Micom P438: Rail Catenary Protection Device P438/En M/Cf8
Micom P438: Rail Catenary Protection Device P438/En M/Cf8
Micom P438: Rail Catenary Protection Device P438/En M/Cf8
P438/EN M/Cf8
Technical Manual
P438/UK M/De7
Technical Manual
! Warning
When electrical equipment is in operation dangerous voltage will be present in certain parts of the equipment.
Failure to observe warning notices, incorrect use or improper use may endanger personnel and equipment
and cause personal injury or physical damage.
Before working in the terminal strip area, the device must be isolated. Where stranded conductors are used,
insulated crimped wire end ferrules must be employed.
The signals 'M a i n : B l o c k e d / f a u l t y ' and 'S F M O N : W a r n i n g ( L E D ) ' (permanently assigned to the LEDs
labeled 'OUT OF SERVICE' and 'ALARM') can be assigned to output relays to indicate the health of the
device. Schneider Electric strongly recommends that these output relays are hardwired into the
substation's automation system, for alarm purposes.
Any modifications to this device must be in accordance with the manual. If any other modification is made
without the express permission of Schneider Electric, it will invalidate the warranty, and may render the
product unsafe.
Proper and safe operation of this device depends on appropriate shipping and handling, proper storage,
installation and commissioning, and on careful operation, maintenance and servicing.
For this reason only qualified personnel may work on or operate this device.
The User should be familiar with the warnings in the Safety Guide (SFTY/4LM/G11 or later version), with the
warnings in Chapters 5, 9, 10 and 11 and with the content of Chapter 13, before working on the equipment. If
the warnings are disregarded, it will invalidate the warranty, and may render the product unsafe.
A protective conductor (ground/earth) of at least 1.5 mm2 must be connected to the DHMI protective
conductor terminal to link the DHMI and the main relay case; these must be located within the same
substation.
To avoid the risk of electric shock the DHMI communication cable must not be in contact with hazardous live
parts.
The DHMI communication cable must not be routed or placed alongside high-voltage cables or connections.
Currents can be induced in the cable which may result in electromagnetic interference.
Qualified Personnel
are individuals who
are familiar with the installation, commissioning and operation of the device and of the system to which it is being connected;
are able to perform switching operations in accordance with safety engineering standards and are authorized to energize and de-
energize equipment and to isolate, ground and label it;
are trained in the care and use of safety apparatus in accordance with safety engineering standards;
are trained in emergency procedures (first aid).
Note
The operating manual for this device gives instructions for its installation, commissioning and operation. However, the manual cannot
cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do
not take any action without proper authorization. Contact the appropriate Schneider Electric technical sales office and request the
necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric, including settlement of
warranties, result solely from the applicable purchase contract, which is not affected by the contents of the operating manual.
3
Notes:
This manual (P438/EN M/De7) is based on the P438-305/307-409/410/411-613 full manual
(P438/EN M/Bd7) but incorporates all the changes up to (and including) version
P438-305-409/410/411-615.
All parts of this manual that are not affected by the product upgrade have not been modified in any
way and therefore still show the -613 version in the footer.
Software version -615 is compatible with two different hardware versions, -305 and -307, which are
therefore both covered in this manual. The only difference is that hardware version -307 was designed
for another communication module, the “Dual Redundant Ethernet Board” (REB). At the time of
publishing the P438 -615 manual, however, the REB module had not been released yet but became
available with hardware version -308, see the Upgrade Description P438 -308 -616.
3 Operation 3-1
3.1 Modular Structure 3-1
3.2 Operator-Machine Communication 3-3
3.3 Configuration of the Measured (Function Group HMI) 3-4
Value Panels
3.4 Serial Interfaces 3-8
3.4.1 PC interface (Function Group PC) 3-8
3.4.2 Communication Interface 1 (Function Group COMM1) 3-10
3.4.3 Communication Interface 2 (Function Group COMM2) 3-19
3.4.4 Communication Interface 3 (Function Group COMM3) 3-22
3.4.5 Communication Interface (Function Groups IEC 3-27
IEC 61850 GOOSE and GSSE)
3.5 IRIG-B Clock Synchronization (Function Group IRIGB) 3-34
3.6 Configurable Function Keys (Function Group F_KEY) 3-35
3.7 Configuration and Operating Mode (Function Group INP) 3-38
of the Binary Inputs
3.8 Measured Data Input (Function Group RTDmA) 3-40
3.8.1 Direct Current Input 3-41
3.8.2 Input for Connection of a 3-45
Resistance Thermometer
3.9 Configuration, Operating Mode, and (Function Group OUTP) 3-46
Blocking of the Output Relays
3.10 Measured Data Output (Function Group mA_OP) 3-49
3.10.1 BCD Measured Data Output 3-52
3.10.2 Analog Measured Data Output 3-54
3.10.3 Output of ‘External’ Measured Data 3-60
3.11 Configuration and Operating Mode (Function Group LED) 3-61
of the LED Indicators
3.12 Main Functions of the P438 (Function Group MAIN) 3-64
3.12.1 Conditioning of the Measured 3-64
Values
3.12.2 Operating Data Measurement 3-68
3.12.3 Configuring and Enabling the 3-77
Protection Functions
4 Design 4-1
4.1 Designs (Case Types) 4-2
4.2 Dimensional Drawings 4-4
4.2.1 Surface-Mounted Case 4-4
4.2.2 Flush-Mounted Case 4-5
4.2.3 Device View of Connection for the Detached User Interface (HMI) 4-7
4.3 Modules 4-8
7 Settings 7-1
7.1 Parameters 7-1
7.1.1 Device Identification 7-2
7.1.2 Configuration Parameters 7-6
7.1.3 Function Settings 7-52
7.1.3.1 Global 7-52
7.1.3.2 General Functions 7-56
7.1.3.3 Setting Groups 7-66
9 Commissioning 9-1
9.1 Safety Instructions 9-1
9.2 Commissioning Tests 9-3
10 Troubleshooting 10-1
11 Maintenance 11-1
12 Storage 12-1
Appendix
TERMINOLOGY NOTE:
The P438 menu texts ("Data Model") referred to throughout this manual are
regional texts which have been customised for the UK market. Most diagrams contained
in this manual use the same terminology. Some diagrams however contain standard
English menu texts when those were very similar to the "regional" ones and modifying
those diagrams was not deemed essential to comprehension. In those diagrams,
references are made to "Parameter Set(s)": This is the direct equivalent to the regional
term "Setting Group(s)". Similarly, the terms "PSx", "PS1", "PS2", "PS3" and "PS4" are
respectively equivalent to "SGx", "SG1", "SG2", "SG3" and "SG4".
The catenary protection device MiCOM P438 is designed for selective short-circuit and
overload protection of catenaries. This device is designed for the protection of classic-
or autotransformer-fed catenaries in single- or multi-voltage systems with nominal
frequencies of 25, 50 or 60 Hz (settable).
The MiCOM P438 ensures fast and selective short circuit protection as well as protection
from excessive catenary overloading.
The multitude of protection functions incorporated into the device enable the user to
cover a wide range of applications in the protection of catenary systems.
Moreover there are numerous backup protection and automatic control functions
available.
The relevant protection parameters are stored in four independent setting groups in
order to adapt the device to various operating and power system management states.
General Functions
General Functions are complete function groups, which may be individually configured
or cancelled, depending on the application (e.g. included in or excluded from the
device’s configuration).
(An exception is the function M A I N , which is always visible.)
Unused or de-configured function groups are hidden to the user (except for the
configuration setting), thus simplifying the menu.
This concept provides a wide choice of functions and makes wide-ranging application of
the protection device possible, with just one model version. On the other hand simple
and clear parameter settings and adaptations to each protection scheme can be made.
The unit’s powerful programmable logic also makes it possible to accommodate special
applications.
General Functions
P438
ANSI IEC 61850 Function group / function
21 DisPDISx DIST Distance Protection
4 zones, individually settable forward and reverse directionals
nd rd th
Train start-up detection for 2 , 3 and 4 zones
Overreach zone, settable
Harmonics adaptation functionality, settable ( )
Wrong phase coupling protection
Classic Single Feed, Autotransformer Feed /
DELTA Stabilized high impedance protection (Delta I function) ( )
50 / 27 SofPhsPSOF1 SOTF Switch on to fault protection
50TD DtpPhsPTOCx DTOC Definite-time overcurrent protection, with two stages
67 Short-circuit direction determination, for each stage
50V Enabling for undervoltage stage, for each stage
50HS High-current stage
51 ItpPhsPTOC1 IDMT Inverse-time overcurrent protection, single stage
67 Short-circuit direction determination
50V Enabling for undervoltage stage
79 RREC1 RECLS Auto-reclose
49 ThmPTTR1 THERM Thermal overload protection
Coolant temperature acquisition (via RTDmA) ( )
27 / 59 VtpPhsPTOVx / V<> Time-delayed voltage protection
VtpPhsPTUVx
30 / 74 AlmGGIO1 C&VTS Measuring circuit monitoring function (VT Supervision)
50BU BocPhsPTOCx BUOC Backup time-delayed overcurrent protection, two stages
DFRST Defrost protection
50BF RBRF1 CBF Circuit breaker failure protection
CBM Circuit breaker condition monitoring
Classic single feed, autotransformer feed /
LIMIT Limit value monitoring
LGC PloGGIOx LOGIC Programmable logic
Global functions
In addition to the listed features, and extensive self-monitoring, the P438 offers the
following global functions:
FT_DA Fault data acquisition for a particular, settable point in time during a fault
Further functions
Further functions
MAIN Main function
DVICE Device
LED LED indicator
HMI User interface
PC PC link
CHECK Comprehensive self-monitoring
MT_RC Monitoring signal recording
Measuring inputs for current / voltage
Phase current / comparison current defrost protection
Voltage
Idfrst
30/74 50BU 26
BC BUOC RTDmA mA_OP Always Further
Available Options
P438 Catenary Protection
Vcat
Vfdr Φ
30/74 50BU 26
BC BUOC RTDmA mA_OP Always Further
Available Options
P438 Catenary Protection
Design
The P438 is modular in design. The plug-in modules are housed in a robust aluminum
case and electrically interconnected via one analog module and one digital module.
3 current-measuring inputs
2 voltage-measuring inputs (depending on order).
Up to 32 binary signal inputs (opto-couplers) with user-definable function assignment
Up to 46 output relays with user-definable function assignment
1 PT 100 input (optional)
1 input, 0 to 20 mA (optional)
2 outputs, 0 to 20 mA (optional)
The nominal current and voltage values of the measuring inputs on the P438 can be set
with the function parameters.
The nominal voltage range of the optical coupler inputs is 24 to 250 V DC. As an option
binary signal input modules with a higher operate threshold are available.
The auxiliary voltage input for the power supply is also designed for an extended range.
The nominal voltage ranges are 48 to 250 V DC and 100 to 230 V AC. A 24 V DC
version is also available.
All output relays can be utilized for signaling and command purposes.
The optional PT 100 input is lead-compensated, balanced and linearized for PT 100
resistance thermometers as per IEC 751.
Two selectable measured variables (cyclically updated measured operating data and
stored measured fault data) can be output as a burden-independent direct current via
the two optional 0 to 20 mA outputs. The characteristics are defined via 3 adjustable
interpolation points allowing a minimum output current (4 mA, for example) for slave-side
open-circuit monitoring, knee-point definition for fine scaling, and a limitation to lower
nominal currents (10 mA, for example). Where sufficient output relays are available,
a selectable measured variable can be output in BCD-coded form by contacts.
Using the first communication interface, the numerical protection device can be linked
either to the substation control system or to a telecontrol system.
The first communication interface is available with selectable protocols (per
IEC 60870-5-103, IEC 870-5-101, DNP 3.0, MODBUS or COURIER).
A direct communication link can be established with another MiCOM protection device
using the optional InterMiCOM teleprotection interface (channel 3).
2 Technical Data
2.1 Conformity
Notice
Applicable to P438 version P438-305-409/410/411-613 and P438-307-412/413/414-613.
Declaration of conformity
CE symbol
This product has been designed and manufactured in conformance with the following
major EC Directives:
EMC Directive 2004/108/EC
Low Voltage Directive 2006/95/EC
Installation Position
Vertical ± 30°.
Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 529
IP 52 for the front of the device
Flush-mounted case
IP 50 for the case (excluding rear connection space)
IP 20 for the rear connection space with pin-terminal connection
IP 10 for the rear connection space with ring-terminal connection
Surface-mounted case
IP 50 for the case
IP 50 for the enclosed connection space when the
rubber grommets included with delivery are applied.
Weight
40TE case: approx. 7 kg; 84TE case: approx. 11 kg
Dimensions and Connections
See Dimensional Drawings (Chapter 4) and Terminal Connection Diagrams (Chapter 5).
Terminals
PC interface (X6):
EIA RS232 (DIN 41652) connector, type D-Sub, 9-pin.
1
Option is not available with redundant design of the Ethernet module.
2.3 Tests
Type tests
All tests per EN 60255-6, IEC 255-6 or EN 50121-5.
Electromagnetic
compatibility (EMC)
Interference Suppression
Per EN 55022 or IEC CISPR 22, Class A.
Insulation
Voltage Test
Per DIN EN 61010 or IEC 255-5.
2 kV AC, 60 s.
Direct voltage (2.8 kV DC) must be used for the voltage test of the power supply inputs.
The PC interface must not be subjected to the voltage test.
Corrosion resistance
Flowing Mixed Gas Corrosion Test
Per IEC 60068-2-60: 1995, part 2, test Ke, severity level 3
21 days at 75 % relative humidity and 30 °C
with reaction to increased concentrations of H2S, NO2, Cl2 and SO2
Mechanical robustness
1(**)
Vibration Test
Per EN 60255-21-1§ or IEC 255-21-1, test severity class 1.
Frequency range in operation: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Frequency range during transport: 10 to 150 Hz, 1 g
Seismic Test
Per EN 60255-21-3 or IEC 60255-21-3, test procedure A, class 1
Frequency range:
5 to 8 Hz, 3.5 mm / 1.5 mm, 8 to 35 Hz, 10 / 5 m/s2, 3 x 1 cycle.
Mechanical robustness
2(**)
Vibration Test
Per EN 60255-21-1 or IEC 255-21-1, test severity class 2.
Frequency range in operation: 10 to 60 Hz, 0.075 mm and 60 to 150 Hz, 1.0 g
Frequency range during transport: 10 to 150 Hz, 2 g
Seismic Test
Per EN 60255-21-3 or IEC 60255-21-3, test procedure A, class 2
Frequency range:
5 to 8 Hz, 3.5 mm / 7.5 mm, 8 to 35 Hz, 20 / 10 m/s2, 3 x 1 cycle.
(*)
Mechanical robustness 1:
Applicable to the following case variants:
Flush mounted case, flush-mounting method 1 (without angle brackets and frame)
(**)
Mechanical robustness 2:
Applicable to the following case variants:
Flush mounted case, flush-mounting method 2 (with angle brackets and frame)
Surface-mounted case
Routine Tests
Voltage Test
Per IEC 255-5.
2.2 kV AC, 1 s.
Direct voltage (2.8 kV DC) must be used for the voltage test of the power
supply inputs.
The PC interface must not be subjected to the voltage test.
Environment
Temperatures
Recommended temperature range: -5 °C to +55 °C [+23 °F to +131 °F]
Limit temperature range: -25 °C to +70 °C [-13°F to +158°F]
Humidity
≤ 75 % relative humidity (annual mean),
56 days at ≤ 95 % relative humidity and 40°C (104°F), condensation not permissible.
Solar Radiation
Direct solar radiation on the front of the device must be avoided.
Measuring inputs
Current
Rated current: 1 or 5 A AC (settable).
Nominal burden per phase: < 0.1 VA at In
Load rating:
continuous: 4 In
for 10 s: 30 In
for 1 s: 100 In
Nominal surge current: 250 In
Voltage
Nominal voltage Vn: 50 to 130 V AC (settable)
Nominal burden per phase: < 0.3 VA at Vn = 130 V AC
Load rating: continuous 150 V AC
Frequency
Nominal frequency fn: 25 Hz, 50 Hz and 60 Hz (settable)
Operating range: 0.95 to 1.05 fn
Special variant:
Vin > Switching threshold: VA • 5 mA ± 30 %.
Notes
The standard variant of binary signal inputs (opto-couplers) is recommended in most
applications, as these inputs operate with any voltage from 19 V. Special versions with
higher pick-up/drop-off thresholds are provided for applications where a higher switching
threshold is expressly required.
The maximum voltage permitted for all binary signal inputs is 300 V DC.
IRIG-B interface
Minimum / maximum input voltage level
(peak-peak): 100 mVpp / 20 Vpp
Input impedance: 33 kΩ at 1 kHz.
Electrical isolation: 2 kV
Resistance thermometer
inputs
Resistance thermometer: The analog I/O module supports only PT 100.
Mapping curve as per IEC 751 § .
Value range: -40.0 ... +215.0 °C
3-wire configuration: max. 20 Ω per conductor.
Open and short-circuited input permitted.
