SUMMARY

Scope of Work
Sr. No Amount

1 HVAC 5923175

TOTAL 5,923,175.0

GSt Extra
Sl.No. Description Unit Qty Supply
Rate Amount

Supply, Installation, testing and commissioning of the


following items including loading and unloading,
shifting to location, and final testing after
commissioning to demonstrate satisfactory
performance.

Air Cooled Ceiling suspended ductable split unit -


R410A / R407C Refrigerant

The out door unit shall consist of the condenser coil,


propeller fan with IP55 motor, Compresser, HP/LP
switch all housed in a powder coated coated
casing.the unit shall be provided with Expansion
valve,liquid line strainer,catchall drier,thermostst etc,
The fan shall be selected for low noise and shall be
provided with fan guard. The unit shall be ceiling
1 suspended in balcony as shown in the drawing.

The unit shall be provided with a microprocessor


based panel housing all starters and display of status
for evaporator , compressor, condenser motors, unit
status, return air temperature and the set point
temperature shall be displayed. The microprocessor
shall have auto restart feature in case of power
failures and shall trip the condenser fan motor when
the compressor trips on low load. The
microprocessor shall be suitable for hooking to BMS .

The indoor unit shall comprise the cooling coil,


evaporator blower and cleanable filter all housed in a
powder coated sheet metal cabinet of robust
construction. Required quantities refrigerant gas and
oil shall be included for outdoor units.

i 2 TR / 800 CFM , Server Room (2W+2S) No.'s 2 55000 110000


Copper Refrigerant piping with 18G HD Copper
pipes, (Hot gas line insulated with specified thickness
nitrile rubber tubings and joints sealed with black
2 cotton tape within the AC premises).

i 1/2 " dia with 13 mm insulation Rmt 90 350 31500


ii 7/8 " dia with 19 mm insulation Rmt 90 600 54000

Control cable of OEM recommended size between


indoor and outdoor units of Ductable type with
3 necessary fixing arrangement. Rmt 90 130 11700

Dx Inverter based Hi wall units- 3 Star Rated, R410A /


R407C Referigerant

The out door unit shall consist of condenser coil,


propeller fan with IP55 motor, Inverter Compressor,
HP/LP switch all housed in a powder coated casing.
The unit shall be provided with Expansion
valve,liquid line strainer,catchall drier,thermostat etc,
The fan shall be selected for low noise and shall be
provided with fan guard. The unit shall be mounted
as per site condition with required supproting /
4 stand.

The indoor unit shall comprise of cooling coil,


evaporator blower, Voltage Stabalizer, Remote
Control and cleanable filter all housed in a powder
coated sheet metal cabinet of robust construction.
Required quantities of Refrigerant gas and oil shall be
included.

i 1 TR, 325 CFM for Surveillance Room (1 Standby) No.'s 1 34000 34000
ii 1.5 TR, 450 CFM No.'s RO
iii 2.0 TR, 650 CFM for UPS & Battery Room (2W+2S) No.'s 2 42000 84000

Copper Refrigerant piping with 18G SD Copper pipes


5 - with nitrile rubber insulation as specified.

i 1 / 2 " dia with 13 mm insulation Rmt RO


ii 1 / 4 " dia with 13 mm insulation Rmt RO
iii 3 / 8 " dia with 13 mm insulation Rmt 200 250 50000
iv 5 / 8 " dia with 13 mm insulation Rmt 200 450 90000

Control cable of OEM recommended size between


indoor and outdoor units with necessary fixing
6 arrangement. Rmt 200 130 26000

Supply & installation of single phase drain pump of 1


litre capacity suitable to be installed to collect
condensate drain from high wall & ductable units to
7 a suitable location. No.s 4 11000 44000

200 CFM, 100 pascals total static pressure circular


type inline fan consisting of backward curved
impeller which is factory matched to the
corresponding external motor and dynamically
balanced for vibration free operation for battery
8 room exhaust with necessary fixing arrangements. No. 1 11800 11800

Hydrogen sensor for the Battery room exhaust with


necessary cabling to trigger the above mentioned
9 exhaust fan No. 1 18900 18900

Variable Air Volume Boxes

Supply, Installation,Testing & commissioning of


Pressure independent networkable VAV terminals
complete with actuator, air flow transducer, remote
zone digital thermostat and step down transformer
to be included. Power will be available within 3 mt
radius. The VAV units shall be BMS compatible and
the interface for transfering all the data to the BMS
system shall be included.Installation of VAV's should
include the cone pieces in either sides of VAV with
15 mm thick open cell nitrile rubber insulation of
density 140-180 kg / m3, class-1 accoustic stuck to
the clean internal surface of the cone pieces with
good quality low VOC content adhesive of Pidlite
10 industries or equivalent.

