MCB 3P 6ka C-25A 3M: Architecture

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Product data sheet

MCN325

MCB 3P 6kA C-25A 3M

MCN325

Architecture

Number of protected poles 3


Number of poles 3P
Type of pole 3P
Concurrently switching N-neutral no
Curve C

Connectivity

Top connection alignement for modular devices Aligned terminal

Main electrical features

Frequency 50/60 Hz
Rated short circuit breaking capacity Icn AC according 6 kA
IEC60898-1
Type of supply voltage AC
Rated operational voltage Ue 230/400 V

Voltage

Rated insulation voltage 500 V


Rated impulse withstand voltage 4000 V

Electric current

Rated ultimate short-circuit breaking capacity Icu 10 kA


under 400V AC IEC 60947-2
Rated short circuit breaking capacity Icn under 400V 6 kA
AC according IEC60898-1
Rated service breaking capacity Ics AC according IEC 6 kA
60898-1
Breaking capacity on 1 pole with 400 V NF 60947-2 3 kA
Rated ultimate short-circuit breaking capacity Icu 10 kA
under 415V AC IEC 60947-2
Magnetic regulating currrent at 40° C 5/10 In
min/maxi threshold value of the DC magnetic 7/15 In
operation
min/maxi threshold value of the AC thermal operation 1,13/1,45 In
min/maxi threshold value of the DC thermal operation 1,13/1,45 In

1 Technical subject to change


Product data sheet
MCN325

Electric current / temperature

Rating current -15°C 30,5 A


Rating current -20°C 31 A
Rating current 0°C 28,8 A
Rating current 10°C 27,6 A
Rating current -10°C 29,9 A
Rating current 15°C 26,9 A
Rating current 20°C 26,3 A
Rating current 25°C 25,7 A
Rating current -25°C 31,5 A
Rating current 30°C 25 A
Rating current 35°C 24,3 A
Rating current 40°C 23,5 A
Rating current 45°C 22,7 A
Rating current 5°C 28,2 A
Rating current -5°C 29,3 A
Rating current 50°C 21,9 A
Rating current 55°C 21,1 A
Rating current 60°C 20,2 A
Rating current 65°C 19,3 A
Rating current 70°C 18,3 A

Current correction factors

Correction factor of magnetic tripping with 100 Hz 1,1


Correction factor of magnetic tripping with 200 Hz 1,2
Correction factor of magnetic tripping with 400 Hz 1,5
Correction factor of magnetic tripping with 60 Hz 1
Correction factor of rating current for 2 devices placed 1
side-by-side
Correction factor of rating current for 3 devices placed 0,95
side-by-side
Correction factor of rating current for 4 and 5 devices 0,9
placed side-by-side
Correction factor of rating current for 6 devices placed 0,85
side-by-side

Power

Power loss per pole at In 3,5 W


Total power loss under IN 10,1 W

Endurance

Electric endurance in number of cycles 4000


Number of mechanical operations 20000

Dimensions

Depth of installed product 70 mm


Height of installed product 83 mm
Width of installed product 52,5 mm

Installation, mounting

Tightening torque 2,8Nm

2 Technical subject to change


Product data sheet
MCN325

Connection

Connection cross-sect. rigid cable 1 / 35mm²


Connection cross-sect. flexible conductor 1 / 25mm²
Type of connection with screw
Connection cross section of access and exit with 1/25 mm²
screws, for flexible conductor
Connection cross-section of input and output with 1/35 mm²
screws, for massive conductors

Equipment

Can be accessorized yes

Standards

Standard text EN 60898-1


European directive RoHs voluntary compliance
European directive WEEE concerned

Safety

Protection index IP IP20

Use conditions

Degree of pollution according to IEC 60664 / IEC 2


60947-2
Class of energy limitation I²t 3
Altitude 2000 m
Storage temperature -25 to 80 °C
Air humidity protection for all climates

3 Technical subject to change