Automation Portal
Settings
Device settings
Settings Value
Edit mode primary
Number settings groups 1
Activat. of settings group settings group 1
DIGSI 5 uses following IP address 172.16.60.60 (Integrated Ethernet interface)
Operation-panel language English (United States)
Binary input channel threshold Low: 44 V, High: 88 V
Used time stamp in GOOSE subscriptions On message reception
Hide settings in IEC 61850 structure Hide all settings
Hide SIPROTEC extensions in IEC 61850 structure Hide all SIPROTEC extensions
Use dynamic reporting True
Block IEC 61850 settings changes False
Access point used in Edition1 No access point is specified for the SCD import.
General \Device
Number Settings Value
91.101 Rated frequency All: 50 Hz
91.102 Minimum operate time All: 0 s
91.115 Set. format residu. comp. All: Kr, Kx
91.138 Block monitoring dir. All: off
General \Measurements
Number Settings Value
91.162 Blk setting change All: false
91.163 Reserv.time for com.prot. All: 120 s
91.111 Energy restore interval Settings group 1: 10 min
91.112 Energy restore time Settings group 1: none
General \Control
Number Settings Value
91.120 Energy restore Settings group 1: latest value
91.121 Energy restore by A.time All: false
91.118 Enable sw.auth. station All: false
1 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
General \Spontan.indic.
Number Settings Value
91.119 Multiple sw.auth. levels All: false
General \CFC
Number Settings Value
91.152 Specific sw. authorities All: false
Localization
Number Settings Value
6211.139 Unit system All: SI
Time settings
General
Settings Value
Date format All: DD.MM.YYYY
Time source
Settings Value
Fault indication after All: 600 s
Time source 1 none
Time source 2 none
Time zone time source 1 All: local
Time zone time source 2 All: local
Sync. latency time src.1 All: 0 μs
Sync. latency time src.2 All: 0 μs
2 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
VT 1
Number Settings Value
11.941.3811.103 Magnitude correction All: 1
11.941.3811.108 Phase All: V A
VT 2
Number Settings Value
11.941.3812.103 Magnitude correction All: 1
11.941.3812.108 Phase All: V B
VT 3
Number Settings Value
11.941.3813.103 Magnitude correction All: 1
11.941.3813.108 Phase All: V C
Supv. balan. V
Number Settings Value
11.941.2521.1 Mode Settings group 1: on
11.941.2521.101 Release threshold Settings group 1: 250 kV
11.941.2521.102 Threshold min/max Settings group 1: 0.75
11.941.2521.6 Delay supervision alarm Settings group 1: 5 s
Supv. ph.seq.V
Number Settings Value
11.941.2581.1 Mode Settings group 1: on
11.941.2581.6 Delay supervision alarm Settings group 1: 5 s
Supv. sum V
Number Settings Value
11.941.2461.1 Mode Settings group 1: off
11.941.2461.3 Threshold Settings group 1: 125 kV
11.941.2461.6 Delay supervision alarm Settings group 1: 5 s
3 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
VT miniatureCB
Number Settings Value
11.941.2641.101 Response time Settings group 1: 0 s
VT 1
Number Settings Value
11.961.3811.103 Magnitude correction All: 1
11.961.3811.108 Phase All: V B
VT miniatureCB
Number Settings Value
11.961.2641.101 Response time Settings group 1: 0 s
CT 1
Number Settings Value
11.931.3841.103 Magnitude correction All: 1
11.931.3841.117 Phase All: I A
4 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
CT 2
Number Settings Value
11.931.3842.103 Magnitude correction All: 1
11.931.3842.117 Phase All: I B
CT 3
Number Settings Value
11.931.3843.103 Magnitude correction All: 1
11.931.3843.117 Phase All: I C
CT 4
Number Settings Value
11.931.3844.103 Magnitude correction All: 1
11.931.3844.117 Phase All: IN
Brk.wire det.
Number Settings Value
11.931.5581.1 Mode Settings group 1: off
11.931.5581.101 Mode of blocking Settings group 1: blocking
11.931.5581.102 Delta value for autoblock Settings group 1: 1
Supv. balan. I
Number Settings Value
11.931.2491.1 Mode Settings group 1: on
11.931.2491.101 Release threshold Settings group 1: 1000 A
11.931.2491.102 Threshold min/max Settings group 1: 0.5
11.931.2491.6 Delay supervision alarm Settings group 1: 5 s
Supv. ph.seq.I
Number Settings Value
11.931.2551.1 Mode Settings group 1: on
11.931.2551.6 Delay supervision alarm Settings group 1: 5 s
Supv. sum I
Number Settings Value
11.931.2431.1 Mode Settings group 1: on
11.931.2431.102 Threshold Settings group 1: 200 A
11.931.2431.101 Slope factor Settings group 1: 0.1
11.931.2431.6 Delay supervision alarm Settings group 1: 5 s
Supv.ADC sum I
Number Settings Value
11.931.2401.1 Mode Settings group 1: on
5 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Saturat. det.
