1.
3
(1) Selfdiagnosis function
(a) Check Indicator Table
Whether a failure exists or not on the indoor unit and outdoor unit can be know by the contents of remote controller eroor code, indoor/outdoor unit green LED (power pilot lamp
and microcomputer normality pilot lamp) or red LED (check pilot lamp).
Diagnosing of microcomputer circuit
1) Indoor unit side
Remote Indoor unit LED Outdoor unit LED
controller Cause
error code Green Red Green Red
Keeps flashing Stays OFF Keeps flashing Stays OFF Normal
Stays OFF Stays OFF Stays OFF Stays OFF Power OFF, L phase wiring is open, power source failure
Keeps flashing Stays OFF Keeps flashing Stays OFF Indoor unit microcomputer failure
No-indication
Remote controller wires X and Y are reversely connected. *For wire breaking at
power ON, the LED is OFF. Remote controller wire is open. (X wire breaking : A
Keeps flashing *3 time flash Keeps flashing Stays OFF beep is produced and no indication is made. Z wire breaking : No beep and no
indication) The remote controller wires Y and Z are reversely connected.
LCD flashes
Poor connection or disconnection in wires connecting the indoor and outdoor
continuously Keeps flashing Stays OFF Keeps flashing 2 time flash
units.
or is off.
-
When multiple remote controllers are used for control, the power supply to some
Keeps flashing Stays OFF Keeps flashing Stays OFF indoor units is OFF.
4-
Stay OFF or Lights
E1 Stay OFF Keeps flashing Stays OFF Indoor unit PCB fault
continously
The remote controller wire Y is open. The remote controller wires X and Y are
Keeps flashing Stay OFF Keeps flashing Stays OFF reversely connected. Noise is penetrating the remote control lines. The remote
controller or indoor control PCB is faulty. (The communications circuit is faulty.)
Keeps flashing 2 time flash Keeps flashing 2 time flash Indoor / outdoor transmission error.
Outdoor unit control PCB is faulty when the power is turned on, or the inverter
E5 Keeps flashing 2 time flash Stays OFF Stays OFF parts are faulty (FDCVA 151~251 type).
Keeps flashing 2 time flash Keeps flashing Stays OFF Outdoor unit microcomputer failure
E6 Keeps flashing 1 time flash Keeps flashing Stays OFF Indoor unit heat exchanger thermistor failure
E7 Keeps flashing 1 time flash Keeps flashing Stays OFF Indoor unit return air thermistor failure
Heating overload (indoor heat exchanger temperature is abnormally high) and
E8 Keeps flashing 1 time flash Keeps flashing Stays OFF indoor heat exchanger thermistor is faulty.
E9 Keeps flashing 1 time flash Keeps flashing Stays OFF The float SW operates (with FS only). Drain up kit wiring fault.
When multi-unit control by remote controller is performed, the number of units is
E10 Keeps flashing Stays OFF Keeps flashing Stays OFF over (more than 17 units). Two remote controller are provided for one controller is
performed.
E16 Keeps flashing Stays OFF Keeps flashing Stays OFF Fan motor is faulty (FDTA 501, 601 type, FDKN type).
E28 Keeps flashing Stays OFF Keeps flashing Stays OFF Remote controller thermistor failure
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
2) Outdoor unit side
Remote Indoor unit LED Outdoor unit LED
controller Cause
error code Green Red Green Red
E32 Keeps flashing Stays OFF Keeps flashing 1 time flash Wiring is open or reversal phase (FDCA 301~601 type)
Inverter primary side current is abnormal. (FDCVA151~251 type)
E33 Keeps flashing Stays OFF Keeps flashing 1 time flash
Abnormal current cut of compressor (FDCA 301~601 type)
E34 Keeps flashing Stays OFF Keeps flashing 1 time flash 52C secondary side L3-phase wiring is open. (FDCA 301~601 type)
Outdoor heat exchanger temperature is high or outdoor heat exchanger thermistor
E35 Keeps flashing Stays OFF Keeps flashing 1 time flash is faulty.
E36 Keeps flashing Stays OFF Keeps flashing 1 time flash Discharge temperature abnormality.
Keeps flashing Stays OFF Keeps flashing 1 time flash Outdoor unit heat exchanger thermistor
E37
failure
E38 Keeps flashing Stays OFF Keeps flashing 1 time flash Outdoor air temperature thermistor failure
E39 Keeps flashing Stays OFF Keeps flashing 1 time flash Discharge pipe thermistor failure
E40 Keeps flashing Stays OFF Keeps flashing 1 time flash 63H1 operation (FDCA 301~601 type)
E42 Keeps flashing Stays OFF 1 time flash Current (Abnormalities in a compressor over current)
-
5-
E47 Keeps flashing Stays OFF 1 time flash Inverter Over-voltage Trouble. (FDCVA 151~251 type)
E48 Keeps flashing Stays OFF 1 time flash DC fan motor abnormal. (FDCVA 151~251 type)
E52 Keeps flashing Stays OFF Keeps flashing Lights contiously 52C abnormal. (FDCA 301~601 type)
Power transistor thermistor is faulty or disconnection or connector
E56 Keeps flashing Stays OFF 1 time flash
connections are poor. (FDCVA 151~251 type)
E57 Keeps flashing Stays OFF Keeps flashing 1 time flash Insufficient refrigerant.
1 time flash
E59 Keeps flashing Stays OFF 2 time flash Compressor startup error (FDCVA 151~251 type)
3 time flash
E60 Keeps flashing Stays OFF 1 time flash Compressor loader position detection error. (FDCVA 151~251 type)