Power Factor Corrector Calculation: System Parameters

The document calculates the power factor correction needed for a 3 phase system with 45 kW of load power at 0.6 power factor. It determines that a 32.11 kVAR capacitor bank is needed to correct the power factor to 0.85. It recommends using a 36 kVAR bank consisting of three 12 kVAR capacitors connected in delta, with each capacitor rated at 200.57 uF.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views1 page

Power Factor Corrector Calculation: System Parameters

The document calculates the power factor correction needed for a 3 phase system with 45 kW of load power at 0.6 power factor. It determines that a 32.11 kVAR capacitor bank is needed to correct the power factor to 0.85. It recommends using a 36 kVAR bank consisting of three 12 kVAR capacitors connected in delta, with each capacitor rated at 200.57 uF.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Power Factor Corrector Calculation

System Parameters
Voltage : 230 V Choose Voltage
Phase : 3
Frequency : 60 Hz
Load Parameters
Power Factor (Uncorrected) : 0.6000 Input uncorrected Power Factor
Power Factor (Corrected) : 0.8500 Input wanted Power Factor
Load Power (kW) : 45.00 Input Load Power in kW

Calculation Table (Capacitor Bank)


P (kW) Q (kVAR) PF ϴ Qcorrector = Q(Corrected) - Q(Uncorrected)

Uncorrected : 45.00 60.00 0.6 53.13 Qcorrected = (Pload/PFnew)*(sin(acos(Pfnew)))

Corrector : 0.0000 -32.11 0.0000 90 Pload (corrected) = Pload(uncorrected) + P(corrector)

Corrected : 45.00 27.89 0.8500 31.79

Capacitor Bank Rating : -32.11 kVAR


Recommended Bank Rating (Q) : 36.00 kVAR Input Recommended Bank rating based on Computed bank rating

No. Of Parallel Capacitors : 3 Input Number of parallel caps to meet Recommended Bank Rating

kVAR Rating for Each Capacitor : 12 kVAR Reference Manufacturer: TDK Film Capacitors - Power factor correction

Capacitance (C), DELTA CONNECT : 200.57 uF x3 Capacitance Calculation is based on Recommended Bank Rating

Reactance (Xc) : 13.23 Ω Q/3 = (V^2)/Xc = (V^2)*(2πfC)


Line Current (I) : 30.12 A C = Q/(3*(V^2)*(2πf))
Xc = 1/(2πfC)
Note: Capacitance can be paralleled to reduce individual uF Rating. I = sqrt(3)*(V/Xc)

Load Power = 45
kW
PF = 0.60 LAG

The kVAR Needed to correct the power factor from 0.6000 LAG to 0.8500 LAG is 32.11 kVAR.
Therefore: Use 3 - 12 kVAR, 230 Vac, Delta connected, 3x200.5 uF, 60 Hz Capacitors