Open-circuit monitoring: Θ > +215 °C and Θ < -40 °C
Output relays
Binary I/O module X (4H):
with heavy-duty contacts, use only for direct voltage/current;
Rated voltage: 250 V DC
Continuous current: 10 A
Short-duration current: 250 A for 30 ms,
30 A for 3 s
Making capacity: 30 A
Breaking capacity: 7500 W (resistive load) or 30 A at 250 V DC,
maximum values: 30 A and 300 V DC
2500 W inductive (L/R 40 ms) or 10 A at 250 V DC,
maximum values: 10 A and 300 V DC
2.6 Interfaces
PC interface
Transmission rate: 300 to 115200 baud (adjustable)
Communication interfaces
COMM1, COMM2,
COMM 3
The communication module can be provided with up to three communication channels,
dependent on the module type. Channels 1 and 3 are designed for twisted pair connection
or fiber optic connection, whereas Channel 2 is intended for twisted pair connection only.
Communication interface 2 can only be operated with the interface protocol based on
IEC 60870-5-103.
1)
Distance to be bridged given for identical optical outputs and inputs at both ends, a
system reserve of 3 dB, and typical fiber attenuation.
IEC communication
interface:
For Wire Leads
IEC 61850-compliant, Ethernet-based communications:
Transmission rate: 10 or 100 Mbit/s
RJ45, 1.5 kV isolation
Maximum distance: 100 m
2.8 Settings
Distance Protection
Directional sensitivity
up to 2 s after fault detection: ∞
up to 2 s after fault detection or for switching on to fault: 200 mV ± 20 %
Shortest tripping time: approx. 1.5 cycles
Starting and measurement resetting ratio (hysteresis): 0.95
Time-voltage protection
Shortest tripping time:
V<, V<<: approx. 150 ms
V>, V>>: approx. 150 ms
Starting reset time: approx. 1.5 cycles
Starting and measurement resetting ratio (hysteresis):
adjustable from 1 to 10%
2.9 Deviations
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fn, total harmonic distortion ≤ 2 %,
ambient temperature 20°C (68°F), and nominal auxiliary voltage VA,nom
Deviation
Deviation relative to the setting under reference conditions.
Distance Protection
Impedance Measurement Z<
Deviation at ϕk = 0°, 90°: ± 3 %
Deviation at ϕk = 30°, 60°: ± 5 %
Direction determination: ± 3°
Harmonics adaptation: ± 5 %
Backup time-delayed
overcurrent protection
Operate values: ± 3 %
Time-voltage protection
Operate values: ± 3 % (in the range 0.6 to 1.4 Unom)
Thermal overload
protection
Operate value Θ: ± 5 %
20 mA DC input
Deviation: ± 1 %
PT100 resistance
thermometer
Deviation: ± 2° or ± 1 %
20 mA analog measured
data output
Deviation: ± 1 %
Output residual ripple with max load: ± 1 %
Definitions
Reference Conditions
Deviation relative to the setting under reference conditions for sinusoidal signals at
nominal frequency fn, total harmonic distortion ≤ 2 %, ambient temperature 20°C (68°F),
and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Definite time-delayed
stages
Deviation 1 % + 20 ms to 40 ms
Inverse time-delayed
stages
Deviation where I ≥ 2 Iref: ± 5 % + 10 to 25 ms
For IEC characteristic 'extremely inverse' and
for thermal overload characteristics:
± 7.5 % + 10 to 20 ms
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fn, total harmonic distortion ≤ 2 %, ambient
temperature 20°C (68°F), and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Load Angle
Deviation: ± 2 %
Frequency
Deviation: ± 10 mHz
Temperature
Deviation: ± 1 %
Fault data
Short-Circuit Current and Voltage
Deviation: ± 3 %
Short-Circuit Impedance
Deviation: ± 5 %
Fault Location
Deviation: ± 5 %
Internal clock
With free running internal clock:
Deviation: < 1 min/month
Time resolution
1 ms
Currents
Dynamic range: 25 In
Amplitude resolution
at In = 1 A: 2.0 mARMS
at In = 5 A: 10.1 mARMS
Voltage
Dynamic range: 150 V
Amplitude resolution: 9.2 mV RMS
Overload memory
Number: The 8 most recent overload events
Scope: All signals relevant for an overload event from a total of
1024 different logic state signals
(from the "Overload Memory")
Depth: 200 entries per overload event
Fault memory
Number: The 8 most recent faults
Scope: Signals:
All fault relevant signals from a total of
1024 different logic state signals
(from the “Fault Memory”)
Fault Values:
Sampled values for all measured currents and voltages
Depth: Signals:
200 entries per fault
Fault Values:
The max number of cycles per fault can be set by user;
storage capacity with a total of 32 s is available for all faults,
e.g. 800 cycles for fn = 25 Hz
1600 cycles for fn = 50 Hz
1920 cycles for fn = 60 Hz
The following equation is used to calculate the specifications of a current transformer for
the offset maximum primary current:
(
Vsat = (R nom + R i ) ⋅ n ⋅ I nom = Rop + Ri ⋅ k ⋅ I1' ,max )
with:
Vsat: saturation voltage (IEC knee point)
I'1,max: non-offset maximum primary current, converted to the secondary side
Inom: rated secondary current
n: rated overcurrent factor
k: over-dimensioning factor
Rnom: rated burden
Rop actual connected operating burden
Ri internal burden
The specifications of a current transformer can then be calculated for the minimum
required saturation voltage Vsat as follows:
( )
Vsat = Rop + R i ⋅ k ⋅ I1,max
n≥
(Rop + Ri ) ⋅k ⋅
I1' ,max
=
(Pop + Pi ) ⋅k ⋅
I1' ,max
( Rnom + Ri ) Inom ( Pnom +P i ) Inom
with
Pi = Ri ⋅ Inom
2
Theoretically, the specifications of the current transformer could be calculated for lack of
saturation by inserting instead of the required over-dimensioning factor k its maximum
value:
k max ≈ 1 + ωT1
with:
ω: system angular frequency
T1: system time constant
The over-dimensioning factor 'k' necessary for the distance protection may be read from
figure 2-1. The dotted line depicts the theoretical characteristic k(T1) = 1 + ωT1.
Current transformers should observe the error limit values for class 5P. CTs class TPY
per IEC 44-6 Part 6 ("Current Transformers with Anti-remanence Cores") should
preferably be used in case a HSR is applied.
3 Operation
The P438, a numerical device, is part of the MiCOM P 30 family of products. The device
types included in this family are built from identical uniform hardware modules.
Figure 3-1 shows the basic hardware structure of the P438.
The external analog and binary quantities – electrically isolated – are converted to the
internal processing levels by the peripheral modules: T, Y, and X. Commands and
signals internally generated by the device are connected to the external plant via
contacts through binary I/O modules X. The external auxiliary voltage is applied to
power supply module V, which in turn supplies the auxiliary voltages that are required
internally.
Analog data is transferred from the transformer module T via the analog bus module B to
the processor module P. The processor module contains all the elements necessary for
the conversion of measured analog values, including multiplexers and analog/digital
converters. The analog data conditioned by the analog I/O module Y is transferred to
the processor module P via the digital bus module. Binary signals are fed to the
processor module by the binary I/O modules X via the digital bus module.
The processor handles the processing of digitized analog vaues and of binary signals,
generates the protective trip and signals, and transfers them to the binary I/O modules X
via the digital bus module. The processor module also handles overall device
communication. As an option, communication module A can be mounted on the
processor module to provide serial communication with substation control systems.
The control and display elements of the integrated user interface (HMI) and the
integrated PC interface are housed on control module L.
The following interfaces are available for the exchange of information between the user
and the device:
All settings and signals as well as all measurements and control functions are arranged
within the branches of the menu tree following a scheme that is uniform throughout the
device family. The main branches are:
‘Settings’ branch
All settings are contained in this branch. This branch carries all settings, including the
device identification data, the configuration parameters for adapting the device's
interfaces to the system, and the function parameters for adapting the device functions
to the process. All values in this group are stored in non-volatile memory, which means
that the values will be preserved even if the power supply fails.
Settings and signals are displayed either in plain text or as addresses, in accordance
with the user’s choice. Chapters 7, 8 and 10 describe the settings, signals and
measured values available with the P438. The possible setting values can be found in
the P438's data model file associated with the PC support software (MiCOM S1).
The configuration of the user interface (HMI) also permits the installation of Measured
Value 'Panels’ on the LCD display. Different Panels are automatically displayed for
specific system operating conditions. Priority increases from normal operation to
operation under overload conditions to operation during a ground fault to operation
following a short circuit in the system. Thus the P438 provides the measured data
relevant for the prevailing conditions.
The P438 offers Measured Value Panels, which display the measured values relevant at
a given time.
During normal power system operation, the Operation Panel is displayed. As an event
occurs, the display switches to the appropriate Event Panel - provided that measured
values have been selected for the Event Panels. In the event of overload event, the
display will automatically switch to the Operation Panel at the end of the event. In the
event of a fault, the Fault Panel remains active until the LED indicators or the fault
memories are reset.
Operation Panel
The Operation Panel is displayed after the set return time has elapsed, provided that at
least one measured value has been configured.
The user can select which of the measured operating values will be displayed on the
Operation Panel by means of an ‘m out of n’ parameter. If more measured values are
selected for display than the LC display can accommodate, then the display will switch to
the next set of values at intervals defined by the setting at H M I : P a n e l H o l d - T i m e
or when the appropriate key on the user interface (HMI) is pressed.
HMI:Operation
Panel Fct
[ 053 007 ]
OSCIL: Record.
in Progress S1 1 C
[ 035 000 ] ≥1
R1
OL_RC: Record. in
Progress
[ 035 003 ] Operation Panel
MAIN: General
Reset USER
[ 003 002 ]
1: Execute ≥1
MAIN: General
Reset EXT
[ 005 255 ]
OSCIL: Reset
Record. USER
[ 003 006 ]
1: Execute
OSCIL: Reset
Record. EXT
[ 005 243 ]
MAIN: Reset LED
306 020
47Z1301A_UK
Fault Panel
The Fault Panel is displayed in place of another data panel when there is a fault,
provided that at least one measured value has been configured. The Fault Panel
remains on display until the LED indicators or the fault memories are reset.
The user can select the measured fault values that will be displayed on the Fault Panel
by setting a 'm out of n' parameter. If more measured values are selected for display
than the LC display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at H M I : P a n e l H o l d - T i m e or when the
appropriate key on the user interface (HMI) is pressed.
Selected Meas.Values
HMI: Panel Hold-
Time
[ 031 075 ]
R
MAIN: General
Reset USER
[ 003 002 ]
1: Execute ≥1 Fault Panel
MAIN: General
Reset EXT
[ 005 255 ]
OSCIL: Reset
Record. USER
[ 003 006 ]
1: Execute
OSCIL: Reset
Record. EXT
[ 005 243 ]
MAIN: Reset LED
306 020
50Z01EJA_UK
Overload Panel
The Overload Panel is automatically displayed in place of another data panel when there
is an overload, provided that at least one measured value has been configured.
The Overload Panel remains on display until the overload ends, unless a fault occurs.
In this case the display switches to the Fault Panel.
The user can select the measured values that will be displayed on the Overload Panel
by setting a 'm out of n' parameter. If more measured values are selected for display
than the LC display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at H M I : P a n e l H o l d - T i m e or when the
appropriate key on the user interface (HMI) is pressed.
HMI: Overload
Panel Fct
[ 053 005 ]
47Z1302A_UK
Additional information pertaining to function keys and their application can be found in
section 'Configurable Function Keys (Function Group F_KEY)' and section 'Resetting
Actions' of Chapter 3 and in section 'Configurable Function Keys F1 to Fx (general)' of
Chapter 6.
Note: Each of the 6 keys has an LED indicator situated next to it which is freely
configurable, like the other 12 LED indicators, but independent of the configuration of the
function keys (i.e. the function assignment is for red and green light emission).
Configuration of the
READ key
Similarly to the setting at H M I : F c t . M e n u J m p L i s t x up to 16 functions may
also be selected from the menu jump list at H M I : F c t R e a d K e y . They are
triggered in sequence by repeated pressing of the "READ" key.
Configuration of the
CLEAR key ('C')
Similarly to the setting at M A I N : F c t . A s s i g n . R e s e t x up to 10 reset functions
may be selected from a list at H M I : F k t R e s e t K e y . These are carried out by
pressing the "CLEAR" C key. Additional information pertaining to reset functions can
be found in sub-section 'Resetting Actions' in section 'Main Functions of the P438
(Function Group MAIN) of Chapter 3.
The P438 has a front port PC link as standard. Optionally a communication module A
providing two communication channels is available. Communication between the P438
and SCADA is done through communication module A. Setting and interrogation is
possible through all the P438’s interfaces.
Two rear port communications interfaces may be fitted. The settings of rear port
communications interface 1 (COMM1) may be assigned to the physical communications
channels 1 or 2 (see function group "MAIN"). If the COMM1 settings have been
assigned to communications channel 2, then the settings of communications interface 2
(COMM2) will automatically be active for communications channel 1. Communication
channel 2 can only be used to transmit data to and from the P438 if its PC link has been
de-activated. As soon as the PC link is used to transmit data, communication channel 2
becomes "dead". It will be enabled again only after the PC interface “Time-out” has
elapsed.
If tests are run on the P438, the user is advised to activate the test mode. In this way the
PC or the control system will recognize all incoming test signals accordingly (see
function group "MAIN").
Communication between the device and a PC is done through the PC link. In order for
data transfer between the P438 and the PC to function, several settings must be made in
the P438.
There is an operating program available as an accessory for control of the P438 (see
Chapter 13).
Relay
Communication between the P438 and the control station’s computer is done through
the communications interface. Several interface protocols are available at the rear port
communications interface 1. The IEC 60870-5-103 protocol is always supported.
The following user-selected interface protocols are available for use with the P438:
In order for data transfer to function properly, several settings must be entered in the
P438.
The rear port communications interface can be blocked through a binary signal input.
In addition, a signal or measured-data block can also be imposed through a binary signal
input.
COMM1: Transm.
enab.cycl.dat
COMM1: Selected
protocol
COMM1: IEC
60870-5-103
COMM1: General
enable USER
COMM1: Command
blocking
COMM1: Sig./meas.
Block.USER
0: No COMM1: Sig./meas.
1: Yes val.block.
COMM1: Sig./meas.
Block EXT
48Z50FFA_EN
3-7 Rear port communications interface 1, settings for the IEC 60870-5-103 interface protocol
COMM1: General
enable USER
COMM1: Command
blocking
Commun. interface
0: No
COMM1: Sig./meas.
1: Yes val.block.
COMM1: Sig./meas.
Block EXT
48Z50FGA_EN
3-8 Rear port communications interface 1, settings for the IEC 870-5-101 interface protocol
COMM1: Contin.
general scan
COMM1: Selected
protocol
COMM1: IEC
60870-5, ILS
COMM1: General
enable USER
1: Yes
COMM1: Command
blocking
Commun. interface
COMM1: Sig./meas.
Block.USER
0: No
COMM1: Sig./meas.
1: Yes val.block.
COMM1: Sig./meas.
Block EXT
48Z50FHA_EN
3-9 Rear port communications interface 1, settings for the ILS_C interface protocol
3-10 Rear port communications interface 1, settings for the MODBUS protocol
Octet 2
Comm.Add DNP3
Ph-Ph
PhasePhase
3-11 Rear port communications interface 1, settings for the DNP 3.0 protocol
3-12 Rear port communications interface 1, settings for the COURIER protocol
Checking spontaneous
signals
For interface protocols based on IEC 60870-5-103, IEC 870-5-101, or ILS_C it is
possible to select a signal for test purposes. The transmission of this signal to the control
station as ‘sig. start‘ or ‘sig. end‘ can then be triggered using setting parameters.
In order for data transfer to function properly, several settings must be made in the P438.
Checking spontaneous
signals
It is possible to select a signal for test purposes. The transmission of this signal to the
control station as ‘sig. start‘ or ‘sig. end‘ can then be triggered using setting parameters.
Application
Communications interface 3 is designed to establish a digital communication link
between two MiCOM devices over which up to 8 binary protection signals may be
transmitted. Whereas communications interfaces 1 and 2 are designed as information
interfaces to connect to data acquisition subsystems and for remote access,
communication interface 3 is designed as a protection signaling interface that will
transmit real time signals (InterMiCOM teleprotection interface). Communications
interface 3 is mainly used to exchange information for teleprotection (protective
signaling). In addition, any other internal or external binary signals may also be
transmitted.
Physical medium
Communications interface 3 is provided as an asynchronous, full-duplex communication
interface. The following physical media are available for data transmission:
Digital network:
Asynchronous data interface of primary multiplexing equipment
Telegram configuration
The communication baud rate is settable (C O M M 3 : B a u d R a t e ) to adapt to the
transmission channel's requirements. Sending and receiving addresses
(C O M M 3 : S o u r c e A d d r e s s and C O M M 3 : R e c e i v i n g A d d r e s s can be set
to different values, thus avoiding that the device communicate with itself.
Binary signals 1 to 4:
Operating mode settable to 'Blocking' or 'Direct Intertrip'
Binary signals 5 to 8:
Operating mode settable to 'Permissive' or 'Direct Intertrip'
Speed
fast
Blocking
Permissive
slow
low
high high
Direct
Security Intertrip Dependability
47Z1030A_EN
3-16 Comparison of speed, security and dependability offered by the three operating modes.
