Preface
Open Source Software
SIPROTEC Table of contents
Basics 1
Multifuction Protection
Mapping 2
7SJ66
IEC61850 Literature
Mapping
Index
C53000-L2640-C554-2
Disclaimer of Liability Copyright
We have checked the text of this manual against the hardware and Copyright Siemens AG 2017
software described. However, deviations from the description can- Dissemination or reproduction of this document, or evaluation and
not be completely ruled out, so that no liability can be accepted for communication of its contents, is not authorized except where ex-
any errors or omissions contained in the information given. pressly permitted. Violations are liable for damages. All rights re-
The information given in this document is reviewed regularly and served, particularly for the purposes of patent application or
any necessary corrections will be included in subsequent editions. trademark registration.
We appreciate any suggestions for improvement.
We reserve the right to make technical improvements without no- Registered Trademarks
tice. SIPROTEC, SINAUT, SICAM and DIGSI are registered trademarks
of Siemens AG. Other designations in this manual might be trade-
Document Release V04.10.02 marks whose use by third parties for their own purposes would in-
Edition 12.2017 fringe the rights of the owner.
Siemens Aktiengesellschaft Order No.: C53000-L2640-C554-2
Preface
Purpose of this manual
In this Manual, you will find the
General information about the effects of configuration of your device to the different Logical
Nodes and DOIs
Mapping of device relevant information to Logical Nodes as part of protocol IEC61850
Target audience
This manual is intended mainly for all persons who configure, parameterize and operate
SIPROTEC Devices 7SJ66
Scope of validity of this Manual
SIPROTEC 7SJ66, Versions from 4.30 and higher
Standards
This document has been created according to the ISO 9001 quality standards.
Further Support
If you have questions about SIPROTEC IEC 61850 interface, please contact your Siemens sales
representative.
SIPROTEC, 7SJ66, IEC61850 MAPPING 3
C53000-L2640-C554-2, Edition 12.2017
4 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Open Source Software
The product contains, among other things, Open Source Software developed by third parties. The Open
Source Software used in the product and the license agreements concerning this software can be found in the
Readme_OSS. These Open Source Software files are protected by copyright. Your compliance with those
license conditions will entitle you to use the Open Source Software as foreseen in the relevant license. In the
event of conflicts between Siemens license conditions and the Open Source Software license conditions, the
Open Source Software conditions shall prevail with respect to the Open Source Software portions of the sot-
ware. The Open Source Software is licensed royalty-free. Insofar as the applicable Open Source Software
License Conditions provide for it you can order the source code of the Open Source Software from your Sie-
mens sales contact - against payment of the shipping and handling charges - for a period of at least 3 years
since purchase of the Product. We are liable for the Product including the Open Source Software contained in
it pursuant to the license conditions applicable to the Product. Any liability for the Open Source Software
beyond the program flow intended for the Product is explicitly excluded. Furthermore any liability for defects
resulting from modifications to the Open Source Software by you or third parties is excluded. We do not provide
any technical support for the Product if it has been modified.
SIPROTEC, 7SJ66, IEC61850 MAPPING 5
C53000-L2640-C554-2, Edition 12.2017
6 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Table of contents
1 Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.2 Effects of Configuration on the Logical Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.2.1 Function parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.2.2 Function parameters SIPROTEC 7SJ66 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.3 Allocation of Logical Nodes to Logical Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.4 Logical Node LLN0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1.4.1 Logical Device PROT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1.4.2 Logical Devices MEAS, DR and EXT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1.4.3 Logical Device CTRL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1.5 DOI Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1.5.1 Logical Device PROT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1.5.2 Logical Devices MEAS, CTRL, DR and EXT. . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2 Mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
2.1 Device (LPHD1, CALH1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2.1.1 Error with a summary alarm and Alarm summary event . . . . . . . . . . . . . . . . . . 31
2.2 Oscillographic Fault Records (RDRE1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2) . . . . . . . . . . . . . . . . . . 36
2.3.1 Overcurrent Protection 50, 51 PH (PTOC6, PTOC7, PTOC18, PTOC1) . . . . . 36
2.3.2 Overcurrent Protection 50N, 51N (PTOC8, PTOC9, PTOC2) . . . . . . . . . . . . . . 41
2.3.3 Overcurrent Protection 50N, 51N (PTRC2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3) . . . . . . . . . . . . . . . . 48
2.4.1 Directional Overcurrent Protection 67 (PTOC10, PTOC11, PTOC19, PTOC3) 48
2.4.2 Directional Overcurrent Protection 67N (PTOC12, PTOC13, PTOC20, PTOC4) 54
2.4.3 Directional Overcurrent Protection 67N (PTRC3) . . . . . . . . . . . . . . . . . . . . . . . 59
2.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17) . . . . . . . . . . . . . . . . . . 63
2.6 Voltage Protection 27, 59 (PTUVx, PTOVx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
2.6.1 Undervoltage Protection 27 (PTUV1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
2.6.2 Undervoltage Protection 27 (PTUV2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
2.6.3 Overvoltage Protection 59 (PTOV1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
2.6.4 Overvoltage Protection 59 (PTOV2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
2.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5) . . . . . . . . . . . . . . 72
2.8 Motor Protection (PMSS1, PMRI1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
2.8.1 Motor Starting Protection 48 (PMSS1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
2.8.2 Motor Restart Inhibit 66 (PMRI1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
SIPROTEC, 7SJ66, IEC61850 MAPPING 7
C53000-L2640-C554-2, Edition 12.2017
2.9 Load Jam Protection (PMLJ1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
2.10 Frequency protection 81 O/U (PTUFx, PTOFx). . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
2.10.1 Frequency protection 81-1 U (PTUF1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
2.10.2 Frequency protection 81-2 U (PTUF2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
2.10.3 Frequency protection 81-3 U (PTUF3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
2.10.4 Frequency protection 81-4 U (PTUF4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
2.10.5 Frequency protection 81-1 O (PTOF1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
2.10.6 Frequency protection 81-2 O (PTOF2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
2.10.7 Frequency protection 81-3 O (PTOF3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
2.10.8 Frequency protection 81-4 O (PTOF4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
2.11 QV Protection 27/Q (PTUV9) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
2.12 Thermal overload protection (PTTR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx) . . . . . . . . . . . . . . . . . 100
2.13.1 Ground Fault Protection 64 (PHIZ1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
2.13.2 Ground Fault Protection 50N(s) (PSDE1, PSDE2) . . . . . . . . . . . . . . . . . . . . . . . 105
2.13.3 51 N(s) (PSDE3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
2.14 Admittance Earth Fault Protection (PSDE4, PSDE5, PSDE6, PSDE7) . . . . . . . . . . 110
2.15 Automatic Reclosing System 79 (RREC1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
2.16 Fault Locator (RFLO1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
2.17 Circuit breaker failure protection 50BF(RBRF1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
2.18 Synchronism and Voltage Check 25 (RSYNx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
2.19 Three-pole tripping 52 Breaker (XCBR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
2.20 Tripping Logic of the Entire Device (PTRC1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
2.21 Measurement (MMXU1, MSQI1, MMTR1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
2.21.1 Measures (MMXU1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
2.21.2 Measured values, symmetrical components (MSQI1) . . . . . . . . . . . . . . . . . . . . 135
2.21.3 Power Metering (MMTR1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
8 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Basics
Basics 1
Contents
This chapter contains general information about the effects of device configuration on Logical
Nodes and DOIs.
1.1 General 10
1.2 Effects of Configuration on the Logical Nodes 12
1.3 Allocation of Logical Nodes to Logical Devices 18
1.4 Logical Node LLN0 22
1.5 DOI Behavior 27
SIPROTEC, 7SJ66, IEC61850 MAPPING 9
C53000-G2640-C554-2, Edition 12.2017
Basics
1.1 General
1.1 General
The protocol IEC 61850 was developed to define a standard that can be internationally
employed for the transmission of power automation system data.
This cross national standard enables an interoperability between automation systems and
devices made by different manufacturers.
7SJ66x can be equipped with an Ethernet module via which the protocol IEC 61850 is
interpreted.
The configuration of the protocol and the integration of the device with redundant IEC 61850
interfaces in your network are performed via the configuration system DIGSI.
Note
The following definitions are taken mainly from standard IEC 61850, Technical Specification
IEC TS 61850-2.
Logical Devices
LD Logical Devices represent a functional structuring of the LN Logical Nodes of a SIPROTEC
device.
The following Logical Devices are present:
Logical Device Protection PROT
Logical Device Measurement MEAS
Logical Device Disturbance Recorder DR
Logical Device Control CTRL
Logical Device Extended EXT
Each LD contains LN LLN0 and LN LPHD1.
The allocation of the Logical Nodes to the Logical Devices is listed in Chapter 1.3.
10 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-G2640-C554-2, Edition 12.2017
Basics
1.1 General
Logical Node LN
Smallest part of a function that exchanges data. A logical node is an object defined by its data
and methods.
Data object instance DOI
A Data object is part of a logical node object representing specific information for example status
of measurement. From an object-oriented point of view, a data object is an instance of a data
class. Specific data classes carry the semantic within a logical node.
Data attribute instance DAI
A Data attribute defines the name (semantic), format, range of possible values, and
representation of values while being communicated.
Annunciation types via GOOSE
Generic Object Oriented Substation Event
A GOOSE report enables high speed trip signals to be issued with a high probability of delivery.
The following types of information can be configured via GOOSE.
External single point indication O/O
External single point indication I/O
External double point indication
External double point indication, fast
External operational measured values
External metered values
SIPROTEC, 7SJ66, IEC61850 MAPPING 11
C53000-G2640-C554-2, Edition 12.2017
Basics
1.2 Effects of Configuration on the Logical Nodes
1.2 Effects of Configuration on the Logical Nodes
1.2.1 Function parameters
Depending on the configuration of the function parameters the functions of the SIPROTEC are
enabled or disabled. If a function is disabled, the corresponding Logical Node is not available.
The following Logical Nodes are always available:
Logical Device Protection: LLN0, LPHD1, XCBR1,
PTRC1
Logical Device Measurement: LLN0, LPHD1, MMXU1,
MMTR1, MSQI1
Logical Device Control: LLN0, LPHD1, CALH1
12 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-G2640-C554-2, Edition 12.2017
Basics
1.2 Effects of Configuration on the Logical Nodes
1.2.2 Function parameters SIPROTEC 7SJ66
The following table shows which Logical Nodes are available when setting the corresponding
function parameter.
The setting (-) implies that no corresponding LN is available.
Table 1-1 SIPROTEC 7SJ66 - Effects of Function parameters to the Logical Nodes
No. Function Setting Logical Nodes
103 Setting Group Change Option No effect
104 Oscillographic Fault Records Disabled -
Enabled RDRE1
112 50/51 (Charac. Phase) Disabled -
Overcurrent Protection
Definite Time PTOC6, PTOC7, PTOC1
PTOC18, PTRC2
TOC IEC PTOC6, PTOC7, PTOC1
PTOC18, PTRC2
TOC ANSI PTOC6, PTOC7, PTOC1
PTOC18, PTRC2
User Defined PU PTOC6, PTOC7, PTOC1
PTOC18, PTRC2
Userdef. Reset PTOC6, PTOC7,
PTOC1, PTOC18,
PTRC2
113 50N/51N (Charac. Ground) Disabled -
Overcurrent Protection
Definite Time PTOC8, PTOC9,
PTOC2, PTRC2
TOC IEC PTOC8, PTOC9,
PTOC2, PTRC2
TOC ANSI PTOC8, PTOC9,
PTOC2, PTRC2
User Defined PU PTOC8, PTOC9,
PTOC2, PTRC2
Userdef. Reset PTOC8, PTOC9,
PTOC2, PTRC2
SIPROTEC, 7SJ66, IEC61850 MAPPING 13
C53000-G2640-C554-2, Edition 12.2017
Basics
1.2 Effects of Configuration on the Logical Nodes
Table 1-1 SIPROTEC 7SJ66 - Effects of Function parameters to the Logical Nodes (Cont.)
No. Function Setting Logical Nodes
115 67, 67-TOC Disabled -
Directional Overcurrent Protection
Definite Time PTOC10, PTOC11,
PTOC19, PTOC3,
PTRC3
TOC IEC PTOC10, PTOC11,
PTOC19, PTOC3,
PTRC3
TOC ANSI PTOC10, PTOC11,
PTOC19, PTOC3,
PTRC3
User Defined PU PTOC10, PTOC11,
PTOC19, PTOC3,
PTRC3
Userdef. Reset PTOC10, PTOC11,
PTOC19, PTOC3,
PTRC3
116 67N, 67N-TOC Disabled -
Directional Overcurrent Protection
Definite Time PTOC12, PTOC13,
PTOC20, PTOC4,
PTRC3
TOC IEC PTOC12, PTOC13,
PTOC20, PTOC4,
PTRC3
TOC ANSI PTOC12, PTOC13,
PTOC20, PTOC4,
PTRC3
User Defined PU PTOC12, PTOC13,
PTOC20, PTOC4,
PTRC3
Userdef. Reset PTOC12, PTOC13,
PTOC20, PTOC4,
PTRC3
117 Cold Load Pickup No effect
122 2nd Harmonic Inrush Restraint No effect
14 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-G2640-C554-2, Edition 12.2017
Basics
1.2 Effects of Configuration on the Logical Nodes
Table 1-1 SIPROTEC 7SJ66 - Effects of Function parameters to the Logical Nodes (Cont.)
