0% found this document useful (0 votes)
873 views16 pages

CB 200 Extinguishing Control Panel Installation and Commissioning Manual

The document is an installation and commissioning manual for the CB200e conventional extinguishing control panel. It contains sections on cabinet installation, panel check procedures, panel configuration, commissioning, technical specifications, additional documentation, access code functions, and DIL switch configuration. The introduction provides an exploded view of the panel components and explains the panel display and indicator lights.

Uploaded by

Nikos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
873 views16 pages

CB 200 Extinguishing Control Panel Installation and Commissioning Manual

The document is an installation and commissioning manual for the CB200e conventional extinguishing control panel. It contains sections on cabinet installation, panel check procedures, panel configuration, commissioning, technical specifications, additional documentation, access code functions, and DIL switch configuration. The introduction provides an exploded view of the panel components and explains the panel display and indicator lights.

Uploaded by

Nikos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

Doc: CB200e Installation Guide Rev.

0 Written By: RP Checked By: AJC Approved By: JBJ Date: 06/05/05

CB200e Extinguishing Control Panel


Installation and Commissioning Manual
Contents

1. Introduction ............................................................................................................1
2. Cabinet Installation ................................................................................................5
3. Panel Check...........................................................................................................7
4. Panel Configuration ...............................................................................................9
5. Commissioning.....................................................................................................10
6. Technical Specifications ......................................................................................15
7. Additional Available Documentation.....................................................................15
8. ACCESS CODE Functions ..................................................................................16
9. DIL switch Configuration ......................................................................................16

1. Introduction
e
Thank you for purchasing the CB200 conventional extinguishing control panel. This
panel is manufactured to meet the highest standards of reliability and will provide
the user with many years of reliable service.

NOTE: You must read and understand this manual before commencing
installation. Failure to correctly follow the instructions given in this
manual could result in damage to the control panel and/or accidental
discharge of extinguishant.

USER CONTROLS ACCESS CODE:


514
ENGINEER’S ACCESS CODE:
5324
SEE SECTION 8. ACCESS CODE Functions FOR DETAILS

Page 1 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

1.1 A Guided Tour of the Product

1.1.1 Exploded View

Company Logo Terminal Cover


Fixing Screw Pre-formed Keyhole for
Semi-flush upper fixing
Bezel Removeable
Gland Plate
PCB Support
with knockouts

PCB
Terminals

Display
Cover

User Battery Space


LED
Controls Transformer
Indicators
Mains Terminal
Red
Block
Battery
Lead

2 x 12V 2.1Ah
Black
SLA Batteries
Battery
Lead
Blue
Battery
Lead

Figure 1 – Exploded View

Page 2 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

1.1.2 Panel Display and Explanatory Notes

Pulses when Manual


Release is activated,
Pulses when Abort steady once alarms
Input is activated are silenced
Zone Fire LEDs, flash
when the zone is in fire, Pulses for a fault on
Zone Fault LEDs, flash steady once alarms the Manual Release
for zone fault or device have been silenced Abort Fault LED Input, steady when
removed, steady for pulses for any fault isolated
zone isolated on the Abort Input

Flashes for a fault


on any of the 3 FIRE EXTINGUISHANT
alarm circuits
ABORT MANUAL AUTO ACTUATOR TIMER
RELEASE OPERATED ON
Toggles the panel
mode between FAULT FAULT FAULT MANUAL FAULT

Auto & Manual


Z1 Z2 AUX Pulses when
delay timer is
N

AUTO/
O

Slide-in insert for running


TI

MANUAL
CA

zone location text ALARM PROC EARTH


FAULT FAULT FAULT
LO

Pulses for a fault


NE

on the Actuator
ZO

SUPPLY BATT ONE MAN Circuit, Steady


HEALTHY FAULT TEST
SILENCE
RESET
when isolated.
ALARMS/ EVACUATE ISOLATE ACCESS
SYSTEM CONTROLS
BUZZER
ACTIVE Illuminates when
1 2 3 4 5 Actuator circuit is
Flashes when energised
an Earth fault
is detected Auto & Manual
LEDs illuminate to
Press to Silence Press to Reset Press to Press to Flashes when show Auto mode
the Alarms the panel after Flashes when
activate activate Panel is in or Manual mode
during a fire a fire alarm. a Battery fault
circuit isolate code entry One-man-Test
condition. Press to test is detected
mode mode mode
Press to silence the LEDs in Press to
the buzzer quiescent activate alarm Illuminates when Illuminates Flashes when a
during a fault mode. circuits 1 & 2. both the Mains when controls processor fault
condition. supply and Battery are enabled occurs
supply are present

