Prefabrication
Prefabrication
SHREEYA GOYAL
160BARCHI088
4B
1. PRESTRESS
Definition : Prestress is defined as a
method of applying pre-compression to
control the stresses resulting due to
external loads below the neutral axis of the
beam tension developed due to external
load which is more than the permissible
limits of the plain concrete. The pre-
compression applied (may be axial or
eccentric) will induce the compressive
stress below the neutral axis or as a whole
of the beam cross-section. Resulting either Pre-tensioning : A method of
no tension or compression. prestressing concrete in which the tendons
Basic Concept : Prestressed concrete is are tensioned before the concrete is
basically concrete in which internal placed. In this method, the concrete is
stresses of a suitable magnitude and introduced by bond between steel &
distribution are introduced so that the concrete.
stresses resulting from the external loads Post-tensioning : A method of
are counteracted to a desired degree. prestressing concrete by tensioning the
tendons against hardened concrete. In this
method, the prestress is imparted to
1.1 TERMINOLOGY concrete by bearing.
Tendon: A stretched element used in a
concrete member of structure to impart
prestress to the concrete.
1.2 MATERIALS FOR PRE-STRESS
CONCRETE MEMBERS:
Cement : The cement used should be any
of the following
Ordinary Portland cement conforming
to IS269
Portland slag cement conforming to
IS455. But the slag content should not
be more than 50%.
Rapid hardening Portland cement
conforming to IS8041.
High strength ordinary
Anchorage: A device generally used to
Portland cement conforming to
enable the tendon to impart and maintain
IS8112.
prestress in concrete.
Concrete : Prestress concrete requires
concrete, which has a high compressive
strength reasonably early age with
comparatively higher tensile strength than
ordinary concrete. The concrete for the
members shall be air-entrained concrete
composed of Portland cement, fine and
coarse aggregates, admixtures and water.
The air-entraining feature may be obtained
by the use of either air-entraining Portland
cement or an approved air-entraining
admixture. The entrained air content shall
be not less than 4 percent or more than 6 Durability, Fire Resistance &
percent. Minimum cement content of 300 Cover Requirements For P.S.C
to 360 kg/m3 is prescribed for the Members: - According to IS:
durability requirement. The water content 1343-1980 20 mm cover for
should be as low as possible. pretensioned members 30 mm or
size of the cable whichever is bigger
for post tensioned members. If the
prestress members are exposed to
an aggressive environment, these
covers are increased by another 10
mm.
Necessity of high grade of
concrete & steel: Higher the
grade of concrete higher the bond
strength which is vital in
pretensioned concrete, also higher
Steel : High tensile steel, tendons, strands bearing strength which is vital in
or cables the steel used in prestress shall post-tensioned concrete. Further
be any one of the following: - creep & shrinkage losses are
minimum with high-grade
Plain hard-drawn steel wire concrete. Generally minimum M30
conforming to IS1785 (Part-I & grade concrete is used for post-
Part-III) tensioned & M40 grade concrete is
Cold drawn indented wire used for pretensioned members.
conforming to IS6003 88 The losses in prestress members
High tensile steel wire bar due to various reasons are
conforming to IS2090 generally in the range of 250
Uncoated stress relived strand N/mm2 to 400 N/mm . If mild steel
2
1.4 DISADVANTAGES OF
PRESTRESSED CONCRETE
The availability of experienced
builders is scanty.
1.3 ADVANTAGE OF PRESTRESSED Initial equipment cost is very high.
CONCRETE Availability of experienced
engineers is scanty.
The use of high strength concrete
Prestressed sections are brittle
and steel in prestressed members
results in lighter and slender Prestressed concrete sections are
members than is possible with RC less fire resistant.
members. 1.5 CLASSIFICATIONS AND TYPES
In fully prestressed members the
member is free from tensile Prestressed concrete structures can be
stresses under working loads, thus classified in a number of ways depending
whole of the section is effective. upon the feature of designs and
In prestressed members, dead constructions.
loads may be counter-balanced by Pre-tensioning: In which the
eccentric prestressing. tendons are tensioned before the
Prestressed concrete member concrete is placed, tendons are
possess better resistance to shear temporarily anchored and
forces due to effect of compressive tensioned and the prestress is
stresses presence or eccentric transferred to the concrete after it
cable profile. is hardened.
