0% found this document useful (0 votes)
550 views4 pages

Upr900 Graphical Indicator Concise Manual English 4 Pages

The document provides installation and safety instructions for the DYNISCO UPR900 graphical 1/4 DIN process indicator. Key points include: - Do not remove panel gaskets which provide a seal against dust and moisture. Double insulation is required for all external circuits. - Installation should only be performed by qualified personnel and comply with electrical codes. Impairment of protection can occur if not used as specified. - Main boards can be accessed by detaching mounting struts. Option modules plug into correct connectors. - Observe transformer color codes when replacing power supply boards to ensure proper voltage. Recalibration is required if display or input boards are replaced. - Panel mounting is

Uploaded by

Neviemaky
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
550 views4 pages

Upr900 Graphical Indicator Concise Manual English 4 Pages

The document provides installation and safety instructions for the DYNISCO UPR900 graphical 1/4 DIN process indicator. Key points include: - Do not remove panel gaskets which provide a seal against dust and moisture. Double insulation is required for all external circuits. - Installation should only be performed by qualified personnel and comply with electrical codes. Impairment of protection can occur if not used as specified. - Main boards can be accessed by detaching mounting struts. Option modules plug into correct connectors. - Observe transformer color codes when replacing power supply boards to ensure proper voltage. Recalibration is required if display or input boards are replaced. - Panel mounting is

Uploaded by

Neviemaky
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

DYNISCO UPR900 CAUTION: Do not remove the panel gasket; it is a seal against dust and

moisture.
GRAPHICAL ¼ DIN PROCESS INDICATOR
Rear Terminal Wiring
CONCISE PRODUCT MANUAL (59479 - 02) CAUTION: The instrument is double insulated. All external circuits
The following symbols are used on the product labels: connected must provide double insulation.
Caution, refer to installation Failure to comply with the installation instructions may impact the
manual when connecting Equipment protected through- protection provided by the unit.
General danger to life or out by double insulation Note: The wiring diagrams show all possible option combinations. The
limb connections required depend on the options fitted. Use single strand (1.2mm /
Both direct and alternating AWG18 max size) copper wire, except for the thermocouple input, where the
Alternating current correct thermocouple or compensating cable and connectors should be used.
current
Main Terminals
1. INSTALLATION CAUTION: Check correct operating voltage on the side label before
CAUTION: Installation should be only performed by technically connecting power. A UL listed 1A anti-surge fuse, rated 250V (for AC)
competent personnel. It is the responsibility of the installing engineer to 65V (for DC) should be fitted to the power input. An IEC60947-1 &
ensure that the configuration is safe. Local regulations regarding IEC60947-3 compliant isolation switch should be fitted close to the unit,
electrical installation & safety must be observed - e.g. US National in easy reach of the operator, and appropriately marked.
Electrical Code (NEC) and/or Canadian Electrical Code. Impairment of All connections to the device must be made through a spade format or
protection will occur if the product is used in a manner not specified by similar connection, with connection to the spade terminal touching both
the manufacturer. the insulation and conductor material.(Use a standard crimping tool)All
Installing Option Modules connections must be Mechanically secured so as to prevent any wiring
Second Input + Linear out becoming loose and coming in contact with other wires or the
Module instrument casing
The above applies to any and all connection to hazardous mains supply
Option A Module either direct or indirect (Through a switch (Relay))

Option 3 Module

Universal Input+ Linear out


Board
Power Supply Board

Option 1 Module

Option 2 Module

Option C Module

To access the option modules, first pull the instrument from the housing.
a. Detach the main boards by lifting first the upper, and lower mounting struts.
b. Plug the required option modules into the correct connectors, as shown below.
c. Locate the module tongues in the corresponding slot on the opposite board.
d. Hold the Power and Input boards together while relocating on their mountings.
e. Push the boards forward to ensure correct connection to the Display board.
f. Replace the instrument by aligning the boards with the guides in the housing, and
then slowly push he instrument back into position.
Note: Option modules are automatically detected at power up.
CAUTION: External computing devices connected to the
Main Board Connectors communications port must comply with the standard, UL 60950.
POWER SUPPLY Option 3 Slot Additional Option Terminals
BOARD Connector PL4B
Transformer Colour
Code Option Slot A
100-240V (Yellow) Connectors
24-48V(Blue) PL5, & PL6