Figure 2 – Display Layout

Page 3 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

1.1.3 Typical Terminal Wiring Schematic

SOLENOID
COIL

3K9 Resistor
End-Of-Line
SOLENOID Device
- + 22µF 22µF 22µF
C1565
Capacitor Capacitor Capacitor
Solenoid Polarity
1N4002 - + End-Of-Line End-Of-Line End-Of-Line
& Suppression
Device Device Device
board mounted
near to solenoid - +

3K9 1A 2A MANUAL CALL 1A 2A


12V

+
-
- - - MANUAL CALL
+ +POINT OR +
POINT WITH
5V SWITCH WITH 680R
BATTERY
Transorb 1N4002 - + - + - + 680R - + RESISTOR
1 2 RESISTOR 1 2

+ DETECTOR 12V
- + ABORT BASE WITH BATTERY

-
PANEL SWITCH - OPTIONAL
ZONE 2 & AUX.
WITH 680R SCHOTTKY
ALARMS 2 & 3 RESISTOR ZONE SAME + DIODE
SAME AS ALARM 1 AS ZONE 1

SECONDARY EARTH LINK FOR


AUX FAULT AUX FIRE ACTUATOR ALARM CIRCUITS ABORT MAN.REL. AUX.ZONE ZONE 2 ZONE 1 AUX 24V AC IN . BUZZER
N/O P N/C N/O P N/C ACT- ACT+ AL3- AL3+ AL2- AL2+ AL1- AL1+ INH- INH+ MR- MR+ Z3- Z3+ Z2- Z2+ Z1- Z1+ 24V 0V BAT- BAT+ ENABLE
~ ~ .
ON
1234

Immed
TBIT2
TBIT1
TBIT0

3K9

ALTERNATIVE WIRING SOLENOID


ARRANGEMENT FOR COIL
SOLENOID. L E N
1N4002
NOTE: THIS METHOD DOES 230V AC 50Hz
NOT MONITOR THE COIL
FOR OPEN CIRCUIT.
1N4002 5A MAINS 230V AC
SUPPLY TRANSFORMER

- +
TO PANEL

Figure 3 – Wiring Schematic


Notes:
The C1565 Solenoid Polarity & Suppression Board is not supplied with the panel and
can be ordered as a separate item. It allows the solenoid coil to be monitored for open
circuit faults. It contains all the components necessary for suppression of the coil,
polarisation of the coil and the end-of-line resistor.
An alternative monitoring arrangement is shown in the above diagram but this does
not monitor the solenoid coil for open circuit fault. (Note: 1N4002 diodes are not
supplied with the panel.)

Page 4 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

2. Cabinet Installation
WARNING: Read this section completely before commencing installation.
Prior to commencing installation of the control panel, ensure that adequate
precautions are taken to prevent damage to the sensitive electronic
components on the control board due to electrostatic discharge. You should
discharge any static electricity you may have accumulated by touching a
convenient earthed object such as an unpainted copper radiator pipe. You
should repeat the process at regular intervals during the installation process,
especially if you are required to walk over carpets.
The panel must be located in a clean, dry position, which is not subject to
shock or vibration and at least 2 metres away from pager systems or any other
radio transmitting equipment. The operating temperature range is 0ºC to 40ºC;
maximum humidity is 95%.

