Siemens VXF PDF
Siemens VXF PDF
Siemens VXF PDF
VVF53.. VXF53..
Acvatix™
Valves VVF..,VXF.., VVG41.., VXG41.., VVI41.., VXI41..
Basic Documentation - Version changes
CE1P4030en
2017-10-25 Building Technologies
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Phone +41 41-724 24 24 © Siemens Switzerland Ltd., 2011.
www.siemens.com/sbt Subject to change
2 / 94
3 / 94
4 / 94
5 / 94
6 / 94
The table below lists the trademarks used in this document and their legal owners.
The use of trademarks is subject to international and domestic provisions of the
law.
All product names listed in the table are registered (®) or not registered (™)
trademarks of the owner listed in the table. We forgo the labeling (e.g. using the
symbols ® and ™) of trademarks for the purposes of legibility based on the
reference in this section.
1.4.2 Copyright
This document may be duplicated and distributed only with the express permission
of Siemens, and may be passed only to authorized persons or companies with the
required technical knowledge.
The document was prepared with great care. Please make sure that you are aware
of the latest document revision date.
If you find lack of clarity while using this document, or if you have any criticisms or
suggestions, please get in touch with your local contact person in the nearest
Siemens branch office. For addresses of the Siemens branch offices, please visit
www.siemens.com/acvatix
7 / 94
Before using our products, it is important that you read the documents supplied
with or ordered at the same time as the products (equipment, applications, tools,
etc.) carefully and in full.
We assume that persons using our products and documents are authorized and
trained appropriately and have the technical knowledge required to use our
products as intended.
Siemens assumes no liability to the extent allowed under the law for any losses
resulting from a failure to comply with the aforementioned points or for improper
compliance of the same.
For project engineers, electrical HVAC planners, system integrators, and service
engineers, the document contains all information required for planning,
engineering, correct installation, commissioning, and servicing.
8 / 94
Page
A Valve stem 71
C Valve neck 71
D Type plate 10
E1 Flange
Connections
External
or
E2
internal
thread
72
F1 Blank flange
F2 Blank fitting
9 / 94
Seite
A Valve stem 71
C Valve neck 71
10
D Type plate
E1 Flange
Connections 72
External
or
E2
internal
thread
10 / 94
11 / 94
All 3-port valves can be used as mixing valves (preferred use) or diverting valves.
For use in closed or open hydraulic circuits, observe chapter "Cavitation", page 56.
VXG41..01
VVF42..K
VVF43..K
VVF53..K
range
VVG41..
VXG41..
VVF43..
VXF43..
VVF53..
VXF53..
V..F22..
V..F32..
V..F42..
VVI41..
VXI41..
Tmin Tmax
[°C] [°C]
2)
Type of connection F ET IT F -
Cold water 1 25 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ -
Low-temperature hot water 1 130 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ -
3)
High-temperature hot water 130 150 - ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ -
150 180 - - - ■ ■ ■ ■ - - - - - - ■ ■ -
180 220 - - - - - ■ ■ - - - - - - - ■ -
7) 7) 7)
Water with antifreeze -25 130 - - - - - - - ■ ■ ■ ■ ■ - - - When using V..F43/53 for
7) 7) 7)
-20 130 - - - ■ ■ ■ ■ ■ ■ ■ ■ ■ - - - medium temperatures
7) 7) 7)
-10 130 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ - - - below -5 °C, the stem
-5 130 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ sealing gland must be
130 150 - ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ replaced by 428488060.
4)
Cooling water 1 25 - - - ■ ■ ■ ■ ■ ■ ■ ■ ■ - ■ ■ -
6)
Drinking water – DVGW VXG41..01:
1 90 - - - - -- - - - - ■ - - - - -
tested - Tight bypass
7) 7) 7)
Brines -25 130 - - - - - - - ■ ■ ■ ■ ■ - - - When using V..F43/53 for
7) 7) 7)
-20 130 - - - ■ ■ ■ ■ ■ ■ ■ ■ ■ - - - medium temperatures
7) 7) 7)
-10 130 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ - - - below -5 °C, the stem
-5 130 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ sealing gland must be
130 150 - ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ replaced by 428488060.
Note For a detailed list of the permissible types of antifreeze and brines, refer to "8.1.7
Overview of antifreeze and brines used in the trade", page 89. The notes given
under "2.14 Medium quality and medium treatment", page 57 must also be
observed.
12 / 94
VXG41..01
VVF42..K
VVF43..K
VVF53..K
VXG41..
VVG41..
VXF22..
VXF32..
VXF42..
VXF43..
VXF53..
VVF22..
VVF32..
VVF42..
VVF43..
VVF53..
VXI41..
VVI41..
2)
Type of connection F F F F F ET IT F F F F F ET IT F F F
Generation
Boiler plants ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
District heating plants - - - - - - - - - ■ ■ ■ ■ ■ - ■ ■ ■
Chiller plants ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
3)
Cooling towers - - - ■ ■ ■ ■ ■ - - - ■ ■ ■ ■ - ■ ■
Distribution
Heating groups ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Air handling units ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
1)
Version: S = standard / H = high-performance / D = pressure-compensated / W = heat transfer oils
2)
Type of connection: F = flanged / ET = externally threaded / IT = internally threaded
3)
Open circuits
13 / 94
Stroke 20 mm 40 mm
Actuators Data Positioning 800 N 1000 N 2800 N 2800 N
Sheet force
SAX.. N4501
PN 6
SKD.. N4561
1)
SKB.. N4564
SKC.. N4566
Stroke 20 mm 40 mm
Actuators Data Positioning 800 N 1000 N 2800 N 2800 N
Sheet force
SAX.. N4501
PN 10
SKD.. N4561
1)
SKB.. N4564
SKC.. N4566
2)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4402 DN kvs SV Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax
3
-10…150 °C Stock number [m /h] [kPa]
VVF32.15-1.6 S55202-V100 15 1.6
VVF32.15-2.5 S55202-V101 15 2.5
VVF32.15-4 S55202-V102 15 4 >50 1000 1000
VVF32.25-6.3 S55202-V103 25 6.3 400
400 1000
VVF32.25-10 S55202-V104 25 10
400 - -
VVF32.40-16 S55202-V105 40 16
550 750
VVF32.40-25 S55202-V106 40 25
VVF32.50-40 S55202-V107 50 40 350 300 450
VVF32.65-63 S55202-V108 65 63 200 150 250 200 700
3) >100
VVF32.80-100 S55202-V109 80 100 125 75 175 125 450
3)
VVF32.100-160 S55202-V110 100 160 300 250
VVF32.125-250 S55202-V111 125 250 - - - - - - 190 160
3)
VVF32.150-400 S55202-V112 150 400 125 100
1)
Flange type: 21; flange design: B (see "Flange types", page 72)
2)
Suitable for medium temperatures up to 130 °C
3) 3 3
Valve characteristic for kvs value 100 m /h from 70 % stroke, kvs value 160 m /h from 85 % stroke
3
and kvs value 400 m /h from 90 % stroke is optimized for maximum volumetric flow
14 / 94
2)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4403 DN kvs SV Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax
3
-10…150 °C Stock number [m /h] [kPa]
VVF42.15-1.6 S55204-V100 15 1.6
VVF42.15-2,5 S55204-V101 15 2.5
VVF42.15-4 S55204-V102 15 4
> 50 1600 1600
VVF42.20-6.3 S55204-V103 20 6.3
VVF42.25-6.3 S55204-V104 25 6.3 400 1600
VVF42.25-10 S55204-V105 25 10 400
VVF42.32-16 S55204-V106 32 16 900 1200
VVF42.40-16 S55204-V107 40 16 400 - -
550 750
VVF42.40-25 S55204-V108 40 25
VVF42.50-31.5 S55204-V109 50 31.5
350 300 450 1200
VVF42.50-40 S55204-V110 50 40
VVF42.65-50 S55204-V111 65 50
200 150 250 200 700
VVF42.65-63 S55204-V112 65 63
VVF42.80-80 S55204-V113 80 80 > 100
3) 125 75 175 125 450
VVF42.80-100 S55204-V114 80 100
VVF42.100-125 S55204-V115 100 125
3) 300 250
VVF42.100-160 S55204-V116 100 160
VVF42.125-200 S55204-V117 125 200
- - - - - - 190 160
VVF42.125-250 S55204-V118 125 250
VVF42.150-315 S55204-V119 150 315
3) 125 100
VVF42.150-400 S55204-V120 150 400
1)
Flange type: 21; flange design: B (see "Flange types", page 72)
2)
Suitable for medium temperatures up to 130 °C
3) 3 3
Valve characteristic for kvs value 100 m /h from 70 % stroke, kvs value 160 m /h from 85 % stroke
3
and kvs value 400 m /h from 90 % stroke is optimized for maximum volumetric flow
15 / 94
5) 2)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4404 DN kvs SV Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax
3
-20…220 °C Stock number [m /h] [kPa]
3)
VVF53.15-.. S55208-.. 15 0.16…1.25 > 50
3)
VVF53.15-.. S55208-.. 15 1.6…4 2500 2500
3) 1200 1200
VVF53.20-.. S55208-.. 20 6.3 2500
3) 1200
VVF53.25-.. S55208-.. 25 5…10 1600 2100 - -
3) > 100
VVF53.32-.. S55208-.. 32 16 900 750 1200 1100
3)
VVF53.40-.. S55208-.. 40 12.5…25 550 500 750 650 2000
3)
VVF53.50-.. S55208-.. 50 31.5…40 350 300 450 400 1200 1150
VVF43.65-50 S55206-V100 50
4) 65 700 650
VVF43.65-63 S55206-V101 63
VVF43.80-80 S55206-V102 80
4) 80 450 400
VVF43.80-100 S55206-V103 100
VVF43.100-125 S55206-V104 125
4) 100 > 100 - - - - - - 300 250
VVF43.100-160 S55206-V105 160
4)
VVF43.125-200 S55206-V106 200
4) 125 190 160
VVF43.125-250 S55206-V107 250
4)
VVF43.150-315 S55206-V108 315
150 125 100
VVF43.150-400 S55206-V109 400
1)
Flange type: 21; flange design: B (see "Flange types", page 72)
2)
Suitable for medium temperatures up to 150 °C
3)
See VVF53.., PN 25 (Data Sheet N4405): Flange dimensions for PN 25 are the same as those for
PN 16
4)
Valve characteristic is optimized for maximum volumetric flow:
3
- kvs value 63 m /h from 90 % stroke,
3
- kvs values 100, 160, 200 and 250 m /h from 80 % stroke,
3
- kvs value 315 m /h from 70 % stroke
5)
Suitable for medium temperatures up to 130 °C
Note For applications with steam the maximum differential and closing pressures differ
from the values above. For further details refer to “Applications with steam” on
page 18.
