operating range 10Hz to 80Hz Voltage variation: IEC 61000-4-11

USER INTERFACE CONTACTS


 1 USB port for connection to PC with Marelli Motori Marelli Motori S.p.A. Marelli Motori Asia Sdn Bhd
proprietary software or custom software Via Sabbionara 1 Lot 1-8, Persiaran Jubli Perak,
36071 Arzignano (VI) - Italy Seksyen 22, 40300 Shah Alam,
 1 Ethernet port for connection to PC with Marelli Motori (T) +39 0444 479 711 Selangor D.E. - Malaysia
proprietary software or custom software (F) +39 0444 479 888 (T) +60 355 171 999
[email protected] (F) +60 355 171 883
 Communication protocol: Modbus RTU (USB), Modbus
[email protected]
TCP/IP (Ethernet)

marellimotori.com

You might also like