The SIPROTEC 7UT85 transformer differential protection device
has been designed specifically for the protection of two-winding
transformers (2 sides). It is the main protection for the trans-
former and contains many other protection and monitoring
functions. The additional protection functions can also be used
as backup protection for subsequent protected objects (such as
cables or lines). The modular expandability of the hardware also
supports you in this process. With its modular structure, flexi-
bility, and the high-performance DIGSI 5 engineering tool,
SIPROTEC 7UT85 offers future-oriented system solutions with
high investment security and low operating costs.
• Safety due to high-performance protection functions • Additional current and voltage inputs can be added for
standard protection functions, such as overcurrent, voltage, 2.11
• Data security and transparency over the entire lifecycle of the frequency protection, etc.
plant, saving time and money
• Purposeful and easy handling of devices and software thanks • Arc protection
to a user-friendly design • Voltage-controller function ANSI 90V for two-winding trans-
formers, three-winding transformers, and grid coupling trans-
• Increased reliability and quality of the engineering process formers with parallel control (master/follower, circulating
• Highest availability even under extreme environmental condi- reactive current minimization)
tions by “conformal coating“ of electronic boards
• Graphical logic editor to create high-performance automation
• Cyber security in accordance with NERC CIP and BDEW White- functions in the device
paper requirements
• Up to 4 pluggable communication modules, usable for
• High-performance communication components warrant safe different and redundant protocols (IEC 61850,
and effective solutions IEC 60870-5-103, IEC 60870-5-104, Modbus TCP, DNP3 serial
• Full compatibility between IEC 61850 Editions 1 and 2 and TCP, PROFINET IO)
• Reliable data transmission via PRP and HSR protocols
Functions
• Extensive cyber-security functionality, such as role-based
DIGSI 5 permits all functions to be configured and combined as access control (RBAC), logging security-related events or
required. signed firmware
• Transformer differential protection for two-winding trans- • Simple, quick, and secure access to device data via a standard
formers with versatile, additional protection functions; Web browser – without additional software
expandable to 3 windings
• Secure serial protection data communication, also over great
• Transformer differential protection for phase-angle regulating distances and all available physical media (optical fiber, two-
transformers of the single-core type and special transformers wire connections, and communication networks)
• Universal usability of the permissible measuring points • Detecting operational measured variables and protection-
function measured values to evaluate the systems, to support
• Applicable from average up to extra-high voltage commissioning, and to analyze faults
• Protection of standard power transformers, auto trans-
formers, and motors
• Typical properties of a transformer differential protection such
as flexible adaptation to the transformer vector group, control
SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5 125
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85
• Frequency tracked protection functions over a wide frequency • Two-winding transformer 1.5 CB (DIFF protection, CBFP, REF)
range (10 Hz to 80 Hz) and the option to assign the protection
functions in a single device to different frequency tracking
• Two-winding-transformer (Diff. protection, voltage controller)
groups. • Motor (DIFF. protection, CBFP)
• Phasor Measurement Unit (PMU) for synchrophasor measured Application Examples
values and IEEE C37.118 protocol
Two-winding transformer basis (Figure 2.11/6)
• High-performance fault recording (buffer for a max. record
time of 80 s at 8 kHz or 320 s at 2 kHz) • Differential protection
• Auxiliary functions for simple tests and commissioning • Overload protection, backup protection for the downstream
power system
• Flexibly adjustable I/O quantity structure within the scope of
the SIPROTEC 5 modular system Two-winding transformer with restricted ground-fault protec-
tion (REF) (Figure 2.11/7)
Applications • Differential protection
DIGSI 5 provides application templates for standard applications. • Restricted ground-fault protection on the neutral side
They include basic configurations and default setting. These can
be used directly or as a template for application-related adapta- • Overload protection, backup protection for the downstream
power system
tion. The available measuring points make varied applications
possible. Before ordering a device, please configure the applica- • Circuit-breaker failure protection
tion with DIGSI 5. The table "Functions and application Two-winding transformer in breaker-and-a-half layout (Figure
templates" shows the functional scope of the device. Use the 2.11/8)
configurator to determine the necessary function points.
• Differential protection
Application Templates • Restricted ground-fault protection on the neutral side
Application templates are available in DIGSI 5 for the applica- • Overload protection, backup protection for the downstream
tions of the device 7UT85. The application templates contain power system
the basic configurations, required functions, and default • Circuit-breaker failure protection.
settings.
Figure 2.11/6 shows the typical structure of an application
The following application templates are available for the template, the measuring points used, the function groups used,
device 7UT85 in the DIGSI 5 function library: their internal circuiting, and the predefined functions. The
2.11
• Two-winding-transformer base (Diff. protection) example shows the two-winding transformer with restricted
ground-fault protection.
• Two-winding transformer with restricted ground-fault protec-
tion (Diff. protection, CBFP, REF)
126 SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85
SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5 127
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85
2.11
[dw_two-winding-temp_02, 3, en_US]
Figure 2.11/7 Application Example: Protection of a Two-Winding Transformer with Restricted Ground-Fault Protection
128 SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85
2.11
[dw_two-winding-temp_03, 3, en_US]
SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5 129
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85
Available
1 2 3 4 5
130 SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85
Available
1 2 3 4 5
SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5 131
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85
Available
1 2 3 4 5
Control ■ ■ ■ ■ ■ ■
Fault recording of analog and binary signals ■ ■ ■ ■ ■ ■
Monitoring ■ ■ ■ ■ ■ ■
Protection interface, serial ■
Circuit breaker ■ ■ ■ ■ ■ ■
Disconnector/grounding conductor ■
Transformer side 7UT85 ■
Frequency group manual update (from V7.8) ■
Cyber security: role-based access control (from ■
V7.8)
Temperature measurement via log ■
Function point class: 0 30 30 175 50
The configuration and function point class for your application can be determined in the SIPROTEC 5 order configurator at www.siemens.com/siprotec.
2.11
132 SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5
SIPROTEC 5 Devices and Fields of Application
Transformer Differential Protection – SIPROTEC 7UT85
2.11
SIPROTEC 5 Device Series ⋅ Protection, Automation, and Monitoring ⋅ Catalog – Edition 5 133