Notes on installation 3
SIMATIC
New features and changes
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified
personnel are those who, based on their training and experience, are capable of identifying risks and avoiding
potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in
this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
1 Security information......................................................................................................................................5
2 Overview.......................................................................................................................................................7
3 Notes on installation.....................................................................................................................................9
3.1 Scope of delivery......................................................................................................................9
3.2 Hardware requirements............................................................................................................9
3.3 Software requirements.............................................................................................................9
3.4 Installation of the PCS 7 Advanced Process Library................................................................9
4 New features and changes as compared to previous versions..................................................................11
4.1 Version 8.2.............................................................................................................................11
4.1.1 What's new in Version 8.2?....................................................................................................11
4.1.2 Changes in version 8.2..........................................................................................................12
4.1.3 Update information for version 8.2.........................................................................................14
5 Information on configuration and operation................................................................................................17
6 Notes on the documentation.......................................................................................................................19
7 Change history of PCS 7 Advanced Process Library.................................................................................21
Siemens Distributor
PCS 7 Advanced Process Library Readme V8.2 (Online)
Readme, 03/2016, A5E36549913-AA 3
Table of contents
Siemens Distributor
PCS 7 Advanced Process Library Readme V8.2 (Online)
Readme, 03/2016, A5E36549913-AA 5
Security information
Siemens Distributor
PCS 7 Advanced Process Library Readme V8.2 (Online)
Readme, 03/2016, A5E36549913-AA 7
Overview
Siemens Distributor
PCS 7 Advanced Process Library Readme V8.2 (Online)
Readme, 03/2016, A5E36549913-AA 9
Notes on installation
3.4 Installation of the PCS 7 Advanced Process Library
Siemens Distributor
PCS 7 Advanced Process Library Readme V8.2 (Online)
Readme, 03/2016, A5E36549913-AA 11
New features and changes as compared to previous versions
4.1 Version 8.2
● Error number 51 is output for invalid input signals in the family Control blocks analogous
to the blocks of the Drives family.
● New AbsR block for the formation of the absolute value function of a real number.
● The VlvAnL block also monitors the analog feedback in the intermediate position
(PosDiClose < RbkOut < PosDiOpen).
The block can now also be operated without analog position feedback (Rbk).
The Rbk.ST parameter must have the value 16#FF for this.
● To prevent the manipulated variable from remaining in the limit range for too long with large
TI values with the PIDConR module following a switchover to automatic mode, it is possible
to accelerate the return of the integral action from the limit via the new Feature bit 17. The
integral action is hereby moved in the direction of the control range just far enough for the
manipulated variable to remove itself quickly and smoothly from the manipulated variable
limits (MV_HiLim/MV_LoLim)when a control deviation is pending.
● The Spd1ChnST/Spd2ChnST inputs have been integrated in the process tag types
Motor2Speed.
● If the internal setpoint in the OpAnL, MotSpdCL, VlvAnL, ModPreCon and MPC10x10
blocks is limited with an adjustment of the setpoint limits, the input for the internal setpoint
is also tracked. Jumps in the internal setpoint can thus be avoided when setting the setpoint
limits to the original value again. This means the blocks react the same as other blocks of
the Control and Dosage family.
● In the MeanTime block the function "Set fixed mean value" is corrected via the Reset
input. The value of the In input is now permanently routed to the Out output and not only
for one cycle.
● If after control in the block VlvMotL an opposite feedback message of the valve occurs while
V_MonTiStatic is running, this control is no longer accepted. Monitoring for maintenance
of the position is started.
● In the MotL, MotRevL, MotSpdL, MotSpdCL and VlvMotL blocks a change to the
IdleTime while the IdleTime is already running is immediately applied and the time already
elapsed is taken into account.
● The operator control enable for opening, closing and stopping in the VlvMotL block with
simultaneous pending valve feedback signals have been corrected.
● A protective interlock for a direction (with Feature 2 bit 16 = 1) is no longer reset in
theMotRevL block when driving in the opposite direction.