No. Function Setting Logical Nodes
127 50 1Ph Disabled -
Single Phase Overcurrent Protection
Enabled PTOC16, PTOC17
130 (sens.) Ground fault dir. characteristic cos / sin see Parameter 131
V0/I0 mea. see Parameter 131
131 (sensitive) Ground fault Disabled -
and
(sens.) Ground fault dir. characteristic = Definite Time PHIZ1, PSDE1, PSDE2
cos / sin
TOC IEC PHIZ1, PSDE2, PSDE3
TOC IANSI PHIZ1, PSDE2, PSDE3
User Defined PU PHIZ1, PSDE2, PSDE3
Log. inverse 1 PHIZ1, PSDE2, PSDE3
Log. inverse 2 PHIZ1, PSDE2, PSDE3
131 (sensitive) Ground fault Disabled -
and
(sens.) Ground fault dir. characteristic = Definite Time PHIZ1, PSDE1, PSDE2
V0/I0 mea.
User Defined PU PHIZ1, PSDE1, PSDE2
133 Intermittent earth fault protection No effect
134 Dir. Intermittent earth fault protection No effect
135 Admittance Earth Fault Protection Disable -
Enable PSDE4, PSDE5, PSDE6,
PSDE7
140 46 Negative Sequence Protection Disabled -
TOC ANSI PTOC14, PTOC15,
PTOC5
TOC IEC PTOC14, PTOC15,
PTOC5
Definite Time PTOC14, PTOC15
SIPROTEC, 7SJ66, IEC61850 MAPPING 15
C53000-G2640-C554-2, Edition 12.2017
Basics
1.2 Effects of Configuration on the Logical Nodes
Table 1-1 SIPROTEC 7SJ66 - Effects of Function parameters to the Logical Nodes (Cont.)
No. Function Setting Logical Nodes
141 48 Startup Supervision of Motors Disabled -
Enabled PMSS1
142 49 Thermal Overload Protection Disabled -
No ambient temp PTTR1
With amb. temp. PTTR1
143 66 Startup Counter for Motors Disabled -
Enabled PMRI1
144 Load Jam Protection Disabled -
Enabled PMLJ1
150 27, 59 Under/Overvoltage Protection Disabled -
Enabled PTUV1, PTUV2,
PTOV1, PTOV2
154 81 Over/Underfrequency Protection Disabled -
Enabled PTOF1 – PTOF4,
PTUF1 – PTUF4
155 27/Q-Protection Disabled -
Enabled PTUV7
161 25 Function group 1 Disabled -
Synchronism and Voltage Check
SYNCHROCHECK RSYN1
170 50BF Breaker Failure Protection Disabled -
Enabled RBRF1
enabled w/ 3I0> RBRF1
171 79 Auto-Reclose Function Disabled -
Enabled RREC1
172 52 Breaker Wear Monitoring No effect
16 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-G2640-C554-2, Edition 12.2017
Basics
1.2 Effects of Configuration on the Logical Nodes
Table 1-1 SIPROTEC 7SJ66 - Effects of Function parameters to the Logical Nodes (Cont.)
No. Function Setting Logical Nodes
180 Fault Locator Disabled -
Enabled RFLO1
181 Line sections for fault locator No effect
182 74TC Trip Circuit Supervision Disabled -
2 Binary Inputs DOI CirSpv, LN XCBR
LD PROT
1 Binary Input DOI CirSpv, LN XCBR
LD PROT
190 External Temperature Input No effect
191 Ext. Temperature Input Connection Type No effect
SIPROTEC, 7SJ66, IEC61850 MAPPING 17
C53000-G2640-C554-2, Edition 12.2017
Basics
1.3 Allocation of Logical Nodes to Logical Devices
1.3 Allocation of Logical Nodes to Logical Devices
All Logical Nodes (LN) are allocated to Logical Devices (LD). The following tables show this
allocation and the DOIs available for each LN.
LD PROT
The Logical Device PROT (Protection) contains the following LNs:
Table 1-2 LD PROT - Logical Nodes
LN Function DOI
LLN0 General Mod, Beh, Health, NamPlt, OpTmh
PTRC1 General device pickup Mod, Beh, Health, NamPlt, Str,Tr,FinTr
General OFF
XCBR1 52 Breaker Mod, Beh, Health, NamPlt, Loc, OpCnt, Pos
Three-pole tripping BlkOpn, BlkCls, CBOpCap
SumSwARs1, SumSwARs2, SumSwARs3
PTOC6 50/51 (Charac. Phase) Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC7
PTOC18
PTOC1
PTRC2
PTOC8 50N/51N (Charac. Ground) Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC9
PTOC2
PRTC2
PTOC10 67, 67-TOC Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC11
PTOC19
PTOC3
PTRC3
PTOC12 67N, 67N-TOC Mod, Beh, Health, NamPlt, Str, Op, ChgSet
PTOC13
PTOC20
PTOC4
PRTC3
PTOC16 50 1Ph Mod, Beh, Health, NamPlt, Str, Op
PTOC17
PTUV1 27 Undervoltage Protection Mod, Beh, Health, NamPlt, Str, Op
PTUV2
PTOV1 59 Overvoltage Protection Mod, Beh, Health, NamPlt, Str, Op
PTOV2
18 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-G2640-C554-2, Edition 12.2017
Basics
1.3 Allocation of Logical Nodes to Logical Devices
Table 1-2 LD PROT - Logical Nodes (Cont.)
LN Function DOI
PTUV7 27/Q-Protection Mod, Beh, Health, NamPlt, Str, Op
PTOC14 46 Negative Sequence Protection Mod, Beh, Health, NamPlt, Str, Op
PTOC15
PTOC5
PMSS1 48 Startup Supervision of Motors Mod, Beh, Health, NamPlt, Str, Op
PMRI1 66 Startup Counter for Motors Mod, Beh, Health, NamPlt, Op, StrInhTmm
PMLJ1 Load Jam Protection Mod, Beh, Health, NamPlt, Str, Op, LDJamAlm,
ChgSet
PTUF1 81 Underfrequency Protection Mod, Beh, Health, NamPlt, Str, Op, BlkV
PTUF2
PTUF3
PTUF4
PTOF1 81 Overfrequency Protection Mod, Beh, Health, NamPlt, Str, Op, BlkV
PTOF2
PTOF3
PTOF4
PTTR1 49 Thermal Overload Protection Mod, Beh, Health, NamPlt, Str, Op, AlmThm
PSDE1 (sensitive) Ground fault Mod, Beh, Health, NamPlt, Str, Op
PSDE2
PSDE3
PSDE4 Admittance Earth Fault Protection Mod, Beh, Health, NamPlt, Str, Op
PSDE5
PSDE6
PSDE7
PHIZ1 (sensitive) Ground fault Mod, Beh, Health, NamPlt, Str, Op
RREC1 79 Auto-Reclose Function Mod, Beh, Health, NamPlt, Op, AutoRecSt
RFLO1 Fault Locator Mod, Beh, Health, NamPlt, FltZ, FltDiskm, FltDisPrc
RBRF1 50BF Breaker Failure Protection Mod, Beh, Health, NamPlt, Str, OpEx, OpIn
LPHD1 Device PhyNam, PhyHealth, Proxy
SIPROTEC, 7SJ66, IEC61850 MAPPING 19
C53000-G2640-C554-2, Edition 12.2017
Basics
1.3 Allocation of Logical Nodes to Logical Devices
LD MEAS
The Logical Device MEAS (Measurement) contains the following LNs:
Table 1-3 LD MEAS - Logical Nodes
LN Function DOIs
LLN0 General Mod, Beh, Health, NamPlt
MMXU1 Operational measured values Mod, Beh, Health, NamPlt,
TotW, TotVAr, TotVA, TotPF, Hz, PPV, PhV, A
MMTR1 Power Metering Mod, Beh, Health, NamPlt,
SupWh, SupVArh, DmdWh, DmdVArh
MSQI1 Measured values, symmetrical Mod, Beh, Health, NamPlt, SeqA, SeqV
components
LPHD1 Device PhyNam, PhyHealth, Proxy
LD DR
The Logical Device DR (Disturbance Recorder) contains the following LNs:
Table 1-4 LD DR - Logical Nodes
LN Function DOIs
LLN0 General Mod, Beh, Health, NamPlt
RDRE1 Oscillographic Fault Records Mod, Beh, Health, NamPlt, RcdMade, RcdStr
FltNum, GriFltNum
LPHD1 Device PhyNam, PhyHealth, Proxy
20 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-G2640-C554-2, Edition 12.2017
Basics
1.3 Allocation of Logical Nodes to Logical Devices
LD CTRL
The Logical Device CTRL (Control) contains the following LNs:
Table 1-5 LD CTRL - Logical Nodes
LN Function DOIs
LLN0 General Mod, Beh, Health, NamPlt, LEDRs, Loc
RSYN1 25 Function group 1 Mod, Beh, Health, NamPlt,
Rel, VInd, AngInd, HzInd, SynPrg,
DifVClc, DifHzClc, DifAngClc
CALH1 Error with a summary alarm and Mod, Beh, Health, NamPlt, GrAlm, GrWrn,
Alarm summary event ErrBoard1, ErrBoard2, ErrBoard3, ErrBoard4,
ErrBoard5, ErrBoard6, ErrBoard7
LPHD1 Device PhyNam, PhyHealth, Proxy, CtlNum, DevStr
LD EXT
The Logical Device EXT (Extended) contains the following LNs:
Table 1-6 LD EXT - Logical Nodes
LN Function DOIs
LLN0 General Mod, Beh, Health, NamPlt, LEDRs, Loc
LPHD1 Device PhyNam, PhyHealth, Proxy, CtlNum
The Logical Nodes of the switching (and userdefined) objects will be created by DIGSI during
the parameterization of your SIPROTEC device.
MICS, Model Implementation Conformance Statement, shows the assignment of the DOIs;
you can use DIGSI to print the MICS.
SIPROTEC, 7SJ66, IEC61850 MAPPING 21
C53000-G2640-C554-2, Edition 12.2017
Basics
1.4 Logical Node LLN0
1.4 Logical Node LLN0
1.4.1 Logical Device PROT
LLN0.Mod
No. Information
51 Device is Operational and Protecting (Device OK) 0 1 1 1 1
Test mode (Test mode) x 0 0 1 1
Stop data transmission (DataStop) x 0 1 0 1
LLN0.Mod.stVal 5 1 2 3 4
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
LLN0.Beh
No. Information
51 Device is Operational and Protecting (Device OK) 0 1 1 1 1
Test mode (Test mode) x 0 0 1 1
Stop data transmission (DataStop) x 0 1 0 1
LLN0.Beh.stVal 5 1 2 3 4
device annunciation / setting: 1 - ON / TRUE IEC Status Beh.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
LLN0.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
LLN0.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
22 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-G2640-C554-2, Edition 12.2017
Basics
1.4 Logical Node LLN0
LLN0.OpTmh
No. Information Value
1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)
SIPROTEC, 7SJ66, IEC61850 MAPPING 23
C53000-G2640-C554-2, Edition 12.2017
Basics
1.4 Logical Node LLN0
1.4.2 Logical Devices MEAS, DR and EXT
LLN0.Mod
No. Information
51 Device is Operational and Protecting (Device OK) 0 1 1 1 1
Test mode (Test mode) x 1 1 0 0
Stop data transmission (DataStop) x 1 0 1 0
LLN0.Mod.stVal 5 4 3 2 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
LLN0.Beh
No. Information
51 Device is Operational and Protecting (Device OK) 0 1 1 1 1
Test mode (Test mode) x 0 0 1 1
Stop data transmission (DataStop) x 0 1 0 1
LLN0.Beh.stVal 5 1 2 3 4
device annunciation / setting: 1 - ON / TRUE IEC Status Beh.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
LLN0.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
LLN0.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
24 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-G2640-C554-2, Edition 12.2017
Basics
1.4 Logical Node LLN0
1.4.3 Logical Device CTRL
LLN0.Mod
No. Information
55 Reset Device (Reset Device) 1 1 1 1 1
51 Device is Operational and Protecting (Device OK) 1 1 1 1 0
Test mode (Test mode) 1 1 0 0 0
Stop data transmission (DataStop) 1 0 1 0 0
LLN0.Mod.stVal 4 3 2 1 5
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
LLN0.Beh
No. Information
55 Reset Device (Reset Device) 1 1 1 1 1
51 Device is Operational and Protecting (Device OK) 1 1 1 1 0
Test mode (Test mode) 1 1 0 0 0
Stop data transmission (DataStop) 1 0 1 0 0
LLN0.Beh.stVal 4 3 2 1 5
device annunciation / setting: 1 - ON / TRUE IEC Status Beh.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
LLN0.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
LLN0.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 25
C53000-G2640-C554-2, Edition 12.2017
Basics
1.4 Logical Node LLN0
LLN0.OpTmh
No. Information Value
1020 Counter of operating hours (Op.Hours=) LLN0.OpTmh.stVal Operating hours (Absolute value)
26 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-G2640-C554-2, Edition 12.2017
Basics
1.5 DOI Behavior
1.5 DOI Behavior
1.5.1 Logical Device PROT
For the Logical Nodes of the PROT Logical Device, LNx.Beh.stVal is formed from
LNx.Mod.stVal of the Logical Node and the status of the following device messages:
Test mode (Test mode),
Stop data transmission and
At Least 1 Protection Funct. is Active.
