Asd
Asd
Asd
1
05/08/2019
Uses
2
05/08/2019
One (1) (Q.T.) for every 10,000 kgs or fraction thereof for
each size
Test Specimen :
Variation in Mass, % :
DPWH Specification:
Variation in Mass, % : Shall not exceed 6% under nominal weight
except for bars smaller than 3/8 in. (10 mm)
plain round. In no case shall the overweight
be the cause for rejection.
3
05/08/2019
4
05/08/2019
AASHTO M 31 ( 2003 )
STANDARD SPECIFICATIONS FOR DEFORMED AND PLAIN STEEL BARS
FOR CONCRETE REINFORCEMENT
Strength Requirements:
Grade Tensile Strenght , MPa, min. Yield Stenght , Mpa, min.
Elongation Requirements:
Bar Designation No. / mm Grade 280(40) Grade 420 (60) Grade 520(75)
No. 3 ( 10 ) 11 9 -
No. 4, 5 ( 13, 16 ) 12 9 -
No. 6 ( 19 ) 12 9 7
No. 7, 8 ( 22, 25 ) - 8 7
No. 9,10,11 ( 29, 32, 36 ) - 7 6
No. 14, 18 ( 43, 57 ) - 7 6
Footnotes:
5
05/08/2019
Elongation Requirements:
PERCENT ELONGATION
GRADE BAR DIAMETER, mm
NON – WELDABLE WELDABLE
230 < 25 mm 18 20
≥ 25 mm 16 18
275 < 25 mm 10 16
≥ 25 mm 8 14
425 < 25 mm 8 14
≥ 25 mm 7 12
Nominal X-Sect. Area, mm2 78.54 113.10 201.06 314.16 490.88 615.75 804.25 1017.88 1256.64
Max. Ave. Spacing, mm 7.0 8.4 11.2 14.0 17.25 19.6 22.4 25.2 28.0
Min. Lug Height, mm 0.4 0.5 0.7 1.0 1.2 1.4 1.6 1.8 2.0
Max. Lug Height, mm 0.8 1.0 1.4 2.0 2.4 2.8 3.2 3.6 4.0
Max. Summ. Of Gaps, mm 7.8 9.4 12.6 15.7 19.6 22.0 25.1 27.5 31.41
Variation in Mass, % ± 6 ± 6 ± 6 ±6 ± 6 ± 6 ± 6 ± 6 ± 6
Note : * Tensile srength shall not be less than 1.25 times the actual yield strength. TS / TY for
Weldable ≥ 1.25
6
05/08/2019
DPWH Specification:
7
05/08/2019
DPWH Specification:
8
05/08/2019
T. Urmaza
S. Orate CLARITA C. FLORES
J. Tagalo Engine e r V
J. B e rgonio
C. de la Cruz ATTESTED :
Witnessed by:
9
05/08/2019
Const. Of 2 Storey RGR Type Sch. Bldg. At Dona Ma. Platon Laurel, Aya, Talisay, Bats.
Project : Const. Of Circumferential Road Around Lake Taal, Agoncillo, Bats.
Completion of Aya-Tranca-Talisay Road, Talisay, Bats.
Kind of material : Reinforcing Steel Bar ( 16 mm dia., deformed )
Sample identification : DMP- 5
Quantity represented : 10,000 kgs.
Sampled at : Stockpile at jobsite
Original source : Top Steel
Supplied by : Revere Construction & Supply
Proposed use : for concrete reinforcement
Spec's Item No. : PNS 49 Grade 275 NW
Sampled by : F. Opena,Lab. Tech. II DP WH-Bats. 3rd DEO 06-08-06
(Name & designation) (Office) (Date)
Submitted by : Ma. B. M. Marquez - do - 6-14-06
(Name & designation) (Office) (Date Received)
Lab. No. : 1718-06 ( Paid under OR No. 2595342 )
10
05/08/2019
Retests
If any tensile property of any tension test specimen is less than
that specified, and any part of the fracture is outside the middle
third of the gage length, as indicated by scribe scratches marked
on the specimen after testing, a retest shall be allowed.
11
05/08/2019
Retests
If a weight ( mass ) test fails for reasons other than flaws in the
specimen, a retest shall be permitted on two random specimens
from the same lot. Both retest specimens shall meet the
requirements of the specification.
12
05/08/2019
Strength Requirements:
Individual - 3.45 Mpa (500 psi) Minimum
Average - 4.14 Mpa (600 psi) Minimum
Absorption - -
Moisture Content - -
Strength Requirements:
Individual - 3.45 Mpa (500 psi) Minimum
Average - 4.14 Mpa (600 psi) Minimum
Absorption - -
Moisture Content - -
13
05/08/2019
Gross Cross Sectional Area of the Unit, mm2 = is the total area of a
section perpendicular to the direction of the load,
including areas within cells.