Option 1 Slot
Connectors PL7 & PL8
Display Board
Connections PC Configurator
Socket SK1

UNIVERSAL Option 2 Slot


INPUT Connector PL4A
BOARD
Electrical shock can result in death or serious injury. Avoid contact with
Note: Plastic pegs the leads and terminals. High voltages that may be present on leads can
prevent fitting of cause electrical shock
older non-
reinforced single 2. SPECIFICATIONS
relay modules – PROCESS INPUTS 1 AND 2
remove the peg to Sampling Rate: Better han 10 times per second.
fit dual relays Resolution: 16 bits. Always four times better than display resolution.
Replacement of Main Boards Impedance: >10M: resistive, except DC mA (5:) and V (47k:).
CAUTION: Replacement of main boards should only be carried out if Temp Stability: Error <0.01% of span per °C change in ambient temperature.
unavoidable, and must only be carried out by trained personnel. Supply Variation: Supply voltage influence negligible within supply limits.
When replacing the power supply board, observe the transformer colour and case Humidity Influence: Negligible if non-condensing.
labelling to check the supply voltage, otherwise irreparable damage may occur. Process Display: Displays up to 5% over and 5% under span limits.
If the display or input boards are replaced, a full recalibration must be carried out
Panel Mounting Process Variable Reading adjustable ± Controller Span. +ve values added to
Input Offset: Process Variable, -ve values subtracted from Process Variable
Slide mounting clamp over
Gasket the instrument housing Sensor Break High or Low range break activates as per user definition(default
towards rear face of Detection: is to Break to a High scale range)
Mounting Panel moun ing panel until the
tongues engage in ratchets Isolation: Isolated from all outputs and other input at 240V AC.
and instrument is clamped in
Ratchets position.

