Design of Top Cover

The document summarizes the design of a top cover for a concrete structure. It calculates the minimum required thickness as 100mm. It then calculates the loads on a 1m strip considering dead and live loads. The ultimate load is calculated as 5.865 KN/m. The moment is calculated as 2.9325 KN.m. The required reinforcement is calculated to be 4 bars of 12mm diameter spaced at 300mm. Additionally, 3 bars of 10mm diameter are required as temperature reinforcement spaced at 350mm.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views2 pages

Design of Top Cover

The document summarizes the design of a top cover for a concrete structure. It calculates the minimum required thickness as 100mm. It then calculates the loads on a 1m strip considering dead and live loads. The ultimate load is calculated as 5.865 KN/m. The moment is calculated as 2.9325 KN.m. The required reinforcement is calculated to be 4 bars of 12mm diameter spaced at 300mm. Additionally, 3 bars of 10mm diameter are required as temperature reinforcement spaced at 350mm.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Design of Top Cover

Compute the Minimum Thickness for simply supported

L fy 2000mm 276MPa
t = [0.4 + 700] = [0.4 + ] = 79.42mm say 100mm
20 20 700

Considering 1m Strip

Computation of loads

Dead load (WDL) ; WDL = (Unit Wt. of Concrete) (1m) (t)

WDL = (23.54 KN⁄m3 )(1m)(0.1m) = 2.354 KN⁄m

Live load (WLL) ; WLL = (LiveLoad)(1m) = (1.9 KN⁄m2 )(1m) = 1.9 KN⁄m

Ultimate load (WU) ; Wu = 1.6(WLL) + 1.2(WDL)

Wu = 1.6(1.9 KN/m) + 1.2(2.354KN/m) = 5.865 KN/m


KN
Wu L2 (5.865 )(2m)2
m
Mu = = = 2.9325 KN. m
8 8

Assume concrete cover = 20mm ; Using ɸBAR = 12mm

1
d = t − cover − (ɸBAR ) = 100mm − 20mm − 6mm = 74mm
2

Design of Reinforcement

Mu (2.9325x106 )N. mm
R𝑛 = = = 0.595 MPa
ɸbd2 (0.90)(1000mm)(74𝑚𝑚)2

0.85 fc′ 2Rn


ρ = (1 − √1 − )
fy 0.85 f′c

0.85(20.7 MPa) 2(0.595 MPa)


ρ = (1 − √1 − = 0.00220
276 MPa 0.85(20.7 MPa)

1.4 ρ < ρmin = thus use ρmin


ρmin = = 0.00507
fy

Area of steel (AS)


AS = ρmin bd = 0.00507(1000mm)(74mm) = 375.18mm2

Required no. of bars (N)


π
ϕBAR = 12mm ; Ab = 4 (12mm)2 = 113.10mm2

AS 375.18mm2
N = = = 3.317 say 4pcs
Ab 113.10mm2

Spacing of bars (S)

Ab 113.10mm2
S = (1000mm) = (1000mm) = 301.46mm say 300mm
AS 375.18mm2

For temperature bars


π
ϕbar = 10mm ; Ab = (10mm)2 = 78.54mm2
4

The area of steel (As)

AS = 0.002bh = 0.002(1000mm)(100mm) (ACI Sec. 7.12)

AS = 200mm2

AS 200mm2
Required no. of bars (N) ; N = = = 2.546 say 3pcs.
Ab 78.54mm2

78.54mm2
Spacing of bars ; S = (1000mm) = 392.70mm say 350mm.
200mm2