API 610 Check Caesar

This document summarizes the results of a nozzle load analysis on a fire water pump using CAESAR II software. It analyzes loads on the suction and discharge nozzles under various load cases including hydrotest, operating, sustain, and expansion. The loads are within allowable limits specified in the API 610 standard. The overall pump status passes for all load cases analyzed.

Uploaded by

Septian Firdaus
Copyright
© © All Rights Reserved
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
300 views

API 610 Check Caesar

This document summarizes the results of a nozzle load analysis on a fire water pump using CAESAR II software. It analyzes loads on the suction and discharge nozzles under various load cases including hydrotest, operating, sustain, and expansion. The loads are within allowable limits specified in the API 610 standard. The overall pump status passes for all load cases analyzed.

Uploaded by

Septian Firdaus
Copyright
© © All Rights Reserved
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 22

C A E S A R I I VERS 4.

40 NOV 14,2009 8:12:22


Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Fire Water Pump P-05A
INPUT (CAESAR II Global Coordinates):
Load Case : Hydrotest

Vertical In-Line Pump

Nozzles direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 8
Discharge Nozzle 10 Side 6

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Force = 0.0 lb. 145.0 lb.


Y Force = 0.0 lb. -62.0 lb.
Z Force = 0.0 lb. 14.0 lb.

X Moment = 0.0 ft.lb. 122.0 ft.lb.


Y Moment = 0.0 ft.lb. 59.0 ft.lb.
Z Moment = 0.0 ft.lb. -144.0 ft.lb.

1
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status

Values Ratios

x force = 0.0 lb. 850 0.00 Passed


y force = 0.0 lb. 1100 0.00 Passed
z force = 0.0 lb. 700 0.00 Passed

x moment = 0.0 ft.lb. 2600 0.00 Passed


y moment = 0.0 ft.lb. 1300 0.00 Passed
z moment = 0.0 ft.lb. 1900 0.00 Passed

Discharge Table 2 Force & Moment Status

Values Ratios

x force = 14.0 lb. 560 0.03 Passed


y force = 145.0 lb. 700 0.21 Passed
z force = -62.0 lb. 460 0.13 Passed

x moment = -144.0 ft.lb. 1700 0.08 Passed


y moment = 122.0 ft.lb. 870 0.14 Passed
z moment = 59.0 ft.lb. 1300 0.05 Passed

The Suction Nozzle Stress (Ss) = 0.0 lb./sq.in. Passed


The Discharge Nozzle Stress (Sd) = 275.0 lb./sq.in. Passed
The allowable nozzle stress = 5950.0 lb./sq.in.

Overall Pump Status ** PASSED **

2
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Fire Water Pump P-005A
INPUT (CAESAR II Global Coordinates):
Load Case : Operating

Vertical In-Line Pump


Nozzles direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 8
Discharge Nozzle 10 Side 6

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Force = 0.0 lb. 488.0 lb.


Y Force = 0.0 lb. -42.0 lb.
Z Force = 0.0 lb. 70.0 lb.

X Moment = 0.0 ft.lb. 151.0 ft.lb.


Y Moment = 0.0 ft.lb. 265.0 ft.lb.
Z Moment = 0.0 ft.lb. -230.0 ft.lb.

3
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status


Values Ratios

x force = 0.0 lb. 850 0.00 Passed


y force = 0.0 lb. 1100 0.00 Passed
z force = 0.0 lb. 700 0.00 Passed

x moment = 0.0 ft.lb. 2600 0.00 Passed


y moment = 0.0 ft.lb. 1300 0.00 Passed
z moment = 0.0 ft.lb. 1900 0.00 Passed

Discharge Table 2 Force & Moment Status


Values Ratios

x force = 70.0 lb. 560 0.12 Passed


y force = 488.0 lb. 700 0.70 Passed
z force = -42.0 lb. 460 0.09 Passed

x moment = -230.0 ft.lb. 1700 0.14 Passed


y moment = 151.0 ft.lb. 870 0.17 Passed
z moment = 265.0 ft.lb. 1300 0.20 Passed

The Suction Nozzle Stress (Ss) = 0.0 lb./sq.in. Passed


The Discharge Nozzle Stress (Sd) = 596.9 lb./sq.in. Passed
The allowable nozzle stress = 5950.0 lb./sq.in.

Overall Pump Status ** PASSED **

4
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Fire Water Pump P-05A
INPUT (CAESAR II Global Coordinates):
Load Case : Sustain

Vertical In-Line Pump


Nozzles direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 8
Discharge Nozzle 10 Side 6

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Force = 0.0 lb. 146.0 lb.


