Totally Integrated 7SL87 - LÍNEA A AYOLAS

Automation Portal

Settings
Device settings
Settings Value
Edit mode primary
Number settings groups 1
Activat. of settings group settings group 1
DIGSI 5 uses following IP address 172.16.60.60 (Integrated Ethernet interface)
Operation-panel language English (United States)
Binary input channel threshold Low: 44 V, High: 88 V
Used time stamp in GOOSE subscriptions On message reception
Hide settings in IEC 61850 structure Hide all settings
Hide SIPROTEC extensions in IEC 61850 structure Hide all SIPROTEC extensions
Use dynamic reporting True
Block IEC 61850 settings changes False
Access point used in Edition1 No access point is specified for the SCD import.

General \Device
Number Settings Value
91.101 Rated frequency All: 50 Hz
91.102 Minimum operate time All: 0 s
91.115 Set. format residu. comp. All: Kr, Kx
91.138 Block monitoring dir. All: off

General \Setting change


Number Settings Value
91.163 Reserv.time for com.prot. All: 120 s

General \Chatter blocking


Number Settings Value
91.123 No. permis.state changes All: 0
91.127 Initial test time All: 1 s
91.124 No. of chatter tests All: 0
91.125 Chatter idle time All: 1 min
91.137 Subsequent test time All: 2 s

General \Measurements
Number Settings Value
91.162 Blk setting change All: false
91.163 Reserv.time for com.prot. All: 120 s
91.111 Energy restore interval Settings group 1: 10 min
91.112 Energy restore time Settings group 1: none

General \Control
Number Settings Value
91.120 Energy restore Settings group 1: latest value
91.121 Energy restore by A.time All: false
91.118 Enable sw.auth. station All: false

1 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

General \Spontan.indic.
Number Settings Value
91.119 Multiple sw.auth. levels All: false

General \CFC
Number Settings Value
91.152 Specific sw. authorities All: false

General \Test support


Number Settings Value
91.139 Fault-display All: with pickup
91.161 CFC chart quality handling All: automatic

Localization
Number Settings Value
6211.139 Unit system All: SI

Time settings
General
Settings Value
Date format All: DD.MM.YYYY

Time source
Settings Value
Fault indication after All: 600 s
Time source 1 none
Time source 2 none
Time zone time source 1 All: local
Time zone time source 2 All: local
Sync. latency time src.1 All: 0 μs
Sync. latency time src.2 All: 0 μs

Time zone and daylight saving time


Settings Value
Time zone offset to UTC All: 60 min
Offset daylight sav. time All: 60 min
Switch daylight sav. time true
Start of daylight sav. time Last Sunday in March at 2:00 AM
End of daylight sav. time Last Sunday in October at 3:00 AM

Power system \General


General
Number Settings Value
11.2311.101 Phase sequence All: ABC

2 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Power system \Tensión derv.AB


VT 3-phase
Number Settings Value
11.941.8911.101 Rated primary voltage All: 500.000 kV
11.941.8911.102 Rated secondary voltage All: 110 V
11.941.8911.104 VT connection All: 3 ph-to-gnd voltages
11.941.8911.106 Inverted phases All: none
11.941.8911.111 Tracking All: active
11.941.8911.130 Measuring-point ID All: 1

VT 1
Number Settings Value
11.941.3811.103 Magnitude correction All: 1
11.941.3811.108 Phase All: V A

VT 2
Number Settings Value
11.941.3812.103 Magnitude correction All: 1
11.941.3812.108 Phase All: V B

VT 3
Number Settings Value
11.941.3813.103 Magnitude correction All: 1
11.941.3813.108 Phase All: V C

Supv. balan. V
Number Settings Value
11.941.2521.1 Mode Settings group 1: on
11.941.2521.101 Release threshold Settings group 1: 250 kV
11.941.2521.102 Threshold min/max Settings group 1: 0.75
11.941.2521.6 Delay supervision alarm Settings group 1: 5 s

Supv. ph.seq.V
Number Settings Value
11.941.2581.1 Mode Settings group 1: on
11.941.2581.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum V
Number Settings Value
11.941.2461.1 Mode Settings group 1: off
11.941.2461.3 Threshold Settings group 1: 125 kV
11.941.2461.6 Delay supervision alarm Settings group 1: 5 s

3 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

VT miniatureCB
Number Settings Value
11.941.2641.101 Response time Settings group 1: 0 s

Power system \Barra


General
Number Settings Value
11.961.2311.101 Rated primary voltage All: 499.53 kV
11.961.2311.102 Rated secondary voltage All: 111 V
11.961.2311.103 Tracking All: inactive
11.961.2311.130 Measuring-point ID All: 2

VT 1
Number Settings Value
11.961.3811.103 Magnitude correction All: 1
11.961.3811.108 Phase All: V B

VT miniatureCB
Number Settings Value
11.961.2641.101 Response time Settings group 1: 0 s

Power system \Meas.point I-3ph 1


CT 3-phase \General
Number Settings Value
11.931.8881.115 CT connection All: 3-phase + IN
11.931.8881.127 Tracking All: active
11.931.8881.130 Measuring-point ID All: 4

CT 3-phase \CT phases


Number Settings Value
11.931.8881.101 Rated primary current All: 2000 A
11.931.8881.102 Rated secondary current All: 1 A
11.931.8881.117 Current range All: 100 x IR
11.931.8881.118 Internal CT type All: CT protection
11.931.8881.116 Neutr.point in dir.of ref.obj All: yes
11.931.8881.114 Inverted phases All: none
11.931.8881.107 CT error changeover All: 1.5
11.931.8881.108 CT error A All: 3 %
11.931.8881.109 CT error B All: 10 %

CT 1
Number Settings Value
11.931.3841.103 Magnitude correction All: 1
11.931.3841.117 Phase All: I A

4 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

CT 2
Number Settings Value
11.931.3842.103 Magnitude correction All: 1
11.931.3842.117 Phase All: I B

CT 3
Number Settings Value
11.931.3843.103 Magnitude correction All: 1
11.931.3843.117 Phase All: I C

CT 4
Number Settings Value
11.931.3844.103 Magnitude correction All: 1
11.931.3844.117 Phase All: IN