IMPORTANT NOTES ON SEALED LEAD ACID BATTERIES:


DANGER: Batteries are electrically live at all times, take great care never to short circuit the
battery terminals.
WARNING: Batteries are often heavy; take care when lifting and transporting batteries. For
weights above 24 Kg, lifting aids should be used.
DANGER: DO NOT attempt to remove the battery lid or tamper with the internal workings of
the battery. Electrolyte is a highly corrosive substance, and presents significant
danger to yourself and to anything else it touches. In case of accidental skin or
eye contact, flush the affected area with plenty of clean, fresh water and seek
immediate medical attention.
Valve Regulated Lead Acid (VRLA) batteries are “low maintenance”, requiring no
electrolyte top-up or measurement of specific gravity.
WARNING: Only clean the battery case with a cloth that has been soaked or dampened with
distilled water. Do not use organic solvents (such as petrol, paint thinner,
benzene or mineral spirits) or other materials that can substantially weaken the
case. Do not use a dry cloth as this will generate static electricity, which in turn
may lead to an explosion.
WARNING: Avoid operating temperatures outside the range of -15C/5F to +50°C/122°F for
float/standby applications.
The recommended normal operating temperature is 20°C.
HIGH TEMPERATURE will reduce battery service life. In extreme cases this
can cause Thermal Runaway, resulting in high oxygen/hydrogen gas production
and battery swelling. Batteries are irrecoverable from this condition and should
be replaced.
LOW TEMPERATURE will prolong battery life but reduce output capacity.
DANGER: Do not incinerate batteries. If placed in a fire, the batteries may rupture, with the
potential to release hazardous gases and electrolyte. VRLA batteries contain
substances harmful to the environment.
Exhausted batteries must be recycled. Return them to the battery manufacturer or
take them to your Council waste disposal site for appropriate disposal.

ELECTRICAL SAFETY:
The volt-free relay contacts provided within the panel must not be used to directly switch
any voltage that exceeds 50VAC or 75VDC. (Please also refer to relay rating data).
This equipment requires a 230V AC supply. All installation work should be carried out in
accordance with the recommendations of BS5839 Part 1 and the current edition of the
IEE regulations by suitably qualified and trained personnel.

THIS PANEL MUST BE EARTHED

Page 5 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

2.1 Installation Sequence


1. Unpack the control panel and locate the small plastic bag containing the
following installation spares:
i) End of line capacitors (22F 35/40 volts – for Zone circuits, Manual
Release & Abort Input only)
ii) End of line resistors (3k9 Ohms – for alarm & actuator circuits only)
iii) Spare mains fuse
iv) A set of battery leads (RED - positive, Black – negative, Blue - jumper
lead)
2. Remove the Terminal Cover and Display Cover by means of the fixing screws.
Place both covers carefully to one side (ideally inside the original packing box).
Note that the A.C. secondary leads from the mains transformer and the Earth
lead from the mains terminal block will need to be disconnected from the
terminals on the control board in order to remove the display cover with the
attached control board.
3. Position the empty enclosure against the wall, mark and fix using fixings suitable
for the weight.
4. Connect the 230V AC mains cable to the mains terminal block provided inside
the enclosure, ensuring that the mains supply is isolated at the source. See
diagram below for cable routing recommendations. The cable must be secured
via the Cable Tie (supplied).
The cable must be protected by a 5A fuse at the source.

Alternative
Mains Cable
Route
Recommended
Mains Cable
Route

230V AC 50Hz
Cable Tie to
5A MAINS secure
SUPPLY Mains Cable

L E N

Page 6 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

NOTE 1 – MAINS ISOLATION:


An appropriate lockable double-pole disconnect device shall be
provided as part of the building installation.
NOTE 2 – MAINS CABLES:
Use only mains cable compliant to BS6004, BS6500, or equivalent,
within the following limits:
Cable Diameter Conductor Diameter
Minimum Dimensions 4.0mm 1.0mm (0.8mm2)
Maximum Dimensions 8.0mm 2.25mm (4.0mm2)

5. Gland the installation wiring into the enclosure using the cable entry holes
provided. Leave the knock-outs or plastic protection plugs in any unused holes.
6. Fill in the zone identification card (supplied) and insert it into the slot in the rear
of the display cover. The zone text should be clearly visible through the display
window.
7. Fit batteries into the space provided. Only connect the blue battery link, do not
connect the red and black battery leads to the batteries at this time.
8. Re-attach the display cover, ensuring that the A.C. secondary leads from the
mains transformer and the earth lead from the mains terminal block pass
through the cable channel to the upper section of the enclosure.
9. Re-connect the A.C. secondary leads to the “AC IN” terminals. Re-connect the
earth lead from the mains terminal block to the “EARTH” terminal. Ensure that
the earth lead to the gland plate is re-connected correctly.