Y Force = 0.0 lb. -63.0 lb.
Z Force = 0.0 lb. 14.0 lb.

X Moment = 0.0 ft.lb. 123.0 ft.lb.


Y Moment = 0.0 ft.lb. 60.0 ft.lb.
Z Moment = 0.0 ft.lb. -143.0 ft.lb.

5
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status


Values Ratios

x force = 0.0 lb. 850 0.00 Passed


y force = 0.0 lb. 1100 0.00 Passed
z force = 0.0 lb. 700 0.00 Passed

x moment = 0.0 ft.lb. 2600 0.00 Passed


y moment = 0.0 ft.lb. 1300 0.00 Passed
z moment = 0.0 ft.lb. 1900 0.00 Passed

Discharge Table 2 Force & Moment Status


Values Ratios

x force = 14.0 lb. 560 0.03 Passed


y force = 146.0 lb. 700 0.21 Passed
z force = -63.0 lb. 460 0.14 Passed

x moment = -143.0 ft.lb. 1700 0.08 Passed


y moment = 123.0 ft.lb. 870 0.14 Passed
z moment = 60.0 ft.lb. 1300 0.05 Passed

The Suction Nozzle Stress (Ss) = 0.0 lb./sq.in. Passed


The Discharge Nozzle Stress (Sd) = 275.0 lb./sq.in. Passed
The allowable nozzle stress = 5950.0 lb./sq.in.

Overall Pump Status ** PASSED **

6
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Fire Water Pump P-05A
INPUT (CAESAR II Global Coordinates):
Load Case : Expansion

Vertical In-Line Pump


Nozzles direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 8
Discharge Nozzle 10 Side 6

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Force = 0.0 lb. 343.0 lb.


Y Force = 0.0 lb. 21.0 lb.
Z Force = 0.0 lb. 55.0 lb.

X Moment = 0.0 ft.lb. 29.0 ft.lb.


Y Moment = 0.0 ft.lb. 205.0 ft.lb.
Z Moment = 0.0 ft.lb. -87.0 ft.lb.

7
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status


Values Ratios

x force = 0.0 lb. 850 0.00 Passed


y force = 0.0 lb. 1100 0.00 Passed
z force = 0.0 lb. 700 0.00 Passed

x moment = 0.0 ft.lb. 2600 0.00 Passed


y moment = 0.0 ft.lb. 1300 0.00 Passed
z moment = 0.0 ft.lb. 1900 0.00 Passed

Discharge Table 2 Force & Moment Status


Values Ratios

x force = 55.0 lb. 560 0.10 Passed


y force = 343.0 lb. 700 0.49 Passed
z force = 21.0 lb. 460 0.05 Passed

x moment = -87.0 ft.lb. 1700 0.05 Passed


y moment = 29.0 ft.lb. 870 0.03 Passed
z moment = 205.0 ft.lb. 1300 0.16 Passed

The Suction Nozzle Stress (Ss) = 0.0 lb./sq.in. Passed


The Discharge Nozzle Stress (Sd) = 372.1 lb./sq.in. Passed
The allowable nozzle stress = 5950.0 lb./sq.in.

Overall Pump Status ** PASSED **

8
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Fire Water Pump P-05B
INPUT (CAESAR II Global Coordinates):
Load Case : Hydrotest

Vertical In-Line Pump


Nozzles direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 8
Discharge Nozzle 500 Side 6

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Force = 0.0 lb. -96.0 lb.


Y Force = 0.0 lb. -179.0 lb.
Z Force = 0.0 lb. 10.0 lb.

X Moment = 0.0 ft.lb. 164.0 ft.lb.


Y Moment = 0.0 ft.lb. 39.0 ft.lb.
Z Moment = 0.0 ft.lb. 336.0 ft.lb.

9
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status


Values Ratios

x force = 0.0 lb. 850 0.00 Passed


y force = 0.0 lb. 1100 0.00 Passed
z force = 0.0 lb. 700 0.00 Passed

x moment = 0.0 ft.lb. 2600 0.00 Passed


y moment = 0.0 ft.lb. 1300 0.00 Passed
z moment = 0.0 ft.lb. 1900 0.00 Passed

Discharge Table 2 Force & Moment Status


Values Ratios

x force = 10.0 lb. 560 0.02 Passed


y force = -96.0 lb. 700 0.14 Passed
z force = -179.0 lb. 460 0.39 Passed

x moment = 336.0 ft.lb. 1700 0.20 Passed


y moment = 164.0 ft.lb. 870 0.19 Passed
z moment = 39.0 ft.lb. 1300 0.03 Passed

The Suction Nozzle Stress (Ss) = 0.0 lb./sq.in. Passed


The Discharge Nozzle Stress (Sd) = 526.6 lb./sq.in. Passed
The allowable nozzle stress = 5950.0 lb./sq.in.