Number Settings Value
11.931.17731.101 CT saturation threshold Settings group 1: 16000 A
Line 1 \General
General \Rated values
Number Settings Value
21.9001.101 Rated current All: 1923 A
21.9001.102 Rated voltage All: 500 kV
21.9001.103 Rated apparent power All: 1665.4 MVA
General \Measurements
Number Settings Value
21.9001.158 P, Q sign Settings group 1: not reversed
6 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
1pol.open det.
Number Settings Value
21.1131.4711.101 Operating mode Settings group 1: with measurement
Volt.criterion
Number Settings Value
21.1131.4801.101 Threshold U open Settings group 1: 120.00 kV
Line 1 \Mes.v.fail.det
Mes.v.fail.det
Number Settings Value
21.2671.1 Mode Settings group 1: on
21.2671.115 Asym.fail.-DO on netw.flt. Settings group 1: no
21.2671.113 Asym.fail. - time delay Settings group 1: 10 s
21.2671.102 3ph.fail. - phs.curr.release Settings group 1: 100 A
21.2671.103 3ph.fail. - phs.curr. jump Settings group 1: 100 A
21.2671.101 3ph.fail. - VA,VB,VC < Settings group 1: 20 kV
21.2671.107 Switch-on 3ph. failure All: on
21.2671.106 SO 3ph.fail. - time delay Settings group 1: 3 s
Line 1 \85-21Perm.overr.