Instrument Hold instrument firmly in


Housing position (apply pressure to
bezel only)
Strain Gauge Inputs 350 to 5K ȍ Strain Gage Accuracy: 0 to 20mA, 4 to 20mA into 500Ÿ max, 0 to 10V, 2 to 10V, 0 to
5V into 500Ÿ min.
Bridge Connec ion 4 or 6 wire (6 to use internal shunt cal
Updated at about 65ms intervals. (130ms settling time)Stability:
switch)
± 76ppm
Bridge Excitation 10 V +/- 7%
Isolation: Reinforced safety isolation from inputs and other outputs.
Bridge Sensitivity 1.4 - 4 mV/V
Transmitter PSU
Input Signal Span - 25% to +125% of full scale (approximately - Power Rating: 24V nominal (18 to 28V DC) into 400: minimum resistance
10 mV to +50 mV) (60mA Drive). (Option to use DC Linear output as 0-10V
Calibration Internal switch between CAL2 & CAL1 terminals stabilised PSU).
(7&6 or 39&40). External resistor only. Isolation: Reinforced safety isolation from inputs and other outputs.
Shunt Value From 40% to 100% COMMUNICATIONS
Supported Type Range °C Range °F PC Configuration
Thermocouple Types B Connection: RS232 via PC Configurator Cable to RJ11 socket under case.
0 to 1824°C 32 to 3315°F
& Ranges: C 0 to 2320°C 32 to 4208°F Isolation: Not isolated from input or SSR Driver outputs. For bench
D 0 to 2315°C 32 to 4199°F configuration only. CAUTION: Do not use in live applications.
E -240 to 1000°C -400 to 1832°F RS485
J -200 to 1200°C -328 to 2192°F * Connection: Locates in Option Slot A. Connection via rear terminals
K -240 to 1373°C -400 to 2503°F * (refer to wiring diagram).
L 0 to 761°C 32 to 1402°F * Protocol: Modbus RTU.
N 0 to 1400°C 32 to 2552°F *
Slave/Master Mode Slave address range 1-255 or Setpoint master mode.
PtRh 20%:40% 0 to 1850°C 32 to 3362°F
R 0 to 1759°C 32 to 3198°F Supported Speeds: 4800, 9600, 19200, 38400, 57600 or 115200 bps.
S 0 to 1762°C 32 to 3204°F Data Type: 8 data bits and 1 stop bit. Odd, even or no parity.
T -240 to 401°C -400 to 754°F *
Isolation: 240V reinforced safety isolation from all inputs and outputs.
Optional decimal place can be displayed up to 999.9°C/F
Thermocouple r0.1% of full range, r1LSD (r1°C for internal CJC if enabled). Ethernet
Calibration: Linearization better than better r0.2 C (r0.05 typical) on ranges Connection: Locates in Option Slot A. Connection via RJ45 connector on top
marked * in he table above. Linearization for other ranges is of case.
better than better than r0.5 C. Protocol: Modbus TCP. Slave only.
BS4937, NBS125 & IEC584 Supported Speed: 10BaseT or 100BaseT
Supported RTD Types Type Range °C Range °F Isolation: 240 V reinforced safety isolation from the supply, inputs and
& Ranges: 3-Wire PT100 -200 to 800°C -328 to 1472°F outputs (except SSR Drivers).
NI120 -80 to 240°C -112 to 464°F
Optional decimal place can be displayed up to 999.9°C/F
ALARMS
Alarm Types: Up to 3 alarms selectable as Process High, Process Low, Rate of
RTD Calibration: 0.1% of full range, r1LSD.
Signal Change (per minute), Sensor/input Break,
Linearization better than r0.2 C (r0.05 typical).
PT100 input to BS1904 & DIN43760 (0.00385:/:/°C). Alarm Hysteresis: A deadband from 1 LSD to full span (in display units) for
Process.Rate Of Change Alarm hysteresis is the shortest time (1
RTD Excitation: Sensor current 150ȝA r10%. to 9999 secs) the rate of change must be above the threshold for
Lead Resistance: <0 5% of span error for max 50: per lead, balanced. the alarm activate, or fall below the threshold to deactivate.
Supported Linear Type Range Offset Range Note: If the duration is less han this time, the alarm will not
Types & Ranges: mA DC 0 to 20mA DC 4 to 20mA DC activate no matter how fast the rate of rise.
mV DC 0 to 50mV DC 10 to 50mV DC Combined Outputs: Logical OR of alarms 1 & 2, 1 to 3,
V DC 0 to 5V DC 1 to 5V DC OPERATING CONDITIONS (FOR INDOOR USE)
V DC 0 to 10V DC 2 to 10V DC
Temperature: 0°C to 55°C (Operating), –20°C to 80°C (Storage).
Scalable from -2000 to 100000. Decimal point selectable from
0 to 3 places, but limited to 5 display digits (e.g. 9999.9) Relative Humidity: 20% to 95% non-condensing.
