Data Sheet Series 2600T Pressure Transmitters

SS/267JS/269JS
Model 267JS/269JS Multivariable
for differential and absolute pressure and temperature
selectable maximum working pressure
up to 41 MPa, 5945 psi

■ Base accuracy: ± 0.075 %/± 0.04 %

■ Multi-sensor high-performance transmitter


for measuring differential pressure,
absolute pressure and process temperature
in a single unit

■ One transmitter replaces three separate


transmitters: less cabling expense, fewer valve
blocks, thus reducing installation costs

■ Reduced process penetrations


– saves money and reduces the chance of leaks

■ Highest level of communication flexibility:


– Selectable HART, PROFIBUS, FOUNDATION
Fieldbus or Modbus

■ Optimal flexibility during process adaptations


to span limits
– 0.05 to 10000 kPa; 0.2 in H20 to 1450 psi for
differential pressure
– 0.6 to 41 MPa; 87 to 5945 psia absolute pressure

■ 5-year stability
®
P R O F I
PROCESS FIELD BUS

■ Compliance with pressure device directive, B U S


PED category III

ABB 2600T Series


Engineered solutions for all
applications
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Introduction
This intelligent multivariable transmitter provides the user with The reduced number of devices per application increases system
precise measurements of differential pressure, absolute pressure availability while reducing the likelihood of an expensive
and process temperature (the latter using an externally-mounted shutdown.
Pt 100 resistance thermometer).
The user may select between either the 4 to 20 mA output or
digital outputs such as HART, PROFIBUS PA, FOUNDATION
Fieldbus or Modbus for data transfer.

Functional Specifications
Measuring range and span limits Span limits

Differential pressure sensors Maximum span = URL = upper range limit


(can be adjusted up to ± URL within the measurement span.
Upper range Lower range Example: -400 to +400 mbar)
Sensor code Minimum span
limit (URL) limit (LRL) In order to optimize performance characteristics, it is recommended
1 kPa -1 kPa 0.05 kPa to select the transmitter sensor providing the lowest turndown ratio.
A 10 mbar -10 mbar 0.5 mbar Zero suppression and elevation
4 in H2O -4 in H2O 0.2 in H2O
Zero and span can be set to any value within the range limits listed in
6 kPa -6 kPa 0.2 kPa the table, if:
C 60 mbar -60 mbar 2 mbar – Calibrated span ≥ minimum span
24 in H2O -24 in H2O 0.8 in H2O
Process temperature range
40 kPa -40 kPa 0.4 kPa
F 400 mbar -400 mbar 4 mbar -50 °C to +650 °C (-58 °F to 1200 °F) with external four-wire RTD.
160 in H2O -160 in H2O 1.6 in H2O Damping
250 kPa -250 kPa 2.5 kPa Adjustable time constant: 0 to 60 sec
L 2500 mbar -2500 mbar 25 mbar This is in addition to sensor response time.
1000 in H2O -1000 in H2O 10 in H2O
Warm-up period
2000 kPa -2000 kPa 20 kPa
N 20 bar -20 bar 0.2 bar Operation within specifications: ≤ 2.5 sec with minimal damping
290 psi -290 psi 2.9 psi
Insulation resistance
10000 kPa -10000 kPa 100 kPa > 100 MΩ at 1000 V DC (between terminals and ground)
R 100 bar -100 bar 1 bar
1450 psi -1450 psi 14.5 psi

Absolute pressure sensors


Upper range Lower range
Sensor code Minimum span
limit (URL) limit (LRL)
600 kPa 6 kPa
1 6 bar 0 abs 0.06 bar
87 psi 0.87 psi
2000 kPa 20 kPa
2 20 bar 0 abs 0.2 bar
290 psi 2.9 psi
10000 kPa 100 kPa
3 100 bar 0 abs 1 bar
1450 psi 14.5 psi
41000 kPa 410 kPa
4 410 bar 0 abs 4.1 bar
5945 psi 59.5 psi

2
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Operating limits Environmental limits


Electromagnetic compatibility (EMC)
Temperature limits °C (°F):
Definition Class 3
Ambient (operating temperature) RFI suppression Limit Class B
(according to EN 550011)
Transmitter: -40 °C to +85 °C (-40 °F and +185 °F)
Meets NAMUR recommendations
LCD display: -20 °C to +70 °C (-4 °F and +158 °F)
Lower limit for Viton and Low voltage directive:
PTFE gaskets: -20 °C (-4 °F)
Meets 73/23/EC
Note: Pressure equipment directive (PED)
For hazardous atmosphere applications, see the temperature range
Instruments with maximum working pressure 41 MPa, 410 bar,
specified on the relevant certificate/approval.
5945 psi comply with 97/23/EC Category III module H.
Process
Humidity
Lower limit
Relative humidity: up to 100 %
– Refer to the lower ambient temperature limits
Condensation, icing: permitted
Upper limit:
– Silicone oil: 120 °C (248 °F) for operating pressures Vibration resistance
≥ 10 kPa abs, 100 mbar abs, 1.45 psia (1) Acceleration up to 2 g at frequencies up to 1000 Hz
– Carbon fluoride: 120 °C (248 °F) (2) (according to 60068-2-26)
for operating pressures ≥ atmospheric pressure
Shock resistance (according to IEC 60068-2-27)
(1) 85 °C (185 °F) for applications below 10 kPa abs, 100 mbar abs, Acceleration: 50 g
1.45 psia to 3.5 kPa abs, 35 mbar abs, 0.5 psia Duration: 11 ms
(2) 85 °C (185 °F) for applications below atmospheric pressure up to
40 kPa abs, 400 mbar abs, 5.8 psia Wet and dust-laden atmospheres (protection type)
The transmitter is dust and sand-tight and protected against
Storage immersion effects as defined by IEC EN60529 (1989) to IP 67 (IP 68
Lower limit: -50 °C (-58 °F), -40 °C (-40 °F) for LCD displays on request) or by NEMA to 4X or by JIS C0920.
Upper limit: +85 °C (+185 °F) Protection type with plugged connection: IP 65

