Smart & AFCI Combiner Manual Ver 1.6 PDF
Smart & AFCI Combiner Manual Ver 1.6 PDF
Smart & AFCI Combiner Manual Ver 1.6 PDF
Installation Manual
SolarBOS, Inc.
310 Stealth Court
Livermore CA 94551-9552
925-456-7744 ph.
925-456-7710 fax
www.solarbos.com
1
Copyright © 2013 SolarBOS, Inc. All rights reserved.
All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or
transmitted, in any form or by any means, electronic, mechanical, photographic, magnetic, or otherwise,
without the prior written permission of SolarBOS, Inc.
SolarBOS makes no representations, express or implied, with respect to this documentation or any of the
equipment and/or software it may describe, including (with no limitation) any implied warranties of utility,
merchantability, or fitness for any particular purpose. All such warranties are expressly disclaimed.
SolarBOS is not liable for any indirect, incidental, or consequential damages under any circumstances.
(The exclusion of implied warranties may not apply in all cases under some statutes, and thus the above
exclusion may not apply.)
Specifications are subject to change without notice. Every attempt has been made to make this document
complete, accurate and up-to-date. Users are cautioned, however, that SolarBOS reserves the right to
make changes without notice and shall not be responsible for any damages, including indirect, incidental
or consequential damages caused by reliance on the material presented, including, but not limited to,
omissions, typographical errors, arithmetical errors or listing errors in the content material.
Revision History
Rev. No. Date By Description
1.0 5 April 2013 AO Preliminary Release
1.1 16 April 2013 JS ETL Release
1.2 9 May 2013 AO Menu Layout
1.3 15 April 2014 AM Reformat TOC, added AFCI section
1.4 17 July 2014 AM Added 24VDC customer input wiring diagram
1.5 24 July 2014 AM Rewrote Appendices 1, 2, and 3
1.6 05 July 2016 JP Updated Menu
SolarBOS, Inc.
310 Stealth Court
Livermore CA 94551
925-456-7744 ph.
925-456-7710 fax
www.solarbos.com
2
Table of Contents
1. Safety Instructions ....................................................................................................... 5
1.1. Symbols ................................................................................................................................. 5
1.2. Warranty ................................................................................................................................ 6
2. Introduction .................................................................................................................. 7
2.1. Unpacking & Inspection ........................................................................................................ 7
3. Installation .................................................................................................................... 8
3.1. Dimensions & Weights .......................................................................................................... 8
3.2. SMART Combiner Orientation .............................................................................................. 9
3.3. Disconnect Switch Assembly ................................................................................................ 9
3.4. Defeating the Disconnect Handle.......................................................................................... 9
4. Wiring ...........................................................................................................................10
4.1. Input Wiring ......................................................................................................................... 10
4.2. Output Wiring ...................................................................................................................... 10
4.3. Wire Entry Locations & Dimensions .................................................................................... 11
5. Circuit Map ...................................................................................................................12
5.1. PV Fuses ............................................................................................................................. 12
6. The Smart Sensor Module ..........................................................................................13
6.1. Smart Combiner Wiring ....................................................................................................... 13
6.1. 24VDC Input Wiring............................................................................................................. 13
7. AFCI Combiner Box.....................................................................................................14
7.1. Even-String CT Installation ................................................................................................. 14
7.2. Odd-String CT Installation ................................................................................................... 15
7.3. Lexan Guard Installation ..................................................................................................... 16
8. Commissioning the Combiner Box ............................................................................17
8.1. Channel Light Map and Menu Navigation ........................................................................... 18
8.2. Zero Current Calibration ...................................................................................................... 20
8.3. Setting Active Channels ...................................................................................................... 21
8.4. Operating Calibration (Only Required for Modbus Users) .................................................. 22