16 / 94
5) 3)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4405 DN kvs SV Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax
3
-20…220 °C Stock number [m /h] [kPa]
VVF53.15-0.16 S55208-V100 0.16
VVF53.15-0.2 S55208-V101 0.2
VVF53.15-0.25 S55208-V102 0.25
VVF53.15-0.32 S55208-V103 0.32
VVF53.15-0.4 S55208-V104 0.4
> 50
VVF53.15-0.5 S55208-V105 0.5
VVF53.15-0.63 S55208-V106 0.63
VVF53.15-0.8 S55208-V107 15 0.8
2500 2500
VVF53.15-1 S55208-V108 1
VVF53.15-1.25 S55208-V109 1.25
1200 1200
VVF53.15-1.6 S55208-V110 1.6 2500
VVF53.15-2 S55208-V111 2
VVF53.15-2.5 S55208-V112 2.5 1200
VVF53.15-3.2 S55208-V113 3.2 - -
VVF53.15-4 S55208-V114 4
VVF53.20-6.3 S55208-V116 20 6.3
VVF53.25-5 S55208-V117 5
VVF53.25-6.3 S55208-V118 6.3
25 1600 2100
VVF53.25-8 S55208-V119 8
VVF53.25-10 S55208-V120 10
VVF53.32-16 S55208-V122 32 16 900 750 1200 1100
> 100
VVF53.40-12.5 S55208-V123 12.5
VVF53.40-16 S55208-V124 16
40 550 500 750 650 2000
VVF53.40-20 S55208-V125 20
VVF53.40-25 S55208-V126 25
VVF53.50-31.5 S55208-V127 31.5
50 350 300 450 400 1200 1150
VVF53.50-40 S55208-V128 40
4)
VVF53.65-63 S55208-V129 65 63 700 650
4)
VVF53.80-100 S55208-V130 80 100 450 400
4)
VVF53.100-160 S55208-V131 100 160 - - - - - - 300 250
4)
VVF53.125-250 S55208-V132 125 250 190 160
VVF53.150-400 S55208-V133 150 400 125 100
1)
DN 15…50: Flange dimensions for PN 16 and PN 25
DN 65…150: Flange dimensions for PN 25 only
2)
Flange type: 21; flange design: B (see "Flange types", page 72)
3)
Suitable for medium temperatures up to 150 °C
4)
Valve is optimized for maximum volumetric flow:
3
- kvs value 63 m /h from 90 % stroke,
3
- kvs values 100, 160 and 250 m /h from 80 % stroke
5)
Suitable for medium temperatures up to 130 °C
Note Other maximum differential and closing pressures are valid for applications with
steam, for further details refer to “Applications with steam” on page 18.
17 / 94
5) 3)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4405 DN kvs SV Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax
3
+100…220 °C Stock number [m /h] [kPa]
VVF53.15-0.16 S55208-V100 0.16
VVF53.15-0.2 S55208-V101 0.2
VVF53.15-0.25 S55208-V102 0.25
VVF53.15-0.32 S55208-V103 0.32
VVF53.15-0.4 S55208-V104 0.4
VVF53.15-0.5 S55208-V105 0.5 > 50
VVF53.15-0.63 S55208-V106 0.63
VVF53.15-0.8 S55208-V107 15 0.8
VVF53.15-1 S55208-V108 1
VVF53.15-1.25 S55208-V109 1.25
VVF53.15-1.6 S55208-V110 1.6 1200
VVF53.15-2 S55208-V111 2
VVF53.15-2.5 S55208-V112 2.5
VVF53.15-3.2 S55208-V113 3.2 2500 2500 1200 - -
4)
VVF53.15-4 S55208-V114 3.6
4)
VVF53.20-6.3 S55208-V116 20 5
- -
VVF53.25-5 S55208-V117 5
VVF53.25-6.3 S55208-V118 6.3
25
VVF53.25-8 S55208-V119 8
4)
VVF53.25-10 S55208-V120 8
4)
VVF53.32-16 S55208-V122 32 15
VVF53.40-12.5 S55208-V123 12.5 > 100
VVF53.40-16 S55208-V124 16
40 1000
VVF53.40-20 S55208-V125 20
4)
VVF53.40-25 S55208-V126 23
VVF53.50-31.5 S55208-V127 31.5
50 600
VVF53.50-40 S55208-V128 40
VVF53.65-63 S55208-V129 65 63 1000
VVF53.80-100 S55208-V130 80 100 750
4)
VVF53.100-160 S55208-V131 100 150 - - - - 2500 500
4)
VVF53.125-250 S55208-V132 125 220 300
VVF53.150-400 S55208-V133 150 360 200
1)
DN 15…50: Flange dimensions for PN 16 and PN 25
DN 65…150: Flange dimensions for PN 25 only
2)
Flange type: 21; flange design: B (see "Flange types", page 72)
3)
Suitable for medium temperatures up to 150 °C
4)
Reduced kvs value
5)
Suitable for medium temperatures up to 130 °C
18 / 94
5) 2)
Data Sheet SAX.. SKD.. SKB.. SKC..
Stock
Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax
N4404 number DN kvs SV
Stock
3 [kPa]
+100…220 °C number [m /h]
VVF43.65-50 S55206-V100 50
65 800
VVF43.65-63 S55206-V101 63
VVF43.80-80 S55206-V102 80
80 750
VVF43.80-100 S55206-V103 100
VVF43.100-125 S55206-V104 125
3) 100 > 100 - - - - - - 1600 500
VVF43.100-160 S55206-V105 150
VVF43.125-200 S55206-V106 200
3) 125 300
VVF43.125-250 S55206-V107 220
3)
VVF43.150-315 S55206-V108 280
3) 150 200
VVF43.150-400 S55206-V109 360
1)
Flange type: 21; flange design: B (see "Flange types", page 72)
2)
Suitable for medium temperatures up to 150 °C
3)
Reduced kvs value
4)
Suitable for medium temperatures up to 130 °C
Stroke 20 mm
Actuators Data Positioning force 800 N 1000 N 2800 N
Sheet
SAX.. N4501
PN 16
SKD.. N4561
SKB.. N4564
1)
Data Sheet SAX.. SKD.. SKB..
N4363 DN kvs SV Threaded connection Δps Δpmax Δps Δpmax Δps Δpmax
3
-25…150 °C Stock number [m /h] [Inch] [kPa]
VVG41.11 VVG41.11 15 0.63 G 1B
VVG41.12 VVG41.12 15 1 G 1B
VVG41.13 VVG41.13 15 1.6 > 50 G 1B
1600
VVG41.14 VVG41.14 15 2.5 G 1B 1600
800 800
VVG41.15 VVG41.15 15 4 G 1B 1600
800
VVG41.20 VVG41.20 20 6.3 G 1¼B
VVG41.25 VVG41.25 25 10 G 1½B 1550
>
VVG41.32 VVG41.32 32 16 G 2B 875 1275
100
VVG41.40 VVG41.40 40 25 G 2¼B 525 525 775 775
VVG41.50 VVG41.50 50 40 G 2¾B 300 300 450 450 1225
1)
Suitable for medium temperatures up to 130 °C
19 / 94
1)
Data Sheet SAX.. SKD..
N4362 DN kvs SV Threaded connection Δps Δpmax Δps Δpmax
3
-25…150 °C Stock number [m /h] [Inch] [kPa]
VVI41.15-2.5 C/VVI41.15-2.5 15 2.5 Rp ½
> 50
VVI41.15-4 C/VVI41.15-4 15 4 Rp ½ 1600
1600
VVI41.20-6.3 C/VVI41.20-6.3 20 6.3 Rp ¾
400
VVI41.25-10 C/VVI41.25-10 25 10 Rp 1 1550 400
>
VVI41.32-16 C/VVI41.32-16 32 16 Rp 1¼ 875 1275
100
VVI41.40-25 C/VVI41.40-25 40 25 Rp 1½ 525 775
VVI41.50-40 C/VVI41.50-40 50 40 Rp 2 300 300 450
1)
Suitable for medium temperatures up to 130 °C
20 / 94
Fluids
Stroke 20 mm 40 mm
Actuators Data Positioning 800 N 1000 N 2800 N 2800 N
Sheet force
SAX.. N4501
PN 16
SKD.. N4561
SKB.. N4564
SKC.. N4566
1)
Product Photo
2)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4403 DN kvs SV Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax
3
-5…150 °C Stock number [m /h] [kPa]
3)
VVF42.50-40K S55204-V121 50 40
3)
VVF42.65-63K S55204-V122 65 63 1600 400 1600 400 1600 400 - -
3)
VVF42.80-100K S55204-V123 80 100
3) > 100
VVF42.100-160K S55204-V124 100 160
3)
VVF42.125-250K S55204-V125 125 250 - - - - - - 1600 400
VVF42.150-360K S55204-V126. 150 360
1)
Flange type: 21; flange design: B (see "Flange types", page 72)
2)
Suitable for medium temperatures up to 130 °C
3) 3
Valve characteristics for pressure compensated valves for kvs value 100 m /h from 70 % stroke,
3 3
kvs value 40,160 and 250 m /h from 80 % stroke and kvs value 63 m /h from 90 % stroke is optimized
for maximum volumetric flow.
Applications with steam Valves of the product lines VVF43..K and VVF53..K are regarding flow
direction optimized for fluids and steam. This results in combination with
electrohydraulic actuators of the product lines SKD.., SKB.. und SKC.. with
significantly higher closing pressures Δps and higher maximum differential
pressures Δpmax.
In individual cases the kVS value is reduced and it has to be assured from the
system side, when the system is starting up that the maximum differential pressure
Δpmax is not exceeded so that the actuator can reliably open the valve.
Stroke 20 mm 40 mm
Actuators Data Positioning 800 N 1000 N 2800 N 2800 N
Sheet force
3)
SAX.. N4501
PN 16 2)
SKD.. N4561
SKB.. N4564
SKC.. N4566
1)
4) 2)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4404 DN kvs SV Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax
3
-5..220 °C Stock number [m /h] [kPa]
3)
VVF43.65-63K S55206-V110 65 63
3)
VVF43.80-100K S55206-V111 80 100
3)
VVF43.100-150K S55206-V120 100 150 > 100 - - - - - - 1600 800
3)
VVF43.125-220K S55206-V121 125 220
VVF43.150-315K S55206-V122 150 315
1)
Flange type: 21; flange design: B (see "Flange types", page 72)
2)
Suitable for medium temperatures up to 150 °C
3) 3
Valve characteristics for pressure compensated valves for k vs value 63 m /h from 90 % stroke,
3
kvs value 100,150 and 220 m /h from 80 % stroke is optimized for maximum volumetric flow.
4)
Suitable for medium temperatures up to 130 °C
21 / 94
2)
5) 3)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4405 DN kvs SV Δps Δpmax Δps Δpmax Δps Δpmax Δps Δpmax
3
-5…220 °C Stock number [m /h] [kPa]
VVF53.50-40K S55208-V134 50 40 - - 2500 1250 2500 1250 - -
4)
VVF53.65-63K S55208-V135 65 63
4)
VVF53.80-100K S55208-V136 80 100
4) > 100
VVF53.100-150K S55208-V158 100 150 - - - - - - 2500 1250
4)
VVF53.125-220K S55208-V159 125 220
VVF53.150-315K S55208-V160 150 315
1)
DN 15…50: Flange dimensions for PN 16 and PN 25
DN 65…150: Flange dimensions for PN 25 only
2)
Flange type: 21; flange design: B (see "Flange types", page 72)
3)
Suitable for medium temperatures up to 150 °C
4) 3
Valve characteristics for pressure compensated valves for k vs value 63 m /h from 90 % stroke,
3
kvs value 100,150 and 220 m /h from 80 % stroke is optimized for maximum volumetric flow.
