Janssens - Fire and Smoke Control Design PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 57

AMCA International

General Principles of Smoke


Control
Patrick Janssens, Sales Manager
Colt International
www.coltinco.co.uk or
www.coltinfo.be

Air System Engineering & Technology (ASET) Conference–Europe


Lyon, France • L’Espace Tête d’Or • 20 February 2018
Copyright
4
AMCA International • www.amca.org
Colt International
General Principles of Smoke Control
2018 ASET-Europe conference

“People feel better in Colt conditions” | www.coltinco.co.uk or www.coltinfo.be


Copyright Materials
This educational activity is protected by U.S. and International copyright
laws. Reproduction, distribution, display, and use of the educational activity
without written permission of the presenter is prohibited.
© AMCA International

6
A brief history of Colt

• A private company founded in 1931

• I J O’Hea OBE (1897 - 1984)

• 2016 Group turnover +/-171 million EUR (2017 not known yet)

• Manufactures in the UK, Holland, Germany and China

I J O’Hea
Colt Founder
Current UK & Belgian Business Markets for SHEV’s

• SHEVS – Shopping Centres, Atria, Warehouses, Factories,


• Smoke Control etc
Static
• Smoke Curtains - Shopping Centres, Atria, Warehouses,
Factories, Carparks, …

• Smoke Control • Atria, Staircases of high buildings, Car Parks, Tunnels,…


Mechanical
General Principles of Smoke Control
Some Notable Recent Fires:
• King’s Cross
• B&Q - Leicester
• Dusseldorf Airport
• Heathrow Airport
• Bradford City Football stadium
• York Minster
• Sainsbury’s – Chichester
• Windsor Castle
• Warehouse, Atherstone
General Principles of Smoke Control

Sainsbury’s
Chichester
Shopping Mall

Arsonist set fire to this unsprinklered and unvented store,


shortly before Christmas. £14.5 million worth of damage
including loss of building, loss of all stock and loss of
business for many months to follow.
General Principles of Smoke Control

Dusseldorf Airport
Germany

17 people killed including a child, several women and a police


officer. Over 60 injured due to smoke logging from a relatively
small fire spreading throughout the Terminal.
General Principles of Smoke Control

Source: Fire Statistics, United


Kingdom, 2011 - DCLG

Smoke is by far the biggest killer


Why Provide Smoke Control?

• Protect escape routes

• Assist fire fighting

• Protect valuable stock or machinery

• Reduce the risk of explosion and/or roof


collapse
Smoke Clearance –vSmoke Control
Smoke Clearance Ventilation

Uses a notional amount of ventilation to assist fire fighting


operations, allowing fire fighters to clear smoke from the
relevant building or part of building often after the fire has
been extinguished.
• Natural: Natural openings providing a percentage of the
plan area of the space
• Mechanical: Extract fans providing a number of air
changes of the volume of the space per hour

By definition, smoke clearance offers limited benefit during


evacuation and has a much simplified design basis.
Smoke Clearance –v- Smoke Control

Smoke Control Ventilation

Smoke Control Systems are designed to control or restrict


the movement of smoke within the building.

In order to do this it is usually necessary to estimate the


amount of smoke produced by a fire and the heat energy
present. Then measures such as ventilation can be used to
remove smoke to provide vertical control and barriers can be
used to control horizontal smoke movement.

Again, these can be natural or mechanical systems, but the


design is much more complex and requires an estimate of
the fire size.
Interaction Between Sprinklers and Vents

Sprinklers Ventilation

• Will limit fire spread • Will prevent smoke


and control growth logging
• Will not reduce • Assist escape
smoke damage • Aid fire fighting

Sprinklers are designed to reduce damage, but offer


limited benefit to occupants. Smoke ventilation alone
will not save the building but is primarily designed to
assist escape.
History and Development

1881 – Ring Theatre, Vienna – 800 dead


1887 – Theatre Royal, Exeter – 187 dead
1887 – Paris Opera – 200 dead
1903 – Iroquois Theatre, Chicago – 602
dead
History and Development