No. Information
Test mode (Test mode) x 0 1 0 1 x
Stop data transmission (DataStop) x 0 0 1 1 x
51 Device is Operational and Protecting (Device OK) x 1 1 1 1 0
LNx .Mod.stVal 5 1 1 1 1 x
LNx.Beh.stVal 5 1 3 2 4 5
device annunciation / setting: 1 - ON / TRUE IEC Status stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
SIPROTEC, 7SJ66, IEC61850 MAPPING 27
C53000-G2640-C554-2, Edition 12.2017
Basics
1.5 DOI Behavior
1.5.2 Logical Devices MEAS, CTRL, DR and EXT
For the Logical Nodes of the MEAS, CTRL, DR and EXT Logical Devices, LNx.Beh.stVal is
formed from LNx.Mod.stVal of the Logical Node and the status of the following device
messages:
Test mode (Test mode),
Stop data transmission.
No. Information
Test mode (Test mode) x 0 1 0 1 0 1
Stop data transmission (DataStop) x 0 0 1 1 x x
LNx .Mod.stVal 5 1 1 1 1 2 2
LNx.Beh.stVal 5 1 3 2 4 2 4
device annunciation / setting: 1 - ON / TRUE IEC Status stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
28 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-G2640-C554-2, Edition 12.2017
Mapping
Mapping 2
Contents
This chapter shows the mapping of the information relevant to the device on the Logical Node of
protocol IEC61850. It is structured according to function. In Chapter 1 you can find what
consequences non-configured functions have on the Logical Nodes as well as general
information about IEC 61850 mapping of information.
2.1 Device (LPHD1, CALH1) 30
2.2 Oscillographic Fault Records (RDRE1) 34
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2) 36
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3) 48
2.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17) 63
2.6 Voltage Protection 27, 59 (PTUVx, PTOVx) 66
2.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5) 72
2.8 Motor Protection (PMSS1, PMRI1) 76
2.9 Load Jam Protection (PMLJ1) 79
2.10 Frequency protection 81 O/U (PTUFx, PTOFx) 81
2.11 QV Protection 27/Q (PTUV9) 97
2.12 Thermal overload protection (PTTR1) 98
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx) 100
2.14 Admittance Earth Fault Protection (PSDE4, PSDE5, PSDE6, PSDE7) 110
2.15 Automatic Reclosing System 79 (RREC1) 116
2.16 Fault Locator (RFLO1) 117
2.17 Circuit breaker failure protection 50BF(RBRF1) 119
2.18 Synchronism and Voltage Check 25 (RSYNx) 121
2.19 Three-pole tripping 52 Breaker (XCBR1) 124
2.20 Tripping Logic of the Entire Device (PTRC1) 128
2.21 Measurement (MMXU1, MSQI1, MMTR1) 130
SIPROTEC, 7SJ66, IEC61850 MAPPING 29
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.1 Device (LPHD1, CALH1)
2.1 Device (LPHD1, CALH1)
LPHD1.DevStr
No. Information
56 Initial Start of Device (Initial Start) 0 0 1 1
67 Resume (Resume) 0 1 0 1
LPHD1.DevStr.stVal T 2 1 T
device annunciation: 1 - ON IEC Status DevStr.stVal: 1 - Initial Start
0 - OFF 2 - Resume
T - toggel between 1 and 2
LPHD1.Proxy
No. Information
55 Reset Device (Reset Device) 0 1
LPHD1.Proxy.stVal 1 0
device annunciation: 1 - ON IEC Status Proxy.stVal: 0 - DEVICE is not a PROXY
0 - OFF 1 - DEVICE is a PROXY
LPHD1.PhyHealth
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
LPHD1.PhyHealth.stVal 3 1
device annunciation: 1 - ON IEC Status PhyHealth.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
30 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.1 Device (LPHD1, CALH1)
2.1.1 Error with a summary alarm and Alarm summary event
CALH1.Mod
No. Information
56 Initial Start of Device (Initial Start) 1 0
CALH1.Mod.stVal 1 5
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
3 - TEST
4 - TEST/BLOCKED
5 - OFF
CALH1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
CALH1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
CALH1.GrAlm
No. Information
140 Error with a summary alarm (Error Sum Alarm) 1 0
CALH1.GrAlm.stVal 1 0
device annunciation: 1 - ON IEC Status GrAlm.stVal: 0 - FALSE
0 - OFF 1 - TRUE
CALH1.GrWrn
No. Information
160 Alarm Summary Event (Alarm Sum Event) 1 0
CALH1.GrWrn.stVal 1 0
device annunciation: 1 - ON IEC Status GrWrn.stVal: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 31
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.1 Device (LPHD1, CALH1)
The LN CALH1.ErrBoard1 to CALH1.ErrBoard7 are available with Firmware
CALH1.ErrBoard1
No. Information
183 Error Board 1 (Error Board 1) 1 0
CALH1.ErrBoard1.stVal 1 0
device annunciation: 1 - ON IEC Status ErrBoard1.stVal: 0 - FALSE
0 - OFF 1 - TRUE
CALH1.ErrBoard2
No. Information
184 Error Board 2 (Error Board 2) 1 0
CALH1.ErrBoard2.stVal 1 0
device annunciation: 1 - ON IEC Status ErrBoard2.stVal: 0 - FALSE
0 - OFF 1 - TRUE
CALH1.ErrBoard3
No. Information
185 Error Board 3 (Error Board 3) 1 0
CALH1.ErrBoard3.stVal 1 0
device annunciation: 1 - ON IEC Status ErrBoard3.stVal: 0 - FALSE
0 - OFF 1 - TRUE
CALH1.ErrBoard4
No. Information
186 Error Board 4 (Error Board 4) 1 0
CALH1.ErrBoard4.stVal 1 0
device annunciation: 1 - ON IEC Status ErrBoard4.stVal: 0 - FALSE
0 - OFF 1 - TRUE
32 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.1 Device (LPHD1, CALH1)
CALH1.ErrBoard5
No. Information
187 Error Board 5 (Error Board 5) 1 0
CALH1.ErrBoard5.stVal 1 0
device annunciation: 1 - ON IEC Status ErrBoard5.stVal: 0 - FALSE
0 - OFF 1 - TRUE
CALH1.ErrBoard6
No. Information
188 Error Board 6 (Error Board 6) 1 0
CALH1.ErrBoard6.stVal 1 0
device annunciation: 1 - ON IEC Status ErrBoard6.stVal: 0 - FALSE
0 - OFF 1 - TRUE
CALH1.ErrBoard7
No. Information
189 Error Board 7 (Error Board 7) 1 0
CALH1.ErrBoard7.stVal 1 0
device annunciation: 1 - ON IEC Status ErrBoard7.stVal: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 33
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.2 Oscillographic Fault Records (RDRE1)
2.2 Oscillographic Fault Records (RDRE1)
RDRE1.Mod
No. Information
55 Reset Device (Reset Device) x
RDRE1.Mod.stVal 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
RDRE1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
RDRE1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
RDRE1.RcdMade
No. Information
30053 Fault recording is running (Fault rec. run.) 0 1
RDRE1.RcdMade.stVal 1 0
device annunciation: 1 - ON IEC Status RcdMade.stVal: 0 - FALSE
0 - OFF 1 - TRUE
(Recording complete)
RDRE1.FltNum
No. Information Value
302 Fault Event (Fault Event) RDRE1.FltNum.stVal Present fault number
RDRE1.GriFltNum
No. Information Value
301 Power System fault (Pow.Sys.Flt.) RDRE1.GriFltNum.stVal Network fault number
34 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.2 Oscillographic Fault Records (RDRE1)
RDRE1.RcdStr
No. Information
30053 Fault recording is running (Fault rec. run.) 0 1
RDRE1.RcdStr.stVal 0 1
device annunciation: 1 - ON IEC Status RcdStr.stVal: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 35
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
2.3.1 Overcurrent Protection 50, 51 PH (PTOC6, PTOC7, PTOC18, PTOC1)
PTOC6.Mod
No. Information
1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0
50-1 PICKUP (P1204) = x 1 0
PTOC6.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC6.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC6.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC6.Str
No. Information
1810 50-1 picked up (50-1 picked up) 0 1
PTOC6.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC6.Op
No. Information
1815 50-1 TRIP (50-1 TRIP) 0 1
PTOC6.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
36 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
PTOC6.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC6.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
PTOC7.Mod
No. Information
1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0
50-2 PICKUP (P1202) = x 1 0
PTOC7.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC7.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC7.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC7.Str
No. Information
1800 50-2 picked up (50-2 picked up) 0 1
PTOC7.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 37
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
PTOC7.Op
No. Information
1805 50-2 TRIP (50-2 TRIP) 0 1
PTOC7.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC7.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC7.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
PTOC18.Mod
No. Information
1751 50/51 O/C switched OFF (50/51 PH OFF) 1 x 0
50-3 PICKUP(P1217) = x 1 0
PTOC18.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC18.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC18.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
38 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
PTOC18.Str
No. Information
1767 50-3 picked up (50-3 picked up) 0 1
PTOC18.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC18.Op
No. Information
1769 50-3 TRIP (50-3 TRIP) 0 1
PTOC18.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC18.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC18.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
PTOC1.Mod
No. Information
1751 50/51 O/C switched OFF (50/51 PH OFF) 1 0
PTOC1.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
SIPROTEC, 7SJ66, IEC61850 MAPPING 39
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
PTOC1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC1.Str
No. Information
1820 51 picked up (51 picked up) 0 1
PTOC1.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC1.Op
No. Information
1825 51 TRIP (51 TRIP) 0 1
PTOC1.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC1.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC1.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
40 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
2.3.2 Overcurrent Protection 50N, 51N (PTOC8, PTOC9, PTOC2)
PTOC8.Mod
No. Information
7156 50N/51N is OFF (50N/51N OFF) 1 x 0
50N-1 PICKUP (P1304) = x 1 0
PTOC8.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC8.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC8.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC8.Str
No. Information
1834 50N-1 picked up (50N-1 picked up) 0 1
PTOC8.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC8.Op
No. Information
1836 50N-1 TRIP (50N-1 TRIP) 0 1
PTOC8.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 41
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
PTOC8.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC8.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
PTOC9.Mod
No. Information
7156 50N/51N is OFF (50N/51N OFF) 1 x 0
50N-2 PICKUP (P1302) = x 1 0
PTOC9.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC9.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC9.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC9.Str
No. Information
1831 50N-2 picked up (50N-2 picked up) 0 1
PTOC9.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
42 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
PTOC9.Op
No. Information
1833 50N-2 TRIP (50N-2 TRIP) 0 1
PTOC9.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC9.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC9.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
PTOC2.Mod
No. Information
1756 50N/51N is OFF (50N/51N OFF) 1 0
PTOC2.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC2.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC2.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 43
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
PTOC2.Str
No. Information
1837 51N picked up (51N picked up) 0 1
PTOC2.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC2.Op
No. Information
1839 51N TRIP (51N TRIP) 0 1
PTOC2.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC2.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC2.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
44 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
2.3.3 Overcurrent Protection 50N, 51N (PTRC2)
PTRC2.Mod
No. Information
1751 50/51 O/C switched OFF (50/51 PH OFF) and 1 0
1756 50N/51N is OFF (50N/51N OFF)
PTRC2.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTRC2.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTRC2.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTRC2.Str
No. Information
1761 50(N)/51(N) O/C PICKUP (50(N)/51(N) PU) 0 1
PTRC2.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTRC2.Str.dirGeneral
No. Information
PTRC2.Str.dirGeneral 0
device annunciation: IEC Status Str.dirGeneral: 0 - UNKNOWN
SIPROTEC, 7SJ66, IEC61850 MAPPING 45
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
PTRC2.Str.phsA
No. Information
1762 50/51 Phase A picked up (50/51 Ph A PU) 0 1
PTRC2.Str.phsA 0 1
device annunciation: 1 - ON IEC Status Str.phsA: 0 - FALSE
0 - OFF 1 - TRUE
PTRC2.Str.dirPhsA
No. Information
PTRC2.Str.dirPhsA 0
device annunciation: IEC Status Str.dirPhsA: 0 - UNKNOWN
PTRC2.Str.phsB
No. Information
