9PX3K3U
9PX EBM 180 V
Installation
and user manual
9PX3K3U US_EN
SAFETY INSTRUCTIONS
The 9PX models that are covered in this manual are intended for installation
in an environment within 0 to 40°C, free of conductive contaminant.
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will
be required to correct the interference at his own expense.
Certification standards
• Safety: IEC/EN 62040-1 / Ed.1: 2008.
UL 1778 4th edition
• EMC: IEC/EN 62040-2 / Ed.2: 2006.
FCC part 15 Class A.
• Performance: IEC/EN 62040-3 / Ed.2.0: 2011.
• IEC 61000-4-2 (ESD): level 3.
• IEC 61000-4-3 (Radiated field): level 3.
• IEC 61000-4-4 (EFT): level 4.
• IEC 61000-4-5 (Fast transients): level 4.
• IEC 61000-4-6 (Electromagnetic field): level 3.
• IEC 61000-4-8 (Conducted magnetic field): level 4.
Special symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Page 2 9PX3K3U_EN
SAFETY INSTRUCTIONS
ENGLISH
Safety of persons
• The system has its own power source (the battery). Consequently, the power outlets may be ener-
gized even if the systems is disconnected from the AC power source. Dangerous voltage levels are
present within the system. It should be opened exclusively by qualified service personnel.
• The system must be properly grounded.
• The battery supplied with the system contains small amounts of toxic materials.
To avoid accidents, the directives listed below must be observed:
-S ervicing of batteries should be performed or supervised by personnel knowledgeable about
batteries and the required precautions.
- When replacing batteries, replace with the same type and number of batteries or battery packs.
- Do not dispose of batteries in a fire. The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
• Precautions must be taken for all handling:
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
-D etermine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if such grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).
Product safety
• The UPS connection instructions and operation described in the manual must be followed in
the indicated order.
• CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with branch circuit
overcurrent protection for : 30A rating, for 9PX3K3U models in accordance with the National
Electric Code, ANSI/NFPA 70.
The upstream circuit breaker must be easily accessible.
The unit can be disconnected from AC power source by opening this circuit breaker.
• Disconnection and overcurrent protection devices shall be provided by others for permanently
connected AC input/output circuits.
• Check that the indications on the rating plate correspond to your AC powered system and
to the actual electrical consumption of all the equipment to be connected to the system.
• For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall
be easily accessible
• Never install the system near liquids or in an excessively damp environment.
• Never let a foreign body penetrate inside the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The admissible storage temperature range is -15ºC to +50ºC.
• The system is not for use in a computer room AS DEFINED IN the standard for the Protection
of Information Technology Equipment, ANSI/NFPA 75.
Contact Eaton resellers to order a special battery kit, if needed to meet the ANSI/NFPA 75
requirement.
9PX3K3U_EN Page 3
SAFETY INSTRUCTIONS
Special precautions
• The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling operations.
• All handling operations will require at least two people (unpacking, lifting, installation in rack sys-
tem).
• Straps are provided only for unpacking manually the unit from the carton; don’t use the straps to
carry the unit around. The unit can slip from the straps during handling (risk of injury and product
damage):
- keep 12in / 30cm minimum distance between the straps
- lift the unit carefully and keep it at low height
- keep the unit horizontal during unpacking.
• Before and after the installation, if the UPS remains de-energized for a long period, the UPS must
be energized for a period of 24 hours, at least once every 6 months (for a normal storage tempera-
ture less than 25°C). This charges the battery, thus avoiding possible irreversible damage.
• During the replacement of the Battery Module, it is imperative to use the same type and number of
element as the original Battery Module provided with the UPS to maintain an identical level of
performance and safety. In case of doubt, don’t hesitate to contact your EATON representative.
• All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
There are NO USER SERVICEABLE PARTS inside the UPS.