Pressure limits
Hazardous atmospheres
Overpressure limits (without damage to the transmitter)
Transmitters with protection type "Intrinsically safe EEx ia"
Lower limit
– 0.5 kPa abs, 5 mbar abs, 0.07 psia for silicone oil according to Directive 94/9/EC (ATEX)
– 40 kPa abs, 400 mbar abs, 5.8 psia for carbon fluoride For applications in explosive areas, the connected RTD must also
have the respective Ex protection class as the transmitter.
Upper limit:
– 0.6 MPa, 6 bar, 87 psi for differential pressure sensor code A
Transmitters with 4 to 20 mA output signal and HART communication
– 2 MPa, 20 bar, 290 psi or 10 MPa, 100 bar, 1450 psi or 41 MPa,
Identification: II 1/2 GD T 50 °C EEx ia IIC T6
410 bar, 5945 psi depending upon the selected code variant for
II 1/2 GD T 95 °C EEx ia IIC T4
sensor code C, F, L, N, R
Power supply and signal circuit with protection type Intrinsic Safety
Static pressure
EEx ib IIB/IIC or EEx ia IIB/IIC for connection to supply units with
This multivariable transmitter operates within specifications with the maximum values:
following limits: II 1/2 GD T 50°C EEx ia or ib IIC T6
Lower limit II 1/2 GD T 95°C EEx ia or ib IIC T4
– 3.5 kPa abs, 35 mbar abs, 0.5 psia for silicone oil Temperature class T4:
– 40 kPa abs, 400 mbar abs, 5.8 psia for carbon fluoride Ui = 30 V
Upper limit: Ii = 200 mA
– 0.6 MPa, 6 bar, 87 psi for sensor code A Pi = 0.8 W for T4 with Ta = -40 °C to +85 °C (-40 °F to +185 °F)
– 2 MPa, 20 bar, 290 psi or 10 MPa, 100 bar, 1450 psi or 41 MPa, Pi = 1.0 W for T4 where Ta = -40 °C to +70 °C (-40 °F to +158 °F)
410 bar, 5945 psi depending upon the selected code variant for
Temperature class T6:
sensor code C, F, L, N, R
Pi = 0.7 W for T4 where Ta = -40 °C to +40 °C (-40 °F to +104 °F)
Test pressure
Effective internal capacitance: Ci ≤ 10 nF
For pressure testing purposes, the transmitter can withstand a Effective internal inductance: Li ≈ 0
pressure test applied simultaneously from both sides of up to 1.5
times the nominal pressure (static pressure range) of the transmitter.

3
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Fieldbus transmitters (PROFIBUS PA / FOUNDATION Fieldbus) Transmitter of protection type "Intrinsically safe EEx ia"
Identification: II 1/2 GD T 50 °C EEx ia IIC T6 according to Directive 94/9/EC (ATEX), or
II 1/2 GD T 95 °C EEx ia IIC T4
protection type "flameproof enclosure EEx d" according to
Supply and signal circuit in Intrinsic Safety protection type Directive 94/9/EC (ATEX), or
EEx ia IIB/IIC or EEx ib IIB/IIC for connection to FISCO supply units
with rectangular or trapezoidal characteristics with maximum values: protection type "Limited energy equipment EEx nL" according to
II 1/2 GD T 50 °C EEx ia or ib IIC T6 Ui = 17.5 V Directive 94/9/EC (ATEX) (alternate certification)
II 1/2 GD T 95 °C EEx ia or ib IIC T4 Ii = 360 mA Transmitters with 4 to 20 mA output signal and HART communication
Pi = 2.52 W Identification: II 1/2 GD T50 °C EEx ia IIC T6
II 1/2 GD T95 °C EEx ia IIC T4;
II 1/2 GD T 50 °C EEx ia or ib IIB T6 Ui = 17.5 V (refer to "EEx ia" for additional data)
II 1/2 GD T 95 °C EEx ia or ib IIB T4 Ii = 380 mA or
Pi = 5.32 W
Identification: II 1/2 GD T85 °C EEx d IIC T6
or connection to supply units or barriers with linear characteristics:
Maximum values: Ambient temperature range:
II 1/2 GD T 50 °C EEx ia or ib IIC T6 Ui = 24 V -40 °C to +75 °C (-40 °F to +167 °F)
II 1/2 GD T 95 °C EEx ia or ib IIC T4 Ii = 250 mA or
Pi = 1.2 W
Identification: II 3 GD T 50 °C EEx nL IIC T6
Effective internal capacitance: Ci ≈ 0 II 3 GD T95 °C EEx nL IIC T4
Effective internal inductance: Li ≤ 10 μH, (refer to "EEx nL" for additional data)