Brk.wire det.
Number Settings Value
11.931.5581.1 Mode Settings group 1: off
11.931.5581.101 Mode of blocking Settings group 1: blocking
11.931.5581.102 Delta value for autoblock Settings group 1: 1

Supv. balan. I
Number Settings Value
11.931.2491.1 Mode Settings group 1: on
11.931.2491.101 Release threshold Settings group 1: 1000 A
11.931.2491.102 Threshold min/max Settings group 1: 0.5
11.931.2491.6 Delay supervision alarm Settings group 1: 5 s

Supv. ph.seq.I
Number Settings Value
11.931.2551.1 Mode Settings group 1: on
11.931.2551.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum I
Number Settings Value
11.931.2431.1 Mode Settings group 1: on
11.931.2431.102 Threshold Settings group 1: 200 A
11.931.2431.101 Slope factor Settings group 1: 0.1
11.931.2431.6 Delay supervision alarm Settings group 1: 5 s

Supv.ADC sum I
Number Settings Value
11.931.2401.1 Mode Settings group 1: on

5 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Saturat. det.
Number Settings Value
11.931.17731.101 CT saturation threshold Settings group 1: 16000 A

Recording \Fault recorder


Control
Number Settings Value
51.791.2761.130 Fault recording All: with pickup & AR cyc.
51.791.2761.131 Storage All: always
51.791.2761.111 Maximum record time All: 5 s
51.791.2761.112 Pre-trigger time All: 0.5 s
51.791.2761.113 Post-trigger time All: 0.5 s
51.791.2761.116 Manual record time All: 0.5 s
51.791.2761.140 Sampling frequency All: 2 kHz
51.791.2761.141 Sampl. freq. IEC61850 rec. All: 1 kHz
51.791.2761.128 Scaling COMTRADE All: Secondary values

Line 1 \General
General \Rated values
Number Settings Value
21.9001.101 Rated current All: 1923 A
21.9001.102 Rated voltage All: 500 kV
21.9001.103 Rated apparent power All: 1665.4 MVA

General \Line data


Number Settings Value
21.9001.149 Neutral point Settings group 1: grounded
21.9001.112 C1 per length unit Settings group 1: 0.014 μF/km
21.9001.148 C0 per length unit Settings group 1: 0.008 μF/km
21.9001.113 X per length unit Settings group 1: 0.267 Ω/km
21.9001.114 Line length Settings group 1: 333 km
21.9001.108 Line angle Settings group 1: 84.43 °
21.9001.104 Kr Settings group 1: 3.45
21.9001.105 Kx Settings group 1: 0.74
21.9001.119 CT saturation detection All: no
21.9001.111 Series compensation Settings group 1: no
21.9001.110 Series capacit. reactance Settings group 1: 0 Ω

General \Measurements
Number Settings Value
21.9001.158 P, Q sign Settings group 1: not reversed

Line 1 \Process monitor


Closure detec.
Number Settings Value
21.1131.4681.101 Operating mode Settings group 1: Manual close only
21.1131.4681.102 Action time after closure Settings group 1: 0.05 s
21.1131.4681.103 Min. time feeder open Settings group 1: 0.25 s

6 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

1pol.open det.
Number Settings Value
21.1131.4711.101 Operating mode Settings group 1: with measurement

Volt.criterion
Number Settings Value
21.1131.4801.101 Threshold U open Settings group 1: 120.00 kV

Line 1 \68 P.swing blk


68 P.swing blk
Number Settings Value
21.5311.1 Mode Settings group 1: on
21.5311.103 Max. blocking time Settings group 1: oo s

68 P.swing blk \Zones to be blocked


Number Settings Value
21.5311.102 21 Distance prot. 1.Z 1 true
21.5311.102 21 Distance prot. 1.Z 2 true
21.5311.102 21 Distance prot. 1.Z 3 true
21.5311.102 21 Distance prot. 1.Z 4 true
21.5311.102 21 Distance prot. 1.Z 1B true

Line 1 \Fault locator


Fault locator
Number Settings Value
21.8671.1 Mode Settings group 1: on
21.8671.101 Start Settings group 1: with going pickup
21.8671.103 Load compensation Settings group 1: no

Line 1 \Mes.v.fail.det
Mes.v.fail.det
Number Settings Value
21.2671.1 Mode Settings group 1: on
21.2671.115 Asym.fail.-DO on netw.flt. Settings group 1: no
21.2671.113 Asym.fail. - time delay Settings group 1: 10 s
21.2671.102 3ph.fail. - phs.curr.release Settings group 1: 100 A
21.2671.103 3ph.fail. - phs.curr. jump Settings group 1: 100 A
21.2671.101 3ph.fail. - VA,VB,VC < Settings group 1: 20 kV
21.2671.107 Switch-on 3ph. failure All: on
21.2671.106 SO 3ph.fail. - time delay Settings group 1: 3 s

Line 1 \85-21Perm.overr.
85-21Perm.over
Number Settings Value
21.1291.5701.1 Mode Settings group 1: on

7 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Number Settings Value


21.1291.5701.101 Send prolongation Settings group 1: 0.05 s
21.1291.5701.102 Send delay Settings group 1: 0 s
21.1291.5701.105 Trans. blk. pickup delay Settings group 1: 0.03 s
21.1291.5701.106 Trans. blk. dropout delay Settings group 1: 0.07 s
21.1291.5701.11 1-pole operate allowed Settings group 1: yes
21.1291.5701.103 Operate delay (1-phase) Settings group 1: 0 s
21.1291.5701.104 Operate delay (multi-ph.) Settings group 1: 0 s

85-21Perm.over \Send with


Number Settings Value
21.1291.5701.140 21 Distance prot. 1.pickup forward false
21.1291.5701.140 21 Distance prot. 1.Z 1 false
21.1291.5701.140 21 Distance prot. 1.Z 2 false
21.1291.5701.140 21 Distance prot. 1.Z 3 false
21.1291.5701.140 21 Distance prot. 1.Z 4 false
21.1291.5701.140 21 Distance prot. 1.Z 1B true

85-21Perm.over \Operate with


Number Settings Value
21.1291.5701.141 21 Distance prot. 1.pickup forward false
21.1291.5701.141 21 Distance prot. 1.Z 1 false
21.1291.5701.141 21 Distance prot. 1.Z 2 false
21.1291.5701.141 21 Distance prot. 1.Z 3 false
21.1291.5701.141 21 Distance prot. 1.Z 4 false
21.1291.5701.141 21 Distance prot. 1.Z 1B true

85-21Perm.over \Trans. block. with


Number Settings Value
21.1291.5701.142 85-67N Dir. comp..85-67N Dir.com true

Line 1 \85-67N Dir. comp.


