Transformer Protection 4may11
Transformer Protection 4may11
CONTENTS
Conclusion
Transformer Protection
Introduction
Transformers in Power System
400 kV AC Transmission
Generation
MV Distribution
LV
M
Introduction
• A Power Transformer is a very valuable and vital
link in a Power Transmission system
Failure of PRV
Transformer Protection-Mechanical
30
Transformer Electrical
Protections
Transformer Protection-Electrical
The Electrical protections is further classified as:
• Unit protection
• Non-Unit protection
Which are operated for a fault outside the transformer also and
are known as back up protection
Differential Protection
• Differential protection is a complete phase and earth fault
protection operating on Merz Price circulating current principle
• Differential relay compares the currents on the primary and
secondary side of the transformer using CTs of matched ratio,
such that the secondary currents are balanced in magnitude and
phase for an external fault on load
• Interposing current transformers for phase shift and
transformation ratio correction
– Magnitude balance is achieved by a proper selection of CT
ratio on primary and secondary side or by using interposing
current transformers (ICTs)
– Phase balance is achieved by appropriate vector connections
of the associated CT/ICTs (e.g. star side CTs connected in
delta and vice versa)
• Influence from OLTC
• Harmonic restrained differential protections
Differential Protection
87
Differential Protection
Differential Protection
Differential Protection
DIFFERENTIAL RELAY – OPERATING PRINCIPLE
Current Distribution (External Fault)
STEADY STATE
At zero volts, flux is “(-) ɸm” since flux in quadrature with voltage
Total flux change in half the voltage cycle is “2ɸm” (-ɸm to +ɸm)
SWITCHING AT VOLTAGE ZERO
Initial flux zero as against (-) ɸm corresponding to steady state
Total flux changes from zero to 2ɸm
Flux doubling causes extreme saturation of core
Differential Protection
DIFFERENTIAL PROTECTION – Magnetizing Inrush
• Set above permissible over load with small time delay (say 5
seconds)
1000
100
time
s
10
Recommended DT of 2Sec
Operating time setting of the relay should be more than the
operating time of distance zones in line protection relay
Inter Turn Fault Protection
Inter-turn fault and protection
• Statistically, approximately 70-80% of all transformer faults
originate as inter-turn faults and finally develop into earth fault
and/or phase faults
• Short circuit of a few turns of a winding will cause a significantly
heavy current in the short circuited portion of the winding, while
the terminal currents will be very small because of large turns
ratio between the main winding and the short circuited turns
• Most probable reasons for inter-turn faults are :
1. Mechanical forces on the winding due to external short circuits
2. Excessive moisture in the paper insulation of the winding
3. Structural failure of paper insulation due to aging
Inter Turn Fault Protection
Inter Turn Fault Protection
• The transformers may be subjected to steep fronted impulse
voltage originated form lightning and switching having very high
equivalent frequency and tend to concentrate on the end
windings
• This has led to reinforced design of end winding insulation
• However, the reinforced end winding insulation is not
comparable to the insulation to the ground and hence a higher
probability of part winding flash over exists as against that for
flashover to ground
• Inter-turn faults involving very few turns are not detectable,
Inter-turn faults involving fairly large number of turns either may
be cleared by transformer differential or rate of gas pressure rise
in transformer liquid insulation protections