5)
Suitable for medium temperatures up to 130 °C
Stroke 20 mm 40 mm
Actuators Data Positioning 800 N 1000 N 2800 N 2800 N
Sheet force
SAX.. N4501
PN 6
SKD.. N4561
1)
SKB.. N4564
SKC.. N4566
22 / 94
2)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4402 DN kvs SV Δpmax Δpmax Δpmax Δpmax
[kPa]
A AB AB A A AB AB A A AB AB A A AB AB A
3
-10…150 °C Stock number [m /h] B B B B B B B B
23 / 94
2)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4403 DN kvs SV Δpmax Δpmax Δpmax Δpmax
[kPa]
A AB AB A A AB AB A A AB AB A A AB AB A
3
-10…150 °C Stock number [m /h] B B B B B B B B
24 / 94
5) 2)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4404 DN kvs SV Δpmax Δpmax Δpmax Δpmax
[kPa]
A AB AB A A AB AB A A AB AB A A AB AB A
3
-20…220 °C Stock number [m /h] B B B B B B B B
3)
VXF53.15-.. S55208-.. 15 1.6/2.5/4
3)
VXF53.20-.. S55208-.. 20 6.3 1200 1200
3)
VXF53.25-.. S55208-.. 25 6.3/10 1200
3) > 100 200 200 200 - -
VXF53.32-.. S55208-.. 32 16 750 1100
3)
VXF53.40-.. S55208-.. 40 16/25 500 650
3)
VXF53.50-.. S55208-.. 50 40 300 400 1150
4)
VXF43.65-63 S55206-V115 65 63 650 200
4)
VXF43.80-100 S55206-V116 80 100 400 200
4)
VXF43.100-160 S55206-V117 100 160 > 100 - - - - - - 250 150
4)
VXF43.125-250 S55206-V118 125 250 160 100
VXF43.150-400 S55206-V119 150 400 100 70
1)
Flange type: 21; flange design: B (see "Flange types", page 72)
2)
Suitable for medium temperatures up to 150 °C
3)
See VXF53.., PN 25 (data sheet N4405): Flange dimensions for PN 25 are the same as for PN 16
4)
Valve is optimized for maximum volumetric flow:
- kvs value 63 m3/h from 90 % stroke,
- kvs values 100, 160 and 250 m3/h from 80 % stroke
5)
Suitable for medium temperatures up to 130 °C
Stroke 20 mm 40 mm
Actuators Data Sheet Positioning 800 N 1000 N 2800 N 2800 N
force
5)
PN 25 SAX.. N4501
1) 3)
PN 16 SKD.. N4561
2)
SKB.. N4564
SKC.. N4566
5) 3)
Data Sheet SAX.. SKD.. SKB.. SKC..
N4405 DN kvs SV Δpmax Δpmax Δpmax Δpmax
[kPa]
A AB AB A A AB AB A A AB AB A A AB AB A
3
-20…220 °C Stock number [m /h] B B B B B B B B
25 / 94
Stroke 20 mm
Actuators Data Sheet Positioning 800 N 1000 N 2800 N
force
2)
SAX.. N4501
PN 16
SKD.. N4561
SKB.. N4564
2)
Data Sheet SAX.. SKD.. SKB..
N4463 Δpmax Δpmax Δpmax
Threaded [kPa]
-25…150 °C DN kvs SV connection A AB AB A A AB AB A A AB AB A
1) 1) 3 B B B B B B
Typ Art.-Nr. Typ Art.-Nr. [m /h] [Inch]
- - VXG41.1301 VXG41.1301 15 1.6 G 1B
>
- - VXG41.1401 VXG41.1401 15 2.5 G 1B
50
VXG41.15 VXG41.15 VXG41.1501 VXG41.1501 15 4 G 1B
800 200 800 200 200
VXG41.20 VXG41.20 VXG41.2001 VXG41.2001 20 6.3 G 1¼B
800
VXG41.25 VXG41.25 VXG41.2501 VXG41.2501 25 10 G 1½B
>
VXG41.32 VXG41.32 VXG41.3201 VXG41.3201 32 16 G 2B
100
VXG41.40 VXG41.40 VXG41.4001 VXG41.4001 40 25 G 2¼B 525 150 775 150 150
VXG41.50 VXG41.50 VXG41.5001 VXG41.5001 50 40 G 2¾B 300 100 450 100 200
1)
These types, as a standard, are equipped with a tight bypass. DVGW and SVGW verified DVGW
applications according to drinking water regulation 2001. For medium temperatures up to 90 °C
2)
Suitable for medium temperatures up to 130 °C
Stroke 20 mm
Actuators Data Positioning force 800 N 1000 N
Sheet
SAX.. N4501
PN 16
SKD.. N4561
1)
Data Sheet SAX.. SKD..
N4362 DN kvs SV Threaded connection Δpmax Δpmax
[kPa]
A AB AB A A AB AB A
3
-25…150 °C Artikelnummer [m /h] [Inch] B B B B
26 / 94
Spring
Product Positioning Operating Positioning Manual Auxiliary
Stock number Stroke return Positioning time LED
number force voltage signal adjuster functions
time
SAX31.00 S55150-A105 120 s
AC 230 V 3-position - 1)
SAX31.03 S55150-A106
0…10 V - Press and fix
30 s
SAX61.03 S55150-A100 20 mm 800 N 4…20 mA
2) 3)
AC 24 V 0…1000 Ω ,
DC 24 V
SAX81.00 S55150-A102 120 s 1)
3-position - - Press and fix
SAX81.03 S55150-A103 30 s
Opening: 30 s
SKD32.21 SKD32.21 8s
Closing: 10 s
1)
AC 230 V 3-position -
SKD32.50 SKD32.50 -
120 s
SKD32.51 SKD32.51 8s
SKD60 SKD60 -
0…10 V Turn, position
2)
SKD62 SKD62 20 mm 1000 N Opening: 30 s
4…20 mA is maintained
SKD62U SKD62U 15 s Closing: 15 s
0…1000 Ω
4)
SKD62UA SKD62UA
AC 24 V
SKD82.50 SKD82.50
-
SKD82.50U SKD82.50U 1)
3-position 120 s -
SKD82.51 SKD82.51
8s
SKD82.51U SKD82.51U
SKB32.50 SKB32.50 - 1)
AC 230 V 3-position 120 s -
SKB32.51 SKB32.51 10 s
SKB60 SKB60 -
0…10 V 2)
SKB62 SKB62 Opening: 120 s
4…20 mA
SKB62U SKB62U 10 s Closing: 20 s Turn, position
20 mm 2800 N 0…1000 Ω
SKB62UA is maintained 4)
SKB62UA
AC 24 V
SKB82.50 SKB82.50
-
SKB82.50U SKB82.50U 1)
3-position 120 s -
SKB82.51 SKB82.51
10 s
SKB82.51U SKB82.51U
SKC32.60 SKC32.60 - 1)
AC 230 V 3-position 120 s -
SKC32.61 SKC32.61 18 s
SKC60 SKC60 -
0…10 V 2)
SKC62 SKC62 Opening: 120 s
4…20 mA
SKC62U SKC62U 20 s Closing: 20 s Turn, position
40 mm 2800 N 0…1000 Ω
SKC62UA SKC62UA is maintained 4)
AC 24 V
SKC82.60 SKC82.60
-
SKC82.60U SKC82.60U 1)
3-position 120 s -
SKC82.61 SKC82.61
18 s
SKC82.61U SKC82.61U
1)
Auxiliary switch, potentiometer
2)
Position feedback, forced control, selection of valve characteristic
3)
Optional: Sequence control, selection of acting direction
4)
Plus sequence control, stroke limitation, and selection of acting direction
27 / 94
Delivery Actuator, valve and accessories are packed and supplied as separate items.
2.5 Accessories
2.5.1 Electrical accessories
ASZ6.6 S55845-Z108 Stem heating element Required for medium temperatures < 0 °C
Note When using a stem heating element and the medium temperature is below –5 °C,
Valve lines V..F43/53.. the stem sealing gland must be replaced. In that case, the sealing gland must be
ordered also (stock number 4 284 8806 0).
Product Stock
Description Remark
number number
When using valves of the V..F43.. or V..F53.. lines with a stem heating
element and a medium temperature of below -5 °C, the stem sealing
- 428488060 Sealing gland gland must be replaced. With the gland 428488060 the valve can be
used with water, water with antifreeze and brines between -20 °C and
+ 150 °C.
28 / 94
29 / 94
Threaded connection
G Rp
Product Stock Product Stock
number number number number Description VVG41.. [Inch] [Inch]
VXG41..
Note Fittings for drinking water applications according to DVGW, drinking water
ordinance 2001, have to be purchased locally from specialized trade.
The valves covered by this document replace the valves of the VVF../VXF.. lines
that have been produced by Siemens, Landis & Staefa and Landis & Gyr since
1974.
Stem coupling for The tables below list former valve types and their successors. There is also an
SKC32../62/82.. online replacement guide "Old2New" available; for access, go to
(stock no. 4 178 5649 8)
www.siemens.com/hit under "Old2New replacement guide".
30 / 94
Note When using valves of the V..F43.. or V..F53.. lines with a stem heating element and
a medium temperature of below -5 °C, the stem sealing gland must be replaced. In
that case, the sealing gland must be ordered also (stock number 4 284 8806 0).
Note Valves of the VVF45.. line close with the pressure, which means that when used in
Valve line VVF45.. combination with SKB.. or SKC.. actuators, very high closing pressures are
permitted. If such closing pressures are indeed required, valves of the VVF43..K
line should be used as a replacement
Note The follow-on series VVF32 supports only select kVS values. For smaller kVS values,
Valve line VVF31.. it makes more sense to replace the VVF31.. valve with series VVF42..valves. The
from DN50 kVS values for services VVF42.. must support the kvs value for VVF31 valves.
The valves series VVF31 and VVF42 are identical regarding face-to-face
dimension, flange bolt circle and flange bolt dimensions.
31 / 94
Note When using valves of the V..F43.. or V..F53.. lines with a stem heating element and
the medium temperature is below -5 °C, the stem sealing gland must be replaced.
In that case, the sealing gland must be ordered also (stock number 4 284 8806 0).
Notes When replacing old valves by new valves, the installation might have to be
modified.
Valve lines The dimension of the bypass is smaller than that of the valves of the former
VXF53../VXF43.. VXF41.. line. This means that a one-to-one replacement of the VXF41.. valves
requires an ALF41B.. adapter. This adapter compensates for the difference in
dimensions, thus facilitating replacement of the valve without having to modify the
piping. The washer to fit the existing SKC actuator to the new valve with 10 mm
stem diameter is added to the ALF41B65 to ..150.
Notes The follow-on series VXF32 supports only select kVS values. For smaller kVS values,
Valve lines VXF31.. it makes more sense to replace the VXF31.. valve with series VXF42..valves. The
from DN50 kVS values for services VXF42.. must support the kvs value for VXF31 valves.
The valves series VXF31 and VXF42 are identical regarding face-to-face
dimension, flange bolt circle and flange bolt dimensions.
32 / 94
ASZ6.5 ASZ6.5
Required for medium temperatures
Not available for Not available Stem heating element
< 0 °C
order for order
Note The ASZ6.5 stem heating element was compatible with actuators SKB.., SKC..,
SKD.., and SQX... Always replace the installed steam heating element with the
ASZ6.6 (S55845-Z108) as needed. However, in the event the actuator needs
replacement as well when replacing the valve, ASZ6.5 stem heating elements
must be replaced by ASZ6.6 on SAX series valves.