1763 50/51 Phase B picked up (50/51 Ph B PU) 0 1
PTRC2.Str.phsB 0 1
device annunciation: 1 - ON IEC Status Str.phsB: 0 - FALSE
0 - OFF 1 - TRUE
PTRC2.Str.dirPhsB
No. Information
PTRC2.Str.dirPhsB 0
device annunciation: IEC Status Str.dirPhsB: 0 - UNKNOWN
PTRC2.Str.phsC
No. Information
1764 50/51 Phase C picked up (50/51 Ph C PU) 0 1
PTRC2.Str.phsC 0 1
device annunciation: 1 - ON IEC Status Str.phsC: 0 - FALSE
0 - OFF 1 - TRUE
46 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.3 Overcurrent Protection 50, 51, 50N, 51N (PTOCx, PTRC2)
PTRC2.Str.dirPhsC
No. Information
PTRC2.Str.dirPhsC 0
device annunciation: IEC Status Str.dirPhsC: 0 - UNKNOWN
PTRC2.Str.neut
No. Information
1765 50N/51N picked up (50N/51NPickedup) 0 1
PTRC2.Str.neut 0 1
device annunciation: 1 - ON IEC Status Str.neut: 0 - FALSE
0 - OFF 1 - TRUE
PTRC2.Str.dirNeut
No. Information
PTRC2.Str.dirNeut 0
device annunciation: IEC Status Str.dirPhsC: 0 - UNKNOWN
PTRC2.Op
No. Information
1791 50(N)/51(N) TRIP (50(N)/51(N)TRIP) 0 1
PTRC2.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 47
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
2.4.1 Directional Overcurrent Protection 67 (PTOC10, PTOC11, PTOC19,
PTOC3)
PTOC10.Mod
No. Information
2651 67/67-TOC switched OFF (67/67-TOC OFF) 1 x 0
67-1 PICKUP (P1504) = x 1 0
PTOC10.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC10.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC10.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC10.Str
No. Information
2660 67-1 picked up (67-1 picked up) 0 1
PTOC10.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
48 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTOC10.Op
No. Information
2665 67-1 TRIP (67-1 TRIP) 0 1
PTOC10.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC10.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC10.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
PTOC11.Mod
No. Information
2651 67/67-TOC switched OFF (67/67-TOC OFF) 1 x 0
67-2 PICKUP (P1502) = x 1 0
PTOC11.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC11.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC11.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 49
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTOC11.Str
No. Information
2642 67-2 picked up (67-2 picked up) 0 1
PTOC11.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC11.Op
No. Information
2649 67-2 TRIP (67-2 TRIP) 0 1
PTOC11.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC11.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC11.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
PTOC19.Mod
No. Information
2651 67/67-TOC switched OFF (67/67-TOC OFF) 1 x 0
67-3 PICKUP (P1528) = x 1 0
PTOC19.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
50 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTOC19.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC19.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC19.Str
No. Information
2697 67-3 picked up (67-3 picked up) 0 1
PTOC19.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC19.Op
No. Information
2678 67-3 TRIP (67-3 TRIP) 0 1
PTOC19.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC19.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC19.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 51
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTOC3.Mod
No. Information
2651 67/67-TOC switched OFF (67/67-TOC OFF) 1 0
PTOC3.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC3.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC3.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC3.Str
No. Information
2670 67-TOC picked up (67-TOC picked up) 0 1
PTOC3.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC3.Op
No. Information
2675 67-TOC TRIP (67-TOC TRIP) 0 1
PTOC3.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
52 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTOC3.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC3.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 53
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
2.4.2 Directional Overcurrent Protection 67N (PTOC12, PTOC13,
PTOC20, PTOC4)
PTOC12.Mod
No. Information
2656 67N/67N-TOC switched OFF (67N OFF) 1 x 0
67N-1 PICKUP (P1604) = x 1 0
PTOC12.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC12.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC12.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC12.Str
No. Information
2681 67N-1 picked up (67N-1 picked up) 0 1
PTOC12.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC12.Op
No. Information
2683 67N-1 TRIP (67N-1 TRIP) 0 1
PTOC12.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
54 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTOC12.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC12.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
PTOC13.Mod
No. Information
2656 67N/67N-TOC switched OFF (67N OFF) 1 x 0
67N-2 PICKUP (P1602) = x 1 0
PTOC13.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC13.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC13.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC13.Str
No. Information
2646 67N-2 picked up (67N-2 picked up) 0 1
PTOC13.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 55
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTOC13.Op
No. Information
2679 67N-2 TRIP (67N-2 TRIP) 0 1
PTOC13.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC13.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC13.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
PTOC20.Mod
No. Information
2656 67N/67N-TOC switched OFF (67N OFF) 1 x 0
67N-3 PICKUP (P1628) = x 1 0
PTOC20.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC20.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC20.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
56 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTOC20.Str
No. Information
2698 67N-3 picked up (67N-3 picked up) 0 1
PTOC20.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC20.Op
No. Information
2603 67N-3 TRIP (67N-3 TRIP) 0 1
PTOC20.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC20.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC20.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
PTOC4.Mod
No. Information
2656 67N/67N-TOC switched OFF (67N OFF) 1 x 0
M.of PU TD (P1630) = x 1 0
PTOC4.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
SIPROTEC, 7SJ66, IEC61850 MAPPING 57
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTOC4.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC4.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC4.Str
No. Information
2684 67N-TOC picked up (67N-TOCPickedup) 0 1
PTOC4.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC4.Op
No. Information
2686 67N-TOC TRIP (67N-TOC TRIP) 0 1
PTOC4.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC4.ChgSet
No. Information
1997 Dynamic settings are ACTIVE (Dyn set. ACTIVE) 0 1
PTOC4.ChgSet.stVal 0 1
device annunciation: 1 - ON IEC Status ChgSet.stVal: 0 - FALSE
0 - OFF 1 - TRUE
58 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
2.4.3 Directional Overcurrent Protection 67N (PTRC3)
PTRC3.Mod
No. Information
67/67-TOC switched OFF (67/67-TOC OFF) (I 2651) and 1 0
67N/67N-TOC switched OFF (67N OFF) (I 2656)
PTRC3.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTRC3.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTRC3.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTRC3.Str
No. Information
2691 67/67N picked up (67/67N pickedup) 0 1
PTRC3.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 59
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTRC3.Str.dirGeneral
No. Information
2691 67/67N picked up (67/67N picked up) 0 1 1 1 1
Phase A forward (Phase A forward) (I 2628) or x 0 1 0 1
Phase B forward (Phase B forward) (I 2629) or
Phase C forward (Phase C forward) (I 2630) or
Ground forward (Ground forward) (I 2635)
Phase A reverse (Phase A reverse) (I 2632) or x 0 0 1 1
Phase B reverse (Phase B reverse) (I 2633) or
Phase C reverse (Phase C reverse) (I 2634) or
Ground reverse (Ground reverse) (I 2636)
PTRC3.Str.dirGeneral 0 0 1 2 3
device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN
0 - OFF 1 - FORWARD
2 - BACKWARD
3 - BOTH
PTRC3.Str.phsA
No. Information
2692 67/67-TOC Phase A picked up (67 A picked up) 0 1
PTRC3.Str.phsA 0 1
device annunciation: 1 - ON IEC Status Str.phsA: 0 - FALSE
0 - OFF 1 - TRUE
PTRC3.Str.dirPhsA
No. Information
2692 67/67-TOC Phase A picked up (67 A picked up) 0 1 1 1 1
2628 Phase A forward (Phase A forward) x 0 1 0 1
2632 Phase A reverse (Phase A reverse) x 0 0 1 1
PTRC3.Str.dirPhsA 0 0 1 2 3
device annunciation: 1 - ON IEC Status Str.dirPhsA: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
60 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTRC3.Str.phsB
No. Information
2693 67/67-TOC Phase B picked up (67 B picked up) 0 1
PTRC3.Str.phsB 0 1
device annunciation: 1 - ON IEC Status Str.phsB: 0 - FALSE
0 - OFF 1 - TRUE
PTRC3.Str.dirPhsB
No. Information
2693 67/67-TOC Phase B picked up (67 B picked up) 0 1 1 1 1
2629 Phase B forward (Phase B forward) x 0 1 0 1
2633 Phase B reverse (Phase B reverse) x 0 0 1 1
PTRC3.Str.dirPhsB 0 0 1 2 3
device annunciation: 1 - ON IEC Status Str.dirPhsB: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
PTRC3.Str.phsC
No. Information
2694 67/67-TOC Phase C picked up (67 C picked up) 0 1
PTRC3.Str.phsC 0 1
device annunciation: 1 - ON IEC Status Str.phsC: 0 - FALSE
0 - OFF 1 - TRUE
PTRC3.Str.dirPhsC
No. Information
2694 67/67-TOC Phase C picked up (67 C picked up) 0 1 1 1 1
2630 Phase C forward (Phase C forward) x 0 1 0 1
2634 Phase C reverse (Phase C reverse) x 0 0 1 1
PTRC3.Str.dirPhsC 0 0 1 2 3
device annunciation: 1 - ON IEC Status Str.dirPhsC: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
SIPROTEC, 7SJ66, IEC61850 MAPPING 61
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.4 Directional Overcurrent Protection 67, 67N (PTOCx, PTRC3)
PTRC3.Str.neut
No. Information
2695 67N/67N-TOC picked up (67N picked up) 0 1
PTRC3.Str.neut 0 1
device annunciation: 1 - ON IEC Status Str.neut: 0 - FALSE
0 - OFF 1 - TRUE
PTRC3.Str.dirNeut
No. Information
2695 67N/67N-TOC picked up (67N picked up) 0 1 1 1 1
2635 Ground forward (Ground forward) x 0 1 0 1
2636 Ground reverse (Ground reverse) x 0 0 1 1
PTRC3.Str.dirNeut 0 0 1 2 3
device annunciation: 1 - ON IEC Status Str.dirPhsC: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
PTRC3.Op
No. Information
2696 67/67N TRIP (67/67N TRIP) 0 1
PTRC3.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
62 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17)
2.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17)
PTOC16.Mod
No. Information
5961 50 1Ph is OFF (50 1Ph OFF) 1 x 0
50 1Ph-1 PICKUP (P2705) = x 1 0
PTOC16.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC16.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC16.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC16.Str
No. Information
5974 50 1Ph-1 picked up (50 1Ph-1 PU) 0 1
PTOC16.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC16.Op
No. Information
5975 50 1Ph-1 TRIP (50 1Ph-1 TRIP) 0 1
PTOC16.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 63
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17)
PTOC17.Mod
No. Information
5961 50 1Ph is OFF (50 1Ph OFF) 1 x 0
50 1Ph-2 PICKUP (P2703) = x 1 0
PTOC17.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC17.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC17.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
64 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.5 Single-Phase Overcurrent Protection (PTOC16, PTOC17)
PTOC17.Str
No. Information
5977 50 1Ph-2 picked up (50 1Ph-2 PU) 0 1
PTOC17.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC17.Op
No. Information
5979 50 1Ph-2 TRIP (50 1Ph-2 TRIP) 0 1
PTOC17.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 65
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.6 Voltage Protection 27, 59 (PTUVx, PTOVx)
2.6 Voltage Protection 27, 59 (PTUVx, PTOVx)
2.6.1 Undervoltage Protection 27 (PTUV1)
PTUV1.Mod
No. Information
6530 27 Undervoltage protection switched OFF (27 OFF) 1 0
PTUV1.Mod.stVal 5 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTUV1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTUV1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
66 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.6 Voltage Protection 27, 59 (PTUVx, PTOVx)
PTUV1.Str
No. Information
6533 27-1 Undervoltage picked up (27-1 picked up) 0 x 1
6534 27-1 Undervoltage PICKUP w/curr. superv (27-1 PU CS) 0 1 x
PTUV1.Str.general 0 1 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
x - irrelevant
PTUV1.Op
No. Information