85-67N Dir.com
Number Settings Value
21.1301.5761.1 Mode Settings group 1: on
21.1301.5761.101 Send prolongation Settings group 1: 0.05 s
21.1301.5761.102 Send delay Settings group 1: 0 s
21.1301.5761.105 Trans. blk. pickup delay Settings group 1: 0.03 s
21.1301.5761.106 Trans. blk. dropout delay Settings group 1: 0.07 s
21.1301.5761.104 3I0 threshold rev./forw. Settings group 1: 75 %
21.1301.5761.11 1-pole operate allowed Settings group 1: yes
21.1301.5761.103 Operate delay (1-phase) Settings group 1: 0 s

85-67N Dir.com \Send with


Number Settings Value
21.1301.5761.140 67N GFP gnd.sys.1.Definite-T 1 false
21.1301.5761.140 67N GFP gnd.sys.1.Definite-T 2 false
21.1301.5761.140 67N GFP gnd.sys.1.Inverse-T 1 true

8 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

85-67N Dir.com \Operate with


Number Settings Value
21.1301.5761.141 67N GFP gnd.sys.1.Definite-T 1 false
21.1301.5761.141 67N GFP gnd.sys.1.Definite-T 2 false
21.1301.5761.141 67N GFP gnd.sys.1.Inverse-T 1 true

85-67N Dir.com \Trans. block. with


Number Settings Value
21.1301.5761.142 85-21Perm.overr..85-21Perm.over true

Line 1 \Switch onto fault 1


Stage 1
Number Settings Value
21.1341.5941.1 Mode Settings group 1: on
21.1341.5941.2 Operate & flt.rec. blocked Settings group 1: no
21.1341.5941.6 Operate delay Settings group 1: 0 s

Stage 1 \Configuration
Number Settings Value
21.1341.5941.102 50/51 OC-3ph 1p 1.Definite-T 1 false
21.1341.5941.102 50N/51N OC-gnd-A1.Definite-T 1 false
21.1341.5941.102 50 high-speed 1pol 1.Standard 1 true
21.1341.5941.102 67N GFP gnd.sys.1.Definite-T 1 false
21.1341.5941.102 67N GFP gnd.sys.1.Definite-T 2 false
21.1341.5941.102 67N GFP gnd.sys.1.Inverse-T 1 true
21.1341.5941.102 21 Distance prot. 1.Z 1 false
21.1341.5941.102 21 Distance prot. 1.Z 2 false
21.1341.5941.102 21 Distance prot. 1.Z 3 false
21.1341.5941.102 21 Distance prot. 1.Z 4 false
21.1341.5941.102 21 Distance prot. 1.Z 1B true

Line 1 \50/51 OC-3ph 1p 1


General
Number Settings Value
21.221.2311.101 Emergency mode Settings group 1: no

Definite-T 1 \General
Number Settings Value
21.221.841.1 Mode Settings group 1: on
21.221.841.2 Operate & flt.rec. blocked Settings group 1: no
21.221.841.11 1-pole operate allowed Settings group 1: no
21.221.841.26 Dynamic settings All: no
21.221.841.8 Method of measurement Settings group 1: fundamental comp.
21.221.841.3 Threshold Settings group 1: 2400 A
21.221.841.4 Dropout ratio Settings group 1: 0.95
21.221.841.102 Pickup delay Settings group 1: 0 s
21.221.841.101 Dropout delay Settings group 1: 0 s
21.221.841.6 Operate delay Settings group 1: 60 s

9 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Line 1 \50N/51N OC-gnd-A1


General
Number Settings Value
21.211.2311.101 Emergency mode Settings group 1: no
21.211.2311.9 Measured value Settings group 1: IN measured

Definite-T 1 \General
Number Settings Value
21.211.751.1 Mode Settings group 1: off
21.211.751.2 Operate & flt.rec. blocked Settings group 1: no
21.211.751.26 Dynamic settings All: no
21.211.751.8 Method of measurement Settings group 1: fundamental comp.
21.211.751.3 Threshold Settings group 1: 1200 A
21.211.751.4 Dropout ratio Settings group 1: 0.95
21.211.751.101 Dropout delay Settings group 1: 0 s
21.211.751.6 Operate delay Settings group 1: 0.3 s

Line 1 \50 high-speed 1pol 1


Standard 1
Number Settings Value
21.981.3961.1 Mode Settings group 1: on
21.981.3961.102 1-pole operate allowed Settings group 1: no
21.981.3961.101 Activation Settings group 1: on CB closure
21.981.3961.3 Threshold Settings group 1: 1507 A
21.981.3961.4 Dropout ratio Settings group 1: 0.9

Line 1 \67N GFP gnd.sys.1


General
Number Settings Value
21.1111.2311.114 Polarization with All: V0 + IY or V2 + I2
21.1111.2311.101 Angle forward α Settings group 1: 338 °
21.1111.2311.102 Angle forward β Settings group 1: 122 °
21.1111.2311.103 Min. zero-seq. voltage V0 Settings group 1: 2.61 kV
21.1111.2311.115 Dir.reslt=forw.at V0<min Settings group 1: no
21.1111.2311.104 Min.3I0 f.increas.dir.sens. Settings group 1: 100 A
21.1111.2311.107 Min. neg.-seq. voltage V2 Settings group 1: 2.61 kV
21.1111.2311.106 Min. neg.-seq. current I2 Settings group 1: 100 A
21.1111.2311.116 Dir.corr.at ser.comp.lines Settings group 1: no

Definite-T 1 \General
Number Settings Value
21.1111.4861.1 Mode Settings group 1: on
21.1111.4861.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4861.114 Directional mode Settings group 1: forward
21.1111.4861.11 1-pole operate allowed Settings group 1: no
21.1111.4861.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4861.130 Blocking by prot. pickup Settings group 1: every pickup
21.1111.4861.129 Op.mode at 1p dead time Settings group 1: blocked