Communication monitoring
Timer stage C O M M 3 : T i m e - O u t C o m m . F a u l t is used to monitor the
transmission channel (this timer is re-triggered with each complete and correct telegram
received). The wide setting range allows adaptation to the actual channel transmission
times and above all this is needed for time-critical schemes such as the blocking
scheme. After the timer has elapsed, signals C O M M 3 : C o m m u n i c a t i o n s F a u l t
and C H E C K : C o m m u n i c . F a u l t C O M M 3 are issued and the received signals
are automatically set to their user-defined default values
(C O M M 3 : D e f a u l t V a l u e R e c . x , with x = 1 to 8). As the main application for this
protective signaling the fault signal may be mapped to the corresponding input signal in
function group PSIG using the C O M M 3 : S i g . A s g . C o m m . F a u l t setting.
Message
received
Blocking signals
accepted
Permissive signals
accepted
(Re-)Trigger
COMM3: Time-out
comm.fault
[120 033]
COMM3:
Communications
1 fault
[120 043]
COMM3: Time-out
link fail
[120 035]
47Z1031B_EN
Supervision of
communication
link quality
After a syntax check of each received message, InterMiCOM updates the ratio of
incorrectly received messages, based on a total of the last 1000 received messages.
The result is provided as an updating measured value C O M M 3 : N o . T e l . E r r o r s
p . u . and the overall maximum ratio can be read from
COMM3: No.T.Err.,Max,Stored.
If the set threshold C O M M 3 : L i m i t T e l e g r . E r r o r s is exceeded the
corresponding signals C O M M 3 : L i m . E x c e e d . , T e l . E r r .
and C H E C K : L i m . E x c e e d . , T e l . E r r . will be issued. All the corrupted telegrams
are counted (C O M M 3 : N o . T e l e g r a m E r r o r s ) . This counter as well as the
stored maximum ratio of corrupted messages can be reset using
C O M M 3 : R s e t . N o . T l g . E r r . U S E R (as well as via the binary signal
C O M M 3 : R e s e t N o . T l g . E r r . E X T ).
Commissioning tools
The actual values of send and receive signals can be read from the device as physical
state signals (C O M M 3 : S t a t e S e n d x and C O M M 3 : S t a t e R e c e i v e x , with
x = 1 to 8). In addition, InterMiCOM provides 2 test facilities for the commissioning of the
protection interface.
For a loop-back test, the send output is directly linked back to the receive input.
After setting the desired bit pattern (as an equivalent decimal number at
C O M M 3 : L o o p B a c k S e n d ) the test can be triggered using
C O M M 3 : L o o p B a c k T e s t . This bit pattern is sent for the duration of the hold time
set at C O M M 3 : H o l d T i m e f o r T e s t . For this test only, the source address is set
to ' 0 '; this value is not used for regular end-to-end communication. The test result can
be checked as long as the hold-time is running by reading the measured operating data
C O M M 3 : L o o p B a c k R e s u l t and C O M M 3 : L o o p B a c k R e c e i v e . As soon
as the hold-time has expired, the loopback test is terminated and InterMiCOM reverts to
the normal send mode (e.g. sending the actual values of the configured send signals,
using the set source address).
Thus, in case of problems with the InterMiCOM teleprotection interface, the loopback
test can be used to verify or to exclude a defective device. The transmission channel
including the receiving device can be checked manually by setting individual binary
signals
(C O M M 3 : S e n d S i g n a l f o r T e s t ) to user-defined test values
(C O M M 3 : L o g . S t a t e f o r T e s t ). After triggering the test by
C O M M 3 : S e n d S i g n a l , T e s t , the preset binary signal is sent with the preset
value for the set hold time C O M M 3 : H o l d T i m e f o r T e s t . The 7 remaining binary
signals are not affected by this test procedure and remain to be sent with their actual
values. During the hold time, a received signal can be checked at the receiving device,
e.g. by reading the physical state signal. After the hold time has expired, the test mode
is automatically reset and the actual values of all 8 signals are transmitted again.
The IEC 61850 communication protocol is implemented by these function groups and
the Ethernet module.
Note:
Function group IEC is only available as an alternative to function group COMM1
(hardware ordering option!).
3.4.5.1 Communications Interface IEC 61850 (Function Group IEC)
IEC 61850
IEC 61850 was created jointly by users and manufacturers as an international standard.
The main target of IEC 61850 is interoperability of devices. This includes the capability
of two or more intelligent electronic devices (IED), manufactured by the same company
or different companies, to exchange data for combined operation.
Now the new IEC 61850 communication standard has created an open and common
basis for communication from the process control level down to the network control level,
for the exchange of signals, data, measured values and commands.
For a standardized description of all information and services available in a field device a
data model, which lists all visible functions, is created. Such a data model, specifically
created for each device, is used as a basis for an exchange of data between the devices
and all process control installations interested in such information. In order to facilitate
engineering at the process control level a standardized description file of the device,
based on XML, is created with the help of the data model. This file can be imported and
processed further by the relevant configuration program used by the process control
device. This makes possible an automated creation of process variables, substations
and signal images.
The following documentation, with the description of the IEC 61850 data model used
with the P438, is available:
IDC file based on XML in the SCL (Substation Configuration Description Language)
with a description of the data, properties and services, available from the device, that
are to be imported into the system configurator.
PICS_MICS_ADL file with the following contents:
PICS (Protocol Implementation Conformance Statement) with an overview of
available services.
MICS (Model Implementation Conformance Statement) with an overview of
available object types.
ADL (Address Assignment List) with an overview of the assignment of parameter
addresses (signals, measuring values, commands, etc.) used by the device with
the device data model as per IEC 61850.
Ethernet Module
The optional Ethernet module provides an RJ45 connection and a fiber optic interface
where an Ethernet network can be connected. The selection of which of the two
interfaces is to be used to connect to the Ethernet network is made by setting the
I E C : E t h e r n e t M e d i a parameter. For the optical interface on the Ethernet
communications module the user may either select as an ordering option the ST
connector or the SC connector with 100 Mbit/s and 1300 nm. The RJ45 connector
supports 10 Mbit/s and 100 Mbit/s.
The optional Ethernet module additionally provides an RS485 interface for remote
access with the MiCOM S1 support software (function group COMM2).
Notes: The P438 can be equipped with the optional Ethernet module only as an
alternative to the standard optional communication module. Therefore the
IEC 61850 Ethernet-based communication protocol is available only as an
alternative to function group COMM1.
The setting parameters for function groups IEC, GOOSE and GSSE are not
automatically activated in the device. Activation occurs either when the I E C : E n a b l e
C o n f i g u r a t i o n command is executed, or automatically when the device is switched
online at M A I N : P r o t e c t i o n E n a b l e d .
Client Log-on
Ethernet communications no longer occur in a restrictive master slave system, as is
common with other protocols. Instead, server or client functionalities, as defined in the
'Abstract Communication Service Interface' (ACSI, IEC 61870-7-2), are assigned to the
devices. A 'server' is always that device which provides information to other devices.
A client may log-on to this server so as to receive information, for instance 'reports'.
In a network a server can supply any number of clients with spontaneous or cyclic
information.
In its function as server the P438 can supply up to 16 clients with information.
Clock Synchronization
With IEC 61850, clock synchronization is effected via the SNTP protocol, defined as
standard for Ethernet. Here the P438 functions as a SNTP client.
For clock synchronization one can select between operating modes Broadcast from
SNTP Server or Request from Server. With the first operating mode synchronization is
effected via a broadcast message sent from the SNTP server to all devices in the
network, and in the second operating mode the P438 requests the device specific time
signal during a settable cycle.
Two SNTP servers may be set. In this case, clock synchronization is preferably
performed by the first server. The second server is used only when messages are no
longer received from the first server.
When looking at the source priority for clock synchronization, which is set at the MAIN
function then, by selecting "COMM1", synchronization per IEC 61850 is automatically
active but only if this communication protocol is applied.
Fault Transmission
Transmission of fault files is supported per "File Transfer".
Transmission of "Goose
Messages"
The so-called "Goose Message" is a particular form of data transmission. Whereas
normal server-client-services are transmitted at the MMS and TCP/IP level, the "Goose
Message" is transmitted directly at the Ethernet level with a high transmission priority.
Furthermore these "Goose Messages" can be received by all participants in the
respective sub-network, independently of their server or client function. In IEC 61850
"Goose Messages" are applied for the accelerated transmission of information between
two or more devices. Application fields are, for example, reverse interlocking, transfer
tripping or decentralized substation interlocking. In the future the "Goose Message" will
therefore replace a wired or serial protective interface.
According to IEC 61850 there are two types of "Goose Messages", GSSE and
IEC-GOOSE. GSSE is used to transmit binary information with a simple configuration by
'bit pairs', and it is compatible with UCA2. However IEC-GOOSE enables transmission
of all data formats available in the data model, such as binary information, integer values
or even analog measured values. But this will require more extensive configuration with
the help of the data model from the field unit situated on the opposite side. With
IEC-GOOSE the P438 at this time supports sending and receiving of binary information.
Communication with the
MiCOM S1 support
software via the Ethernet
Interface
Direct access by the MiCOM S1 support software via the Ethernet interface on the
device may occur through the "tunneling principle". Transmission is carried out by an
Ethernet Standard Protocol, but this is only supported by the associated MiCOM S1
support software (specific manufacturer solution). Such transmission is accomplished
over the same hardware for the network, which is used for server-client communication
and "Goose Messages".
Available are all the familiar functions offered by the MiCOM S1 support software such
as reading/writing of setting parameters or retrieving stored data.
The various settings, measured values and signals for function group IEC are described
in chapters 7 and 8.
The setting parameters for function groups IEC, GOOSE and GSSE in the device are not
automatically activated. Activation occurs either when the
I E C : E n a b l e C o n f i g u r a t i o n command is executed or automatically when the
device is switched online with M A I N : P r o t e c t i o n E n a b l e d . In addition function
group IEC must be configured and enabled.
Sending GOOSE
With GOOSE, up to 32 logic binary state signals from the P438 can be sent. Selection of
binary state signals is made by setting
G O O S E : O u t p u t n F c t . A s s i g . (n = 1 to 32). The assignment of data object
indexes to logic state signals is made in the range from 1 to 32 according to the
assignment to GOOSE outputs.
A GOOSE message is automatically sent with each new state change of a configured
binary state signal or an external device. There are numerous sending repetitions in
fixed ascending time periods (10 ms, 20 ms, 50 ms, 100 ms, 500 ms, 1000 ms, and
2000 ms). If after 2 seconds there is no further state change apparent, the GOOSE
message is then sent cyclically at 2-second intervals.
GOOSE-DataSet: LLN0$GooseST
VLAN Identifier: 0
VLAN Priority: 4
64Z6090A_EN
With GOOSE up to 16 logic binary state signals can be received. Configuration of the
logic state signals received (G O O S E : I n p u t n F c t . A s s i g . , where n = 1 to 16) is
made on the basis of the selection table of the binary inputs (opto coupler inputs).
For each state signal to be received the GOOSE message is selected by setting the
GOOSE ID, Application ID and 'DataSet Reference' which includes the information
wanted. With the further setting of the data object index and the data attribute index
through parameters, the required information from the chosen GOOSE will be selected.
The device will not evaluate the identification features VLAN identifier and ‘Dataset
Configuration Revision’ that are also included in the GOOSE received.
Each GOOSE message includes time information on the validity of its information.
This corresponds to the double time period to the next GOOSE repetition. If the validity
period has elapsed before this GOOSE message is received again (i.e. because of a
fault in communication), the received signals will automatically be set to their respective
default values at G O O S E : I n p u t n D e f a u l t .
The various settings, measured values and signals for function group GOOSE are
described in chapters 7 and 8.
The setting parameters for function groups IEC, GOOSE and GSSE in the device are not
automatically activated. Activation occurs either when the I E C : E n a b l e
C o n f i g u r a t i o n command is executed or automatically when the device is switched
on-line at
M A I N : P r o t e c t i o n E n a b l e d . In addition the IEC function group must be
configured and enabled.
Sending GSSE
With GSSE up to 32 logic binary state signals can be sent. Selection of binary state
signals is made by setting G S S E : O u t p u t n F c t . A s s i g . (n = 1 to 32). Each
selected state signal is to be assigned to a bit pair in GSSE
(G S S E : O u t p u t n B i t P a i r (n = 1 to 32)), which will transmit this state signal.
A GSSE message is automatically sent with each state change of a selected state
signal. There will be multiple send repetitions at ascending time periods. The first send
repetition occurs at the given cycle time set for G S S E : M i n . C y c l e . The cycles for
the following send repetitions result from a conditional equation with the increment set
using the G S S E : I n c r e m e n t parameter. Should no further state changes occur up
to the time when the maximum cycle time has elapsed (G S S E : M a x . C y c l e ) , then
the GSSE will be sent cyclically at intervals as set for the max. cycle time.
In order to have unambiguous identification of a sent GSSE message, the IED name is
used which was set in function group IEC.
Receiving GSSE
With GSSE up to 32 logic binary state signals can be received. Configuration of the
logic binary state signals received (G S S E : I n p u t n F c t . A s s i g . , where n = 1 to 32)
is made on the basis of the selection table of the binary inputs (opto coupler inputs).
For each state signal to be received, the GSSE message, which will include the required
information, must be selected by setting the IED name (G S S E : I E D N a m e ) .
Selection of information wanted from the selected GSSE will occur by setting the bit pair
(G S S E : B i t P a i r ) .
Each GSSE message includes time information on the validity of its information.
This corresponds to the double time period to the next GSSE repetition. If the validity
period has elapsed before this GSSE message is received again (i.e. because of a
communications fault), the signals received will automatically be set to their respective
default values ( G S S E : I n p u t n D e f a u l t (n = 1 to 32)).
The various settings and signals for function group GOOSE are described in chapters 7
and 8.
If, for example, a GPS receiver with IRIG-B connection is available, the internal clock of
the P438 can be synchronized to run on GPS time using the optional IRIG-B interface.
It should be noted that the IRIG-B signal holds information on the day only (day of the
current year). Using this information and the year set at the P438, the P438 calculates
the current date (DD.MM.YY).
Ready to synchronize
If the IRIG-B interface is enabled and receiving a signal, the P438 checks the received
signal for plausibility. Implausible signals are rejected by the P438. If the P438 does not
receive a correct signal in the long run, synchronization will not be ready any longer.
The P438 includes six additional function keys that are freely configurable. A password
can be assigned to each of the function keys F1 to Fx at
F _ K E Y : P a s s w o r d F u n c t . K e y x so that the function key will be enabled only
after the password is entered. The default setting (as of version -613) however requires
no password entry when pressing a function key.
Configuration of function
keys with a single function
Each function key may be assigned a single function by selecting a logic state signal at
F _ K E Y : F c t . A s s i g n m . F x (Fx: F1 to F6), but with the exception:
H M I : T r i g . M e n u J m p x E X T (x: 1 or 2). This function is triggered by pressing
the corresponding function key on the P438.
Configuration of function
keys with menu jump lists
Instead of a single function, each function key may be assigned one of the two menu
jump lists at F _ K E Y : F c t . F x A s s i g n (Fx: F1 to F6) by selecting the list at
H M I : T r i g . M e n u J m p x E X T (x: 1 or 2). The functions of the selected menu
jump list are triggered in sequence by pressing repeatedly the assigned function key.
Note: LED indicators - including the six positioned directly next to the function keys - are
configured independently and in this respect there is no relationship to the respective
function key configuration.
Configuration of the
READ key
Similarly to the setting at H M I : F c t . M e n u J m p L i s t x up to 16 functions can also
be selected from the menu jump list at H M I : F c t . R e a d K e y . They are triggered in
sequence by pressing repeatedly the "READ" key.
Handling keys
If the LCD backlight is switched off it will automatically light up again when a function key
or the "READ" key is pressed. The assigned function will be triggered only when the
respective key is pressed a second time. This is also valid for the other keys.
F_KEY: Fct.
F1 Assign
[ 080 112 ]
Function 1 EXT
Function 2 EXT
Function 3 EXT
Function n EXT
F_KEY: Operating
Mode F1
[ 080 132 ]
1 F_KEY: State F1
[ 080 122 ]
2
1: Key
2: Switch
3-20 Configuration and operating mode of function keys. The assigned function is either a single function, one of the two group resetting
functions or a menu jump list.
3.7 Configuration and Operating Mode of the Binary Inputs (Function Group INP)
The P438 has optical coupler inputs for processing binary signals from the system.
The functions that will be activated in the P438 by triggering these binary signal inputs
are defined by the configuration of the binary signal inputs. The typical response time is
less than 10 ms, although for reliability it is recommended that the initiating signal is
maintained for at least 20 ms so that it will be reliably detected by the P438. When a
general start is apparent this response time may be extended to 40 ms under
unfavorable conditions.
In this manual, we assume that the required functions (marked 'EXT' in the address
description) have been assigned to binary signal inputs by configuration.
