Modbus RTU TCP/IP: HMI Setting

The document provides instructions for connecting an MT500 HMI to a Modbus RTU TCP/IP device via Ethernet. It includes settings for the HMI and device addressing information. Wiring diagrams are given for connecting via an Ethernet hub/switch through a router or directly with a crossover cable.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
213 views

Modbus RTU TCP/IP: HMI Setting

The document provides instructions for connecting an MT500 HMI to a Modbus RTU TCP/IP device via Ethernet. It includes settings for the HMI and device addressing information. Wiring diagrams are given for connecting via an Ethernet hub/switch through a router or directly with a crossover cable.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Modbus RTU TCP/IP

MT500 must has Ethernet port, Modbus RTU TCP/IP device.


http://www.modbus.org

HMI Setting:
Parameters Recommend Option Notes
PLC type MODBUS RTU TCP/IP
Com port Ethernet
HMI Station No. 0 Does not apply
PLC Station No. 0 Does not apply
Multiple HMI Master Must set Master

PLC Setting:
Communication mode

Device address:
Bit/Word Device Type Format Range Memo
B 1x ddd 1-9999 Output bit
B 0x ddd 1-9999 Input bit
W 3x ddd 1-9999 Input Register
W 4x ddd 1-9999 Output Register

Wiring diagram:
Ethernet::
MT500 Ethernet Wire color Ethernet Hub or Switch
RJ45 RJ45
1 TX+ White/Orange 1 RX+
1 8
2 TX- Orange 2 RX-
RJ45 connector
3 RX+ White/Green 3 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 6 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-
Internet or
Intranet

MT500 Router
Modbus RTU TCP/IP Device
192.168.10.182 192.168.10.1 210.66.120.180

Ethernet: Direct connect (crossover cable)


MT500 Ethernet Wire color Modbus TCP Device
RJ45 RJ45
1 TX+ White/Orange 3 RX+
2 TX- Orange 6 RX-
3 RX+ White/Green 1 TX+
4 BD4+ Blue 4 BD4+
5 BD4- White/Blue 5 BD4-
6 RX- Green 2 TX-
7 BD3+ White/Brown 7 BD3+
8 BD3- Brown 8 BD3-

Modbus RTU TCP/IP Device


192.168.10.181

MT500
192.168.10.182