Data Sheet 6ES7314-6CH04-0AB0: General Information
Data Sheet 6ES7314-6CH04-0AB0: General Information
Data Sheet 6ES7314-6CH04-0AB0: General Information
General information
HW functional status 01
Firmware version V3.3
Engineering with
● Programming package STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher
with HSP 203
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines Miniature circuit breaker, type C; min. 2 A; miniature circuit
(recommendation) breaker type B, min. 4 A
Mains buffering
● Mains/voltage failure stored energy time 5 ms
● Repeat rate, min. 1 s
Load voltage L+
Digital inputs
— Rated value (DC) 24 V
Input current
Current consumption (rated value) 880 mA
Current consumption (in no-load operation), typ. 150 mA
Inrush current, typ. 5 A
I²t 0.7 A²·s
Digital inputs
● from load voltage L+ (without load), max. 80 mA
Digital outputs
● from load voltage L+, max. 50 mA
Power loss
Power loss, typ. 13 W
Memory
Work memory
● integrated 192 kbyte
● expandable No
● Size of retentive memory for retentive data 64 kbyte
blocks
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
● Data management on MMC (after last 10 y
programming), min.
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
● without battery Yes; Program and data
CPU-blocks
Number of blocks (total) 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks
can be reduced by the MMC used.
DB
● Number, max. 1 024; Number range: 1 to 16000
● Size, max. 64 kbyte
FB
Address area
I/O address area
● Inputs 2 048 byte
● Outputs 2 048 byte
of which distributed
— Inputs 2 003 byte
— Outputs 2 010 byte
Process image
● Inputs 2 048 byte
● Outputs 2 048 byte
● Inputs, adjustable 2 048 byte
● Outputs, adjustable 2 048 byte
● Inputs, default 128 byte
● Outputs, default 128 byte
Default addresses of the integrated channels
— Digital inputs 124.0 to 126.7
— Digital outputs 124.0 to 125.7
— Analog inputs 752 to 761
— Analog outputs 752 to 755
Digital channels
● Inputs 16 048
Hardware configuration
Number of expansion units, max. 3
Number of DP masters
● integrated 1
● via CP 4
Number of operable FMs and CPs (recommended)
● FM 8
● CP, PtP 8
● CP, LAN 10
Rack
● Racks, max. 4
● Modules per rack, max. 8; In rack 3 max. 7
Time of day
Clock
● Hardware clock (real-time) Yes
● retentive and synchronizable Yes
● Backup time 6 wk; At 40 °C ambient temperature
● Deviation per day, max. 10 s; Typ.: 2 s
● Behavior of the clock following POWER-ON Clock continues running after POWER OFF
● Behavior of the clock following expiry of backup Clock continues to run with the time at which the power failure
period occurred
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 h
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master Yes; With DP slave only slave clock
● to DP, slave Yes
Digital inputs
Number of digital inputs 24
● of which inputs usable for technological 16
functions
integrated channels (DI) 24
Input characteristic curve in accordance with IEC Yes
61131, type 1
Number of simultaneously controllable inputs
horizontal installation
— up to 40 °C, max. 24
— up to 60 °C, max. 12
vertical installation
— up to 40 °C, max. 12
Input voltage
● Rated value (DC) 24 V
● for signal "0" -3 to +5V
● for signal "1" +15 to +30V
Input current
● for signal "1", typ. 8 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of
the standard inputs during program runtime. Please note that
under certain circumstances your newly set filter time may not be
effective until the next filter cycle.)
— Rated value 3 ms
for technological functions
— at "0" to "1", max. 8 µs; Minimum pulse width/minimum pause between pulses at
maximum counting frequency
Cable length
● shielded, max. 1 000 m; 50 m for technological functions
● unshielded, max. 600 m; for technological functions: No
for technological functions
— shielded, max. 50 m; at maximum count frequency
— unshielded, max. not allowed
Digital outputs
Number of digital outputs 16
● of which high-speed outputs 4; Notice: You cannot connect the fast outputs of your CPU in
parallel
integrated channels (DO) 16
Analog inputs
Number of analog inputs 5
● For voltage/current measurement 4
● For resistance/resistance thermometer 1
measurement
integrated channels (AI) 5; 4x current/voltage, 1x resistance
permissible input voltage for current input 5 V; Permanent
(destruction limit), max.
