Tap Changr
Tap Changr
V1/V2= N1/N2
V2=N2/N1×V1
From the above equation
by altering the turn ratio
to suitable values the
secondary voltage can be
adjusted desired level.
Lets – N1=2750,
N2=100, turn ratio=
N1/N2=2750/100=27.5
Tap
selector
Motor drive unit (MDU)- This unit has got a
motor diver and other necessary controls.
Motor charges the spring to rapidly perform
the switching. Power is transferred via shaft &
gear mechanism.
Diverter switch /Oil compartment- This has
the diverter switch, which has moving and
fixed contacts. It is filled with oil or SF6 gas
to avoid the sparking & quenching during
opening and closing of the contacts.
Tap selector- It has different tap
combinations as specified by the customer
requirements and different standards.
Due to opening closing of contacts the sparks
produce and the oil degrades over the time. The oil
test & analysis needs to be done in lab at regular
interval
The contacts wear over the time after number of
operations.
The oil seals damage over the time and leakage
happens. Maintaining the oil level is must. For
condition monitoring its must to check for oil leak
and level regularly.
Oil dripping is dangerous for environment as well.
OLTC includes a lot of gear, spring and mechanical
parts which have a usual wear and tear, that need to
be taken care as an when required.
Vacuum type OLTC use the vacuum interrupters
which has some advantages over oil / SF6.
It is hermetically sealed and has no interaction
with surrounding medium despite the arc.
Contacts wear is lower than OIL/SF6.
No aging or quenching medium is required.
Its more environment friendly.
Vacuum interrupters perform up to 600000
operation with out replacement.
Has low maintenance cost and greater reliability.
Vacuum OLTC Vacuum interrupter
A dual voltage transformer can be defined as
the one which is capable of providing two
types of voltage.
A dual voltage transformer has two windings
in primary and two other windings in
secondary.
By connecting the both windings either of
primary or secondary in series or parallel two
different voltages are produced.
From the figure two
primary windings and
two secondary
windings are
connected in series
resulting in 240 volt
input and 24 volt out
put voltage.
From the adjacent
figure the primary and
secondary windings are
connected in parallel,
resulting 120 volt
input and 12 volt out
put voltage.
There can be either
type of arrangements
as per requirement.
The details in the
adjacent figure shows
the winding arrangement
of a dual transformer. It
produces 33/7.1 and
33/11 kV voltages
according to
arrangement of winding.
The unit produces
different outputs, based
on the connections as
advised in the name plate
details.
Upon simplifying the
connection diagrams
they turn out to be series
connected winding for
33/11 kv output and
combination of series
and parallel for 33/7.1
kv output.