Use of high strength concrete and Post-tensioning: In which the
freedom from cracks, contribute to tendon is tensioned after concrete
improve durability under has hardened. Tendons are placed
aggressive environmental in sheathing at suitable places in
conditions. the member before casting and
Long span structures are possible later after hardening of concrete.
so that saving in weight is
significant & thus it will be The various methods by which pre-
economic. compression are imparted to concrete are
Factory products are possible. classified as follows:
Prestressed members are tested Generation of compressive force
before use. between the structural elements
Prestressed concrete structure and its abutments using flat jack.
deflects appreciably before Development of hoop compression
ultimate failure, thus giving ample in cylindrically shaped structures by
warning before collapse. circumferential wire binding.
Fatigue strength is better due to Use of longitudinally tensioned
small variations in prestressing steel embedded in concrete or
housed in ducts.
Use of principle of distortion of a and used for tensioning of steel wires and
statically indeterminate structure deformed bars.
either by displacement or by
rotation of one part relative to the Chemical devices : Expanding cements
remainder. are used and the degree of expansion is
Use of deflected structural steel controlled by varying the curing condition.
sections embedded in concrete Since the expansive action of cement 90
until the hardening of the latter. while setting is restrained, it induces
tensile forces in tendons and compressive
Development of limited tension in
stresses in concrete.
steel and compression in concrete
by using expanding cements. The 1.7 PRESTRESSING SYSTEM
most widely used method for
prestressing of structural concrete Pretensioning system : In the pre-
elements is longitudinal tensioning tensioning systems, the tendons are first
of steel by different tensioning tensioned between rigid anchor-blocks
devices. Prestressing by the cast on the ground or in a column or unit –
application of direct forces mould types pretensioning bed, prior to
between abutments is generally the casting of concrete in the mould. The
used for arches and pavements, tendons comprising individual wires or
while flat jacks are invariably used strands are stretched with
to impart the desired forces. constant eccentricity or a variable
eccentricity with tendon anchorage at one
1.6 TENSIONING DEVICES end and jacks at the other. With the forms
The various types devices used for in place, the concrete is cast around the
tensioning steel are grouped under four stressed tendon.
principal categories, viz.
Basic principle
Core elements
Lightweight insulated precast insulated
moulds
Insulated curing covers that shall be used
in conjunction with Waffle-Crete moulds 2.3 TYPES OF PRECAST CONCRETE
Specialized equipment shall be designed PANELS AND WALLS
for use with Waffle-Crete moulds and (According to The Building Code of India –
covers 2005)
A construction methodology for casting
and erecting concrete panels with moulds
and equipment.
Standard reinforced require, so that the top two ribs are
Standard reinforced precast concrete wall, continuous around the perimeter of the
floor and roof panels are 2.43 m wide and building, above window and door
are manufactured in lengths of 3.65 m, openings. A wide range of external finishes
4.26 m, 5 4.87 m, 5.48 m, 6.09 m & 7.31 m. and textures can be applied during casting
The surface of each panel shall consist of a of any of the panels.
51mm thick slab, stiffened with tapered
ribs around the perimeter and across the
panel. The ribs shall
be at approx. 1214 mm centres in one
direction and 610 mm in the other and give
an overall panel thickness of 152 mm or
203 mm, as required. Panels for single or
double storey building shall be either 152
mm or 203 mm thick but panels for
buildings over two floors high shall always
be 203 mm thick.
Accessory panels
Eave panels shall be used as decorative
building trim and also cover waffle voids
that may be exposed on the edges of cut
roof panels.
Grade beams shall be used to cast a first
floor foundation. Grade beam panel shall
be keyed to fit floor panel ribs.
Stair panels shall include an adjustable
blockout to cast concrete stairs of variable
width up to 2.44m. Stair moulds shall be
Harmonized reinforced available in 3.66m & 6.10m lengths with
Harmonized reinforced precast concrete 164mm risers
wall panels are 2.58 m high and are
manufactured in lengths of 3.65 m, 4.26 m, Ceiling / floor panel
4.87 m, 5.48 m, 6.09 m & 7.31 m. All Thickness of concrete of topping may vary
harmonized panels shall be 152 mm or 203 for different requirement of fire ratings.
mm thickness. The surface of these panels Floor slabs with a 60 minute fire-resistance
shall consist of a 51-mm thick slab, rating shall require a minimum of 38 mm
stiffened with ribs around the perimeter concrete topping and floor slabs with a 120
and across the panel. The ribs shall be at minute fire-resistance rating shall require a
approx. 610 mm centres, with two minimum concrete topping of 75 mm or
horizontal ribs along its length, one approx. cladding to the underside. Where ribbed
836mm from the bottom and the other panel require a 60 minute fire- resistance
418 mm from the top. These panels shall rating, the cladding to the underside of the
be used for window/door and window cut- floor shall consist of 12.7 mm thick x-rated
outs. Harmonized wall panels shall be used gypsum plasterboard of 63.5 mm x 35 mm
when a different elevation treatment is
x 0.71 mm thick on galvanized steel wound around threaded 6 mm dia.