33 / 94
34 / 94
Header with pressure and variable Header with pressure and constant volumetric flow,
volumetric flow or
Header with low differential pressure and variable
volumetric flow
Continue with Δp VR Continue with ΔpMV
3 Determine ΔpV100 p VR
p V100 p V100 pMV
2
4 Determine the volumetric flow Determine V100 depending on the type of medium
V100 Water without antifreeze: Water with antifreeze, heat transfer oil:
Q Q 3600
V 100 100
100
100
V
1.163 T c T
For steam, see "2.9 Sizing valves for steam", page 40
5 Determine the kvs value There are different ways to determine the kvs value:
Flow chart By way of calculation HIT sizing and Valve slide
selection: rule
V 100
kV www.siemens.com/hit
p V100
100
Determine the kvs value according to:
1)
0.85 k V value k VS value
or within the following band:
0,74 k VS value k V 1.175 k VS value
This procedure shows the mathematical approach. The following examples make use of the flow chart
and show the way of calculation
6 Check the resulting The resulting differential pressure Δp V100 is used for calculating the valve authority P V:
differential pressure Δp V100 V
2
35 / 94
Valves are sized based on the volumetric flow passing through them. The most
important characteristic of a valve is its kvs value. Since this value is determined
with water at a temperature of 5…30 °C and a differential pressure Δp of 100 kPa
(1 bar), additional influencing factors must be taken into consideration if the
properties of the medium passing through the valve are different.
36 / 94
2.8.3.1 Density ρ
The amount of heat Q carried by a fluid depends on the available mass flow m, the
specific heat capacity c, and the temperature spread ΔT:
m
Q c T
In the HVAC field, calculations are usually based on the volumetric flow V, resulting
from the available mass flow m and the density ρ:
V c T
Q
Within the temperature range normally used in the HVAC field, the density ρ of
3
water is assumed to be about 1000 kg/m and the specific heat capacity c 4.19
kJ/(kg·K). This makes it possible to apply a simplified formula with a constant of
3 3
1.163 kWh/(m ·K) for calculating the volumetric flow V in m /h:
Q
V
1.163 T
The rated capacity Q100 of a plant with the valve fully open is calculated with the
following formula:
Q
V 100 100
1.163 T
For watery solutions, such as mixtures of water and antifreeze, or other fluids like
heat transfer oils, refer to the chapters below.
The amount of heat Q carried by a fluid depends on the available mass flow m, the
specific heat capacity c, and the temperature spread ΔT.
Within the temperature range normally used in the HVAC field, the specific heat
capacity c of water changes only slightly. Therefore, the approximate value used
for the specific heat capacity c is 4.19 kJ/(kg·K). This makes it possible to apply a
simplified formula with a constant of 1.163 kWh/(m3·K) for calculating the
volumetric flow V in m 3/h:
Q
V
1.163 T
If watery solutions, such as mixtures of water and antifreeze, or other fluids like
heat transfer oils are used for the transmission of heat, the required volumetric flow
V is to be calculated with the density ρ and the specific heat capacity c at the
operating temperature:
Q
V
c T
The specific heat capacity of fluids is specified in trade literature. For mixtures, the
specific heat capacity c is calculated on the basis of the mixture’s mass proportions
m1 and m2:
37 / 94
In the case of heating applications, the specific heat capacity c1 or c2 at the highest
temperature must be used, and in the case of cooling applications that at the
lowest temperature.
The kinematic viscosity ν affects the type of flow (laminar or turbulent) and thus the
friction losses inside the valve. It has a direct impact on the differential pressure at
a given volumetric flow.
2
The kinematic viscosity ν is specified either in mm /s or centistokes (cSt):
1 cSt = 10-6 m2/s = 1 mm2/s
When sizing valves for media with other kinematic viscosities ν, a correction must
2
be made. Up to a kinematic viscosity ν of less than 10 mm /s, the impact is
negligible since it is smaller than the permissible tolerance of the kvs value (+/-
10 %).
In general practice, the correction is made by applying a correction factor FR, which
gives consideration to the different flow and friction conditions when calculating the
kvs value.
FR is the factor used for the impact of the valve’s Reynolds number. It must be
applied when there is nonturbulent flow in the valve, when the differential pressure
is low, for example, in the case of high-viscosity fluids, very low flow coefficients, or
combinations of them. It can be determined by way of experiment.
FR = flow coefficient for nonturbulent flow conditions divided by the flow coefficient
ascertained under the same plant conditions for turbulent flow
(EN 60534-2-1[1998])
38 / 94
Group of fluids
Water No No No (FR = 1)
Water with antifreeze Yes Yes Yes
Heat transfer oils Yes Yes Yes
Brines Yes Yes Yes
Notes on water and The HVAC Integrated Tool (HIT) supports sizing and selection of valves for water
water with antifreeze and water with antifreeze (www.siemens.com/hit).
Notes on heat transfer When sizing valves for use with heat transfer oils or brines, the medium properties
oils and brines specified by the suppliers must be taken into account:
Specific heat capacity c
Kinematic viscosity ν
Specific density ρ
During the heating up phase, the kinematic viscosity ν can reach a high level
while the volumetric flow V and thus the available amount of heat Q heating up phase
are much smaller than planned. This must be taken into account during the
planning phase and when sizing the valves, see "2.10.3 Example for heat
transfer oil", page 45.
39 / 94
When sizing and selecting a valve, it must be ensured that – in the controlled
operating state – the output does not drop below the minimum controllable output
Qmin. Otherwise, the controlling element only regulates in on/off mode within the
range of the initial flow surge. On/off mode reduces the plant’s energy efficiency
and adversely affects the controlling element’s life.
For more detailed information on the subject, refer to the brochure "Hydraulics in
building systems" (ordering no. 0-91917-en).
Since steam is compressible, valve sizing for steam must be based on other
criteria. The most important characteristic of compressible flow is that the speed of
flow in the throttling section can only increase up to the speed of sound. When this
limit is reached, the speed of flow and thus the volumetric flow, or the steam mass
flow, no longer increases, even if the differential pressure ∆p rises. To ensure good
controllability and favorably priced valve selection, it is advisable to have the
differential pressure in normal operation as close as possible to the critical
pressure ratio.
Before starting valve sizing, the plant-related process parameters and the
prevailing operating state must be defined:
Absolute steam pressure [kPa abs], [bar abs]
Temperature of saturated or superheated steam [°C]
Differential pressure ∆pmax in normal operation
The dryness of saturated steam at the valve’s inlet must be > 0.98.
Sizing procedure 1. Calculate the steam mass flow m based on the amount of energy required
Q100, the steam pressure, and the steam temperature.
2. Determine whether the pressure ratio is in the sub- or supercritical range.
3. Determine the kvs value based on the steam mass flow and the steam
pressure.
Q100 3600
m
p1 p3
100%
Steam mass flow rp1 Pressure ratio = p1
40 / 94
Note The level of absolute pressure p1 at the valve inlet must be at least such that the
absolute pressure p3 at the valve outlet is higher than the atmospheric pressure.
Notes on the When there is a pressure ratio (p1 – p3) / p1 >0.42, the flow passing through the
supercritical range narrowest section of the valve reaches the speed of sound. This can lead to higher
noise levels. A throttling system operating at a lower noise level (multistage
pressure reduction, damping throttle by the outlet) alleviates the problem.
Subcritical < 42 % Steam-controlled heat transfer medium without condensation
Shutoff valve on the steam side of condensation-controlled heat transfer media
Recommendation for For saturated and superheated steam, the differential pressure pmax across the
differential pressure valve should be as close as possible to the critical pressure ratio.
pmax
Chart example: The chart of the
Abs. operating pressure [bar]
1 Water -
2 Wet steam To be avoided
3 Saturated steam Permissible operating
1Superheated steam range
41 / 94
Pressure Temperature Spec. volume Spec. volume Density steam Enthalpy water Enthalpy Heat of
water steam steam vaporization
p p T V' V'' ρ'' h' h'' r
3 3 3]
[kPa] [bar] [°C] [dm /kg] [m /kg] [kg/m [kJ/kg] [kJ/kg] [kJ/kg]
1 0.010 6.9808 1.0001 129.20 0.007739 29.34 2514.1 2485.0
2 0.020 17.513 1.0012 67.01 0.01492 73.46 2533.6 2460.2
3 0.030 24.100 1.0027 45.67 0.02190 101.00 2545.6 2444.6
4 0.040 28.983 1.0040 34.80 0.02873 121.41 2554.5 2433.1
5 0.050 32.898 1.0052 28.19 0.03547 137.77 2561.6 2423.8
6 0.060 36.183 1.0064 23.74 0.04212 151.50 2567.5 2416.0
7 0.070 39.025 1.0074 20.53 0.04871 163.38 2572.6 2409.2
8 0.080 41.534 1.0084 18.10 0.05523 173.86 2577.1 2403.2
9 0.090 43.787 1.0094 16.20 0.06171 183.28 2581.1 2397.9
10 0.10 45.833 1.0102 14.67 0.06814 191.83 2584.8 2392.9
20 0.20 60.086 1.0172 7.650 0.1307 251.45 2609.9 2358.4
30 0.30 69.124 1.0223 5.229 0.1912 289.30 2625.4 2336.1
40 0.40 75.886 1.0265 3.993 0.2504 317.65 2636.9 2319.2
50 0.50 81.345 1.0301 3.240 0.3086 340.56 2646.0 2305.4
60 0.60 85.954 1.0333 2.732 0.3661 359.93 2653.6 2293.6
70 0.70 89.959 1.0361 2.365 0.4229 376.77 2660.1 2283.3
80 0.80 93.512 1.0387 2.087 0.4792 391.72 2665.8 2274.0
90 0.90 96.713 1.0412 1.869 0.5350 405.21 2670.9 2265.6
100 1.0 99.632 1.0434 1.694 0.5904 417.51 2675.4 2257.9
150 1.5 111.37 1.0530 1.159 0.8628 467.13 2693.4 2226.2
200 2.0 120.23 1.0608 0.8854 1.129 504.70 2706.3 2201.6
250 2.5 127.43 1.0675 0.7184 1.392 535.34 2716.4 2181.0
300 3.0 133.54 1.0735 0.6056 1.651 561.43 2724.7 2163.2
350 3.5 138.87 1.0789 0.5240 1.908 584.27 2731.6 2147.4
400 4.0 143.62 1.0839 0.4622 2.163 604.67 2737.6 2133.0
450 4.5 147.92 1.0885 0.4138 2.417 623.16 2742.9 2119.7
500 5.0 151.84 1.0928 0.3747 2.669 640.12 2747.5 2107.4
600 6.0 158.84 1.1009 0.3155 3.170 670.42 2755.5 2085.0
700 7.0 164.96 1.1082 0.2727 3.667 697.06 2762.0 2064.9
800 8.0 170.41 1.1150 0.2403 4.162 720.94 2767.5 2046.5
900 9.0 175.36 1.1213 0.2148 4.655 742.64 2772.1 2029.5
1'000 10 179.88 1.1274 0.1943 5.147 762.61 2776.2 2013.6
