General Data: Table 4. Modulating Valve Selections For Horizontal Concealed Units

This document contains two tables providing specifications for modulating valve selections for different unit sizes of horizontal concealed and vertical cabinet air handling units. Table 4 provides valve selections for horizontal concealed units based on coil type and size, flow rate, pressure drop and valve Cv. Table 5 provides the same specifications for vertical cabinet units. The valves are selected to match the coil and unit size in order to regulate water flow.

Uploaded by

Saul Cervera
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
47 views1 page

General Data: Table 4. Modulating Valve Selections For Horizontal Concealed Units

This document contains two tables providing specifications for modulating valve selections for different unit sizes of horizontal concealed and vertical cabinet air handling units. Table 4 provides valve selections for horizontal concealed units based on coil type and size, flow rate, pressure drop and valve Cv. Table 5 provides the same specifications for vertical cabinet units. The valves are selected to match the coil and unit size in order to regulate water flow.

Uploaded by

Saul Cervera
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

UNT-PRC001-EN.

book Page 24 Tuesday, May 8, 2012 10:54 AM

General Data

Table 4. Modulating valve selections for horizontal concealed units


Horizontal Concealed (High Static Motor)
Coil Coil Valve
Unit Size Coil Gpm WPD Cv Cv
02 2-Row 1.29 8.8 0.66 0.7
3-Row 1.80 23.9 0.56 0.7
4-Row 1.84 6.1 1.13 1.5
03 2-Row 1.58 14.1 0.64 0.7
3-Row 1.86 5.4 1.22 1.5
4-Row 2.26 9.7 1.10 1.5
04 2-Row 1.90 4.6 1.35 1.5
3-Row 2.94 13.9 1.20 1.5
4-Row 3.35 22.3 1.08 0.7
06 2-Row 3.32 15.3 1.29 1.5
3-Row 4.24 7.5 2.35 2.5
4-Row 4.99 11.9 2.20 2.5
08 2-Row 3.90 5.7 2.48 2.5
3-Row 5.13 11.8 2.27 2.5
4-Row 5.68 16.9 2.10 2.5
10 2-Row 5.23 10.8 2.42 2.5
3-Row 7.14 24.2 2.21 2.5
4-Row 7.63 32.8 2.03 2.5
12 2-Row 6.35 16.6 2.37 2.5
3-Row 7.98 18.5 2.82 2.5
4-Row 9.47 25.2 2.87 2.5

Table 5. Modulating valve selections for vertical cabinet units


Vertical Cabinet (Free Discharge Motor)
Coil Coil Valve
Unit Size Coil Gpm WPD Cv Cv
02 2-Row 1.04 6.1 0.64 0.7
3-Row 1.40 15.4 0.54 0.7
4-Row 1.40 3.7 1.11 1.5
03 2-Row 1.32 10.3 0.63 0.7
3-Row 1.57 4.0 1.19 1.5
4-Row 1.88 7.0 1.08 0.7
04 2-Row 1.68 3.7 1.33 1.5
3-Row 2.25 8.6 1.17 1.5
4-Row 2.54 13.6 1.05 0.7
06 2-Row 2.86 11.7 1.27 1.5
3-Row 3.19 4.4 2.31 2.5
4-Row 3.74 7.0 2.15 2.5
08 2-Row 3.14 3.8 2.45 2.5
3-Row 4.01 7.5 2.23 2.5
4-Row 4.44 10.8 2.05 2.5
10 2-Row 4.39 7.8 2.39 2.5
3-Row 5.60 15.4 2.17 2.5
4-Row 5.88 20.4 1.98 1.5
12 2-Row 5.28 11.8 2.34 2.5
3-Row 6.14 11.2 2.79 2.5
4-Row 7.23 15.4 2.80 2.5

24 UNT-PRC001-EN