Thank you for purchasing a Toshiba “Open type TOSVERT VF-S11 series inverter.”
This Manual gives a supplementary explanation of some items referred to in the instruction manual E6581158
included with the product. Please read this manual carefully along with the instruction manual E6581158.
■Safety precautions
Before reading this manual, please read the following instructions in addition to “I. Safety Precautions,” of the
instruction manual E6581158.
■General operation
Danger
• The inverter is of an open type, and its high-voltage section, rotary section and hot
Mandatory section are exposed. So be sure to take all necessary measures for safety. Otherwise
you could get a shock, get injured or get burned.
• The inverter has no means of protecting itself from dust and water drops, so take
necessary measures against them.
• Do not touch any parts other than the operation panel when the inverter is energized or
within 10 minutes after power is turned off. Otherwise you could get a shock, get
injured or get burned.
■Transportation
Warning
• When handling the inverter unit, hold it by both the sides firmly.
Mandatory
(3)
▲ MODE
(5)
▼ ENT
1) Cooling fan
The inverter is equipped with cooling fans. The cooling fan has a useful life of approximately 30,000 hours (2 to
3 years when operated continuously), so it needs to be replaced periodically.
If the cooling fan does not operate normally, the temperatures of the internal electrical components will rise
high, and as a result their lives will be shortened. So inspect it periodically.
1
E6581263
Control circuit
terminal board
Main circuit
terminal board
■Wiring diagram
(6)
(7) (7) To detach the capacitor, connect the
green grounding wire to this side.
Cautions
• The inverter is shipped from the factory with the main circuit section and the circuit board section exposed.
High voltages are applied to some parts in the main circuit section and circuit board section, so read Section
2.1, “Cautions on wiring,” of the instruction manual E6581158 carefully before wiring.
When connecting cables, take care not to damage the circuit board with a screwdriver or a similar tool.
Also, be sure to take necessary safety measures to prevent accidents caused by the high-voltage section,
rotary section, hot section, and so on. Otherwise you could get a shock, get injured or get burned.
• For instructions about how to detach the grounding capacitor, refer to 1.3.2 (2), “Grounding capacitor
disconnecting switch and taps,” of the instruction manual E6581158.
2
E6581263
A
Screw
Direction of
insertion
Screw
Board
Working space: 1m
or more
3
E6581263
■ Outside dimensions
Installation
Voltage Applicable Motor Outside dimensions (mm)
Inverter type dimension (mm) * Drawing
class (kW)
W H D W1 H1
5.5 VFS11-4055PLU
400 600 243 310 570 Fig. A
3-phase 7.5 VFS11-4075PLU
500V 11 VFS11-4110PLU
450 700 267 340 670 Fig. B
15 VFS11-4150PLU
* Here are the dimensions for the standard installation.
12-M4,
7 mm in depth
Fig. A
4
E6581263
12-M4,
7 mm in depth
Fig. B
5
E6581263
■Specifications
Item Specification
Voltage class 3-phase 500 V
Applicable motor (kW) 5.5 7.5 11 15
Model
Voltage class VFS11-
Model
number
Three-phase
VFS11- 4055PLU 4075PLU 4110PLU 4150PLU
500V class
Capacity (kVA) Note 1: 11 13 21 25
Rating
Output current (A) Note 2: 14.3 (13.0) 17.0 (17.0) 27.7 (25.0) 33(30)
Output voltage Note 3: 3-phase 380 to 500V
Overload current rating 150%-1min., 200%-0.5 sec. (50%-reduction value)
Voltage-frequency 3-phase 380 to 500V-50/60Hz
supply
Power
explosive gases
Ambient temperature -10 to +40°C
Storage temperature -25 to +70°C
Relative humidity 20 to 93%
Vibration 5.9m/s2 or less (10 to 55Hz)
Note 1: Output capacity at an output voltage of 440V
Note 2: Indicates rated output current setting when the PWM carrier frequency (parameter F300) is 4kHz or less.
The values between parentheses refer to output currents at PWM carrier frequencies of over 4kHz. They
need to be reduced further at frequencies over 12kHz (If a motor cable over 30m in length is used, it is
necessary to reduce them more. This means that the lives of the internal components will be shortened).
They need to be reduced more if the supply voltage exceeds 480V. The default setting of the PWM
carrier frequency is 12kHz.
Note 3: The maximum output voltage is equal to the input supply voltage.
Note 4: ±10% when the inverter is operated continuously (under a load of 100%).
Note 5: For control specifications, parameters and functions, refer to the instruction manual E6581158.
Note 6: The factory default settings of the following parameters are different from those of the VFS11 standard
type.
Standard
Title Function Open type VF-S11
VF-S11
EOQF Command mode
1 0
selection
HOQF Frequency setting mode
0 2
selection
Note 7: The inverter is equipped with cooling fans. The cooling fan has a useful life of approximately 30,000
hours (2 to 3 years when operated continuously), so it needs to be replaced periodically.
If the cooling fan does not operate normally, the temperatures of the internal electrical components will
rise high, and as a result their lives will be shortened. So inspect it periodically.
6
E6581263
■Dimensional drawing of the board to be cut when mounting the fin outside (for 5.5 and 7.5kW models)
■Dimensional drawing of the board to be cut when mounting the fin outside (for 11 and 15kW models)