1'100 11 184.07 1.1331 0.1774 5.637 781.13 2779.7 1998.5
1'200 12 187.96 1.1386 0.1632 6.127 798.43 2782.7 1984.3
1'300 13 191.61 1.1438 0.1511 6.617 814.70 2785.4 1970.7
1'400 14 195.04 1.1489 0.1407 7.106 830.08 2787.8 1957.7
1'500 15 198.29 1.1539 0.1317 7.596 844.67 2798.9 1945.2
1'600 16 201.37 1.1586 0.1237 8.085 858.56 2791.7 1933.2
1'700 17 204.31 1.1633 0.1166 8.575 871.84 2793.4 1921.5
1'800 18 207.11 1.1678 0.1103 9.065 884.58 2794.8 1910.3
1'900 19 209.80 1.1723 0.1047 9.555 896.81 2796.1 1899.3
2'000 20 212.37 1.1766 0.09954 10.05 908.59 2797.2 1888.6
2'500 25 223.94 1.1972 0.07991 12.51 961.96 2800.9 1839.0
3'000 30 233.84 1.2163 0.06663 15.01 1008.4 2802.3 1793.9
4'000 40 250.33 1.2521 0.04975 10.10 1087.4 2800.3 1712.9
5'000 50 263.91 1.2858 0.03743 25.36 1154.5 2794.2 1639.7
6'000 60 275.55 1.3187 0.03244 30.83 1213.7 2785.0 1571.3
7'000 70 285.79 1.3513 0.02737 36.53 1267.4 2773.5 1506.0
8'000 80 294.97 1.3842 0.02353 42.51 1317.1 2759.9 1442.8
9'000 90 303.31 1.4179 0.02050 48.79 1363.7 2744.6 1380.9
10'000 100 310.96 1.4526 0.01804 55.43 1408.0 2727.7 1319.7
11'000 110 318.05 1.4887 0.01601 62.48 1450.6 2729.3 1258.7
12'000 120 324.65 1.5268 0.01428 70.01 1491.8 2689.2 1197.4
13'000 130 330.83 1.5672 0.01280 78.14 1532.0 2667.0 1135.0
14'000 140 336.64 1.6106 0.01150 86.99 1571.6 2642.4 1070.7
15'000 150 342.13 1.6579 0.01034 96.71 1611.0 2615.0 1004.0
20'000 200 365.70 2.0370 0.005877 170.2 1826.5 2418.4 591.9
22'000 220 373.69 2.6714 0.003728 268.3 2011.1 2195.6 184.5
22'120 221.2 374.15 3.17 0.00317 315.5 2107.4 2107.4 0
42 / 94
Pressure class PN 16
Control DC 0…10 V
Operating voltage AC 24 V
By way of calculation
V 2.36 m3 / h
kv 100
5.7 m3 / h
p V100 17 kPa
100 100
3 3 3 3
kvs value ≥ 0.85 • 5.7 m /h = 4.8 m /h kvs value = 5 m /h or 6.3 m /h
3
1. kvs value: 5 m /h
3
2. kvs value: 6.3 m /h
7 Select suitable line of valves 2-port valve (resulting from the basic hydraulic circuit)
Flanged (specified by the planner)
PN class 16 (specified by the planner)
Nominal size DN (resulting from the selected valve)
Maximum medium temperature: 60 °C
Type of medium: Water
43 / 94
Pressure class PN 16
Control 3-position
Operating voltage AC 230 V
1 Heating group 1
2 Boiler 1
By way of calculation
V 4 m3 / h
kv 100
12.1m3 / h
p V100 11kPa
100 100
3 3 3
kvs value ≥ 0.85 • 12 m /h = 10.2 m /h kvs value = 10 m /h
3
kvs value: 10 m /h
44 / 94
7 Select suitable line of valves 2-port valve (resulting from the basic hydraulic circuit)
Flanged (specified by the planner)
PN class 16 (specified by the planner)
Nominal size DN (resulting from selected valve)
Maximum medium temperature: 60 °C
Type of medium: Water
Selection: VXF53.25-10
8 Check the valve authority P V Check P V using the resulting differential pressure Δp V100:
(control stability) p V100 16 kPa
PV 0.59
p V100 pMV 16 kPa 11kPa
As outlined in chapter "2.8.3 Impact of fluid properties on valve sizing", page 36,
when sizing a valve, the density ρ, the specific heat capacity c, and the kinematic
viscosity ν must be taken into consideration. Also, to ensure correct and efficient
operation, a closer look should be taken at the controlled mode and the startup
mode.
Properties
When planning and commissioning a plant or when sizing valves, the suppliers’
specifications must be observed. The experience and know-how of the suppliers
help select the right type of heat transfer oil.
45 / 94
Differential pressure Δp V100 With pressure and variable volumetric flow Must be calculated
p VR
p V100
2
ΔpV100 = 25 kPa (0.25 bar)
Flow temperature T VL 280 °C Approx. 20 °C
2 2
Kinematic viscosity ν At 300 °C: 0.58 mm /s 50.5 mm /s
Correction factor FR At 280 °C: 1 At 20 °C: 0.75
Kinematic viscosity υ <10 mm /s
2 Interpolated according to the correction factor
table on page 39
Determine the kvs value 100
V 1 -
kV
FR p100
100
FR = 1
V 1.97 m3 / h
kv 100
3.94 m3 / h
p V100 25 kPa
100 100
25 kPa 25 kPa
V 100 5 m3 / h 1 V 100 5 m3 / h 0.75
100 100
V 2.5 m / h
100 1.9 m / h
3 3
100 V
In the heating up phase, the volumetric flow is
reduced by 5 %!
Select the 2-port valve VVF61.242
46 / 94
As outlined in chapter "2.9 Sizing valves for steam", page 40, it must be
determined first whether a supercritical or subcritical pressure ratio exists in the
plant.
30 % 500 kPa
p3 500kPa 350 kPa (3.5bar)
100%
460 kg / h 460 kg / h
k v 4.4 1 k v 8.8 1
350kPa (500kPa 350kPa ) 500 kPa
3
kv = 8.83 m /h
3 kv = 8.09 m /h
3 3
Selected kvs = 10 m /h VVF53.25-10 kvs = 8 m /h VVF53.25-8
Solution 1. Vertical line upward to an absolute prepressure p1 = 1.5 bar (150 kPa).
2. Horizontal line to the right to the point of intersection 1.5 bar (15 kPa) and differential
pressure 0.4 bar (40 kPa).
3. Vertical line downward to 75 kg/h.
4. Point of intersection kvs value
Select available kvs value of VVF.. valve lines.
3
5. Selected kvs value: 5 m /h.
3
Selected kvs value: 5 m /h VVF53.25-5
47 / 94
Example 2:
Saturated
steam
48 / 94
0…30 %: Linear
Stroke H / H100
For valves:
VVF32.125-250
VVF42.125-250
Flow rate kv / kvs
VVF42.125-250K
VVF43.125-200
VVF43.125-250
VVF43.125-220K
VVF53.125-250 0…100 %: Linear
VVF53.125-220K
VVF32.150-400
VVF42.150-400
VVF42.150-360K
VVF43.150-400
VVF43.150-315K Stroke H / H100
VVF53.150-400
VVF53.150-315K
2.11.2 3-port valves
Throughport A-AB
0...30 %: Linear
30...100 %: Equal-percentage
Flow rate kv / kvs
Bypass B-AB
VXF53.125-250
VXF32.150-400 0...100 %: Linear
VXF42.150-400
VXF43.150-400
VXF53.150-400
Stroke H / H100
49 / 94
ISO 7005 and EN 1092 cover PN-classified, round flanges for pipes, valves, plain
fittings and accessories, plus their dimensions and tolerances, categorized
according to different types of materials.
Both standards also contain the assignment of pressures and medium
temperatures.
The connecting dimensions, flange and face types plus descriptions conform to the
relevant ISO 7005 standards.
Since the valves covered by this document are used throughout the world, the
international standard ISO 7005 was selected as a basis. The information given
below explains the differences between ISO 7005 and EN 1092.
EN 1092: Part 1, The international standard ISO 7005-1 on steel flanges was used as a basis for the
steel flanges development of EN 1092. EN 1092 deviates from ISO 7005 in the following ways:
It solely covers flanges with PN designation
A number of technical requirements of flanges originating from DIN standards
have been changed
The differences between EN 1092-1 and ISO 7005-1 are as follows:
In many cases, the pressure-temperature assignments of this standard have
been reduced, either by limiting the assignments at lower temperatures – which
may no longer exceed the value of the PN class – or by increasing the rate at
which the admissible pressure drops on temperature rise
In addition to the PN 2.5 – PN 40 range of flanges originating from DIN
standards, which is defined in ISO 7005, EN 1092 also contains flanges up to
PN 400
EN 1092: Part 2, In terms of flanges of the same PN class, this standard refers to ISO 7005-2 and
cast iron flanges ISO 2531. Flange types and connecting dimensions are compatible with the same
DN and PN class of ISO 7005 and ISO 2531.
Pressure-temperature assignments: There are no differences between EN 1092-
2 and ISO 7005-2
EN 1092: Part 3, flanges In terms of flanges of the same PN class, this standard refers to ISO 7005-3.
made of copper alloys Flange types and connecting dimensions are compatible with the same DN and PN
class of ISO 7005.
Pressure-temperature assignments: There are no differences between EN 1092-
3 and ISO 7005-3
50 / 94
Fluids
Operating pressure and operating temperatures as per ISO 7005 and EN 1092
Fluids
Operating pressure [bar]
with V..F32..
V..F42..
Operating pressure and operating temperatures as per ISO 7005 and EN 1092
51 / 94
Fluids
Fluids
16
with V..F43..
Operating pressure [bar]
15
V..F53..
14
13
12
1
0
-20 0 20 80 100 120 140 160 180 200 220 240
Medium temperature [°C]
Curve for saturated steam; steam forms below this line
Operating pressure according to EN 1092, valid for 2-port valves with
blank flange
Operating pressure and operating temperatures as per ISO 7005, EN 1092
and EN 12284
Notes V..F53..: Applies when these valves are used in PN 16 plants
All relevant local directives must be observed
52 / 94
Fluids
V..F53.. 25
24
23
Operating pressure [bar]
22
21
20
19
18
1
0
-20 -10 0 20 80 100 120 140 160 180 200 220 240
Medium temperature [°C]
Curve for saturated steam; steam forms below this line
Operating pressure according to EN 1092, valid for 2-port valves with
blank flange
53 / 94
1 Water -
2 Wet steam To be avoided
3 Saturated steam
Permissible operating range
Superheated steam
A Subcritical pressure ratio
B Supercritical pressure ratio
54 / 94
1 2
SKD..
SAX..
VVI41..
Abs. operating pressure [bar]
1 2
55 / 94
Progression of speed
Progression of pressure p
56 / 94
Note To avoid cavitation in the case of cold water circuits, it must also be made certain
that there is sufficient static counter-pressure at the valve’s outlet. This can be
ensured by installing a throttling valve downstream from the heat exchanger, for
example. In that case, the maximum pressure drop across the valve should be
selected according to the 80 °C curve in the flow chart above on page 56.
All relevant local directives must be observed whenever it comes to water quality,
corrosion or contamination.
2.14.1 Water
Note Water treatment as per VDI 2035 to avoid boiler scale and damage due to
corrosion on the water side
The requirements of DIN EN 12953-10 should be observed
Local guidelines and directives should be observed
Installation and The company making the installation is responsible for the water quality in HVAC
commissioning plants
Before filling a hydraulic HVAC circuit with water, the installer must observe the
specifications of suppliers regarding water quality. If such specifications or
regulations are not observed, severe damage to the plant can occur
When commissioning a plant, the company that made the installation is obliged
to write a commissioning report including information about water quality and
filling (plant volume) and, if necessary, about water treatment and the additives
used
Maintenance and The installer should check hydraulic HVAC circuits at least once a year.
service
Before adding water to a hydraulic HVAC circuit, the installer must observe the
specifications of suppliers regarding water quality (water treatment as per VDI
2035). If such specifications or regulations are not observed, severe damage to the
plant can occur.