Analog outputs
Number of analog outputs 2
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes; with external supply
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire Yes; Without compensation of the line resistances
connection
● for resistance measurement with three-wire No
connection
● for resistance measurement with four-wire No
connection
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire 1.5 mA
sensor), max.
Errors/accuracies
Temperature error (relative to input range), (+/-) 0.006 %/K
Crosstalk between the inputs, min. 60 dB
Repeat accuracy in steady state at 25 °C (relative to 0.06 %
input range), (+/-)
Output ripple (relative to output range, bandwidth 0 to 0.1 %
50 kHz), (+/-)
Linearity error (relative to output range), (+/-) 0.15 %
Temperature error (relative to output range), (+/-) 0.01 %/K
Crosstalk between the outputs, min. 60 dB
Repeat accuracy in steady state at 25 °C (relative to 0.06 %
output range), (+/-)
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 1 %
● Current, relative to input range, (+/-) 1 %
● Resistance, relative to input range, (+/-) 1 %
● Voltage, relative to output range, (+/-) 1 %
● Current, relative to output range, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.8 %; Linearity error ±0.06 %
● Current, relative to input range, (+/-) 0.8 %; Linearity error ±0.06 %
● Resistance, relative to input range, (+/-) 0.8 %; Linearity error ±0.2 %
● Resistance thermometer, relative to input 0.8 %
range, (+/-)
Interfaces
Number of industrial Ethernet interfaces 0
Number of PROFINET interfaces 0
Number of RS 485 interfaces 2; MPI and PROFIBUS DP
Number of RS 422 interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated No
Power supply to interface (15 to 30 V DC), max. 200 mA
Protocols
● MPI Yes
● PROFIBUS DP master No
● PROFIBUS DP slave No
● Point-to-point connection No
MPI
● Transmission rate, max. 187.5 kbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes; Only server, configured on one side
— S7 communication, as client No; but via CP and loadable FB
— S7 communication, as server Yes
2. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Protocols
● MPI No
● PROFINET IO Controller No
● PROFINET IO Device No
● PROFINET CBA No
Communication functions
PG/OP communication Yes
Data record routing Yes
Global data communication
● supported Yes
● Number of GD loops, max. 8
● Number of GD packets, max. 8
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 8
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with
X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● as client Yes; Via CP and loadable FB
● User data per job, max. 180 kbyte; With PUT/GET
● User data per job (of which consistent), max. 240 byte; as server
S5 compatible communication
● supported Yes; via CP and loadable FC
Number of connections
● overall 12
● usable for PG communication 11
— reserved for PG communication 1
— adjustable for PG communication, min. 1
— adjustable for PG communication, max. 11
● usable for OP communication 11
— reserved for OP communication 1
— adjustable for OP communication, min. 1
S7 message functions
Number of login stations for message functions, max. 12; Depending on the configured connections for PG/OP and S7
basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 300
Interrupts/diagnostics/status information
Diagnostics indication LED
● Status indicator digital input (green) Yes
● Status indicator digital output (green) Yes
Potential separation
Potential separation digital inputs
● Potential separation digital inputs Yes
● between the channels No
● between the channels and backplane bus Yes
Potential separation digital outputs
● Potential separation digital outputs Yes
● between the channels Yes
● between the channels, in groups of 8
● between the channels and backplane bus Yes
Potential separation analog inputs
● Potential separation analog inputs Yes; common for analog I/O
● between the channels No
● between the channels and backplane bus Yes
Potential separation analog outputs
● Potential separation analog outputs Yes; common for analog I/O
● between the channels No
● between the channels and backplane bus Yes
Isolation
Isolation tested with 600 V DC
Ambient conditions
Ambient temperature during operation
● min. 0 °C
● max. 60 °C
Configuration
Dimensions
Width 120 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 680 g