Page 4 9PX3K3U_EN
Contents
ENGLISH
1. Introduction........................................................................................ 6
1.1 Environmental protection................................................................................................6
2. Presentation....................................................................................... 8
2.1 Standard installations......................................................................................................8
2.2 Rear panels.....................................................................................................................9
2.3 Accessories.................................................................................................................. 10
2.4 Control panel................................................................................................................. 12
2.5 LCD description............................................................................................................ 13
2.6 Display functions.......................................................................................................... 14
2.7 User settings................................................................................................................ 14
3. Installation....................................................................................... 16
3.1 Inspecting the equipment ............................................................................................ 16
3.2 Unpacking the cabinet.................................................................................................. 16
3.3 Checking the accessory kit........................................................................................... 17
3.5 Connecting the EBM(s) ................................................................................................ 19
3.6 Connecting other accessories ..................................................................................... 19
3.7 Tower installation..........................................................................................................20
3.8 Rack installation............................................................................................................21
3.9 Installation requirements..............................................................................................23
5. Operation......................................................................................... 25
5.1 UPS startup and shutdown...........................................................................................25
5.2 Operating modes..........................................................................................................26
5.3 Transferring the UPS between modes..........................................................................26
5.4 Setting High Efficiency mode.......................................................................................27
5.5 Configuring Bypass settings.........................................................................................27
5.6 Configuring battery settings.........................................................................................27
5.7 Retrieving the Event log................................................................................................28
5.8 Retrieving the Fault log.................................................................................................28
6. Communication............................................................................... 29
6.1 Communication ports...................................................................................................29
6.2 Eaton Intelligent Power Software suite........................................................................32
7. UPS maintenance............................................................................. 33
7.1 Equipment care.............................................................................................................33
7.2 Storing the equipment..................................................................................................33
7.3 When to replace batteries............................................................................................33
7.4 Replacing batteries.......................................................................................................34
7.5 Replacing the UPS equipped with a HotSwap MBP or with a PPDM..........................37
7.6 Recycling the used equipment.....................................................................................37
8. Troubleshooting............................................................................... 38
8.1 Typical alarms and faults...............................................................................................38
8.2 Silencing the alarm.......................................................................................................40
8.3 Service and support......................................................................................................40
9. Specifications................................................................................... 41
9.1 Model specifications.....................................................................................................41
10. Glossary.......................................................................................... 45
9PX3K3U_EN Page 5
1. Introduction
Thank you for selecting an EATON product to protect your electrical equipment.
The 9PX range has been designed with the utmost care.
We recommend that you take the time to read this manual to take full advantage of the many features
of your UPS (Uninterruptible Power System).
Before installing your 9PX, please read the booklet presenting the safety instructions.
Then follow the indications in this manual.
To discover the entire range of EATON products and the options available for the 9PX range,
we invite you to visit our web site at www.eaton.com/powerquality or contact your EATON representative.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
• The cardboard we use comprises over 50% of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packing materials are recyclable and bear the appropriate identification symbol 01
PET
End of life
EATON will process products at the end of their service life in compliance with local regulations.
EATON works with companies in charge of collecting and eliminating our products at the end of
their service life.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing center for electrical and
electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations
concerning batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
Page 6 9PX3K3U_EN
1. Introduction
ENGLISH
The Eaton® 9PX uninterruptible power system (UPS) protects your sensitive electronic equipment from the
most common power problems, including power failures, power sags, power surges, brownouts, line noise,
high voltage spikes, frequency variations, switching transients, and harmonic distortion.
Power outages can occur when you least expect it and power quality can be erratic. These power problems
have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware - causing
hours of lost productivity and expensive repairs.
With the Eaton 9PX, you can safely eliminate the effects of power disturbances and guard the integrity
of your equipment. Providing outstanding performance and reliability, the Eaton 9PX’s unique benefits
include:
• True online double-conversion technology with high power density, utility frequency independence, and
generator compatibility.
• ABM® technology that uses advanced battery management to increase battery service life, optimize
recharge time, and provide a warning before the end of useful battery life.
• Selectable High Efficiency mode of operation.
• Standard communication options: one RS-232 communication port, one USB communication port, and
relay output contacts.
• Optional connectivity cards with enhanced communication capabilities.
• Extended runtime with up to twelve Extended Battery Modules (EBMs) per UPS.
• Firmware that is easily upgradable without a service call.
• Remote On/Off control through Remote On/Off (ROO) and Remote Power Off (RPO) ports.
