Eaton 9px 3 Kva 3u Ups Manual 9px3k3un en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 46

ENGLISH

9PX3K3U
9PX EBM 180 V

Installation
and user manual

Copyright © 2016 EATON


All rights reserved.

Service and support:


Call your local service representative

9PX3K3U US_EN
SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS. This manual contains important instructions


that should be followed during installation and maintenance of the UPS and batteries.

The 9PX models that are covered in this manual are intended for installation
in an environment within 0 to 40°C, free of conductive contaminant.

This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will
be required to correct the interference at his own expense.

Certification standards
• Safety: IEC/EN 62040-1 / Ed.1: 2008.
UL 1778 4th edition
• EMC: IEC/EN 62040-2 / Ed.2: 2006.
FCC part 15 Class A.
• Performance: IEC/EN 62040-3 / Ed.2.0: 2011.
• IEC 61000-4-2 (ESD): level 3.
• IEC 61000-4-3 (Radiated field): level 3.
• IEC 61000-4-4 (EFT): level 4.
• IEC 61000-4-5 (Fast transients): level 4.
• IEC 61000-4-6 (Electromagnetic field): level 3.
• IEC 61000-4-8 (Conducted magnetic field): level 4.

Special symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:

RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.

Important instructions that must always be followed.

Do not discard the UPS or the UPS batteries in the trash.


This product contains sealed lead acid batteries and must be disposed as it's explain in this manual.
For more information, contact your local recycling/reuse or hazardous waste center.

This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.

Information, advice, help.

Refer to the user manual of UPS accessories.

Page 2 9PX3K3U_EN
SAFETY INSTRUCTIONS

ENGLISH
Safety of persons
• The system has its own power source (the battery). Consequently, the power outlets may be ener-
gized even if the systems is disconnected from the AC power source. Dangerous voltage levels are
present within the system. It should be opened exclusively by qualified service personnel.
• The system must be properly grounded.
• The battery supplied with the system contains small amounts of toxic materials.
To avoid accidents, the directives listed below must be observed:
-S ervicing of batteries should be performed or supervised by personnel knowledgeable about
batteries and the required precautions.
- When replacing batteries, replace with the same type and number of batteries or battery packs.
- Do not dispose of batteries in a fire. The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
• Precautions must be taken for all handling:
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
-D etermine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if such grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).

Product safety
• The UPS connection instructions and operation described in the manual must be followed in
the indicated order.
• CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with branch circuit
overcurrent protection for : 30A rating, for 9PX3K3U models in accordance with the National
Electric Code, ANSI/NFPA 70.
The upstream circuit breaker must be easily accessible.
The unit can be disconnected from AC power source by opening this circuit breaker.
• Disconnection and overcurrent protection devices shall be provided by others for permanently
connected AC input/output circuits.
• Check that the indications on the rating plate correspond to your AC powered system and
to the actual electrical consumption of all the equipment to be connected to the system.
• For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall
be easily accessible
• Never install the system near liquids or in an excessively damp environment.
• Never let a foreign body penetrate inside the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The admissible storage temperature range is -15ºC to +50ºC.
• The system is not for use in a computer room AS DEFINED IN the standard for the Protection
of Information Technology Equipment, ANSI/NFPA 75.
Contact Eaton resellers to order a special battery kit, if needed to meet the ANSI/NFPA 75
requirement.

9PX3K3U_EN Page 3
SAFETY INSTRUCTIONS

Special precautions
• The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling operations.
• All handling operations will require at least two people (unpacking, lifting, installation in rack sys-
tem).
• Straps are provided only for unpacking manually the unit from the carton; don’t use the straps to
carry the unit around. The unit can slip from the straps during handling (risk of injury and product
damage):
- keep 12in / 30cm minimum distance between the straps
- lift the unit carefully and keep it at low height
- keep the unit horizontal during unpacking.
• Before and after the installation, if the UPS remains de-energized for a long period, the UPS must
be energized for a period of 24 hours, at least once every 6 months (for a normal storage tempera-
ture less than 25°C). This charges the battery, thus avoiding possible irreversible damage.
• During the replacement of the Battery Module, it is imperative to use the same type and number of
element as the original Battery Module provided with the UPS to maintain an identical level of
performance and safety. In case of doubt, don’t hesitate to contact your EATON representative.
• All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
There are NO USER SERVICEABLE PARTS inside the UPS.

Page 4 9PX3K3U_EN
Contents

ENGLISH
1. Introduction........................................................................................ 6
1.1 Environmental protection................................................................................................6

2. Presentation....................................................................................... 8
2.1 Standard installations......................................................................................................8
2.2 Rear panels.....................................................................................................................9
2.3 Accessories.................................................................................................................. 10
2.4 Control panel................................................................................................................. 12
2.5 LCD description............................................................................................................ 13
2.6 Display functions.......................................................................................................... 14
2.7 User settings................................................................................................................ 14

3. Installation....................................................................................... 16
3.1 Inspecting the equipment ............................................................................................ 16
3.2 Unpacking the cabinet.................................................................................................. 16
3.3 Checking the accessory kit........................................................................................... 17
3.5 Connecting the EBM(s) ................................................................................................ 19
3.6 Connecting other accessories ..................................................................................... 19
3.7 Tower installation..........................................................................................................20
3.8 Rack installation............................................................................................................21
3.9 Installation requirements..............................................................................................23

4. Power cables connection................................................................ 24


4.1 Access to terminal blocks.............................................................................................24
4.2 Input/Output connection...............................................................................................24

5. Operation......................................................................................... 25
5.1 UPS startup and shutdown...........................................................................................25
5.2 Operating modes..........................................................................................................26
5.3 Transferring the UPS between modes..........................................................................26
5.4 Setting High Efficiency mode.......................................................................................27
5.5 Configuring Bypass settings.........................................................................................27
5.6 Configuring battery settings.........................................................................................27
5.7 Retrieving the Event log................................................................................................28
5.8 Retrieving the Fault log.................................................................................................28

6. Communication............................................................................... 29
6.1 Communication ports...................................................................................................29
6.2 Eaton Intelligent Power Software suite........................................................................32

7. UPS maintenance............................................................................. 33
7.1 Equipment care.............................................................................................................33
7.2 Storing the equipment..................................................................................................33
7.3 When to replace batteries............................................................................................33
7.4 Replacing batteries.......................................................................................................34
7.5 Replacing the UPS equipped with a HotSwap MBP or with a PPDM..........................37
7.6 Recycling the used equipment.....................................................................................37

8. Troubleshooting............................................................................... 38
8.1 Typical alarms and faults...............................................................................................38
8.2 Silencing the alarm.......................................................................................................40
8.3 Service and support......................................................................................................40

9. Specifications................................................................................... 41
9.1 Model specifications.....................................................................................................41

10. Glossary.......................................................................................... 45

9PX3K3U_EN Page 5
1. Introduction

Thank you for selecting an EATON product to protect your electrical equipment.

The 9PX range has been designed with the utmost care.
We recommend that you take the time to read this manual to take full advantage of the many features
of your UPS (Uninterruptible Power System).