Maximum Overload: 1A on mA input terminals, 30V on voltage input terminals. Supply Voltage and Mains versions: 100 to 240VAC r10%, 50/60Hz, 24VA.
DC Calibration: r0.1% of full range, r1LSD. Power: Low voltage versions: 20 to 48VAC 50/60Hz 15VA or
22 to 65VDC 12W.
DC Input Multi-Point Up to 15 scaling values can be defined anywhere between 0.1
Linearization: and 100% of input. CONFORMANCE NORMS
EMI: CE: Complies with EN61326.
DIGITAL INPUTS
Volt-free contacts Open contacts (>5000: or 2 to 24VDC signal = Logic High Safety CE: Complies with EN61010-1. UL, cUL to UL61010C-1.
(or TTL): Closed contacts (<50: or -0.6 to +0.8VDC signal = Logic Low. Considerations: Pollution Degree 2, Installation Category II.
Isolation: Reinforced safety isolation from inputs and other outputs. Front Panel Sealing: To IP66 (IP65 front USB connector). IP20 behind the panel.
Digital Input Edge Sensitive. Requires High-Low or Low-High transition to (IP rating not recognised / approved by UL).
Sensitivity: change function. Front Panel Wash with warm soapy water and dry immediately.
Response Time: Slot A <0.25 second, Cleaning Close the USB cover (if fitted) before cleaning.
Selectable Digital Function Logic High Logic Low DISPLAY
Input Functions: Peak Reset No Action Reset Peak reading Display Type: 160 x 80 pixels, monochrome graphic LCD with a dual colour
Alarm and Peak No Action Reset Peak reading and (red/green) backlight.
Reset Resets latched alarm if
alarm conditions no longer Display Area: 66.54mm (W) x 37.42mm (H).
exists Display Characters: 0 to 9, a to z, A to Z, plus ( ) - and _
Zero Calibration No Action Perform zero Calibration Trend View: 120 of 240 data points shown in a scrollable window. Data is not
Zero Calibration, No Action Perform zero Calibration, retained when power turned off or if time base is changed.
Alarm and Peak Reset Peak reading and Trend Data: Any active alarm plus PV (solid) & SP (dotted) at sample time or
Reset Resets latched alarm if Max/Min PV between samples (candle-stick graph).
alarm conditions no longer Auto scales from 2 to 100% of Input Span.
exists
Reset Latched No Action Resets latched alarm if Trend Sample Rate: 1; 2; 5; 10; 15; 30 seconds or 1; 2; 5; 10; 15; 30 minutes.
Alarms alarm conditions no longer DIMENSIONS
exists Weight: 0.65kg maximum.
Data Recorder Stop Start Recording Size: 96 x 96mm (Front Bezel). 117mm (Depth Behind Panel).
Recording
OUTPUTS Mounting Panel: Panel must be rigid. Maximum thickness 6.0mm (0.25inch).
Caution: Plastic pegs prevent fitting of older non-reinforced single relay modules – Panel Cut-out Size: 92mm x 92mm. Tolerance +0.5, -0.0mm.
Remove the peg to fit dual relays (all dual relay modules have reinforced isolation) Ventilation 20mm gap required above, below and behind.
Single Relay
Type & Rating: Single pole double throw (SPDT); 2A resistive at 120/240VAC. Manufacturing Site
Lifetime: >500,000 operations at rated voltage/current. Address The Hyde Business Park, Brighton, BN2 4JU, United Kingdom
Isolation: Reinforced safety isolation from inputs and other outputs.
Dual Relay
Type & Rating: Single pole single throw (SPST), 2A resis ive at 120/240VAC.
Dual relay modules have shared common.
Lifetime: >200,000 operations at rated voltage/current.
Isolation: Reinforced safety isolation from inputs and other outputs.
Linear DC
Ranges 0 to 5, 0 to 10, 1-5, 2 to 10V & 0 to 20, 4 to 20mA (selectable)
with 2% over/under-drive when used for control outputs.
Resolution: 15 3/4 bit (1 part in 52K)
3. POWER UP SEQUENCE Trend View
Active Alarm(s) Trend Upper Scale Value
Following the power-up self-test and logo screen, the instrument normally enters Cursor Line
Operation Mode, from which the user can select the instrument’s Main Menu (refer Process Variable Trend PV Value At Cursor Line
to the Screen Sequence list). The exceptions to this are the first power-up after
purchase, when option modules have been changed or if an error is detected. Setpoint Trend (dotted) Trend Lower Scale Value