85-21Perm.over
Number Settings Value
21.1291.5701.1 Mode Settings group 1: on
7 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
8 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Stage 1 \Configuration
Number Settings Value
21.1341.5941.102 50/51 OC-3ph 1p 1.Definite-T 1 false
21.1341.5941.102 50N/51N OC-gnd-A1.Definite-T 1 false
21.1341.5941.102 50 high-speed 1pol 1.Standard 1 true
21.1341.5941.102 67N GFP gnd.sys.1.Definite-T 1 false
21.1341.5941.102 67N GFP gnd.sys.1.Definite-T 2 false
21.1341.5941.102 67N GFP gnd.sys.1.Inverse-T 1 true
21.1341.5941.102 21 Distance prot. 1.Z 1 false
21.1341.5941.102 21 Distance prot. 1.Z 2 false
21.1341.5941.102 21 Distance prot. 1.Z 3 false
21.1341.5941.102 21 Distance prot. 1.Z 4 false
21.1341.5941.102 21 Distance prot. 1.Z 1B true
Definite-T 1 \General
Number Settings Value
21.221.841.1 Mode Settings group 1: on
21.221.841.2 Operate & flt.rec. blocked Settings group 1: no
21.221.841.11 1-pole operate allowed Settings group 1: no
21.221.841.26 Dynamic settings All: no
21.221.841.8 Method of measurement Settings group 1: fundamental comp.
21.221.841.3 Threshold Settings group 1: 2400 A
21.221.841.4 Dropout ratio Settings group 1: 0.95
21.221.841.102 Pickup delay Settings group 1: 0 s
21.221.841.101 Dropout delay Settings group 1: 0 s
21.221.841.6 Operate delay Settings group 1: 60 s
9 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Definite-T 1 \General
Number Settings Value
21.211.751.1 Mode Settings group 1: off
21.211.751.2 Operate & flt.rec. blocked Settings group 1: no
21.211.751.26 Dynamic settings All: no
21.211.751.8 Method of measurement Settings group 1: fundamental comp.
21.211.751.3 Threshold Settings group 1: 1200 A
21.211.751.4 Dropout ratio Settings group 1: 0.95
21.211.751.101 Dropout delay Settings group 1: 0 s
21.211.751.6 Operate delay Settings group 1: 0.3 s
Definite-T 1 \General
Number Settings Value
21.1111.4861.1 Mode Settings group 1: on
21.1111.4861.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4861.114 Directional mode Settings group 1: forward
21.1111.4861.11 1-pole operate allowed Settings group 1: no
21.1111.4861.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4861.130 Blocking by prot. pickup Settings group 1: every pickup
21.1111.4861.129 Op.mode at 1p dead time Settings group 1: blocked
10 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Definite-T 1 \Blocking by
Number Settings Value
21.1111.4861.140 87 Line diff. prot..Group indicat. true
21.1111.4861.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4861.140 21 Distance prot. 1.Z 1 false
21.1111.4861.140 21 Distance prot. 1.Z 2 false
21.1111.4861.140 21 Distance prot. 1.Z 3 false
21.1111.4861.140 21 Distance prot. 1.Z 4 false
21.1111.4861.140 21 Distance prot. 1.Z 1B false
Definite-T 2 \General
Number Settings Value
21.1111.4862.1 Mode Settings group 1: off
21.1111.4862.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4862.114 Directional mode Settings group 1: non-directional
21.1111.4862.11 1-pole operate allowed Settings group 1: no
21.1111.4862.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4862.129 Op.mode at 1p dead time Settings group 1: blocked
21.1111.4862.112 Hold mode 1p dead time Settings group 1: 0.04 s
21.1111.4862.115 Dynamic settings All: no
21.1111.4862.111 Stabiliz. w. phase current Settings group 1: 10 %
21.1111.4862.3 Threshold Settings group 1: 3288 A
21.1111.4862.6 Operate delay Settings group 1: 0.25 s
Definite-T 2 \Blocking by
Number Settings Value
21.1111.4862.140 87 Line diff. prot..Group indicat. false
21.1111.4862.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4862.140 21 Distance prot. 1.Z 1 false
21.1111.4862.140 21 Distance prot. 1.Z 2 false
21.1111.4862.140 21 Distance prot. 1.Z 3 false
21.1111.4862.140 21 Distance prot. 1.Z 4 false
21.1111.4862.140 21 Distance prot. 1.Z 1B false
Inverse-T 1 \General
Number Settings Value
21.1111.4891.1 Mode Settings group 1: on
21.1111.4891.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4891.115 Directional mode Settings group 1: forward
21.1111.4891.11 1-pole operate allowed Settings group 1: no
21.1111.4891.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4891.131 Blocking by prot. pickup Settings group 1: every pickup
21.1111.4891.130 Op.mode at 1p dead time Settings group 1: blocked
21.1111.4891.113 Hold mode 1p dead time Settings group 1: 0.04 s
21.1111.4891.116 Dynamic settings All: no
11 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Inverse-T 1 \Blocking by
Number Settings Value
21.1111.4891.140 87 Line diff. prot..Group indicat. true
21.1111.4891.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4891.140 21 Distance prot. 1.Z 1 false
21.1111.4891.140 21 Distance prot. 1.Z 2 false
21.1111.4891.140 21 Distance prot. 1.Z 3 false
21.1111.4891.140 21 Distance prot. 1.Z 4 false
21.1111.4891.140 21 Distance prot. 1.Z 1B false
Definite-T 2
Number Settings Value
21.51.182.1 Mode Settings group 1: on
21.51.182.2 Operate & flt.rec. blocked Settings group 1: no
21.51.182.9 Measured value Settings group 1: phase-to-phase
21.51.182.8 Method of measurement Settings group 1: fundamental comp.
21.51.182.101 Pickup mode Settings group 1: 1 out of 3
21.51.182.3 Threshold Settings group 1: 600 kV
