Experiment-5 Bus Admittance Matrix Formulation
Experiment-5 Bus Admittance Matrix Formulation
Experiment-5 Bus Admittance Matrix Formulation
Experiment-5
Bus Admittance Matrix Formulation
Consider a test system of your choice. Write down the base voltages
and base MVA. Compute the base impedance. Determine the per
unit values of the parameters of the elements of the transmission
system.
Assume that you are provided with the bus impedance matrix of a
power system with ‘N’ number of buses and ‘B’ number of branches.
If a new branch ‘B+1’ is to be added between two existing buses.
What is the modification to be done in the existing bus between two
existing bus impedance matrix and what is the order of the new bus
Impedance matrix. Write a generalized MATLAB code for building the
new bus impedance matrix for the above mentioned case.
Test your program with your test system and show the results.
MATLAB PROGRAM:-
Function :
function z=base(x,v)
z=x*(30)/(v^2);
end
RESULT :
INPUTS:
For 1:
g1=[1.6;10;11];%[old pu;old MVA;KV with respect to new base KV]
g2=[1.2;15;6.2];
g3=[0.56;25;6.2];
g4=[11;10];%[base KV,base MVA]
t1=[15;15;33];%[Reactance;old MVA;KV with respect to new base KV]
t2=[16;15;33];
tr.line=[20.5;33];%[Reactance;old KV]
For 2:
Enter the number of buses = 4
Enter impedence value between row 1 and column 1 = 0.754
Enter impedence value between row 1 and column 2 = 0.655
Enter impedence value between row 1 and column 3 = 0.496
Enter impedence value between row 1 and column 4 = 0.496
Enter impedence value between row 2 and column 2 = 0.786
Enter impedence value between row 2 and column 3 = 0.595
Enter impedence value between row 2 and column 4 = 0.595
Enter impedence value between row 3 and column 3 = 0.754
Enter impedence value between row 3 and column 4 = 0.754
Enter impedence value between row 4 and column 4 = 0.954
Enter the bus number between which the new impedance is to be connceted
Enter bus number 1 =4
Enter bus number 2 =2
Enter the impedence between the buses = 0.125
OUTPUTS:
For 1.
t1 =
0.4132
t2 =
0.4408
g1 =
0.3967
g2 =
0.9365
g3 =
0.4370
g4 =
tr =
0.5647
For 2.
Znew =
Inference:-
1.Base MVA value will be same for all the buses, base kv value will be changed based on the
transformer rating and there is no unit for the per-unit system.
2.After adding the new branch between the 2 nodes of the given transmission system, the
size of the impedance matrix will be same as the old given matrix.