Setup Wizard Time Markers Sample Interval (or Time


(10 samples per marker) Trend View At Cursor Line)
An easy Setup Wizard runs automatically at first ever power-up. Follow the
Wizard to setup parameters required for typical applications (screens marked w in Trend View graphs PV; or Max/Min PV between samples, plus active alarms.
the Screen Sequence list). A partial Wizard also runs whenever option modules Trend Scale Values adjust automatically to visible data (between 2 to 100% of the
have been changed, this only shows parameters affected by the changes. The input span). Sample intervals are set in Display Configuration.
Wizard can also be run from the Main Menu. It exits to Operation Mode once Pressing % or & moves the Cursor Line back through the last 240 data points.
completed. Note: Data is not retained at power down or the Sample Interval is changed.
Start-Up Errors Over/Under Range & Input Fail Indications
These messages indicate that a hardware or configuration an error has occurred. If the process or auxiliary inputs are >5% above or below the scale max/min, their
Caution: Do not continue with the process until the issue is resolved. displayed value is replaced with the word “HIGH” or “LOW”.
If a signal break is detected, their value is replaced with “OPEN” and an un-
Message Displayed Reason
calibrated input is replaced by “ERROR”. In OPEN or ERROR conditions, the
Option Slot n Error Fault detected. Replace the module in slot n
Control Outputs go to the pre-set power value (see Control Config)...
Configuration Problem Check all instrument parameters before using Caution: Correct the problem before continuing normal operation.
For Service Contact Details of who to contact if a fault persists

4. OPERATION MODE 5. SERIAL COMMUNICATIONS


This mode is entered at power on, or accessed from the Main Menu. If required, all Set Ethernet option IP address with supplied software for networks without DHCP
Operation Mode parameters can be made read only (see Display Configuration). Refer to he User guide (from your supplier) for help with communications.
Note: Configuration must be completed before starting normal operations.
Normal Operation 6. STRAIN GUAGE CALIBRATION MODE
LED Indicators Press the %+ Gto enter calibration mode from any location for quick access (see
LED Function Labels Strain Gauge Calibration in Configuration Mode)
Process Variable Value 1 Only applicable when Sensor input type is set to Strain Gauge
Engineering Units
Process Variable Value 2
Input as Percentage of Span
Typical Operation Screen Span
Subsequent screens allow the display and selection/adjustment* alarm status and
trends.
Press G or $ to move forward or back though the screens.
Where adjustment is possible*, press % or & to alter the values.
*If adjustment is not disabled in Configuration.

7. SCREEN SEQUENCES
The parameters displayed depend on how the instrument has been configured. After 2 minutes without key activity, most screens revert to the next higher menu level, until
reaching the base Operation Mode display. Note: Additional screens will be displayed if the USB, Profiler or Recorder Options are fitted - Refer to the Supplementary Manual.
Screens marked   persist unless changed by the user. Screens marked W are also included in the Setup Wizard. Menus marked ± = Require a un-lock code for access.
Screen Navigation
$= Accept Value & Move Back % = Next Item/Increment & = Prior Item/Decrement ' = Accept Value & Move Forward F+ G = Move Up One Menu Level
The symbols !are showed to the right of the lists when more menu options are available above  or below .
Operation Mode
Base operating screen. LED Labels;   LED Labels = LED indicator functions. Defaults are ALM1, ALM2 & TUNE - these labels can be altered with configuration software
PV value(s);Bar Graph Bar Graph = Input 1 percentage of Span (Values shown depend on configuration Display parameters)
Peak Display Screen(s) PV1 or PV2 and the Peak value(Peak Max or Min values shown depend on configuration Display parameters)
Select Main MenuS Option from list. Press ' to continue. - Press F+ G to move from Operation Mode to Main Menu

Alarm Status Active / inactive status of all configured Alarms.


Trend View(s)   A trend graph of PV1 PV2 or Differential or the Max/Min value of the PV between samples. Any active alarm(s) are indicated at the top of the
graph.(Values shown depend on configuration Display parameters)
- Custom Display screens … Up to 50 Configuration parameters can be copied into Operation Mode using the PC software. In this mode they are not pass code protected.
Note Operation Mode screens can be made globally read only from Display Configuration
± Setup Wizard
Setup Wizard Unlocking w Enter correct code number to access Setup Wizard. Default Value = 10
- Screens marked w … w Press ' to select each major configuration parameter in turn. Follow the on-screen prompts to alter the values.
Setup Wizard Completed w Confirms completion of the Setup Wizard. Exits to Operation Mode.
± Supervisor Mode
Supervisor Mode Unlocking If Supervisor Mode is configured (requires PC software), enter correct code number to continue. Default Value = 10
- Supervisor Mode Screens … Press ' to select up to 50 Configuration parameters in turn. Follow on-screen prompts to alter the values.
± Configuration Menu
Configuration Mode Unlocking Enter correct code number to access Configuration Mode. Default Value = 10
MAIN MENU OPTIONS