i 0-225 Nos 0
ii 0-350 Nos 2 27500 55000
iii 0-450 Nos 3 27500 82500
iv 0-650 Nos 3 31000 93000
v 0-800 Nos 4 31000 124000
vi 0-1050 Nos 2 35000 70000
vii 0-1350 Nos 2 36000 72000
viii 0-2100 Nos 3 42000 126000
ix 0-3200 Nos 0 0
x 0-4000 Nos RO
xi 0-5000 Nos RO
xi 0-6500 Nos RO

WIRING & CONDUITING

Supply, Laying, Termination, Testing & Comissioning


11 of following cables & conduits

VAV Related Cabling

Surface laying of 2C x 1.5 Sq MM shielded ATC cable


i for VAV Looping. Rmt 400 95 38000

Surface laying of Fexible UTP CAT 5 Data Cable to


ii connect to the digital thermostat of VAV boxes. Rmt 300 185 55500

Surface laying of 3C x 1 Sq MM unshielded ATC cable


iii for VAV power cabling including flexible conduit. Rmt 111 115 12765
Surface laying of 19 mm dia PVC-FRLS conduits
iv complete with all fittings & accessories. Rmt 950 55 52250

Supplying, installing, testing and commissioning of


Differential Pressure Transmitter (0 - 500pa) for VFD
12 Control Nos 5 18900 94500

Supply, installation, testing and commissioning of


Wall mounted display device with all required
software and graphics to control and monitor all the
VAVs & VFDs. To consider 185 points for all VAV's and
20 points for all VFD's.The compatibility of protocal
of VAVs to be checked and if required necessary
interface for conversion of protocal also to be
considered. Necessary accessories including power
13 and control cabling to be included. No's 1 650000 650000
AUTO SEQUENTIAL CONTROL PANEL

Supply & installation of Auto sequential control panel


for the AC units as per ductable & split unit schedule
of critical areas i.e. 1 working + 1 stand by unit . The
14 panel should have the following features.
Provision for on/off & trip status with auto/manual
selector switch
A/C units shall be able to restart automatically after
power failure/interruption.
Automatic fault changeover
Sequential changeover of operating units every
6/8/12 hours.
Normally duty and standby units will be as per Hi
wall units schedule. If high temp is attained, all units
shall be in operation to cool down the room.
Should generate an alarm if the unit trips or the area
temperature goes beyond the set point and provision
of this alarm integration should be provided.
The Panel should be provided with provision of RS
485 port connection.

A wall mounted temperature, RH sensor display to


be fixed near to the critical room door and the same
should be connected to the panel to let know the
high wall unit which is working at any point of time. No.s 4 18500 74000

Air distribution System

Rectangular Ducting

CNC machine fabricated sheet metal ducting as per


IS standards & completely assembled in to box shape
from factory complete with TDF / TDC flanges, duct
damper, vanes, splitters, neoprone or equivalent
approved gasket. suspension arrangement using
threaded rods, slotted angle supports, anchor
fastners etc. Connection to fans shall be provided
with Canvas connections. Price should also include
duct pressure test which has to be carried out for 20
% of total duct qty. All ducts inlet and outlet to be
cleanly covered with polythene sheet in order to
15 prevent dust entry to inside surface of ducts.
i 24G , Duct Width 0 - 750 mm Sq.m 141 650 91650
ii 22G , Duct Width 751 - 1500 mm Sq.m 68 800 54400
iii 20G , Duct Width 1501 - 2250 mm Sq.m RO
iv 18G , Duct Width 2250 - 2700 mm Sq.m RO

Flat Oval Spiral Ducting

CNC machine fabricated elliptical sheet metal


ducting as per IS standards of class VIII, 120 GSM zinc
coating, pressure rating of 250pa and with collars to
16 fix grilles / diffusers.

i 24G , Duct Width 0 - 600 mm Sq.m 300 950 285000


ii 22G , Duct Width 601 - 1200 mm Sq.m 400 1100 440000
iii 20G , Duct Width 1201 - 1750 mm Sq.m RO

Transformation pieces from rectangular duct to


17 eliptical duct made out of 24 G sheets No's 11 2500 27500

Spray painting for elliptical ducts with one coat of red


oxide primer and two coats of enamel with
18 architects approved colour Sq.m 735 75 55125

