Product datasheet 48231

Characteristics circuit breaker Masterpact NW08H1 - 800 A - 3


poles - drawout - w/o trip unit

Main

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product Masterpact NW
Product or component type Basic frame
Device short name Masterpact NW08
Circuit breaker name Masterpact NW08H1
Poles description 3P
Network type AC
Breaking capacity code H1
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B

Complementary
Network frequency 50/60 Hz
Control type Push-button
Mounting mode Drawout
[In] rated current 800 A at 40 °C
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
[Icm] rated short-circuit making 143 kA 525 V AC at 50/60 Hz
capacity 143 kA 690 V AC at 50/60 Hz
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Circuit breaker CT rating 800 A
Breaking capacity 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Protection type Without protection
Mechanical durability 12500 cycles without maintenance conforming to IEC 60947-2
25000 cycles with maintenance conforming to IEC 60947-2
Electrical durability 10000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
10000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 10000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2

28 Sep, 2019
1
AC-23A: 10000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Connection pitch 115 mm
[Icw] rated short-time withstand current 36 kA 3 s conforming to IEC 60947-2
65 kA 1 s conforming to IEC 60947-2
Maximum breaking time 25 ms
Maximum closing response time 70 ms
Height 439 mm
Width 441 mm
Depth 394.5 mm

Environment
Standards IEC 60947-2
Product certifications ASTA
Pollution degree 4 conforming to IEC 60664-1
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -40…85 °C

Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Under investigation
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information

Contractual warranty
Warranty 18 months

You might also like