When adding water at a later stage, the company that made the installation is
obliged to write a commissioning report including information about water quality
and the filling (plant volume) and, if necessary, about water treatment and the
additives used.
57 / 94
Note For water with antifreeze, such as ethylene glycol or propylene glycol, the supplier-
specific values for the density ρ, the specific heat capacity c, and the kinematic
viscosity ν are to be determined by way of concentration and medium temperature.
These values must be observed when sizing valves to make certain that correct kvs
values are obtained.
2
In the case of antifreeze concentrations with a kinematic viscosity of < 10 mm /s,
correction factors for the sizing of valves are not required. Refer to chapter "2.8.3
Impact of fluid properties on valve sizing", page 36.
Planning The type of antifreeze (product and dosage) added to the system must be
approved by the supplier for use in HVAC plants
If several additives are used (e.g. antifreeze and hardness stabilizers), the
required combination must be approved by the same supplier
Install a strainer (dirt trap)
Installation and The company making the installation is responsible for the correct antifreeze
commissioning concentration and water quality in HVAC plants
Before filling a hydraulic HVAC circuit with a medium, the installer must observe
the specifications of the supplier. If such specifications or regulations are not
observed, severe damage to the plant can occur
When commissioning a plant, the company that made the installation is obliged
to write a commissioning report including information about water quality,
antifreeze concentration and filling (plant volume) and, if necessary, about water
treatment and the additives used
Maintenance and The installer should check hydraulic HVAC circuits at least once a year.
service According to supplier specifications, the antifreeze concentration, the pH value,
and the concentration of inhibitors must be checked once a year, for example.
Recommendation The antifreeze concentration and water quality in open or closed HVAC plants must
be checked at regular intervals. The plant record must always be kept up to date.
58 / 94
Note These media have an impact on valve selection (material of O-rings, gaskets,
plug/seat, and valve body). Compatibility must be checked.
Deionized water Demineralized water Super-clean water
The ions of salts The minerals contained in Intensely treated water with a high specific
contained in the water the water have been resistance and containing no organic
have been removed removed substances
To avoid corrosion and to ensure a long service life of the valves, gaskets and
plugs, the following limits must be observed:
Oxygen: < 0.02 mg/l
pH value: 8.2…8.5
Electric conductance: < 5 Si
Sum of alkaline earths: < 0.0051 mmol/l
Hardness: < 0.03 °dH
Planning The media must be approved by the supplier for use in HVAC plants
Install a strainer (dirt trap)
Installation and The company making the installation is responsible for the quality of the media
commissioning used
Before filling a hydraulic HVAC circuit with a medium, the installer must observe
the supplier’s specification. If such specifications or regulations are not
observed, severe damage to the plant can occur
When commissioning a plant, the company that made the installation is obliged
to write a commissioning report including information about medium quality and
filling (plant volume) and, if necessary, about water treatment and additives used
Maintenance, service The installer should check hydraulic HVAC circuits at least once a year.
Recommendation The quality of the medium used in open or closed HVAC plants must be checked at
regular intervals. The plant record must always be kept up to date.
59 / 94
Note Heat transfer oil has an impact on valve selection (material of O-rings and
gaskets). Compatibility must be checked.
When planning and commissioning a plant or when sizing valves, the suppliers’
specifications must be observed. To make certain the right type of heat transfer oil
is used, one should rely on the suppliers’ experience and know-how.
When using heat transfer oil (thermal oil), the following supplier-specific values
must be taken into consideration:
Correction factor FR, if the supplier-specific kinematic viscosity ν exceeds
2
10 mm /s
Density ρ
Room and operating temperature
During the heating up phase, the kinematic viscosity ν is very high. The
volumetric flow is much smaller than planned and thus the available amount of
energy Qheating up phase as well. This must be taken into account during the
planning phase and when sizing the valve
Refer to chapter "2.8.3 Impact of fluid properties on valve sizing", page 36.
Installation and The company making the installation is responsible for the quality of the media
commissioning used
Before filling a hydraulic HVAC circuit with a medium, the installer must observe
the supplier’s specification. If such specifications or regulations are not
observed, severe damage to the plant can occur
When commissioning a plant, the company that made the installation is obliged
to write a commissioning report including information about medium quality and
filling (plant volume) and, if necessary, about water treatment and the additives
used
Maintenance and The installer should check hydraulic HVAC circuits at least once a year.
service
Before adding medium to a hydraulic HVAC circuit, the installer must observe the
supplier’s specification. If such specifications or regulations are not observed,
severe damage to the plant can occur.
When adding medium at a later stage, the company that made the installation is
obliged to write a commissioning report including information about the quality of
the medium and the filling (plant volume) and, if necessary, about treatment and
additives used.
Recommendation The quality of the medium in open or closed plants must be checked at regular
intervals. The plant record must always be kept up to date.
60 / 94
Open and closed HVAC plants require a strainer (dirt trap). This improves the
quality of the water, ensures proper functioning of the valve, and a long service life
of the HVAC plant with its components.
When 3-port valves in HVAC plants are fully closed, false circulation can occur
when hot water rises or when water is pulled away near rectangular pipe
connections.
Note False circulation can be avoided by proper planning – with almost no extra cost –
but remedy is usually very costly in existing plants.
Measures against Observe guide value for the water speed: 0.5…1 m/s.
false circulation The lower the water speed, the smaller the risk that the diverted flow pulls water
from the critical piping section. If required, balancing valves can be installed to
improve flow conditions
Observe a certain distance between bypass and collector/header or short-circuit:
H ≥ 10 x pipe dia., minimum 400 mm
or
Installation of a check valve or gravity brake R with small spring pressure in the
critical piping section, aimed at ensuring a minimum flow in the opening range
61 / 94
Recommendation:
Thermal insulation of pipes and
valves conforming to EnEV 2009
62 / 94
When using materials with a heat conductance other than 0.035 W/(m·K), the
minimum thickness of the insulating layers must be appropriately adapted. For the
conversion and heat conductance of insulating material, the calculation methods
and data applied by established technical rules must be used.
2.16 Warranty
Note If the valves are used in combination with actuators supplied by thirds, proper
functioning must be ensured by the user himself and Siemens Building
Technologies will assume no liability.
63 / 94
1)
Indoors Outdoors
1)
Only in combination with weather shield ASK39.1 and actuators SAX..
For general illustration and further details, refer to chapter "4.3 Technical and
mechanical design", page 70.
For use with all actuators For use with all actuators
64 / 94
Hinweis 2-port valves do not become 3-port valves by removing the blank flange!
3.1.3 Flanges
To ensure that flanges are correctly connected, the nominal, maximum and
minimum tightening torques must be observed. They depend on the strength and
size of the bolts and nuts, the material of the flanges, the PN class, the flange
gaskets used and the medium in the hydraulic system.
The tightening torques also depend on the specification of the gasket supplier and
must be observed, using a torque wrench.
65 / 94
66 / 94
Scope of delivery
1 Stem heating element ASZ6.6 1 screw M4 x 30 mm including nut
To fit the stem heating element, stroke actuator and valve must be assembled. The
stem heating element is powered separately.
1 10 mm 14 mm 2
3 4 8 mm
Note When using a stem heating element and medium temperatures are below -5 °C,
Valve lines V..F43/53.. the stem sealing gland must be replaced.
In that case, the sealing gland must be ordered also (stock number 4 284 8806 0).
67 / 94
The valve may be put into operation only if actuator and valve are correctly
assembled.
Note Ensure that actuator stem and valve stem are rigidly connected in all positions.
3.2.2 Maintenance
3.3 Disposal
Before disposal, the valve must be dismantled and separated into its various
constituent materials.
Legislation may demand special handling of certain components, or it may be
sensible from an ecological point of view.
All local and currently valid legislation must be observed.
68 / 94
The valve’s characteristic and acting direction (push to open, pull to open, normally
open, normally closed) have an impact on the acting direction and valve
characteristic selected with the actuator’s DIL switches as well as on the required
function in the event of a power failure (actuator with or without spring return
function).
The objective is the following: As the positioning signal Y increases, the volumetric
flow V through the valve shall rise or, in the event of a power failure, the valve shall
fully open, V = 100 % (NO = normally open), or fully close, V = 0 % (NC = normally
closed), depending on plant requirements.
Actuator
pushing
69 / 94
Calibration must be performed when valve and actuator are correctly assembled.
The illustrations below only show the valves’ basic design; constructional features,
such as the shape of plugs, may differ.
2-port valves Closing against the pressure Closing with the pressure
Note 2-port valves do not become 3-port valves by removing the blank flange!
Depending on the nominal valve size, a guided parabolic, perforated or slot plug is
used – rigidly connected to the valve stem.
The seat is pressed into the valve body together with a special sealing compound.
70 / 94
The valves VVF42...K, VVF43...K and VVF53...K are equipped with a pressure-
compensated plug. Thereby volume flow rates with same actuators at higher
differential pressure can be controlled.
Closing with the pressure
Note 2-port valves do not become 3-port valves by removing the blank flange!
1 Valve stem
2 Valve neck
3 Valve stem coupling
4 Valve neck coupling
2-port valves do not become 3-port valves by removing the blank flange!
71 / 94
Notes In that case, the type plate is no longer in compliance with the valve’s function.
Siemens does not supply replacement type plates.
Flanges, flange dimensions and flange connections conform to ISO 7005 and
EN 1092 respectively.
Flange type Type 21 (integral flange) as per ISO 7005 is an integral component of a pressure
device.
Gaskets In the case of ISO 7005, the gaskets do not constitute part of the standard – in
contrast to EN 1092.
72 / 94
Connecting dimensions The valve series VXF22, VXF32, VXF42, VXF43 and VXF53 have a greater interior
[mm] diameter in bypass port B versus the nominal value. This is not a problem when
Bypass-Port B used with any standard ISO7005 and EN1092 steel flanges but ensure that any
connection method used is explicitly designed for a specific interior diameter is
compatible with this grater interior diameter..
DN D3
Ø Inside diameter bypass-flange
VXF22 VXF32 VXF42 VXF43 VXF53
15 - 23 23 - 25
20 - - 29 - 35
25 36 36 36 - 38
32 - - 46 - 46
40 52 56 56 - 57
50 65 69 69 - 69
65 85 85 85 86 86
80 98 102 102 100 100
100 116 124 124 123 123
125 - 149 149 149 149
150 - 174 174 174 174
73 / 94
74 / 94
75 / 94
VVF22..
Product
DN B ØD Ø D1 Ø D2 L1 L2 L3 ØK H1 H2 H
number
SAX.. SKD.. SKB.. SKC..
VVF22.. 25 4.1 11 100 58 11 (4x) 150 75 99 75 37 133.5 479 537 612 -
40 6.5 13 130 78 14 (4x) 180 90 116 100 37 133.5 479 537 612 -
50 8 14 140 88 14 (4x) 200 100 128 110 50 146.5 492 550 625 -
65 11.9 14 160 108 14 (4x) 240 120 142.5 130 75 171.5 517 575 650 -
80 17.1 16 190 124 19 (4x) 260 130 157 150 75 171.5 517 575 650 -
100 23.8 16 210 144 19 (4x) 300 150 179 170 110 226.5 - - - 685
VVF32..