• Backed by worldwide agency approvals.
9PX3K3U_EN Page 7
2. Presentation
Tower installation
Rack installation
Page 8 9PX3K3U_EN
2. Presentation
ENGLISH
2.2 Rear panels
9PX3K3U
13
1 RS232 communication port
2 USB communication port
6 7 4 3 12 11 3 Dry (relay) contacts communication
port
4 Connector for ROO (Remote On/Off)
control
5 Connectors for automatic recognition
of an additional battery module
6 Connector for RPO (Remote Power Off)
control
7 Slot for optional communication card
5 8 1 2 9 10 8 Connector for additional battery
module
9 (2) L6-20R outlets
10 (2) L6-30R outlets
11 Input/Output terminal blocks
12 Connector for HotSwap MBP detection
13 Input power cable with L6-30P plug
9PX3K3U_EN Page 9
2. Presentation
2.3 Accessories
Part number Description
9PXEBM180RT Extended Battery Module
MBP6K208
5 4 3 1 Input/Output terminal blocks
2 Normal AC source switch
3 Input/Output connector to the UPS
4 Manual Bypass switch
5 (2) 30A outlets
1 2
9PXTFMR5
1 L6-30P input power cable
2 (18) 5-20R 120V outlets
3 20A circuit breaker
3 2 1
Page 10 9PX3K3U_EN
2. Presentation
ENGLISH
9PXPPDM1
3 1 L6-30P input power cable
2 L6-30R outlet for connection to UPS
5 input
3 L6-30P cable for connection to UPS
output
4 L14-30R 120V/240V outlet
5 L6-30R 240V outlet
6 30A circuit breaker
7 (6) 5-20R 120V outlets
8 20A circuit breaker
7 8 4 6 2
9PXPPDM2
2 1 Input/Output terminal blocks
2 L6-30R outlet for connection to UPS
input
3 L6-30P cable for connection to UPS
output
4 30A output circuit breaker
4 1
9PX3K3U_EN Page 11
2. Presentation
Online mode
67% 100%
2.0kW 60min
2.1kVA 1EBM
Efficiency: 90%
Page 12 9PX3K3U_EN
2. Presentation
ENGLISH
2.5 LCD description
After 5 minutes of inactivity, the LCD displays the screen saver.
The LCD backlight automatically dims after 10 minutes of inactivity. Press any button to restore the screen.
Operation status
Online mode
67% 100%
Load/equipment status
2.0kW 60min Battery status
2.1kVA 1EBM
Efficiency: 90%
Efficiency information
The following table describes the status information provided by the UPS
Note: If other indicator appears, see troubleshooting on page 38 for additional information.
Online mode The UPS is operating normally. The UPS is powering and protecting
the equipment.
Battery mode A utility failure has occured and The UPS is powering the equipment
the UPS is on Battery mode. with the battery power.
Prepare your equipment for
shutdown.
Bypass mode An overload or a fault has occurred, Equipment is powered but not
or a command has been received, protected by the UPS.
and the UPS is in Bypass mode.
9PX3K3U_EN Page 13
2. Presentation
Page 14 9PX3K3U_EN
2. Presentation
ENGLISH
Submenu Available settings Default settings
Interrupt time If Bypass transfer is enabled, [10ms]
Interrupt time: [10ms] [20ms]
Define break duration when transfer
on Bypass
In/Out settings
Overload [10%] … [102%] [102%]
prealarm Load % when overload alarm occurs
Redundancy [Unitary UPS] [Hot Standby] Unitary UPS
mode Force slew rate value to 0.5Hz/s
Cold start [Enabled] [Disabled] [Enabled]
Authorize the product to start on
battery power.
Forced reboot [Enabled] [Disabled] [Enabled]
If mains recover during a shutdown
sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disabled, shutdown
sequence will not complete and
restart will occur immediately.
Auto restart [Enabled] [Disabled] [Enabled]
Authorize the product to restart
automatically when mains recovers
after a complete battery discharge.
Auto start [Enabled] [Disabled] [Disabled]
The UPS automatically starts up as
On/Off settings soon as mains power is available
(no need topress the button).