Maximum permissible ambient temperatures depending on the Factory Mutual (FM)


temperature class: Transmitters with 4 to 20 mA output signal and HART communication
T4: -40 °C to +85 °C (-40 °F to +185 °F) Intrinsically Safe: Class I; Division 1; Group A, B, C, D;
T5, T6: -40 °C to +40 °C (-40 °F to +104 °F) Class I; Zone 0; Group IIC; AEx ia IIC
Protection type: NEMA type 4X (interior or exterior)
Transmitter of category 3 for the application in "Zone 2"
Maximum permissible ambient temperatures depending on the
according to Directive 94/9/EC (ATEX)
temperature class:
Transmitters with 4 to 20 mA output signal and HART communication
Identification: II 3 GD T 50 °C EEx nL IIC T6 Umax = 30 V, Ci = 10.5 nF, Li = 10 μH
II 3 GD T 95 °C EEx nL IIC T4 Ambient temperature Temperature Imax Pi
class
Operating conditions:
-40 °C to +85 °C (-40 °F to +185 °F) 0.8 W
Supply and signal circuit (terminal signal +/-): T4 200 mA
U ≤ 45 V -40 °C to +70 °C (-40 °F to +158 °F) 1W
I ≤ 22.5 mA
T5 0.75 W
Ambient temperature range: -40 °C to +40 °C (-40 °F to +104 °F) 25 mA
Temperat. class T4 and T6 Ta = -40 °C to +85 °C (-40 °F to +185 °F) T6 0.5 W
Temperat. class T5 and T6 Ta = -40 °C to +40 °C (-40 °F to +104 °F)
Fieldbus transmitters
(PROFIBUS PA / FOUNDATION Fieldbus)
Transmitter of protection type "flameproof enclosure EEx d"
Intrinsically Safe:
according to Directive 94/9/EC (ATEX) Class I, II, and III; Division 1; Group A, B, C, D, E, F, G
Transmitter with 4 to 20 mA output signal and HART communication Class I; Zone 0; AEx ia Group IIC T6, T4;
and Fieldbus transmitter (PROFIBUS PA/FOUNDATION Fieldbus) Non-incendive Class I, II, and III; Division 2; Group A, B, C, D, F, G

Identification: II 1/2 G EEx d IIC T6 Transmitters with 4 to 20 mA output signal and HART communication
and Fieldbus transmitter
Operating conditions: (PROFIBUS PA / FOUNDATION Fieldbus)
Ambient temperature range: -40 °C to +75 °C (-40 °F to +167 °F) Explosion-Proof: Class I; Division 1, Group A, B, C, D
Class II/III, Division 1, Group E, F, G
Degree of protection: NEMA Type 4X (indoor or outdoor)

Canadian standard (CSA)


Transmitters with 4 to 20 mA output signal and HART communication
and Fieldbus transmitter
(PROFIBUS PA / FOUNDATION Fieldbus)
Explosion-Proof: Class I; Division 1; Group B, C, D
Class II/III; Division 1; Group E, F, G
Degree of protection: NEMA Type 4X (indoor or outdoor)

4
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Standards Association of Australia (SAA) Electrical Data and Options


Transmitters of protection type "Intrinsically safe Ex ia" and
"Non-sparking material" Ex n HART digital communication and 4 to 20 mA output
Transmitters with 4 to 20 mA output signal and HART communication Power supply
Identification:
The transmitter operates from 10.5 to 45 V DC with no load and is
Ex ia IIC T4 (Pi 0.8 W Ta = 85 °C) / T6 (Pi 0.7 W Ta = 40 °C)
protected against reverse polarity connection (additional load allows
Ex n IIC T4 (Ta = 85 °C / T6 (Ta = 40 °C)
operations over 45 V DC).
IP 66
Minimum power supply is 14 V DC with backlit display.
For EEx ia and other intrinsically safe approval power supply must not
Intrinsically safe installation input parameters:
exceed 30 V DC.
Ui = 30 V
Ii = 200 mA Ripple
Pi = 0.8 W for T4 where Ta = +85 °C (+185 °F) or
Maximum permissible voltage ripple of power supply during
Pi = 0.7 W for T4 where Ta = +40 °C (+104 °F)
communication:
7 Vss at f = 50 to 100 Hz
Effective internal capacitance: Ci = 52 nF
1 Vss at f = 100 to 200 Hz
Effective internal inductance: Li ≈ 0 mH
0.2 Vss at f = 200 to 300 Hz
Ex n installation input parameters: Load limitations
Ui = 30 V
Total loop resistance at 4 to 20 mA and HART:
Supplyvoltage – minimumoperatingvoltage (V DC)
R ( kΩ ) = ---------------------------------------------------------------------------------------------------------------------------------------------------
Transmitter with protection type "flameproof enclosure Ex d"
22.5 mA
Transmitter with 4 to 20 mA output signal and HART communication
and Fieldbus transmitter (PROFIBUS PA/FOUNDATION Fieldbus, A minimum of 250 Ω is required for HART communication.
Modbus) LCD display (optional)
Identification:
Zone 1: Ex d IIC T6 (Tamb +75 °C) IP66/IP67 19-segment alphanumeric display (2-line, 6-character ) with
Zone A21: Ex tD A21 T85 (Tamb +75 °C) IP66/IP67 additional bar chart display, optionally with back illumination.
User-specific display:
Output current in percent or
Output current in mA or
Freely-selectable process variable
Diagnostic messages, alarms, measuring range infringements and
changes to the configuration are also displayed.
Output signal
Two-wire 4 to 20 mA related to differential pressure
HART® communication provides digital process variables (%, mA or
engineering units), absolute pressure and process temperature
(engineering unit) superimposed on the 4 to 20 mA signal.
Output current limits (according to NAMUR standard)
Overload condition
– Lower limit: 3.8 mA (configurable down to 3.5 mA)
– Upper limit: 20.5 mA (configurable up to 22.5 mA)
Alarm current
Minimum alarm current: configurable from 3.5 to 4 mA
Standard setting: 3.6 mA
Maximum alarm current: configurable from 20 to 22.5 mA
Standard setting: 21 mA
Standard setting: maximum alarm current
SIL: Functional safety (optional) according to IEC 61508/61511
Device with certificate of conformity for use in safety-relevant
applications, including SIL 2.