General Motors Factory, Michigan


1953

6 dead

140,000 m2 plant destroyed

Loss of production of automatic


gearboxes for 5 major car
manufacturers
History and Development
Current Documents:

The Building Regulations 2000: Approved Document B (2006)

Codes of Practice: BS 5588-1 to 12, BS 9999, BS 9991

Specifications: EN 12101-1, 2, 3, 7, 8 & 10

Design Guidance:
Great-Britain: BR 368 – Design Methodologies for Smoke
and Heat Exhaust Ventilation
BS 7346-4, 5 & 7, CEN TR 12101-5
BS 7974
Belgium: NBN-S-21-208-1 (single storey buildings)
NBN-S-21-208-2 (Car Parks)
Breakdown of Smoke Control Applications

• Factories/Warehouses/Retail Sheds
• Shopping Centres
• Atria
• Car Parks
Factories/Warehouses/Retail Sheds –
Large Single Storey Buildings

Control of the temperature of the smoke layer (max. 300°C)

Control of the height between the floor and the smoke layer (min. 3m)

Design Guidance: BS 7346-4 & 5


Great-Britain SVA Guide Issue 3

Belgium: NBN-S-21-208-1 (single storey buildings


Applications: Large Single Storey Buildings

In the early stages of fire, smoke quickly rises


into roof space
General Principles of Smoke Control

Smoke travels laterally beneath the roof and spreads


throughout the building
Applications: Large Single
Storey Buildings

Even large buildings can become totally smoke


logged in minutes
Applications: Large Single Storey Buildings

In a smoke logged building, way finding can be very


difficult and temperatures will rise rapidly – leading
to loss of structural stability and building collapse.
Applications: Large Single Storey Buildings

Evacuation is safer and fire fighting more effective


when the routes are clear
Applications: Large Single Storey Buildings

Objectives of Smoke Control:

• Assist escape by extending available safe


evacuation time

• Assist fire fighting by improving conditions in the


building during the fire and clearing smoke from the
building after.

• Protect valuable stock or machinery


• Reduce the risk of explosion and/or roof collapse
Applications: Fire and Smoke without SHEV’s.

Time taken for smoke to affect escape routes Available Safe


Escape Time

Detection
Time
Clear layer height (m)

Pre-movement
time

Evacuation Time

Required Safe
Escape Time

Fire
Starts
Applications: Fire and Smoke with SHEV’s.

Time taken for smoke to affect escape routes Available Safe


Escape Time

Detection
Time
Clear layer height (m)

Pre-movement
time

Evacuation Time

Required Safe
Escape Time

Fire
Starts
Applications: Fire and Smoke

Time dependent Fires Steady State Fires


Steady state fire
Peak size
Heat output

Ultrafast

Fire Size
fast
medium
slow
Growth Decay

Time Time

Steady State design ignores growth and decay of fire and


takes into account the largest probable fire for a given risk
Applications: Large Single Storey Buildings

Steady State Fires

• 3 m x 3 m (minimum)
• 4,5 x 4,5 m
• 6mx6m
• 9 m x 9 m (maximum)

Fire Engineer estimates the size


of the fire surface according the
type of industry.
3m 3m
Applications: Smoke Control

Components of a Smoke Control System


Applications: Large Single Storey Buildings
Applications: Large Single Storey Buildings

1. Smoke exhaust.
2. Air inlet.
3. Smoke screen.
4. Smoke detector.
5. Fire detection panel.
6. Control panel SHEV’s.
Applications: Large Single Storey Buildings

In buildings larger than 2.000 m²


or longer than 60 m, the use of
smoke screens is mandatory to
avoid recirculation.
Applications: Large Single Storey Buildings

Mezzanine Floors
needs a separate
approach to
engineer.
Applications: Shopping Centres

• Large uncompartmented buildings


• Full of people who are unfamiliar with the building layout.
• Varied cross-section community, e.g. elderly and disabled.
• Evacuation time can be considerable.

Smoke Control is therefore a requirement to assist in keeping escape


routes safe for an extended time period.