10 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Number Settings Value


21.1111.4861.112 Hold mode 1p dead time Settings group 1: 0.04 s
21.1111.4861.115 Dynamic settings All: no
21.1111.4861.111 Stabiliz. w. phase current Settings group 1: 10 %
21.1111.4861.3 Threshold Settings group 1: 3288 A
21.1111.4861.6 Operate delay Settings group 1: 0.25 s

Definite-T 1 \Blocking by
Number Settings Value
21.1111.4861.140 87 Line diff. prot..Group indicat. true
21.1111.4861.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4861.140 21 Distance prot. 1.Z 1 false
21.1111.4861.140 21 Distance prot. 1.Z 2 false
21.1111.4861.140 21 Distance prot. 1.Z 3 false
21.1111.4861.140 21 Distance prot. 1.Z 4 false
21.1111.4861.140 21 Distance prot. 1.Z 1B false

Definite-T 2 \General
Number Settings Value
21.1111.4862.1 Mode Settings group 1: off
21.1111.4862.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4862.114 Directional mode Settings group 1: non-directional
21.1111.4862.11 1-pole operate allowed Settings group 1: no
21.1111.4862.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4862.129 Op.mode at 1p dead time Settings group 1: blocked
21.1111.4862.112 Hold mode 1p dead time Settings group 1: 0.04 s
21.1111.4862.115 Dynamic settings All: no
21.1111.4862.111 Stabiliz. w. phase current Settings group 1: 10 %
21.1111.4862.3 Threshold Settings group 1: 3288 A
21.1111.4862.6 Operate delay Settings group 1: 0.25 s

Definite-T 2 \Blocking by
Number Settings Value
21.1111.4862.140 87 Line diff. prot..Group indicat. false
21.1111.4862.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4862.140 21 Distance prot. 1.Z 1 false
21.1111.4862.140 21 Distance prot. 1.Z 2 false
21.1111.4862.140 21 Distance prot. 1.Z 3 false
21.1111.4862.140 21 Distance prot. 1.Z 4 false
21.1111.4862.140 21 Distance prot. 1.Z 1B false

Inverse-T 1 \General
Number Settings Value
21.1111.4891.1 Mode Settings group 1: on
21.1111.4891.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4891.115 Directional mode Settings group 1: forward
21.1111.4891.11 1-pole operate allowed Settings group 1: no
21.1111.4891.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4891.131 Blocking by prot. pickup Settings group 1: every pickup
21.1111.4891.130 Op.mode at 1p dead time Settings group 1: blocked
21.1111.4891.113 Hold mode 1p dead time Settings group 1: 0.04 s
21.1111.4891.116 Dynamic settings All: no

11 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Number Settings Value


21.1111.4891.112 Stabiliz. w. phase current Settings group 1: 10 %
21.1111.4891.3 Threshold Settings group 1: 300 A
21.1111.4891.133 Type of character. curve Settings group 1: IEC normal inverse
21.1111.4891.106 Time dial Settings group 1: 0.12
21.1111.4891.132 Additional time delay Settings group 1: 0 s
21.1111.4891.134 Reset Settings group 1: instantaneous

Inverse-T 1 \Blocking by
Number Settings Value
21.1111.4891.140 87 Line diff. prot..Group indicat. true
21.1111.4891.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4891.140 21 Distance prot. 1.Z 1 false
21.1111.4891.140 21 Distance prot. 1.Z 2 false
21.1111.4891.140 21 Distance prot. 1.Z 3 false
21.1111.4891.140 21 Distance prot. 1.Z 4 false
21.1111.4891.140 21 Distance prot. 1.Z 1B false

Line 1 \59 Overvolt.-3ph 1


Definite-T 1
Number Settings Value
21.51.181.1 Mode Settings group 1: on
21.51.181.2 Operate & flt.rec. blocked Settings group 1: no
21.51.181.9 Measured value Settings group 1: phase-to-phase
21.51.181.8 Method of measurement Settings group 1: fundamental comp.
21.51.181.101 Pickup mode Settings group 1: 3 out of 3
21.51.181.3 Threshold Settings group 1: 575 kV
21.51.181.4 Dropout ratio Settings group 1: 0.95
21.51.181.6 Operate delay Settings group 1: 5 s

Definite-T 2
Number Settings Value
21.51.182.1 Mode Settings group 1: on
21.51.182.2 Operate & flt.rec. blocked Settings group 1: no
21.51.182.9 Measured value Settings group 1: phase-to-phase
21.51.182.8 Method of measurement Settings group 1: fundamental comp.
21.51.182.101 Pickup mode Settings group 1: 1 out of 3
21.51.182.3 Threshold Settings group 1: 600 kV
21.51.182.4 Dropout ratio Settings group 1: 0.95
21.51.182.6 Operate delay Settings group 1: 1 s

Line 1 \21 Distance prot. 1


General
Number Settings Value
21.901.2311.110 Zone timer start Settings group 1: on dist. pickup
21.901.2311.107 Dist. characteristic angle Settings group 1: 72 °
21.901.2311.105 Ground-fault detection Settings group 1: 3I0 or V0
21.901.2311.103 3I0> threshold value Settings group 1: 200 A
21.901.2311.102 V0> threshold value Settings group 1: 21.74 kV
21.901.2311.104 3I0 pickup stabilization Settings group 1: 0.1
21.901.2311.108 Loop select. with ph-ph-g Settings group 1: block leading phase

12 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Pickup Z<
Number Settings Value
21.901.3661.101 Min. phase-current thresh Settings group 1: 200 A
21.901.3661.102 Use ph-g load cutout All: no
21.901.3661.105 Use ph-ph load cutout All: no

Z1
Number Settings Value
21.901.3571.1 Mode Settings group 1: on
21.901.3571.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3571.121 Blocked if diff.prot.active Settings group 1: yes
21.901.3571.11 1-pole operate allowed Settings group 1: yes
21.901.3571.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3571.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3571.109 Directional mode Settings group 1: forward
21.901.3571.102 X reach Settings group 1: 75.57 Ω
21.901.3571.103 R (ph-g) Settings group 1: 42 Ω
21.901.3571.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3571.113 Zone-inclination angle Settings group 1: 10 °
21.901.3571.110 Operate delay (1-phase) Settings group 1: 0 s
21.901.3571.112 Operate delay (multi-ph.) Settings group 1: 0 s