Overall Pump Status ** PASSED **

10
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Fire Water Pump P-05B
INPUT (CAESAR II Global Coordinates):
Load Case : Operating

Vertical In-Line Pump


Nozzles direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 8
Discharge Nozzle 500 Side 6

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Force = 0.0 lb. 934.0 lb.


Y Force = 0.0 lb. -189.0 lb.
Z Force = 0.0 lb. 59.0 lb.

X Moment = 0.0 ft.lb. 155.0 ft.lb.


Y Moment = 0.0 ft.lb. 195.0 ft.lb.
Z Moment = 0.0 ft.lb. 375.0 ft.lb.

11
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status


Values Ratios

x force = 0.0 lb. 850 0.00 Passed


y force = 0.0 lb. 1100 0.00 Passed
z force = 0.0 lb. 700 0.00 Passed

x moment = 0.0 ft.lb. 2600 0.00 Passed


y moment = 0.0 ft.lb. 1300 0.00 Passed
z moment = 0.0 ft.lb. 1900 0.00 Passed

Discharge Table 2 Force & Moment Status


Values Ratios

x force = 59.0 lb. 560 0.11 Passed


y force = 934.0 lb. 700 1.33 Failed
z force = -189.0 lb. 460 0.41 Passed

x moment = 375.0 ft.lb. 1700 0.22 Passed


y moment = 155.0 ft.lb. 870 0.18 Passed
z moment = 195.0 ft.lb. 1300 0.15 Passed

The Suction Nozzle Stress (Ss) = 0.0 lb./sq.in. Passed


The Discharge Nozzle Stress (Sd) = 777.4 lb./sq.in. Passed
The allowable nozzle stress = 5950.0 lb./sq.in.

Overall Pump Status ** PASSED **

12
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Fire Water Pump P-05B
INPUT (CAESAR II Global Coordinates):
Load Case : Sustain

Vertical In-Line Pump


Nozzles direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 8
Discharge Nozzle 500 Side 6

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Force = 0.0 lb. -96.0 lb.


Y Force = 0.0 lb. -180.0 lb.
Z Force = 0.0 lb. 10.0 lb.

X Moment = 0.0 ft.lb. 166.0 ft.lb.


Y Moment = 0.0 ft.lb. 40.0 ft.lb.
Z Moment = 0.0 ft.lb. 340.0 ft.lb.

13
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status


Values Ratios

x force = 0.0 lb. 850 0.00 Passed


y force = 0.0 lb. 1100 0.00 Passed
z force = 0.0 lb. 700 0.00 Passed

x moment = 0.0 ft.lb. 2600 0.00 Passed


y moment = 0.0 ft.lb. 1300 0.00 Passed
z moment = 0.0 ft.lb. 1900 0.00 Passed

Discharge Table 2 Force & Moment Status


Values Ratios

x force = 10.0 lb. 560 0.02 Passed


y force = -96.0 lb. 700 0.14 Passed
z force = -180.0 lb. 460 0.39 Passed

x moment = 340.0 ft.lb. 1700 0.20 Passed


y moment = 166.0 ft.lb. 870 0.19 Passed
z moment = 40.0 ft.lb. 1300 0.03 Passed

The Suction Nozzle Stress (Ss) = 0.0 lb./sq.in. Passed


The Discharge Nozzle Stress (Sd) = 532.7 lb./sq.in. Passed
The allowable nozzle stress = 5950.0 lb./sq.in.

Overall Pump Status ** PASSED **

14
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Fire Water Pump P-05B
INPUT (CAESAR II Global Coordinates):
Load Case : Expansion

Vertical In-Line Pump


Nozzles direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 8
Discharge Nozzle 500 Side 6

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Force = 0.0 lb. 1030.0 lb.


Y Force = 0.0 lb. -9.0 lb.
Z Force = 0.0 lb. 49.0 lb.

X Moment = 0.0 ft.lb. -11.0 ft.lb.


Y Moment = 0.0 ft.lb. 156.0 ft.lb.
Z Moment = 0.0 ft.lb. 36.0 ft.lb.