3. Panel Check
1. Ensure the mains supply has been inspected and tested in line with BS5839
Part 1 and the current IEE regulations and that the system is correctly earthed.
2. Leave all resistors and capacitors in the terminals and switch on the 230 volts
AC mains only. The control panel should react as follows:
i) The GREEN “SUPPLY HEALTHY” LED illuminates
ii) The GREEN “CONTROLS ACTIVE” LED illuminates
iii) After 5 seconds the yellow “AUTO” LED illuminates
3. No other indications should be present at this time. If there are, identify the fault
and rectify it by checking that the end-of-line devices are connected correctly in
the terminals on each zone, manual release input, abort input, alarm circuit,
actuator circuit and battery terminals. Also check that all four DIL switches are in
the OFF position.
4. Remove the resistor from the battery terminals on the control panel. The panel
should react as follows:
i) The AMBER “BATT FAULT” LED illuminates
ii) The control panel internal buzzer pulses
iii) The Fault Relay output operates and the GREEN “SUPPLY
HEALTHY” LED is extinguished
5. Connect the Red battery lead to the [BAT+] terminal on the panel and connect
the Black battery lead to the [BAT-] terminal on the panel.

Page 7 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

6. Connect the shrouded end of the Red battery lead to the Red (+) terminal on
one battery and connect the shrouded end of the Black battery lead to the Black
(-) terminal on the other battery. The control panel should react as follows:
i) The buzzer silences and the fault indications are extinguished
ii) The GREEN “SUPPLY HEALTHY” LED re-illuminates
7. Press and hold the “RESET SYSTEM” button (also operates as Test Lamps) on
the display and check that the control panel reacts as follows:
i) All LEDs on the display illuminate whilst the button is operated
ii) The internal buzzer sounds
8. Release the “RESET SYSTEM” button and observe that the panel returns to it’s
previous state.
9. Press the “EVACUATE” button on the display and check that the control panel
reacts as follows:
i) The panel buzzer operates
ii) 28VDC can be measured across the terminals of Alarm circuits 1 & 2.
10. Press the “EVACUATE” button again to return the panel to normal.
11. Switch off the 230V AC supply to the control panel and check that the control
panel reacts as follows:
i) The “SUPPLY HEALTHY” LED flashes
ii) The internal buzzer in the control panel sounds
iii) The Fault Relay output operates
12. Re-instate the 230V AC supply and check that the panel returns to normal.
13. Check that the zone detection circuits are monitoring the wiring for faults
correctly, as follows:
i) Open circuit (simulate a break in the zone circuit wiring) – disconnect
the zone capacitor
ii) Short circuit (simulate a short between cores) – insert a wire link into
the zone terminals (do not reconnect the capacitor at this stage, as a
short circuit across the capacitor will generate an electrical spark.)
iii) Remove the wire link and reconnect the capacitor to return the panel
to normal.
Simulate the faults described above and check that the control panel reacts as
follows:
i) The appropriate AMBER “FAULT” LED pulses
ii) The internal buzzer on the control panel sounds
iii) The fault relay operates
14. Repeat step 13 for the Manual Release circuit.
15. Repeat step 13 for the Abort Input circuit. Note that the Abort Active LED will
also pulse and remain pulsing until the RESET SYSTEM button is pressed.
16. Check that alarm circuits 1, 2 & 3 and the actuator circuit are monitoring the
wiring for faults correctly, as follows:
i) Open circuit (simulate a break in the circuit wiring) – remove the end-
of-line resistor
ii) Short circuit (simulate a short between cores) – replace the resistor &
short circuit the alarm circuit terminals