Design guidance is given in BS 5588 Part 10: 1991, BS 9999, BS 7346-4


and BR 368 and for Belgium in the EN-12101-5
Applications: Shopping Centres

Extract direct from shop


• Extract from under
balcony
• Extract from mall roof
space

Multiple levels further


complicate the situation
Applications: Large Shopping
Centres
• Smoke flow only through one
void
• Limit perimeter of spill edge
• Limit smoke reservoir length in
mall
• Limit plume height for
practicality / cost effectiveness
• Natural ventilators to be as high
as possible
• Inlet availability
Applications: Atria Buildings

Atria

If the vertical compartmentation specified in ADB cannot be met, i.e. the


building has an Atrium, then it should be designed in accordance with
BS5588 Part 7:1997 or BS 9999, which, depending on the application,
may require smoke clearance or smoke control.

Important factors are whether people are unfamiliar with the building (e.g.
public buildings) and possibly asleep (e.g. hospitals or hotels).
Applications: Atria Buildings

Sterile Tube Closed Atrium

Open Atrium
Applications: Atria Buildings

Possible Solutions
Depends on use of building, fire risk, occupancy type, type of atria, etc….

But usually one of the following:


• Smoke clearance
• Extract from room of origin
• Extract from floor of origin
• Through flow
• Depressurisation
Applications: Atria Buildings

As natural ventilation are buoyancy driven, exhaust


ventilators should be located at the highest point possible.
Natural or Mechanical Extraction

Natural Mechanical

• Fail safe operation • Not wind pressure sensitive


• Self compensating • Suitable for ducting
• Silent operation • Fixed extract volume
• No time or temperature limits • Noise and Weight
• Lightweight • Maintained electrical supply
• Sensitive to wind effects • Dedicated air inlet
• Standby unit in case of fan failure
Wind effects

Positive wind pressures may be


experienced on roof pitches
steeper than 30 degees…
Wind effects

… and from higher


adjacent structures
Wind effects

Mechanical Ventilation may


be the only alternative
Ventilator Types

Louvred Roof Vents

Glazed Wall Louvres


Ventilator Types

Casement Roof Vents

Double-Flap Roof Vents


Ventilator Types
Mechanical (powered) vent
Ventilator Types
Mechanical (powered) vent

Tunnel ventilation
Inlet or “Replacement” Air
Smoke Reservoirs

• Required to limit the spread of smoke

• Formed using fixed or automatic drop smoke barriers

• Arranged to limit the size of the smoke reservoir at high level to a maximum of
:

- 2000m2 plan area, and


- 60 m long in any direction

Note: In shopping centres the reservoir is assumed to be 50% in the shop and
50% in
the mall
Smoke Reservoirs
Applications: Car Park Ventilation

Ventilation in car parks is provided for two purposes

• To prevent the build up of fume during the daily


use of the car park in accordance with Approved
Document F

• To provide smoke clearance ventilation in the


event of a fire to assist the Fire Service in
accordance with Approved Document B.

A single dual purpose system is normally provided to


meet both requirements
Applications: Car Park Ventilation

Smoke Control Systems

Specifically designed to achieve the CONTROL of smoke movement. Usually requires


additional extract over and above the basic clearance requirement.
Min. 120.000 m³/h

Can be designed to:


• Aid escape and therefore extend safe escape distances
• Assist fire fighting as an alternative to sprinklers. The fire brigade must be able to
reach the fire within 15 m with the wind in their back.
In the UK and Belgium, sprinklers are generally not required in car parks, except in
certain applications, such as shopping centres or larger projects in London and
Scotland.
Applications: Car Park Ventilation

Smoke Control Systems

Velocity between 1,1 m/s


and 1,5 m/s depending on
the width of the car park.
Applications: Car Park Ventilation

Smoke Control Systems

CFD is a common
tool to design smoke
and heat systems for
Car Parks
Conclusions

The application of smoke clearance and smoke control are


varied and with specialist knowledge can be used to
compensate for other standard features in many ways.

As with many fire safety systems, the concept is usually quite


straightforward but life safety systems must be robust and
comprehensive, not only in their design, but also in the
application and maintenance of the equipment that makes up
the system.
Ventilation In Car Parks

Thank you.
Patrick Janssens

“People feel better in Colt conditions” | www.coltgroup.com

You might also like