Thyristor control unit - Compact design TST3
3-phase control
Fully controlled
Phase-angle and burst control
(switchable)
Multi control signal
Industrial design
Technical data
1. Functions 8a. Control contact 2-7-8
Operation modes Function: set point adjustment (direct proportional
PH Phase-angle setting of firing angle)
SP Burst control Input impedance: 500Ω/50kΩ (switchable)
Actuation: potentiometer 2.5 to 47kΩ
2. Indicators (not included)
LED 1 green Ready for operation Line length: max. 10m, twisted pair
LED 1 red: General fault
LED 2 green: Device activated 8b. Control contact 7-8
LED2 orange: Device activated and working Function: set point adjustment (direct proportional
Subject to alterations and errors
LED 3 orange ON/OFF: 100% voltage output setting of firing angle)
LED 4 yellow: Level of signal Input impedance: 500Ω/50kΩ (umschaltbar)
Actuation: external signaling voltage 0 to 10V
3. Mechanical design or signaling current 0 to 20mA
Aluminium housing, IP rating IP 20 ine length: max. 10m, twisted pair
mounted on mounting plate
Mounting position: any 8c. Control contact 8-11
Control circuit: Function: inverted set point adjustment (indirect
Terminal capacity: 1 x 1.5mm2 proportional setting of firing angle)
Initial torque: 0.5Nm Input impedance: 5kΩ
Actuation: external signaling voltage 0 to 10V
Power circuit: Line length: max. 10m, twisted pair
Shockproof terminal covers,
IP rating IP 20 8d. Control contact 8-12
Terminal capacity: 1 x 16mm2 with/without multicore cable end Function: set point adjustment (direct proportional
setting of firing angle)
4. Control circuit Input impedance: 10kΩ
Supply voltage: 230V AC (optional 110V, 400V, 500V AC Actuation: puls-width-modulated signal
or internal generated) terminals 22-24 Line length: max. 10m, twisted pair
Tolerance: ±15%
Rated frequency: 45 to 65Hz 9. Control contact9-10
Duration of operation: 100% Function: interlock of power circuit
Connection: potential free
5. Control contact 1-2 Loadable: No
Function: activation Line length: max.10m, twisted pair
Connection: potential free
Loadable: No 10. Signaling contact 13-14-15
Line length: max. 10m, twisted pair 1 potential free change-over contact
Function: general fault
6. Control contact 3-4 Switching capacity: 3A/230V AC1
Function: reset
Connection: potential free 11. Signaling contact 16-17-18
Loadable: No 1 potential free change-over contact
Line length: max.10m, twisted pair Function: indication 100% voltage output
Switching capacity: 3A/230V AC1
7. Control contact 5-6
Function: PTC-temperature monitoring 12. Signaling contact 19-20-21
Initial resistance: <1.0kΩ 1 potential free change-over contact
Response value (relay in off-position): ≥2.0kΩ Function: indication normal operation / general fault
Release value (relay in on-position): ≤1.0kΩ Switching capacity: 3A/230V AC1
Disconnection (short circuit thermistor): no
Measuring voltage 5-6: max. 18V DC
Release 02/04 10.01-1
TST3
Technical data
13. Power circuit 15. Ambient conditions
Supply voltage: 3~ 110 to 500V terminals L1-L2-L3 Ambient temperature: -25 to +55°C (according toIEC 68-1)
Tolerance: 10% Storage temperature: -25 to +75°C
Rated frequency: 48 to 63Hz Transport temperature: -25 to +75°C
Relative humidity: 5% to 95% not condensing
14. Power classes (according toIEC 721-3-3 class 3K3)
TST3 05 Rated current 3~ 5A Pollution degree: 2 (according toIEC 664-1)
TST3 15 Rated current 3~ 15A
TST3 25 Rated current 3~ 25A
TST3 35 Rated current 3~ 35A
TST3 50 Rated current 3~ 50A
Functions
The TST3 offers five types of setpoint adjustment.l Burst control:
For power control the device clocks the output voltage. Depending
Potentiometer actuation on the setting of the remote control potentiometer, the output of the
Direct or indirect (if inverse wired) setting of firing angle via potentio- device is disconnected from the power supply for short periods. Over
meter. a control period therefore, the power draw of the connected load
is reduced by the value set on the potentiometer. Since the load is
Signaling voltage 0-10V switched on and off only at zero crossing, the supply system is not
Direct setting of firing angle proportional to value of applied signaling subjected to additional reactive power components or harmonics by
voltage 0-10V the ESGT-SP(N). This power control can only be used for slow-acting
loads (such as heating elements) as the operation of loads such as
Inverted signaling voltage10-0V motors and lighting systems is disturbed by the off-times.
Indirect setting or firing angle indirect proportional to value applied at
signaling input.
Supply voltage
Signaling current 0-20mA
Direct proportional setting of firing angle via 0-20mA signaling current.
Subject to alterations and errors
Puls-width-modulated signal
Firing angle is set proportional to pulse-pause ratio of the applied
signaling voltage (5V, 5-10kHz).
Voltage output TST3 at 50%
The control of the output power is achieved by reducing nominal
voltage at the power output terminals T1 to T3. This can be provided
by two different principles wich can be preselected.
Phase-angle control:
A thyristor bridge is set by the remote control potentiometer so that
the thyristor switches the connected loads to the supply network in
every sinusoidal half-wave only when the selected voltage level is
reached. This produces a reduced rms voltage and therefore a small-
er power draw by the load. This type of power control is suitable for all
types of ohmic and inductive loads.
In three-wire systems (without a neutral conductor) the output power
can be infinitely regulated from around 20% to 100%; in four-wire sys-
tems (3~/N) it can be infinitely regulated from around 5% to 100%.
Supply voltage
Voltage output TST3
Set point approx. 50%
TST3
Connections
Power circuits:
Phase-angle or burst control connection in 4-wire Burst control connection
supply systems in 3-wire supply systems
L1
L2
L1 L3
L2 N
L3 PE
N
PE
F 1-3 F 01
F 1-3 F 01
L1 L2 L3 PE 22 24
L1 L2 L3 PE 22 24
TST3
TST3
T1 T2 T3
T1 T2 T3
Subject to alterations and errors
L1 L2 L3 PE
L1 L2 L3 N PE
Load
3~400V
Load without neutral
wire connection
Activation
Fan Activation
TST3
Reset
Reset
not included
PTC or strap
not included
PTC or strap
Setpoint device
(SPC, controller etc.)
Setpoint device
(SPC, controller etc.)
Control circuit:
140mm
0 to +10V
Mass
55mm
Mass
+10 to 0V Device locked
Device locked
Dimensions
Connections
180mm
Master alarm
Inverted actuation 10-0VDC
200mm Master alarm
100% output voltage reached 100% output voltage reached
Signaling outputs
Device in operation
Signaling outputs
Device in operation
Actuation via signaling voltage 0-10VDC
Supply voltage
135mm
Supply voltage
Switch in position 0-10V Switch in position 0-10V
www.tele-power-net.com
Activation
Activation
Reset
Reset
not included
PTC or strap
PTC or strap
Setpoint device
(SPC, controller etc.)
Mass
Device locked
Device locked
Master alarm Master alarm
100% output voltage reached 100% output voltage reached
Signaling outputs
Device in operation
Signaling outputs
Device in operation
Actuation via potentiometer TELE R20
Actuation via signaling current 0-20mA
Supply voltage Supply voltage
Switch in position 0-10V Switch setting 0-20mA
Subject to alterations and errors