5
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

PROFIBUS PA output FOUNDATION Fieldbus output


Type of appliance Power supply
Pressure transmitter in conformance with Profile 3.0, Class A and B; The transmitter is driven with 10.2 to 32 V DC (no polarity).
ID number 04C2 HEX The power supply must not exceed 17.5 V DC when used in EEx ia
zones.
Power supply Intrinsic safety installation according to FISCO model.
The transmitter is driven with 10.2 to 32 V DC (no polarity).
The power supply must not exceed 17.5 V DC when used in EEx ia Current consumption
zones. Operating (quiescent): 11.7 mA
Intrinsic safety installation according to FISCO model. Fault current limiting: 17.3 mA max.
Current consumption Output signal
Operating (quiescent): 11.7 mA Physical layer in compliance with IEC 1158-2/EN 61158-2 with
Fault current limiting: 17.3 mA max. transmission to Manchester II modulation, at 31.25 kbit/sec.
Output signal Function blocks/execution time
Physical layer in compliance with IEC 1158-2/EN 61158-2 with 3 standard analog input function blocks (each 80 ms)
transmission to Manchester II modulation, at 31.25 kbit/sec. 1 standard PID function block (100 ms)
Output interface Additional blocks
PROFIBUS PA communication according to PROFIBUS DP50170 1 custom pressure with calibration transducer block
Part 2/DIN 19245 Part 1-3 1 standard resource block
1 custom temperature with calibration transducer block
Output cycle time
40 ms Number of link objects
10
Function blocks
3 standard analog input function blocks, Number of VCRs
2 transducer blocks 16
1 physical block
Output interface
LCD display (optional) FOUNDATION Fieldbus digital communication protocol to standard
19-segment alphanumeric display (2-line, 6-character ) with H1, compliant with specification V. 1.5
additional bar chart display, optionally with back illumination.
User-specific display: LCD display (optional)
Output value in percent or 19-segment alphanumeric display (2-line, 6-character ) with
OUT (analog input) additional bar chart display, optionally with back illumination.
Diagnostic messages, alarms, measuring range infringements and User-specific display:
changes to the configuration are also displayed. Output value in percent or
OUT (analog input)
Transmitter failure mode Diagnostic messages, alarms, measuring range infringements and
Permanent self-diagnostic; possible errors indicated in diagnostic changes to the configuration are also displayed.
parameters and in the status of process values.
Transmitter interference mode
Permanent self-diagnostic; possible errors indicated in diagnostic
parameters and in the status of process values.

6
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Measuring accuracy Operating influences


Reference conditions according to IEC 60770 apply: ambient Ambient temperature
temperature of 20 °C (68 °F), relative humidity of 65 %, atmospheric (turndown to 15:1)
pressure of 1013 hPa (1013 mbar), mounting position with vertical Per 20 K change between the limits of
diaphragm and zero-based range for transmitter with isolating -20 °C to +65 °C (-4 °F to +149 °F)
diaphragms in Hastelloy and silicone oil fill. Measurement range with
HART digital trim values equal to 4 to 20 mA span end points and Differential pressure sensor
linear characteristic. 267JS
Unless otherwise specified, errors are quoted as % of ± (0.04 % URL + 0.065 % span)
span.
269JS
The accuracy related to the Upper Range Limits (URL) is affected by ± (0.03 % URL + 0.05 % span)
the actual turndown (TD) as a ratio between Upper Range Limit (URL)
and calibrated span (URL/span). Absolute pressure sensor
± (0.08 % URL + 0.08 % span)
In order to optimize performance characteristics, it is recommended Limited to ± (0.1 % URL + 0.1 % span) per the complete temperature
to select the transmitter sensor providing the lowest turndown ratio. range of 120 K (216 °F)