6539 27-1 Undervoltage TRIP (27-1 TRIP) 0 1
PTUV1.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 67
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.6 Voltage Protection 27, 59 (PTUVx, PTOVx)
2.6.2 Undervoltage Protection 27 (PTUV2)
PTUV2.Mod
No. Information
6530 27 Undervoltage protection switched OFF (27 OFF) 1 0
PTUV2.Mod.stVal 5 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTUV2.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTUV2.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
68 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.6 Voltage Protection 27, 59 (PTUVx, PTOVx)
PTUV2.Str
No. Information
6537 27-2 Undervoltage picked up (27-2 picked up) 0 x 1
6538 27-2 Undervoltage PICKUP w/curr. superv (27-2 PU CS) 0 1 x
PTUV2.Str.general 0 1 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
X - irrelevant
PTUV2.Op
No. Information
6540 27-2 Undervoltage TRIP (27-2 TRIP) 0 1
PTUV2.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 69
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.6 Voltage Protection 27, 59 (PTUVx, PTOVx)
2.6.3 Overvoltage Protection 59 (PTOV1)
PTOV1.Mod
No. Information
6565 59-Overvoltage protection switched OFF (59 OFF) 1 0
PTOV1.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOV1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOV1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOV1.Str
No. Information
6568 59 picked up (59-1 picked up) 0 1
PTOV1.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOV1.Op
No. Information
6570 59 TRIP (59-1 TRIP) 0 1
PTOV1.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
70 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.6 Voltage Protection 27, 59 (PTUVx, PTOVx)
2.6.4 Overvoltage Protection 59 (PTOV2)
PTOV2.Mod
No. Information
6565 59-Overvoltage protection switched OFF (59 OFF) 1 0
PTOV2.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOV2.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOV2.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOV2.Str
No. Information
6571 59-2 Overvoltage V>> picked up (59-2 picked up) 0 1
PTOV2.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOV2.Op
No. Information
6573 59-2 Overvoltage V>> TRIP (59-2 TRIP) 0 1
PTOV2.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 71
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5)
2.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5)
PTOC14.Mod
No. Information
5151 46 switched OFF (46 OFF) 1 0
PTOC14.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC14.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC14.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC14.Str
No. Information
5165 46-1 picked up (46-1 picked up) 0 1
PTOC14.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC14.Op
No. Information
46-1 TRIP (46-1 TRIP) 0 1
PTOC14.Op.general 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
72 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5)
PTOC15.Mod
No. Information
5151 46 switched OFF (46 OFF) 1 0
PTOC15.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC15.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC15.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTOC15.Str
No. Information
5159 46-2 picked up (46-2 picked up) 0 1
PTOC15.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC15.Op
No. Information
46-2 TRIP (46-2 TRIP) 0 1
PTOC15.Op.general 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 73
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5)
PTOC5.Mod
No. Information
5151 46 switched OFF (46 OFF) 1 0
PTOC5.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOC5.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOC5.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
74 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.7 Negative Sequence Protection 46 (PTOC14, PTOC15, PTOC5)
PTOC5.Str
No. Information
5166 46-TOC picked up (46-TOC pickedup) 0 1
PTOC5.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PTOC5.Op
No. Information
46-TOC TRIP (46-TOC TRIP) 0 1
PTOC5.Op.general 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 75
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.8 Motor Protection (PMSS1, PMRI1)
2.8 Motor Protection (PMSS1, PMRI1)
2.8.1 Motor Starting Protection 48 (PMSS1)
PMSS1.Mod
No. Information
6811 Startup supervision OFF (START-SUP OFF) 1 0
PMSS1.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PMSS1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PMSS1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
76 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.8 Motor Protection (PMSS1, PMRI1)
PMSS1.Str
No. Information
6823 Startup supervision Pickup (START-SUP pu) 0 1
PMSS1.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PMSS1.Op
No. Information
6821 Startup supervision TRIP (START-SUP TRIP) 0 1
PMSS1.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 77
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.8 Motor Protection (PMSS1, PMRI1)
2.8.2 Motor Restart Inhibit 66 (PMRI1)
PMRI1.Mod
No. Information
4824 66 Motor start protection OFF (66 OFF)) 1 0
PMRI1.Mod.stVal 5 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PMRI1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PMRI1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PMRI1.Op
No. Information
4827 66 Motor start protection TRIP (66 TRIP) 0 1
PMRI1.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PMRI1.StrInhTmm
No. Information Value
809 Time untill release of reclose-blocking (T reclose=) PMRI1.StrInhTmm.stVal Absolute value
78 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.9 Load Jam Protection (PMLJ1)
2.9 Load Jam Protection (PMLJ1)
Function available with Firmware
PMLJ1.Mod
No. Information
10022 Load Jam Protection is OFF (JAM PROT.OFF) 1 0
PMLJ1.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PMLJ1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PMLJ1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 79
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.9 Load Jam Protection (PMLJ1)
PMLJ1.Str
No. Information
10025 Load Jam Protection picked up (Load Jam pickup) 0 1
PMLJ1.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PMLJ1.Op
No. Information
10026 Load Jam Protection TRIP (Load Jam TRIP) 0 1
PMLJ1.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PMLJ1.LodJamAlm
No. Information
10024 Load Jam Protection alarm (Load Jam alarm) 0 1
PMLJ1.LodJamAlm.stVal 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
80 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
2.10.1 Frequency protection 81-1 U (PTUF1)
PTUF1.Mod
No. Information
5211 81 OFF (81 OFF) x 1 0
81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 1
PTUF1.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTUF1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTUF1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 81
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
PTUF1.Str
No. Information
5232 81-1 picked up (81-1 picked up) 0 0 1 1
81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1
PTUF1.Str.general 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTUF1.Op
No. Information
5236 81-1 TRIP (81-1 TRIP) 0 0 1 1
81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1
PTUF1.Op.general 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTUF1.BlkV
No. Information
5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1
81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1
PTUF1.BlkV.stVal 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
82 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
2.10.2 Frequency protection 81-2 U (PTUF2)
PTUF2.Mod
No. Information
5211 81 OFF (81 OFF) x 1 0
81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 1
PTUF2.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTUF2.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTUF2.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 83
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
PTUF2.Str
No. Information
5233 81-2 picked up (81-2 picked up) 0 0 1 1
81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1
PTUF2.Str.general 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTUF2.Op
No. Information
5237 81-2 TRIP (81-2 TRIP) 0 0 1 1
81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1
PTUF2.Op.general 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTUF2.BlkV
No. Information
5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1
81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1
PTUF2.BlkV.stVal 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
84 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
2.10.3 Frequency protection 81-3 U (PTUF3)
PTUF3.Mod
No. Information
5211 81 OFF (81 OFF) x 1 0
81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 1
PTUF3.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTUF3.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTUF3.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 85
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
PTUF3.Str
No. Information
5234 81-3 picked up (81-3 picked up) 0 0 1 1
81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1
PTUF3.Str.general 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTUF3.Op
No. Information
5238 81-3 TRIP (81-3 TRIP) 0 0 1 1
81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1
PTUF3.Op.general 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTUF3.BlkV
No. Information
5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1
81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1
PTUF3.BlkV.stVal 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
86 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
2.10.4 Frequency protection 81-4 U (PTUF4)
PTUF4.Mod
No. Information
5211 81 OFF (81 OFF) x 1 0
81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 1
PTUF4.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTUF4.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTUF4.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 87
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
PTUF4.Str
No. Information
5235 81-4 picked up (81-4 picked up) 0 0 1 1
81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1
PTUF4.Str.general 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTUF4.Op
No. Information
5239 81-4 TRIP (81-4 TRIP) 0 0 1 1
81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1
PTUF4.Op.general 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTUF4.BlkV
No. Information
5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1
81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1
PTUF4.BlkV.stVal 0 0 0 1
device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
88 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
2.10.5 Frequency protection 81-1 O (PTOF1)
PTOF1.Mod
No. Information
5211 81 OFF (81 OFF) x 1 0
81-1 PICKUP (P5403/5404) Rated Frequency (P214) 1 x 0
PTOF1.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOF1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOF1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 89
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
PTOF1.Str
No. Information
5232 81-1 picked up (81-1 picked up) 0 0 1 1
81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1
PTOF1.Str.general 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTOF1.Op
No. Information
5236 81-1 TRIP (81-1 TRIP) 0 0 1 1
81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1
PTOF1.Op.general 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTOF1.BlkV
No. Information
5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1
81-1 PICKUP (P5403/5404) < Rated Frequency (P214) 0 1 0 1
PTOF1.BlkV.stVal 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
90 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
2.10.6 Frequency protection 81-2 O (PTOF2)
PTOF2.Mod
No. Information
5211 81 OFF (81 OFF) x 1 0
81-2 PICKUP (P5406/5407) Rated Frequency (P214) 1 x 0
PTOF2.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOF2.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOF2.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 91
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
PTOF2.Str
No. Information
5233 81-2 picked up (81-2 picked up) 0 0 1 1
81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1
PTOF2.Str.general 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTOF2.Op
No. Information
5237 81-2 TRIP (81-2 TRIP) 0 0 1 1
81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1
PTOF2.Op.general 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTOF2.BlkV
No. Information
5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1
81-2 PICKUP (P5406/5407) < Rated Frequency (P214) 0 1 0 1