Before installing your 9PX, please read the booklet presenting the safety instructions.
Then follow the indications in this manual.

To discover the entire range of EATON products and the options available for the 9PX range,
we invite you to visit our web site at www.eaton.com/powerquality or contact your EATON representative.

1.1 Environmental protection


EATON has implemented an environmental-protection policy.
Products are developed according to an eco-design approach.

Substances
This product does not contain CFCs, HCFCs or asbestos.

Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
• The cardboard we use comprises over 50% of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packing materials are recyclable and bear the appropriate identification symbol 01
PET

Materials Abbreviations Number in 01


the symbols PET

Polyethylene terephthalat PET 01


High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Polypropylene PP 05
Polystyrene PS 06

Follow all local regulations for the disposal of packing materials.

End of life
EATON will process products at the end of their service life in compliance with local regulations.
EATON works with companies in charge of collecting and eliminating our products at the end of
their service life.

Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing center for electrical and
electronic waste.

Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations
concerning batteries.
The battery may be removed to comply with regulations and in view of correct disposal.

Page 6 9PX3K3U_EN
1. Introduction

ENGLISH
The Eaton® 9PX uninterruptible power system (UPS) protects your sensitive electronic equipment from the
most common power problems, including power failures, power sags, power surges, brownouts, line noise,
high voltage spikes, frequency variations, switching transients, and harmonic distortion.
Power outages can occur when you least expect it and power quality can be erratic. These power problems
have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware - causing
hours of lost productivity and expensive repairs.
With the Eaton 9PX, you can safely eliminate the effects of power disturbances and guard the integrity
of your equipment. Providing outstanding performance and reliability, the Eaton 9PX’s unique benefits
include:
• True online double-conversion technology with high power density, utility frequency independence, and
generator compatibility.
• ABM® technology that uses advanced battery management to increase battery service life, optimize
recharge time, and provide a warning before the end of useful battery life.
• Selectable High Efficiency mode of operation.
• Standard communication options: one RS-232 communication port, one USB communication port, and
relay output contacts.
• Optional connectivity cards with enhanced communication capabilities.
• Extended runtime with up to twelve Extended Battery Modules (EBMs) per UPS.
• Firmware that is easily upgradable without a service call.
• Remote On/Off control through Remote On/Off (ROO) and Remote Power Off (RPO) ports.
• Backed by worldwide agency approvals.

9PX3K3U_EN Page 7
2. Presentation

2.1 Standard installations

Tower installation

Rack installation

Description Weights Dimensions (inch/mm)


(lb/kg) D xW x H
9PX3K3U 106 / 48 28.4 x 17.3 x 5.1 / 722 x 440 x 130
9PX EBM 180V 150 / 68 25.4 x 17.3 x 5.1 / 645 x 440 x 130

Page 8 9PX3K3U_EN
2. Presentation

ENGLISH
2.2 Rear panels
9PX3K3U
13
1 RS232 communication port
2 USB communication port
6 7 4 3 12 11 3 Dry (relay) contacts communication
port
4 Connector for ROO (Remote On/Off)
control
5 Connectors for automatic recognition
of an additional battery module
6 Connector for RPO (Remote Power Off)
control
7 Slot for optional communication card
5 8 1 2 9 10 8 Connector for additional battery
module
9 (2) L6-20R outlets
10 (2) L6-30R outlets
11 Input/Output terminal blocks
12 Connector for HotSwap MBP detection
13 Input power cable with L6-30P plug

9PX EBM 180V (Extended Battery Module)


14 15 14 Connectors for battery modules
(to the UPS or to the other battery
modules)
15 Connectors for automatic recognition
of battery modules

9PX3K3U_EN Page 9
2. Presentation

2.3 Accessories
Part number Description
9PXEBM180RT Extended Battery Module

9RK Rack kit 9PX

RK2PC 2-post Rack Kit 9PX

Network-MS Network card

Modbus-MS Modbus and network card

Relay-MS Relay card

MBP6K208 HotSwap MBP 6000 208

9PXTFMR5 5kVA Transformer

9PXPPDM1 6kVA PPDM (Type 1)

9PXPPDM2 6kVA PPDM (Type 2)

BINTSYS Battery Integration System

EBMCBL180 1.8m cable 180V EBM

MBP6K208
5 4 3 1 Input/Output terminal blocks
2 Normal AC source switch
3 Input/Output connector to the UPS
4 Manual Bypass switch
5 (2) 30A outlets

1 2

9PXTFMR5
1 L6-30P input power cable
2 (18) 5-20R 120V outlets
3 20A circuit breaker

3 2 1

Page 10 9PX3K3U_EN
2. Presentation

ENGLISH
9PXPPDM1
3 1 L6-30P input power cable
2 L6-30R outlet for connection to UPS
5 input
3 L6-30P cable for connection to UPS
output
4 L14-30R 120V/240V outlet
5 L6-30R 240V outlet
6 30A circuit breaker
7 (6) 5-20R 120V outlets
8 20A circuit breaker

7 8 4 6 2

9PXPPDM2
2 1 Input/Output terminal blocks
2 L6-30R outlet for connection to UPS
input
3 L6-30P cable for connection to UPS
output
4 30A output circuit breaker

4 1

9PX3K3U_EN Page 11
2. Presentation

2.4 Control panel


The UPS has a five-button graphical LCD. It provides useful information about the UPS itself, load status,
events, measurements and settings.

Online mode Fault


indicator (green) indicator (red)

Battery mode Bypass mode


indicator (orange) indicator (orange)

Online mode

67% 100%
2.0kW 60min
2.1kVA 1EBM

Efficiency: 90%

Escape Up Down Enter On/Off


button

The following table shows the indicator status and description:


Indicator Status Description
The UPS is operating normally on Online or on High
On
Green Efficiency mode.

On The UPS is on Battery mode.


Orange

On The UPS is on Bypass mode.


Orange
The UPS has an active alarm or fault. See trouble-
On
shooting on page 38 for additional information.
Red

Page 12 9PX3K3U_EN
2. Presentation

ENGLISH
2.5 LCD description
After 5 minutes of inactivity, the LCD displays the screen saver.

The LCD backlight automatically dims after 10 minutes of inactivity. Press any button to restore the screen.

Operation status

Online mode

67% 100%
Load/equipment status
2.0kW 60min Battery status

2.1kVA 1EBM

Efficiency: 90%

Efficiency information
The following table describes the status information provided by the UPS

Note: If other indicator appears, see troubleshooting on page 38 for additional information.

Operation status Cause Description


Standby mode The UPS is Off. Equipment is not powered until
button is pressed.

Online mode The UPS is operating normally. The UPS is powering and protecting
the equipment.

Battery mode A utility failure has occured and The UPS is powering the equipment
the UPS is on Battery mode. with the battery power.
Prepare your equipment for
shutdown.

1 beep every 10 seconds


End of backup time The UPS is on Battery mode and This warning is approximate, and
the battery is running low. the actual time to shutdown may
vary significantly.
Depending on the UPS load
and number of Extended Battery
Modules (EBMs), the "Battery Low"
1 beep every 3 seconds warning may occur before the
battery reaches 20% capacity.
High Efficiency mode The UPS is operating on High The UPS is powering and
Efficiency mode. protecting the equipment

Bypass mode An overload or a fault has occurred, Equipment is powered but not
or a command has been received, protected by the UPS.
and the UPS is in Bypass mode.