Energy saving [Disabled] [100W] … [1000W] [Disabled]
If Enabled, UPS will shutdown after
5 min. of back-up time, if load is less
than threshold.
Sleep mode [Enabled] [Disabled] [Enabled]
If Disabled, LCD and communication
will turn OFF immediately after UPS
is OFF.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
Remote command [Enabled] [Disabled] [Enabled]
If Enabled, shutdown or restart
commands from software are
authorized.
Bypass standby [Enabled] [Disabled] [Disabled]
Define if output is powered from
Bypass in Standby mode.
Automatic battery In constant charge mode: [Every ABM cycle]
test [No test] [Every day] [Every week]
[Every month]
In ABM cycling mode :
[No test] [Every ABM cycle]
Low battery [0%] ... [100%] [20%]
warning The alarm triggers when the set
percentage of battery capacity is
reached during back-up time.
Restart bat. level [0%] ... [100%] [0%]
If set, automatic restart will occur
only when percentage of battery
Battery settings charge is reached.
Battery charge [ABM cycling] [Constant charge] [ABM cycling]
mode
External battery [Auto detection] [Auto detection]
[Manual EBM set.] Using standard EBM, UPS
[Manual battery set.] detects automatically the
[No battery] number of EBM connected
Deep Disch. [Yes] [No] [Yes]
protect. If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold.
Warranty void if set to No.
9PX3K3U_EN Page 15
3. Installation
Check the battery recharge date on the shipping carton label. If the date has passed and the
batteries were never recharged, do not use the UPS. Contact your service representative.
• The cabinet is heavy (see page 41). Follow Special precautions provided on page 4 and on the
carton.
Unpack the equipment and remove all the packing materials and shipping carton.
Note: Do not lift the UPS or EBM from the front panel.
Discard or recycle the packaging in a responsible manner, or store it for future use.
Place the cabinet in a protected area that has adequate airflow and is free of humidity, flammable gas, and
corrosion.
Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.
Page 16 9PX3K3U_EN
3. Installation
ENGLISH
3.3 Checking the accessory kit
• Verify that the following additional items are included with the UPS:
1 (2)Tower stands
2 Rack kit for 19-inch enclosures
11 3 Cable gland for Output connection
Additional cable gland for Input
4 Network card-MS communication card
1 5 RS232 communication cable
6 USB communication cable
7 User manual
8 Safety instructions
9 Warranty sheet
10 Software CD-ROM
11 Screwdriver
7 8 9
5 6
10 4
3
• If you ordered an optional Extended Battery Module (EBM), verify that the following additional items are
included with the EBM:
3 1
4
Discard the EBM user’s guide if you are installing the EBM with a new UPS at the same time.
Use the UPS user’s guide to install both the UPS and the EBM.
If you ordered other UPS accessories, refer to specific user manuals to check the packing
contents.
9PX3K3U_EN Page 17
3. Installation
A small amount of arcing may occur when connecting the internal batteries. This is normal
and will not harm personnel. Connect the cables quickly and firmly.
Page 18 9PX3K3U_EN
3. Installation
ENGLISH
3.5 Connecting the EBM(s)
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and
will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.
1. Plug the EBM power cable(s) into the battery connector(s). Up to 12 EBMs may be connected
to the UPS.
2. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for
each cable.
3. Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
If you ordered other UPS accessories, refer to specific user manuals to check the connection
to the UPS.
9PX3K3U_EN Page 19
3. Installation
If you ordered other UPS accessories, refer to specific user manuals to check the tower installation
with the UPS.
Page 20 9PX3K3U_EN
3. Installation
ENGLISH
3.8 Rack installation
If you ordered other UPS accessories, refer to specific user manuals to check the rack installation
with the UPS.
The UPS is heavy. To ease its rack mounting, you can remove the battery pack from the UPS
as explained below.
1. Remove the center cover of the front panel
2. Remove the two screws to open the left side of the front panel
3. Remove the two screws to pull out the metal protection cover of the battery
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or
disconnect it.
4. Pull out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable sur-
face. Use two hands to support the battery pack. Set it aside for reinstalling after that the UPS
is rack mounted.