Z2
Number Settings Value
21.901.3572.1 Mode Settings group 1: on
21.901.3572.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3572.121 Blocked if diff.prot.active Settings group 1: no
21.901.3572.11 1-pole operate allowed Settings group 1: no
21.901.3572.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3572.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3572.109 Directional mode Settings group 1: forward
21.901.3572.102 X reach Settings group 1: 106.69 Ω
21.901.3572.103 R (ph-g) Settings group 1: 42 Ω
21.901.3572.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3572.113 Zone-inclination angle Settings group 1: 0 °
21.901.3572.110 Operate delay (1-phase) Settings group 1: 0.5 s
21.901.3572.112 Operate delay (multi-ph.) Settings group 1: 0.5 s

Z3
Number Settings Value
21.901.3573.1 Mode Settings group 1: off
21.901.3573.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3573.121 Blocked if diff.prot.active Settings group 1: no
21.901.3573.11 1-pole operate allowed Settings group 1: no
21.901.3573.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3573.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3573.109 Directional mode Settings group 1: forward
21.901.3573.102 X reach Settings group 1: 209.17 Ω
21.901.3573.103 R (ph-g) Settings group 1: 42 Ω
21.901.3573.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3573.113 Zone-inclination angle Settings group 1: 0 °
21.901.3573.110 Operate delay (1-phase) Settings group 1: 1.3 s

13 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Number Settings Value


21.901.3573.112 Operate delay (multi-ph.) Settings group 1: 1.3 s

Z4
Number Settings Value
21.901.3574.1 Mode Settings group 1: on
21.901.3574.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3574.121 Blocked if diff.prot.active Settings group 1: no
21.901.3574.11 1-pole operate allowed Settings group 1: no
21.901.3574.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3574.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3574.109 Directional mode Settings group 1: reverse
21.901.3574.102 X reach Settings group 1: 21.34 Ω
21.901.3574.103 R (ph-g) Settings group 1: 42 Ω
21.901.3574.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3574.113 Zone-inclination angle Settings group 1: 0 °
21.901.3574.110 Operate delay (1-phase) Settings group 1: 1.5 s
21.901.3574.112 Operate delay (multi-ph.) Settings group 1: 1.5 s

Z 1B
Number Settings Value
21.901.3575.1 Mode Settings group 1: on
21.901.3575.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3575.121 Blocked if diff.prot.active Settings group 1: no
21.901.3575.11 1-pole operate allowed Settings group 1: yes
21.901.3575.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3575.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3575.109 Directional mode Settings group 1: forward
21.901.3575.102 X reach Settings group 1: 106.69 Ω
21.901.3575.103 R (ph-g) Settings group 1: 42 Ω
21.901.3575.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3575.113 Zone-inclination angle Settings group 1: 0 °
21.901.3575.110 Operate delay (1-phase) Settings group 1: oo s
21.901.3575.112 Operate delay (multi-ph.) Settings group 1: oo s

Line 1 \78 Out-of-step 1


General
Number Settings Value
21.911.2311.101 I1<threshold blocks zone Settings group 1: 20 %
21.911.2311.100 I2>threshold blocks zone Settings group 1: 20 %

Zone 1
Number Settings Value
21.911.3691.1 Mode Settings group 1: on
21.911.3691.2 Operate & flt.rec. blocked Settings group 1: no
21.911.3691.103 Zone limit R Settings group 1: 51.477 Ω
21.911.3691.104 Zone limit X top Settings group 1: 47.091 Ω
21.911.3691.105 Zone limit X bottom Settings group 1: -54.886 Ω
21.911.3691.102 Rotation angle Settings group 1: 85 °
21.911.3691.108 Count at Settings group 1: entry
21.911.3691.107 Number of power swings Settings group 1: 1

14 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Number Settings Value


21.911.3691.101 Re-entry time Settings group 1: 20 s
21.911.3691.100 Signal time Settings group 1: 0.05 s

Line 1 \Weak infeed


Weak infeed
Number Settings Value
21.1331.5821.101 Echo block time after Tx Settings group 1: 0.05 s
21.1331.5821.102 Echo and operate delay Settings group 1: 0.04 s
21.1331.5821.103 Echo pulse Settings group 1: 0.05 s
21.1331.5821.104 Weak infeed action Settings group 1: only echo
21.1331.5821.105 85-21/67N common chan. Settings group 1: no
21.1331.5821.106 Undervoltage threshold Settings group 1: 108.70 kV

Line 1 \87 Line diff. prot.


General
Number Settings Value
21.831.2311.1 Mode Settings group 1: on
21.831.2311.11 1-pole operate allowed Settings group 1: yes
21.831.2311.102 Min. current for release Settings group 1: 0 A
21.831.2311.104 Supervision Idiff All: yes: block diff. prot.

I-DIFF
Number Settings Value
21.831.3451.1 Mode Settings group 1: on
21.831.3451.2 Operate & flt.rec. blocked Settings group 1: no
21.831.3451.3 Threshold Settings group 1: 416 A
21.831.3451.101 Thresh. switch onto fault Settings group 1: 416 A
21.831.3451.6 Operate delay Settings group 1: 0 s

I-DIFF fast 2
Number Settings Value
21.831.18211.1 Mode Settings group 1: on
21.831.18211.2 Operate & flt.rec. blocked Settings group 1: no
21.831.18211.3 Threshold Settings group 1: 2000 A
21.831.18211.101 Thresh. switch onto fault Settings group 1: 2000 A

Ic-compensat.
Number Settings Value
21.831.3511.1 Mode Settings group 1: on
21.831.3511.101 Ic-stabilization/Ic-rated Settings group 1: 1.5
21.831.3511.102 Total line length Settings group 1: 333 km
21.831.3511.110 Rated charging current Settings group 1: 415 A

15 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Line 1 \87 Stub diff. prot. 1


General
Number Settings Value
21.1431.2311.1 Mode Settings group 1: on

S-DIFF
Number Settings Value
21.1431.8401.1 Mode Settings group 1: on
21.1431.8401.2 Operate & flt.rec. blocked Settings group 1: no
21.1431.8401.3 Threshold Settings group 1: 400 A
21.1431.8401.6 Operate delay Settings group 1: 0 s

