Chapter 2 - Transformers
Chapter 2 - Transformers
Chapter 2 - Transformers
Chapter 2: Transformers
“A device that changes AC electrical power at one voltage level to another voltage level
through the action of a magnetic field.”
In both types, the core is made up of thin laminations to minimize eddy current.
1
EME4363 Electrical Machines– Transformer
There are also two special-purpose transformers, ie. Potential transformer and current
transformer.
When an AC voltage is supplied to the primary side, an alternating flux in the core will
link both windings.
𝑑∅𝑖
𝑒𝑖𝑛𝑑 = − 𝑑𝑡
𝑑∅𝑖
𝑒𝑖𝑛𝑑 = −𝑁 𝑑𝑡
Therefore,
𝑒𝑖𝑛𝑑 = (𝑣. 𝐵)𝑙
2
EME4363 Electrical Machines– Transformer
To find the current relationship, apply Ampere’s Law around the core. Assuming the core
is infinitely permeable, H = 0, in the core:
𝑉𝑝 𝐼𝑝 = 𝑉𝑠 𝐼𝑠
𝑉𝑝 𝐼𝑠
= =𝑎
𝑉𝑠 𝐼𝑝
𝐼𝑝 1
=
𝐼𝑠 𝑎
In phasor form, the voltage and current relationships are:
Note that the turns ratio of the ideal transformer only affects the magnitudes of
current and voltage. Phase angles are not affected.
But as mentioned, the phase angles are unaffected by the ideal transformer, hence:
,
Vp
And since, Vs and I s aI p ,
a
The same idea can be applied for reactive power Q and apparent power S:
3
EME4363 Electrical Machines– Transformer
Thus,
Output Power = Input Power
When a load is connected to the secondary terminals of the ideal transformer, it’s
impedance is given by:
Useful for calculations to replace the ideal transformer and the load with a single load.
This load must draw:
The same current from the primary.
The same power from the primary.
The easiest way to analyze is by simplifying the transformer into an equivalent circuit.
How?
1. Replace the ideal transformer and the load connected to it by it’s apparent
impedance.
Z 'L a 2 Z L
4
EME4363 Electrical Machines– Transformer
If there is more than one transformer in the circuit start from the end farthest
from the source and replace each transformer by its apparent impedance one by
one. This is called “referring the transformer”.
2. After substituting the transformers, the equivalent circuit can be solved for its
voltages and currents. Do not forget to apply the transformer voltage and
current relationships when calculating for the replaced transformers!
a. Calculate the voltage at the load and what are the transmission losses.
5
EME4363 Electrical Machines– Transformer
6
EME4363 Electrical Machines– Transformer
Total impedance at the transmission line level (Zline + Zload) reflected across T1 is
Having known this, we can work back to find the transmission line and the load currents
(Iload and Icurrent):
7
EME4363 Electrical Machines– Transformer
In reality, an ideal transformer is non-existent due to the losses present. We will now
look into the characteristics of a real transformer.
When a voltage vp(t) is applied directly to the primary of a real transformer, flux will be
present and the average flux due to the primary is:
Based on this relationship, p av v p (t )dt , this generated flux will travel to the
secondary side and voltage is induced across the secondary terminal.
The remaining flux that links with the secondary is termed mutual flux m. (flux
component linking both primary and secondary coils.
Primary:
Secondary:
8
EME4363 Electrical Machines– Transformer
Hence, Faraday’s Law for the primary circuit can be expressed as:
It is clear that a common term is present in the primary and secondary voltage
expressions due to the mutual flux, i.e.:
and
Therefore,
This equation means that in real transformers: the transformer turns ratio is related to
the induced voltage due to the mutual flux”.
9
EME4363 Electrical Machines– Transformer
Proof:
In the transformer, the flux produced is proportional to the current. Therefore, sinusoidal
flux means sinusoidal current.
However, due to the non-linear magnetization curve of the core, the transformer will
saturate, i.e. more current is required to increase the flux in the core.
Core-loss current ih+e is also present which is required to compensate for hysteresis and
eddy current losses (this also occurs even when the secondary is open-circuited).
10
EME4363 Electrical Machines– Transformer
According to the dot convention: “A current flowing into the dotted end of a winding
produces a positive mmf and vice versa.”
Two currents flowing into the dotted ends of their respective windings produce
rnagnetomotive forces that add. If one current flows into a dotted end of a winding and
one flows out of a dotted end, then the magnetomotive forces will subtract from each
other.
Now, when we connect a load to the real transformer, the primary current will produce a
positive mmf:
Due to Lenz’s Law, the secondary current will flow out of the dotted end to produce a
negative mmf:
(current flow will be in a direction as such to oppose the core flux direction)
Therfore, the net mmf in the transformer required to produce flux in the core is given by
To accurately model the transformer, the following losses will have to be included:
11
EME4363 Electrical Machines– Transformer
12
EME4363 Electrical Machines– Transformer
(a) The transformer model referred to its primary voltage level. (b) The transformer
model referred to its secondary voltage level.
(a) Referred to the primary side; (b) referred to the secondary side; (c) with no excitation
branch referred to the primary side; (d) with no excitation branch referred to the
secondary side.