Configuration Options Select required Configuration Menu Option from list. Press ' to continue.
Refer to the Configuration Menu screens sequences opposite for information about the Configuration Sub-Menus.
± USB Menu
USB Mode Unlocking Enter correct code number to access USB Menu. Default Value = 10
Read/Write To USB Device? From: Read/Write Configuration File; Read/Write Profile File or Write Recorder Log File.
Write

Enter an 8-character folder name for logs, or a file name for configurations and profiles. An extension (.bct for configurations, .pfl for profiles) is
Enter A File or Folder Name
added automatically. Caution Existing files/folders with the same name will be over-written.
Writing Configuration File The file is being written. Caution Do not disconnect USB device until completed! Data loss or corruption may result.
Transfer Successful Confirmation of successful data transfer. Press ' to continue
Read

Select File Select the Configuration file to transfer from the USB stick. Caution A configuration read overwrites all existing instrument settings.
Reading Configuration File The file is being read. Caution Do not remove the memory stick whist this operation is in progress. Data loss or corruption may result.
Transfer Successful Confirmation of successful data transfer. Press ' to continue
Transfer Failure For write failures, check the disk space on the USB stick. For read failures, check the maximum number of profiles/segments is not being exceeded.
± Recorder Control
Recorder Mode Unlocking Enter correct code number to access Data Recorder Menu. – If Log Trigger is Recorder Menu Start/Stop. Default Value = 10
Recording In Progress Warning If recording in progress when Recorder Menu entered. - Access to the Start/Stop or Abort screens only until the recording is stopped.
Start/Stop Data Recording Manually Stop, or Start a new recording. – If Log Trigger is Recorder Menu Start/Stop.
Abort Recording Forces a recording to Stop, overriding the selected record trigger. – If Log Trigger is During Alarms; Digital Input A or B; or During Profile.
Delete Recording Clears the recorder memory. Caution Permanently removes All recorded data.
Product Information Mode
Input(s)Calibration Status Calibration status of mVDC, VDC, mADC, RTD and Thermocouple CJC inputs. All should be “Calibrated”.
Calibration Check Due Date Date re-calibration is due. - If Calibration Reminder Enabled in Inputs Configuration.
Option Slot n Information Type of Option Modules (if any) fitted in Option Slot s 1-4, A or B
Units Feature Information Display Only; USB Port; Data Recorder (includes USB Port).
Firmware Information Type and version of firmware.
Serial Number Information Instrument serial number.
Date of Manufacture Date of Manufacture
Service Information Mode
For Service Contact Contact information for Service, Sales or Technical Support.
Input Configuration
Input n Setup
Process Variable Input Type w From Strain Gauge, Thermocouple, RTD and Linear inputs. - see specifications section for details.
Engineering Units w Select display units from: °C; °F; °K; bar; %; %RH; pH; MPa; KGcm; psi or none.
Decimal Point Position w Display resolution with 0 1 2 or 3 decimal places. Temperature inputs are limited to 1 decimal place.
Multi-Point Scaling Enable Enables/disables Linear Input Multi-Point Scaling.
Scale Range Lower Limit w Sets the usable span (min = 100 units, max = range limits - see specs) for temperature inputs. For Linear inputs, Upper & Lower Limits define the
Multi-Point Scale Point(s) Values shown (-1999 to 100000) when input is at minimum and maximum values. Min span = 100 units. If Multi-Point Scaling is enabled, up to 15
Scale Range Upper Limit w Breakpoints* can scale input vs. displayed value, between the linear input scale limits. *A breakpoint set at 100% input ends the sequence.
Input Filter time Filter unwanted noise from input signal. Adjustable from 0.5 to 100.0 seconds (default = 0.5s). Caution Use with care!
Input Failure Mode Set to Fail High or Fail Low on sensor break
Input Peak Detection Disabled Maximum Peak or Minimum Peak
CJC Enable/Disable Enables/disables internal Thermocouple Cold Junction Compensation. The default value is Enabled.
Process Variable Offset Trims the PV. +Ve values add to, –Ve values subtract from measured input. Caution Use with care!
Input n Calibration (viewed when temperature input type selected)
Calibration Type Select from: Factory, single point and Two point Calibration
Calibration Offset Enter value to offset input signal by, from off (no off set applied) to + ve or – ve maximum of input Span
Calibration Low Temp & Low Offset Enter the value at which you conduct the low end calibration and required offset for calibration
Calibration High Temp & High Offset Enter the value at which you conduct the High end calibration and required offset for calibration
Calibration reminder
Calibration reminder Enable or Disable Calibration reminder
Calibration Reminder Date Set the date that the Calibration reminder is due
Digital Input Function Select
Digital input C1...4 Choose from the following: Input 1,2 or 1+2 Peak reset, Input, Alarm Reset, Input 1,2 or 1+2 Alarm and Peak reset, Input 1,2 or 1+2 Zero Calibration
Input 1 2 or 1+2 Zero Calibration Alarm and Peak reset Data Recorder Start/Stop*.
Strain Gauge Calibration
Input n Shunt resistor Enabled or Disable Default : Enabled
Select required Main Menu Option from list. Press ' to continue. - Press F+ G to move back to Main Menu