S-DIFF fast 2
Number Settings Value
21.1431.18241.1 Mode Settings group 1: on
21.1431.18241.2 Operate & flt.rec. blocked Settings group 1: no
21.1431.18241.3 Threshold Settings group 1: 2000 A

Line 1\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Line 1\ 85-21Perm.overr.\ 85-21Perm.over Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 85-67N Dir. comp.\ 85-67N Dir.com Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ Switch onto fault 1\ Stage 1 Circuit breaker 1:Blk. auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Blk. auto.recl., Circuit breaker 2:Trip
Line 1\ 50/51 OC-3ph 1p 1\ Definite-T 1 Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 50N/51N OC-gnd-A1\ Definite-T 1 Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 67N GFP gnd.sys.1\ Definite-T 1 Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 67N GFP gnd.sys.1\ Definite-T 2 Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 67N GFP gnd.sys.1\ Inverse-T 1 Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 59 Overvolt.-3ph 1\ Definite-T 2 Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 87 Line diff. prot.\ General Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 87 Stub diff. prot. 1\ General Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 21 Distance prot. 1\ Z 1 Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 21 Distance prot. 1\ Z 2 Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 21 Distance prot. 1\ Z 3 Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 21 Distance prot. 1\ Z 4 Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 78 Out-of-step 1\ Zone 1 Circuit breaker 1:Trip, Circuit breaker 2:Trip

Circuit breaker 1 \General


General \Ref. for %-values
Number Settings Value
301.2311.101 Rated normal current All: 2000.00 A
301.2311.102 Rated voltage All: 500.00 kV

16 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

General \Breaker settings


Number Settings Value
301.2311.112 Current thresh. CB open All: 100 A
301.2311.113 1-pole operate allowed All: yes

Circuit breaker 1 \Trip logic


Trip logic
Number Settings Value
301.5341.101 Trip at 2ph short circuit All: 3-pole
301.5341.102 3-pole coupling All: with trip
301.5341.103 Reset of trip command All: with I<

Circuit breaker 1 \Circuit break.


Circuit break.
Number Settings Value
301.4261.101 Output time All: 0.1 s
301.4261.105 Indicat. of breaking values All: always

Circuit breaker 1 \Manual close


Manual close
Number Settings Value
301.6541.101 Action time Settings group 1: 0.3 s
301.6541.102 CB open dropout delay Settings group 1: 0 s

Circuit breaker 1 \Control


Control
Number Settings Value
301.4201.101 Control model All: SBO w. enh. security
301.4201.102 SBO time-out All: 30 s
301.4201.103 Feedback monitoring time All: 1 s
301.4201.104 Check switching authority All: yes
301.4201.105 Check if pos. is reached All: yes
301.4201.106 Check double activat. blk. All: yes
301.4201.107 Check blk. by protection All: yes

Circuit breaker 1 \CB test


CB test
Number Settings Value
301.6151.101 Dead time All: 0.1 s
301.6151.102 Trip only All: false
301.6151.103 Consider current criterion All: false

17 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Circuit breaker 1 \79 Auto. reclosing


General
Number Settings Value
301.1361.6601.1 Mode Settings group 1: off
301.1361.6601.101 79 operating mode All: with op., with act. time
301.1361.6601.102 CB ready check bef. start Settings group 1: no
301.1361.6601.103 Reclai. time aft.succ.cyc. Settings group 1: 3 s
301.1361.6601.104 Block. time aft. man.close Settings group 1: 1 s
301.1361.6601.105 Start signal supervis.time Settings group 1: 0.13 s
301.1361.6601.106 CB ready superv. time Settings group 1: 3 s
301.1361.6601.107 3-pole operate by 79 Settings group 1: yes
301.1361.6601.108 Evolving-fault detection Settings group 1: with trip
301.1361.6601.109 Response to evolv. faults Settings group 1: blocks 79
301.1361.6601.110 Max. dead-time delay Settings group 1: 0.5 s
301.1361.6601.111 Max. dead-time extension Settings group 1: 1.2 s
301.1361.6601.112 Send delay f. remot. close Settings group 1: 0.05 s

General \DLC, RDT


Number Settings Value
301.1361.6601.113 Dead-line check/reduc.d.t All: without

Cycle 1
Number Settings Value
301.1361.6571.102 Start from idle state allow. Settings group 1: yes
301.1361.6571.103 Action time Settings group 1: 0.2 s
301.1361.6571.108 Dead time aft. 3-pole trip Settings group 1: 0.5 s
301.1361.6571.107 Dead time aft. 1-pole trip Settings group 1: 1.2 s
301.1361.6571.109 Dead time aft. evolv. fault Settings group 1: 1.2 s
301.1361.6571.111 CB ready check bef.close Settings group 1: no
301.1361.6571.110 Synchroch. aft. 3-pole d.t. Settings group 1: none

Cycle 1 \Intern. synchrocheck with


Number Settings Value
301.1361.6571.112 Intern. synchrocheck with

Circuit breaker 1 \25 Synchronization


General
Number Settings Value
301.1151.2311.127 Angle adjust. (transform.) Settings group 1: 0 °

Synchrocheck 1 \General
Number Settings Value
301.1151.5071.1 Mode Settings group 1: off
301.1151.5071.101 Min. operating limit Vmin Settings group 1: 360 kV
301.1151.5071.102 Max. operat. limit Vmax Settings group 1: 440 kV
301.1151.5071.110 Max.durat. sync.process Settings group 1: 30 s
301.1151.5071.108 Direct close command Settings group 1: no
301.1151.5071.126 Voltage adjustment Settings group 1: 1

18 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Synchrocheck 1 \De-en.gized switch.