9PX3K3U_EN Page 13
2. Presentation

2.6 Display functions


Press the Enter ( ) button to activate the menu options. Use the two middle buttons ( and ) to scroll
through the menu structure. Press the Enter ( ) button to select an option. Press the button to cancel
or return to the previous menu.
Main menu Submenu Display information or Menu function
Measurements [Load] W VA A pf / [Input/Bypass] V Hz / [Output/Efficiency] V Hz /
[Battery] % min V n° / [DCbus] V / [Average power usage] Wh /
[Cumulat. power usage] Wh since date
Control Go to Bypass Transfers the UPS on Bypass mode
Start battery test Starts a manual battery test
Reset fault state Clears active fault
Restore factory set Returns all settings to original values
Reset average power Clears average power usage measurement
Reset cumul. power Clears cumulated power usage measurement
Dry contacts test Tests dry contact relay outputs
Settings Local settings Sets product general parameters
In/Out settings Sets Output parameters
On/Off settings Sets On/Off conditions
Battery settings Sets battery configuration
Event log Event filter Selects faults, alarms and/or events to display
Event list Displays the events stored
Reset event list Clears events
Fault log Fault list Displays the faults stored
Reset fault list Clears faults
Identification [Product type/model] / [Part/Serial number] / [UPS/NMC
firmware] / [Com card IPv4], [Com card IPv6], [Com card MAC] /
[Detected accessories]
Register product Links to Eaton registration website

2.7 User settings


The following table displays the options that can be changed by the user.
Submenu Available settings Default settings
Language [English] [Français] [Deutsch] [English]
[Español] [Русский] [Português] User selectable when UPS is
[Italiano] powered for the first time.
Menus, status, notices and alarms,
UPS fault, Event Log data and
settings are in all supported
languages.
Date/ time Format: [US]
Local settings
[International] [US]
LCD Modify LCD screen brightness and
contrast to be adapted to room light
conditions.
Audible alarm [Enabled] [Disabled on battery] [Enabled]
[Always disabled]
Enable or disable the buzzer
if an alarm occurs.
Output voltage [200V] [208V] [220V] [230V] [240V] [208V]
Can be changed only in Standby
mode
Output frequency Frequency converter: Disabled
[Enabled] [Disabled]
Frequency settable in frequency
converter mode
Output mode [Industrial] [Network] [Network]
Set UPS behavior regarding transfer
In/Out settings on Bypass
Input volt hysteresis Sets input voltage hysteresis [10V]
from 1 to 10V
High Efficiency [Enabled] [Disabled] [Disabled]
mode Power the output from Bypass
for high efficiency
Bypass transfer [Transfer if BP AC NOK] [Disabled]
[Enabled] [Disabled]
Allow transfer on Bypass out
of tolerance

Page 14 9PX3K3U_EN
2. Presentation

ENGLISH
Submenu Available settings Default settings
Interrupt time If Bypass transfer is enabled, [10ms]
Interrupt time: [10ms] [20ms]
Define break duration when transfer
on Bypass
In/Out settings
Overload [10%] … [102%] [102%]
prealarm Load % when overload alarm occurs
Redundancy [Unitary UPS] [Hot Standby] Unitary UPS
mode Force slew rate value to 0.5Hz/s
Cold start [Enabled] [Disabled] [Enabled]
Authorize the product to start on
battery power.
Forced reboot [Enabled] [Disabled] [Enabled]
If mains recover during a shutdown
sequence:
If set to Enabled, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disabled, shutdown
sequence will not complete and
restart will occur immediately.
Auto restart [Enabled] [Disabled] [Enabled]
Authorize the product to restart
automatically when mains recovers
after a complete battery discharge.
Auto start [Enabled] [Disabled] [Disabled]
The UPS automatically starts up as
On/Off settings soon as mains power is available
(no need topress the button).
Energy saving [Disabled] [100W] … [1000W] [Disabled]
If Enabled, UPS will shutdown after
5 min. of back-up time, if load is less
than threshold.
Sleep mode [Enabled] [Disabled] [Enabled]
If Disabled, LCD and communication
will turn OFF immediately after UPS
is OFF.
If Enabled, LCD and communication
stays ON 1h30 min after UPS is OFF.
Remote command [Enabled] [Disabled] [Enabled]
If Enabled, shutdown or restart
commands from software are
authorized.
Bypass standby [Enabled] [Disabled] [Disabled]
Define if output is powered from
Bypass in Standby mode.
Automatic battery In constant charge mode: [Every ABM cycle]
test [No test] [Every day] [Every week]
[Every month]
In ABM cycling mode :
[No test] [Every ABM cycle]
Low battery [0%] ... [100%] [20%]
warning The alarm triggers when the set
percentage of battery capacity is
reached during back-up time.
Restart bat. level [0%] ... [100%] [0%]
If set, automatic restart will occur
only when percentage of battery
Battery settings charge is reached.
Battery charge [ABM cycling] [Constant charge] [ABM cycling]
mode
External battery [Auto detection] [Auto detection]
[Manual EBM set.] Using standard EBM, UPS
[Manual battery set.] detects automatically the
[No battery] number of EBM connected
Deep Disch. [Yes] [No] [Yes]
protect. If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold.
Warranty void if set to No.
9PX3K3U_EN Page 15
3. Installation

3.1 Inspecting the equipment


If any equipment has been damaged during shipment, keep the shipping cartons and packing materials
for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after
acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage:
1. File with the carrier within 15 days of receipt of the equipment;
2. Send a copy of the damage claim within 15 days to your service representative.

Check the battery recharge date on the shipping carton label. If the date has passed and the
batteries were never recharged, do not use the UPS. Contact your service representative.

3.2 Unpacking the cabinet


• Unpacking the cabinet in a low-temperature environment may cause condensation to occur
in and on the cabinet. Do not install the cabinet until the inside and outside of the cabinet are
absolutely dry (hazard of electric shock).

• The cabinet is heavy (see page 41). Follow Special precautions provided on page 4 and on the
carton.

Unpack the equipment and remove all the packing materials and shipping carton.
Note: Do not lift the UPS or EBM from the front panel.

Unpacking UPS and Extended Battery Module.

Discard or recycle the packaging in a responsible manner, or store it for future use.
Place the cabinet in a protected area that has adequate airflow and is free of humidity, flammable gas, and
corrosion.

Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.

Page 16 9PX3K3U_EN
3. Installation

ENGLISH
3.3 Checking the accessory kit
• Verify that the following additional items are included with the UPS:
1 (2)Tower stands
2 Rack kit for 19-inch enclosures
11 3 Cable gland for Output connection
Additional cable gland for Input
4 Network card-MS communication card
1 5 RS232 communication cable
6 USB communication cable
7 User manual
8 Safety instructions
9 Warranty sheet
10 Software CD-ROM
11 Screwdriver

7 8 9

5 6

10 4
3

• If you ordered an optional Extended Battery Module (EBM), verify that the following additional items are
included with the EBM:

1 Battery power cable, attached with battery


detection cable
2 Stabilizer bracket (4 screws included)
3 Rack kit for 19-inch enclosures
4 EBM Installation manual

3 1
4

Discard the EBM user’s guide if you are installing the EBM with a new UPS at the same time.
Use the UPS user’s guide to install both the UPS and the EBM.