8.5. Setting Modbus Address ..................................................................................................... 24
8.6. Arc Fault Self-Test............................................................................................................... 26
8.7. Exiting the Menu.................................................................................................................. 26
8.8. Arc Fault Detection and Interruption ................................................................................... 26
8.9. Resuming normal operation after a fault ............................................................................. 26
9. APPENDIX 1 - Sensor Board Operation Quick Guide (Active Channels Version) ...27
9.1. Accessing and navigating the menus.................................................................................. 27
3
9.2. Menu indicators ................................................................................................................... 27
9.3. Entering Modbus address and Operation Calibration values ............................................. 27
10. APPENDIX 2 – Sensor Board Reset Button and Menu/Select Button Clarification 28
11. APPENDIX 3 – Torque Values .....................................................................................29
12. APPENDIX 4 – Factory Provided Control Wire Schematic .......................................30
13. APPENDIX 5 – Previous Menu Version ......................................................................31
13.1. Differences between Versions ........................................................................................ 31
13.2. Sensor Board Functions Menu ........................................................................................ 31
13.3. Setting the report type ..................................................................................................... 32
14. APPENDIX 6 - Sensor Board Operation Quick Guide (Previous Menu Version) .....33
14.1. Accessing and navigating the menus.............................................................................. 33
14.2. Menu indicators ............................................................................................................... 33
14.3. Entering Modbus address and Operation Calibration values ......................................... 33
15. APPENDIX 7 – Dual/Single Control Board Differentiation ........................................34
15.1. Dual Top Board with No Ribbon Cable ........................................................................... 34
15.2. Single Top Board with Ribbon Cable .............................................................................. 34
16. APPENDIX 8 - Troubleshooting ..................................................................................35
16.1. Board will start up, but only Channel 1 light is lit up........................................................ 35
16.2. Board’s green light is solid .............................................................................................. 35
16.3. Board frozen/locked up ................................................................................................... 35
4
IMPORTANT SAFETY INSTRUCTIONS
***SAVE THESE INSTRUCTIONS***
This manual contains important instructions for all SolarBOS Smart Combiner Box models that must be
followed during the installation and use of the Smart Combiner Box.
The Smart Combiner Boxes are designed and tested according to international safety requirements. As
with all electrical and electronic equipment, certain precautions must be observed when installing the
Smart Combiner. To reduce the risk of personal injury and to ensure the safe installation and operation of
the Smart Combiner, you must carefully read and follow all instructions and warnings in this Installation
Guide.
1. Safety Instructions
1.1. Symbols
Safety and Hazard Symbols
HAZARD: This symbol appears beside instructions and warnings that deal with
dangerous voltages that can injure people who come in contact with them.
Warnings
WARNING: A warning describes a hazard to equipment or personnel. It calls
attention to a procedure or practice, which, if not correctly performed or adhered to,
could result in damage to or destruction of part or all of the SolarBOS equipment
and/or other equipment connected to the SolarBOS equipment or personal injury.
Warnings may also be accompanied by one or more of the safety and hazard symbols described above
to indicate the type of hazard described therein.
Other Symbols
In addition to the safety and hazard symbols described previously, the following symbol is also used in
the Installation Guide:
GROUND: This symbol marks the areas in the combiner for connecting equipment
grounds only.
5
1.2. Warranty
All combiners sold in the USA have a five-year warranty. For warranty coverage, or if you have questions
about the combiner warranty, contact SolarBOS at the address, telephone number, or web site listed on
page 1 (to send e-mail, see the contact section of the SolarBOS web site: www.solarbos.com).
WARNING: All electrical installation must be done in accordance with the National
Electrical Code ANSI/NFPA 70, local building codes, and the requirements of the
authority having jurisdiction.
WARNING: To prevent electrical shock or injury, all wiring and commissioning
procedures must be performed by qualified personnel.
WARNING: Before installing or using the Smart Combiner, read all of the
instructions and warnings on the combiner and in this Installation Guide.
WARNING: PV arrays produce electrical energy when exposed to light and thus
create an electrical shock hazard.
