1MRK 505 340-BEN A Busbar Protection REB670 2.1 IEC Product Version: 2.1

The document provides technical specifications for a busbar protection device including: 1. Definitions for reference value, nominal range, and operative range as they relate to influencing factors and energizing quantities. 2. Tables listing the rated values, nominal ranges, and limits for analog current and voltage inputs, as well as frequency for protection transformer modules. 3. A table specifying the rated value, nominal range, and input resistance for mA input modules covering various current ranges and signal types.

Uploaded by

Daniel Christian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views1 page

1MRK 505 340-BEN A Busbar Protection REB670 2.1 IEC Product Version: 2.1

The document provides technical specifications for a busbar protection device including: 1. Definitions for reference value, nominal range, and operative range as they relate to influencing factors and energizing quantities. 2. Tables listing the rated values, nominal ranges, and limits for analog current and voltage inputs, as well as frequency for protection transformer modules. 3. A table specifying the rated value, nominal range, and input resistance for mA input modules covering various current ranges and signal types.

Uploaded by

Daniel Christian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

1MRK 505 340-BEN A

Busbar protection REB670 2.1 IEC


Product version: 2.1

20. Technical data

General

Definitions

Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment

Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified
requirements

Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements

Energizing quantities, rated values and limits


Analog inputs

Table 15. TRM - Energizing quantities, rated values and limits for protection transformer modules

Quantity Rated value Nominal range

Current Ir = 1 or 5 A (0.2-40) × Ir

Operative range (0-100) x Ir

Permissive overload 4 × Ir cont.


100 × Ir for 1 s *)

Burden < 150 mVA at Ir = 5 A


< 20 mVA at Ir = 1 A

Ac voltage Ur = 110 V 0.5–288 V

Operative range (0–340) V

Permissive overload 420 V cont.


450 V 10 s

Burden < 20 mVA at 110 V

Frequency fr = 50/60 Hz ±5%

*) max. 350 A for 1 s when COMBITEST test switch is included.

Table 16. MIM - mA input module

Quantity: Rated value: Nominal range:

Input resistance Rin = 194 Ohm -

Input range ±5, ±10, ±20mA -


0-5, 0-10, 0-20, 4-20mA

Power consumption -
each mA-board £2W
each mA input £ 0.1 W

ABB 39