If you ordered other UPS accessories, refer to specific user manuals to check the packing
contents.

9PX3K3U_EN Page 17
3. Installation

3.4 Connecting the internal battery


Do not make unauthorized changes to the UPS; otherwise, damage may occur to your
equipment and void your warranty.
Do not connect the UPS to utility until installation is completed.

To install the UPS:


1. Remove the center cover of the front panel
2. Remove the two screws to open the left side of the front panel
3. Remove the two screws to pull out the metal protection cover of the battery
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or
disconnect it.

A small amount of arcing may occur when connecting the internal batteries. This is normal
and will not harm personnel. Connect the cables quickly and firmly.

4. Connect the two battery connectors together.


5. Screw back the metal protection cover and the front panel, then clip the center cover.

Page 18 9PX3K3U_EN
3. Installation

ENGLISH
3.5 Connecting the EBM(s)
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and
will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.

1. Plug the EBM power cable(s) into the battery connector(s). Up to 12 EBMs may be connected
to the UPS.
2. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for
each cable.
3. Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).

3.6 Connecting other accessories

If you ordered other UPS accessories, refer to specific user manuals to check the connection
to the UPS.

9PX3K3U_EN Page 19
3. Installation

3.7 Tower installation

If you ordered other UPS accessories, refer to specific user manuals to check the tower installation
with the UPS.

To install the cabinet:


1. Place the UPS on a flat, stable surface in its final location.
2. Always keep 150 mm of free space behind the UPS rear panel.
3. If installing additional cabinets, place them next to the UPS in their final location.

• Adjustment of the orientation of the LCD panel and of the logo.

• Adjustment of the angle of vision of the LCD panel.

Page 20 9PX3K3U_EN
3. Installation

ENGLISH
3.8 Rack installation
If you ordered other UPS accessories, refer to specific user manuals to check the rack installation
with the UPS.

• Prepare UPS for rack mounting.

This step requires two people.

The UPS is heavy. To ease its rack mounting, you can remove the battery pack from the UPS
as explained below.
1. Remove the center cover of the front panel
2. Remove the two screws to open the left side of the front panel
3. Remove the two screws to pull out the metal protection cover of the battery

A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or
disconnect it.

4. Pull out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable sur-
face. Use two hands to support the battery pack. Set it aside for reinstalling after that the UPS
is rack mounted.
5. Mount the UPS on rack
6. Put back the battery pack, screw back the metal protection cover and the front panel,
then clip the center cover.

9PX3K3U_EN Page 21
3. Installation

• Rack mounting of UPS, EBM, and accessory modules.

Follow steps 1 to 4 for module mounting on the rails.


1

2
3

The rails and necessary hardware are supplied by EATON.

Page 22 9PX3K3U_EN
3. Installation

ENGLISH
3.9 Installation requirements
Recommended protective devices and cable cross-sections

1. Recommended upstream protection

UPS power rating Upstream circuit breaker


9PX3K3U D curve – 30A

2 poles circuit breaker

L1
N(L2) to UPS Normal AC source

G N(L2) L1

2. Recommended cable cross-sections

Terminal Wire Terminal wire Minimum input Tightening


position function size rating wire size torque
L1 Phase 4-16 mm2 (12-6 AWG) 6 mm2 (10 AWG) 105°C 10 lb in / 1.13 Nm
N(L2) Neutral
(Phase) 10 mm2 (8 AWG) 75°C

Ground

Copper wire, solid or stranted.

9PX3K3U_EN Page 23
4. Power cables connection

4.1 Access to terminal blocks


1. Remove the terminal blocks cover (one screw)
2. Punch the knockouts and insert the cables/conduits inside
Note: the L6-30P input power cable is attached by Eaton.

• High leakage current:


Earth connection essential before connecting supply.

4.2 Input/Output connection


This type of connection must be carried out by qualified electrical personnel
Before carrying out any connection, check that the upstream protection device (Normal AC
source) is open "O" (Off). Always connect the ground wire first

If you ordered a HotSwap MBP or a PPDM, refer to the specific user manual to check the
terminal blocks connection of the UPS with this accessory.

1. Insert the Normal AC cable through the cable


NORMAL AC SOURCE

gland.
L1

2. Connect the three cables to the Normal AC source


N(L2)

terminal blocks.

3. Insert the Output cable through the cable gland.


t

4. Connect the three cables to the Output terminal


L1

blocks.
OUTPUT
N(L2)

5. Put back and secure the terminal blocks cover


with the screw.
t

6. Tighten the cable glands.

Page 24 9PX3K3U_EN
5. Operation

ENGLISH
5.1 UPS startup and shutdown
If you ordered a HotSwap MBP or a PPDM, refer to the specific user manual to check the startup
sequence of the UPS with this accessory.

Starting the UPS

Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload
alarm.

To start the UPS:


1. Verify that the internal batteries are connected. See "Connecting the internal battery" on page 17
2. If optional EBMs are installed, verify that the EBM are connected to the UPS.
See "Connecting the EBM(s)" on page 19.
3. Verify that the UPS terminal blocks are connected to AC source.
4. Set the upstream circuit breaker (not provided) to the "I" position (On) to switch on the utility power.
The UPS front panel display illuminates and shows EATON logo.
5. Verify that the UPS status screen shows , press to start.
6. Press the button on the UPS front panel for at least 3 seconds.
The UPS front panel display changes status to "UPS starting...".
7. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before conti-
nuing. See "Troubleshooting" on page 38.
If the indicator is on, do not proceed until all alarms are clear. Check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if necessary.
8. Verify that the indicator illuminates solid, indicating that the UPS is operating normally and powe-
ring the output.
The UPS should be in Online mode.

The internal batteries charge to 90% capacity in less than 3 hours. However, Eaton recommends
that the batteries charge for 48 hours after installation or long-term storage.

Starting the UPS on Battery

Before using this feature, the UPS must have been powered by utility power with output enabled
at least once. Battery start can be disabled. See Coldstart setting in user settings on page 14.

To start the UPS on battery:


1. Press the button on the UPS front panel until the UPS front panel display illuminates and shows a
status of "UPS starting...".
The UPS cycles through Standby mode to Battery mode. The indicator illuminates solid.
The UPS supplies power to your equipment.
2. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before conti-
nuing. See "Troubleshooting" on page 38.
Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if
necessary.

UPS shutdown
To shut down the UPS:
1. Press the button on the UPS front panel. The UPS transfers to Standby mode.
2. Set the upstream circuit breaker (not provided) to the "O" position (Off) to switch off the utility power.

9PX3K3U_EN Page 25
5. Operation

5.2 Operating modes


The Eaton 9PX front panel indicates the UPS status through the UPS indicators, see page 14.