Factory fabricated double skin plenum of 25mm


thick PUF panels of density 40 kg/cum, casing inside
& outside material - GI & casing inside & outside
thickness - 0.6 mm . The area indicated is the surface
19 area of the plenum. Sq.m 63 3500 220500

Preinsulated flexible ducts for connecting branch


ducts with the diffuser boxes complete with brass
circular clips at both ends etc. The insulation used
20 shall be fibre glass type of denisty 16 Kg / M3.

i dia 150 Rmt RO


ii dia 200 Rmt 5 350 1750
iii dia 250 Rmt 38 450 17100
iv dia 300 Rmt RO

Rigid round ducts fabricated out of 24G sheets to be


21 used as extension pieces at the diffuser boxes.
i dia 150 Rmt RO
ii dia 200 Rmt 3 550 1650
iii dia 250 Rmt 38 700 26600
iv dia 300 Rmt RO

Accoustic Insulation of ducting with 15mm thick


open cell nitrile rubber insulation of class-1 accoustic
140-180 Kg / M3density stuck to the clean internal
surface of the duct with good quality low VOC
22 content adhesive of Pidlite industries or equivalent. Sq.m 121 1100 133100

Accoustic Insulation of AHU room walls with 50mm


thick Fibreglass 48 Kg / M3 density fibre glass
covered with two layers of RP tissue and finished
with 26 G Aluminum perforated sheet with 70%
perforations. an overlap of 50 mm shall be provided
at all joints.GI fasteners shall be used to hold the
insulation in place. The insulation shall be fixed in a
23 24 G GI hat section frame work of 600 x 600 centres. Sq.m 76 950 72200

Thermal insulation of ducting with 9/10 mm thick,


40-60 Kg / M3 density, class 'O' rated nitrile rubber
faced with Aluminum foil 80 µ thickness,stuck to the
cleaned external duct surface with synthetic rubber
low VOC content ahdhesive of Pidlite industries or
equivalent and to be used for tail end insulation of
24 ducting. Sq.m 780 325 253500

Thermal insulation of ducting with 13 mm thick, 40-


60 Kg / M3 density, class 'O' rated nitrile rubber
faced with Aluminum foil 80 µ thickness,stuck to the
cleaned external duct surface with synthetic rubber
low VOC content ahdhesive of Pidlite industries or
equivalent and to be used for ducts routed in
25 unconditioned space. Sq.m RO
Return air cross talk attenuators -Factory fabricated Z
type made of 24G GI sheets of 300mm wide x
300mm height of 1.5m length with accoustic lining of
15mm thick open cell nitrile rubber insulation of
class-1 accoustic 140-180 Kg / M3 density stuck to
the clean internal surface of the duct with good
26 quality low VOC content adhesive.

i 300 mm w x 300 mm h x 1500 mm l No.s 10 11500 115000


ii 400 mm w x 500 mm h x 1500 mm l No.s 13 13500 175500

Extruded Aluminum powder coated continuous grill


27 with end flanges.

i 150 mm Rmt RO
ii 100 mm Rmt RO
iii 300 mm Rmt 4 2100 8400

Al.powder coated Patch Grill with end flanges


28 necessary fixing arrangements

i 500x300 No.s 14 1000 14000


ii 1100X750 No.s 1 9800 9800

Al.powder coated 2 way deflection Patch Grill with


29 end flanges necessary fixing arrangements

i 400x100 No.s 1 650 650


ii 500x100 No.s 16 650 10400
iii 600x100 No.s 2 650 1300
iv 650x100 No.s 28 650 18200
v 700x100 No.s 1 650 650
vi 700x200 No.s 4 900 3600
vii 500x300 No.s RO
viii 1100X750 No.s RO

SA Slot diffuser - 3 slot complete with end flanges,


hit and miss dampers.The price quoted shall also
30 include the plenum matching the diffuser length. Rmt 54 3000 162000
RA Slot diffuser without Hit and miss dampers. - 3
31 slot complete with end flanges. Rmt 78 1450 113100

Opposed blade collar dampers of powder coated


32 Aluminium. Sq.m 4 2800 11200

Round Supply air diffuser with damper of powder


33 coated aluminium finish with following neck size

i 305 mm dia. Nos RO


ii 350 mm dia. Nos RO
iii 355 mm dia. Nos RO

Butter fly dampers of GI construction made out of


22G sheet with lever, brass bush with spindle and
locking arrangement at the take off for the supply air
34 diffusers.