15
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status


Values Ratios

x force = 0.0 lb. 850 0.00 Passed


y force = 0.0 lb. 1100 0.00 Passed
z force = 0.0 lb. 700 0.00 Passed

x moment = 0.0 ft.lb. 2600 0.00 Passed


y moment = 0.0 ft.lb. 1300 0.00 Passed
z moment = 0.0 ft.lb. 1900 0.00 Passed

Discharge Table 2 Force & Moment Status


Values Ratios

x force = 49.0 lb. 560 0.09 Passed


y force = 1030.0 lb. 700 1.47 Failed
z force = -9.0 lb. 460 0.02 Passed

x moment = 36.0 ft.lb. 1700 0.02 Passed


y moment = -11.0 ft.lb. 870 0.01 Passed
z moment = 156.0 ft.lb. 1300 0.12 Passed

The Suction Nozzle Stress (Ss) = 0.0 lb./sq.in. Passed


The Discharge Nozzle Stress (Sd) = 404.4 lb./sq.in. Passed
The allowable nozzle stress = 5950.0 lb./sq.in.

Overall Pump Status ** PASSED **

16
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Jockey Pump P-006
INPUT (CAESAR II Global Coordinates):
Load Case : Operating

Horizontal Pump
Pump axis direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 3
Discharge Nozzle 360 Side 2

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Distance = 0.0 in. 0.0 in.


Y Distance = 0.0 in. 11.8 in.
Z Distance = 0.0 in. 11.8 in.

X Force = 0.0 lb. 80.0 lb.


Y Force = 0.0 lb. -43.0 lb.
Z Force = 0.0 lb. 1.0 lb.

X Moment = 0.0 ft.lb. 11.0 ft.lb.


Y Moment = 0.0 ft.lb. 4.0 ft.lb.
Z Moment = 0.0 ft.lb. 107.0 ft.lb.

17
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status


Values Ratios
x distance = 0.0 in.
y distance = 0.0 in.
z distance = 0.0 in.

x force = 0.0 lb. 240 0.00 Passed


y force = 0.0 lb. 300 0.00 Passed
z force = 0.0 lb. 200 0.00 Passed

x moment = 0.0 ft.lb. 700 0.00 Passed


y moment = 0.0 ft.lb. 350 0.00 Passed
z moment = 0.0 ft.lb. 530 0.00 Passed

Discharge Table 2 Force & Moment Status


Values Ratios
x distance = 0.0 in.
y distance = -11.8 in.
z distance = 11.8 in.

x force = 80.0 lb. 160 0.50 Passed


y force = -1.0 lb. 200 0.00 Passed
z force = -43.0 lb. 130 0.33 Passed

x moment = 11.0 ft.lb. 340 0.03 Passed


y moment = -107.0 ft.lb. 170 0.63 Passed
z moment = 4.0 ft.lb. 260 0.02 Passed

Check of Condition F.1.2.2 Requirement Status

(FRSa/1.5FRSt2) + (MRSa/1.5MRSt2) = 0.000 < or = 2.00 Passed


(FRDa/1.5FRDt2) + (MRDa/1.5MRDt2) = 0.365 < or = 2.00 Passed

Check of Condition F.1.2.3 Requirement Status

1.5 ( FRSt2 + FRDt2 ) = 1080. > 91. (FRCa) Passed


2.0 ( MYSt2 + MYDt2 ) = 1040. > 28. (MYCa) Passed
1.5 ( MRSt2 + MRDt2 ) = 2115. > 103. (MRCa) Passed

Overall Pump Status ** PASSED **

18
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Jockey Pump P-006
INPUT (CAESAR II Global Coordinates):
Load Case : Hydrotest

Horizontal Pump
Pump axis direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 3
Discharge Nozzle 360 Side 2

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Distance = 0.0 in. 0.0 in.


Y Distance = 0.0 in. 11.8 in.
Z Distance = 0.0 in. 11.8 in.

X Force = 0.0 lb. -1.0 lb.


Y Force = 0.0 lb. -43.0 lb.
Z Force = 0.0 lb. 0.0 lb.

X Moment = 0.0 ft.lb. 11.0 ft.lb.


Y Moment = 0.0 ft.lb. 0.0 ft.lb.
Z Moment = 0.0 ft.lb. 107.0 ft.lb.