Online mode
During Online mode, the indicator illuminates solid and the UPS is powered from the utility.
The UPS monitors and charges the batteries as needed and provides filtered power protection to your
equipment. Optional High Efficiency and Energy Saving settings minimize heat contribution to the rack
environment. See user settings on page 14.

Battery mode

When the UPS is operating during a power outage, the alarm beeps once every ten seconds and the
indicator illuminates solid. The necessary energy is provided by the battery.
When the utility power returns, the UPS transfers to Online mode operation while the battery recharges.
If battery capacity becomes low while in Battery mode, the audible alarm beeps once every 3 seconds.
This warning is approximate, and the actual time to shutdown may vary significantly.
Shutdown all applications on the connected equipment because automatic UPS shutdown is imminent.
When utility power is restored after the UPS shuts down, the UPS automatically restarts.

Bypass mode
In the event of a UPS overload or internal failure, the UPS transfers your equipment to utility power.
Battery mode is not available and your equipment is not protected; however, the utility power continues
to be passively filtered by the UPS. The indicator illuminates.
Depending on overload conditions, the UPS remains in Bypass mode for at least 5 seconds and will stay
in this mode if three transfers to Bypass occur within 20 minutes.
The UPS transfers to Bypass mode when:
• the user activates Bypass mode through the front panel.
• the UPS detects an internal failure.
• the UPS has an overtemperature condition.
• the UPS has an overload condition listed in table 6 on page 42.

The UPS shuts down after a specified delay for overload conditions listed in table 6 on page 42.
The UPS remains on to alarm the fault

Standby mode
When the UPS is turned-off and remains connected to AC source, the UPS is in Standby mode.
Depending if Bypass Standby setting is enabled, the output is powered but not protected.
The battery recharges when necessary and the communication ports are powered.

5.3 Transferring the UPS between modes


From Online (or Battery) to Bypass mode. Press any button to activate the menu options, then select
Control and Go to Bypass.
From Bypass to Online (or Battery) mode. Press any button to activate the menu options, then select
Control and Go back normal.

Page 26 9PX3K3U_EN
5. Operation

ENGLISH
5.4 Setting High Efficiency mode
In High Efficiency mode, the UPS operates normally on Bypass and transfers to Online (or Battery) mode
in less than 10 ms when utility fails. Transfers to High Efficiency mode will be active after 5 minutes
of Bypass voltage monitoring: if Bypass quality is not in tolerance, then the UPS will remain in Online
mode.

Eaton recommends to use the HE mode only to protect I/T equipment.

To set the High Efficiency mode:


1. Put the UPS on Bypass: press any button to activate the menu options, select Control and Go to
Bypass.
2. Then press Escape and select Settings, In/Out settings, and High Efficiency mode.
3. Select Enabled and Enter to confirm.
4. The UPS transfers to High Efficiency mode in 5 minutes.

5.5 Configuring Bypass settings


The following settings are available for configuring Bypass operation.

Bypass transfer out of tolerance


1. Press any button to activate the menu options, then select Settings, Output settings, and Bypass
transfer.
2. Select Enabled or Disabled for BP AC NOK, and Enter to confirm.
If Enabled, the UPS transfers to Bypass even if Bypass AC source is out of tolerance, depending on
output mode. If Disabled, the UPS output is shutdown.

Interrupt time
This setting is displayed to define the break duration during transfer to Bypass, only if transfer out of
tolerance is enabled. 10 ms or 20 ms can be selected.

5.6 Configuring battery settings


Automatic battery test
Automatic battery tests are done every week in constant charging mode and at each cycle in ABM
mode. The tests frequency can be modified.
During the test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds under
load.

Battery mode is not displayed and battery low alarm does not activate during a battery test.

The battery test may be cancelled due to bad conditions, or failed.

Low battery warning


During discharge, the low battery alarm is activated if the battery capacity goes below 20%.
This threshold can be modified.

External battery setting


The number of Extended Battery Module is automatically detected, or can be set manually in number
of EBM or in Ah.

Deep discharge protection


This setting is recommended to avoid damaging the battery. Warranty is void if deep discharge protec-
tion is disabled.

9PX3K3U_EN Page 27
5. Operation

5.7 Retrieving the Event log


To retrieve the Event log through the display:
1. Press any button to activate the menu options, then select Event log.
2. Scroll through the listed events.

5.8 Retrieving the Fault log


To retrieve the Fault log through the display:
1. Press any button to activate the menu options, then select Fault log.
2. Scroll through the listed faults.

Page 28 9PX3K3U_EN
6. Communication

ENGLISH
6.1 Communication ports

• RS232 or USB communication ports


The RS232 and USB communication ports cannot operate simultaneously.
1. Connect the RS232 16 or USB
17 communication cable to
16 the serial or USB port on
the computer.

2. C
 onnect the other end of the
17
communication cable 16 or
17 to the RS232 1 or USB 2
communication port on
the UPS.

The UPS can now communicate


with EATON power management
software.

• Relay output contacts


The UPS incorporates four relay outputs; each information is available with a close or open contact.

5 4 3 2 1
9 8 7 6

n.c. n.o. n.c. n.o. n.o. n.c. n.o. n.c.

common

Status active information: (if contact between pin and common is closed)
• Pin 1: not on Bypass
• Pin 2: load not protected
• Pin 3: not low battery
• Pin 4: not on Battery
• Pin 5: user common
• Pin 6: on Bypass
• Pin 7: low battery
• Pin 8: load protected
• Pin 9: on Battery
• n.o.: contact normally open
• n.c.: contact normally closed

The relay output contacts must not be connected to any utility connected circuits.
Reinforced insulation to the utility is required. The relay output contacts have a maximum rating
of 250 Vac/5A.

9PX3K3U_EN Page 29
6. Communication

• Remote On/Off
Remote On/Off allows remote action of button to switch On/Off the UPS.

Normally open

When contact changes from open to closed, the UPS is switched-on (or stays On).
When contact changes from closed to open, the UPS is switched-off (or stays Off).

On/Off control via button has priority over the remote control.

• Remote Power Off


RPO is used to shutdown the UPS remotely. This feature can be used for shutting down the load and
the UPS by thermal relay, for instance in the event of room over temperature. When RPO is activated,
the UPS shuts down the output and all its power converters immediately. The UPS remains on to alarm
the fault.

The RPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be
separated from any hazardous voltage circuits by reinforced insulation.

• The RPO must not be connected to any utility connected circuits. Reinforced insulation to the
utility is required. The RPO switch must have a minimum rating of 27 Vdc and 20 mA and be a
dedicated latching-type switch not tied into any other circuit. The RPO signal must remain active
for at least 250 ms for proper operation.
• To ensure the UPS stops supplying power to the load during any mode of operation, the input
power must be disconnected from the UPS when the Remote Power Off function is activated.

Leave the RPO connector installed in the RPO port on the UPS even if the RPO function is not
needed.

RPO connections:
Internal power supply External power supply

1 3 1 3 1 3 1 3
Normally closed Normally open Normally closed Normally open

Terminal wire size rating is 0.32-4 mm2 (22-12 AWG).


Suggested wire size is 0.82 mm2 (18 AWG).