PTOF2.BlkV.stVal 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
92 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
2.10.7 Frequency protection 81-3 O (PTOF3)
PTOF3.Mod
No. Information
5211 81 OFF (81 OFF) x 1 0
81-3 PICKUP (P5409/5410) Rated Frequency (P214) 1 x 0
PTOF1.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOF3.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOF3.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 93
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
PTOF3.Str
No. Information
5234 81-3 picked up (81-3 picked up) 0 0 1 1
81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1
PTOF3.Str.general 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTOF3.Op
No. Information
5238 81-3 TRIP (81-3 TRIP) 0 0 1 1
81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1
PTOF3.Op.general 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTOF3.BlkV
No. Information
5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1
81-3 PICKUP (P5409/5410) < Rated Frequency (P214) 0 1 0 1
PTOF3.BlkV.stVal 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
94 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
2.10.8 Frequency protection 81-4 O (PTOF4)
PTOF4.Mod
No. Information
5211 81 OFF (81 OFF) x 1 0
81-4 PICKUP (P5412/5413) Rated Frequency (P214) 1 x 0
PTOF4.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTOF4.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTOF4.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 95
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.10 Frequency protection 81 O/U (PTUFx, PTOFx)
PTOF4.Str
No. Information
5235 81-4 picked up (81-4 picked up) 0 0 1 1
81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1
PTOF4.Str.general 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status Str.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTOF4.Op
No. Information
5239 81-4 TRIP (81-4 TRIP) 0 0 1 1
81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1
PTOF4.Op.general 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status Op.general: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
PTOF4.BlkV
No. Information
5214 81 Under Voltage Block (81 Under V Blk) 0 0 1 1
81-4 PICKUP (P5412/5413) < Rated Frequency (P214) 0 1 0 1
PTOF4.BlkV.stVal 0 0 1 0
device annunciation / setting: 1 - ON / TRUE IEC Status BlkV.stVal: 0 - FALSE
0 - OFF / FALSE 1 - TRUE
96 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.11 QV Protection 27/Q (PTUV9)
2.11 QV Protection 27/Q (PTUV9)
PTUV9.Mod
No. Information
6411 27/Q -Protection off (27/Q OFF) 0 1
PTUV9.Mod.stVal 5 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTUV9.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTUV9.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTUV9.Str
No. Information
6423 27/Q-Protection PICKUP (27/Q PICKUP) 0 1
PTUV9.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
x - irrelevant
PTUV9.Op
No. Information
6421 27/Q -Protection Gen TRIP (27/Q Gen TRIP) 0 1 0 1
6422 27/Q -Protection Gen TRIP (27/Q Gen TRIP) 0 0 1 1
PTUV9.Op.general 0 1 1 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 97
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.12 Thermal overload protection (PTTR1)
2.12 Thermal overload protection (PTTR1)
PTTR1.Mod
No. Information
1511 49 Overload Protection is OFF (49 O / L OFF) 1 0
PTTR1.Mod.stVal 5 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTTR1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTTR1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTTR1.Str
No. Information
1517 49 Winding Overload (49 Winding O/L) 0 1
PTTR1.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
98 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.12 Thermal overload protection (PTTR1)
PTTR1.Op
No. Information
1521 49 Thermal Overload TRIP (49 Th O/L TRIP) 0 1
PTTR1.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PTTR1.AlmThm
No. Information
1516 49 Overload Alarm! Near Thermal Trip (49 O/L Alarm) 0 1
PTTR1.AlmThm.general 0 1
device annunciation: 1 - ON IEC Status AlmThm.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 99
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
2.13.1 Ground Fault Protection 64 (PHIZ1)
PHIZ1.Mod
No. Information
1211 50Ns/67Ns is OFF (50Ns/67Ns OFF) 1 0
PHIZ1.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PHIZ1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PHIZ1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PHIZ1.Str
No. Information
1215 64 displacement voltage pick up (64 Pickup) 0 1
PHIZ1.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
100 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
PHIZ1.Str.dirGeneral
No. Information
1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1
1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x 0 1 0 1 x
1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x 0 0 1 1 x
1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x 0 0 0 0 1
PHIZ1.Str.dirGeneral 0 0 1 2 3 0
device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH
PHIZ1.Str.phsA
No. Information
1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1
1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x
1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x
1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1
1272 Sensitive Ground fault picked up in Ph A (Sens. Gnd Ph A) x 0 1 1 1 1
PHIZ1.Str.phsA 0 0 1 1 1 1
device annunciation: 1 - ON IEC Status Str.phsA: 0 -FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 101
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
PHIZ1.Str.dirPhsA
No. Information
1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1
1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x
1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x
1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1
1272 Sensitive Ground fault picked up in Ph A (Sens. Gnd Ph A) x 0 1 1 1 1
PHIZ1.Str.dirPhsA 0 0 1 2 0 0
device annunciation: 1 - ON IEC Status Str.dirPhsA: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
PHIZ1.Str.phsB
No. Information
1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1
1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x
1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x
1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1
1273 Sensitive Ground fault picked up in Ph B (Sens. Gnd Ph B) x 0 1 1 1 1
PHIZ1.Str.phsB 0 0 1 1 1 1
device annunciation: 1 - ON IEC Status Str.phsB: 0 -FALSE
0 - OFF 1 - TRUE
102 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
PHIZ1.Str.dirPhsB
No. Information
1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1
1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x
1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x
1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1
1273 Sensitive Ground fault picked up in Ph B (Sens. Gnd Ph B) x 0 1 1 1 1
PHIZ1.Str.dirPhsB 0 0 1 2 0 0
device annunciation: 1 - ON IEC Status Str.dirPhsB: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
PHIZ1.Str.phsC
No. Information
1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1
1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x
1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x
1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1
1274 Sensitive Ground fault picked up in Ph C (Sens. Gnd Ph C) x 0 1 1 1 1
PHIZ1.Str.phsC 0 0 1 1 1 1
device annunciation: 1 - ON IEC Status Str.phsC: 0 -FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 103
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
PHIZ1.Str.dirPhsC
No. Information
1215 64 displacement voltage pick up (64 Pickup) 0 x 1 1 1 1
1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x x 1 0 1 x
1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x x 0 1 1 x
1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x x 0 0 x 1
1274 Sensitive Ground fault picked up in Ph C (Sens. Gnd Ph C) x 0 1 1 1 1
PHIZ1.Str.dirPhsC 0 0 1 2 0 0
device annunciation: 1 - ON IEC Status Str.dirPhsC: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
PHIZ1.Op
No. Information
1217 64 displacement voltage element TRIP (64 TRIP) 0 1
PHIZ1.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
104 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
2.13.2 Ground Fault Protection 50N(s) (PSDE1, PSDE2)
PSDE1.Mod
No. Information
1211 50Ns/67Ns is OFF (50Ns/67Ns OFF) 1 0
PSDE1.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PSDE1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PSDE1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PSDE1.Str
No. Information
1224 50Ns-1 Pickup (50Ns-1 Pickup) 0 1
PSDE1.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 105
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
PSDE1.Str.dirGeneral
No. Information
1224 50Ns-1 Pickup (50Ns-1 Pickup) 0 1 1 1 1 1
1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x 0 1 0 1 x
1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x 0 0 1 1 x
1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x 0 0 0 0 1
PSDE1.Str.dirGeneral 0 0 1 2 3 0
device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH
PSDE1.Op
No. Information
1226 50Ns-1 TRIP (50Ns-1 TRIP) 0 1
PSDE1.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PSDE2.Mod
No. Information
1211 50Ns/67Ns is OFF (50Ns/67Ns OFF) 1 0
PSDE2.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PSDE2.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PSDE2.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
106 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
PSDE2.Str
No. Information
1221 50Ns-2 Pickup (50Ns-2 Pickup) 0 1
PSDE2.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PSDE2.Str.dirGeneral
No. Information
1221 50Ns-2 Pickup (50Ns-2 Pickup) 0 1 1 1 1 1
1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x 0 1 0 1 x
1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x 0 0 1 1 x
1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x 0 0 0 0 1
PSDE2.Str.dirGeneral 0 0 1 2 3 0
device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH
PSDE2.Op
No. Information
1223 50Ns-2 TRIP (50Ns-2 TRIP) 0 1
PSDE2.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 107
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
2.13.3 51 N(s) (PSDE3)
PSDE3.Mod
No. Information
1211 50Ns/67Ns is OFF (50Ns/67Ns OFF) 1 x 0
M.of PU TD (P3131) = x 1 0
PSDE3.Mod.stVal 5 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PSDE3.Health
No. Information
51 Device is Operational and Protecting (Device OK) x 0 1
16029 sens.grd.flt. 51Ns BLOCKED Setting Error (51Ns BLK PaErr) 1 x 0
PSDE3.Health.stVal 3 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
x - irrelevant 3 - ALARM
PSDE3.Str
No. Information
1227 51Ns picked up (51Ns Pickup) 0 1
PSDE3.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
108 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.13 Ground Fault Protection 64, 50N(s), 51N(s) (PHIZ1, PSDEx)
PSDE3.Str.dirGeneral
No. Information
1227 51Ns picked up (51Ns Pickup) 0 1 1 1 1 1
1276 Sensitive Gnd fault in forward direction (SensGnd Forward) x 0 1 0 1 x
1277 Sensitive Gnd fault in reverse direction (SensGnd Reverse) x 0 0 1 1 x
1278 Sensitive Gnd fault direction undefined (SensGnd undef.) x 0 0 0 0 1
PSDE3.Str.dirGeneral 0 0 1 2 3 0
device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH
PSDE3.Op
No. Information
1229 51Ns TRIP (51Ns TRIP) 0 1
PSDE3.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 109
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.14 Admittance Earth Fault Protection (PSDE4, PSDE5, PSDE6, PSDE7)
2.14 Admittance Earth Fault Protection (PSDE4, PSDE5, PSDE6, PSDE7)
PSDE4.Mod
No. Information
18516 Y0(G0/B0) is OFF (Y0 OFF) 1 0
PSDE4.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PSDE4.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PSDE4.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Str.general: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PSDE4.Str
No. Information
18501 Y0(G0/B0)-1 Pickup (Y0-1 Pickup) 0 1
PSDE4.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
110 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.14 Admittance Earth Fault Protection (PSDE4, PSDE5, PSDE6, PSDE7)
PSDE4.Str.dirGeneral
No. Information
18501 Y0(G0/B0)-1 Pickup (Y0-1 Pickup) 0 1 1 1 1 1
18485 Y0(G0/B0)-1 in forward direction (Y0-1 Forward) x 0 1 0 1 x
18486 Y0(G0/B0)-1 in reverse direction (Y0-1 Reverse) x 0 0 1 1 x
PSDE4.Str.dirGeneral 0 0 1 2 3 0
device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH
PSDE4.Op
No. Information
18505 Y0(G0/B0)-1 TRIP (Y0-1 TRIP) 0 1
PSDE4.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PSDE5.Mod
No. Information
18516 Y0(G0/B0) is OFF (Y0 OFF) 1 0
PSDE5.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
SIPROTEC, 7SJ66, IEC61850 MAPPING 111