Dynamic behavior (according to IEC 61298-1) Static pressure


Devices with standard configuration and turndown to (zero errors can be calibrated out at operating pressure)
30:1 and linear output characteristic
Dead time: 30 ms Meas. Sensor A Sensor Sensor R
Time constant (63.2 % of total step change): range C, F, L, N
– Sensors F to R: 150 ms to 2 bar: to 100 bar: to 100 bar:
– Sensor C: 400 ms 0.05 % URL 0.05 % URL 0.1 % URL
– Sensor A: 1000 ms On zero
> 2 bar: > 100 bar: > 100 bar:
0.05 % URL/bar 0.05 % URL/100 bar 0.1 % URL/100 bar
Accuracy rating
to 2 bar: to 100 bar: to 100 bar:
Percentage of calibrated span including combined effects of linearity, 0.05 % span 0.05 % span 0.1 % span
hysteresis and reproducibility. On span > 2 bar:
For Fieldbus versions SPAN refers to analog input function block > 100 bar: > 100 bar:
0.05 % span/bar 0.05 % span/ 0.1 % span/
outscale range. 100 bar 100 bar
Differential pressure sensor Power supply
267JS
Within the specified limits for the voltage/load the total influence is less
– ± 0.075 % for turndown from 1:1 to 10:1
than 0.001 % per volt.
– ± ⎛ 0.075 % + 0.005 × ------------ – 0.05⎞ % At turndown > 10:1
URL
⎝ ⎠ Load
Span
Within the specified load/voltage limits, the total effect is negligible.
269JS
Electromagnetic fields
– ± 0.04 % for turndown from 1:1 to 10:1
Total effect: less than 0.05 % of span from 80 to 1000 MHz and for
– ± ⎛ 0.04 % + 0.005 × -----------
URL
- – 0.05⎞ % At turndown > 10:1 field strengths up to 10 V/m when tested with unshielded conduit,
⎝ Span ⎠ with or without meter.
Common-mode interference
Absolute pressure sensor
– 0.1 % URL for absolute pressure sensor No effect from 250 Veff (50 Hz) or 50 V DC
Installation position
Process temperature measurement (Pt 100)
– ± 0.3 °C (0.54 °F) Rotations in the plane of the transmitter diaphragm have negligible
effect. A tilt from vertical causes a zero shift of sin α x 0.35kPa
(3.5 mbar, 1.4 in H2O) of URL which can be corrected with the zero
adjustment. No effect on the span.
Stability
± 0.15 % of URL over a sixty-month period
Vibration effect
± 0.10 % of URL (according to IEC 61298–3)

7
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Technical Specification Optional accessories


(Refer to ordering information sheets for variant availability related to the Mounting bracket
specific model) For vertical and horizontal 60 mm (2 in) pipes or wall mounting
LCD display
Materials
Plug-in and rotatable
Process isolating diaphragms1)
Additional tag plate
Hastelloy C276™ stainless steel (1.4435); Monel 400™,
Tantalum Tag with wire (both stainless steel) attached to the transmitter, with a
maximum of 30 characters including spaces.
Process flange, adapter, plugs and drain/vent valves1)
Cleanliness level for oxygen application
Hastelloy C276™ stainless steel (1.4404); Monel 400™, Kynar (PVDF)
Preparation for hydrogen application
Sensor fill fluid
Silicone oil, inert fill (carbon fluoride) Certificates (test, model, calibration, material traceability)
Sensor housing
Stainless steel
Process connections
Flange: ¼-18 NPT on the process axis, selectable with fixing threads
Mounting bracket 7/16-20 UNF or DIN 19213 connection with M10 threading for
Stainless steel operating pressures up to 10 MPa, 100 bar, 1450 psi or M12
threading for higher operating pressures up to 41 MPa, 410 bar,
Gaskets1) 5945 psi
Viton™ (FPM), Perbunan (NBR), EPDM, PTFE (for sensor C, F, L, N, Adapter: ½-14 NPT on process axis
R) or FEP coated Viton™ (for sensor A) Center distance between flanges: 54 mm (2.13 in);
51, 54 or 57 mm (2.01, 2.13 or 2.24 in) as per adapter fittings
Bolts and nuts
Stainless steel, bolts and nuts Class A4-70 according to ISO 3506, Electrical connections
conforming to NACE MR0175 Class II
Two ½-14 NPT or M20 x 1.5 threaded bores for cable glands, direct
Electronics housing and cover on housing
Barrel version or plug connector
– Aluminum alloy with low copper content, baked epoxy finish – HART: straight or angle Harting Han 8D (8U) connector and one
– Stainless steel mating plug
– FOUNDATION-Fieldbus/PROFIBUS PA; plug 7/8 in / M12 x 1
DIN version
Terminal blocks
– Aluminum alloy with low copper content, baked epoxy finish
HART version: four terminals for signal/external display, for wiring up
Covers O-ring to 2.5 mm² (14 AWG) and four connection points for test and
Viton™ communication purposes.
Fieldbus versions: two signal terminals (bus connector) for wiring up
Local zero and span adjustments: to 2.5 mm² (14 AWG)
Fiberglass-reinforced polycarbonate plastic (removable), no local
control keys for stainless steel housings. Ground
Internal and external 4 mm² (12 AWG) ground termination points are
Type plate provided.
Stainless steel (316) or plastic data plate attached to the electronics
housing Installation position
The transmitter can be mounted in any position.
Calibration The electronics housing may be rotated 360°. A positive stop
Standard: at maximum span, zero-based range, ambient prevents over-travel.
temperature and pressure
Optional: at specified range and ambient conditions Weight (without options)
Approximately 3.5 kg (8lb), add 1.5 kg ( 3.4lb) for stainless steel
housing. Packaging adds 650 g

Packaging
™ Hastelloy is a Cabot Corporation trademark
™ Monel is an International Nickel Co. trademark Carton approx. 230 x 250 x 270 mm (9 x 10 x 11 in)
™ Viton is a DuPont de Nemours trademark

