0% found this document useful (1 vote)
336 views

Project Name: Standpipe & Hose System of Norban Comtex LTD Area Reference: Most Unfavourable

This document provides a 3-page printout of hydraulic calculations for a standpipe and hose system from a computer program. It includes project details, operating sprinkler heads and nozzles, and details on 19 hydraulically significant pipes in the system including pipe sizes, lengths, angles, heights, velocities, and pressures. The source duty is 764.4 l/min at 6.557 bar and there are no heads below required pressures.

Uploaded by

rashal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
336 views

Project Name: Standpipe & Hose System of Norban Comtex LTD Area Reference: Most Unfavourable

This document provides a 3-page printout of hydraulic calculations for a standpipe and hose system from a computer program. It includes project details, operating sprinkler heads and nozzles, and details on 19 hydraulically significant pipes in the system including pipe sizes, lengths, angles, heights, velocities, and pressures. The source duty is 764.4 l/min at 6.557 bar and there are no heads below required pressures.

Uploaded by

rashal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Full Hydraulic Calculations Computer Printout Page No 1

Submitted by Engr Md. Maksudul Hasan Project: Standpipe & Hose System of Norban Comtex Ltd
Address: Kasimpur. Gazipur
Number: SA-NCL-5H-V1.0
Area ref: Most Unfavourable
Hazard: Ordinary
Authority: National Fire Protection Association
Source: 764.4 l/min @ 6.557 bar
Tel: Fax:

Project Data and Design Parameters


Project name : Standpipe & Hose System of Norban Comtex Ltd
Area reference : Most Unfavourable
Address / location : Kasimpur. Gazipur
Project number : SA-NCL-5H-V1.0
Installation number(s) : 0
Drawing number(s) : SA-NCL-5H-V1.0
Issue no / date : 13.07.2016
Designers reference : 5th floor
Project Data File : F:\DeFire BD
Hazard classification : Ordinary
Design authority : National Fire Protection Association
Insurance company : ---
Specified density of discharge : 0.00 mm/min (l/min/m2)
Assumed maximum area of operation : 0.00 m2
Number of operating sprinkler heads : 2
Maximum area covered per head : 0.00 m2
Highest head / nozzle above source : 0.00 m
Number of pipes in system : 19 from 40 to 150 mm
Pressure loss equation used : Hazen-Williams
Fluid : Water
Pipe Data Table : STD_PIPE.PDT
Maximum fluid velocity : 4.68 m/s in pipe 116 117
Volume of pipework and fittings : 1.23 m3
Elbows are welded for : 65 mm and above
Comment : ---
Checked by & Date :

Source duty = 764.4 l/min @ 6.557 bar at node no 100

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email [email protected] Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 2
Submitted by Engr Md. Maksudul Hasan Project: Standpipe & Hose System of Norban Comtex Ltd
Address: Kasimpur. Gazipur
Number: SA-NCL-5H-V1.0
Area ref: Most Unfavourable
Hazard: Ordinary
Authority: National Fire Protection Association
Source: 764.4 l/min @ 6.557 bar
Tel: Fax:

Operating Sprinkler Heads, Nozzles and Hydrants


Head|Node| Size | 'K' |F l o w|A r e a|Density mm/min|Pressure bar|Heights|Pipe
no | no | mm | factor| l/min | m2 |Req.d Actual| Min Actual| m | no
5 117 178.19 386.4 0.000 0.00 0.00 4.50 4.703 15.370 17
6 119 178.19 378.0 0.000 0.00 0.00 4.50 4.500 18.420 19

0 heads are under the required density / minimum pressures

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email [email protected] Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 3
Submitted by Engr Md. Maksudul Hasan Project: Standpipe & Hose System of Norban Comtex Ltd
Address: Kasimpur. Gazipur
Number: SA-NCL-5H-V1.0
Area ref: Most Unfavourable
Hazard: Ordinary
Authority: National Fire Protection Association
Source: 764.4 l/min @ 6.557 bar
Tel: Fax:

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size Type| L/min | Length VJ|Dir. | Eq.len | Start | Start Frict
no | End |Bore 'C'| Vel m/s |EL T VT|Slope| mbar/m | End | End Static
1 100 150mm MW 764.4 1.000 Up 11.14 0.000 6.557 -0.004
101 155.32 120 0.7 0 0 MV 90.0 0.4 1.000 6.455 -0.098
2 101 150mm MW 764.4 0.650 Up 3.82 1.000 6.455 -0.002
102 155.32 120 0.7 0 0 BV 90.0 0.4 1.650 6.389 -0.064
3 102 150mm MW 764.4 3.210 0 6.06 1.650 6.389 -0.002
103 155.32 120 0.7 1 0 0.0 0.4 1.650 6.387 +0.000
4 103 150mm MW 764.4 9.440 90 12.29 1.650 6.387 -0.005
104 155.32 120 0.7 1 0 0.0 0.4 1.650 6.382 +0.000
5 104 150mm MW 764.4 26.330 180 29.18 1.650 6.382 -0.012
105 155.32 120 0.7 1 0 0.0 0.4 1.650 6.371 +0.000
6 105 150mm MW 764.4 15.680 90 18.53 1.650 6.371 -0.007
106 155.32 120 0.7 1 0 0.0 0.4 1.650 6.363 +0.000
7 106 100mm MW 764.4 1.520 Up 3.61 1.650 6.363 -0.010
107 105.14 120 1.5 1 0 90.0 2.7 3.170 6.205 -0.149
10 107 100mm MW 764.4 3.050 Up 3.05 3.170 6.205 -0.008
110 105.14 120 1.5 0 0 90.0 2.7 6.220 5.898 -0.299
12 110 100mm MW 764.4 3.050 Up 3.05 6.220 5.898 -0.008
112 105.14 120 1.5 0 0 90.0 2.7 9.270 5.591 -0.299
14 112 100mm MW 764.4 3.050 Up 3.05 9.270 5.591 -0.008
114 105.14 120 1.5 0 0 90.0 2.7 12.320 5.284 -0.299
16 114 100mm MW 764.4 3.050 Up 3.05 12.320 5.284 -0.008
116 105.14 120 1.5 0 0 90.0 2.7 15.370 4.977 -0.299
17 116 40mm MW 386.4 1.400 180 4.12 15.370 4.977 -0.274
117 41.86 120 4.7 0 1 0.0 66.5 15.370 4.703 +0.000
18 116 100mm MW 378.0 3.050 Up 3.05 15.370 4.977 -0.002
118 105.14 120 0.7 0 0 90.0 0.7 18.420 4.676 -0.299
19 118 40mm MW 378.0 1.400 180 2.76 18.420 4.676 -0.176
119 41.86 120 4.6 1 0 0.0 63.9 18.420 4.500 +0.000

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email [email protected] Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 4

MRH

BV MV 100

FHC - Hydraulic Analysis Software - Ver: 1.8.0


By CANUTE LLP - Email [email protected] Web www.canutesoft.com
Program FHC