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.14 Admittance Earth Fault Protection (PSDE4, PSDE5, PSDE6, PSDE7)
PSDE5.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PSDE5.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Str.general: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PSDE5.Str
No. Information
18502 Y0(G0/B0)-2 Pickup (Y0-2 Pickup) 0 1
PSDE5.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PSDE5.Str.dirGeneral
No. Information
18502 Y0(G0/B0)-2 Pickup (Y0-2 Pickup) 0 1 1 1 1 1
18488 Y0(G0/B0)-2 in forward direction (Y0-2 Forward) x 0 1 0 1 x
18489 Y0(G0/B0)-2 in reverse direction (Y0-2 Reverse) x 0 0 1 1 x
PSDE5.Str.dirGeneral 0 0 1 2 3 0
device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH
PSDE5.Op
No. Information
18506 Y0(G0/B0)-2 TRIP (Y0-2 TRIP) 0 1
PSDE5.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
112 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.14 Admittance Earth Fault Protection (PSDE4, PSDE5, PSDE6, PSDE7)
PSDE6.Mod
No. Information
18516 Y0(G0/B0) is OFF (Y0 OFF) 1 0
PSDE6.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PSDE6.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PSDE6.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Str.general: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PSDE6.Str
No. Information
18503 Y0(G0/B0)-3 Pickup (Y0-3 Pickup) 0 1
PSDE6.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
PSDE6.Str.dirGeneral
No. Information
18503 Y0(G0/B0)-3 Pickup (Y0-3 Pickup) 0 1 1 1 1 1
18491 Y0(G0/B0)-3 in forward direction (Y0-3 Forward) x 0 1 0 1 x
18492 Y0(G0/B0)-3 in reverse direction (Y0-3 Reverse) x 0 0 1 1 x
PSDE6.Str.dirGeneral 0 0 1 2 3 0
device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH
SIPROTEC, 7SJ66, IEC61850 MAPPING 113
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.14 Admittance Earth Fault Protection (PSDE4, PSDE5, PSDE6, PSDE7)
PSDE6.Op
No. Information
18507 Y0(G0/B0)-3 TRIP (Y0-3 TRIP) 0 1
PSDE6.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
PSDE7.Mod
No. Information
18516 Y0(G0/B0) is OFF (Y0 OFF) 1 0
PSDE7.Mod.stVal 5 1
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
PSDE7.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PSDE7.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Str.general: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PSDE7.Str
No. Information
18504 Y0(G0/B0)-4 Pickup (Y0-4 Pickup) 0 1
PSDE7.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
114 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.14 Admittance Earth Fault Protection (PSDE4, PSDE5, PSDE6, PSDE7)
PSDE7.Str.dirGeneral
No. Information
18504 Y0(G0/B0)-4 Pickup (Y0-4 Pickup) 0 1 1 1 1 1
18494 Y0(G0/B0)-4 in forward direction (Y0-4 Forward) x 0 1 0 1 x
18495 Y0(G0/B0)-4 in reverse direction (Y0-4 Reverse) x 0 0 1 1 x
PSDE7.Str.dirGeneral 0 0 1 2 3 0
device annunciation: 1 - ON IEC Status Str.dirGeneral: 0 - UNKNOWN
0 - OFF 1 - FORWARD
x - irrelevant 2 - BACKWARD
3 - BOTH
PSDE7.Op
No. Information
18508 Y0(G0/B0)-4 TRIP (Y0-4 TRIP) 0 1
PSDE7.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 115
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.15 Automatic Reclosing System 79 (RREC1)
2.15 Automatic Reclosing System 79 (RREC1)
RREC1.Mod
No. Information
2781 79 Auto recloser is switched OFF (79 OFF) 1 0
RREC1.Mod.stVal 5 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
RREC1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
RREC1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
RREC1.Op
No. Information
2851 79 - Close command (79 Close) 0 1
RREC1.Op.general 0 1
device annunciation: 1 - ON IEC Status Op.general: 0 - FALSE
0 - OFF 1 - TRUE
RREC1.AutoRecSt
No. Information
2801 79 - in progress (79 in progress) 1 1 0 0
2862 79 - cycle successful (79 Successful) 1 0 1 0
RREC1.AutoRecSt.stVal 3 2 3 1
device annunciation: 1 - ON IEC Status AutoRecST.stVal: 1 - ready
0 - OFF 2 - in progress
3 - successful
116 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.16 Fault Locator (RFLO1)
2.16 Fault Locator (RFLO1)
RFLO1.Mod
No. Information
Fault Locator (P180) = Enabled 1 0
RFLO1.Mod.stVal 1 5
device annunciation / setting: 1 - ON / TRUE IEC Status Mod.stVal: 1 - ON
0 - OFF / FALSE 2 - BLOCKED
3 - TEST
4 - TEST/BLOCKED
5 - OFF
RFLO1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
RFLO1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
RFLO1.FltZ
No. Information Value
Absolute value of the fault RFLO1.FltZ.cVal.mag.f Measured value Absolute value
impedance
RFLO1.FltZ.units.SIUnit 30 (Ohm)
RFLO1.FltZ.units.multiplier 0 1
Angle of the fault RFLO1.FltZ.cVal.ang.f Measured value Angle in °
impedance
SIPROTEC, 7SJ66, IEC61850 MAPPING 117
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.16 Fault Locator (RFLO1)
RFLO1.FltDiskm
No. Information Value
1119 Flt Locator: Distance to fault RFLO1.FltDiskm.mag.f Measured value Absolute value
or (dist =)
1122 RFLO1.FltDiskm.units.SIUnit 2 Meter
RFLO1.FltDiskm.units.multiplie 3 Kilo
r
RFLO1.FltDisPrc
No. Information Value
1120 Flt Locator: Distance [%] to RFLO1.FltDisPrc.mag.f Measured value Absolute value
fault (d[%] =)
RFLO1.FltDisPrc.units.SIUnit 1 NONE
RFLO1.FltDisPrc.multiplier 0 1
118 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.17 Circuit breaker failure protection 50BF(RBRF1)
2.17 Circuit breaker failure protection 50BF(RBRF1)
RBRF1.Mod
No. Information
1451 Breaker failure is switched OFF (BkrFail OFF) 1 0
RBRF1.Mod.stVal 5 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
3 - TEST
4 - TEST/BLOCKED
5 - OFF
RBRF1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
RBRF1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
RBRF1.Str
No. Information
1456 50BF (internal) PICKUP (50BF int Pickup) 0 0 1 1
1457 50BF (external) PICKUP (50BF ext Pickup) 0 1 0 1
RBRF1.Str.general 0 1 1 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
RBRF1.OpEx
No. Information
1481 50BF (external) TRIP (50BF ext TRIP) 0 1
RBRF1.OpEx.general 0 1
device annunciation: 1 - ON IEC Status OpEx.general: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 119
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.17 Circuit breaker failure protection 50BF(RBRF1)
RBRF1.OpIn
No. Information
1480 50BF (internal) TRIP (50BF int TRIP) 0 1
RBRF1.OpIn.general 0 1
device annunciation: 1 - ON IEC Status OpIn.general: 0 - FALSE
0 - OFF 1 - TRUE
x - irrelevant
120 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.18 Synchronism and Voltage Check 25 (RSYNx)
2.18 Synchronism and Voltage Check 25 (RSYNx)
RSYN1.Mod
No. Information
170.2101 Sync-group 1 is switched OFF (25-1 OFF) 0 1
RSYN1.Mod.stVal 1 5
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
RSYN1.Health
No. Information
170.0050 25 Synchronization Error (25 Sync. Error) x x 1 0
51 Device is Operational and Protecting (Device OK) x x 1 1
170.2096 25 Multiple selection of func-groups (25 FG-Error) 1 x 0 0
170.2097 25 Setting error (25 Set-Error) x 1 0 0
RSYN1.Health.stVal 3 3 2 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
x - irrelevant 3 - ALARM
RSYN1.Rel
No. Information
170.0049 25 Sync. Release of CLOSE Command (25 CloseRelease) 0 1
RSYN1.Rel.stVal 0 1
device annunciation: 1 - ON IEC Status Rel.stVal: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 121
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.18 Synchronism and Voltage Check 25 (RSYNx)
RSYN1.VInd
No. Information
170.2030 25 Voltage difference (Vdiff) okay (25 Vdiff ok) 0 1
RSYN1.VInd.stVal 1 0
device annunciation: 1 - ON IEC Status VInd.stVal: 0 - FALSE
0 - OFF 1 - TRUE
RSYN1.AngInd
No. Information
170.2032 25 Angle difference (alphadiff) okay (25 diff ok) 0 1
RSYN1.AngInd.stVal 1 0
device annunciation: 1 - ON IEC Status AngInd.stVal: 0 - FALSE
0 - OFF 1 - TRUE
RSYN1.HzInd
No. Information
170.2031 25 Frequency difference (fdiff) okay (25 fdiff ok) 0 1
RSYN1.HzInd.stVal 1 0
device annunciation: 1 - ON IEC Status HzInd.stVal: 0 - FALSE
0 - OFF 1 - TRUE
RSYN1.SynPrg
No. Information
170.2022 25-group 1: measurement in progress (25-1 meas.) 0 1
RSYN1.SynPrg.stVal 0 1
device annunciation: 1 - ON IEC Status SynPrg.stVal: 0 - FALSE
0 - OFF 1 - TRUE
122 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.18 Synchronism and Voltage Check 25 (RSYNx)
RSYN1.DifVCIc
No. Information Value
170.2054 dV = (dV =) RSYN1.DifVClc.mag.f Measured value Absolute value
RSYN1.DifVClc.units.SIUnit 29 V (Volt)
RSYN1.DifVClc.units.multiplier 3 Kilo
RSYN1.DifHzCIc
No. Information Value
170.2055 df = (df =) RSYN1. DifHzClc.mag.f Measured value Absolute value
RSYN1. DifHzClc.units.SIUnit 33 Hz
RSYN1. DifHzClc.units.multiplier 0 1
RSYN1.DifAngCIc
No. Information Value
170.2056 dalpha = (d =) RSYN1. DifAngClc.mag.f Measured value Absolute value
RSYN1. DifAngClc.units.SIUnit 9 ° (Degree)
RSYN1. DifAngClc.units.multiplier 0 1
SIPROTEC, 7SJ66, IEC61850 MAPPING 123
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.19 Three-pole tripping 52 Breaker (XCBR1)
2.19 Three-pole tripping 52 Breaker (XCBR1)
XCBR1.Mod
No. Information
51 Device is Operational and Protecting (Device OK) 1 0
XCBR1.Mod.stVal 1 5
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
3 - TEST
4 - TEST/BLOCKED
5 - OFF
XCBR1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
XCBR1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
x - irrelevant 3 - ALARM
XCBR1.Loc
No. Information
55 Reset Device (Reset Device) 1 0
XCBR1.Loc.stVal 1 0
device annunciation: 1 - ON IEC Status Loc.stVal: 0 - FALSE
0 - OFF 1 - TRUE
XCBR1.OpCnt
No. Information Value
Number of TRIPs= (#of XCBR1.OpCnt.stVal Metered value Absolute value
TRIPs=)
124 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.19 Three-pole tripping 52 Breaker (XCBR1)
XCBR1.Pos
No. Information
4601 >52-a contact (OPEN, if bkr is open) (>52-a) 0 1 0 1
4602 >52-b contact (OPEN, if bkr is closed) (>52-b) 0 0 1 1
XCBR1.Pos.stVal - if spontan information 11 01 10 11
XCBR1.Pos.stVal - if command is running 00 01 10 00
device annunciation: 1 - ON IEC Status Pos.stVal: 00 - INTERMEDIATE STATE
0 - OFF 01 - OFF
10 - ON
11 - BAD STATE
XCBR1.BlkOpn
No. Information
55 Reset Device (Reset Device) 1 0
XCBR1.BlkOpn.stVal 0 1
device annunciation: 1 - ON IEC Status BlkOpn.stVal: 0 - FALSE
0 - OFF 1 - TRUE
XCBR1.BlkCls
No. Information
55 Reset Device (Reset Device) 1 0
XCBR1.BlkCls.stVal 0 1
device annunciation: 1 - ON IEC Status BlkCls.stVal: 0 - FALSE
0 - OFF 1 - TRUE
XCBR1.CBOpCap
No. Information
XCBR1.CBOpCap.stVal 1
device annunciation: IEC Status CBOpCap.stVal: 1 - NONE
SIPROTEC, 7SJ66, IEC61850 MAPPING 125
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.19 Three-pole tripping 52 Breaker (XCBR1)
XCBR1.CirSpv
No. Information
6865 74TC Failure Trip Circuit (74TC Trip cir.) 0 1
XCBR1.CirSpv.stVal 0 1
device annunciation: 1 - ON IEC Status CirSpv.stVal: 0 - FALSE
0 - OFF 1 - TRUE
126 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.19 Three-pole tripping 52 Breaker (XCBR1)
XCBR1.SumSwARs1
No. Information Value
1021 Accumulation of XCBR1.SumSwARs1.actVal Metered value Current value of
interrupted current Ph A acummulated interrupted
( Ia =) current = actVal pulsQty
XCBR1.SumSwARs1.units.SIUnit 5 A (Ampere)
XCBR1.SumSwARs1.units.multiplier 3 Kilo
XCBR1.SumSwARs1.pulsQty 1.000000e-002 A / Metered value
XCBR1.SumSwARs2
No. Information Value
1022 Accumulation of XCBR1.SumSwARs2.actVal Metered value Current value of
interrupted current Ph B acummulated interrupted
( Ib =) current = actVal pulsQty
XCBR1.SumSwARs2.units.SIUnit 5 A (Ampere)
XCBR1.SumSwARs2.units.multiplier 3 Kilo
XCBR1.SumSwARs2.pulsQty 1.000000e-002 A / Metered value
XCBR1.SumSwARs3
No. Information Value
1023 Accumulation of XCBR1.SumSwARs3.actVal Metered value Current value of
interrupted current Ph C acummulated interrupted
( Ic =) current = actVal pulsQty
XCBR1.SumSwARs3.units.SIUnit 5 A (Ampere)
XCBR1.SumSwARs3.units.multiplier 3 Kilo
XCBR1.SumSwARs3.pulsQty 1.000000e-002 A / Metered value
SIPROTEC, 7SJ66, IEC61850 MAPPING 127
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.20 Tripping Logic of the Entire Device (PTRC1)
2.20 Tripping Logic of the Entire Device (PTRC1)
PTRC1.Mod
No. Information
51 Device is Operational and Protecting (Device OK) 0 1 1
52 At Least 1 Protection Funct. is Active (ProtActive) x 0 1
PTRC1.Mod.stVal 5 5 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
3 - TEST
4 - TEST/BLOCKED
5 - OFF
PTRC1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
PTRC1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
PTRC1.Str
No. Information
501 Relay PICKUP (Relay PICKUP) 0 1
PTRC1.Str.general 0 1
device annunciation: 1 - ON IEC Status Str.general: 0 - FALSE
0 - OFF 1 - TRUE