WARNING: The Smart Combiner uses an integrated disconnect switch, yet both
the line and load side of the switch may still be energized in the OFF position.
Always test both sides of the disconnect before servicing the combiner.
6
2. Introduction
SolarBOS has introduced a new line of Smart Combiner Boxes designed for use with all module and
inverter combinations.
Combiner features include:
Listed to UL 1741
Capable of detecting and interrupting series arcs in the array wiring
Available in NEMA 3, 3R, 4 powder-coated steel, and NEMA 4X stainless steel or fiberglass
enclosures (others available upon request)
Integrated load-break disconnect switch (optional)
Integrated load-break contactor switch (optional)
Current sensing (optional)
Arc-Fault Circuit Interruption (AFCI) (optional)
A note on nomenclature:
The solar industry oftentimes refers to a combiner box as a “combiner” or “string combiner” and if these
terms are used within this manual they should be considered to mean a “combiner box.”
Additionally, UL (Underwriters Laboratories) makes a distinction between an Arc Fault Detection (AFD)
device and an Arc Fault Circuit Interruption (AFCI) device. An AFD device detects series arcs per the UL
1699B test standard whereas an AFCI device detects and interrupts series arcs per the UL 1699B test
standard. SolarBOS combiners are AFCI devices, even though they also meet the requirements of an
AFD device.
7
3. Installation
3.1. Dimensions & Weights
Refer to Figure 1 and Tables 1-2 for enclosure dimensions. Use appropriate hardware for the mounting
surface. The dimensions of the unit for each Smart Combiner option and the respective weights are
shown in Table 1 below.
8
3.2. SMART Combiner Orientation
NEMA-3/4/4X enclosures may be installed in either the vertical or the horizontal orientation. This applies
to Smart Combiner with the “N3” “N4” “4XF” and “4XSS” designation. If installed horizontally (with the
door facing the sky), they should be supported by appropriate mounts.
WARNING: Do not install the Smart Combiner directly to the roof material. Doing
so will void the warranty.
WARNING: Only qualified personnel should defeat the handle door interlock on
the SMART Combiner.
9
4. Wiring
4.1. Input Wiring
Refer to Figure 2 and Table 2 for the input wiring locations of the SMART Combiner. PV positive and
negative conductors are wired into the positive lug and negative distribution block, respectively. These
terminal locations are clearly marked. All PV safety ground conductors are wired into the ground bus
located at the bottom of the SMART Combiner.
NOTE: The SMART Combiner enclosure is shipped with no entry holes. A knock-
out is required for the appropriate conduit size. SolarBOS recommends wire entry
to be made according to Figure 2.
NOTE: On units with provision for using crimp lugs use Panduit part number
LAA250-38-5 for 250MCM wire or a UL listed equivalent part from another
manufacturer. Be sure to use the appropriate part number for the intended wire
gauge.
NOTE: Rain tight or wet location hubs that comply with the Standard UL514B must
be used for NEMA 3/3R outdoor applications. NEMA 4 or 4X applications must use
watertight hubs that comply with the StandardUL514B. Use Myers-type, water-tight
conduit fittings such as Thomas & Betts H200TB (for 2” conduit) or H300TB (for 3”
conduit) or equivalent from others. Install fittings per manufacturer’s
recommendations.
10
4.3. Wire Entry Locations & Dimensions
Dimension “A”, “B”, “C”, and “D” are for input and output wire locations. These locations are
recommendations only. Care should always be taken to assure there is enough wire bend space for the
desired output wire gauge when choosing a conduit entry location. The wire entry locations for the
standard, contactor and disconnect combiners are shown in Table 2.