Page 8 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

Simulate the faults described above for each circuit in turn and check that the
control panel reacts as follows:
i) The “Alarm Fault” or “Actuator Fault” LED illuminates
ii) The internal buzzer in the control panel sounds
iii) The fault relay operates

4. Panel Configuration
WARNING: The “LINK FOR BUZZER ENABLE” jumper link, located at the top right-
hand corner of the control board, is a non-monitored buzzer
disable/enable facility. It is provided ONLY to allow the commissioning
engineer to disable the internal buzzer should the engineer find this
necessary during commissioning. DO NOT remove this link unless there
are unavoidable circumstances, and ALWAYS check that it is in place
before closing the cover.

4.1 The One-Man-Test Facility


Engineer’s Access Code: 5-3-2-4.
1. Enter the engineer’s access code (5324), the “Controls Active” LED will flash. To
exit engineer’s mode, press 5. If no controls are operated for 10 seconds the
panel will automatically exit engineer’s mode.
2. One-man-Test Mode – with the engineer’s controls active, press button 1 to
enable One-Man-Test. Check that the control panel reacts as follows:
i) The “ONE MAN TEST” LED flashes
ii) The fault buzzer sounds intermittently

Press button 1 again to exit the One-Man-Test mode.


NOTE:The control panel will automatically de-select the one-man-test
mode after 10 minutes of inactivity.

4.2 Earth Fault Enable/Disable


With engineer’s controls active, press button 2 to enable/disable earth fault
monitoring. In engineer’s mode, the “EARTH FAULT” LED will illuminate when earth
fault monitoring is enabled (factory default).

4.3 Processor Fault Indication


If the processor on the control board fails to function correctly, the processor will be
re-started automatically and the “PROC FAULT” LED will pulse. To clear the LED
indication, first enter the engineer’s code (5324) and then press 3.

4.4 Zone Circuit, Manual Release Circuit & Actuator Circuit Isolation
Enter the User access code (514), the “Controls Active” LED will illuminate, then
follow the instructions below. Isolated circuits are indicated by a steady amber fault
LED.
i) With controls active, press “ISOLATE”. The Zone 1 Fault LED will pulse
rapidly every 2 seconds (flashing cursor mode).
ii) Press “ACCESS” (button 5) to move the cursor to the fault LED of the
required circuit.
iii) Press “ISOLATE” to isolate or de-isolate the required circuit.
iv) Repeat (ii) and (iii) for any further circuits.

Page 9 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

v) Press “RESET” to clear the flashing cursor mode.


Each Isolated circuit will be indicated by illuminating the corresponding fault LED
steady.

5. Commissioning

5.1 Introduction
The following equipment should be available where possible to minimise the
commissioning period:
i) VHF/UHF Two-Way Radio System (for two engineers)
ii) Multi-meter capable of measuring voltages and resistances

5.2 Checklist
Before commissioning, the engineer should check the following:
i) All field wiring has been inspected and tested in accordance with
manufacturer’s wiring recommendations, BS5839 part 1 and current IEE
wiring regulations.
ii) All field cables are routed into the control panel cabinet through suitable
cable glands.
iii) Detector bases are linked through but detector heads are not fitted (place a
link across Schottky diodes if fitted). Any devices with electronic components
are not fitted. Terminations to devices with electronic components should be
linked through to maintain cable continuity.
iv) Manual Call points are not connected but the cable is linked through to
maintain continuity.
v) No end-of-line devices are fitted.

The following information should be available to the commissioning team:


i) Zone detection layout drawings
ii) Wiring schematic diagram
iii) Installation manuals for all equipment connected to the system

Tracing wiring faults on long circuits that are routed through risers etc. can be
difficult without prior knowledge of the wiring route.
It is recommended that the electrical installer is available until basic wiring integrity is
proven. A minimum of 2 persons (e.g. engineer & mate) is recommended for
efficient commissioning.