128 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.20 Tripping Logic of the Entire Device (PTRC1)
PTRC1.Tr
No. Information
511 Relay GENERAL TRIP command (Relay TRIP) 0 1
PTRC1.Tr.general 0 1
device annunciation: 1 - ON IEC Status Tr.general: 0 - FALSE
0 - OFF 1 - TRUE
PTRC1.FinTr
No. Information
2863 79 - Lockout (79 Lockout) 0 1
PTRC1.FinTr.stVal 0 1
device annunciation: 1 - ON IEC Status FinTr.stVal: 0 - FALSE
0 - OFF 1 - TRUE
SIPROTEC, 7SJ66, IEC61850 MAPPING 129
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.21 Measurement (MMXU1, MSQI1, MMTR1)
2.21 Measurement (MMXU1, MSQI1, MMTR1)
2.21.1 Measures (MMXU1)
MMXU1.Mod
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
MMXU1.Mod.stVal 0 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
MMXU1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
MMXU1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
130 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.21 Measurement (MMXU1, MSQI1, MMTR1)
MMXU1.TotW
No. Information Value
641 P (active power) (P =) MMXU1.TotW.mag.f Measured value Absolute value
MMXU1.TotW.units.SIUnit 62 W (Watt)
MMXU1.TotW.units.multiplier 6 Mega
MMXU1.TotVAr
No. Information Value
642 Q (reactive power) (Q =) MMXU1.TotVAr.mag.f Measured value Absolute value
MMXU1.TotVAr.units.SIUnit 63 VAr
MMXU1.TotVAr.units.multiplier 6 Mega
MMXU1.TotVA
No. Information Value
645 S (apparent power) (S =) MMXU1.TotVA.mag.f Measured value Absolute value
MMXU1.TotVA.units.SIUnit 61 VA
MMXU1.TotVA.units.multiplier 6 Mega
MMXU1.TotPF
No. Information Value
901 Power Factor (PF =) MMXU1.TotPF.mag.f Measured value Absolute value
MMXU1.TotPF.units.SIUnit 1 NONE
MMXU1.TotPF.units.multiplier 0 1
SIPROTEC, 7SJ66, IEC61850 MAPPING 131
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.21 Measurement (MMXU1, MSQI1, MMTR1)
MMXU1.Hz
No. Information Value
644 Frequency (Freq=) MMXU1.Hz.mag.f Measured value Absolute value
MMXU1.Hz.units.SIUnit 33 Hz
MMXU1.Hz.units.multiplier 0 1
MMXU1.A
No. Information Value
601 Ia (Ia =) MMXU1.A.phsA.cVal.mag.f Measured value Absolute value
MMXU1.A.phsA.units.SIUnit 5 A (Ampere)
MMXU1.A.phsA.units.multiplier 0 1
No. Information Value
602 Ib (Ib =) MMXU1.A.phsB.cVal.mag.f Measured value Absolute value
MMXU1.A.phsB.units.SIUnit 5 A (Ampere)
MMXU1.A.phsB.units.multiplier 0 1
No. Information Value
603 Ic (Ic =) MMXU1.A.phsC.cVal.mag.f Measured value Absolute value
MMXU1.A.phsC.units.SIUnit 5 A (Ampere)
MMXU1.A.phsC.units.multiplier 0 1
No. Information Value
604 In (In =) MMXU1.A.neut.cVal.mag.f Measured value Absolute value
MMXU1.A.neut.units.SIUnit 5 A (Ampere)
MMXU1.A.neut.units.multiplier 0 1
132 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.21 Measurement (MMXU1, MSQI1, MMTR1)
MMXU1.PPV
No. Information Value
624 Va-b (Va-b=) MMXU1.PPV.phsAB.cVal.mag.f Measured value Absolute value
MMXU1.PPV.phsAB.units.SIUnit 29 V (Volt)
MMXU1.PPV.phsAB.units.multiplier 3 Kilo
No. Information Value
625 Vb-c (Vb-c=) MMXU1.PPV.phsBC.cVal.mag.f Measured value Absolute value
MMXU1.PPV.phsBC.units.SIUnit 29 V (Volt)
MMXU1.PPV.phsBC.units.multiplier 3 Kilo
No. Information Value
626 Vc-a (Vc-a=) MMXU1.PPV.phsCA.cVal.mag.f Measured value Absolute value
MMXU1.PPV.phsCA.units.SIUnit 29 V (Volt)
MMXU1.PPV.phsCA.units.multiplier 3 Kilo
SIPROTEC, 7SJ66, IEC61850 MAPPING 133
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.21 Measurement (MMXU1, MSQI1, MMTR1)
MMXU1.PhV
No. Information Value
621 Va (Va =) MMXU1.PhV.phsA.cVal.mag.f Measured value Absolute value
MMXU1.PhV.phsA.units.SIUnit 29 V (Volt)
MMXU1.PhV.phsA.units.multiplier 3 Kilo
No. Information Value
622 Vb (Vb =) MMXU1.PhV.phsB.cVal.mag.f Measured value Absolute value
MMXU1.PhV.phsB.units.SIUnit 29 V (Volt)
MMXU1.PhV.phsB.units.multiplier 3 Kilo
No. Information Value
623 Vc (Vc =) MMXU1.PhV.phsC.cVal.mag.f Measured value Absolute value
MMXU1.PhV.phsC.units.SIUnit 29 V (Volt)
MMXU1.PhV.phsC.units.multiplier 3 Kilo
No. Information Value
627 VN (VN =) MMXU1.PhV.neut.cVal.mag.f Measured value Absolute value
MMXU1.PhV.neut.units.SIUnit 29 V (Volt)
MMXU1.PhV.neut.units.multiplier 3 Kilo
134 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.21 Measurement (MMXU1, MSQI1, MMTR1)
2.21.2 Measured values, symmetrical components (MSQI1)
MSQI1.Mod
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
MSQI1.Mod.stVal 0 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
MSQI1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
MSQI1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
SIPROTEC, 7SJ66, IEC61850 MAPPING 135
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.21 Measurement (MMXU1, MSQI1, MMTR1)
MSQI1.SeqA
No. Information Value
605 I1 (positive sequence) (I1 =) MSQI1.SeqA.c1.cVal.mag.f Measured value Absolute value
MSQI1.SeqA.c1.units.SIUnit 5 A (Ampere)
MSQI1.SeqA.c1.units.multiplier 0 1
No. Information Value
606 I2 (negative sequence) (I2 =) MSQI1.SeqA.c2.cVal.mag.f Measured value Absolute value
MSQI1.SeqA.c2.units.SIUnit 5 A (Ampere)
MSQI1.SeqA.c2.units.multiplier 0 1
No. Information Value
831 3Io (zero sequence) (3Io =) MSQI1.SeqA.c3.cVal.mag.f Measured value Absolute value
MSQI1.SeqA.c3.units.SIUnit 5 A (Ampere)
MSQI1.SeqA.c3.units.multiplier 0 1
MSQI1.SeqV
No. Information Value
629 V1 (positive sequence) (V1 =) MSQI1.SeqV.c1.cVal.mag.f Measured value Absolute value
MSQI1.SeqV.c1.units.SIUnit 29 V (Volt)
MSQI1.SeqV.c1.units.multiplier 3 Kilo
No. Information Value
630 V2 (negative sequence) (V2 =) MSQI1.SeqV.c2.cVal.mag.f Measured value Absolute value
MSQI1.SeqV.c2.units.SIUnit 29 V (Volt)
MSQI1.SeqV.c2.units.multiplier 3 Kilo
No. Information Value
832 Vo (zero sequence) (Vo =) MSQI1.SeqV.c3.cVal.mag.f Measured value Absolute value
MSQI1.SeqV.c3.units.SIUnit 29 V (Volt)
MSQI1.SeqV.c3.units.multiplier 3 Kilo
136 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.21 Measurement (MMXU1, MSQI1, MMTR1)
2.21.3 Power Metering (MMTR1)
MMTR1.Mod
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
MMTR1.Mod.stVal 0 1
device annunciation: 1 - ON IEC Status Mod.stVal: 1 - ON
0 - OFF 2 - BLOCKED
x - irrelevant 3 - TEST
4 - TEST/BLOCKED
5 - OFF
MMTR1.Health
No. Information
51 Device is Operational and Protecting (Device OK) 0 1
MMTR1.Health.stVal 3 1
device annunciation: 1 - ON IEC Status Health.stVal: 1 - OK
0 - OFF 2 - WARNING
3 - ALARM
MMTR1.SupWh
No. Information Value
924 Wp Forward (Wp+=) MMTR1.SupWh.actVal Metered value Current value of acummulated
interrupted current =
actVal pulsQty
MMTR1.SupWh.units.SIUnit 72 Wh
MMTR1.SupWh.units.multiplier 6 Mega
MMTR1.SupWh.pulsQty 3.464200e-005 Wh / Metered value
SIPROTEC, 7SJ66, IEC61850 MAPPING 137
C53000-L2640-C554-2, Edition 12.2017
Mapping
2.21 Measurement (MMXU1, MSQI1, MMTR1)
MMTR1.SupVArh
No. Information Value
925 Wq Forward (Wq+=) MMTR1.SupVArh.actVal Metered value Current value of acummulated
interrupted current =
actVal pulsQty
MMTR1.SupVArh.units.SIUnit 73 VArh
MMTR1.SupVArh.units.multiplier 6 Mega
MMTR1.SupVArh.pulsQty 3.464200e-005 VArh / Metered value
MMTR1.DmdWh
No. Information Value
928 Wp Reverse (Wp-=) MMTR1.DmdWh.actVal Metered value Current value of acummulated
interrupted current =
actVal pulsQty
MMTR1.DmdWh.units.SIUnit 72 Wh
MMTR1.DmdWh.units.multiplier 6 Mega
MMTR1.DmdWh.pulsQty 3.464200e-005 Wh / Metered value
MMTR1.DmdVArh
No. Information Value
929 Wq Reverse (Wq-=) MMTR1.DmdVArh.actVal Metered value Current value of acummulated
interrupted current =
actVal pulsQty
MMTR1.DmdVArh.units.SIUnit 73 VArh
MMTR1.DmdVArh.units.multiplier 6 Mega
MMTR1.DmdVArh.pulsQty 3.464200e-005 VArh / Metered value
138 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Literature
/1/ SIPROTEC 4 System Description
E50417-H1176-C151
/2/ SIPROTEC DIGSI, StartUP
E50417-G1176-C152
/3/ DIGSI CFC, Manual
E50417-H1176-C098
/4/ SIPROTEC SIGRA 4, Manual
E50417-H1176-C1100-C070
SIPROTEC, 7SJ66, IEC61850 MAPPING 139
C53000-L2640-C554-2, Edition 12.2017
140 SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Index
C PhV 134
CALH1 12, 21, 31 PPV 133
ErrBoard1 32 TotPF 131
ErrBoard2 32 TotVA 131
ErrBoard3 32 TotVAr 131
ErrBoard4 32 TotW 131
ErrBoard5 33 MSQI1 12, 20, 135
ErrBoard6 33 Health 135
ErrBoard7 33 Mod 135
GrAlm 31 SeqA 136
GrWrn 31 SeqV 136
Health 31
Mod 31
P
PHIZ1 15, 19, 100
D Health 100
DOI 11 Mod 100
Op 104
F Str.dirGeneral 101
Function parameters 12 Str.dirPhsA 102
Functional Scope Str.dirPhsB 103
7SJ66 13 Str.dirPhsC 104
Str.general 100
L Str.phsA 101
LD Str.phsB 102
CTRL (Control) 12, 21 Str.phsC 103
DR (Disturbance Recorder) 20 PMLJ1 16, 19, 79
EXT (Extended) 21 Health 79
Logical Device 10 LodJamAlm 80
MEAS (Measurement) 12, 20 Mod 79
PROT (Protection) 12, 18 Op 80
LLN0 10, 12, 18, 20, 21 Str 80
Beh 22, 24, 25 PMRI1 16, 19, 78
Health 22, 24, 25 Health 78
Mod 24, 25 Mod 78
OpTmh 23, 26 Op 78
Logical Node 11, 13, 18 StrInhTmm 78
LPHD1 10, 12, 19, 20, 21, 30 PMSS1 16, 19, 76
DevStr 30 Health 76
PhyHealth 30 Mod 76
Proxy 30 Op 77
Str 77
M PSD 110
MMTR1 12, 20, 137 PSDE1 15, 19, 105
DmdVArh 138 Health 105
DmdWh 138 Mod 105
Health 137 Op 106
Mod 137 Str.dirGeneral 106
SupVArh 138 Str.general 105
SupWh 137 PSDE2 15, 19, 106
MMXU1 12, 20, 130 Health 106
A 132, 135 Mod 106
Health 130 Op 107
Hz 132 Str.dirGeneral 107
Mod 130 Str.general 107
141
SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
PSDE3 15, 19, 108 Op 56
Health 108 Str 55
Mod 108 PTOC14 15, 19, 72
Op 109 Health 72
Str.dirGeneral 109, 116 Mod 72
Str.general 108, 116 Op 72
PSDE4 15, 19, 110 Str 72
Health 110 PTOC15 15, 19, 73
Mod 110 Health 73
Op 111 Mod 73
Str. 110 Op 73
Str.dirGeneral 111 Str 73
PSDE5 15, 19 PTOC16 15, 18, 63
Health 112 Health 63
Mod 111 Mod 63
Op 112 Op 63
Str 112 Str 63
Str.dirGeneral 112 PTOC17 15, 18, 64
PSDE6 15, 19, 110 Health 64
Health 113 Mod 64
Mod 113 Op 65
Op 114 Str 65
Str 113 PTOC18 13, 18
Str.dirGeneral 113 Health 38
PSDE7 15, 19, 110 Mod 38
Health 114 Op 39
Mod 114 Str 39
Op 115 PTOC19 14, 18
Str 114 ChgSet 51
Str.dirGeneral 115 Health 51
PTOC1 13, 18, 39 Mod 50
ChgSet 40 Op 51
Health 40 Str 51
Mod 39 PTOC2 13, 18, 43
Op 40 ChgSet 44
Str 40 Health 43
PTOC10 14, 18, 48 Mod 43
ChgSet 49 Op 44
Health 48 Str 44
Mod 48 PTOC20 14, 18
Op 49 ChgSet 57
Str 48 Health 56
PTOC11 14, 18, 49, 50 Mod 56
ChgSet 50 Op 57
Health 49 Str 57
Mod 49 PTOC3 14, 18, 52
Op 50 ChgSet 53
Str 50 Health 52
PTOC12 14, 18, 54 Mod 52
ChgSet 55 Op 52
Health 54 Str 52
Mod 54 PTOC4 14, 18, 57
Op 54 ChgSet 58
Str 54 Health 58
PTOC13 14, 18, 55, 56 Mod 57
ChgSet 56 Op 58
Health 55 Str 58
Mod 55 PTOC5 15, 19, 74
SIPROTEC, 7SJ66, IEC61850 MAPPING 142
C53000-L2640-C554-2, Edition 12.2017
Health 74 Mod 71
Mod 74 Op 71
Op 75 Str 71
Str 75 PTRC1 12, 18, 128
PTOC6 13, 18, 36 FinTr 129
ChgSet 37 Health 128
Health 36 Mod 128
Mod 36 Str 128
Op 36 Tr 129
Str 36 PTRC2 13, 18, 45
PTOC7 13, 18, 37 Health 45
ChgSet 38 Mod 41, 45
Health 37 Op 41, 47
Mod 37 Str 45
Op 38 Str.dirGeneral 45
Str 37 Str.dirNeut 47
PTOC8 13, 18 Str.dirPhsA 46
ChgSet 42 Str.dirPhsB 46
Health 41 Str.dirPhsC 47
Mod 41 Str.neut 47, 62
Op 41 Str.phsA 46
Str 41 Str.phsB 46, 47, 61, 62
PTOC9 13, 18, 42 Str.phsC 46, 47, 61, 62
ChgSet 43 PTRC3 14, 18, 59
Health 42 Health 59
Mod 42 Mod 59
Op 43 Op 62
Str 42 Str 59
PTOF1 16, 19, 89 Str.dirGeneral 60
BlkV 90 Str.dirNeut 62
Health 89 Str.dirPhsA 60
Mod 89, 91 Str.dirPhsB 61
Op 90 Str.dirPhsC 61
Str 90 Str.neut 62
PTOF2 91 Str.phsA 60
BlkV 92 Str.phsB 61
Health 91 Str.phsC 61
Mod 91 PTTR1 16, 19, 98
Op 92 AlmThm 99
Str 92 Health 98
PTOF3 93 Mod 98
BlkV 94 Str 98
Health 93 Tr 99
Mod 93 PTUF1 16, 19, 81
Op 94 BlkV 82
Str 94 Health 81
PTOF4 95 Mod 81
BlkV 96 Op 82
Health 95 Str 82
Mod 95 PTUF2 83
Op 96 BlkV 84
Str 96 Health 83
PTOV1 16, 18, 70 Mod 83
Health 70 Op 84
Mod 70 Str 84
Op 70 PTUF3 85
Str 70 BlkV 86
PTOV2 16, 71 Health 85
Health 71 Mod 85
143
SIPROTEC, 7SJ66, IEC61850 MAPPING
C53000-L2640-C554-2, Edition 12.2017
Op 86 Mod 121
Str 86 Rel 121
PTUF4 87 SynPrg 122
BlkV 88 VInd 122
Health 87 RSYN2
Mod 87 DifAngCIc 123
Op 88 DifVCIc 123
Str 88 Health 123
PTUV1 16, 18, 66, 97 RSYN3
Health 66 DifVCIc 123
Mod 66 RSYN4
Op 67 HzInd 124
Str 67
PTUV2 16, 68 X
Health 68 XCBR1 12, 18, 124
Mod 68 BlkCls 125
Op 69 BlkOpn 125
Str 69 CBOpCap 125
PTUV7 19 CirSpv 126
Health 97 Health 124
Mod 97 Loc 124
Op 97 Mod 124
Str 97 OpCnt 124
PVOC1 Pos 125
Mod 41, 47 SumSwARs1 127
SumSwARs2 127
R SumSwARs3 127
RBRF1 16, 19, 119
Health 119
Mod 119
OpEx 119
OpIn 120
Str 119
RDRE1 13, 20, 34
FltNum 34
GriFltNum 34
Health 34
Mod 34
RcdMade 34, 35
RcdStr 35
RFLO1 17, 19, 117
FltDiskm 118
FltDisPrc 118
FltZ 117
Health 117
Mod 117
RREC1 16, 19, 116
AutoRecSt 116
Health 116
Mod 116
Op 116
RSYN1 16, 21, 121
AngInd 122
DifAngCIc 123
DifHzCIc 123
DifVCIc 123
Health 121
HzInd 122
SIPROTEC, 7SJ66, IEC61850 MAPPING 144
C53000-L2640-C554-2, Edition 12.2017