0% found this document useful (0 votes)
51 views2 pages

Document Title Project No.: Job No.: Doc No.:: New 48" Crude Transit Line From North Kuwait To CMM

This document provides a heat dissipation calculation for a generator and control panel. It calculates the heat produced by various components during stand-by and running periods in different locations, including the control panel, generator canopy, generator room, and outside building. The total heat dissipation in the electrical room is estimated at 2.67 kW and the largest sources of heat outside are from the engine exhaust system at 300 kW and generator canopy ventilation at 381.4 kW.

Uploaded by

Keval Desai
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views2 pages

Document Title Project No.: Job No.: Doc No.:: New 48" Crude Transit Line From North Kuwait To CMM

This document provides a heat dissipation calculation for a generator and control panel. It calculates the heat produced by various components during stand-by and running periods in different locations, including the control panel, generator canopy, generator room, and outside building. The total heat dissipation in the electrical room is estimated at 2.67 kW and the largest sources of heat outside are from the engine exhaust system at 300 kW and generator canopy ventilation at 381.4 kW.

Uploaded by

Keval Desai
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

NEW 48” CRUDE TRANSIT LINE FROM NORTH KUWAIT TO CMM

Document Title Doc No.:

Project No.: XXX HEAT DISSIPATION CALCULATION FOR XXXX


GENERATOR AND CONTROL PANEL FOR
Job No.: XX 105-Z-001 Rev. No.: 0 PAGE: 1

HEAT DISSIPATION
POS. ST / RN LOCATION Q.ty EQUIPMENT kW NOTE
per unit total

A ST / RN ELR 1 DG CONTROL PANEL 2.67

A.1 ST / RN ELR 5 Anticondensation heaters 0.1 0.50 Eximated average value

A.2 ST / RN ELR 2 Battery chargers 0.2 0.40

A.3 ST / RN ELR 3 Cabinet fan 0.2 0.60

A.4 ST / RN ELR 1 Gensys contoller 0.02 0.02

A.5 ST / RN ELR 1 I/O modules 0.09 0.09

A.6 ST / RN ELR 1 HMI 19" display 0.06 0.06

A.7 ST / RN ELR 1 Protection relay 0.06 0.06

A.8 ST / RN ELR 2 Automatic Voltage Regulator (AVR) 0.08 0.16

A.9 RN ELR 1 LV generator breaker & busbars 0.14 0.14

A.10 RN ELR 1 LV load bank breaker & busbars 0.04 0.04 Only for test period

A.11 ST / RN ELR 1 Other components of Control Panel 0.6 0.60

TOTAL HEAT DISSIPATION IN THE ELECTRICAL ROOM 2.67

NOTE ST HEAT DISSIPATION DURING STAND-BY PERIOD

RN HEAT DISSIPATION DURING RUNNING PERIOD

DGR DIESEL GENERATOR ROOM

DGC DIESEL GENERATOR CANOPY

ELR ELECTRICAL ROOM

OUT OUTSIDE BUILDING

7/20/2018
NEW 48” CRUDE TRANSIT LINE FROM NORTH KUWAIT TO CMM

Document Title Doc No.:

Project No.: XXX HEAT DISSIPATION CALCULATION FOR XXXX


GENERATOR AND CONTROL PANEL FOR
Job No.: XX 105-Z-001 Rev. No.: 0 PAGE: 2

HEAT DISSIPATION
POS. ST / RN LOCATION Q.ty EQUIPMENT kW NOTE
per unit total

B DGC 1 DIESEL GENERATOR CANOPY/ENCLOSURE 381.40

B.1 RN OUT 1 Engine cooling system 115 227.00

B.2 RN OUT 1 Engine intercooler system 100 100.00

B.3 RN DGC 1 Radiated from engine 28 28.00

B.4 ST DGC 1 Engine preheating system 1.4 1.40 Estimated average value

B.5 RN DGC 1 Alternator cooling system 24 24.00

B.6 ST DGC 1 Alternator anticondensation system 0.4 0.40 Estimated average value

B.7 ST / RN DGC 2 Starting battery bank 0.3 0.60 Estimated average value

C DGR 1 DIESEL GENERATOR ROOM 5.00

C.1 RN DGR 1 Radiated from noise enclosure 1 1.00 Estimated average value

C.2 RN DGR 1 Radiated from exhaust system 4 4.00

D OUT 1 OUTSIDE BUILDING 741.40

D.1 RN OUT 1 Engine exhaust system 300 300.00

D.2 RN OUT 1 Diesel generator canopy ventilation 381.40 381.40 See previous Item D

D.3 RN OUT 1 Load Bank 60 60.00 Only for test period

NOTE ST HEAT DISSIPATION DURING STAND-BY PERIOD

RN HEAT DISSIPATION DURING RUNNING PERIOD

DGR DIESEL GENERATOR ROOM

DGC DIESEL GENERATOR CANOPY

ELR ELECTRICAL ROOM