Input n Calibration resistor Set the percentage of range the calibration shunt resistor needs to be set at between 40%and 100%. Default 80%
Percentage
Start Input n Low Point Calibration Press %+&keys to begin calibration procedure
Start Input n High Point Calibration Press %+&keys to begin calibration procedure (Can only be accessed once a successful low calibration has been completed)
Error Messages Count Fail means the low calibration will fail if the offset is less than -10mV or greater than +10mV. This signifies potential faulty sensors or the high
calibration will fail if the count value is less than +20mV or greater than +50mV. This signifies potential faulty sensors
RCal Fail means the high calibration will fail if the mV value is within 10mV of the low calibration value. This is a potential RCAL failure.
Output Configuration
Linear Output n Type w From: 0-5, 0-10, 1-5, 2-10V & 0-20, 4-20mA or 0-10VDC adjustable Transmitter PSU.
Adjustable 0-10V Transmitter PSU n w Voltage required if Output n is 0-10VDC adjustable Transmitter PSU.
Output n Usage w From: Alarms; Retransmit Process Variable.
CONFIGURATION MENU OPTIONS

Output n Alarm Selection w Alarm 1; 2; 3; or Logical OR of alarms 1 to 2; 1 to 3; Selectable Direct or Reverse Action.
Retransmit Output n Scale Low w Displayed value at which the retransmission output = minimum. Adjustable from -1999 to 9999.
Retransmit Output n Scale High w Displayed value at which the retransmission output = maximum. Adjustable from -1999 to 9999.
Alarm Configuration
Alarm n Type w From: Unused; High; Low; Rate Of Signal Change per minute; PV Signal Break; Percentage of Memory Used
Alarm n Input Selection From: Universal Input 1 or 2
Alarm n Value w Alarm activation point. – applicable if type is High; Low;
Alarm n Hysteresis Deadband on “safe” side of alarm, through which the signal must pass before alarm deactivates.
Signal change Alarm n Min. Duration Minimum time the rate of PV change must be above the alarm threshold for a Rate Of Change Alarm to change state (on or off). 1 to 9999 secs.
Alarm n Inhibit Prevents alarm activation if the alarm condition is true at power up. Activation occurs only after the condition has passed and then reoccurred.
Percentage of Memory used 0-100%
Alarm n Filter Time Filter the time the alarm needs to be active for the action to take place from 0 5s to 100s
Communications Configuration
No Comms Warning If Communications Configuration menu is entered without a communications module fitted.
Modbus RTU Parity w From: Odd; Even or None.
Modbus RTU Data Rate w From: 9600; 19200; 57600 or 115200 bps.
Master Mode, or Slave Address w Slave address (1 to 255), or multi-zone Setpoint Master Mode.
Master Mode Format The data format required by the attached setpoint slaves. From: Integer; integer with 1 decimal place & float.
Serial Communications Write Enable Enables/disables writing via RS485 or Ethernet (if fitted). When disabled, all parameters are read only.
Recorder Configuration Refer to the Supplementary Product Manual for information about the additional screens when Data Recorder is fitted.
No Recorder Warning If the Recorder Configuration menu is entered on an instrument without this option.