1) Wetted transmitter parts

8
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Configuration Transmitter with FOUNDATION Fieldbus


communication
Transmitter with HART communication and 4 to Transmitters are factory calibrated to the customer's specified range.
20 mA output current Calibrated range and measuring point number are stamped on the
type plate. If this data has not been specified, the transmitter will be
Standard configuration delivered configured as follows:
Transmitters are factory calibrated to the customer's specified range. Measure profile Pressure
Calibrated range and measuring point number are stamped on the
type plate. If this data has not been specified, the transmitter will be Engineering unit mbar/bar
delivered configured as follows: Output scale 0 % Lower range limit (LRL)
4 mA Zero point
Output scale 100 % Upper range limit (URL)
20 mA Upper range limit (URL)
Output linear
Output linear
Upper alarm limit Upper range limit (URL)
Damping 0.125 sec
Upper warning limit Upper range limit (URL)
Transmitter failure mode 21 mA
Lower warning limit Lower range limit (LRL)
Optional LCD display 0 to 100 % linear
Lower alarm limit Lower range limit (LRL)
Any or all the above configurable parameters, including lower range
Limit hysteresis 0.5 % of output scale
value and upper range value can be easily changed by a PC, running
the configuration software SMART VISION with DTM for 2600T. Data PV filter 0.125 sec
regarding flange type and material, O-rings and filling liquid is stored
in the device. Address not required
Any or all the above configurable parameters, including lower range
value and upper range-value can be changed by any FOUNDATION
Transmitter with PROFIBUS PA communication Fieldbus-compatible configurator. Data regarding flange type and
Transmitters are factory calibrated to the customer's specified range. material, O-rings and filling liquid is stored in the device.
Calibrated range and measuring point number are stamped on the
type plate. If this data has not been specified, the transmitter will be
delivered configured as follows:
Measure profile Pressure
Engineering unit mbar/bar
Output scale 0 % Lower range limit (LRL)
Output scale 100 % Upper range limit (URL)
Output linear
Upper alarm limit Upper range limit (URL)
Upper warning limit Upper range limit (URL)
Lower warning limit Lower range limit (LRL)
Lower alarm limit Lower range limit (LRL)
Limit hysteresis 0.5 % of output scale
PV filter 0.125 sec
Address 126
Any or all the above configurable parameters, including lower range
value and upper range value can be easily changed by a PC, running
the configuration software SMART VISION with DTM for 2600T. Data
regarding flange type and material, O-rings and filling liquid is stored
in the device.

9
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Mounting Dimensions (not design data)

Transmitter with barrel housing


Deviations in the drawing are possible. Measurements in mm (inches)

Space must be available to


rotate the keyboard cover

70 (2.76)
114 (4.49) 23 (0.91) LCD display

9 (0.35) 58 (2.28) 20 (0.79)


Terminal side Clearance for
cover removal
required

(1.02)
26
Tag
e.g., for indicating
measuring points
(optional)
Housing rotating
186 (7.32)
108 (4.25)
Threaded bore
stop-screw (optional) ¼-18 NPT
Drain/vent valve
(optional) for drain/vent valve

Transducer

61 (2.40)
(1.63)

plate
41.3

(1.18)

-+
30

Process
connection
54 (2.13) Threads for fixing screws 90 (3.54)
(see process flange data)
96 (3.78)
71 (2.80)

Electrical connection Plate with key


legend

Type plate
∅ 83 (3.27)

140 (5.51)

Housing cover

Pt 100 connection Captive screw for


keyboard cover

15_0085x1

10
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Transmitter with DIN housing

Pt 100 connection

70 (2.76)

140 (5.51)
83 (3.27)
Space must be available
to rotate the keyboard
cover 43
(1.69)
Electrical connection
Additional tag plate, e.g., for
indicating measuring points Housing rotating
stop-screw Captive screw for
(optional) keyboard cover
61 (2.40)

Plate with key


legend
90 (3.54)

96 (3.78) 20 (0.79)
107 (4.21)
54 (2.13)
Transducer plate 138 (5.43)
168 (6.61) 23 (0.91)
Process LCD display
connection
(1.63)
41.3

Threads for fixing


screws (see
process flange
data) Terminal side

Type plate
Electrical connection

Housing cover 15_0086x1


27 (1.06) 48 (1.89)
20 (0.79)
139 (5.47) Clearance for
cover removal
required

11
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Mounting options with bracket


Deviations in the drawing are possible. Measurements in mm (inches)

∅ 11 (0.43)

∅ 10 (0.4)

72 (2.83)
60(2.36) 135.5 (5.33)
72 (2.83)

57(2.24)
72 (2.83)

136 (5.35)
56(2.20) 110 (4.33)

214 (8.43)
M01517x1

Vertical pipe mounting Horizontal pipe mounting Vertical pipe mounting and Horizontal pipe mounting and
transmitter above the mounting transmitter above the
bracket mounting bracket

M01520x1 M01521x1

M01518x1 M01519x1

12
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Electrical connections

Standard terminal block

Grounding/potential
Test sockets for 4 to 20 mA equalizing terminal Output signal/power supply Fieldbus plug connector
(not with Fieldbus
transmitters) 7/8 in connector
1 3

Cable Pt 100 cable entry


entry 2 4

M12 x 1 connector
14 12 Screw terminals for leads with 0.5 to 2
13 TEST 11 2.5 mm² cross-section
SIGNAL
- + - +
3 1

4 15_0066x1

Pin (male) assignment


Number FOUNDATION PROFIBUS PA
Fieldbus
1 FF- PA+
2 FF+ Ground
3 Shield PA-
4 Ground Shield

Mating plug (socket) not supplied


M01450x1

Harting Han 8D (8U) connector

DIN housing Barrel housing

1 2

- +
Harting Han 8D (8U) pin assignment
(socket view)