Page 30 9PX3K3U_EN
6. Communication

ENGLISH
Remote control connection and test
1. Check the UPS is shut down and the electrical supply network disconnected.
2. Remove RPO connector from the UPS by unfitting the screws.
3. Connect a normally closed volt-free contact between the two pins of connector.

Contact open: shut down of UPS


To return to normal operation, deactivate the external remote shut down
contact and restart the UPS from the front panel.

1 3
Normally closed

4. Plug the RPO connector into the back of the UPS and fix the screws.
5. Connect and restart the UPS according to the previously described procedures.
6. Activate the external remote shut down contact to test the function.

Always test the RPO function before applying your critical load to avoid accidental load loss.

• Connectivity Cards
Connectivity cards allow the UPS to communicate in a variety of networking environments and with
different types of devices. The 9PX models have one available communication bay for the following
connectivity cards:
• Network-MS card - has SNMP and HTTP capabilities as well as monitoring through a Web browser
interface; connects to Ethernet network. In addition, a Environmental Monitoring Probe can be atta-
ched to obtain humidity, temperature, smoke alarm, and security information.
• Modbus-MS card - has connection to Modbus protocol in addition to network management.
• Relay-MS card - has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery
low, UPS alarm/OK, or on Bypass.
See on page 21 for the location of the communication bay.
ETHERNET Setting/Sensor ETHERNET Setting/Sensor

100M 10M UPS data Reset 100M 10M UPS data Reset

Network-MS card Modbus-MS card Relay-MS card

9PX3K3U_EN Page 31
6. Communication

Installation of the communication cards

It is not necessary to shutdown


the UPS before installing
a communication card.

1. R
 emove the slot cover 4
secured by screws.
2. Insert the communication
card in the slot.
3. S ecure the card cover with
the 2 screws.

6.2 Eaton Intelligent Power Software suite


Each 9PX UPS ships with Eaton Intelligent Power Software suite. To begin installing,
see the instructions accompanying the Software suite CD.
Eaton Software suite provides up-to-date graphics of UPS power and system data and power flow.
It also gives you a complete record of critical power events, and it notifies you of important UPS or power
information.
If there is a power outage and the 9PX UPS battery power becomes low, Eaton Software suite can
automatically shut down your computer system to protect your data before the UPS shutdown occurs.

Page 32 9PX3K3U_EN
7. UPS maintenance

ENGLISH
7.1 Equipment care
For the best preventive maintenance, keep the area around the equipment clean and dust free.
If the atmosphere is very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the equipment at an ambient temperature of 25°C (77°F).

If the UPS requires any type of transportation, verify that the UPS is disconnected and turned off
and then disconnect the UPS internal battery connector (see on page 35).
The batteries are rated for a 3-5 year service life. The length of service life varies, depending on
the frequency of usage and ambient temperature. Batteries used beyond expected service life
will often have severely reduced runtimes. Replace batteries at least every 4 years to keep units
running at peak efficiency.

7.2 Storing the equipment


If you store the equipment for a long period, recharge the battery every 6 months by connecting the
UPS to utility power. The internal batteries charge to 90% capacity in less than 3 hours.
However, Eaton recommends that the batteries charge for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label.
If the date has passed and the batteries were never recharged, do not use them. Contact your service
representative.

7.3 When to replace batteries


When the battery replacement screen is displayed, it is recommended to replace the batteries.
Contact your service representative to order new batteries.

Load not
Battery powered
replacement
4-% 100%
years battery
!
Replacement
-kW is
100min
recommended
-kVA 1 EBM
OK

9PX3K3U_EN Page 33
7. UPS maintenance

7.4 Replacing batteries

DO NOT DISCONNECT the batteries while the UPS is in Battery mode.

Batteries can be replaced easily without turning off the UPS or disconnecting the load.
If you prefer to remove input power to change the batteries, see "UPS Shutdown" on page 25.

Consider all warnings, cautions, and notes before replacing batteries.


• Servicing should be performed by qualified service personnel knowledgeable of batteries and
required precautions. Keep unauthorized personnel away from batteries.

• Batteries can present a risk of electrical shock or burn from high short circuit current.
Observe the following precautions:
1. Remove watches, rings, or other metal objects,
2. Use tools with insulated handles,
3. Do not lay tools or metal parts on top of batteries,
4. Wear rubber gloves and boots.
• When replacing batteries, replace with the same type and number of batteries or battery packs.
Contact your service representative to order new batteries.
• Proper disposal of batteries is required. Refer to your local codes for disposal requirements.

• Never dispose of batteries in a fire. Batteries may explode when exposed to flame.

• Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and
eyes and may be extremely toxic.

• Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source


from ground. Contact with any part of a grounded battery can result in electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during installation
and maintenance (applicable to equipment and remote battery supplies not having a grounded
supply circuit).

• ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.
Attempting to alter wiring can cause injury.

• Disconnect charging source prior to connecting or disconnecting battery terminals.

Page 34 9PX3K3U_EN
7. UPS maintenance

ENGLISH
• Replacing the internal battery

The internal battery is heavy. Use caution when handling the heavy batteries.

To replace the battery pack:


1. Remove the center cover of the front panel
2. Remove the two screws to open the left side of the front panel
3. Remove the two screws to pull out the metal protection cover of the battery

A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it.

4. Pull out the plastic handle of the battery pack, and slide the pack out slowly on to a flat and stable
surface. Use two hands to support the battery pack. See "Recycling the used equipment"
on page 37 for proper disposal.
5. Verify that the replacement batteries have the same rating as the batteries being replaced.
6. Put the new battery pack into the UPS. Push the battery pack firmly to ensure a proper connection.
7. Screw back the metal protection cover and the front panel, then clip the center cover.
8. Continue to “Testing new batteries” on page 36.

9PX3K3U_EN Page 35
7. UPS maintenance

• Replacing the EBM(s)

The EBM is heavy. Lifting the cabinet into a rack requires a minimum of two people.

To replace the EBM(s):


1. Unplug the EBM power cable and battery detection cable from the UPS.
If additional EBM(s) are installed, unplug the EBM power cable and battery detection cable
from each EBM.
2. Replace the EBM(s). See "Recycling the used equipment" on page 37 for proper disposal.

A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and
will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.

3. Plug the EBM cable(s) into the battery connector(s). Up to twelve EBMs may be connected to the UPS.
4. Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each
cable.
5. Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).

• Testing new batteries


To test new batteries:
1. Charge the batteries for 48 hours.
2. Press any button to activate the menu options.
3. Select Control then Start battery test.
The UPS starts a battery test if the batteries are fully charged, the UPS is in Normal mode with no active
alarms, and the bypass voltage is acceptable.
During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds.
The front panel displays "Battery test in progress" and the percentage of the test completed.

Page 36 9PX3K3U_EN
7. UPS maintenance

ENGLISH
7.5 Replacing the UPS equipped with a HotSwap MBP or with a PPDM
The HotSwap MBP as well as the PPDM allows to service or replace the UPS without interrupting the
connected loads.
Refer to the specific user manual for more information about this accessory.

• Replacing the UPS equipped with a HotSwap MBP.


