Derating Factor Standard PDF
Derating Factor Standard PDF
Derating Factor Standard PDF
Note: This table applies where the associated overcurrent protective device is intended to provide short circuit protection only. Except
where the device is a semi-enclosed fuse to BS3036 the table also applies where the device is intended to provide overload
protection.
0
Operating Ambient Temperature C
Type of insulation
temperature 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
Rubber
0
(flexible cables 60 C 1.04 1.0 0.91 0.82 0.71 0.58 0.41
only)
General purpose 0
70 C 1.03 1.0 0.94 0.87 0.79 0.71 0.61 0.5 0.35
PVC
0
Paper 80 C 1.02 1.0 0.95 0.89 0.84 0.77 0.71 0.63 0.55 0.45 0.32
0
Rubber 85 C 1.02 1.0 0.95 0.9 0.85 0.8 0.74 0.67 0.6 0.52 0.43 0.3
0
Hear resisting 85 C 1.03 1.0 0.97 0.94 0.91 0.87 0.84 0.79 0.71 0.61 0.5 0.35 0.35
o o
PVC*85 C/90 C 90 C
o
0.8 0.76 0.71 0.61 0.5
Thermosetting 0
90 C 1.02 1.0 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.5 0.41 0.29
(XLPE)
0
70 C
1.03 1.0 0.93 0.85 0.77 0.67 0.57 0.45 0.31
sheath
Mineral: 0
105 C
1.02 1.0 0.96 0.92 0.88 0.84 0.8 0.75 0.7 0.65 0.6 0.54 0.47 0.4 0.32
Sheath
Table 2: Correction factors for ambient temperature where the overload protective device is a semi-
enclosed fuse to BS3036
0
Type of Operating Ambient Temperature C
insulation temperature 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
Rubber
0
(flexible cables 60 C 1.04 1 0.96 0.91 0.87 0.79 0.56
only)
General 0
70 C 1.03 1 0.97 0.94 0.91 0.87 0.84 0.69 0.48
purpose PVC
0
Paper 80 C 1.02 1 0.97 0.95 0.92 0.90 0.87 0.84 0.76 0.62 0.43
0
Rubber 85 C 1.02 1 0.97 0.95 0.93 0.91 0.88 0.86 0.83 0.71 0.58 0.41
0
Heat resisting 85 C 1.03 1 0.97 0.94 0.91 0.87 0.84 0.80 0.76 0.72 0.68 0.49 0.49
o o
PVC*85 C/90 C 0
90 C 0.63
Thermosetting 0
90 C 1.02 1 0.98 0.95 0.93 0.91 0.89 0.87 0.85 0.79 0.69 0.56 0.39
(XLPE)
Mineral:Bare
0
and exposed to 70 C
1.03 1 0.96 0.93 0.89 0.86 0.79 0.62 0.42
touch or PVC sheath
covered
Bare and not 0
105 C
exposed to 1.02 1 0.98 0.96 0.93 0.91 0.89 0.86 0.84 0.82 0.79 0.77 0.64 0.55 0.43
sheath
touch
o o
Note :Correction factors for flexible cords and for 85 C or 150 C rubber insulated flexible cables are given in the relevant table of
current carrying capacity in BS 7671.
*These factors are applicable only to ratings in columns 2 to 5 Table 1 of Appendix 2.
Table (3): Correction factors for groups of more than one circuit of single-core cables, or more than
one multicore cable
Correction Factor
Reference Method of Installation (See Appendix7) Number of Circuits or Multicore Cables
2 3 4 5 6 7 8 9 10 12 14 16 18 20
Enclosed (Method 3 or 4) or bunched and clipped
0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38
direct to a non-metallic surface (Method 1)
Single layer Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70
clipped to a non-
metallic Spaced* 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
surface.(Method 1)
Single layer Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 0.71 0.7
multicore on a
perforated metal
cable tray, vertical
or Spaced*# 0.91 0.89 0.88 0.87 0.87
horizontal(Method
11)
Single layer single- Horizontal 0.90 0.85
core on a
perforated metal
cable tray,
Vertical 0.85
touching(Method
11)
Single layer multicore touching on ladder supports
0.86 0.82 0.8 0.79 0.78 0.78 0.78 0.77
(Method 13)
For a cable installed in a thermally insulated wall or above a thermally insulated ceiling, the cable being in
contact with a thermally conductive surface on one side, current carrying capacities are tabulated in
Appendix 2, Method 4 of Appendix 3 being the appropriate Reference method.
For a single cable likely to be totally surrounded by thermally insulating material over a length of more than
0.5m, the current carrying capacity shall be taken, in the absence of more precise information, as 0.5 times
the current carrying capacity for that cable clipped direct to a surface and open (Reference Method 1 of
Appendix 3).
Where a cable is to be totally surrounded by thermal insulation for less than 0.5 m the current carrying
capacity of the cable shall be reduced appropriately depending on the size of cable, length in Table 4 are
appropriate to conductor size up to 10 mmsq in thermal insulation having a thermal conductivity greater than
0.0625 W/K.m.
Table 6: Correction factors for cable installed in enclosed trenches (Installation Methods 18, 19 and
20 for Appendix 3)
The correction factors tabulated below relate to the disposition of cables illustrated in items 18 to 20 of
Appendix 3 and are applicable to the current carrying capacities for installation methods 12 or 13 of Appendix
3 as given in the tables of Appendix 2:
Correction Factors
* When cables having different conductor operating temperatures are grouped together the current rating should be based on the
lowest operating temperature of any cable in the group.