5. Mount the UPS on rack
6. Put back the battery pack, screw back the metal protection cover and the front panel,
then clip the center cover.
9PX3K3U_EN Page 21
3. Installation
2
3
Page 22 9PX3K3U_EN
3. Installation
ENGLISH
3.9 Installation requirements
Recommended protective devices and cable cross-sections
L1
N(L2) to UPS Normal AC source
G N(L2) L1
Ground
9PX3K3U_EN Page 23
4. Power cables connection
If you ordered a HotSwap MBP or a PPDM, refer to the specific user manual to check the
terminal blocks connection of the UPS with this accessory.
gland.
L1
terminal blocks.
blocks.
OUTPUT
N(L2)
Page 24 9PX3K3U_EN
5. Operation
ENGLISH
5.1 UPS startup and shutdown
If you ordered a HotSwap MBP or a PPDM, refer to the specific user manual to check the startup
sequence of the UPS with this accessory.
Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload
alarm.
The internal batteries charge to 90% capacity in less than 3 hours. However, Eaton recommends
that the batteries charge for 48 hours after installation or long-term storage.
Before using this feature, the UPS must have been powered by utility power with output enabled
at least once. Battery start can be disabled. See Coldstart setting in user settings on page 14.
UPS shutdown
To shut down the UPS:
1. Press the button on the UPS front panel. The UPS transfers to Standby mode.
2. Set the upstream circuit breaker (not provided) to the "O" position (Off) to switch off the utility power.
9PX3K3U_EN Page 25
5. Operation
Online mode
During Online mode, the indicator illuminates solid and the UPS is powered from the utility.
The UPS monitors and charges the batteries as needed and provides filtered power protection to your
equipment. Optional High Efficiency and Energy Saving settings minimize heat contribution to the rack
environment. See user settings on page 14.
Battery mode
When the UPS is operating during a power outage, the alarm beeps once every ten seconds and the
indicator illuminates solid. The necessary energy is provided by the battery.
When the utility power returns, the UPS transfers to Online mode operation while the battery recharges.
If battery capacity becomes low while in Battery mode, the audible alarm beeps once every 3 seconds.
This warning is approximate, and the actual time to shutdown may vary significantly.
Shutdown all applications on the connected equipment because automatic UPS shutdown is imminent.
When utility power is restored after the UPS shuts down, the UPS automatically restarts.
Bypass mode
In the event of a UPS overload or internal failure, the UPS transfers your equipment to utility power.
Battery mode is not available and your equipment is not protected; however, the utility power continues
to be passively filtered by the UPS. The indicator illuminates.
Depending on overload conditions, the UPS remains in Bypass mode for at least 5 seconds and will stay
in this mode if three transfers to Bypass occur within 20 minutes.
The UPS transfers to Bypass mode when:
• the user activates Bypass mode through the front panel.
• the UPS detects an internal failure.
• the UPS has an overtemperature condition.
• the UPS has an overload condition listed in table 6 on page 42.
The UPS shuts down after a specified delay for overload conditions listed in table 6 on page 42.
The UPS remains on to alarm the fault
Standby mode
When the UPS is turned-off and remains connected to AC source, the UPS is in Standby mode.
Depending if Bypass Standby setting is enabled, the output is powered but not protected.
The battery recharges when necessary and the communication ports are powered.
Page 26 9PX3K3U_EN
5. Operation
ENGLISH
5.4 Setting High Efficiency mode
In High Efficiency mode, the UPS operates normally on Bypass and transfers to Online (or Battery) mode
in less than 10 ms when utility fails. Transfers to High Efficiency mode will be active after 5 minutes
of Bypass voltage monitoring: if Bypass quality is not in tolerance, then the UPS will remain in Online
mode.
Interrupt time
This setting is displayed to define the break duration during transfer to Bypass, only if transfer out of
tolerance is enabled. 10 ms or 20 ms can be selected.
Battery mode is not displayed and battery low alarm does not activate during a battery test.
9PX3K3U_EN Page 27
5. Operation
Page 28 9PX3K3U_EN
6. Communication
ENGLISH
6.1 Communication ports
2. C
onnect the other end of the
17
communication cable 16 or
17 to the RS232 1 or USB 2
communication port on
the UPS.