15_0079x1

13
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Ordering Information
Multivariable transmitter Variant digit No. 1- 6 7 8 9 10 11 Code
for differential & absolute pressure / temperature
267JS Base accuracy: 0.075 % Catalog No. 267JS-
269JS Base accuracy: 0.04 % Catalog No. 269JS-
Sensor - Span limits
0.05 ... 1 kPa 0.5 ... 10 mbar 0.2 ... 4 in H2O A
0.2 ... 6 kPa 2 ... 60 mbar 0.8 ... 24 in H2O C
0.4 ... 40 kPa 4 ... 400 mbar 1.6 ... 160 in H2O F
2.5 ... 250 kPa 25 ... 2500 mbar 10 ... 1000 in H2O L
20 ... 2000 kPa 0.2 ... 20 bar 2.9 ... 290 psi N
100 ... 10000 kPa 1 ... 100 bar 14.5 ... 1450 psi R
Static pressure
0 ... 0.6 MPa 0 ... 6 bar 0 ... 87 psi 1) 1
0 ... 2 MPa 0 ... 20 bar 0 ... 290 psi 2) 2
0 ... 10 MPa 0 ... 100 bar 0 ... 1450 psi 3) 3
0 ... 41 MPa 0 ... 410 bar 0 ... 5945 psi 3) 4
Diaphragm material / Fill fluid (wetted parts)
AISI 316L ss Silicone oil NACE S
Hastelloy C276 Silicone oil NACE K
Monel 400 Silicone oil NACE M
Monel 400 gold plated Silicone oil NACE V
Tantalum Silicone oil NACE T
AISI 316L ss Inert fluid NACE 4) A
Hastelloy C276 Inert fluid NACE 4) F
Monel 400 Inert fluid NACE 4) C
Monel 400 gold plated Inert fluid NACE 4) Y
Tantalum Inert fluid NACE 4) D
Process connection material / Process connection (wetted)
AISI 316L ss (horizontal) 1/4-18 NPT-f direct NACE A
(7/16-20 UNF U.S. thread)
AISI 316L ss (horizontal) 1/4-18 NPT-f direct (DIN 19213) NACE C
AISI 316L ss (horizontal) 1/2-14 NPT-f through adapter NACE B
(7/16-20 UNF U.S. thread)
Hastelloy C276 (horizontal) 1/4-18 NPT-f direct NACE D
(7/16-20 UNF U.S. thread)
Hastelloy C276 (horizontal) 1/4-18 NPT-f direct (DIN 19213) NACE F
Hastelloy C276 (horizontal) 1/2-14 NPT-f through adapter NACE E
(7/16-20 UNF U.S. thread)
Monel 400 (horizontal) 1/4-18 NPT-f direct NACE G
(7/16-20 UNF U.S. thread)
Monel 400 (horizontal) 1/4-18 NPT-f direct (DIN 19213) NACE L
Monel 400 (horizontal) 1/2-14 NPT-f through adapter NACE H
(7/16-20 UNF U.S. thread)
Kynar (PVDF) (MWP 1 MPa) (lateral / axial) 1/4-18 NPT-f direct P
(7/16-20 UNF U.S. thread)
Bolts / Gaskets (wetted)
AISI 316L ss Viton NACE 4) 3
AISI 316L ss PTFE (max. 10 MPa) NACE 4
AISI 316L ss EPDM NACE 5
AISI 316L ss Perbunan 6

1) Not available with Sensor - Span limits code C, F, L, N, R Continued on next page
2) Not available with Sensor - Span limits code A, R
3) Not available with Sensor - Span limits code A
4) Suitable for oxygen applications

14
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Ordering Information, continued


Multivariable transmitter Variant digit No. 1- 6 9 10 11 12 13 Code
for differential & absolute pressure / temperature
267JS Base accuracy: 0.075 % Catalog No. 267JS-
269JS Base accuracy: 0.04 % Catalog No. 269JS-
Electronic housing
material Electrical connection
Aluminium alloy (Barrel version) 1/2-14 NPT A
Aluminium alloy (Barrel version) M20 x 1.5 (N/A: FM, CSA) B
Aluminium alloy (Barrel version) Harting Han connector (N/A: EExnL, EExd, FM, CSA) 5) E
Aluminium alloy (Barrel version) Fieldbus connector (N/A: EExnL, EExd, FM, CSA) 5) G
AISI 316L ss (Barrel version) 1/2-14 NPT S
AISI 316L ss (Barrel version) M20 x 1.5 (N/A: FM, CSA) T
Aluminium alloy (DIN version) M20 x 1.5 (N/A: FM, CSA) J
Aluminium alloy (DIN version) Harting Han connector (N/A: EExnL, EExd, FM, CSA) 5) K
Aluminium alloy (DIN version) Fieldbus connector (N/A: ATEX EExd, FM, CSA) 5) W
Output Additional options
HART digital communication and 4 ... 20 mA No additional options 6) 7) H
HART digital communication and 4 ... 20 mA Options requested 6) 1
(to be ordered by Additional ordering code)
PROFIBUS PA No additional options 6) 7) P
PROFIBUS PA Options requested 7) 2
(to be ordered by Additional ordering code)
FOUNDATION Fieldbus No additional options 6) 7) F
FOUNDATION Fieldbus Options requested 7) 3
(to be ordered by Additional ordering code)