channels at 600 mm centers fixed to the galvanized steel fasteners hand-driven into
ribs of the panels with 18 gauze steel a previously drilled hole in the rib of the
galvanized wire wound around threaded 6 floor panel.
mm dia. galvanized steel fasteners hand- Type 4 Wall panels lined on one side with
driven into a previously drilled hole in the two layers of 12.7 mm thick X-rated
rib of the floor panel. When ribbed panel gypsum plasterboard on galvanized steel
require a 120 minute fire- resistance studs with staggered joints similar to those
rating, two layers of 12.7 mm thick X-rated used in Type 3 wall fixed to the panel ribs
gypsum plasterboard are used, fixed as for in the same manner as wall Type 3.
floors with a 60 minute fire- resistance Type 5 Wall panels lined on one side with
rating. A 120 minute fire-resistance rating 12.7 mm thick X rated gypsum
shall also be required for wall, floors and plasterboard on top hat section galvanized
ceilings that enclose emergency routes in steel channels fixed to the panel ribs as for
buildings. The joints between the wall Type 3 and insulated with 150 mm
plasterboard shall be sealed according to thick glass fibre.
the manufacturer’s recommendations. Type 6 Wall panels lined on one side with
Floor slabs with a 30 minute fire-resistance 12.7 mm thick X-rated gypsum
rating shall not require a concrete topping. plasterboard on timber studs fixed to the
Thickness of concrete topping may vary for panel in the same manner as for wall Type
different requirement of fire-ratings. 2 and insulated with 50 mm thick glass
fibre.
2.5.1 MANUFACTURING
REQUIREMENTS
Concrete requirements
2.4 TYPES OF WALLS All precast concrete components shall be
adequately cured. Components shall be
SPECIFICATIONS OF THE SIX TYPES removed from the molds only when the
concrete has attained 75% of the strength
Type 1 152 mm or 203 mm panels, unlined. specified by the engineer.
Type 2 Wall panels lined on one side with All precast concrete components shall be
12.7 mm thick xrated gypsum plasterboard free of honeycombing and any patching or
on 38 mm x 38 mm timber studs 7 at 600 remedial work to minor damage shall be in
mm centers fixed to the panel ribs with accordance with the relevant Standard.
screws into nailer blocks cast into concrete Mortar used for such work shall have a
at 600 mm centers. sand cement ratio equal to the aggregate:
Type 3 Wall panels lined on one side with cement ratio of the concrete.
12.7 mm thick Xrated gypsum plasterboard
of 63.5 mm x 35 mm x 0.71 mm thick on 2.5.2 DEVIATION LIMITS
galvanized steel studs spaced at maximum All precast concrete panels shall be
450 mm centres fixed to the ribs of the manufactured with the limits specified
panels with 18 gauze steel galvanized wire
below: i. The panel thickness shall not vary essential to ensure good compaction.
by more than -3 mm and + 6 mm. 9 Needle vibrators can be used for
ii. The slab (skin) thickness shall not vary by compacting concrete in the ribs and
more than ± 2 mm screed vibrators can be used for corn
iii. The panel shall not be more than 3 mm pacting concrete in the flange. For larger
out of square per 3 m length, measured on factories, concrete placing machine which
the diagonal. iv. All anchors and inserts level, vibrate and finish the concrete units
shall be within 9 mm of the centre line can be utilized.
location shown on the drawings
v. Blockouts and reinforcement shall be
within 6 mm of the position shown on the 2.5.5 TRANSPORTATION
drawings. REQUIREMENTS
2.5.3 MOULD REQUIREMENTS Lifting hooks
The mould used for manufacturing waffle Wherever lifting hooks/holes are used
slabs normally consists of two parts (a) these shall be provided at structurally
bottom mould and (b) side moulds, advantageous points to facilitate
The bottom mould can be made out of demoulding and erection of the Precast
timber, masonry, concrete, steel FRP, unit. The lifting hooks can be formed out of
plastic or any other material acceptable to normal mild steel reinforcing bars with
engineer-ill-charge. The side moulds adequate carrying capacity to carry the self
similarly can be tirnber, steel, FRP or weight during demoulding, handling and
plastic. erection. After the erection the hooks can
When using masonry or concrete moulds, be either cut or bent down inside the
the top surface shall be finished to the screed or joint concrete that will be laid
required accuracy and made smooth. subsequently
In case of masonry moulds, the use of
chicken mesh or fibre reinforcement in the
Stacking of units
top surface
After removal from moulds the precast
will help in making the mould last longer
units shall be stacked over support places
for higher efficiency.
at about l.6’) of span from ends. Care shall
be taken to see that no support is at the
centre of the span
Transportation
For transporting and erecting the units,
rope slings shall be tied near the ends at
1/5 th of length from either end of the
In case the units are transported in trolleys,
the overhang of the units from the trolley
shall not be more than 1/5 th of length.