5 4 3 2 1
9 8 7 6
common
Status active information: (if contact between pin and common is closed)
• Pin 1: not on Bypass
• Pin 2: load not protected
• Pin 3: not low battery
• Pin 4: not on Battery
• Pin 5: user common
• Pin 6: on Bypass
• Pin 7: low battery
• Pin 8: load protected
• Pin 9: on Battery
• n.o.: contact normally open
• n.c.: contact normally closed
The relay output contacts must not be connected to any utility connected circuits.
Reinforced insulation to the utility is required. The relay output contacts have a maximum rating
of 250 Vac/5A.
9PX3K3U_EN Page 29
6. Communication
• Remote On/Off
Remote On/Off allows remote action of button to switch On/Off the UPS.
Normally open
When contact changes from open to closed, the UPS is switched-on (or stays On).
When contact changes from closed to open, the UPS is switched-off (or stays Off).
On/Off control via button has priority over the remote control.
The RPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be
separated from any hazardous voltage circuits by reinforced insulation.
• The RPO must not be connected to any utility connected circuits. Reinforced insulation to the
utility is required. The RPO switch must have a minimum rating of 27 Vdc and 20 mA and be a
dedicated latching-type switch not tied into any other circuit. The RPO signal must remain active
for at least 250 ms for proper operation.
• To ensure the UPS stops supplying power to the load during any mode of operation, the input
power must be disconnected from the UPS when the Remote Power Off function is activated.
Leave the RPO connector installed in the RPO port on the UPS even if the RPO function is not
needed.
RPO connections:
Internal power supply External power supply
1 3 1 3 1 3 1 3
Normally closed Normally open Normally closed Normally open
Page 30 9PX3K3U_EN
6. Communication
ENGLISH
Remote control connection and test
1. Check the UPS is shut down and the electrical supply network disconnected.
2. Remove RPO connector from the UPS by unfitting the screws.
3. Connect a normally closed volt-free contact between the two pins of connector.
1 3
Normally closed
4. Plug the RPO connector into the back of the UPS and fix the screws.
5. Connect and restart the UPS according to the previously described procedures.
6. Activate the external remote shut down contact to test the function.
Always test the RPO function before applying your critical load to avoid accidental load loss.
• Connectivity Cards
Connectivity cards allow the UPS to communicate in a variety of networking environments and with
different types of devices. The 9PX models have one available communication bay for the following
connectivity cards:
• Network-MS card - has SNMP and HTTP capabilities as well as monitoring through a Web browser
interface; connects to Ethernet network. In addition, a Environmental Monitoring Probe can be atta-
ched to obtain humidity, temperature, smoke alarm, and security information.
• Modbus-MS card - has connection to Modbus protocol in addition to network management.
• Relay-MS card - has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery
low, UPS alarm/OK, or on Bypass.
See on page 21 for the location of the communication bay.
ETHERNET Setting/Sensor ETHERNET Setting/Sensor
100M 10M UPS data Reset 100M 10M UPS data Reset
9PX3K3U_EN Page 31
6. Communication
1. R
emove the slot cover 4
secured by screws.
2. Insert the communication
card in the slot.
3. S ecure the card cover with
the 2 screws.
Page 32 9PX3K3U_EN
7. UPS maintenance
ENGLISH
7.1 Equipment care
For the best preventive maintenance, keep the area around the equipment clean and dust free.
If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the equipment at an ambient temperature of 25°C (77°F).
If the UPS requires any type of transportation, verify that the UPS is disconnected and turned off
and then disconnect the UPS internal battery connector (see on page 35).
The batteries are rated for a 3-5 year service life. The length of service life varies, depending on
the frequency of usage and ambient temperature. Batteries used beyond expected service life
will often have severely reduced runtimes. Replace batteries at least every 4 years to keep units
running at peak efficiency.
Load not
Battery powered
replacement
4-% 100%
years battery
!
Replacement
-kW is
100min
recommended
-kVA 1 EBM
OK
9PX3K3U_EN Page 33
7. UPS maintenance
Batteries can be replaced easily without turning off the UPS or disconnecting the load.
