The document provides crack control calculations for rebar in a 1200mm thick slab for a project in Atlantis Royal Tower Sector 14. It includes inputs for material strengths, geometry, and actual bending moment. The calculations determine the stress in the rebar and compare it to acceptable ranges for cracking based on the location and exposure of the concrete. The calculated stress of 206.09 MPa is within the acceptable range of 17,000-20,000 N/mm for tanked concrete.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
86 views1 page

NORR Limited Architects & Engineers

The document provides crack control calculations for rebar in a 1200mm thick slab for a project in Atlantis Royal Tower Sector 14. It includes inputs for material strengths, geometry, and actual bending moment. The calculations determine the stress in the rebar and compare it to acceptable ranges for cracking based on the location and exposure of the concrete. The calculated stress of 206.09 MPa is within the acceptable range of 17,000-20,000 N/mm for tanked concrete.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

NORR Limited Architects & Engineers

Project Code : 3180


Project Name : Atlantis Royal Tower Sector 14
Area of Concern : Piping Tunnel Slab
Bars of Concern : Slab bars for 1200 thick slab
Subject : Crack Control Calculations
Date : 01 Dec '05

INPUT
Materials
f'c (Mpa) 35 Mpa
fy (Mpa) 460 Mpa

Geometry
Thickness, t (mm) 1200 mm
ClearCover, cc (mm) 50 mm Bar Area
Dia.Bar, db (mm) 25 mm As= 490.875 mm2
Spacing, s (mm) 125 mm

Actual Moment at Area of Concern


Munf (KN-m)/m 870 KN-m/m

CALCULATIONS
Ms= Munf x s KN-m
Ms= 108.75

dc= cc+db/2 Moment Arm


dc= 62.5 mm Marm= 1075 mm

Ac= 2 x dc x s
Ac= 15625 mm2

fs= Msx1E6/(As x Marm)


fs= 206.08666 Mpa

z= fs x (dc x Ac)^(1/3) Range of Acceptability:


z= 20,446.39 N/mm 30,000 N/mm Interior Exposure
25,000 N/mm Exterior Exposure
17,000 to 20,000 N/mm Tanked Concrete