Recording In Progress Warning If recording in progress when Recorder Configuration entered. - Access to the Start/Stop or Abort screens only until the recording is stopped.
Recording Mode Record Until Memory Used (Stop recording when full) or Continuous FIFO (First In - First Out - overwrites oldest data when full).
Recording Sample Interval From: Every 1; 2; 5; 10; 15; 30 Seconds, or Every 1; 2; 5; 10; 15; 30 Minutes.
Recorder Trigger The recording Start/Stop trigger method. From: Operation Mode; Recorder Menu; On Alarm; Digital Input.
Trigger On Alarms Any from: Alarm n – Where n is alarms 1 to 5. Any combination of these can be set to trigger (TRG) or not (OFF).
Values To Record Any from: Process Variable value; Maximum or Minimum PV (since previous sample).
Events To Record Any from: Alarm n Status or Unit On/Off. Note: An alarm state change between samples is also recorded. This uses additional recorder memory.
Recorder Status Information Shows if a recording is in progress; the recording mode; memory usage per sample; memory remaining and approximate recording time remaining.
Recorder Clock Configuration Refer to the Supplementary Product Manual for information about the additional screens when Data Recorder is fitted.
Date Format w The format used for displayed dates: dd/mm/yyyy (Day / Month / Year) or mm/dd/yyyy (Month / Day / Year). – Recorder versions only.
Set Date w Sets the internal clock Date. – Entered in the format defined by Date Format screen. – Recorder versions only.
Set Day Of Week w Sets the day of week used by the internal clock. – Recorder versions only.
Set Time w Sets the internal clock Time. - In hh:mm:ss (Hours : Minutes : Seconds) format. – Recorder versions only.
Display Configuration
Enable Custom Display Mode Enables/disables Custom Operation Mode, if configured (requires PC configuration software).
Read Only Operation Mode? Allows Operation Mode to be Read-Only or Read/Write. Screens can be seen but, values cannot be changed if Read-Only.
Operation Mode Bar Graph Format From: PID Power or Control Deviation or.
Trend Sample Interval Interval between display of next value on the trend graph From: Every 1 2 5 10 15 30 Seconds or Every 1 2 5 10 15 30 Minutes.
Select Trend Mode From: PV only, or Max/Min PV between samples (candle-stick graph). Alarm activity is always shown.
Display Colour From: Red only; Green only; Red to Green on Alarm or Green to Red on Alarm.
Invert Display Standard or Negative display image.
Display Contrast Screen contrast (0 and 100) to improve clarity. 100 = maximum contrast.
Language Select English or the alternate local language. The alternate language type can be changed using the PC software.
Lock Code Configuration
Lock Code View 1 View and edit the Setup Wizard; Configuration Mode Supervisor Mode USB Menu and Recorder Menu Lock Codes (1-9999 or OFF). Default Values
= 10
Reset To Defaults
Reset To Defaults Set all parameters to default values. Caution User must reconfigure all required settings before using the instrument following a reset.
*Both Recorder Trigger state and Digital input selection must be the same to start recording

You might also like