COMBINER ENCLOSURE # OF
A B C D
TYPE TYPE CIRCUITS
N3/N4 8, 12, 16 20 8 8 7
N3/N4 24, 32 30 12 12 7
STANDARD
4XF 8, 12, 16 21 8 8 8
4XF 24, 32 31 12 12 8
N3/N4 8, 12, 16 20 8 8 7
N3/N4 24, 32 30 12 12 7
CONTACTOR
4XF 8, 12, 16 21 8 8 8
4XF 24, 32 31 12 12 8
N3/N4 8, 12, 16 20 8 8 7
N3/N4 24, 32 30 12 12 7
DISCONNECT
4XF 8, 12, 16 21 8 8 8
4XF 24, 32 31 12 12 8
All dimensions are in inches unless otherwise noted
11
5. Circuit Map
The following figure shows the channel map for the PV string inputs for up to 8, 12 and 16 channels.
2 4 6 8 10 12 14 16
Figure 4. Input wire labeling schematic for (a) 8 strings, (b) 12 strings, and (c) 16 strings
The Modbus output will report PV string current readings according to the channel map shown above.
5.1. PV Fuses
All SolarBOS SMART Combiners ship with fuses installed according to the user’s predetermined
requirements. All fuses and connection points are electrically tested prior to shipment. SolarBOS
maintains stock of common fuse sizes if replacements are necessary or spares desired.
WARNING: Never open a fuse holder while it is under load. Electrical arcing and
damage to the fuse holder will occur if a fuse holder is opened under load.
12
6. The Smart Sensor Module
Smart Combiners include a sensor module located on top of the bus bar in between the fuse holders as
shown in Figure 5. The unit requires a 24V DC power supply available separately from SolarBOS. The
module measures the current of each circuit. The module is also capable of communicating current
information via Modbus/RS-485.
6.1. Smart Combiner Wiring
The output from the current sensor module is RS-485 serial using the standard Modbus RTU protocol.
The positive data, negative data, and data shield should be wired to the RS-485 network. The 24V DC in
is wired to the power supply. Minimum wire size of 24 AWG is required for RS-485 communications. The
24V DC wire should be sized based on distance and number of combiners.
6.1. 24VDC Input Wiring
The user must apply 24VDC at the provided terminals (600mA for AFCI models, and 100mA for AFD
model combiner boxes).
PV IN (-)
PV IN (+)
PV OUT (-)
MENU/SELECT
BUTTON
PV OUT (+)
PV IN (+)
Figure 5. The SolarBOS Smart Combiner connection points. AFCI combiner shown.
13
7. AFCI Combiner Box
7.1. Even-String CT Installation
The Current Transducer (CT) is installed in one of two ways: “even-count” and “odd-count”. The terms
“even” and “odd” refer to the total number of string inputs entering a given combiner box. Figure 7 shows
an example of an even-count string input installation.
NOTE: Colored conductors shown for illustrative purposes only. Use appropriately sized conductors.
EVEN HALF OF
EVEN TOTAL STRINGS
NUMBER
OF
TOTAL
STRINGS
EVEN HALF OF
TOTAL STRINGS
14
7.2. Odd-String CT Installation
Figure 8 shows the top and bottom halves of an example odd-count CT installation. The lower half of the
strings is short one conductor. For the CT electronics to work properly, the number of strings going each
way through the CT must be balanced. For this to work with an odd-stringed system, one string must be
double-wrapped as shown below.
NOTE: Colored conductors shown for illustrative purposes only. Use appropriately sized conductors.
EVEN HALF OF
ODD TOTAL STRINGS
NUMBER
OF
TOTAL
STRINGS ODD HALF OF
TOTAL STRINGS:
Loop only one
conductor twice
15
7.3. Lexan Guard Installation
Plug in the lead from the MENU/SELECT button to the sensor board header labeled “SW.” Replace the
Lexan guard as shown in the Figure 8. To correctly secure the Lexan guard, insert one side, and then
squeeze the other side into place to fit the guard in between the fuse holders and completely cover the
sensor board.