If you prefer to remove input power to change the batteries, see "UPS Shutdown" on page 25.
• Batteries can present a risk of electrical shock or burn from high short circuit current.
Observe the following precautions:
1. Remove watches, rings, or other metal objects,
2. Use tools with insulated handles,
3. Do not lay tools or metal parts on top of batteries,
4. Wear rubber gloves and boots.
• When replacing batteries, replace with the same type and number of batteries or battery packs.
Contact your service representative to order new batteries.
• Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
• Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
• Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and
eyes and may be extremely toxic.
• ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.
Attempting to alter wiring can cause injury.
Page 34 9PX3K3U_EN
7. UPS maintenance
ENGLISH
• Replacing the internal battery
The internal battery is heavy. Use caution when handling the heavy batteries.
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it.
4. Pull out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable
surface. Use two hands to support the battery pack. See "Recycling the used equipment"
on page 37 for proper disposal.
5. Verify that the replacement batteries have the same rating as the batteries being replaced.
6. Put the new battery pack into the UPS. Push the battery pack firmly to ensure a proper connection.
7. Screw back the metal protection cover and the front panel, then clip the center cover.
8. Continue to “Testing new batteries” on page 36.
9PX3K3U_EN Page 35
7. UPS maintenance
The EBM is heavy. Lifting the cabinet into a rack requires a minimum of two people.
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and
will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.
3. Plug the EBM cable(s) into the battery connector(s). Up to twelve EBMs may be connected to the UPS.
4. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each
cable.
5. Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
Page 36 9PX3K3U_EN
7. UPS maintenance
ENGLISH
7.5 Replacing the UPS equipped with a HotSwap MBP or with a PPDM
The HotSwap MBP as well as the PPDM allows to service or replace the UPS without interrupting the
connected loads.
Refer to the specific user manual for more information about this accessory.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper
disposal, contact your local recycling/reuse or hazardous waste center.
9PX3K3U_EN Page 37
8. Troubleshooting
The Eaton 9PX is designed for durable, automatic operation and also alerts you whenever potential
operating problems may occur. Usually the alarms shown by the control panel do not mean that the
output power is affected. Instead, they are preventive alarms intended to alert the user.
• Events are silent status information that are recorded into the Event log. Example = "AC freq in range".
• Alarms are recorded into the Event log and displayed on the LCD status screen with the logo blinking.
Some alarms may be announced by a beep every 3 seconds. Example = "Battery low".
• Faults are announced by a continuous beep and red LED, recorded into the Fault log and displayed on
the LCD with a specific message box. Example = Out. short circuit.
Use the following troubleshooting chart to determine the UPS alarm condition.
No battery The batteries are disconnected. Verify that all batteries are properly
connected.
If the condition persists, contact your
service representative.
LED is On.
Beep continuous.
Battery fault The battery test is failed due to Verify that all batteries are properly
bad or disconnected batteries, connected. Start a new battery test :
or the battery minimum voltage is if the condition persists, contact your
reached in ABM cycling mode. service representative.
LED is On.
Beep continuous.
The UPS does not The batteries need charging or Apply utility power for 48 hours to
provide the expected service. charge the batteries. If the condition
backup time. persists, contact your service
representative.
Bypass mode An overload or a fault has Equipment is powered but not
occurred, or a command has been protected by the UPS.
received and the UPS is in Bypass Check for one of the following alarms:
mode overtemperature, overload or UPS
LED is on.
failure.
Power overload Power requirements exceed the Remove some of the equipment from
UPS capacity (greater than the UPS.
100% of nominal; see in table 6 The UPS continues to operate, but
on page 42 for specific output may switch to Bypass mode or shut
LED is On. overload ranges). down if the load increases.
Beep continuous. The alarm resets when the condition
becomes inactive.
Page 38 9PX3K3U_EN
8. Troubleshooting
ENGLISH
UPS overtemperature The UPS internal temperature is If the UPS transferred to Bypass
too high or a fan has failed. mode, the UPS will return to normal
At the warning level, the UPS operation when the temperature drops
generates the alarm but remains 5°C below the warning level.