i 200 mm dia Nos RO


ii 250 mm dia Nos 38 850 32300
iii 300 mm dia Nos RO

Prefabricated diffuser boxes made out of 24G sheet


suitable for diffusers of the following neck size with
circular collar for connecting flexible duct,
suspension arrangement using anchor fasteners,
35 threaded rods etc.

i 450 x 450 mm Nos RO


ii 375 x 375 mm Nos RO
iii 300 x 300 mm Nos RO
iv 225 x 225 mm Nos RO
v 150 x 150 mm Nos RO

Supply (without diffuser box) & Return air diffusers


of powder coated Aluminium of the following neck
sizes of tegular type with outer to outer size of 600 x
600 mm. The sample shall be approved by
36 consultants / architects / clients before procurement.

i 450 x 450 mm Nos RO


ii 375 x 375 mm Nos RO
iii 300 x 300 mm Nos RO
iv 225 x 225 mm Nos RO

Supply (without diffuser box) & Return air diffusers


of powder coated Aluminium of the following neck
sizes of tegular type with outer to outer size of 450 x
450 mm. The sample shall be approved by
37 consultants / architects / clients before procurement.

i 450 x 450 mm Nos RO


ii 375 x 375 mm Nos RO
iii 300 x 300 mm Nos RO
iv 225 x 225 mm Nos RO

CBRI certified 1.5 hours rated Fire dampers


fabricated out of 16G GI complete with outer frame,
damper blades, minimum GI sleeve of 450mm length
& suitable flange for connecting to the duct. The
required step down transformer for providing power
to the fire damper and wiring shall be included. Cost
shall include the control panel to receive the input
signal from the fire alarm system and shall give an
output signal to activate the actuator to close the
38 damper. Sq.m 5 9000 45000

Actuators for the above fire dampers including the


step down transformer for the incoming power
supply to the actuator and wiring to the transformer
and the actuator. The actuator should be internally
39 mounted in sleeve. Nos 12 13000 156000

GI Volume control dampers fabricated out of 18G


complete with linkage gears of hardened plastic with
40 flanges for mounting on branch ducts. Sq.m 7 8000 56000
Non Return Damper with Frame and Blades
fabricated out of 1.6 mm thick GSS complete with
41 linkages and operating handle for branch ducts. Sq.m 0.25 9000 2250

Motorised volume control damper fabricated out of


18G GI complete with outer frame, damper blades &
suitable flange for connecting to the duct. The
required step down transformer for providing power
to the damper and wiring shall be included. Cost
shall include the control panel to receive the input
signal from the AC unit and shall give an output
42 signal to activate the actuator to open the damper. Sq.m RO

Actuators for the above volume control dampers


including the step down transformer for the
incoming power supply to the actuator and wiring to
the transformer and the actuator. The actuator
should be internally/externally mounted in sleeve as
43 per site condition.. Nos RO

Disc valve consisting of frame and disc made of high


quality GSS with powder coating and disc attached to
the frame by threaded rod. Foam gasket should be
sealed around the back of the frame to avoid any air
44 leakage.

i 150 mm dia Nos RO

Non Vision grills for the toilet doors. The grills shall
be supplied in two matching halves and shall match
the door thickness. The grills shall be powder
45 coated . Sq.M RO

46 Drain piping using water quality CPVC pipes & fittings

i 40 mm dia Rmt 10 230 2300


ii 32 mm dia Rmt 15 0
iii 25 mm dia Rmt 25 0

Total 4783140
Gr Total 5923175

Note
GSt shall be extra @185 on the above prices
Installation Remarks
Rate Amount

price is per unit . In the bOQ


2W+2S written so qty should be
4000 8000 4 Nos.Make Considered Midea
130 11700
175 15750

45 4050

2500 2500

2500 5000

130 26000
150 30000

45 9000

1500 6000

1500 1500 with forward cuveted impeller

1500 1500
3500 7000
3500 10500
3500 10500
3500 14000
4000 8000
4000 8000
5000 15000
0

35 14000

65 19500

35 3885

15 14250

2500 12500

150000 150000
4500 18000
250 35250
300 20400

250 75000
300 120000

750 8250

30 22050

450 28350

150 750
150 5700
250 750
350 13300

400 48400

350 26600

200 156000
1500 15000
1500 19500

200 800

200 2800
1500 1500

200 200
200 3200
200 400
200 5600
200 200
200 800

650 35100
300 23400

800 3200

150 5700
1200 6000

1500 18000

1500 10500
1200 300

90 900
0
0

1140035
5923175