5.3 An Overview of the Commissioning Procedure


The approach to be used when commissioning a fire alarm system is to check each
circuit and function in turn to ensure correct operation of the entire system. In this
way any faults may be located quickly and accurately. The general procedure is as
follows:
1. Alarm circuits should be checked first. The operation of each sounder should be
checked for correct audibility as specified in BS5839 pt 1, using the panel’s
“EVACUATE” facility.
2. Detection circuits should be commissioned next. The requirement is to verify the
correct operation of each device and correct indication at the control panel.
3. Finally, any auxiliary circuits should be tested.

Page 10 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

WARNING: Before testing, the engineer must be fully aware of the operation of
all devices fitted to the actuator circuit and auxiliary circuits and of
the consequences of their operation. It is recommended that the
solenoid not be connected during commissioning in order to avoid
accidental discharge of the extinguishing agent. A 24VDC relay
may be used in place of the solenoid in order to verify correct
operation of the actuator circuit.

5.4 Pre-Commissioning Wiring Check


NOTE: This pre-commissioning wiring check procedure should be followed in
order to test all wiring prior to specific commissioning of any
detection, alarm and auxiliary circuits.
The following assumes that the control panel has been installed in accordance with
the installation procedure and is powered with only the “Supply Healthy” and
“Controls Active” LEDs illuminated. Do not connect field wiring at this stage.
1. Ensure that no devices are connected to the zone circuits, manual release
circuit, abort input, actuator circuit and alarm circuits but the cables are linked
through at the device locations to achieve a continuous circuit.
2. Ensure that resistance of all cables to earth and between cores is more than
1M. Check the following:
i) Positive to earth resistance is greater than 1M
ii) Negative to earth resistance is greater than 1M
iii) Positive to negative resistance is greater than 1M
iv) Connect a wire link as the end-of-line device on each of the zone,
manual release, abort input, actuator and alarm circuits. At the panel
end, measure the resistance across the positive & negative ends of the
cables for each of the circuits; ensuring the value does not exceed 20.
Remember to remove the wire links after the tests.
3. Correct polarity throughout all circuits must be maintained. Rectify any faults.
4. All bells/sounders, detector heads and call points should now be connected and
the correct end-of-line devices fitted. Use the spare end-of-line devices supplied
and leave the EOL devices in the panel terminals at this stage. Remember to
remove any links fitted to detector bases. Be very careful to maintain correct
polarity at each device.
5. For the actuator circuit, use a 24VDC relay in place of the solenoid and either fit
a C1565 polarity & suppression board (not supplied) or fit diodes (not supplied)
and a resistor as shown in Figure 3 – Wiring Schematic.

5.5 Alarm and Actuator Circuits


After completion of the pre-commissioning wiring check, the following procedure
should be followed:
1. Remove the resistor from the first alarm circuit terminal and connect the first
alarm circuit wiring to the terminals, observing correct polarity. Check that any
alarm fault indications clear after a few seconds.
2. Enter the access code to enable the controls and press the “Evacuate” button.
Check that all sounders connected to the alarm circuit operate.
3. Press the “Evacuate” button again and check that the alarms silence.
4. Repeat steps 1 to 3 for the second alarm circuit.

Page 11 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

5. Repeat step 1 for alarm circuit 3. This alarm circuit does not respond to the
Evacuate button and can be checked as part of the zone commissioning
process.
6. Repeat step 1 for the Actuator circuit. Operation of the Actuator circuit can be
checked as part of the zone commissioning process.