21.51.182.4 Dropout ratio Settings group 1: 0.95
21.51.182.6 Operate delay Settings group 1: 1 s
12 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Pickup Z<
Number Settings Value
21.901.3661.101 Min. phase-current thresh Settings group 1: 200 A
21.901.3661.102 Use ph-g load cutout All: no
21.901.3661.105 Use ph-ph load cutout All: no
Z1
Number Settings Value
21.901.3571.1 Mode Settings group 1: on
21.901.3571.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3571.121 Blocked if diff.prot.active Settings group 1: yes
21.901.3571.11 1-pole operate allowed Settings group 1: yes
21.901.3571.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3571.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3571.109 Directional mode Settings group 1: forward
21.901.3571.102 X reach Settings group 1: 75.57 Ω
21.901.3571.103 R (ph-g) Settings group 1: 42 Ω
21.901.3571.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3571.113 Zone-inclination angle Settings group 1: 10 °
21.901.3571.110 Operate delay (1-phase) Settings group 1: 0 s
21.901.3571.112 Operate delay (multi-ph.) Settings group 1: 0 s
Z2
Number Settings Value
21.901.3572.1 Mode Settings group 1: on
21.901.3572.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3572.121 Blocked if diff.prot.active Settings group 1: no
21.901.3572.11 1-pole operate allowed Settings group 1: no
21.901.3572.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3572.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3572.109 Directional mode Settings group 1: forward
21.901.3572.102 X reach Settings group 1: 106.69 Ω
21.901.3572.103 R (ph-g) Settings group 1: 42 Ω
21.901.3572.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3572.113 Zone-inclination angle Settings group 1: 0 °
21.901.3572.110 Operate delay (1-phase) Settings group 1: 0.5 s
21.901.3572.112 Operate delay (multi-ph.) Settings group 1: 0.5 s
Z3
Number Settings Value
21.901.3573.1 Mode Settings group 1: off
21.901.3573.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3573.121 Blocked if diff.prot.active Settings group 1: no
21.901.3573.11 1-pole operate allowed Settings group 1: no
21.901.3573.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3573.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3573.109 Directional mode Settings group 1: forward
21.901.3573.102 X reach Settings group 1: 209.17 Ω
21.901.3573.103 R (ph-g) Settings group 1: 42 Ω
21.901.3573.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3573.113 Zone-inclination angle Settings group 1: 0 °
21.901.3573.110 Operate delay (1-phase) Settings group 1: 1.3 s
13 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Z4
Number Settings Value
21.901.3574.1 Mode Settings group 1: on
21.901.3574.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3574.121 Blocked if diff.prot.active Settings group 1: no
21.901.3574.11 1-pole operate allowed Settings group 1: no
21.901.3574.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3574.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3574.109 Directional mode Settings group 1: reverse
21.901.3574.102 X reach Settings group 1: 21.34 Ω
21.901.3574.103 R (ph-g) Settings group 1: 42 Ω
21.901.3574.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3574.113 Zone-inclination angle Settings group 1: 0 °
21.901.3574.110 Operate delay (1-phase) Settings group 1: 1.5 s
21.901.3574.112 Operate delay (multi-ph.) Settings group 1: 1.5 s
Z 1B
Number Settings Value
21.901.3575.1 Mode Settings group 1: on
21.901.3575.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3575.121 Blocked if diff.prot.active Settings group 1: no
21.901.3575.11 1-pole operate allowed Settings group 1: yes
21.901.3575.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3575.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3575.109 Directional mode Settings group 1: forward
21.901.3575.102 X reach Settings group 1: 106.69 Ω
21.901.3575.103 R (ph-g) Settings group 1: 42 Ω
21.901.3575.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3575.113 Zone-inclination angle Settings group 1: 0 °
21.901.3575.110 Operate delay (1-phase) Settings group 1: oo s
21.901.3575.112 Operate delay (multi-ph.) Settings group 1: oo s
Zone 1
Number Settings Value
21.911.3691.1 Mode Settings group 1: on
21.911.3691.2 Operate & flt.rec. blocked Settings group 1: no
21.911.3691.103 Zone limit R Settings group 1: 51.477 Ω
21.911.3691.104 Zone limit X top Settings group 1: 47.091 Ω
21.911.3691.105 Zone limit X bottom Settings group 1: -54.886 Ω
21.911.3691.102 Rotation angle Settings group 1: 85 °
21.911.3691.108 Count at Settings group 1: entry
21.911.3691.107 Number of power swings Settings group 1: 1
14 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
I-DIFF
Number Settings Value
21.831.3451.1 Mode Settings group 1: on
21.831.3451.2 Operate & flt.rec. blocked Settings group 1: no
21.831.3451.3 Threshold Settings group 1: 416 A
21.831.3451.101 Thresh. switch onto fault Settings group 1: 416 A
21.831.3451.6 Operate delay Settings group 1: 0 s
I-DIFF fast 2
Number Settings Value
21.831.18211.1 Mode Settings group 1: on
21.831.18211.2 Operate & flt.rec. blocked Settings group 1: no
21.831.18211.3 Threshold Settings group 1: 2000 A
21.831.18211.101 Thresh. switch onto fault Settings group 1: 2000 A
Ic-compensat.