Filter function
An additional filter function may be enabled in order to suppress transient interference
peaks at the logic signal inputs (operating modes 'Active "High", Filt.' or 'Active "Low",
Filt.'). Where this function is enabled a status change at the binary logic input is signaled
only when the input signal remains at a steady signal level during a set number of
sampling steps (sampling step size = period / 20). The number of sampling steps is set
at I N P : F i l t e r .
The P438 has a measured data input function involving two inputs. Direct current is fed
to the P438 through one of the inputs. The other input is designed for connection of a
resistance thermometer.
The input current IDC is displayed as a measured operating value. The current that is
conditioned for monitoring purposes (IDC,lin) is also displayed as a measured operating
value. In addition, it is monitored by the limit value monitoring function to detect whether
it exceeds or falls below set thresholds (see "Limit Value Monitoring").
When setting the characteristic the user must remember that only monotonically
increasing curve is allowed (no peak or vee-shapes). If the setting differs, the
C H E C K : I n v a l i d S c a l i n g I D C signal will be generated.
1.1
IDC,lin 20 1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
IDC,lin 1 0
0 0.1 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.6 IDC / IDC, nom
IDC 1 IDC 20
D5Z52KDA
19Z5266A_EN
3-23 Example of the conversion of 4-10 mA input current to 0-20 mA monitored current, IDC,lin
IDC,lin / IDC,nom
0.8
Interpolation points
IDC,lin20 0.7
0.6
IDC,lin4 0.5
0.4
IDC,lin3 0.3
IDC,lin2 0.2
IDC,lin1 0.1
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
3-24 Example of a characteristic having five interpolation points (characteristic with zero suppression setting of 0.1 IDC,nom is shown as a
broken line)
Zero suppression
Zero suppression is defined by setting R T D m A : E n a b l e I D C p . u . If the direct
current does not exceed the set threshold, the per-unit input current IDC p.u. and the
current IDC,lin will be displayed as having a value of ‘ 0 ’.
The input current is monitored in order to protect the 20 mA input against overloading.
If it exceeds the fixed threshold of 24.8 mA, the R T D m A : O v e r l o a d 2 0 m A I n p u t
signal is issued.
Beyond the linearization described above, the user has the option of scaling the
linearized values. Thereby negative values, for example, can be displayed as well and
are available for further processing by protection functions.
This input is designed to connect a PT 100 resistance thermometer. The mapping curve
R = f(T) of PT 100 resistance thermometers is defined in the DIN IEC 751 standard. If
the PT 100 resistance thermometer is connected using the 3-wire method, then no
further calibration is required.
Open-circuit monitoring
If there is an open measuring circuit due to a broken wire, the R T D m A : P T 1 0 0
F a u l t y signal is issued.
The P438 has output relays for the output of binary signals. The binary signal
assignment is freely configured by the user..
In these cases the relays are treated according to their set operating mode, i.e. relays in
a normally open arrangement (NO) are not triggered, whereas relays in a normally
closed arrangement (NC) are triggered.
If the self-monitoring feature detects a serious hardware fault (see error messages in
Chapter 10, which will lead to a blocking of protection), all output relays are reset
regardless of the set operating mode or signal configuration.
0
OUTP: Outp.
1 ≥1 Relays Blocked
[ 021 015 ]
0: No
OUTP: Block 1: Yes
Outp.Rel. EXT
[ 040 014 ] ≥1
MAIN: Prot. Ext.
Disabled
[ 038 046 ]
CHECK: Hardware
Fault
304 950
1 ≥1
2
3
4 -K xxx
≥1
5
6
≥1
1: Follower
2: Follower Latching
≥1
3: Follower Rst on Flt
4: Follower Rst onStart
5: Inverted & ≥1 OUTP: State K xxx
[ zzz zzz ]
6: Inverted Latching &
&
& ≥1
Signal 1
Signal 2
Signal 3 m out of n
Signal n
≥1 & ≥1
Selected Signals
&
OSCIL: Record.
in Progress OUTP: Latching
[ 035 000 ] 1 Reset
& [ 040 088 ]
OSCIL: System
Disturb. runn
[ 035 004 ]
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
OUTP: Reset
Latch. USER
[ 021 009 ]
0
1 1
100 ms
0: Don't Execute
1: Execute
OUTP: Reset
Latch. EXT
[ 040 015 ]
50Z0141A_UK
3-28 Configuration, setting the operating mode, and blocking the output relays
Measured values made available by the P438 can be provided in BCD (binary coded
decimal) form through output relays or in analog form as direct current output.
Output as direct current can only occur if the device is equipped with analog
module Y. BCD-coded output, however, is possible, regardless of whether the
device is equipped with analog module Y or not.
Disabling or enabling
the measured data
output function
Measured data output can be disabled or enabled using a setting parameter.
Enabling measured
data output
Measured data output can be enabled through a binary signal input, provided that the
function m A _ O P : O u t p u t e n a b l e d E X T has been configured. If
m A _ O P : O u t p u t e n a b l e d E X T has not been assigned to a binary signal
input, then measured data output is always enabled.
The measured data output function is reset either using a setting parameter or an
appropriately configured binary signal input.
There is a general reset.
The LED indicators have been reset.
mA_OP: Reset
Output USER
[ 037 116 ]
0
1
0: Don't Execute
1: Execute
MAIN: General
Reset USER mA_OP: Reset
[ 003 002 ] meas.val.outp.
1: Execute 304 601
MAIN: Reset
Indicat. USER
[ 021 010 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
MAIN: Reset
Indicat. EXT
[ 065 001 ]
47Z13H6A_UK
Scaling
Scaling is used to map the physical measuring range to the device’s inherent setting
range.
The user can select a measured value for output in BCD form by assigning output
relays.
The selected measured value is available in BCD-coded form for the duration of the
set hold time m A _ O P : H o l d T i m e O u t p u t B C D . If the selected variable was
not measured, then there is no output of a measured value value.
Output of measured
event values
If the measured event value is updated during the hold time, the measured value
output memory is cleared and the hold time is re-started. This leads to an immediate
output of the updated value.
Output of measured
operating values
The selected measured operating value is available for the duration of the set hold
time. After the hold time has elapsed, the current value is saved and the hold time is
re-started. If the hold time has been set to ’Blocked’, the measured operating value
that has been output will be stored until the measured data output function is reset.
M x ,max
M x , scal =
Scaling Factor
where:
M x , scal : scaled measured value
M x,max maximum transmitted value for the selected measured value
The user can select two of the measured values available in the P438 for output in
the form of load-independent direct current. Three interpolation points per channel
can be defined for specific adjustments such as adjustment to the scaling of a
measuring instrument. The direct current that is output is displayed as a measured
operating value.
The selected measured value is output as direct current for the duration of the set
hold time m A _ O P : H o l d T i m e O u t p u t A - x . If the selected variable was not
measured, then there is no output of a measured value value.
Output of measured
event values
If the measured event value is updated during the hold time, the measured value
output memory is cleared and the hold time is re-started. This leads to an immediate
output of the updated value.
Output of measured
operating values
The selected measured operating value is available for the duration of the set hold
time. After the hold time has elapsed, the current value is saved and the hold time is
re-started. If the hold time has been set to ’Blocked’, the measured operating value
that has been output will be stored until the measured data output function is reset.
Configuration of output
relays assigned to the
output channels
The user must keep in mind that direct current output only occurs when the output
relays assigned to the output channels are configured for m A _ O P : V a l u e A - x
O u t p u t , since the output channels would otherwise remain short-circuited (see
terminal connection diagrams).
Associated display
range
The associated display range is defined by setting the following parameters:
/Settings/Configuration/
Address Description Current value
056 020 mA_OP: Current Loop mA Outp Enabled
031 074 mA_OP: General Enable USER Yes
053 000 mA_OP: Function A-1 Assign MAIN:
Voltage A-B p.u.
010 114 mA_OP: Hold Time Output A-1 1.00 s
037 104 mA_OP: Scaled Min. Val. A-1 0.013 (corresponds with 0.02
Vn)
037 105 mA_OP: Scaled Knee Val. A-1 0.067 (corresponds with 0.10
Vn)
037 106 mA_OP: Scaled Max. Val. A-1 0.667 (corresponds with 1.00
Vn)
037 107 mA_OP: AnOut Min. Val. A-1 4 mA
037 108 mA_OP: AnOut Knee Point A-1 16 mA
037 109 mA_OP: AnOut Max. Val. A-1 18 mA
Note:
A check of the set characteristic and its acceptance by the device, if the setting was
properly entered, will only occur after the device, set to M A I N : P r o t e c t i o n
E n a b l e d is switched on-line again.
Ia / mA
20
Max.
output value 18
Knee point
16
output value
14
12
10
6
Min.
output value 4
0
0 0.02 0.1 1 1.2 1.3 1.4 1.5 Vnom
0.013 0.067 0.667 1.0 Mx,scal
19Z5265B_EN
D5Z52KFA
3-34 Example of a characteristic curve for analog measured data output . In this example the range starting value is = 0; also possible is
directional-signed output (see corresponding example in section BCD Measured Data Output).
Measured data from external devices, which must be scaled to 0 ... 100%, can be
written to the following parameters of the P438 using the communications interface.
These "external" measured values are output by the P438 either in BCD data form or
as load-independent direct current, provided that the BCD measured data output
function or the channels of the analog measured data output function are configured
accordingly.
The P438 has 17 LED indicators for the indication of binary signals. Four of the LED
indicators are permanently assigned to fixed functions. The other 12 LED indicators are
freely configurable. These freely configurable multicolor LED indicators may be set to
emit red, green or amber light, but amber cannot be configured individually as it results
from the LED indicator simultaneously emitting both red and green light.
H 1 (green) 'HEALTHY' Not configurable. H 1 indicates the operational readiness of the device
(supply voltage is present).
H 17 (red) 'EDIT MODE' Not configurable. H 17 indicates the input mode. Only when the device
is in this mode, can setting parameters be changed by pressing the
and keys. (See Chapter 6, section 'Display and Keypad')
H 4 (red) 'TRIP' With the P438 this LED indicator is assigned the
M A I N : G e n . T r i p S i g n a l function by default. This assignment
can be modified.
H 4 (green) ---- This LED indicator may be freely configured to emit green light.
H 5 to H 16 ---- Both colors (red & green) may be configured individually and freely for
these LED indicators.
The figure below shows the layout of the LED indicators situated on the front panel user
interface (HMI) of the 40TE & 84TE cases.
H4
H3
TRIP
ALARM
F1 H18
H2 OUT OF SERVICE
H1
H17
HEALTHY
EDIT MODE
F2 H19
H5
H6
F3 H20
H7
H8 C
G
H9
H10
G F4 H21
H11
H12
G G F5
G
H13 H22
H14
H15
H16
G F6 H23
12 Z6100B_EN
3-36 Layout of the LED indicators situated on the front panel user interface (HMI)
Therefore the operating modes turn out to be the 23=8 possible combinations of the
following components:
• flashing / continuous,
• energize-on-signal (ES) / normally-energized (NE),
• updating / latching with manual reset,
• energize-on-signal (ES) with reset after new fault (flashing / continuous) and
• energize-on-signal (ES) with reset after new system disturbance (flashing /
continuous),
LED: Operating
Mode H xx
[ xxx xxx ]
1
2
3
4
5
6
7
8
9
10
11
-Hxx
12 (Red)
! G !
1: ES Updating
2: ES Manual Reset
3: ES Reset (Fault) ≥1
4: ES Reset (Syst.Dist)
5: NE Updating
6: NE Manual Reset
7: ES Updating Bl
8: ES Manual Reset Bl
9: ES Reset (Fault) Bl LED: State H xx
10: ES Rst (Syst.Dst) Bl & Red
[ zzz zzz ]
11: NE Updating Bl
&
12: NE Manual Reset Bl &
& S1 1
R1
LED: Fct.Assig.
Hxx Red
[ yyy yyy ]
Signal 1
Signal 2
Signal 3 m out of n LED: State H xx
Signal n & Green
[ zzz zzz ]
&
&
Selected Signals
& S1 1
R1
LED: Fct.Assig.
Hxx Green
[ yyy yyy ]
Signal 1
Signal 2 -Hxx
Signal 3 m out of n (Green)
Signal n
&
OSCIL: Record.
in Progress
[ 035 000 ]
&
OSCIL: System
Disturb. runn
[ 035 004 ]
MAIN: General
Reset EXT
[ 005 255 ]
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: Reset
LED
306 020
12Z6200A_UK
The secondary phase currents and voltages of the system transformers are fed into the
P438 and are – electrically isolated – converted to standardized electronics levels.
The analog quantities are digitized and are thus available for further processing.
Settings that do not refer to nominal quantities are converted by the P438 to nominal
quantities. The user must therefore set the secondary nominal currents and voltages of
the system transformers.
The connection arrangement of the measuring circuits on the P438 must also be set.
Figures 3-38 and 3-40 show the standard connection. The phase of the digitized
currents is rotated by 180° by this setting.
The P438 is designed for operation in Classic single feed or Autotransformer feed
modes. Figure 3-38 shows the connection in Classic single feed mode and figure 3-39
the connection in Autotransformer feed mode.
Supply
Catenary
I>
MAIN: Feeding
Mode
[ 010 135 ]
1
2
1: Classic Single
Feed
2: Auto-
Transformer Feed
MAIN: Vn VT.
c Sec.
[ 010 009 ]
1U
2U V
Catenary
Rail
48Z5411A_UK
3-38 Connecting the P438 measuring circuits in the 'Classic single feed' operating mode
Supply Catenary
Supply Feeder
MAIN: Feeding
Mode
[ 010 135 ]
1
2
I>
1: Classic Single
Feed
2: Auto-
Transformer Feed
MAIN: Vn VT.
I> c Sec.
[ 010 009 ]
1U
2U Vcat
3U Vfdr
4U
S
+ V
-
1: Standard
(Y = 1)
2: Opposite
(Y = -1) S
+ I
-
Feeder
Catenary
Rail
48Z5412A_UK
3-39 Connecting the P438 measuring circuits in the 'Autotransformer feed' operating mode
In addition to the protection of the catenary in normal train operation, the P438 also
provides defrost protection. An additional current transformer must be connected when
the device is in the 'Defrost operation' operating mode. Figure 3-40 shows the
connection with 'Defrost operation'. In this operating mode, circuit breakers Q1, Q3 and
Q4 are closed whereas circuit breaker Q2 is open. It is important to ensure - from the
installation side - that circuit breaker Q2 is opened before circuit breakers Q3 and Q4 are
closed.
Supply
Catenary
Q1 Q2
MAIN: Line CT MAIN: In Device
Orientation [ 010 003 ]
[ 010 004 ]
Icat
X X.Y I
1: Standard
(Y = 1)
2: Opposite
(Y = -1)
1: Standard
(Y = 1)
2: Opposite
(Y = -1)
Catenary 1
Q3
Catenary 2
Q4
Rail
48Z5413A_UK
The P438 has an operating data measurement function for the display of currents and
voltages measured as well as quantities derived from these measured values.
Set minimum thresholds must be exceeded in order for measured values to be
displayed, in orderso as to avoid fluctuating small values from noise. If these minimum
thresholds are not exceeded, 'Not Measured' is displayed in place of a value. The
following measured values are displayed:
The ratio of the second, third and fifth harmonic current components to the
fundamental component of the current: kHarm,ΣI(xfn)/I(fn)
The measured data are updated at 1 s intervals. Updating is interrupted if the self-
monitoring function detects a hardware fault.
MAIN: Minimum I
MAIN: Hardware Measurem't
fault [ 011 030 ]
306 018
I
Icat
Ifdr
MAIN: Current
I p.u.
[ 004 111 ]
MAIN: Current
Icat p.u.
[ 005 041 ]
MAIN: Current
Ifdr p.u.
[ 006 041 ]
MAIN: Inom C.T.
prim.
[ 010 001 ]
MAIN: Current
I prim.
[ 004 110 ]
MAIN: Current
Icat prim.
[ 005 040 ]
MAIN: Current
Ifdr prim.
[ 006 040 ]
48Z5432A_UK
Harmonic current
components
The harmonic current components are displayed both as per-unit quantities referred to
the nominal quantities of the P438 and as primary quantities. When the optional
processor module with an integrated DSP coprocessor is fitted the additional third and
fifth harmonic current components are displayed both as per-unit quantities referred to
the nominal quantities of the P438 and as primary quantities. To allow display in primary
values, the primary nominal current of the system current transformer should be set in
the P438.
When distance protection is operated with the harmonics adaptation feature enabled
then dynamic harmonics factor M A I N : k H a r m . Σ I ( x f n ) / I ( f n ) is displayed.
3-42 Measured operating data - Harmonic current components and harmonics factor for distance protection
MAIN: Minimum V
C&VTS: VTS Volts Meas'mt
Failure [ 011 032 ]
[ 038 023 ]
MAIN: Hardware
fault
306 018
V
Vcat
Vfdr
MAIN: Voltage
V p.u.
[ 004 113 ]
MAIN: Voltage
Vcat p.u.
[ 005 043 ]
MAIN: Voltage
Vfdr p.u.
[ 006 043 ]
MAIN: Vn V.T.
prim.
[ 010 002 ]
MAIN: Voltage
V prim.
[ 004 112 ]
MAIN: Voltage
Vcat prim.