To remove the UPS:
1. Press any button to activate the menu options. Select Control then Go to Bypass.
2. Check that the UPS is in Bypass mode (Bypass LED should be On).
3. Turn the HotSwap MBP switch to the Bypass position: the red LED on the HotSwap MBP goes On,
indicating that the load is now powered directly from utility power.
4. Set the Normal AC source switch on the HotSwap MBP to the "O" position and wait for 30s.
5. The UPS stops and can now be disconnected.

To reinstall the UPS:


1. Check that the UPS is correctly connected to the HotSwap MBP.
2. Set the Normal AC source switch on the HotSwap MBP to the "I" position.
3. Press the button to switch On the UPS.
4. Select Control then Go to Bypass (Bypass LED should be On).
5. Turn the HotSwap MBP switch to the Normal position: the red LED on the HotSwap MBP goes Off,
indicating that the load is now powered by the UPS.
6. Select Control then Go back normal.
7. Check that the UPS is in Online mode: the load is now protected by the UPS. (Online LED should be On).

• Replacing the UPS equipped with a PPDM.


To remove the UPS:
1. Press any button to activate the menu options. Select Control then Go to Bypass.
2. Check that the UPS is in Bypass mode (Bypass LED should be On).
3. Remove the center cover of the PPDM front panel.
4. Turn the PPDM switch to the Bypass position: the load is now powered directly from utility power.
5. Press the button to switch Off the UPS.
6. The UPS is in Standby mode and can now be disconnected.

To reinstall the UPS:


1. Check that the UPS is correctly connected to the PPDM.
2. Press the button to switch On the UPS.
3. Select Control then Go to Bypass.
4. Check that the UPS is in Bypass mode (Bypass LED should be On).
5. Turn the PPDM switch to the Normal position: the load is now powered by the UPS.
6. Clip back the center cover of the PPDM front panel.
7. Select Control then Go back normal.
8. Check that the UPS is in Online mode: the load is now protected by the UPS.

7.6 Recycling the used equipment


Contact your local recycling or hazardous waste center for information on proper disposal of the used
equipment.
• Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of
batteries is required. Refer to your local codes for disposal requirements.
• Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and
eyes. It may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead acid
batteries and must be disposed of properly. For more information, contact your local recycling/
reuse or hazardous waste center.

Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper
disposal, contact your local recycling/reuse or hazardous waste center.

9PX3K3U_EN Page 37
8. Troubleshooting

The Eaton 9PX is designed for durable, automatic operation and also alerts you whenever potential
operating problems may occur. Usually the alarms shown by the control panel do not mean that the
output power is affected. Instead, they are preventive alarms intended to alert the user.
• Events are silent status information that are recorded into the Event log. Example = "AC freq in range".
• Alarms are recorded into the Event log and displayed on the LCD status screen with the logo blinking.
Some alarms may be announced by a beep every 3 seconds. Example = "Battery low".
• Faults are announced by a continuous beep and red LED, recorded into the Fault log and displayed on
the LCD with a specific message box. Example = Out. short circuit.
Use the following troubleshooting chart to determine the UPS alarm condition.

8.1 Typical alarms and faults


To check the Event log or Fault log :
1. Press any button on the front panel display to activate the menu options.
2. Press the button to select Event log or Fault log.
3. Scroll through the listed events or faults.

The following table describes typical conditions.

Conditions Possible cause Action


Battery mode A utility failure has occurred and The UPS is powering the equipment
the UPS is in Battery mode. with battery power. Prepare your
equipment for shutdown.
LED is On.
1 beep every 10 seconds.
Battery low The UPS is in Battery mode and This warning is approximate, and the
the battery is running low. actual time to shutdown may vary
significantly.
LED is On. Depending on the UPS load and
1 beep every 3 seconds. number of Extended Battery Modules
(EBMs), the "Battery Low" warning
may occur before the batteries reach
20% capacity.

No battery The batteries are disconnected. Verify that all batteries are properly
connected.
If the condition persists, contact your
service representative.
LED is On.
Beep continuous.
Battery fault The battery test is failed due to Verify that all batteries are properly
bad or disconnected batteries, connected. Start a new battery test :
or the battery minimum voltage is if the condition persists, contact your
reached in ABM cycling mode. service representative.
LED is On.
Beep continuous.
The UPS does not The batteries need charging or Apply utility power for 48 hours to
provide the expected service. charge the batteries. If the condition
backup time. persists, contact your service
representative.
Bypass mode An overload or a fault has Equipment is powered but not
occurred, or a command has been protected by the UPS.
received and the UPS is in Bypass Check for one of the following alarms:
mode overtemperature, overload or UPS
LED is on.
failure.
Power overload Power requirements exceed the Remove some of the equipment from
UPS capacity (greater than the UPS.
100% of nominal; see in table 6 The UPS continues to operate, but
on page 42 for specific output may switch to Bypass mode or shut
LED is On. overload ranges). down if the load increases.
Beep continuous. The alarm resets when the condition
becomes inactive.

Page 38 9PX3K3U_EN
8. Troubleshooting

ENGLISH
UPS overtemperature The UPS internal temperature is If the UPS transferred to Bypass
too high or a fan has failed. mode, the UPS will return to normal
At the warning level, the UPS operation when the temperature drops
generates the alarm but remains 5°C below the warning level.
LED is On. in the current operating state. If the condition persists, shut down
1 beep every 3 seconds. If the temperature rises another the UPS.
10°C, the UPS transfers to Bypass Clear vents and remove any heat
mode or shuts down if Bypass is sources. Allow the UPS to cool.
unusable. Ensure the airflow around the UPS is
not restricted. Restart the UPS.
If the condition continues to persist,
contact your service representative.
The UPS does not start. The input source is not connected Check the input connections.
correctly.
The Remote Power Off (RPO) If the UPS Status menu displays the
switch is active or the RPO "Remote Power Off" notice, inactivate
connector is missing. the RPO input.
Input bad wiring / Input/Output cables are not Connect correctly the Input/Output
Output bad wiring connected to the correct terminal cables.
blocks.

Led is On.
Beep continuous.
MBP disconnected The HotSwap MBP is no more If the HotSwap MBP is connected
connected to the UPS. to the UPS, check that the detection
connector is correctly plugged.

9PX3K3U_EN Page 39
8. Troubleshooting

8.2 Silencing the alarm


Press the ESC (Escape) button on the front panel display to silence the alarm. Check the alarm condition
and perform the applicable action to resolve the condition. If the alarm status changes, the alarm beeps
again, overriding the previous alarm silencing.

8.3 Service and support


If you have any questions or problems with the UPS, call your Local Distributor or your local service
representative and ask for a UPS technical representative.
Please have the following information ready when you call for service:
• Model number

• Serial number

• Firmware version number

• Date of failure or problem

• Symptoms of failure or problem

• Customer return address and contact information

If repair is required, you will be given a Returned Material Authorization (RMA) number. This number must
appear on the outside of the package and on the Bill Of Lading (if applicable). Use the original packaging
or request packaging from the Help Desk or distributor. Units damaged in shipment as a result of improper
packaging are not covered under warranty. A replacement or repair unit will be shipped, freight prepaid for
all warrantied units.