Number Settings Value
301.1151.5071.105 Close cmd. at V1< & V2> Settings group 1: no
301.1151.5071.106 Close cmd. at V1> & V2< Settings group 1: no
301.1151.5071.107 Close cmd. at V1< & V2< Settings group 1: no
301.1151.5071.103 V1, V2 without voltage Settings group 1: 20 kV
301.1151.5071.104 V1, V2 with voltage Settings group 1: 320 kV
301.1151.5071.109 Supervision time Settings group 1: 0.1 s

Synchrocheck 1 \Synchr. conditions


Number Settings Value
301.1151.5071.122 Max. voltage diff. V2>V1 Settings group 1: 20 kV
301.1151.5071.123 Max. voltage diff. V2<V1 Settings group 1: 20 kV
301.1151.5071.117 Max. frequency diff. f2>f1 Settings group 1: 0.1 Hz
301.1151.5071.118 Max. frequency diff. f2<f1 Settings group 1: 0.1 Hz
301.1151.5071.124 Max. angle diff. α2>α1 Settings group 1: 10 °
301.1151.5071.125 Max. angle diff. α2<α1 Settings group 1: 10 °

Sychr./Asycr.1 \General
Number Settings Value
301.1151.5041.1 Mode Settings group 1: on
301.1151.5041.101 Min. operating limit Vmin Settings group 1: 450 kV
301.1151.5041.102 Max. operat. limit Vmax Settings group 1: 550 kV
301.1151.5041.110 Max.durat. sync.process Settings group 1: 30 s
301.1151.5041.108 Direct close command Settings group 1: no
301.1151.5041.126 Voltage adjustment Settings group 1: 1

Sychr./Asycr.1 \De-en.gized switch.


Number Settings Value
301.1151.5041.105 Close cmd. at V1< & V2> Settings group 1: yes
301.1151.5041.106 Close cmd. at V1> & V2< Settings group 1: yes
301.1151.5041.107 Close cmd. at V1< & V2< Settings group 1: no
301.1151.5041.103 V1, V2 without voltage Settings group 1: 50 kV
301.1151.5041.104 V1, V2 with voltage Settings group 1: 400 kV
301.1151.5041.109 Supervision time Settings group 1: 0.1 s

Sychr./Asycr.1 \Asynchr. op.mode


Number Settings Value
301.1151.5041.114 Async. operating mode Settings group 1: on
301.1151.5041.113 CB make time Settings group 1: 0.06 s
301.1151.5041.115 Max. voltage diff. V2>V1 Settings group 1: 50 kV
301.1151.5041.116 Max. voltage diff. V2<V1 Settings group 1: 50 kV
301.1151.5041.117 Max. frequency diff. f2>f1 Settings group 1: 0.08 Hz
301.1151.5041.118 Max. frequency diff. f2<f1 Settings group 1: 0.08 Hz

Sychr./Asycr.1 \Synchr. op.mode


Number Settings Value
301.1151.5041.119 Sync. operating mode Settings group 1: off
301.1151.5041.120 f-threshold ASYN<->SYN Settings group 1: 0.01 Hz

19 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Number Settings Value


301.1151.5041.122 Max. voltage diff. V2>V1 Settings group 1: 20 kV
301.1151.5041.123 Max. voltage diff. V2<V1 Settings group 1: 20 kV
301.1151.5041.124 Max. angle diff. α2>α1 Settings group 1: 10 °
301.1151.5041.125 Max. angle diff. α2<α1 Settings group 1: 10 °
301.1151.5041.121 Delay close command Settings group 1: 0 s

Circuit breaker 2 \General


General \Ref. for %-values
Number Settings Value
302.2311.101 Rated normal current All: 2000.00 A
302.2311.102 Rated voltage All: 500.00 kV

General \Breaker settings


Number Settings Value
302.2311.112 Current thresh. CB open All: 100 A
302.2311.113 1-pole operate allowed All: yes

Circuit breaker 2 \Trip logic


Trip logic
Number Settings Value
302.5341.101 Trip at 2ph short circuit All: 3-pole
302.5341.102 3-pole coupling All: with trip
302.5341.103 Reset of trip command All: with I<

Circuit breaker 2 \Circuit break.


Circuit break.
Number Settings Value
302.4261.101 Output time All: 0.1 s
302.4261.105 Indicat. of breaking values All: always

Circuit breaker 2 \Manual close


Manual close
Number Settings Value
302.6541.101 Action time Settings group 1: 0.3 s
302.6541.102 CB open dropout delay Settings group 1: 0 s

Circuit breaker 2 \Control


Control
Number Settings Value
302.4201.101 Control model All: SBO w. enh. security
302.4201.102 SBO time-out All: 30 s
302.4201.103 Feedback monitoring time All: 1 s
302.4201.104 Check switching authority All: yes
302.4201.105 Check if pos. is reached All: yes

20 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Number Settings Value


302.4201.106 Check double activat. blk. All: yes
302.4201.107 Check blk. by protection All: yes

Circuit breaker 2 \CB test


CB test
Number Settings Value
302.6151.101 Dead time All: 0.1 s
302.6151.102 Trip only All: false
302.6151.103 Consider current criterion All: false

Circuit breaker 2 \79 Auto. reclosing


General
Number Settings Value
302.1361.6601.1 Mode Settings group 1: off
302.1361.6601.101 79 operating mode All: with op., with act. time
302.1361.6601.102 CB ready check bef. start Settings group 1: no
302.1361.6601.103 Reclai. time aft.succ.cyc. Settings group 1: 3 s
302.1361.6601.104 Block. time aft. man.close Settings group 1: 1 s
302.1361.6601.105 Start signal supervis.time Settings group 1: 0.13 s
302.1361.6601.106 CB ready superv. time Settings group 1: 3 s
302.1361.6601.107 3-pole operate by 79 Settings group 1: yes
302.1361.6601.108 Evolving-fault detection Settings group 1: with trip
302.1361.6601.109 Response to evolv. faults Settings group 1: blocks 79
302.1361.6601.110 Max. dead-time delay Settings group 1: 0.5 s
302.1361.6601.111 Max. dead-time extension Settings group 1: 1.2 s
302.1361.6601.112 Send delay f. remot. close Settings group 1: 0.05 s

General \DLC, RDT


Number Settings Value
302.1361.6601.113 Dead-line check/reduc.d.t All: without

Cycle 1
Number Settings Value
302.1361.6571.102 Start from idle state allow. Settings group 1: yes
302.1361.6571.103 Action time Settings group 1: 0.2 s
302.1361.6571.108 Dead time aft. 3-pole trip Settings group 1: 0.5 s
302.1361.6571.107 Dead time aft. 1-pole trip Settings group 1: 1.2 s
302.1361.6571.109 Dead time aft. evolv. fault Settings group 1: 1.2 s
302.1361.6571.111 CB ready check bef.close Settings group 1: no
302.1361.6571.110 Synchroch. aft. 3-pole d.t. Settings group 1: none

Cycle 1 \Intern. synchrocheck with


Number Settings Value
302.1361.6571.112 Intern. synchrocheck with

21 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Circuit breaker 2 \25 Synchronization


General
Number Settings Value
302.1151.2311.127 Angle adjust. (transform.) Settings group 1: 0 °

Synchrocheck 1 \General
Number Settings Value
302.1151.5071.1 Mode Settings group 1: on
302.1151.5071.101 Min. operating limit Vmin Settings group 1: 360 kV
302.1151.5071.102 Max. operat. limit Vmax Settings group 1: 440 kV
302.1151.5071.110 Max.durat. sync.process Settings group 1: 30 s
302.1151.5071.108 Direct close command Settings group 1: no
302.1151.5071.126 Voltage adjustment Settings group 1: 1

Synchrocheck 1 \De-en.gized switch.