[ 005 042 ]
MAIN: Voltage
Vfdr prim.
[ 006 042 ]
48Z5433A_UK
The fundamental components of current and voltage are used for determining the
measured values.
Angles and load flow direction are determined only if the current exceeds the minimum
threshold of 0.1 In and if the voltage exceeds the threshold of 1 V. The active power
factor is determined if, in addition to the previously mentioned thresholds, the apparent
power exceeds the threshold of 0.05 Sn.
1 2 3 4 5 6 7
MAIN: Hardware
fault
306 018
I I > 0.1 In
V V > 1 V
MAIN: Frequency fn
[ 010 030 ]
C
fn
-45°> N<135° 1
-45°< N>135° 2
48Z6310A_UK
1 2 3 4 5 6 7
MAIN: Hardware
fault
306 018
MAIN: Frequency
fn
[ 010 030 ]
C
fn
1)
Icat (I)
fn
1)
MAIN: Active
Ifdr Power P p.u.
[ 004 051 ]
fn
Vcat (V) 1)
MAIN: Reac.
Power Q p.u.
[ 004 053 ]
S > 0.05 Sn
&
MAIN: Active
Power Factor
[ 004 054 ]
MAIN: In C.T.
Prim.
[ 010 001 ]
MAIN: Vn V.T.
Prim.
[ 010 002 ]
MAIN: Active
Power P Prim.
[ 004 050 ]
MAIN: Reac.
Power Q Prim.
[ 004 052 ]
Operating impedance,
reactance and resistance
If there is a fault in the hardware or in the voltage-measuring circuit, the measured
values are not determined.
The fundamental components of current and voltage are used for determining the
measured values. The values are determined only if the current exceeds the minimum
threshold of 0.1 In and if the voltage exceeds the threshold of 1 V.
V
V
MAIN: Frequency fn
[ 010 030 ]
MAIN: Load
impedance Z p.u
[ 005 004 ]
MAIN: In device
[ 010 003 ]
MAIN: Load
impedance Z sec
[ 005 000 ]
MAIN: Load
reactance X sec
[ 005 195 ]
MAIN: Load
resist. R sec
[ 005 197 ]
MAIN: In C.T.
prim.
[ 010 001 ]
MAIN: Vn V.T.
prim.
[ 010 002 ]
48Z5415A_UK
Frequency
The P438 determines the frequency from the voltage. The frequency is determined only
if the voltage exceeds a minimum threshold of 10 V and if there is no fault in the voltage-
measuring circuit.
MAIN: Frequency f
[ 004 040 ]
C&VTS: Frequency
fn
[ 010 030 ]
MAIN: Frequency
f p.u.
[ 004 070 ]
48Z5416A_UK
Cancelling a protection
function
The following conditions must be met before a protection function can be cancelled:
If the above conditions are met, proceed through the Configuration branch of the menu
tree to access the setting relevant for the protection function to be cancelled. If, for
example, the "LIMIT" function group is to be cancelled, access the L I M I T : L i m i t
T h r e s h o l d s I < > parameter and set its value to 'Disabled'. To re-include the
"LIMIT" function in the device configuration, access the same parameter and set its value
to 'Enabled'.
Blocking inrush
stabilization
Inrush stabilization is blocked if M A I N : I n r . I ( 2 f n ) / I ( f n ) S G x is set to 'Blocked' or
if an external blocking signal has been triggered.
1 2 3 4 5 6 7
MAIN: Inrush
MAIN: Protection Restr. Ready
Active & [ 041 024 ]
306 001
MAIN: Block.
Inrush RstrEXT
[ 039 169 ]
MAIN: Inr.
I(2fn)/I(fn)SGx
[ * ]
Blocked
*
Setting MAIN: Inr.
I(2fn)/I(fn)SGx
Operation of inrush
stabilization
The inrush stabilization function identifies an inrush current by evaluating the ratio of the
second harmonic current component to the fundamental. Inrush stabilization will start
when this ratio exceeds the threshold set at M A I N : I n r . I ( 2 * f n ) / I ( f n ) S G x .
The current triggers M A I N : I > E n a b . I n r . R e s t . S G x and
M A I N : I > L i f t I n r . R s t r . S G x limit the operating range of inrush stabilization.
The function will be blocked if the current drops below or exceeds these set thresholds.
1 2 3 4 5 6 7
MAIN: Inr.Restr.
I & 1 t & Triggered
[ 041 025 ]
MAIN: Inr.
I(2fn)/I(fn)SGx
[ * ]
MAIN: I(2fn)/
I(fn)
310 052
*
Setting MAIN: I> Lift MAIN: t Lift MAIN: I> Enab. MAIN: Inr.
Inr.Rstr.SGx Inr.Rstr. SG Inr.Rest.SGx I(2fn)/I(fn)SGx
1 2 3 4 5 6 7
MAIN: Fct.Asg.
Inr.Rstr.SGx
[ * ]
Starting signal 1
m out of n
Starting signal 2
...
Starting signal n
Selected
starting signals
Using the measured values U and I, a fault's resistance and direction are determined by
the distance, high impedance and directional overcurrent protection functions. Voltage
memory is available so that direction measurement will function correctly, even with very
low fault voltages.
The voltage V is fed to a voltage memory. If the voltage exceeds the default value of
0.55 Vn and if there is no general starting of the distance protection function, then the
voltage memory will be synchronized. Synchronization requires approximately 10 full
cycles.
If the magnitude of the voltage V drops below 0.5 Vn or if distance protection starts,
voltage memory synchronization will be terminated. The voltage memory is then free-
running and remains enabled for 6 s.
1 2 3 4 5 6 7
MAIN: General
starting
[ 036 000 ] &
BUOC: Starting I>
[ 036 013 ]
1 MAIN: Vmemory
& & S1 1 enable
10 T 305 049
V R MAIN: tVmemory
active
1 [ 040 034 ]
6.0 s
C C
V(memory)
48Z6318A_EN
Two multiple blockings can be defined using 'm out of n' parameters. The selected
functions may then be blocked using an appropriately configured binary signal input.
3.12.7 Blocked/Faulty
As of version –606 the circuit breaker may be closed either by the auto-reclose function
(RECLS) integrated in the P438, by a setting or by an appropriately configured binary
signal input. The close command issued from the user interface (HMI), the setting
parameter or the binary signal input will only be executed if there is no main-trip or re-trip
command present at the P438. Moreover an appropriate enable condition must be met.
Additionally the close command is not executed when, with the setting of
M A I N : C l C m d I n h i b . b y C B C l to 'Yes', there is a "CB closed" position signal
present.
The duration of the close command can be set. The close command is terminated when
a main-trip command or re-trip command is issued.
Close command counter
The number of close commands is counted. This counter and the trip command counter
may be reset together or by "General Reset".
1 2 3 4 5 6 7
MAIN: Main-Trip
Signal
[ 039 101 ]
MAIN: Re-Trip
Signal
[ 039 103 ]
MAIN: CB Closed
Sig. EXT &
[ 036 051 ]
MAIN: ClCmd
Inhib.by CB Cl
[ 015 042 ]
0: No
1: Yes
0: No
MAIN: Man. Close MAIN: Man. Close
1: Yes Cmd. USER Cmd. EXT
[ 018 033 ] [ 041 022 ]
MAIN: Man. Close
0 & Command
500 ms [ 037 068 ]
1
&
0: don't execute
MAIN: Man.Cl.Cmd 1: execute
Enabl.EXT MAIN: CB Close
[ 041 023 ] Pulse Durn.
MAIN: Man. Close [ 015 067 ]
Cmd. EXT
[ 041 022 ] MAIN: Close
1 t & Command
[ 037 009 ]
RECLS: Close
Command
303 021
MAIN: General
Reset USER
[ 003 002 ]
0: don't execute
1: execute
MAIN: General
Reset EXT
[ 005 255 ]
MAIN: Rst.
C.Cl/Tr.Cmd USER
[ 003 007 ]
0: don't execute
1: execute
MAIN: Rst.
Co.Cl/Tr.Cmd EXT
[ 005 210 ]
48Z6316A_UK
reverse
General start
Starting signals from the distance, backup overcurrent, definite-time overcurrent,
inverse-time overcurrent and high impedance protection functions are collectively issued
as the "General Start" signal. The number of general starts is counted.
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
48Z6315A_EN
PIR Starting
In the event of the end of the main-trip and re-trip command a timer stage of 500 ms is
started. While this timer stage is running, the 'PIR Starting' signals are set.
(PIR: Automatic testing device for Catenary, with a pre-insertion/pre-closing resistor as a
line check)
PIR Main-Trip
Re-Trip
command PIR Re-Trip
Trip command
The P438 provides the following trip commands:
Main-Trip command
Re-Trip command
Back-Trip command
The functions required to trip can be selected by setting an 'm out of n' parameter
independently for each of the trip commands. The trip command minimum trip time is
settable. The trip signals are present only as long as the conditions for the signal are
satisfied.
Block
MainTrip USER
Main-Trip
Block.
MainTrip EXT
Man. Main-Trip
MainTrip sig.
Main-Trip
'OR' gate tDWELL
MainTrip Cmd
Main-Trip
Latch
MainTrip Cmd?
Block
ReTrip USER
Re-Trip
Block.
ReTrip EXT
Man. Re-Trip
ReTrip signal
Re-Trip
'OR' gate tDWELL
ReTrip Cmd
Re-Trip
Latch
ReTrip Cmd?
Block
BackTrip USER
Back-Trip
Block.
BackTrip EXT
Man. Back-Trip
BackTrip sig.
Back-Trip
'OR' gate tDWELL
BackTrip Cmd
Back-Trip
Latch
BackTrip Cmd?
Man.M-trip
cmd USER
Man.
MainTrip sig.
Man. Mtrip
cmd EXT
Man.Re-Trip
cmd USER
Man.
ReTrip signal
Man. ReTrip
cmd. EXT
Man.B-trip
cmd USER
Man.
BackTrip sig.
Man. Btrip
cmd. EXT
1 2 3 4 5 6 7
0: Don't Execute
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
MAIN: Rst.C.
Cl/Tr.Cmd USER
[ 003 007 ]
0: Don't Execute
1: Execute
MAIN: Rst.Co.
Cl/Tr.Cmd EXT
[ 005 210 ]
48Z6317A_UK
MAIN: Re-Trip
Signal
MAIN: Back-Trip
Signal
48Z5016A_UK
The data stored in the operating data memory, the monitoring signal memory and the
event memories are date- and time-tagged. For correct time-tagging, the date and time
need to be set in the P438.
Note: It is not possible to use a signal input on the analog module Y as a minute
pulse input.
Synchronization source
The P438 provides numerous options to synchronize the internal clock:
o Telegram including the time of day received via communication interface
COMM1/IEC (full time)
o Telegram including the time of day received via communication interface
COMM2/PC (full time)
o IRIG-B signal (IRIGB; time of day only)
o Minute signal pulse presented to a binary signal input (MAIN), see figure 3-67 and
the paragraph above this figure.
With older device versions these interfaces had equal ranking i.e. clock synchronization
was carried out regardless of which sub-function initiated triggering. No conflicts have to
be taken into account as long as synchronization sources (communication master, IRIG-
B and minute pulse source) operate at the same time of day. Should the
synchronization sources operate with a different time basis unwanted step changes in
the internal clock may occur. On the other hand a redundant time of day synchronization
is often used so as to sustain time synchronization via IRIG-B interface even if and while
the SCADA communication is out of service.
For such applications the current device versions provide a selectable primary source
and back-up source for time of day synchronization that feature all of the four options
listed above.
MAIN: Prim.Source TimeSync
MAIN: BackupSourceTimeSync
Synchronization is carried out from the primary source only as long as repeated
synchronization telegrams (or minute signal pulses) are received within the timeout
period set at M A I N : T i m e S y n c . T i m e - O u t . The backup source is required if
after the set time-out there is no synchronization through the primary source.
When selecting the time telegram via IEC as the primary source the device will expect
time synchronization telegrams from server SNTP2 after server SNTP 1 has become
defective, before it will switch over to the backup source.
Time synchronization occurs solely from the primary source when the time-out stage is
blocked.
Stored data such as event logs, measured fault data etc, can be cleared in several ways.
The following mechanisms are available:
Automatic resetting of the event signals provided by LED indicators (given that the
LED operating mode has been set accordingly) and of the display of measured event
data on the front panel LCD whenever a new event occurs. In this case only the
displays on the front panel LCD are cleared but not the internal memories such as the
fault memory.
Resetting of LED indicators and measured event data displayed on the front panel
LCD by pressing the "CLEAR" key C located on the front panel user interface
(HMI). By selecting the required function at H M I : F c t . R e s e t K e y further
memories may be assigned which will then also be cleared when the "CLEAR" key is
pressed.
Selective resetting of a particular memory type (e.g. only the fault memory) via setting
parameters. For this example: Navigate to menu point
O S C I L : R e s e t R e c o r d . U S E R and set to 'Execute', see also the exact step-
for-step description in Chapter 6 'User Interface (HMI)' section 'Reset'.
Selective resetting of a particular memory type (e.g. only the fault memory) through
appropriately configured binary signal inputs. (For this example: Assign parameter
O S C I L : R e s e t R e c o r d . E X T to the relevant binary signal input, e.g.
I N P : F c t . A s s i g n m . U 3 0 1 .)
Group resetting by setting parameters, by navigating to menu point
M A I N : G r o u p R e s e t x U S E R and setting it to 'Execute'. For this the relevant
memories (i.e. those to be reset) must be assigned to parameter
MAIN: Fct.Assign. Reset x.
Group resetting through appropriately configured binary signal inputs. (Assign
parameter M A I N : G r o u p r e s e t . x E X T to the relevant binary signal input, e.g.
I N P : F c t . A s s i g n m . U 3 0 1 after memories to be reset have been assigned to
parameter M A I N : F c t . A s s i g n . R e s e t x .)
General resetting by setting parameters (menu point
M A I N : G e n e r a l R e s e t U S E R ). All memories, counters, events etc. are reset
without any special configuration options.
Should several resetting actions have been configured for one particular memory then
they all have equal priority.
In the event of a cold restart, namely simultaneous failure of both internal battery and
substation auxiliary supply, all stored signals and values will be lost.
Further resetting possibilities are basically not distinct resetting actions but make access
especially easy to one of the resetting actions described above i.e. by configuring them
to a function key.
Function keys may be configured in such a way that resetting of a specific memory is
assigned. Technically this is similar to resetting through an appropriately configured
binary signal input. When a function key is pressed a signal to a binary signal input is
simulated. (See section 'Configurable Function Keys'.)
Similarly to this, but one step less direct, is the possibility to assign one of the two
menu jump lists (L O C : T r i g . M e n u J m p x E X T ) to a function key and to
include the relevant menu point for a resetting action (e.g.
O U T P : R e s e t L a t c h . U S E R ) in the definition
(L O C : F c t . M e n u J m p L i s t x ) of the selected menu jump list.
The same may be achieved with the "READ" key by assigning it a menu point for a
resetting action through H M I : F c t . R e a d K e y .
3-68 General reset, LED reset and measured event data reset from the user interface (HMI)
m out of n
MAIN: Group
Reset 1 USER
[ * ]
0
1 ≥1 &
0: Don't Execute
1: Execute
MAIN: Group
Reset 1 EXT
[ * ]
MAIN: Fct.Assign.
Reset 1
[ * ]
m out of n
12Z61RMB_UK
3-69 "CLEAR" key on the user interface (HMI) and, as an example, group resetting of the operating data recording (e.g. as an example for the
reset signal O P _ R C : R e s e t R e c o r d . E X T ); further examples for resetting signals generated in this way are:
- MAIN: Rst.Co.Cl/Tr.Cmd EXT
- MT_RC: Reset Record. EXT
- OL_RC: Reset Record. EXT
- OSCIL: Reset Record. EXT
- RECLS: Reset Counters EXT
- CBM: Reset Meas.Val.EXT
- [005 255] MAIN: General Reset EXT
- [006 054] COMM3: Reset No.Tlg.Err.EXT
- [034 059]... [034 066] LOGIC: Reset x EXT (x=1...8)
- [036 087] RTDmA: Reset Output EXT
- [036 223] RECLS: Reset Recl.Time2 EXT
- [038 061] THERM: Reset Replica EXT
- [040 015] OUTP: Reset Latch. EXT
- [040 138] MAIN: Reset Latch.Trip EXT
- [065 001] MAIN: Reset Indicat. EXT
3-70 Assigning the rear port communication interfaces to physical communication channels
If tests are run on the P438, the user is advised to activate the test mode so that all
incoming signals via the serial interfaces using protocols according to IEC will be marked
accordingly.
With the P438, four independent setting groups may be pre-set. The user may switch
between setting groups during operation without interrupting the protection function.
If, after the supply voltage is turned on, no logic level of ' 1 ' is present at any of the
binary signal inputs selected for the setting group selection, then the setting group
selected using the function parameter will become active once the stored time has
elapsed. The previous setting group remains active while the stored hold timer stage is
running.
Setting group selection may also occur during a general starting condition. In this case,
the settings of all protection functions, for example the Impedance-Time Characteristics
of the distance protection, are immediately updated. For setting group selection, a
maximum inherent delay of approximately 100 ms must be taken into account. This
must be considered for the duration of the triggering signal when binary signal inputs are
used for setting group selection.