● In the family of blocks Dosage and drives, there is no longer a switchover at startup of the
AS (OB100) to manual operating mode from the operating mode out of service.
● The PIDConL block with configured deadband and simultaneous "Proportional action in
feedback path" no longer generates a manipulated variable jump within the deadband.
● After installing the ModPreCon or MPC10x10 block and configuring the DB number for
controller data, the controller data now take effect immediately with Restart = 1.
● The stop pulse signal P_Stop at the VlvMotL block is now also within the pulse width
PulseWith. The device behaves like all the other valves and motors.
● If one of the valve feedbacks is absent (NoFbkOpen =1 or NoFbkClose =1) and the other
incorrect, the VlvMotL now block detects the V_MonTiStatic monitoring error by the
missing adherence to the neutral position.
● The limitation of the analog signal increase In.Value at the block RateLim now functions
with twice the accuracy.
Siemens Distributor
PCS 7 Advanced Process Library Readme V8.2 (Online)
Readme, 03/2016, A5E36549913-AA 13
New features and changes as compared to previous versions
4.1 Version 8.2
● In the PIDConR block, the control behavior on switchover to automatic has been optimized.
For this purpose, the limit of the integral action has been set to the maximum range from
-10000% to +10000% in the PIDKernR block. This guarantees smooth switchover from
manual to automatic mode when a control deviation is present. To prevent the manipulated
variable from remaining in the limit range for too long with large TI values, it is possible to
accelerate the return of the integral action from the limit via Feature bit 17. The integral
action is hereby moved in the direction of the control range just far enough for the
manipulated variable to remove itself quickly and smoothly from the manipulated variable
limits (MV_HiLim/MV_LoLim) when a control deviation is pending.
● With interlocking the PIDConL and PIDConR blocks now behave like closed-loop
controllers with an open control loop (cf. for example manual operation or tracking). Setpoint
tracking is therefore also active and the outputs LoopClosed, CascaCut are set
accordingly. When leaving interlocking the manipulated variable behaves smoothly if
Feature Bit 18 = 0 is set.
Note
Updating the blocks from the PCS 7 Advanced Process Library with TCiR
"Type import - Changed default value" dialog box
● If information on changed internal local default values in the static area is displayed during
type import in the dialog box, these changes are not relevant. A complete download in
STOP mode is not necessary.
● If information on changed default values is displayed at block I/Os during type import in the
dialog box, these new default values must be applied in the "Update Block Types" dialog.
Siemens Distributor
PCS 7 Advanced Process Library Readme V8.2 (Online)
Readme, 03/2016, A5E36549913-AA 15
New features and changes as compared to previous versions
4.1 Version 8.2
Note
● Blocks for which only attributes, message texts, and/or version number were changed, are
not listed.
● If "Yes" is listed in the column "Interface change" and "No" in the column "Code change",
only the interfaces were prepared for a future function.
Siemens Distributor
PCS 7 Advanced Process Library Readme V8.2 (Online)
Readme, 03/2016, A5E36549913-AA 17
Information on configuration and operation
● ManModLi I/O
The attribute S7_contact is missing on the ManModLi I/O and must be set manually if
needed at the block interface. You can reach the interface by double-clicking the
appropriate block in the block folder. To retain backward compatibility with existing projects,
the attribute can no longer be set because otherwise the existing connections between the
SFC and the block would be changed.
● The messages of the block VlvPosL contain the origin instead of the OS area.
This can be changed as follows by adapting the alarm properties at the block type.
– Select Special object properties --> Messages from the shortcut menu.
– Click the "Advanced>>" button.
– Change the keyword from "$$AKZ$$" to "$$AREA$$" in the line OS area.
– Click "OK".
– Re-import the block type.
The change is made to already existing instances.
Siemens Distributor
PCS 7 Advanced Process Library Readme V8.2 (Online)
Readme, 03/2016, A5E36549913-AA 19
Notes on the documentation
Siemens Distributor
PCS 7 Advanced Process Library Readme V8.2 (Online)
Readme, 03/2016, A5E36549913-AA 21
Change history of PCS 7 Advanced Process Library