14
05/08/2019
15
05/08/2019
16
05/08/2019
Sample Identification 1 2
3
150 150 150
1. Width, mm - - - - - - - - - - - -
400 400 400
2. Length, mm - - - - - - - - - - -
200 200 200
3. Height, mm - - - - - - - - - - -
60,000 60,000 60,000
4. Gross-cross sectional area, mm - -
5. Compressive Strength:
66,000# 76,000# 67,000#
Ultimate Load, kg
Compressive Strength, MN/m2 4.9 5.6 5.0
Compressive Strength, MN/2 (Avg. of 3 units) 5.2
17
05/08/2019
COMPUTATION:
Moisture Content, % (1) - (2) 1666 - 1624
--------------- x 100 = -------------------- x 100 = 28
(3) - (3) 1776 - 1624
L. Casanova
T. Urmaza CLARITA C. FLORES
S. Orate Engine e r V
J. Bergonio ATTESTED:
J. Tagalo
Witne s s e d by :
18
05/08/2019
B ASILIA S. VILLANUEVA
Engine e r IV JUDY F. SESE
OIC, B ure au Dire ctor
19
05/08/2019
II 50.0 75.0 27.6 Mpa (4000 psi) 27.6 Mpa (4000 psi)
III 65.0 100.0 27.6 Mpa (4000 psi) 27.6 Mpa (4000 psi)
IV 100.0 150.0 34.5 Mpa (5000 psi) 27.6 Mpa (4000 psi)
V 140.0 175.0 41.4 Mpa (6000 psi) 41.4 Mpa (6000 psi)
Basis of Acceptance:
Load Bearing Test - shall be determine by the results of :
a. three –edge bearing tests to produce a 0.3 mm crack and the
ultimate load (strength) of the pipe
b. Absorption test on selected samples of concrete from the wall of
the pipe
c. Visual inspection of the finished pipe to determine its
conformance with the accepted design and its freedom from
defects.
20
05/08/2019
Length, mm 990 min. 990 min. 990 min. 990 min. 990 min.
REINFORCEMENT
Spacing, mm 100 max. 100 max. 100 max. 150 max. 150 max.
Alternative Requirements:
- 1 - set consisting of 3 cylinder samples -
For not more than 25 pipes cast in the field
- 1 – Inspection Report for each size for not more
than 25 pipes cast in the field
- For cement, fine aggregate and water – testing is
sample for Item 405 (Structural Concrete)
21
05/08/2019
- Proof of design
Absorption Test
Significance :
The crushing test can be either a quality control test performed to
establish that the finished pipe has sufficient strength to withstand
the crushing loads stated in the specifications or a proof of design
testing performed to prove the adequacy of design.
Record the load to produce a 0.3 mm crack. The 0.3 mm crack load is the
maximum load applied to the pipe before a crack having a width
of 0.3 mm occurs throughout a continuous length of 300 mm or
more measured parallel to the longitudinal axis of pipe barrel.
22
05/08/2019
Dimensions:
1. Actual internal diameter, mm - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- 600
2. Thickness of wall, mm - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 85
3. Laying length, mm - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1000
3a. Laying length, m - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1
Strength Test
4. Load to produce 0.3 mm crack, kg - - - - - - - - - - - - - - - - - - - - - - - - - - - ------ - - - - - - - 3410
5. Ultimate load, kg - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5681
Reinforcement:
Type of reinforcement: Circular _______________________ Elliptical ______________________
6. Diameter, mm - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5.29
7. No. of lines ------------------------------------------------- 1
8. No. of hoops - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 13
9. Spacing, mm - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 80
10. Not protective covering, mm - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ----- 40
Absorption Test
Computation
Strength:
(4) X (9.8) 3410 x 9.8
Load to produce 0.3 mm crack /m/mm = --------------- = --------------- = -- 56
(3a) x (1) 1 x 600
23
05/08/2019
Absorption, %
24
05/08/2019
Proje ct :
Subic Port Development Project - SBMA
Kind and Clas s :
RCCP 750 mmØ Circular Class IV Wall B
Quantity re pre s e nte d :
50 pcs.
Sample d at :
Supermix Redi-Concrete Casting Yard
Original s ource :
Supermix Redi-Concrete
Propos e d us e :
Access Road
Spe c's Ite m No. :
ASTM C-76 M Class IV Wall B
Sample d by :
R. Benito-Engrs. Rep. PCI 10-23-04
(Name & de s ignation) (Office ) (Date )
Submitte d by : R. Testado- not stated A.M. Oreta & Co., Inc. 11-8-04
(Name & de s ignation) (Office ) (Date re ce ive d)
Lab. No. : 5990-04 (Paid under OR # 3708704)
Proje ct :
Subic Port Development Project - SBMA
Kind and Clas s :
RCCP 750 mmØ Circular Class IV Wall B
Quantity re pre s e nte d :
50 pcs.
Sample d at :
Supermix Redi-Concrete Casting Yard
Original s ource :
Supermix Redi-Concrete
Propos e d us e :
Access Road
Spe c's Ite m No. :
ASTM C-76 M Class IV Wall B
Sample d by :
R. Benito-Engrs. Rep. PCI 10-23-04
(Name & de s ignation) (Office ) (Date )
Submitte d by : R. Testado- not stated A.M. Oreta & Co., Inc. 11-8-04
(Name & de s ignation) (Office ) (Date re ce ive d)
Lab. No. : 5990-04 (Paid under OR # 3708704)
25