Settings for which only one address is given in the following sections are equally
effective for all four setting groups.
Comprehensive monitoring routines in the P438 ensure that internal faults are detected
and do not lead to malfunctions.
Cyclic tests
After start-up has been successfully completed, cyclic self-monitoring tests will be run
during operation. In the event of a positive test result, a specified monitoring signal will
be issued and stored in a non-volatile memory – the monitoring signal memory – along
with the assigned date and time (see also Monitoring Signal Recording).
The self-monitoring function monitors the built-in battery for any drop below the minimum
acceptable voltage level. If the associated monitoring signal is displayed, then the
battery should be replaced within a month, since otherwise there is the danger of data
loss if the supply voltage should fail. Chapter 11 gives further instructions on battery
replacement.
Peripheral fault
By setting an 'm out of n' parameter, a peripheral fault can generate an alarm in addition
to the self-monitoring signals.
Signal
The monitoring signals are also signaled via the output relay mapped to
C H E C K : A l a r m . The output relay operates as long as an internal fault is detected.
Device response
The response of the P438 depends on the type of monitoring signal. The following
responses are possible:
Signaling Only
If there is no malfunction associated with the monitoring signal, then only a signal is
issued, and there are no further consequences. This situation exists, for example,
when internal data acquisition memories overflow.
Selective Blocking
If a fault is diagnosed solely in an area that does not affect the protection functions,
then only the affected area is blocked. This would apply, for example, to the
detection of a fault on the communication module or in the area of the PC interface.
Warm Restart
If the self-monitoring function detects a fault that might be eliminated by a system
restart – such as a fault in the hardware –, then a procedure called a warm restart is
automatically initiated. During this procedure, as with any start-up, the computer
system is reset to a defined state. A warm restart is characterized by the fact that no
stored data and, in particular, no settings are affected by the procedure. A warm
restart can also be triggered manually by a control action. During a warm restart
sequence the protection functions and the communication through serial interfaces
will be blocked. If the same fault is detected after a warm restart has been triggered
by the self-monitoring function, then the protection functions remain blocked but
communication through the serial interfaces will usually be possible again.
Cold Restart
If a corrupted setting group is diagnosed during the checksum test, which is part of
the self-monitoring procedure, then a cold restart is carried out. This is necessary
because the protection device cannot identify which setting in the group is corrupted.
A cold restart causes all internal memories to be reset to a defined state. This means
that all the device's settings are also erased after a cold restart. In order to establish
a safe initial state, the default values have been selected so that the protection
functions are blocked. Both the monitoring signal that triggered the cold restart and
the value indicating settings loss are entered in the monitoring signal memory.
The behavior caused by sporadic faults could lead to an unwanted blocking of the device
if the monitoring signal memory has not been reset in the interim, for example, because
the substation is difficult to reach in wintertime or display and clearing of the monitoring
signal memory via the communication interfaces was not enabled. A "memory retention
time" timer has been introduced to defuse this problem.
Now device blocking only occurs when the same internal device fault is detected twice
during this time duration. Otherwise, the device will continue to operate normally after a
warm restart. This timer is blocked is blocked by default so that, when an internal fault is
detected, the device will operate in the same way as the previous versions.
OP_RC: Operat.
data record.
[ 003 024 ]
Operating memory
MAIN: Oper.-relev.
signal
306 024
MAIN: General
reset USER + OP_RC: No. oper.
[ 003 002 ] data sig.
[ 100 002 ]
1: execute R
MAIN: General
reset EXT
[ 005 255 ]
OP_RC: Reset
record. EXT
[ 005 213 ]
OP_RC: Reset
record. USER
[ 100 001 ]
1
0: don't execute
1: execute
12Z61CMB_EN
3-74 Operating data recording and counter for signals relevant to system operation
The monitoring signals generated by the self-monitoring function are recorded in the
monitoring signal memory. The memory buffer allows for a maximum of 30 entries.
If more than 29 monitoring signals occur without interim memory clearance, the
C H E C K : O v e r f l o w M T _ R C signal is entered as the last entry. Monitoring signals
prompted by a hardware fault in the unit are always entered in the monitoring signal
memory. Monitoring signals prompted by a peripheral fault can be entered into the
monitoring signal memory, if desired. The user can select this option by setting an
'm out of n' parameter (see 'Self-Monitoring').
If at least one entry is stored in the monitoring signal memory, this fact is signaled by the
red LED indicator H 3 on the user interface (HMI). Each new entry causes the LED to
flash (on/off/on....).
The monitoring signal memory can only be cleared manually by a control action.
Entries in the monitoring signal memory are not cleared automatically, even if the
corresponding test in a new test cycle now shows the device to be healthy. The
contents of the monitoring signal memory can be read from the local control panel or
through the PC or communication interface. The time and date information assigned to
the individual entries can be read out through the PC or communication interface or from
the user interface (HMI) or operating program.
CHECK: Hardware
fault
304 950
Selected Monit.
sig.
MT_RC: Reset
Record. USER
[ 003 008 ]
CT30 CHECK: Overflow
≥1 MT_RC
[ 090 012 ]
0
MT_RC: No. Monit.
1 ≥1 Signals
[ 004 019 ]
0: Don't Execute
MT_RC: Reset 1: Execute
Record. EXT
[ 005 240 ]
12Z6155A_UK
Overload Duration
In the event of an overload, the P438 determines the overload duration. The overload
duration is defined as the time between the start and end of the OL_ R C : R e c o r d . i n
P r o g r e s s signal.
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
OL_RC: Reset
record. USER
[ 100 003 ]
1: execute
50Z0137A_EN
OL_RC: Record.
in progress C
[ 035 003 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
OL_RC: Reset
record. USER
[ 100 003 ]
1: execute
12Z6238A_EN
OL_RC: Record. in
progress
[ 035 003 ]
THERM: Starting OL_RC: No.
k*Iref> + overload
[ 041 108 ] [ 004 101 ]
R
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
OL_RC: Reset
record. USER
[ 100 003 ]
1: execute
45Z63DXA_EN
Time tagging
The date of each overload event is stored. The overload start or end signals are likewise
time-tagged by the internal clock. The date and time assigned to an overload event
when the event begins can be read out from the overload memory on the local control
panel or through the PC and communication interfaces. The time information (relative to
the onset of the overload) can be retrieved from the overload memory or through the PC
or communication interfaces.
Overload logging
Protection signals during an overload event are logged in chronological order with
reference to the specific event. A total of eight overload events, each involving a
maximum of 200 start or end signals, can be stored in the non-volatile overload
memories. After eight overload events have been logged, the oldest overload log will be
overwritten, unless memories have been cleared in the interim. If more than 199 start or
end signals have occurred during a single overload event, then OL_ R C : O v e r l .
M e m . O v e r f l o w will be entered as the last signal.
In addition to the signals, the measured overload data will also be entered in the
overload memory.
The overload logs can be read from the user interface (HMI) or through the PC or
communication interfaces.
OL_RC: Record. C
in Progress
[ 035 003 ]
OL_RC: Overload
n
Measured Value 1 Recording n
1 033 020
Measured Value 2
2 033 021
Measured Value 3
Measured Value n 3 033 022
0
1 ≥1
MAIN: General
Reset USER 0: Don't Execute
[ 003 002 ] 1: Execute
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
OL_RC: Reset
Record. EXT
[ 005 241 ]
12Z6117A_UK
When there is a primary system fault, the P438 collects the following measured fault
data:
Running Time
Fault Duration
Fault Determination
Run Time to Measurement
Fault current
Fault voltage (short-circuit voltage)
Fault angle
Primary and secondary fault reactance
Primary and secondary fault resistance
Fault location in km or percentage of the protected line
Catenary current (only in ‘Autotransformer feed’ operating mode)
Feeder current (only in ‘Autotransformer feed’ operating mode)
Current which determines the defrost protection
Voltage of the catenary (only in ‘Autotransformer feed’ operating mode)
Voltage of the feeder (only in ‘Autotransformer feed’ operating mode)
The ratio of the second, third and fifth harmonic current components to the
fundamental component of the current, kHarmΣI(xfn)/I(fn) (only in ‘Autotransformer
feed’ operating mode and with the optional processor module with an integrated DSP
coprocessor fitted and if the harmonics adaptation feature is enabled in the distance
protection function)
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
64Z70DMA_UK
The time difference between the begining of the fault and the fault data acquisition time
is also displayed.
OSCIL: Record.
in Progress
[ 035 000 ]
DTOC: Starting
I>H
[ 035 022 ]
DIST: Starting
[ 036 135 ]
OSCIL: I>
Triggered
[ 035 013 ]
OSCIL: Trigger
[ 037 076 ]
I Imax
1 ... 4, 6 ... 9
Id,max 5
Idfrst
48Z6321A_UK
'Always'
The calculation and output of fault location always takes place if the other measured
fault data have also been determined.
'Only aft. trip Z1/t1'
The calculation and output of fault location takes place if the P438 issues the 'trip in
impedance zone 1 with normal reach’ decision.
'Only aft.trp Z1ze/t1'
The calculation and output of the fault location takes place if the P438 issues the 'trip
in impedance zone 1 with extended reach’ decision.
FT_DA: Save
measured values
305 052
FT_DA: Outp.
Fault Loc. SGx
[ * ]
1: Always
2: Only aft. Trip
Z1/t1
3: Only aft. Tr.
Z1ze/t1 FT_DA: Outp.
fault location
305 051
DIST: Trip
Signal Z1/t1
[ 039 016 ]
DIST: Trip
Signal Z1,ze
[ 035 074 ]
48Z5021A_UK
If the fault is detected by the Backup DTOC protection, the fault voltage, the voltage of
the catenary and feeder, as well as the fault reactance, the fault impedance and the fault
angle cannot be determined.
The currents and voltages are displayed as per-unit quantities referred to In and Vn If
the measured or calculated values are outside of the acceptable measuring range,
‘Overflow’ is displayed.
FT_DA: Record.
in progress
[ 035 000 ]
FT_DA: Save C
measured values
305 052
I
FT_DA: Fault
current p.u.
[ 004 025 ]
R
V
FT_DA: Fault
voltage p.u.
[ 004 026 ]
R
FT_DA: Fault
loop angle
[ 004 024 ]
R
FT_DA: Fault
reactance,sec.
[ 004 028 ]
R
FT_DA: Fault
impedance,sec.
[ 004 023 ]
R
FT_DA: Fault
reactance,prim
[ 004 029 ]
R
FT_DA: Fault
impedance,prim
[ 004 176 ]
R
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset LED
306 020
3-83 Acquisition of the fault currents and voltage, fault angles, fault reactance and impedance
FT_DA: Record.
in Progress
[ 035 000 ]
FT_DA: Save C
measured Values
305 052
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
MAIN: Reset LED
306 020
48Z6323A_UK
FT_DA: Record.
in progress
[ 035 000 ]
FT_DA: Save
measured values C C
305 052
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset LED
306 020
48Z6324A_EN
FT_DA: Line
Length 1 SGx
[ * ]
FT_DA: Line
ReactXSec 1 SGx
[ * ]
FT_DA: Outp. C
fault location
305 051
FT_DA: Fault
FT_DA: Fault Location
Reactance,Sec. [ 004 022 ]
[ 004 028 ] R
3-86 Fault location acquisition. (The diagram displays data points with only one line section used. The P438 can consider a maximum of 10 line
sections in its acquisition of the fault location.)
Each line section is considered a linear segment; line sections must be configured in
consecutive sequence. Any line section not needed is set to Blocked.
The example in the figure below shows the setting for three line sections. For this
example line sections 4 to 10 are set to Blocked.
Reactance
X3
XF
X2
X1
L1 L2 L(XF) L3 Length
of Line
48Z6320A_EN
3-87 Illustrated example for a fault location acquisition with three line sections used for calculation
Reactance values exceeding the set parameter range are calculated with the values set
for the last line section.
In the example in figure 3-87 the fault location results from the sum L2 of the first two line
sections' lengths and the calculated segment of line section 3.
Example: X1 = 10 Ω, L1 = 10 km
X2 = 18 Ω, L2 = 20 km
X3 = 30 Ω, L3 = 35 km
XF = 27.5 Ω, Xmax = X3 = 30 Ω
therefore:
XFnorm = (27.5 Ω / 30 Ω) · 100 % = 91.67 %
A line section is considered to be Blocked when at least one of its parameters (reactance
or line length) is set to Blocked.
In case of an incorrect setting the P438 will issue an error message which is entered into
the monitoring signal memory:
In this case the fault location is not calculated. The measured value is issued as 'Not
Measured'.
OSCIL: I>
OSCIL: Trigger
In addition, the user can set a logical "OR" combination of logic signals ('m out of n'
setting) which appearance will trigger fault recording.
Fault counting
Faults are counted and identified by sequential numbers.
OSCIL: I>
[ 016 013 ]
I OSCIL: I>
Triggered
[ 035 013 ]
OSCIL: Fct
Assig. Trigger
[ 003 085 ]
Signal 1
Signal 2
m out of n
Signal 3
Signal n
Selected signals
OSCIL: Trigger
USER
[ 003 041 ]
0 OSCIL: Record.
in Progress
1 [ 035 000 ]
48Z6325A_UK
Time tagging
The date that is assigned to each fault by the internal clock is stored. A fault’s individual
start or end signals are likewise time-tagged. The date and time assigned to a fault
when the fault begins can be read out from the fault memory on the HMI or through the
PC and communication interfaces. The time information (relative to the onset of the
fault) that is assigned to the signals can be retrieved from the fault memory or through
the PC or communication interfaces.
Fault recordings
Protection signals, including the signals during the settable pre-fault and post-fault
windows, are logged in chronological order with reference to the specific fault. A total of
eight faults, each involving a maximum of 200 start or end signals, can be stored in the
non-volatile fault memories. After eight faults have been recorded, the oldest fault
recording will be overwritten, unless memories have been cleared in the interim. If more
than 199 start or end signals have occurred during a single fault, then O S C I L : F a u l t
M e m . O v e r f l o w will be entered as the last signal. If the time and date are changed
during the pre-fault time, the O S C I L : F a u l t y T i m e T a g signal is generated.
In addition to the fault signals, the RMS measured fault data will also be entered in the
fault memory.
The fault recordings can be read from the user interface (HMI) or through the PC or
communication interfaces.
OSCIL: Record. C
in Progress
[ 035 000 ]
OSCIL: Fault Mem.
Signal 1 + CT200 Overflow
1 [ 035 001 ]
Signal 2 1 R
Signal 3 1
Signal n 1
OSCIL: Fault
Recording n
1 [ * ]
OSCIL: Pre-Fault
Time
[ 003 078 ]
OSCIL: Post-
Fault Time
[ 003 079 ]
OSCIL: Fault
n Recording n
Fault Memory n
1 003 000
2 033 001
3 033 002
OSCIL: Reset
Record. USER
[ 003 006 ]
0
1 1: Execute
0: Don't Execute
1: Execute
12Z6161B_UK
The signals are recorded before, during and after a fault. The window length for
disturbance recording before and after the fault can be set. A maximum time period of
32 s - independent of system frequency - is available for recording. This period can be
divided among a maximum of eight faults. The maximum recording time per fault can be
set. If a fault, including the set pre-fault and post-fault times, lasts longer than the set
maximum recording time, then recording will terminate when the set maximum recording
time is reached.
The pre-fault time is exactly adhered to if it is shorter than the set maximum recording
time. Otherwise the pre-fault time is set to the maximum recording time minus a
sampling increment, and the post-fault time is set to zero.
If the maximum recording time of 32 s is exceeded, the analog values for the oldest fault
are overwritten, but not the binary values. If more than eight faults have occurred since
the last reset, then all data for the oldest fault are overwritten.
The analog waveform data of the fault record can only be read out through the PC or
communication interfaces.
When the supply voltage is interrupted or after a warm restart, the values of all faults
remain stored.
FT_DA: Record.
in Progress C
[ 035 000 ]
OSCIL: Max
Record Time
[ 003 075 ]
OSCIL: Pre-Fault
Time
[ 003 078 ]
OSCIL: Post-Fault
Time
[ 003 079 ]
Idfrst
Analog Channel 3
R
Vcat
Analog Channel 4
R
Vfdr
Analog Channel 5
R
OSCIL: Reset
Record. USER
[ 003 006 ]
1: Execute
≥1
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
OSCIL: Reset
Record. EXT
[ 005 243 ]
48Z6326A_UK
Four impedance zones are provided by the distance protection function. The first
impedance zone offers dynamic reach settings. Zones 2, 3 and 4 provide train start-up
detection, di/dt, dv/dt and dϕ/dt, to differentiate start-ups from short circuits and overload
conditions. The user can select polygonal (quadrilateral) or circular tripping
characteristics.
Disabling or enabling
distance protection
Distance protection may be disabled or enabled using setting parameters. Enabling can
be carried out separately for each setting group.