Number Settings Value
21.831.3511.1 Mode Settings group 1: on
21.831.3511.101 Ic-stabilization/Ic-rated Settings group 1: 1.5
21.831.3511.102 Total line length Settings group 1: 333 km
21.831.3511.110 Rated charging current Settings group 1: 415 A
15 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
S-DIFF
Number Settings Value
21.1431.8401.1 Mode Settings group 1: on
21.1431.8401.2 Operate & flt.rec. blocked Settings group 1: no
21.1431.8401.3 Threshold Settings group 1: 400 A
21.1431.8401.6 Operate delay Settings group 1: 0 s
S-DIFF fast 2
Number Settings Value
21.1431.18241.1 Mode Settings group 1: on
21.1431.18241.2 Operate & flt.rec. blocked Settings group 1: no
21.1431.18241.3 Threshold Settings group 1: 2000 A
16 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
17 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Cycle 1
Number Settings Value
301.1361.6571.102 Start from idle state allow. Settings group 1: yes
301.1361.6571.103 Action time Settings group 1: 0.2 s
301.1361.6571.108 Dead time aft. 3-pole trip Settings group 1: 0.5 s
301.1361.6571.107 Dead time aft. 1-pole trip Settings group 1: 1.2 s
301.1361.6571.109 Dead time aft. evolv. fault Settings group 1: 1.2 s
301.1361.6571.111 CB ready check bef.close Settings group 1: no
301.1361.6571.110 Synchroch. aft. 3-pole d.t. Settings group 1: none
Synchrocheck 1 \General
Number Settings Value
301.1151.5071.1 Mode Settings group 1: off
301.1151.5071.101 Min. operating limit Vmin Settings group 1: 360 kV
301.1151.5071.102 Max. operat. limit Vmax Settings group 1: 440 kV
301.1151.5071.110 Max.durat. sync.process Settings group 1: 30 s
301.1151.5071.108 Direct close command Settings group 1: no
301.1151.5071.126 Voltage adjustment Settings group 1: 1
18 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Sychr./Asycr.1 \General
Number Settings Value
301.1151.5041.1 Mode Settings group 1: on
301.1151.5041.101 Min. operating limit Vmin Settings group 1: 450 kV
301.1151.5041.102 Max. operat. limit Vmax Settings group 1: 550 kV
301.1151.5041.110 Max.durat. sync.process Settings group 1: 30 s
301.1151.5041.108 Direct close command Settings group 1: no
301.1151.5041.126 Voltage adjustment Settings group 1: 1
19 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
20 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Cycle 1
Number Settings Value
302.1361.6571.102 Start from idle state allow. Settings group 1: yes
302.1361.6571.103 Action time Settings group 1: 0.2 s
302.1361.6571.108 Dead time aft. 3-pole trip Settings group 1: 0.5 s
302.1361.6571.107 Dead time aft. 1-pole trip Settings group 1: 1.2 s
302.1361.6571.109 Dead time aft. evolv. fault Settings group 1: 1.2 s
302.1361.6571.111 CB ready check bef.close Settings group 1: no
302.1361.6571.110 Synchroch. aft. 3-pole d.t. Settings group 1: none
21 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Synchrocheck 1 \General
Number Settings Value
302.1151.5071.1 Mode Settings group 1: on
302.1151.5071.101 Min. operating limit Vmin Settings group 1: 360 kV
302.1151.5071.102 Max. operat. limit Vmax Settings group 1: 440 kV
302.1151.5071.110 Max.durat. sync.process Settings group 1: 30 s
302.1151.5071.108 Direct close command Settings group 1: no
302.1151.5071.126 Voltage adjustment Settings group 1: 1
Sychr./Asycr.1 \General
Number Settings Value
302.1151.5041.1 Mode Settings group 1: off
302.1151.5041.101 Min. operating limit Vmin Settings group 1: 360 kV
302.1151.5041.102 Max. operat. limit Vmax Settings group 1: 440 kV
302.1151.5041.110 Max.durat. sync.process Settings group 1: 30 s
302.1151.5041.108 Direct close command Settings group 1: no
302.1151.5041.126 Voltage adjustment Settings group 1: 1
22 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal
Disconnector 1 \Control
Control
Number Settings Value
601.4201.101 Control model All: SBO w. enh. security
601.4201.102 SBO time-out All: 30 s
601.4201.103 Feedback monitoring time All: 10 s
601.4201.104 Check switching authority All: yes
601.4201.105 Check if pos. is reached All: yes
601.4201.106 Check double activat. blk. All: yes
Disconnector 1 \Disconnector
Disconnector
Number Settings Value
601.5401.101 Maximum output time All: 10 s
601.5401.102 Seal-in time All: 0 s
601.5401.103 Switching-device type All: disconnector
23 of 23
PLANILLA RELÉ ABB REB500
Marca: ABB
Modelo: REB500
Barra 1:
Barra 2:
Ikmin = 1663 A
k= 0.8
Differential current alarm = 10 %
Delay = 5s
BFP = active
Setting (TC) = 0,1 IN
Timer 1 = active
Timer 2 = active
Timer 1 = 100 ms
Timer 2 = 200 ms
Intertripping pulse duration = 150 ms
Logic Type = 1
EFP = active
Pick-up delay = 0.4 s
Pick-up setting = 0.1 In