Product
DN B ØD Ø D1 Ø D2 L1 L2 L3 ØK H1 H2 H
number
SAX.. SKD.. SKB.. SKC..
VVF32.. 15 3.7 14 95 46 14 (4x) 130 65 86 65 37 133.5 479 537 612 -
20 - - - - - - - - - - - - - - -
25 5.4 15 115 65 14 (4x) 160 80 104 85 37 133.5 479 537 612 -
32 - - - - - - - - - - - - - - -
40 9.3 16 150 84 19 (4x) 200 100 126 110 37 133.5 479 537 612 -
50 12.2 16 165 99 19 (4x) 230 115 143 125 50 146.5 492 550 625 -
65 17 17 185 118 19 (4x) 290 145 173 145 75 171.5 517 575 650 -
80 25 17 200 132 19 (8x) 310 155 185 160 75 171.5 517 575 650 -
100 35.7 17 220 156 19 (8x) 350 175 205 180 110 226.5 - - - 685
125 52.5 17 250 184 19 (8x) 400 200 232 210 123 239.5 - - - 698
150 74.3 17 284 211 23 (8x) 480 240 275 240 150.5 267 - - - 726
76 / 94
Product
DN B ØD Ø D1 Ø D2 L1 L2 L3 ØK H1 H2 H
number
SAX.. SKD.. SKB.. SKC..
VVF42.. 15 3.7 14 95 46 14 (4x) 130 65 86 65 37 133.5 479 537 612 -
20 4.7 16 105 56 14 (4x) 150 75 97 75 37 133.5 479 537 612 -
25 5.4 15 115 65 14 (4x) 160 80 106.5 85 37 133.5 479 537 612 -
32 8.4 17 140 76 19 (4x) 180 90 119 100 37 133.5 479 537 612 -
40 9.3 16 150 84 19 (4x) 200 100 126 110 37 133.5 479 537 612 -
50 12.2 16 165 99 19 (4x) 230 115 144 125 50 146.5 492 550 625 -
65 17 17 185 118 19 (4x) 290 145 174 145 75 171.5 517 575 650 -
80 25 17 200 132 19 (8x) 310 155 186 160 75 171.5 517 575 650 -
100 35.7 17 220 156 19 (8x) 350 175 205 180 110 226.5 - - - 685
125 52.5 17 250 184 19 (8x) 400 200 233 210 123 239.5 - - - 698
150 74.3 17 284 211 23 (8x) 480 240 275.5 240 150.5 267 - - - 726
VVF43..
VVF43..K
Product
DN B ØD Ø D1 Ø D2 L1 L2 L3 ØK H1 H2 H
number
SAX.. SKD.. SKB.. SKC..
VVF43.. 65 21.8 17 185 118 19 (4x) 290 145 178 145 115 231.5 - - - 690
80 27.7 17 200 132 19 (8x) 310 155 190 160 115 231.5 - - - 690
100 33.6 17 220 156 19 (8x) 350 175 206 180 146 262.5 - - - 721
125 50 17 250 184 19 (8x) 400 200 233 210 159 275.5 - - - 734
150 66.3 17 284 211 23 (8x) 480 240 275.5 240 186.5 303 - - - 762
VVF43..K 65 22.0 17 185 118 19 (4x) 290 145 178 145 115 231.5 - - - 690
80 27.9 17 200 132 19 (8x) 310 155 190 160 115 231.5 - - - 690
100 33.9 17 220 156 19 (8x) 350 175 206 180 146 262.5 - - - 721
125 46.9 17 250 184 19 (8x) 400 200 233 210 159 275.5 - - - 734
150 67.7 17 284 211 23 (8x) 480 240 275.5 240 186.5 303 - - - 762
77 / 94
Product
DN B ØD Ø D1 Ø D2 L1 L2 L3 ØK H1 H2 H
number
SAX.. SKD.. SKB.. SKC..
VVF53.. 15 4.2 14 95 46 14 (4x) 130 65 87.5 65 63 159.5 505 563 638 -
20 5.4 16 105 56 14 (4x) 150 75 99.5 75 63 159.5 505 563 638 -
25 6.1 15 115 65 14 (4x) 160 80 104.5 85 63 159.5 505 563 638 -
32 8.8 17 140 76 19 (4x) 180 90 119 100 60 156.5 502 560 635 -
40 10.2 16 150 84 19 (4x) 200 100 129 110 60 156.5 502 560 635 -
50 13.7 16 165 99 19 (4x) 230 115 146 125 100 196.5 542 600 675 -
65 22.2 17 185 118 19 (8x) 290 145 178 145 115 231.5 - - - 690
80 27.7 17 200 132 19 (8x) 310 155 190 160 115 231.5 - - - 690
100 38.6 17 235 156 23 (8x) 350 175 212.5 190 146 262.5 - - - 721
125 54.4 17 270 184 28 (8x) 400 200 242 220 159 275.5 - - - 734
150 74.3 17 297 211 28 (8x) 480 240 284 250 186.5 303 - - - 762
VVF53..K 50 13.6 16 165 99 19 (4x) 230 115 146 125 100 196.5 542 600 675 -
65 22.3 17 185 118 19 (8x) 290 145 178 145 115 231.5 - - - 690
80 27.9 17 200 132 19 (8x) 310 155 190 160 115 231.5 - - - 690
100 39.0 17 235 156 23 (8x) 350 175 212.5 190 146 262.5 - - - 721
125 54.4 17 270 184 28 (8x) 400 200 242 220 159 275.5 - - - 734
150 75.8 17 297 211 28 (8x) 480 240 284 250 186.5 303 - - - 762
VVG41..
Product DN
G L1 L2 L3 H1 H2 H
number
[Inch] SAX.. SKD.. SKB..
VVG41.. 15 1.25 G 1B
20 1.3 G 1¼B 100 50 57 26 122,5 > 468 > 526 > 601
25 1.6 G 1½B 59
32 2.2 G 2B 105 52.5 60 34 130,5 > 476 > 534 > 609
40 2.7 G 2¼B 130 65 73
50 3.9 G 2¾B 150 75 83 46 142,5 > 488 > 546 > 621
78 / 94
Product DN
G L1 L2 L3 H1 H2 H
number
[Inch] SAX.. SKD..
VVI41.. 15 1.3 Rp ½
90 45 40 26 122,5 > 468 > 526
20 1.35 Rp ¾
25 1.7 Rp 1 105 52.5
41 34 130,5 > 476 > 534
32 2.1 Rp 1¼ 115 57.5
40 2.75 Rp 1½ 130 65 46
46 142,5 > 488 > 546
50 3.7 Rp 2 150 75 56
VVF42..K
Product DN
B ØD Ø D1 Ø D2 L1 L2 L3 ØK H1 H2 H
number
SAX.. SKD.. SKB.. SKC..
VVF42..K 50 12.3 16 165 99 19 (4x) 230 115 144 125 50 146.5 492 550 625 -
65 17.5 17 185 118 19 (4x) 290 145 174 145 75 171.5 517 575 650 -
80 25.6 17 200 132 19 (8x) 310 155 186 160 75 171.5 517 575 650 -
100 35.9 17 220 156 19 (8x) 350 175 206 180 110 226.5 - - - 685
125 52.3 17 250 184 19 (8x) 400 200 233 210 123 239.5 - - - 698
150 76.3 17 284 211 23 (8x) 480 240 275.5 240 150.5 267 - - - 726
79 / 94
Product
DN B ØD Ø D1 Ø D2 Ø D3 L1 L2 L3 ØK H1 H2 H
number
SAX.. SKD.. SKB.. SKC..
VXF22.. 25 3.1 11 100 58 11 (4x) 36 150 75 75 75 37 133.5 479 537 612 -
40 4.9 13 130 78 14 (4x) 52 180 90 90 100 37 133.5 479 537 612 -
50 6.2 14 140 88 14 (4x) 65 200 100 100 110 50 146.5 492 550 625 -
65 9.5 14 160 108 14 (4x) 85 240 120 120 130 75 171.5 517 575 650 -
80 13.1 16 190 124 19 (4x) 98 260 130 130 150 75 171.5 517 575 650 -
100 19 16 210 144 19 (4x) 116 300 150 150 170 110 226.5 - - - 685
VXF32..
Product
DN B ØD Ø D1 Ø D2 Ø D3 L1 L2 L3 ØK H1 H2 H
number
SAX.. SKD.. SKB.. SKC..
VXF32.. 15 2.6 14 95 46 14 (4x) 23 130 65 65 65 37 133.5 479 537 612 -
20 - - - - - - - - - - - - - - - -
25 3.8 15 115 65 14 (4x) 36 160 80 80 85 37 133.5 479 537 612 -
32 - - - - - - - - - - - - - - - -
40 6.3 16 150 84 19 (4x) 56 200 100 100 110 37 133.5 479 537 612 -
50 8.7 16 165 99 19 (4x) 69 230 115 115 125 50 146.5 492 550 625 -
65 12.9 17 185 118 19 (4x) 85 290 145 145 145 75 171.5 517 575 650 -
80 19.2 17 200 132 19 (8x) 102 310 155 155 160 75 171.5 517 575 650 -
100 28.8 17 220 156 19 (8x) 124 350 175 175 180 110 226.5 - - - 685
125 43.2 17 250 184 19 (8x) 149 400 200 200 210 123 239.5 - - - 698
150 61.5 17 284 211 23 (8x) 174 480 240 240 240 150.5 267 - - - 726
80 / 94
Product DN B ØD Ø D1 Ø D2 Ø D3 L1 L2 L3 ØK H1 H2 H
number
SAX.. SKD.. SKB.. SKC..
VXF42.. 15 2.6 14 95 46 14 (4x) 23 130 65 65 65 37 133.5 479 537 612 -
20 3.3 16 105 56 14 (4x) 29 150 75 75 75 37 133.5 479 537 612 -
25 3.8 15 115 65 14 (4x) 36 160 80 80 85 37 133.5 479 537 612 -
32 5.7 17 140 76 19 (4x) 46 180 90 90 100 37 133.5 479 537 612 -
40 6.3 16 150 84 19 (4x) 56 200 100 100 110 37 133.5 479 537 612 -
50 8.7 16 165 99 19 (4x) 69 230 115 115 125 50 146.5 492 550 625 -
65 12.9 17 185 118 19 (4x) 85 290 145 145 145 75 171.5 517 575 650 -
80 19.2 17 200 132 19 (8x) 102 310 155 155 160 75 171.5 517 575 650 -
100 28.8 17 220 156 19 (8x) 124 350 175 175 180 110 226.5 - - - 685
125 43.2 17 250 184 19 (8x) 149 400 200 200 210 123 239.5 - - - 698
150 61.5 17 284 211 23 (8x) 174 480 240 240 240 150.5 267 - - - 726
VXF43..
Product DN B ØD Ø D1 Ø D2 Ø D3 L1 L2 L3 ØK H1 H2 H
number SAX.. SKD.. SKB.. SKC..
VXF43.. 65 17.1 17 185 118 19 (4x) 86 290 145 145 145 115 231.5 - - - 690
80 21.2 17 200 132 19 (8x) 100 310 155 155 160 115 231.5 - - - 690
100 27.1 17 220 156 19 (8x) 123 350 175 175 180 146 262.5 - - - 721
125 37.1 17 250 184 19 (8x) 149 400 200 200 210 159 275.5 - - - 734
150 54.5 17 284 211 23 (8x) 174 480 240 240 240 186.5 303 - - - 762
81 / 94
Product DN B ØD Ø D1 Ø D2 Ø D3 L1 L2 L3 ØK H1 H2 H
number SAX.. SKD.. SKB.. SKC..