5.6 Zone Circuits


NOTE: Remember to enable the controls using the access code before using
any of the controls.
1. Configure the Actuator Delay time as required via the DIL switches as shown in
section 9.
2. Remove the capacitor from the zone 1 terminals and connect the zone 1 circuit
cables to the zone 1 terminals, observing the correct polarity. Check that any
zone 1 fault indications clear after a few seconds.
3. Check that the zone detection circuits are monitoring the wiring for faults
correctly by doing the following:
i) Open circuit – disconnect the EOL capacitor
ii) Short circuit – short circuit the EOL capacitor
Return the EOL capacitor to normal and check that the panel returns to normal.
4. Operate the first manual call point (BGU) on the zone and check the following:
i) The zone 1 fire LEDs pulse
ii) The internal buzzer sounds
iii) Alarm circuits 1 & 2 sound
iv) The auxiliary fire relay operates
Reset the manual call point to its normal condition. Press the “Silence Alarms”
button and then the “Reset System” button on the panel and check that the
control panel returns to the normal state.
5. Repeat step 4 for all manual call points on the zone.
6. Activate the first detector on the zone and check the following:
i) The zone 1 fire LEDs pulse
ii) The internal buzzer sounds
iii) The alarms sound
iv) The auxiliary fire relay operates
v) The LED on the detector illuminates
Press the “Silence Alarms” button and then the “Reset System” button on the
panel and check that the control panel returns to the normal state.
7. Repeat step 6 for all detectors on the zone.
8. If line continuity diodes are NOT fitted to detector bases then skip to step 11.
9. Remove the first detector from zone 1 and observe the following:
i) The appropriate amber zone fault LED illuminates
ii) The internal buzzer sounds
iii) The fault relay operates
Operate a manual call point between the detector that has been removed and
the EOL capacitor. Check that the panel reacts as described above for a fire
condition. Refit the detector, reset the manual call point, press the “Silence

Page 12 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

Alarms” button and then the “Reset System” button on the panel and check that
the control panel returns to the normal state.
10. Repeat step 9 for all detectors on the zone.
11. Repeat steps 2 to 10 for zone 2 & the Auxiliary zone until all three zones are
commissioned.
12. Any faults that are found must be traced and rectified before proceeding.

5.7 Manual Release Circuit


NOTE: Remember to enable the controls using the access code before using
any of the controls.
1. Remove the capacitor from the Manual Release terminals and connect the
Manual Release circuit cables to the Manual Release terminals, observing the
correct polarity. Check that any Manual Release fault indications clear after a
few seconds.
2. Check that the circuit is monitoring the wiring for faults correctly by doing the
following:
i) Open circuit – disconnect the EOL capacitor
ii) Short circuit – short circuit the EOL capacitor
Return the EOL capacitor to normal and check that the panel returns to normal.
3. Operate the first manual release point and check the following:
i) The Manual Release Operated LED pulses
ii) The internal buzzer sounds
iii) Alarm circuit 3 pulses (to indicate discharge timer running)
iv) The Timer On LED pulses (to indicate discharge timer running)
v) The auxiliary fire relay operates
After the delay timer ends, check the following:
i) The Timer On LED is OFF
ii) The Actuator Operated LED is ON
iii) Alarm circuit 3 changes to continuous
iv) The Actuator circuit is energised
Reset the manual release point to its normal condition. Press the “Silence
Alarms” button and then the “Reset System” button on the panel and check that
the control panel returns to the normal state.
4. Repeat step 3 for all manual release points on the circuit.

5.8 Emergency Abort Input


NOTE: Remember to enable the controls using the access code before using
any of the controls.
1. Remove the capacitor from the Abort input terminals and connect the Abort
circuit cables to the Abort input terminals, observing the correct polarity. The
Abort Active LED will pulse and the Abort Fault LED will pulse. Press the RESET
button to clear the indication.
2. Check that the circuit is monitoring the wiring for faults correctly by doing the
following:
i) Open circuit – disconnect the EOL capacitor
ii) Short circuit – short circuit the EOL capacitor

Page 13 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

For each of the above faults check that the panel reacts as follows:
i) The Abort Operated LED pulses
ii) The Abort Fault LED pulses
iii) The internal buzzer sounds intermittently
iv) The auxiliary fault relay operates
For each of the above faults, return the EOL capacitor to normal, press the
RESET button and check that the panel returns to normal.
3. Operate the first Emergency Abort switch and check the following:
i) The Abort Operated LED pulses
ii) The internal buzzer sounds intermittently
iii) The auxiliary fault relay operates
Reset the Emergency Abort switch to its normal condition, press the RESET
button and check that the control panel returns to the normal state.
4. Repeat step 3 for all Emergency Abort switches on the circuit.