LED is On. in the current operating state. If the condition persists, shut down
1 beep every 3 seconds. If the temperature rises another the UPS.
10°C, the UPS transfers to Bypass Clear vents and remove any heat
mode or shuts down if Bypass is sources. Allow the UPS to cool.
unusable. Ensure the airflow around the UPS is
not restricted. Restart the UPS.
If the condition continues to persist,
contact your service representative.
The UPS does not start. The input source is not connected Check the input connections.
correctly.
The Remote Power Off (RPO) If the UPS Status menu displays the
switch is active or the RPO "Remote Power Off" notice, inactivate
connector is missing. the RPO input.
Input bad wiring / Input/Output cables are not Connect correctly the Input/Output
Output bad wiring connected to the correct terminal cables.
blocks.
Led is On.
Beep continuous.
MBP disconnected The HotSwap MBP is no more If the HotSwap MBP is connected
connected to the UPS. to the UPS, check that the detection
connector is correctly plugged.
9PX3K3U_EN Page 39
8. Troubleshooting
• Serial number
If repair is required, you will be given a Returned Material Authorization (RMA) number. This number must
appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging
or request packaging from the Help Desk or distributor. Units damaged in shipment as a result of improper
packaging are not covered under warranty. A replacement or repair unit will be shipped, freight prepaid for
all warrantied units.
For critical applications, immediate replacement may be available. Call the Help Desk for the
dealer or distributor nearest you.
Page 40 9PX3K3U_EN
9. Specifications
ENGLISH
9.1 Model specifications
Table 1. Power Module model list
Model Power ratings
9PX3K3U 3000VA / 3000W
9PX3K3U_EN Page 41
9. Specifications
Page 42 9PX3K3U_EN
9. Specifications
ENGLISH
Agency markings CE / cULus / energy star
Operating temperature 0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note: thermal protection switches load to Bypass in case of overheating.
Storage temperature 0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
Transit temperature -25 to 55°C (-13 to 130°F)
Relative humidity 0 to 95% no condensing
Operating altitude Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Transit altitude Up to 10,000 meters (32,808 ft) above sea level
Audible noise < 45 dBA at 1 meter typical
Table 9. Battery
Internal batteries EBM
Rack / Tower 9PX3K3U: 180Vdc 9PXEBM180RT: 180Vdc
configuration
Type Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F).
Lifetime is reduced above 30°C.
Monitoring Advanced monitoring for earlier failure detection and warning
Battery port External three-pole SBS75G Black connector on UPS for connection to EBM
EBM battery 40cm (15.7in)
cable length
9PX3K3U_EN Page 43
EATON
Customer Care Center
Assembly Number:__________________________________________________________________________________________
Serial number:_______________________________________________________________________________________________
Who To Contact
For Technical Support, Customer Care Center, Customer FAQ please visit our website: www.eaton.com
Date: _______________________________________________________________________________________________________
Contact Name:_______________________________________________________________________________________________
Page 44 9PX3K3U_EN
10. Glossary
ENGLISH
Bypass AC source Source supplying the bypass line. The equipment can be transferred to the
bypass line if an overload occurs on the UPS output, for maintenance or in
the event of a malfunction.
Frequency converter Operating mode used to convert the AC-power frequency between the UPS input
and output (50Hz -> 60Hz or 60Hz -> 50Hz).
Low-battery warning This is a battery-voltage level indicating that battery power is low and that
the user must take action to prevent the imminent break in the supply of power
to the load.
Backup time Time during which the load can be supplied by the UPS operating on battery
power.
HE mode Operating mode by which the load is supplied directly by the AC source if it is
within the tolerances defined by the user. This mode reduces the consumption
of electrical power
Manual bypass Rotary switch controlled by the user, used to connect the loads directly to the
AC source. Transfer of the load to the manual bypass enables UPS maintenance
without interrupting the supply of power to the connected loads.
Normal (double The normal UPS operating mode in which the AC source supplies the UPS which
conversion) mode in turn supplies the connected loads (after electronic double conversion).
Relay contacts Contacts supplying information to the user in the form of signals.
9PX3K3U_EN Page 45