ERECTION DETAILS
Advantages
Compared to conventional brick and block
construction the waffle crete system
Reduces material and labour costs
Slashes construction time which is monolithic or continuous,
Eliminates need for skilled labour precast concrete buildings are made
Has low life cycle cost of separate pieces that are bolted or
connected together.
Detail drawings
Advantages
Specialised formwork
(moulds) can be built for doing
many repetitions of the same
component.
Wall panels can be ribbed, to However for the ease of precasting, the
increase their vertical span capacity skeletal frame joint is formed near the
while minimizing weight, or formed beam-column connection as shown below.
into other special shapes
4.4 APLICATION
Warehouses
Showrooms
Outdoor and indoor stadiums
Gas stations
Metro stations, Bus terminals,
Parking lots
Industrial Buildings
Cutting
Any conventional sawing equipment
appropriate for aluminium can be used.
This includes stationary vertical panel
saw, circular hand saw, jig saw or
indeed hand saw.
6. LIGHT GAUGE
Steel is widely used in the construction of
multi-storey buildings. However, steel
construction is seldom used and is
traditionally considered uneconomical for
landed properties. In many parts of the
Hand Holding world, timber or structural brickwork is
It is easy to fold ACP by hand if a ‘V’ preferred whereas in Singapore,
shaped groove is milled on the rear reinforced concrete construction is usually
side of the panel. preferred for landed properties.
The upper cladding sheet as well as An economical light gauge steel frame
0.2mm thick polyethylene should system is increasingly being used in
remain on the bottom. To enable a America, Europe, Australia and New
good fold it is recommended to opt for Zealand.
a groove flat of 3mm. This light gauge steel frame is developed
through a cold-formed process without the
use of heat. This process enables steel
manufacturers to produce light-weight but
high tensile steel sheets. The sheet surface
is coated with a zinc alloy that completely
covers the steel surface and seals it from
the corrosive action of its environment.
Routing and Milling This results in buildings that are more solid,
The copy milling machine, the hand milling rigid, stronger, durable and easier to build.
cutters and other conventional tools used As such, the light gauge steel frame system
by aluminium fabricators are acceptable is an attractive alternative for use in landed
properties. This is particularly in view of
concerns on the depletion of timber offering larger open spaces and increased
resources and low productivities design flexibility without requiring
associated with reinforced concrete intermediate columns or load bearing
construction. walls.
Recyclable : All steel products are
recyclable.
Jack Stud : A vertical structural member Load Bearing Wall : A wall that carries
that does not span the full height of the vertical loads from above or lateral loads
wall and supports vertical loads and/or resulting from wind. These loads may act
transfers lateral loads. Jack studs are used separately or in combination. Both internal
to support headers. and external walls may be load bearing.
King Stud : A vertical structural member Material Thickness : The base metal
that spans the full height of the wall and thickness excluding any protective
supports vertical loads and lateral loads. coatings. Thickness is expressed in mils
Usually located at both ends of a header (traditionally expressed in gauge).
adjacent to the jack studs to resist lateral
loads. Mil : A unit of measurement typically used
in measuring the thickness of thin
elements. One mil equals 1/1000 of an
inch.
http://questin.org/sites/default/files/stan
dards/is.10505.1983_0.pdf
http://bmtpc.org/DataFiles/CMS/file/PDF
_Files/35_PAC-SRPL.pdf
https://www.slideshare.net/larry757/intr
oduction-to-waffle-crete-11611
http://questin.org/sites/default/files/stan
dards/is.10505.1983_0.pdf
http://bmtpc.org/DataFiles/CMS/file/PDF
_Files/35_PAC-SRPL.pdf
https://www.slideshare.net/larry757/intr
oduction-to-waffle-crete-11611
https://www.bca.gov.sg/Publications/Buil
dabilitySeries/others/bsl_cp9.pdf
https://www.wiley.com/legacy/products/
subject/architecture/archdesign/construct
ioneducation/chapter/page8.html
https://www.wiley.com/legacy/products/
subject/architecture/archdesign/construct
ioneducation/chapter/page4.html