VXF53.. 15 3.2 14 95 46 14 (4x) 25 130 65 65 65 63 159.5 505 563 638 -
20 4.1 16 105 56 14 (4x) 35 150 75 75 75 63 159.5 505 563 638 -
25 4.6 15 115 65 14 (4x) 38 160 80 80 85 63 159.5 505 563 638 -
32 6.1 17 140 76 19 (4x) 46 180 90 90 100 60 156.5 502 560 635 -
40 7.2 16 150 84 19 (4x) 57 200 100 100 110 60 156.5 502 560 635 -
50 9.8 16 165 99 19 (4x) 69 230 115 115 125 100 196.5 542 600 675 -
65 16.8 17 185 118 19 (8x) 86 290 145 145 145 115 231.5 - - - 690
80 21.2 17 200 132 19 (8x) 100 310 155 155 160 115 231.5 - - - 690
100 29 17 235 156 23 (8x) 123 350 175 175 190 146 262.5 - - - 721
125 39.7 17 270 184 28 (8x) 149 400 200 200 220 159 275.5 - - - 734
150 57 17 297 211 28 (8x) 174 480 240 240 250 186.5 303 - - - 762
VXG41..
Product DN
G L1 L2 L3 H1 H2 H
number
[Inch] SAX.. SKD.. SKB..
VXG41.. 15 1.3 G 1B
100 50 50 26 122.5 > 468 > 526 > 601
20 1.42 G 1¼B
25 1.65 G 1½B
32 2.1 G 2B 105 52.5 52.5 34 130.5 > 476 > 534 > 609
40 2.8 G 2¼B 130 65 65
50 3.9 G 2¾B 150 75 75 46 142.5 > 488 > 546 > 621
82 / 94
Product DN
G L1 L2 L3 H1 H2 H
number
[Inch] SAX.. SKD..
VVI41.. 15 1.5 Rp ½ 68
90 45 26 122.5 > 468 > 526
20 1.6 Rp ¾ 69
25 2.1 Rp 1 105 52.5 73.5
34 130.5 > 476 > 534
32 2.3 Rp 1¼ 115 57.5 74
40 3.1 Rp 1½ 130 65 84 46 142.5 > 488 > 546
83 / 94
VVF42.50-40K ..A
VVF42.65-63K ..A
VVF42.80-100K ..A
VVF42.100-160K ..A
VVF42.125-250K ..A
VVF42.150-360K ..A
VVF43.65-50 ..B
VVF43.65-63 ..B
VVF43.80-80 ..B
VVF43.80-100 ..B
VVF43.100-125 ..B
VVF43.100-160 ..B
VVF43.125-200 ..B
VVF43.125-250 ..B
VVF43.150-315 ..B
VVF43.150-400 ..B
VVF43.65-63K ..B
VVF43.80-100K ..B
VVF43.100-150K ..B
VVF43.125-220K ..B
VVF43.150-315K ..B
84 / 94
VXF42.15-1.6 ..A
VXF42.15-2.5 ..A
VXF42.15-4 ..A
VXF42.20-6.3 ..A
VXF42.25-6.3 ..A
VXF42.25-10 ..A
VXF42.32-16 ..A
VXF42.40-16 ..A
VXF42.40-25 ..A
VXF42.50-31.5 ..A
VXF42.50-40 ..A
VXF42.65-50 ..A
VXF42.65-63 ..A
VXF42.80-80 ..A
VXF42.80-100 ..A
VXF42.100-125 ..A
VXF42.100-160 ..A
VXF42.125-200 ..A
VXF42.125-250 ..A
VXF42.150-300 ..A
VXF42.150-400 ..A
Product number Valid from Product number Valid from Product number Valid from
VVG41.., VXG41.. rev. no. rev. no. rev. no.
VVG41.11 ..A
VVG41.12 ..A
VXG41.1301 ..A VVG41.13 ..A
VXG41.1401 ..A VVG41.14 ..A
VXG41.15 ..A VVG41.15 ..A VXG41.1501 ..B
VXG41.20 ..A VVG41.20 ..A VXG41.2001 ..B
VXG41.25 ..A VVG41.25 ..A VXG41.2501 ..B
VXG41.32 ..A VVG41.32 ..A VXG41.3201 ..B
VXG41.40 ..A VVG41.40 ..A VXG41.4001 ..B
VXG41.50 ..A VVG41.50 ..A VXG41.5001 ..B
85 / 94
86 / 94
DIN EN 14597 Standard on temperature controls and temperature limiters for use in heat
generating plants. This standard also covers actuating equipment (actuating
devices) with safety function for temperature and pressure limitation as per
DIN EN 14597
HIT The HVAC Integrated Tool (HIT) supports sizing and selection of valves for water
with antifreeze (www.siemens.com/hit)
Actuating device Combination of valve and actuator
Rangeability SV Characteristic of an actuating device, used to assess the device’s controllable
range; ratio of the nominal flow rate kvs to the smallest controllable flow kvr
Valve authority Pv Ratio of the differential pressure across the fully open valve (H100) to the differential
pressure across the valve plus that of the pipe section with variable volume. To
ensure correct control, the valve authority must be a minimum of 0.25
Specific heat capacity The specific heat capacity is the amount of heat required to heat the mass of 1 kg
of a substance by 1 K.
It increases as the temperature of the substance rises; in the case of gases, also
as the pressure of the substance rises. Therefore, with gases, a distinction is made
between cP, the specific heat at a constant pressure, and cV, the specific heat at a
constant volume
87 / 94
Film temperature Temperature of the valve surfaces that are in contact with the heat transfer oil at
which the oil starts to disintegrate
Cavitation Due to high speeds of the medium in the narrowest section of the valve, local
underpressure occurs. If this pressure drops below the medium’s boiling pressure,
cavitation occurs (steam bubbles), possibly leading to material removal (abrasion).
Also, when cavitation starts, the noise level increases abruptly. Cavitation can be
avoided by limiting the pressure differential across the valve as a function of the
medium temperature and the prepressure. For more detailed information, refer to
"2.13 Cavitation", page 56
Selection of valve Certain types of Siemens actuators are equipped with DIL switches for the
characteristic selection of a linear or an equal-percentage valve characteristic. The objective is to
linearize the volumetric flow through the consumer and the valve
Closed circuit The medium circulates in a closed hydraulic system with no contact to the
atmosphere
Open circuit The circulating medium is in contact with the atmosphere, that is, the hydraulic
system is open to atmosphere (e.g. cooling towers with open tanks, or showers).
Hence, the system can absorb oxygen from the surrounding air, which can lead to
rust; in addition, more attention is to be paid to cavitation; for more information,
refer to "2.13 Cavitation", page 56
Control stability The stability of a closed control loop depends on the degree of difficulty S of the
controlled system and the circuit amplification V0. For more detailed information,
refer to the Siemens brochure "Control technology" (ordering no. 0-91913-en)
Return temperature TRL Temperature of the medium at which it returns from the consumer to the heat or
cooling source
Gravity circulation The density of a medium depends on its temperature. If a medium is hot in one
place and cold in another, it starts to circulate due to different densities
Volumetric flow V Volume of a medium that passes through an opening for a certain time
Flow temperature TVL Temperature of a heating or cooling medium at which it leaves its source to enter a
hydraulic circuit
Selection of acting Certain types of Siemens actuators are equipped with DIL switches for selection of
direction the operating action of the respective valve (push to open, pull to open, normally
open, normally closed). The objective is to drive the valve to the fully open or fully
closed position should a power failure occur, depending on plant requirements
Forced control If forced control is demanded, no consideration is given to any other control
command. For example, if there is risk of frost, more heat is supplied to prevent
freeze-ups
88 / 94
The list below is not exhaustive. It specifies manufacturer data and is not to be
regarded as an official approval for Siemens products in the indicated temperature
range. For temperature ranges of individual product lines, see chapter 2.12, page
50.
The notes given under "2.14 Medium quality and medium treatment", page 57 must
also be observed.
89 / 94
point
Arteco NV/SA Zitrec MC Multipurpose heat transfer medium < 70 % -55…120 °C No known
on the basis of monoethylene glycol, restriction
www.zitrec.com/ mixed with an adequate amount of
water
Zitrec LC Multipurpose heat transfer medium < 70 % -55…120 °C No known
on the basis of monopropylene restriction
glycol, mixed with an adequate
amount of water
Zitrec FC Multipurpose heat transfer medium < 70 % -50…120 °C No known
on the basis of monopropylene restriction
glycol, mixed with an adequate
amount of water; all substances
contained in the medium are
approved by FDA
Zitrec S Multipurpose heat transfer medium Ready-to-use -55…120 °C Restricted -
without glycol, on the basis of a mixture compatibility must
substance consisting of potassium be tested
formate and sodium propionate
Tyforop Chemie GmbH TYFOCOR® L Freezing and anticorrosion agent, - -25…140 °C Restricted -
safe with regard to health, specifically compatibility,
www.tyfo.de/index_deuts for keeping food cool and for solar especially with
ch.html plants, virtually odourless, respect to soft
hygroscopic liquid. It is based on solder - individual
propylene glycol, which poses no case must be
hazard to health and which may be tested
used as a coolant or heat-transfer
fluid in food processing and water
purification applications.
TYFOCOR® HTL Ready-to-use heat transfer medium - ...170 °C Restricted -
for solar plants with higher thermal compatibility,
loads, clear, blue-green colored liquid especially with
with a faint odour and is based on respect to soft
1,2-propylene glycol and solder - individual
polyethylene glycol. case must be
tested
TYFOCOR® LS Special, ready-to-use heat transfer - -25…170 °C Restricted -
medium, evaporating without residue, compatibility,
for solar plants with high thermal especially with
loads (vacuum tube collectors); respect to soft
faint odour, based on physiologically solder - individual
unobjectionable propylene glycol, case must be
and water. tested
90 / 94
Arteco NV/SA Freezium Salt brine on the basis of potassium 24 ..50 % -60…35 °C Restricted -
formate, specially developed for use individual case
www.zitrec.com/Products in indirect cooling systems and heat must be tested
_Freezium.htm pumps. Suitable for a temperature
range from -60 to 95 °C
Tyforop Chemie GmbH TYFOXIT®F15-F50 High-performance coolant on the - -60…100 °C Restricted
basis of potassium formate (safe with permissibility,
www.tyfo.de/index_deuts regard to food). Available as a ready- more precise
ch.html to-use mixture in 6 variants (F15 - evaluations at
F50), cooling limits from 20...80 °C
-15 to -60 °C. Excellent flow necessary
properties at low temperatures, due (test soft solder in
to low viscosity individual case)
TYFOXIT® 1.25 High-performance coolant on the - -55…100 °C Restricted
basis of potassium acetate (safe with permissibility,
regard to food). Supplied as a more precise
concentrate or ready-to-fill mixture evaluations at
and suited for use at temperatures 20...80 °C
down to -55 °C necessary
(test soft solder in
individual case)
91 / 94
Cast iron at
higher
temperatures
unsuitable
Non-ferrous metal
suited to a limited
extent, must be
tested in
individual case
1)
Supplier’s Usage Instructions must be observed.
2)
Restricted usage with regard to concentration or temperature
92 / 94
93 / 94