16
8. Commissioning the Combiner Box
Previous versions of the AFCI Smart Board use a different commissioning procedure than is listed
here. The procedure listed here requires the user to set all active channels. If your version does not
require you to set active channels please refer to Appendix 5 and 6 – “Previous Menu Versions” for
additional information. If you are unsure of which version you have, compare the label on the inside of
the combiner box with figure 9 and 10 below:
1 3 5 7 9 11 13 15
Channel / Light Map:
2 4 6 8 10 12 14 16
1 3 5 7 9 11 13 15
Channel / Light Map:
2 4 6 8 10 12 14 16
17
8.1. Channel Light Map and Menu Navigation
1. The menu is accessible only while the board is in RUN mode (green LED flashing).
2. To enter the menu, press and hold the MENU/SELECT button until the LEDs flash, then release
the button.
3. The MENU/SELECT Button (Figure 12) performs two functions in menu mode, momentarily
press the button for scrolling through LED’s or press and hold about 4 seconds for selecting an
option, value, or entering a desired menu choice.
4. To abort from any menu option, power cycle the 24VDC power to the board OR press the on-
board green reset button (Figure 13). The board reboot is completed when the green LED
starts blinking.
5. Figure 11 shows the LEDs with the corresponding channel/menu number.
6. For a list of menu options, see below.
7. For step by step instructions, see sections 8.2 through 8.9
8. For an abbreviated “Quick Start Guide”, see Appendix 1. (Use Appendix 6 for Previous Menu
Version)
9. If you are using a single control board/dual busbar design, refer to Appendix 7.
1 3 5 9 11 13 15
2 4 6 8 10 12 14 16
Reset Button
19
8.2. Zero Current Calibration (Required for All Devices)
After hardware installation (combiner box completely installed and wired with the PV system fully
operational), it is necessary to calibrate the current sensors.
1. Turn off the contactor by using the manual switch and then opening the fuse holders on each
circuit. Ensure zero current is flowing through the busbar.
2. Enter Menu Mode. Press and hold the MENU/SELECT button for 4 seconds, until all red lights
flash. Release the button and channel 1 LED will light up. See Figure 14.
3. With the channel 1 light lit, press and hold the MENU/SELECT button for 4 seconds (until the
channel 1 light flashes), then release. The sensor board will cycle through all circuits setting the
zero point on each. No additional user action is required.
4. When finished, the board will return to normal operation, indicated by the flashing green light.
20
8.3. Setting Active Channels (Required for All Devices)
STEP INSTRUCTIONS NOTES
Press and hold the MENU/SELECT button
1 for 4 seconds until all channel lights flash This enters the Menu Mode.
ON and then OFF momentarily.
21
STEP INSTRUCTIONS NOTES
To turn a channel from active to inactive, or
visa versa, press and hold the
MENU/SELECT button until the amber LED
6a switches state.
22
STEP INSTRUCTIONS NOTES
Release button
23
STEP INSTRUCTIONS NOTES
17 Release the button. The desired third digit will be stored.
The board will cycle through each channel one at
18 No further user action is required.
a time.
When the user-action portion of the OPERATION CALIBRATION procedure is completed, the sensor
module will automatically:
1. Read back the stored values by flashing each digit one time.
a. The user should verify that the correct current values were entered.
b. In the example for 85A, the board will flash “0,” then “8,” and finally “5.”
2. Next, the board will calibrate each channel one by one.
3. Then it will light up all active channels simultaneously.
a. The user should verify that all active and inactive channels are correctly identified.
4. When finished, the board will enter RUN mode, indicated by the flashing green LED near the USB
connector.
Note: Calibration steps MUST be performed in order to ensure accurate readings of string
currents. It is recommended that the current be steady during the calibration procedure (i.e. no
clouds or overcast sky).
24
STEP INSTRUCTIONS NOTES
When LED 6 is selected, press and hold
4
the button until it flashes.
When the SET MODBUS ADDRESS procedure is completed, the board automatically returns to RUN
mode.