For critical applications, immediate replacement may be available. Call the Help Desk for the
dealer or distributor nearest you.

Page 40 9PX3K3U_EN
9. Specifications

ENGLISH
9.1 Model specifications
Table 1. Power Module model list
Model Power ratings
9PX3K3U 3000VA / 3000W

Table 2. Extended Battery Module model list


Model Configuration Battery voltage For power ratings
9PXEBM180RT Rack / Tower 180Vdc 3000VA

Table 3. Weights and dimensions


Model (UPS) Dimensions D x W x H (mm / in) Weight (lb / kg)
9PX3K3U 722 x 440 x 130 (28.4 x 17.3 x 5.1) 106 / 48
Model (EBM) Dimensions D x W x H (mm / in) Weight (lb / kg)
9PXEBM180RT 645 x 440 x 130 (25.4 x 17.3 x 5.1) 150 / 68

Table 4. Electrical input


Nominal frequency 50/60Hz auto-sensing
Frequency range 50Hz : 40-60Hz before transfer to battery
60Hz : 50-70Hz before transfer to battery
Bypass voltage range -20% / +15% of nominal value (default)
Noise filtering MOV for normal and common mode noise

Model Default input Selectable input Voltages


(Voltage/Current) Voltage range at 100% load
9PX3K3U 208V / 16A 200V, 208V, 220V, 176-276V
230V, 240V

Table 5. Electrical input connections


Model Input connection
9PX3K3U L6-30P cord or Hardwired

9PX3K3U_EN Page 41
9. Specifications

Table 6. Electrical output


All models Normal mode Battery mode
Voltage regulation ±1% ±1%
Efficiency > 98% (High Efficiency mode) > 91%
> 93%
Frequency regulation Sync with line ±5% of nominal line ±0.5% of auto-selected nominal
frequency (outside this range: ±0.5% frequency
of auto-selected nominal frequency)
Nominal output 200/208/220/230/240V (voltage configurable)
3000VA 3000W
Frequency 50 or 60Hz, autosensing or configurable as a frequency converter
Output overload 100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10s
> 150% : load transfers to Bypass mode after 500ms
Output overload 100-125% : no alarm
(Bypass mode) 125-150% : UPS shuts down after 1 minute
> 150% : UPS shuts down after 1s
Voltage waveform Sinewave
Harmonic distortion < 2% THDV on linear load
< 5% THDV on non-linear load
Transfer time Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Power factor 1
Load crest ratio 3 to 1

Table 7. Electrical output connections


Model Output connection
9PX3K3U Hardwired
(2) L6-30R
(2) L6-20R

Table 8. Environmental and safety


EMC certifications IEC/EN 62040-1: 2008
IEC/EN 62040-2: 2006 Cat. C2
IEC/EN 62040-3: 2011
IEC 60950-1
UL 1778 4th
CSA 22.2
EMC (Emissions)* CISPR22 Class A
AS/NZS 22 Class A
IEC 61000-3-2 (-3-12)
IEC 61000-3-3 (-3-11)
FCC part 15 Class A
EMC (Immunity) IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
* for output cable < 10m.

Page 42 9PX3K3U_EN
9. Specifications

ENGLISH
Agency markings CE / cULus / energy star
Operating temperature 0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note: thermal protection switches load to Bypass in case of overheating.
Storage temperature 0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
Transit temperature -25 to 55°C (-13 to 130°F)
Relative humidity 0 to 95% no condensing
Operating altitude Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Transit altitude Up to 10,000 meters (32,808 ft) above sea level
Audible noise < 45 dBA at 1 meter typical

Table 9. Battery
Internal batteries EBM
Rack / Tower 9PX3K3U: 180Vdc 9PXEBM180RT: 180Vdc
configuration
Type Sealed, maintenance-free, valve-regulated, lead-acid,
with minimum 3-year float service life at 25°C (77°F).
Lifetime is reduced above 30°C.
Monitoring Advanced monitoring for earlier failure detection and warning
Battery port External three-pole SBS75G Black connector on UPS for connection to EBM
EBM battery 40cm (15.7in)
cable length

Table 10. Communication options


Communication bay (1) available independent communication bay for connectivity cards
Compatible connectivity Network-MS
cards Modbus-MS
Relay-MS
Communication ports RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
Relay output contacts (4) relay outputs (normally open or normally closed)
Remote On/Off 2 pins jumper (normally open)
Remote Power Off 3 pins jumper (normally open or normally closed)

9PX3K3U_EN Page 43
EATON
Customer Care Center

Technical Support and Product Services


Technical questions? If you encounter a problem while following the instructions in this manual, or have
? questions about the operation, repair, or servicing of your equipment, please visit our web site www.
eaton.com for complete service information.
To insure that your questions are correctly answered, please obtain the part number, assembly number, and
serial number of the unit and include them in any discussions or correspondence.

Part Number: ________________________________________________________________________________________________

Assembly Number:__________________________________________________________________________________________

Serial number:_______________________________________________________________________________________________

Who To Contact
For Technical Support, Customer Care Center, Customer FAQ please visit our website: www.eaton.com

Scheduling Field Service Engineer Support


Scheduling of the EATON Field Service Engineers typically should be done 7 to 10 days before they are required
on-site. If the startup of the UPS is critical to maintaining your schedule, please contact EATON, to insure a safe
installation and start-up that will maintain the EATON warranty and insure smooth performance.

Return Policy for Single Phase Products (RMA)


Should you require factory service for your equipment, contact EATON Customer Care Center and obtain a Return
Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to EATON without first obtaining
an RMA number.
For further details please visit our website: www.eaton.com

Date: _______________________________________________________________________________________________________

RMA Number: _______________________________________________________________________________________________

Contact Name:_______________________________________________________________________________________________

Page 44 9PX3K3U_EN
10. Glossary

ENGLISH
Bypass AC source Source supplying the bypass line. The equipment can be transferred to the
bypass line if an overload occurs on the UPS output, for maintenance or in
the event of a malfunction.

Frequency converter Operating mode used to convert the AC-power frequency between the UPS input
and output (50Hz -> 60Hz or 60Hz -> 50Hz).

Low-battery warning This is a battery-voltage level indicating that battery power is low and that
the user must take action to prevent the imminent break in the supply of power
to the load.

Backup time Time during which the load can be supplied by the UPS operating on battery
power.

Load Devices or equipment connected to the UPS output.

HE mode Operating mode by which the load is supplied directly by the AC source if it is
within the tolerances defined by the user. This mode reduces the consumption
of electrical power

Manual bypass Rotary switch controlled by the user, used to connect the loads directly to the
AC source. Transfer of the load to the manual bypass enables UPS maintenance
without interrupting the supply of power to the connected loads.

Normal (double The normal UPS operating mode in which the AC source supplies the UPS which
conversion) mode in turn supplies the connected loads (after electronic double conversion).

Normal AC source Normal source of power for the UPS.

Relay contacts Contacts supplying information to the user in the form of signals.

UPS Uninterruptible Power Supply.

9PX3K3U_EN Page 45
Page 46 9PX3K3U_EN

You might also like