5.9 Actuator & Auxiliary Circuits


Once the above commissioning procedure has been successfully completed,
remove any test equipment from the end of the Actuator Circuit (e.g. 24VDC relay
used during commissioning). Ensure that the Actuator/Solenoid is mechanically
isolated before connecting the Solenoid to the Actuator circuit and check that any
fault indications clear after a few seconds. If any fault indications remain then trace
the fault and rectify.
All auxiliary circuits or equipment that is not supplied as a standard part of the fire
alarm panel is the responsibility of the installer and must be tested for safe and
correct operation by the commissioning engineer.
After completion of the above commissioning procedure, the panel should be left on
soak test for a minimum of 48 hours WITH THE ACTUATOR/SOLENOID
MECHANICALLY ISOLATED and the system status set to MANUAL.
After the panel has been successfully soak-tested, check that the DIL switches are
correctly set (see section 9. DIL switch Configuration), de-isolate the
ACTUATOR/SOLENOID and set the system status to AUTO. The panel is now fully
operational.

Page 14 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

6. Technical Specifications
Maximum field equipment load: 800mA
Auxiliary 24VDC output 250mA
Mains failed current consumption: 40mA @24VDC
Integral battery charger output: 500mA @27.5VDC
Common fire relay: Volt-free contacts - 1A, 30V DC max.
Common fault relay: Volt-free contacts - 1A, 30V DC max.
Alarm circuit output: 3 at 500mA each @28VDC
Actuator circuit output: 1 at 500mA @28VDC
Battery size: 2 x 12V 2.1AH sealed lead acid
Weight (excluding batteries): 2.4kg

NOTE:
The total available current for field devices is 800mA at 28VDC. This current
must be shared between the auxiliary 24VDC supply, the Actuator circuit and
the three alarm circuits such that the total current drain across the five circuits
does not exceed 800mA.
WARNING:
A fuse protects the internal mains transformer; always replace this with the
correct type and rating:

T1AH 250V 20mm fuse, 1A, HBC, Anti-surge, approved to BS EN 60127


or equivalent.

7. Additional Available Documentation


e
CB200 Application Guide
e
CB200 User Instructions

Page 15 of 16
Doc: CB200e Installation Guide Rev.0 Written By: RP Checked By: AJC Date: 06/05/05

8. ACCESS CODE Functions


The functions available at the USER and ENGINEER access levels are listed below.
USER ACCESS CODE: 5 1 4
USER CONTROLS:
1. Silence Buzzer
2. Silence Alarms
3. Manual Evacuate
4. System Reset
5. Zone Isolate/De-isolate
6. Manual Release Isolate/De-isolate
7. Actuator Isolate/De-isolate
8. System Auto/Manual
ENGINEER’S ACCESS CODE: 5 3 2 4
1. One-Man-Test ON/OFF (button 1)
2. Earth Fault Monitoring Enable/Disable (button 2)
3. Processor Fault Reset (button 3)

9. DIL switch Configuration


The DIL switches allow configuration of the Delay and Manual Release options.
DELAY DIL SWITCH
TIME
(Seconds) TBIT2 TBIT1 TBIT0
ON
1234

Immed
TBIT2
0 OFF OFF OFF TBIT1
TBIT0
ON
1234

Immed
TBIT2
10 OFF OFF ON TBIT1
TBIT0
ON
1234

Immed
TBIT2
20 OFF ON OFF TBIT1
TBIT0
ON
1234

Immed
TBIT2
30 OFF ON ON TBIT1
TBIT0
ON
1234

Immed
TBIT2
40 ON OFF OFF TBIT1
TBIT0
ON
1234

Immed
TBIT2
50 ON OFF ON TBIT1
TBIT0
ON
1234

Immed
TBIT2
ON ON OFF TBIT1
TBIT0
60
ON
1234

Immed
TBIT2
ON ON ON TBIT1
TBIT0

The DIL switch marked “Immed” allows the Manual Release input to either
operate the actuator after the delay (DIL switch OFF) or immediately with
no delay (DIL switch ON).

Page 16 of 16

You might also like