In some cases, the excitation branch is entirely neglected since it has small excitation
current.
Connection for transformer open-circuit test. Connection for transformer short-circuit test
13
EME4363 Electrical Machines– Transformer
Secondary winding open-circuit, i.e. Z' L . Full rated line voltage applied to the
primary terminals. Measure input voltage VOC, input current IOC and input power POC.
Based on the equivalent circuit, input voltage is dropped across excitation branch.
Note: -ve angle because PF is always lagging for a transformer, i.e. current lags voltage.
The power factor is always lagging for real transformer, so the angle of the current
always lags the angle of the voltage by θ degrees. So the admittance, YE is
14
EME4363 Electrical Machines– Transformer
Short circuit secondary terminals, i.e. Z ' L 0 . Input voltage adjusted until rated
secondary current is produced. Measure input voltage, VSC, input current ISC and input
power PSC.
Because the voltage is so low, negligible current flows through excitation branch.
Equivalent circuit becomes:
Since the excitation branch is neglected, the series impedance is given by:
Where PF =
The short circuit test only determines the total series impedance referred to the
primary side.
There is no easy way to split the series impedance into their primary and secondary
components. Fortunately, such separation is not required when solving transformer
problems.
15
EME4363 Electrical Machines– Transformer
The base value is the reference value that can be utilized as a reference point for per unit
conversion. It is also customary to select 2 base values at a specific point in the system:
Voltage, Vbase
Apparent power, Sbase
Hence, the P.U. system automatically referes quantities to a common voltage level.
When analyzing only one device, its own ratings are used as Sbase and Vbase. If more than
one machine and one transformer are present, Sbase and Vbase can be chosen arbitrarily but
the entire system must have the same base.
P.U. values given to another base can be converted to a new base using:
16
EME4363 Electrical Machines– Transformer
a. Find the base voltage, current, impedance and apparent power at every point
in the power system.
b. Convert this system to its per-unit equivalent circuit.
c. Find the power supplied to the load in this system.
d. Find the power lost in the transmission line.
Solution:
a. Find the base voltage, current, impedance and apparent power at every point
in the power system.
Sbase
Ibase
Zbase
Each component must be divided by its base value in its region of the system.
The generator’s per unit voltage is:
17
EME4363 Electrical Machines– Transformer
Hence, the per-unit equivalent circuit for the power system is:
18
EME4363 Electrical Machines– Transformer
Transformer voltage regulation is a measure of how changes in load would vary the
output of the transformer.
By definition:
Or in a per-unit system,
A low value of VR is often desirable – indicating that the load variations do not
significantly affect transformer output.
19
EME4363 Electrical Machines– Transformer
Effects of the excitation branch ignored – only small current flows through.
VP VP
VS , meaning VR > 0. VS , meaning VR > 0.
a a
Leading PF ( I S leads V S )
VP
VS , meaning VR < 0.
a
20
EME4363 Electrical Machines– Transformer
VP
Therefore we can assume that is horizontal. By using this approximation:
a
“In all the following phasor diagrams, the phasor voltage V s is assumed to be at an
angle of 0°, and all other voltages and currents are compared to that reference.”
Considering the horizontal components, the primary voltage magnitude is given by:
Transformer Efficiency
Or
21
EME4363 Electrical Machines– Transformer
Why 3-phase?
Get more power per kg of metal from a machine.
Constant power is delivered at all times.
The generators are supplied by voltages The voltage waveform in three phases
that are equal in magnitude but differing are:
in phase angle by 120o, i.e.,
22
EME4363 Electrical Machines– Transformer
Line voltages are shifted 30o with respect to Line currents are shifted 30o with respect to phase
phase voltages: currents.
The current flowing in the neutral conductor. No neutral conductor (since there is no common
point.)
Balanced system: Loads are the same. Balanced System: Loads are the same
Unbalanced System: Loads aren’t the same. Unbalanced System: Loads aren’t the same.
𝑍𝑎 ≠ 𝑍𝑏 ≠ 𝑍𝑐 ≠ 𝑍∆
𝑍1 ≠ 𝑍2 ≠ 𝑍3 ≠ 𝑍𝑌
The total power supplied by the 3 phase system is sum of each individual generator
power. Hence, under balanced conditions:
23
EME4363 Electrical Machines– Transformer
2 types of construction:
3 separate transformers, or
3 sets of primary and secondary winding on one core.
The 3 primary and 3 secondary windings are independently connected in either a wye
or delta connection.
To analyze 3-phase transformer banks – employ per-phase basis, i.e. just look at a single
transformer. (Previous equations apply!)
All others will behave exactly the same except for the 120o phase shift between them.
24
EME4363 Electrical Machines– Transformer
Since the transformer has 3 phases, the appropriate voltage conversion is required in
order to relate the turns ratio to the line voltages.
The basic concept of calculating the per unit values for a single phase transformer applies
to 3-phase systems on a per-phase basis.
If, Sbase = total base voltampere of the 3-phase transformer, then for one transformer,
Line quantities can also be represented in per-unit system. However, suitable conversion
is needed:
Wye Connection:
Delta Connection:
25