19
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status


Values Ratios
x distance = 0.0 in.
y distance = 0.0 in.
z distance = 0.0 in.

x force = 0.0 lb. 240 0.00 Passed


y force = 0.0 lb. 300 0.00 Passed
z force = 0.0 lb. 200 0.00 Passed

x moment = 0.0 ft.lb. 700 0.00 Passed


y moment = 0.0 ft.lb. 350 0.00 Passed
z moment = 0.0 ft.lb. 530 0.00 Passed

Discharge Table 2 Force & Moment Status


Values Ratios
x distance = 0.0 in.
y distance = -11.8 in.
z distance = 11.8 in.

x force = -1.0 lb. 160 0.01 Passed


y force = 0.0 lb. 200 0.00 Passed
z force = -43.0 lb. 130 0.33 Passed

x moment = 11.0 ft.lb. 340 0.03 Passed


y moment = -107.0 ft.lb. 170 0.63 Passed
z moment = 0.0 ft.lb. 260 0.00 Passed

Check of Condition F.1.2.2 Requirement Status

(FRSa/1.5FRSt2) + (MRSa/1.5MRSt2) = 0.000 < or = 2.00 Passed


(FRDa/1.5FRDt2) + (MRDa/1.5MRDt2) = 0.255 < or = 2.00 Passed

Check of Condition F.1.2.3 Requirement Status

1.5 ( FRSt2 + FRDt2 ) = 1080. > 43. (FRCa) Passed


2.0 ( MYSt2 + MYDt2 ) = 1040. > 108. (MYCa) Passed
1.5 ( MRSt2 + MRDt2 ) = 2115. > 120. (MRCa) Passed

Overall Pump Status ** PASSED **

20
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

Description:
Discharge Nozzle Load of Jockey Pump P-006
INPUT (CAESAR II Global Coordinates):
Load Case : Expansion

Horizontal Pump
Pump axis direction cosines (X,Z): ( 1.000, 0.000)

Node # Orientation Nominal Diameter


Suction Nozzle 0 Side 3
Discharge Nozzle 360 Side 2

Table 2 Allowable ( ratio ) = 1.00

Suction Nozzle Discharge Nozzle

X Distance = 0.0 in. 0.0 in.


Y Distance = 0.0 in. 11.8 in.
Z Distance = 0.0 in. 11.8 in.

X Force = 0.0 lb. 81.0 lb.


Y Force = 0.0 lb. 0.0 lb.
Z Force = 0.0 lb. 1.0 lb.

X Moment = 0.0 ft.lb. 0.0 ft.lb.


Y Moment = 0.0 ft.lb. 4.0 ft.lb.
Z Moment = 0.0 ft.lb. 0.0 ft.lb.

21
C A E S A R I I VERS 4.40 NOV 14,2009 8:12:22
Job: ...\Discharge Nozzle Pump.610
Licensed To: ID 20616

CAESAR II ANALYSIS REPORT: API 610 1995 - Centrifugal Pumps (8th Ed.)

OUTPUT (API 610 8th Edition Local Coordinates):

Suction Table 2 Force & Moment Status


Values Ratios
x distance = 0.0 in.
y distance = 0.0 in.
z distance = 0.0 in.

x force = 0.0 lb. 240 0.00 Passed


y force = 0.0 lb. 300 0.00 Passed
z force = 0.0 lb. 200 0.00 Passed

x moment = 0.0 ft.lb. 700 0.00 Passed


y moment = 0.0 ft.lb. 350 0.00 Passed
z moment = 0.0 ft.lb. 530 0.00 Passed

Discharge Table 2 Force & Moment Status


Values Ratios
x distance = 0.0 in.
y distance = -11.8 in.
z distance = 11.8 in.

x force = 81.0 lb. 160 0.51 Passed


y force = -1.0 lb. 200 0.00 Passed
z force = 0.0 lb. 130 0.00 Passed

x moment = 0.0 ft.lb. 340 0.00 Passed


y moment = 0.0 ft.lb. 170 0.00 Passed
z moment = 4.0 ft.lb. 260 0.02 Passed

Check of Condition F.1.2.2 Requirement Status

(FRSa/1.5FRSt2) + (MRSa/1.5MRSt2) = 0.000 < or = 2.00 Passed


(FRDa/1.5FRDt2) + (MRDa/1.5MRDt2) = 0.192 < or = 2.00 Passed

Check of Condition F.1.2.3 Requirement Status

1.5 ( FRSt2 + FRDt2 ) = 1080. > 81. (FRCa) Passed


2.0 ( MYSt2 + MYDt2 ) = 1040. > 80. (MYCa) Passed
1.5 ( MRSt2 + MRDt2 ) = 2115. > 116. (MRCa) Passed

Overall Pump Status ** PASSED **