1 2 3 4 5 6 7
DIST: General
enable USER
[ 031 073 ]
0
1 DIST: Enabled
& [ 036 104 ]
0: No
1: Yes
DIST: Enable
SGx
[ * ]
0
1
0: No
1: Yes ** *
GROUP: Group y GROUP: Group y Setting DIST: Enable
Active Active SGx
y
[ ** ]
1 036 090 Group 1 072 200
2 036 091 Group 2 073 200
3 036 092 Group 3 074 200
4 036 093 Group 4 075 200
48Z6331A_UK
Distance protection
blocking
Distance protection is blocked if one of the following conditions occurs:
C&VTS
DIST: Blocking
DIST: Z1 Forward
Reach SGx
Blocked
DIST: Z1 Reverse
Reach SGx
Blocked
DIST: tZ1,
SGx
Blocked
DIST: Blocking
t1 EXT
Blocked
DIST: Z1' Dynamic
Rev SGx
Blocked
Setting DIST: Z1 Forward DIST: Z1 Reverse DIST: tZ1 DIST: Z1' Dynamic DIST: Z1' Dynamic
Reach SGx Reach SGx SGx Fwd SGx Rev SGx
Group 1
Group 2
Group 3
Group 4
48Z5030A_UK
1 2 3 4 5 6 7
DIST: Blocking ≥1
303 667
&
Setting DIST: Z2 Forward DIST: Z2 Reverse DIST: Z2' DIST: Z2' DIST: tZ2S Short
Reach SGx Reach SGx Dynamic Fwd SGx Dynamic Rev SGx Delay SGx
Group 1 076 094 076 101 076 097 076 104 012 029
Group 2 077 094 077 101 077 097 077 104 012 079
Group 3 078 094 078 101 078 097 078 104 013 029
Group 4 079 094 079 101 079 097 079 104 013 079
Setting DIST: tZ2L Long DIST: Z2 Op.Mode DIST: Z2Delta DIST: Z2Delta DIST: Z2D.phi
Delay SGx dx/dt SGx I(di/dt) SGx V(dv/dt) SGx (dphi/dt) SGx
Group 1 012 190 072 107 072 198 072 139 072 206
Group 2 012 191 073 107 073 198 073 139 073 206
Group 3 012 192 074 107 074 198 074 139 074 206
Group 4 012 193 075 107 075 198 075 139 075 206
48Z5410C_UK
Readiness of distance
protection
The distance protection function issues the D I S T : N o t r e a d y signal if all
impedance zones and the wrong phase coupling protection are blocked.
1 2 3 4 5 6 7
DIST: Zone 2
not ready
[ 038 035 ]
DIST: Zone 3
not ready
[ 038 036 ]
DIST: Zone 4
not ready
[ 038 064 ]
DIST: WPC
not ready
[ 039 156 ]
48Z6332A_EN
3-95 D I S T : N o t r e a d y signal
Inrush Stabilization
(Harmonic Restraint)
Depending on the setting for M A I N : F c t . I n r u s h R s t r . S G x , starting decisions
made by the distance zones can be cancelled when the inrush stabilization function has
detected an inrush current.
The base point trigger compares the r.m.s. value of the current to the set value I>.
The pickup of the base point trigger is determined by a half-cycle r.m.s. calculation of the
current in order to ensure a short response time.
After operation, the full-cycle r.m.s. value of the current is monitored. This ensures the
required stability and accuracy of the measuring system.
DIST: I>
SGx
[ * ]
DIST: Enabled C
[ 036 104 ]
I DIST: I>
Starting
[ 039 001 ]
48Z5032A_UK
The P438 determines the fault impedance and the fault direction using the measured
variables V and I. In order for direction measurement to function correctly, even at very
small fault voltage values, the information stored in the voltage memory is also put to
use in these cases.
Direction measurement
The following applies to direction measurement:
For very low fault voltages, the voltage from the voltage memory is used in place of the
measured voltage in order to avoid erroneous direction decisions. The direction
decision is dependent on the following conditions:
VF > 0.1 Vn
The direction decision is issued on the basis of the fault current and the measured
fault voltage VF.
VF < 0.1 Vn
Voltage memory enabled:
The direction decision is issued on the basis of the fault current and the voltage
stored in the voltage memory.
Voltage memory not enabled:
The direction decision is issued on the basis of the fault current and the measured
fault voltage down to a minimum value of 1 V. If the fault voltage drops to a value of
less than approximately 1 V, an accurate direction determination is no longer
possible. In this case, a Fault forward decision is issued - independent of the actual
fault direction.
1 2 3 4 5 6 7
DIST: Direct.
< 1 V & using Vmeas
[ 038 045 ]
&
DIST: Direct.
& using memory
[ 038 047 ]
V
K 1
DIST: Direction
forward
I 303 669
S 2 -45° > N < 135°
V(stored)
DIST: Direction
1 … 2 -45° < N > 135° backward
303 670
DIST: Forward
& fault
[ 036 138 ]
DIST: Starting
[ 036 135 ]
DIST: Backwards
& fault
[ 036 139 ]
48Z6335A_EN
Distance characteristic
Distance characteristics for zones 1 and 2 are always visible. If they are required
distance characteristics for zones 3 and 4 can also be switched to visible and activated.
The P438 offers both circular and polygonal (quadrilateral) tripping characteristics.
The required tripping characteristics can be selected separately for each setting group.
1 2 3 4 5 6 7
Polygon
The polygonal (qadrilateral)
characteristic is active.
*
Setting DIST: Charac-
teristic SGx
48Z6333A_UK
1 2 3 4 5 6 7
0
DIST: Control via
1 user
[ 038 172 ]
0: No
1: Yes
DIST: Control
via user EXT
[ 038 171 ]
DIST: Select
Z1/Z1' USER
[ 022 011 ] DIST: Z1 enabled
& [ 039 066 ]
1
2 &
1: Z1
2: Z1'
& DIST: Z1'
DIST: Z1' enabled
enabled EXT [ 039 067 ]
[ 038 067 ]
&
DIST: Z1' ext.
enabled
[ 038 078 ]
DIST: Select
Z2/Z2' USER DIST: Z2
[ 022 021 ] enabled
& [ 039 068 ]
1
2 &
1: Z2
2: Z2'
& DIST: Z2'
DIST: Z2' enabled
enabled EXT [ 039 069 ]
[ 038 069 ]
&
DIST: Z2' ext.
enabled
[ 038 079 ]
DIST: Select
Z3/Z3' USER DIST: Z3
[ 022 038 ] enabled
& [ 036 124 ]
1
2 &
1: Z3
2: Z3'
& DIST: Z3'
DIST: Z3' enabled
enabled EXT [ 036 125 ]
[ 036 123 ]
&
DIST: Z3' ext.
enabled
[ 038 147 ]
DIST: Select
Z4/Z4' USER DIST: Z4
[ 022 194 ] enabled
& [ 036 154 ]
1
2 &
1: Z4
2: Z4'
& DIST: Z4'
DIST: Z4' enabled
enabled EXT [ 036 156 ]
[ 036 129 ]
&
DIST: Z4' ext.
enabled
[ 038 090 ]
48Z6334A_EN
Circular characteristic
In the R-X diagram, the characteristic shown in Figure 3-100 is obtained.
1 2 3 4 5 6 7
Forward direction
Zn,fwd
Tripping zone
Reverse direction
βn
αn
Rgn,rev
Rgn,fwd R
γn
Zn,rev
48Z5453BA_UK
3-100 Impedance and direction characteristic of the P438 for the 'Circle' setting
Circular characteristic,
settings
The characteristic is determined by the settings listed below. It can be set separately for
all four zones (n: 1 to 4).
Impedance Zn or Zn' in forward direction.
Impedance Zn or Zn' in reverse direction
The impedance limits the maximum reach of the circular characteristic.
If the setting is Blocked, the zone in the corresponding direction is ineffective.
Resistance limit Rgn or Rgn' in forward direction.
Resistance limit Rgn or Rgn' in reverse direction.
Therefore the tripping zone is limited to the resistances within the load blinder – i.e.
lower than Rgn (Rgn’).
For this setting, the condition: Rgn ≤ Zn must be met for all enabled zones (all
4 setting groups, all unblocked Z and Z´ zones).
If the condition is not satisfied, a warning indication and the device blocking alarm are
issued.
Load blinding angle αn
This setting is only applied if the resistive limit line, defined by Rgn, falls within the Z
circle (this is the case for α < arccos (Rgn/Zn) or α < arccos (Rgn‘/Zn‘)).
At fault impedance angles outside of the blinder cone region, the circle characteristic
operates unaffected (non-blinded).
Angle βn
Angle γn
These angles limit the tripping area in quadrants 2 and 4..
Angle γn defines areas with the form of a triangle in the 2nd and 4th quadrants.
The limit in the R-direction is given either by Rgn or by Zn, depending on the value
leading to the smaller zone.
The P438 checks whether the impedance locus is within the defined tripping area or not.
Since the reach for forward and reverse direction can be selected separately, the
direction decision determines the quadrilateral segment where the measured impedance
locus must be located so that a distance decision is issued. If the short-circuit voltages
are lower than 10 V, angles αn, βn and γn are not taken into account. The dashed
characteristic in Figure 3-100 results.
Circular characteristic,
harmonics adaptation
If distance protection operates while the harmonics adaptation feature is enabled
(D I S T : H a r m . A d a p t . A v a i l . = Yes) then impedance and reactance settings for all
zones are processed with dynamic harmonics factor
M A I N : k H a r m . Σ I ( x f n ) / I ( f n ) . In this case distance zone boundaries are reduced
dynamically:
1 1
Z n,Harm. = ⋅ Zn or Z n,Harm. ' = ⋅ Zn '
1 + k Harm. 1 + k Harm .
1 1
R gn,Harm. = ⋅ R gn or R gn,Harm. ' = ⋅ R gn '
1 + k Harm . 1 + k Harm .
Circular characteristic,
zone 1,
Zone extensions
For zone 1, the impedance reach can be extended by the zone extension factor kze.
Valid impedance and reactance values are extended for each of the set directions.
Circular characteristic,
Zones 2, 3 and 4
Figure 3-102 shows the formation of the distance decisions for impedance zone 2.
This will apply similarly to impedance zones 3 and 4.
1 2 3 4 5 6 7
*
DIST: Enabled C Setting
[ 036 104 ] & Group 1 Group 2 Group 3 Group 4
DIST: I> Starting DIST: Charac- 012 040 073 097 074 097 075 097
[ 039 001 ] C teristic SGx
C&VTS: VTS Volts DIST: Z1 Forward DIST: Z1 Forward 076 093 077 093 078 093 079 093
Failure C Reach SGx Reach SGx
[ 038 023 ] [ * ] DIST: Rg1,
DIST: Charac- DIST: Rg1, Forward SGx 076 138 077 138 078 138 079 138
teristic SGx C Forward SGx
[ * ] [ * ] DIST: Z1' 076 096 077 096 078 096 079 096
Circle DIST: Z1' Dynamic Fwd SGx
DIST: Harm. Adapt. C Dynamic Fwd SGx DIST: Rg1',
Avail. [ * ] Forward SGx 076 141 077 141 078 141 079 141
[ 022 197 ] 1) DIST: Rg1',
Yes C Forward SGx DIST: Z1 Reverse
Reach SGx 076 100 077 100 078 100 079 100
[ * ]
DIST: Forward DIST: Rg1, DIST: Rg1,
direction C Reverse SGx Reverse SGx 076 144 077 144 078 144 079 144
303 669 & [ * ]
DIST: Z1 DIST: Z1'
Enabled DIST: Rg1, Dynamic Rev SGx 076 103 077 103 078 103 079 103
[ 039 066 ] C Reverse SGx
[ * ] DIST: Rg1',
& 076 147 077 147 078 147 079 147
DIST: Z1' DIST: Z1' Reverse SGx
Enabled C Dynamic Rev SGx
[ 039 067 ] [ * ] DIST: Alpha 1 076 090 077 090 078 090 079 090
DIST: Rg1', SGx
& C Reverse SGx
DIST: Reverse DIST: beta 1 072 208 073 208 074 208 075 208
direction [ * ] Angle SGx
303 670
DIST: Alpha 1
C SGx DIST: gamma 1 076 247 077 247 078 247 079 247
& [ * ] Angle SGx
DIST: beta 1 DIST: kze
C Angle SGx Extended HSR SGx 012 034 012 084 013 034 013 084
[ * ]
DIST: gamma 1 DIST: kze 012 046 012 096 013 046 013 096
C Angle SGx Extended TDR SGx
[ * ] DIST: kze
RECLS: Zone DIST: kze SOTF/EXT SGx 012 067 012 068 012 069 012 070
Extension HSR C Extended HSR SGx
[ 036 226 ] [ * ]
RECLS: Zone DIST: kze DIST: Starting
Extension TDR C Extended TDR SGx [ 036 135 ]
[ 036 227 ] [ * ]
SOTF: Z1 Extended DIST: kze DIST: Z1 (Z1,ze)
[ 035 076 ] C SOTF/EXT SGx Starting
[ * ] & [ 039 003 ]
DIST: Zone
Extension EXT
[ 036 046 ] DIST: Z1'
& (Z1',ze) Starting
[ 039 004 ]
MAIN: Σ I(xfn)/
I(fn) 1)
310 053
CHECK: Wrong
V set. DIST Rg1
[ 098 046 ]
CHECK: Wrong
I set. DIST Rg1'
[ 098 047 ]
DIST: Wrong
MAIN: Inrush Setting Rg,x
stabil. trigg [ 041 085 ]
306 014
DIST: Zone
& Extension HSR
[ 036 103 ]
DIST: Zone
& Extension TDR
[ 038 022 ]
DIST: Zone
& Extension SOTF
[ 036 134 ]
DIST: Z1 Extended
& Extern.
[ 036 140 ]
1) only if the processor module with DSP co-processor (optional) is fitted. 48Z6330A_UK
3-101 Setting impedance zone 1 and distance measurement, operating mode set to 'Circle'
1 2 3 4 5 6 7
DIST: Enabled C
[ 036 104 ] &
DIST: I>
Starting C
[ 039 001 ]
C&VTS: VTS Volts DIST: Z2 Forward
Failure C Reach SGx
[ 038 023 ] [ * ]
DIST: Charac- DIST: Rg2,
teristic SGx C Forward SGx
[ * ] [ * ]
Circle DIST: Z2'
DIST: Harm.- 1) C Dynamic Fwd SGx
Adapt. Avail. [ * ]
[ 022 197 ] DIST: Rg2',
Yes C Forward SGx
[ * ]
DIST: Forward DIST: Z2 Reverse
direction & C Reach SGx
303 669 [ * ]
DIST: Z2 DIST: Rg2,
Enabled C Reverse SGx
[ 039 068 ] [ * ]
&
DIST: Z2' DIST: Z2'
Enabled C Dynamic Rev SGx
[ 039 069 ] [ * ]
& DIST: Rg2',
DIST: Reverse C Reverse SGx
direction [ * ]
303 670
DIST: Alpha 2
& C SGx
[ * ]
DIST: beta 2 DIST: Starting
C Angle SGx [ 036 135 ]
[ * ]
DIST: gamma 2 DIST: Z2
C Angle SGx Starting
[ * ] & [ 039 005 ]
DIST: Z2'
& Starting
[ 039 006 ]
MAIN: ΣI(xfn)/
I(fn) 1)
310 053
CHECK: Wrong set.
V DIST Rg2
[ 098 048 ]
CHECK: Wrong set.
I DIST Rg2'
[ 098 049 ]
DIST: Wrong
MAIN: Inrush Setting Rg,x
stabil. trigg [ 041 085 ]
306 014
* Setting DIST: Charac- DIST: Z2 Forward DIST: Rg2, DIST: Z2' DIST: Rg2', DIST: Z2 Reverse
teristic SGx Reach SGx Forward SGx Dynamic Fwd SGx Forward SGx Reach SGx
Group 1 012 040 076 094 076 139 076 097 076 142 076 101
Group 2 073 097 077 094 077 139 077 097 077 142 077 101
Group 3 074 097 078 094 078 139 078 097 078 142 078 101
Group 4 075 097 079 094 079 139 079 097 079 142 079 101
* Setting DIST: Rg2, DIST: Z2' DIST: Rg2', DIST: Alpha 2 DIST: beta 2 DIST: gamma 2
Reverse SGx Dynamic Rev SGx Reverse SGx SGx Angle SGx Angle SGx
Group 1 076 145 076 104 076 148 076 091 072 209 076 248
Group 2 077 145 077 104 077 148 077 091 073 209 077 248
Group 3 078 145 078 104 078 148 078 091 074 209 078 248
Group 4 079 145 079 104 079 148 079 091 075 209 079 248
1) only if the processor module with DSP co-processor (optional) is fitted. 48Z6341A_UK
3-102 Setting impedance zone 2 and distance measurement, operating mode set to 'Circle'
Polygonal (quadrilateral)
characteristic
In the R-X diagram, the characteristic shown in Figure 3-103 is obtained.
1 2 3 4 5 6 7
Tripping zone
Reverse direction
βn
αLn
αn
Rgn,rev
Rn,fwd
Rn,rev
Rgn,fwd R
γn
Zn,rev
48Z6344A_UK
3-103 Impedance and direction characteristic of the P438 for the 'Polygon’ setting
Polygonal (quadrilateral)
characteristic,
settings
The characteristic is determined by the settings listed below. It can be set separately for
all four zones (n: 1 to 4).