Number Settings Value
302.1151.5071.105 Close cmd. at V1< & V2> Settings group 1: no
302.1151.5071.106 Close cmd. at V1> & V2< Settings group 1: no
302.1151.5071.107 Close cmd. at V1< & V2< Settings group 1: no
302.1151.5071.103 V1, V2 without voltage Settings group 1: 20 kV
302.1151.5071.104 V1, V2 with voltage Settings group 1: 320 kV
302.1151.5071.109 Supervision time Settings group 1: 0.1 s

Synchrocheck 1 \Synchr. conditions


Number Settings Value
302.1151.5071.122 Max. voltage diff. V2>V1 Settings group 1: 20 kV
302.1151.5071.123 Max. voltage diff. V2<V1 Settings group 1: 20 kV
302.1151.5071.117 Max. frequency diff. f2>f1 Settings group 1: 0.1 Hz
302.1151.5071.118 Max. frequency diff. f2<f1 Settings group 1: 0.1 Hz
302.1151.5071.124 Max. angle diff. α2>α1 Settings group 1: 10 °
302.1151.5071.125 Max. angle diff. α2<α1 Settings group 1: 10 °

Sychr./Asycr.1 \General
Number Settings Value
302.1151.5041.1 Mode Settings group 1: off
302.1151.5041.101 Min. operating limit Vmin Settings group 1: 360 kV
302.1151.5041.102 Max. operat. limit Vmax Settings group 1: 440 kV
302.1151.5041.110 Max.durat. sync.process Settings group 1: 30 s
302.1151.5041.108 Direct close command Settings group 1: no
302.1151.5041.126 Voltage adjustment Settings group 1: 1

Sychr./Asycr.1 \De-en.gized switch.


Number Settings Value
302.1151.5041.105 Close cmd. at V1< & V2> Settings group 1: no
302.1151.5041.106 Close cmd. at V1> & V2< Settings group 1: no
302.1151.5041.107 Close cmd. at V1< & V2< Settings group 1: no
302.1151.5041.103 V1, V2 without voltage Settings group 1: 20 kV
302.1151.5041.104 V1, V2 with voltage Settings group 1: 320 kV
302.1151.5041.109 Supervision time Settings group 1: 0.1 s

22 of 23
Totally Integrated 7SL87 - LÍNEA A AYOLAS
Automation Portal

Sychr./Asycr.1 \Asynchr. op.mode


Number Settings Value
302.1151.5041.114 Async. operating mode Settings group 1: on
302.1151.5041.113 CB make time Settings group 1: 0.06 s
302.1151.5041.115 Max. voltage diff. V2>V1 Settings group 1: 20 kV
302.1151.5041.116 Max. voltage diff. V2<V1 Settings group 1: 20 kV
302.1151.5041.117 Max. frequency diff. f2>f1 Settings group 1: 0.1 Hz
302.1151.5041.118 Max. frequency diff. f2<f1 Settings group 1: 0.1 Hz

Sychr./Asycr.1 \Synchr. op.mode


Number Settings Value
302.1151.5041.119 Sync. operating mode Settings group 1: on
302.1151.5041.120 f-threshold ASYN<->SYN Settings group 1: 0.01 Hz
302.1151.5041.122 Max. voltage diff. V2>V1 Settings group 1: 20 kV
302.1151.5041.123 Max. voltage diff. V2<V1 Settings group 1: 20 kV
302.1151.5041.124 Max. angle diff. α2>α1 Settings group 1: 10 °
302.1151.5041.125 Max. angle diff. α2<α1 Settings group 1: 10 °
302.1151.5041.121 Delay close command Settings group 1: 0 s

Disconnector 1 \Control
Control
Number Settings Value
601.4201.101 Control model All: SBO w. enh. security
601.4201.102 SBO time-out All: 30 s
601.4201.103 Feedback monitoring time All: 10 s
601.4201.104 Check switching authority All: yes
601.4201.105 Check if pos. is reached All: yes
601.4201.106 Check double activat. blk. All: yes

Disconnector 1 \Disconnector
Disconnector
Number Settings Value
601.5401.101 Maximum output time All: 10 s
601.5401.102 Seal-in time All: 0 s
601.5401.103 Switching-device type All: disconnector

23 of 23
PLANILLA RELÉ ABB REB500

S.E. VILLA HAYES 500 KV

Marca: ABB

Modelo: REB500

Transformadores de corriente asociados:

Barra 1:

Sector A: 3000/1 A (línea a MD)

Sector B: 2000/1 A (línea a AYO)

Sector C: 1000/1 A (nuevo diámetro para el transformador 2AT-3)

Barra 2:

Sector A: 3000/1 A (transformador 2AT-1)

Sector B: 3000/1 A (transformador 2AT-2)

Sector C: 1000/1 A (nuevo diámetro para el transformador 2AT-3)

Función Diferencial De Barra 87B

Ikmin = 1663 A
k= 0.8
Differential current alarm = 10 %
Delay = 5s

Función Falla Interruptor 50BF-1-2

BFP = active
Setting (TC) = 0,1 IN
Timer 1 = active
Timer 2 = active
Timer 1 = 100 ms
Timer 2 = 200 ms
Intertripping pulse duration = 150 ms
Logic Type = 1

Función Falla Zona Muerta 50BF-0 (End Fault Protection)

EFP = active
Pick-up delay = 0.4 s
Pick-up setting = 0.1 In