Omicron PTL: Omicron PTL ABB RET670 V1.2 Transformer PTT User Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

OMICRON PTL ABB RET670 V1.

2 Transformer PTT User Manual

OMICRON PTL

ABB RET670 V1.2 Transformer PTT

User Manual

V1.000

© OMICRON electronics GmbH 1/7


OMICRON PTL ABB RET670 V1.2 Transformer PTT User Manual

Content
1. General ...................................................................................................................................................3
2. Software and Hardware Requirements ...............................................................................................3
3. Hardware ................................................................................................................................................4
4. Functional Range...................................................................................................................................5
5. XRIO Converter ......................................................................................................................................7
5.1 Specialties of the Additional Information block .....................................................................................7
6. Specific Protection Tests ......................................................................................................................7
6.1 Overload Protection ..............................................................................................................................7
6.1.1.1 Thermal Overload Trip Time Test ...........................................................................................7

© OMICRON electronics GmbH 2/7


OMICRON PTL ABB RET670 V1.2 Transformer PTT User Manual

1. General
This user manual describes details of testing ABB RET670 V1.2 relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.

The template has been tested with the following relay:


Manufacturer: ABB
Model: RET670

2. Software and Hardware Requirements


To use this template, you must have a valid test license for the OMICRON Test Universe 2.40 software or
higher versions and the following test modules:
• Control Center
• Ramping
• Overcurrent
• State Sequencer
• Diff Configuration
• Diff Operating Characteristic
• Diff Trip Time Characteristic

Any CMC test set except the CMC353 can be used with this Protection Test Template.

© OMICRON electronics GmbH 3/7


OMICRON PTL ABB RET670 V1.2 Transformer PTT User Manual

3. Hardware
There are multiple possibilities of wiring a RET670 relay to a CMC test set. The advised connections are
shown in Figure 1 and Figure 2. These connections are the default settings in the
Hardware Configuration of the PTT.

Figure 1: Connection for RET670 Winding 1 – Winding 2

Figure 2: Connection for RET670 Winding 1 – Winding 3

© OMICRON electronics GmbH 4/7


OMICRON PTL ABB RET670 V1.2 Transformer PTT User Manual

4. Functional Range
Supported functions:
• Transformer differential protection T3WPDIF, T2WPDIF (87T)
• Instantaneous phase overcurrent protection PHPIOC (50)
• Four step phase non-directional overcurrent protection OC4PTOC (50/51)
• Instantaneous residual overcurrent protection EFPIOC (50N)
• Four step residual non-directional overcurrent protection EF4PTOC (50N/51N)
• Thermal overload protection, two time constant TRPTTR (49)

Not supported functions:


• 1Ph high impedance differential protection HZPDIF (87)
• Restricted earth fault protection, low impedance REFPDIF (87N)
• Negative sequence differential current protection
• Impedance protection (21)
• Power swing (78)
• Four step residual directional overcurrent protection EF4PTOC (67N)
• Four step phase directional overcurrent protection OC4PTOC (67)
• Four step directional negative phase sequence overcurrent protection NS4PTOC (46I2)
• Sensitive directional residual overcurrent and power protection SDEPSDE (67N)
• Breaker failure protection CCRBRF (50BF)
• Pole discordance protection CCRPLD (52PD)
• Directional underpower protection GUPPDUP (37)
• Directional overpower protection GOPPDOP (32)
• Broken conductor check BRCPTOC (46)
• Two step undervoltage protection UV2PTUV (27)
• Two step overvoltage protection OV2PTOV (59)
• Two step residual overvoltage protection ROV2PTOV (59N)
• Overexcitation protection OEXPVPH (24)
• Voltage differential protection VDCPTOV (60)
• Loss of voltage check LOVPTUV (27)
• Underfrequency protection SAPTUF (81)
• Overfrequency protection SAPTOP (81)
• Rate-of-change frequency protection SAPFRC (81)
• Synchrocheck, energizing check and synchronizing SERSYN (25)

Although the functions listed above are not supported by the Protection Test Template, the
Relay Parameter Section of the XRIO Converter includes all protection parameters of the relay.

Not supported Parameters/Configuration:


• Transformer differential protection:
o TconfigForW1,
o CT1RatingW1,
o CT2RatingW1,
o TconfigForW2,
o CT1RatingW2,
o CT2RatingW2,
o TconfigForW3,
o CT1RatingW3,
o CT2RatingW3,
o LocationOLTC1,
o LowTapPosOLTC1,
o RatedTapOLTC1,
o HighTapPsOLTC1,
o TapHighVoltTC1,
o StepSizeOLTC1,
o LocationOLTC2,

© OMICRON electronics GmbH 5/7


OMICRON PTL ABB RET670 V1.2 Transformer PTT User Manual

o LowTapPosOLTC2,
o RatedTapOLTC2,
o HighTapPsOLTC2,
o TapHighVoltTC2,
o StepSizeOLTC2,
o NegSeqDiffEn,
o IMinNegSeq,
o NegSeqROA,
o OpenCTEnable,
o tOCTAlarmDelay,
o tOCTResetDelay and
o tOCTUnrstDelay
• Instantaneous phase overcurrent protection PHPIOC:
o StVaMult
• Instantaneous residual overcurrent protection EFPIOC:
o StVaMult
• Four step phase overcurrent protection OC4PTOC:
o 2ndHarmStab,
o I1Mult,
o HarmRestrain1,
o I2Mult,
o HarmRestrain2,
o I3Mult,
o HarmRestrain3,
o I4Mult and
o HarmRestrain4
• For step residual overcurrent protection EF4PTOC:
o 2ndHarmStab,
o BlkParTransf,
o SOTF,
o ActivationSOTF,
o StepForSOTF,
o HarmResSOTF,
o tSOTF,
o t4U,
o ActUnderTime,
o tUnderTime,
o IN1Mult,
o HarmRestrain1,
o IN2Mult,
o HarmRestrain2,
o IN3Mult,
o HarmRestrain3,
o IN4Mult and
o HarmRestrain4
• Thermal overload protection:
o ILowTau1,
o Tau1Low,
o ILowTau2,
o Tau2Low,
o Alarm1,
o Alarm2,
o ResLo,
o Warning and
o tPulse

© OMICRON electronics GmbH 6/7


OMICRON PTL ABB RET670 V1.2 Transformer PTT User Manual

5. XRIO Converter
The Test Object already contains the ABB RET670 XRIO Converter, which includes setting parameters
of the modelled protection relay. The setting parameters are built as an image of the PCM600 software.

The Standard Filter for XRIO Files can be used for importing settings into the Relay Parameter
Section.

5.1 Specialties of the Additional Information block

Hardware Configuration
The Hardware Configuration contains information on usage of analog modules which can be set in the
IED Configuration of the PCM600 software

Relay Configuration (ACT/CAP531)


The Relay Configuration (ACT/CAP531) contains configuration details which can be found in the
ACT/CAP531 tool of the PCM600 like usage of thermal overload configuration.

Power System Parameters


The Power System Parameters stores data important for correct definition of the protected power
transformer and circuit breaker information for CB trip time tests.

6. Specific Protection Tests

6.1 Overload Protection


6.1.1.1 Thermal Overload Trip Time Test
The Overcurrent test module is used for trip time tests of the Thermal Overload function for winding 1 and
winding 2. One test relative to the minimum trip value of this function is preset in this test, but it can be
adjusted if necessary.

© OMICRON electronics GmbH 7/7

You might also like