Kidde Horn Strobe
Kidde Horn Strobe
FEATURES
• Sleek Modern Aesthetics • Universal Mounting Base (Patented)
• Finger Slide Switches • Ceiling and Wall, Mounts to 5 Backbox Types
• Voltage Test Points • Environmentally Friendly
• Multiple Voltages • Low Current Draw
• 3 Audible Settings: 90, 95, 99 dB • FM Approved
• 8 Candela Settings (Patented) • UL Listed
• Wall: 15/15_75/30/75/95/110/135/185 • ULC Listed
• Ceiling: 15/30/60/75/95/115/150/177 • California State Fire Marshal (CSFM) Approved
DESCRIPTION
The Exceder Series notification appliances are compati- Wall models provide an optional locking screw for extra
ble with all Kidde suppression control panels and offer secure installation, while the ceiling models provide a capti-
modern designs with pleasing aesthetics and low cost of vated screw to prevent the screw from falling during instal-
ownership. lation.
The Exceder Series devices incorporate high reliability
COMPATIBILITY AND REQUIREMENTS
and high efficiency optics to minimize current draw allow-
ing for a greater number of appliances on the notification- – Synchronize using the Sync Modules or panels
appliance circuit. All strobe models feature an industry with built-in Patented Sync Protocol
first of 8 candela settings on a single appliance. Audible – Compatible with UL “Regulated Voltage” using
models feature 3 sound settings (90, 95, 99 dB). All filtered VDC or unfiltered VRMS input voltage
switches to change settings can be set without the use of
a tool and are located behind the appliance to prevent – Strobes produce 1 flash per second over the
tampering. Wall models feature voltage test points to take “Regulated Voltage” range
readings with a voltage meter for troubleshooting and
AHJ inspection.
An additional included benefit is the Universal Mounting
Base (UMB). The UMB allows retrofitting for previous
generation of Wheelock notification appliances. The UMB
can be pre-wired to allow full testing of circuit wiring
before the appliance is installed. It comes complete with a
Contact Cover for protection against dirt, dust, paint and
damage to the contacts. The Contact Cover also acts as a
shunting device to allow pre-wire testing for common
wiring issues. The Contact Cover is polarized to prevent it
from being installed incorrectly and prevents the
appliance from being installed while it is on the UMB.
When the Contact Cover is removed, the circuit will show
an open until the appliance is installed.
PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY
BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. CONTACT KIDDE FIRE SYSTEMS FOR
THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE
INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,
WARNING INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH
COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
GENERAL NOTES:
• Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”.
• All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
• Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range
of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%) UL 464 (85% UL 1971).
• Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only).
Strobe Rating per UL Standard 1971
UL Max Current*
24 VDC / 24 FWR 12 VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Range VDC
ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140
STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110
-2-
SPECIFICATIONS & ORDERING INFORMATION
All Exceder Series of notification appliances meet the following requirements:
• Can be powered by 12 or 24 VDC
• Can synchronize with SM, DSM, or SD-6 and PS-8 power supplies
• Uses the Universal Mounting Base
• In the case of any model including a strobe, can be set to the following candela: 15, 15-75, 30, 75, 95, 110, 135, 185
-3-
ARCHITECTS & ENGINEERS SPECIFICATIONS