Additional ordering information


267JS , 269JS Code
Vent valve material / Position (wetted parts)
AISI 316L ss On process axis NACE 8) V1
AISI 316L ss On flanges side top NACE 8) V2
AISI 316L ss On flanges side bottom NACE 8) V3
Hastelloy C276 On process axis NACE 9) V4
Hastelloy C276 On flanges side top NACE 9) V5
Hastelloy C276 On flanges side bottom NACE 9) V6
Monel 400 On process axis NACE 10) V7
Monel 400 On flanges side top NACE 10) V8
Monel 400 On flanges side bottom NACE 10) V9
N/A - Not available with
Continued on next page
5) Select connector type with additional ordering code
6) Not available with Electronic housing material / Electrical connection code G, W
7) Not available with Electronic housing material / Electrical connection code E, K
8) Not available with Process connection material / Process connection code D, E, F, G, H, L, P
9) Not available with Process connection material / Process connection code A, B, C, G, H, L, P
10) Not available with Process connection material / Process connection code A, B, C, D, E, F, P

15
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Additional ordering information


267JS , 269JS Code
Explosion protection
ATEX Group II Category 1/2 GD - Intrinsic Safety EEx ia E1
ATEX Group II Category 1/2 G - Flameproof EEx d E2
ATEX Group II Category 3 GD - Type of protection N EEx nL energy limited E3
ATEX II 1/2 GD, EEx ia + ATEX II 1/2 GD EEx d + ATEX EEx nL EW
Factory Mutual (FM) - Intrinsically Safe EA
Factory Mutual (FM) - Explosion Proof EB
(only with electrical connection 1/2-14 NPT and Stainless steel Tag plate)
Canadian Standard Association - Intrinsically Safe ED
Canadian Standard Association - Explosion Proof EE
Canadian Standard Association - Explosion Proof (Canada & USA) EM
SAA Ex d IIC T6 and Ex td A21 IP66 T85 °C X1
SAA Ex ia IIC T4/T6 and Ex n IIC T4/T6 (only with output HART / 4 ... 20 mA) X2
Integrated digital display (LCD)
With integrated LCD display L1
With integrated LCD display (backlit) L2
Mounting bracket shape / Material
For pipe mounting AISI 316L ss B2
For wall mounting AISI 316L ss B4
Operating manual
German M1
Label and Tag Language
German (stainless steel) (not with DIN Electronic Housing code J, K, W) T1
German and English (plastic) (not with Factory Mutual - Explosion Proof) TA
Additional tag plate
Stainless steel I1
Applications
Oxygen service cleaning (Pmax = 12 MPa, Tmax = 60 °C) P1
(only available with inert fill and Viton gasket)
Hydrogen application (H2) (fluid film) P2
Certificates
Inspection certificate EN 10204-3.1 B of calibration C1
Inspection certificate EN 10204-3.1 B of the cleanliness stage according to DIN 25410 C3
Inspection certificate EN 10204-3.1 B of helium leakage test of the sensor module C4
Inspection certificate EN 10204-3.1 B of the pressure test C5
Certificate of compliance with the order EN 10204-2.1 of instrument design C6
Material traceability
Certificate of compliance with the order EN 10204-2.1 of process wetted parts H1
Inspection certificate EN 10204-3.1.B for pressure-bearing process wetted parts H3
with analysis certificates as material verification
(minor parts with Factory Certificate acc. to EN 10204)
Test report EN 10204-2.2 of the pressure bearing and process wetted parts H4
Connectors
Fieldbus 7/8 in (without mating plug, recommended for FOUNDATION Fieldbus) 7) 11) U1
Fieldbus M12 x 1 (without mating plug, recommended for PROFIBUS PA) 7) 11) U2
Harting Han 8D (8U) - straight entry 6) 11) U3
Harting Han 8D (8U) - angle entry 6) 12) U4

6) Not available with Electronic housing material / Electrical connection code G, W


7) Not available with Electronic housing material / Electrical connection code E, K
11) Not available with Electronic housing material / Electrical connection code T, S, A, B, J, E
12) Not available with Electronic housing material / Electrical connection code T, S, A, B, J, K

Hastelloy is a trademark of Cabot Corporation


Monel is a trademark of International Nickel Corporation
Viton is a trademark of DuPont Dow Elastomers

16
Series 2600T Pressure Transmitters SS/267JS/269JS
Model 267JS/269JS Multivariable

Standard delivery items (changes possible by an additional ordering code)


– Adapters supplied singly
– Plugs for process axis (no drain/vent valves)
– General purpose (no Ex application)
– No display, no mounting bracket
– English-language manual and labels
– Type plate material: barrel electronics housing code A, B, E, G, S, T – stainless steel
DIN electronics housing code J, K, W – plastic
– Configuration with kPa and °C units
– No test, inspection or material certificates

If not otherwise specified prior to manufacture, the customer shall be responsible for the selection of suitable wetted parts and appropriate fill fluid
to assure compatibility with the relevant process medium.

17
ABB has Sales & Customer Support The Company’s policy is one of continuous product
expertise in over 100 countries worldwide.. improvement and the right is reserved to modify the
information contained herein without notice.
www.abb.com/pressure
Printed in the Fed. Rep. of Germany (06.2006)

© ABB 2006
SS/267JS/269JS

ABB Limited ABB Inc. ABB Automation Products GmbH


Howard Road, St. Neots 125 E. County Line Road Schillerstr. 72
Cambridgeshire, PE19 8EU Warminster, PA 18974 32425 Minden
UK USA Germany
Tel: +44 (0)1480 475321 Tel: +1 215 674 6000 Tel: +49 551 905-534
Fax: +44 (0)1480 217948 Fax: +1 215 674 7183 Fax: +49 551 905-555
[email protected]

You might also like