25
8.6. Arc Fault Self-Test
In order to verify the board is able to detect an arc, an arc fault self-test may be performed. To perform a
self-test:
1. Enter menu mode by holding the MENU/SELECT button for 4 seconds
2. Select channel 7 in the menu mode, then hold the MENU/SELECT button for 4 seconds. This will
cause the board to detect a simulated arc and light up all Red LEDS and open the contactor.
3. Exit the self-test cycle by holding the MENU/SELECT button for 4 seconds. This turns the red
LEDs off, and closes the contactor.
26
9. APPENDIX 1 - Sensor Board Operation Quick Guide (Active Channels Version)
Reset Button
Menu/Select
Button Input
28
11. APPENDIX 3 – Torque Values
29
12. APPENDIX 4 – Factory Provided Control Wire Schematic
AFCI COMBINER
BOXES ONLY
NOTE: For AFCI applications, power to the contactor is controlled by a set of dry contacts on the sensor
board. The dry contacts are accessible at the 2-pin connector labeled “CONT.” The sensor board does
not source power to the contactor.
30
13. APPENDIX 5 – Previous Menu Version
NOTE: It is possible to update the AFCI unit to the most current firmware version. Please
contact SolarBOS if you would like to perform this update.
ONLY USE THIS MENU IF THE LABEL IN YOUR COMBINER BOX LOOKS LIKE THE
FOLLOWING:
1 3 5 7 9 11 13 15
Channel / Light Map:
2 4 6 8 10 12 14 16
31
13.3. Setting the report type
The sensor board can report string level data in one of three intervals:
1. Instantaneous
2. 1-minute average
3. 15-minute average
The sensor Board does not push data. Rather it populates registers available to a gateway device.
SolarBOS offers a gateway device separately or it may be provided by the monitoring provider. SolarBOS
sensor boards default to 1 minute average reporting however some systems only collect data every 15
minutes and setting the report for 15 minute average may be advantageous, however, not required.
STEP INSTRUCTIONS NOTES
1 Ensure that the PV system is ON.
Press and hold the MENU/SELECT button
2 for 3 seconds until all channel lights flash
ON and then OFF momentarily.
When the SET REPORT TYPE procedure is completed, the board automatically enters RUN mode.
32
14. APPENDIX 6 - Sensor Board Operation Quick Guide (Previous Menu Version)
33
15. APPENDIX 7 – Dual/Single Control Board Differentiation
Some AFCI products have more than one control board. When two boards are present each must be
calibrated with the preceding procedures. Note: The right board is “upside down” and menu and string
numbers are accordingly opposite. Units with one control board and two separate fuseholder assemblies
are numbered in the same way. See below. Note: The unit below has “unused” channels.
16 14 12 10
1 3 5 7
15 13 11 9
2 4 6 8
No Top Board
34
16. APPENDIX 8 - Troubleshooting
16.1. Board will start up, but only Channel 1 light is lit up.
Pull off the lexan cover and pull off all three pin headers from the board (Contactor, button, CT).
Push the green restart button on the board. If the board starts up and goes to normal operation, then plug
in the contactor and CT to the correct pin locations. Do not plug in the button.
If the board is on the left side of the combiner box, place the contactor in the top right pin header
above the relay (black box), named CONT. Place the CT in the pin header right below the relay named
CT.
If the board is on the right side of the combiner box, place the contactor in the bottom left pin header
below the relay (black box), named CONT. Place the CT in the pin header right above the relay named
CT.
Push the green restart button. If the board continues to run and goes to normal operation, plug in the
button.
If the board is on the left side of the combiner box, place the button in the bottom right header named
SW. The three pin connector labeled VT should remain unconnected.
If the board is on the right side of the combiner box, place the button in the top left header named
SW. The three pin connector labeled VT should remain unconnected.
If the board continues operation after plugging in the button, then the pin header connections were
originally incorrect.
If the board goes into the menu after plugging in the button, then the menu button is faulty, please contact
SolarBOS for a replacement button.
35