Impedance Zn or Zn' in forward direction.
Impedance Zn or Zn' in reverse direction
Line impedance angle αLn.
The maximum X-reach of the polygonal characteristic is calculated using the
impedance and the line angle. If the impedance setting is Blocked, the zone in the
corresponding direction is disabled.
Resistance Rn or Rn' in forward direction.
Resistance Rn or Rn' in reverse direction
Therefore the R-reach of the tripping zones is limited. The gradient of the resistive
reach line is also defined by the line angle αLn.
Resistance limit Rgn or Rgn' in forward direction.
Resistance limit Rgn or Rgn' in reverse direction.
Therefore the tripping zone is limited to the resistances within the load blinder –
i.e. lower than Rgn (Rgn’).
For this setting, the condition: Rgn ≤ Rn must be met for all enabled zones (all 4
setting groups, all unblocked Z and Z´ zones).
If the condition is not satisfied, a warning indication and the device blocking alarm are
issued.
Load blinding angle αn
At fault impedance angles outside of the blinder cone region, the circular
characteristic operates unaffectedly (non-blinded).
Angle βn
Angle γn
These angles limit the tripping area in quadrants 2 and 4..
The P438 checks whether the impedance locus is within the defined tripping area or not.
Since the reaches for forward and reverse directions can be selected separately, the
directional decision determines the quadrilateral segment where the measured
impedance locus must be located so that a distance decision is issued. If the short-
circuit voltage is lower than 10 V, angles αn, βn and γn are not taken into account.
The dashed characteristic in Figure 3-103 results.
Polygonal (quadrilateral)
characteristic,
harmonics adaptation
If distance protection operates while the harmonics adaptation feature is enabled
(D I S T : H a r m . A d a p t . A v a i l . = Yes) then impedance and reactance settings for all
zones are processed with dynamic harmonics factor
M A I N : k H a r m . Σ I ( x f n ) / I ( f n ) . In this case distance zone boundaries are reduced
dynamically
1 1
Z n,Harm. = ⋅ Zn or Z n,Harm. ' = ⋅ Zn '
1 + k Harm. 1 + k Harm .
1 1
R n,Harm. = ⋅ Rn or R n,Harm. ' = ⋅ Rn '
1 + k Harm. 1 + k Harm.
1 1
R gn,Harm. = ⋅ R gn or R gn,Harm. ' = ⋅ R gn '
1 + k Harm. 1 + k Harm .
Polygon (quadrilateral)
characteristic, Zone 1
Zone extensions
For zone 1, the impedance reach can be extended by the zone extension factor kze.
Valid impedance and reactance values are extended for each of the set directions.
Polygonal characteristic,
zones 2, 3 and 4
Figure 3-105 shows the formation of the distance decisions for impedance zone 2.
This will apply similarly to impedance zones 3 and 4.
* Setting
DIST: Enabled C
[ 036 104 ] & Group 1 Group 2 Group 3 Group 4
DIST: I> Starting DIST: Charac- 012 040 073 097 074 097 075 097
[ 039 001 ] C teristic SGx
C&VTS: VTS Volts DIST: Z1 Forward DIST: Z1 Forward 076 093 077 093 078 093 079 093
Failure C Reach SGx Reach SGx
[ 038 023 ] [ * ] DIST: R1,
DIST: Charac- DIST: Z1 Forward forw. (poly) SGx 076 115 077 115 078 115 079 115
teristic SGx C Reach SGx
[ * ] [ * ] DIST: Rg1,
Circle Forward SGx 076 138 077 138 078 138 079 138
DIST: Rg1,
DIST: Harm. C Forward SGx DIST: Z1'
Adapt. Avail. [ * ] Dynamic Fwd SGx 076 096 077 096 078 096 079 096
[ 022 197 ] 1) DIST: Z1'
Yes C Dynamic Fwd SGx DIST: R1',Dyn.
Fwd(Poly)SGx 076 118 077 118 078 118 079 118
[ * ]
DIST: Forward
direction & DIST: R1',Dyn. DIST: Rg1',
C Fwd(Poly)SGx 076 141 077 141 078 141 079 141
DIST: 303
Z1669 [ * ]
Forward SGx
Enabled
[ 039 066 ] DIST: Rg1', DIST: Z1 Reverse 076 100 077 100 078 100 079 100
C Forward SGx Reach SGx
& [ * ]
DIST: Z1' DIST: R1,Rev.
Enabled DIST: Z1 Reverse Res.(Poly)SGx 076 121 077 121 078 121 079 121
[ 039 067 ] C Reach SGx
[ * ] DIST: Rg1, 076 144 077 144 078 144 079 144
DIST: R1,Rev. Reverse SGx
C Res.(Poly)SGx DIST: Z1'
& [ * ] 076 103 077 103 078 103 079 103
Dynamic Rev SGx
DIST: Reverse DIST: Rg1,
direction C Reverse SGx DIST: R1',Dyn. 076 124 077 124 078 124 079 124
303 670 [ * ] Rev(Poly)SGx
DIST: Z1' DIST: Rg1',
C Dynamic Rev SGx Reverse SGx 076 147 077 147 078 147 079 147
& [ * ]
DIST: R1',Dyn. DIST: alpha_L 1 012 013 012 063 013 033 013 063
C Fwd(Poly)SGx (Poly) SGx
[ * ] DIST: Alpha 1
DIST: Rg1', SGx 076 090 077 090 078 090 079 090
C Reverse SGx
[ * ] DIST: beta 1 072 208 073 208 074 208 075 208
DIST: alpha_L 1 Angle SGx
C (Poly) SGx DIST: gamma 1
[ * ] Angle SGx 076 247 077 247 078 247 079 247
DIST: Alpha 1
C SGx DIST: kze 012 034 012 084 013 034 013 084
[ * ] Extended HSR SGx
DIST: beta 1 DIST: kze
C Angle SGx Extended TDR SGx 012 046 012 096 013 046 013 096
[ * ]
DIST: gamma 1 DIST: kze 012 067 012 068 012 069 012 070
C Angle SGx SOTF/EXT SGx
[ * ]
RECLS: Zone DIST: kze
Extension HSR C Extended HSR SGx
[ 036 226 ] [ * ]
RECLS: Zone DIST: kze DIST: Starting
Extension TDR C Extended TDR SGx [ 036 135 ]
[ 036 227 ] [ * ]
SOTF: Z1 Extended DIST: kze DIST: Z1 (Z1,ze)
[ 035 076 ] C SOTF/EXT SGx Starting
[ * ] & [ 039 003 ]
DIST: Zone
Extension EXT
[ 036 046 ] DIST: Z1'(Z1',ze)
Starting
& [ 039 004 ]
MAIN: I(xfn)/
I(fn) 1)
310 053
CHECK: Wrong
V set. DIST Rg1
[ 098 046 ]
CHECK: Wrong
I set. DIST Rg1'
[ 098 047 ]
DIST: Wrong
MAIN: Inrush Setting Rg,x
stabil. trigg [ 041 085 ]
306 014
DIST: Zone
& Extension HSR
[ 036 103 ]
DIST: Zone
& Extension TDR
[ 038 022 ]
DIST: Zone
& Extension SOTF
[ 036 134 ]
DIST: Z1 Extended
Extern.
& [ 036 140 ]
1) only if the processor module with DSP co-processor (optional) is fitted. 48Z6342B_UK
3-104 Setting impedance zone 1 and distance measurement, operating mode set to ‘Polygon’
1 2 3 4 5 6 7
DIST: Enabled C
[ 036 104 ] &
DIST: I>
Starting C
[ 039 001 ]
C&VTS: VTS DIST: Z2 Forward
Volts Failure C Reach SGx
[ 038 023 ] [ * ]
DIST: Charac- DIST: R2,Fwd.
teristic SGx C Res.(Poly)SGx
[ * ] [ * ]
Circle DIST: Rg2,
DIST: Harm.- C Forward SGx
adapt. avail. [ * ]
[ 022 197 ] 1) DIST: Z2'
Yes C Dynamic Fwd SGx
DIST: Forward [ * ]
direction & DIST: R2',
303 669 C forw. (Poly) SGx
DIST: Z2 [ * ]
Enabled
[ 039 068 ] DIST: Rg2',
C Forward SGx
& [ * ]
DIST: Z2'
Enabled DIST: Z2 Reverse
[ 039 069 ] C Reach SGx
[ * ]
DIST: R2,Rev.
& C Res.(Poly)SGx
[ * ]
DIST: Reverse DIST: Rg2,
direction C Reverse SGx
303 670 [ * ]
DIST: Z2'
C Dynamic Rev SGx
& [ * ]
DIST: R2',Dyn.
C Rev(Poly)SGx
[ * ]
DIST: Rg2',
C Reverse SGx
[ * ]
DIST: alpha_L 2
C (Poly) SGx
[ * ]
DIST: Alpha 2
C SGx
[ * ]
DIST: beta 2 DIST: Starting
C Angle SGx [ 036 135 ]
[ * ]
DIST: gamma 2 DIST: Z2
C Angle SGx Starting
[ * ] & [ 039 005 ]
DIST: Z2'
& Starting
[ 039 006 ]
MAIN: Σ I(xfn)/
I(fn) 1)
310 053
CHECK: Wrong
V set. DIST Rg2
[ 098 048 ]
CHECK: Wrong
I set. DIST Rg2'
[ 098 049 ]
DIST: Wrong
MAIN: Inrush Setting Rg,x
stabil. trigg [ 041 085 ]
306 014
*
Setting DIST: Charac- DIST: Z2 Forward DIST: R2,Fwd. DIST: Rg2, DIST: Z2' DIST: Rg2', DIST: R2',Dyn.
teristic SGx Reach SGx Res.(Poly)SGx Forward SGx Dynamic Fwd SGx Forward SGx Fwd(Poly)SGx
Group 1 012 040 076 094 076 116 076 139 076 097 076 142 076 119
Group 2 073 097 077 094 077 116 077 139 077 097 077 142 077 119
Group 3 074 097 078 094 078 116 078 139 078 097 078 142 078 119
Group 4 075 097 079 094 079 116 079 139 079 097 079 142 079 119
Setting DIST: Z2 Reverse DIST: R2,Rev. DIST: Rg2, DIST: Z2' DIST: R2',Dyn. DIST: Rg2', DIST: alpha_L 2
Reach SGx Res.(Poly)SGx Reverse SGx Dynamic Rev SGx Rev(Poly)SGx Reverse SGx (Poly) SGx
Group 1 076 101 076 122 076 145 076 104 076 125 076 148 012 014
Group 2 077 101 077 122 077 145 077 104 077 125 077 148 012 064
Group 3 078 101 078 122 078 145 078 104 078 125 078 148 013 014
Group 4 079 101 079 122 079 145 079 104 079 125 079 148 013 064
1) only if the processor module with DSP co-processor (optional) is fitted. 48Z6343A_UK
3-105 Setting impedance zone 2 and distance measurement, operating mode set to ‘Polygon’
Distance measurement
If the base point current is exceeded, the inductive and resistive components (X and R)
of the loop impedance (Z) are calculated continuously even during normal operation.
The algorithm is based on solving the first-order line differential equation according to
"Bonard-Bastide".
The X and R components are calculated from the 0.5 ms instantaneous values of
current and voltage and updated every 2 ms.
In the event of a line fault there is the danger of a transient overreach and an incorrect
angle measurement since the measured impedance can be lower than the static fault
impedance for a period longer than a cycle.
These measures ensure the selectivity of impedance and direction for any zones with
zero, or short applied time delays.
Switching on to a Line Without Voltage:
In this event, impedance measurement can temporarily yield undefined measured
values.
Isolation of a Line:
When a faulty or healthy line is isolated externally, the impedance measurement can
also temporarily yield undefined values.
The danger of an unwanted tripping is eliminated by a special di/dt stage that will
block distance measurement if a negative current gradient of approx. 8 % within a
half-cycle occurs with a simultaneous voltage drop (breaker open blocking).
These optimization measures provide stable operation of the device in normal operation
of the installation.
For a timer stage setting of tZ1 = 0 s, the trip command times in zone 1 are approx.
1.5 cycles in the 'core region'. For the P438, the 'core region' is defined as 0 to 95 %
of the set tripping area.
Outside the 'core region', the trip times are longer.
For fault currents < 0.8 In the calculation window is extended to achieve a stable
response.
Each impedance zone has a timer stage assigned. These timer stages are triggered by a
distance decision of the associated impedance zone. Each timer stage can be blocked
through a binary input signal.
Tripping in extended
zone 1
The impedance reach for zone 1 may be extended by the zone extension factor set at
D I S T : k z e S O T F / E X T S G x . Tripping in the extended zone takes place after the
set time-delay D I S T : t 1 , z e S O T F / E X T S G x has elapsed, and if the impedance
Z1 lies within the tripping zone of the Impedance and direction characteristic of the P438
for the 'Polygon’ setting (see Figure 3-103 on Page 3-145). The latter condition is
determined by means of the “Z1 Decision” block which evaluates the amount of
harmonics, the zero-crossings and the logic to detect fault- clearance at the end of a
fault.
1 2 3 4 5 6 7
DIST: t1,ze
& SOTF/EXT PSx
DIST: Z1 extended [ * ]
extern.
[ 036 140 ]
DIST: Zone DIST: t1,ze
extension SOTF t 0 elapsed
[ 036 134 ] [ 035 079 ]
48Z6336B_EN
Tripping in
zones 2, 3 and 4
There are two timer stages available for zone 2 and two timer stages for zone 3. One of
these timer stages is triggered if fault (short-circuit) conditions apply, the other for
overload conditions. The train start-up detection stages di/dt, dv/dt and dϕ/dt determine
which timer stage is triggered. “Zn Decision” blocks similar to zone 1.
1 2 3 4 5 6 7
DIST : t2 S
DIST : t2 S & t 0 elapsed
Enable [ 039 009]
303 671
DIST : t2 L
& t 0 elapsed
DIST : Z 2 [ 039 010]
starting
[ 039 005]
DIST : Z2 ' Z2 Decision DIST : Trip signal
starting Z2/t2L
[ 039 006] [ 039 018]
DIST : t3 S
DIST : t3 S & t 0 elapsed
Enable [ 039 143]
303 672
DIST : t3 L
& t 0 elapsed
DIST : Z 3 [ 039 144]
starting
[ 039 140]
DIST : Z3 ' Z3 Decision DIST : Trip signal
starting Z3/t3L
[ 039 141] [ 039 146]
DIST : t4 S
DIST : t4 S & t 0 elapsed
Enable [ 039 047]
310 056
DIST : t4 L
t 0 elapsed
& [ 039 048]
DIST : Z 4
starting
[ 039 042]
DIST : Z4 ' Z4 Decision DIST : Trip signal
starting Z4/t4L
[ 039 043] [ 039 041]
Parameter DIST : t2S DIST : t2L DIST : t3S DIST : t3L DIST : t4S DIST : t4L
PSx PSx PSx PSx PSx PSx
set 1 012 029 012 190 012 030 012 194 080 011 080 012
set 2 012 079 012 191 012 080 012 195 081 011 081 012
set 3 013 029 012 192 013 030 012 196 082 011 082 012
set 4 013 079 012 193 013 080 012 197 083 011 083 012
48Z6337B_EN
3-107 Setting the time-delay period for distance protection, zones 2, 3 and 4
Using zone 2 as an example, Figure 3-108 shows the conditions to be met for the train
start-up detection stages to be ready. This will apply accordingly to zones 3 and 4.
DIST: Z2 Op.mode
dx/dt SGx
[ * ]
0: Disabled
DIST: Z2Delta I
(di/dt) SGx
[ * ]
0: Blocked DIST: dv/dt
>
not ready, Z2
1 [039 031]
DIST: Z2Delta V
(dv/dt) SGx
[ * ]
0: Blocked DIST: dphi/dt
>
not ready,Z2
1 [039 032]
DIST: Z2D.phi
(dphi/dt) SGx
[ * ]
0: Blocked
Setting DIST: Z2 Op.mode DIST: Z2Delta I DIST: Z2Delta V DIST: Z2D.phi
dx/dt SGx (di/dt) SGx (dv/dt) SGx (dphi/dt) SGx
Group 1 072 107 072 198 072 139 072 206
Group 2 073 107 073 198 073 139 073 206
Group 3 074 107 074 198 074 139 074 206
Group 4 075 107 075 198 075 139 075 206
48Z5443A_UK
The P438 user can select by setting whether all three criteria (AND operation) or just one
criterion (OR operation) must be met for a short-circuit detection. If not all the criteria are
used, the P438 will set outputs of the blocked stages according to the operation selected
such that a switch between overload and short-circuit mode can be effected by the
remaining stages, as required.
If all three delta criteria are set to Blocked, short time-delays tZ2S, tZ3S or tZ4S are
always used regardless of the operation criteria (WITHOUT, OR, AND).
The dx/dt decisions remain stored for the duration of the distance protection start.
Figure 3-109 shows the operation of the train start-up detection stages, using zone 2 as
an example. This will apply similarly to zones 3 and 4.
1 2 3 4 5 6 7
DIST: Z2 Op.Mode
dx/dt SGx
[ * ] DIST: tZ2S
Enable
303 671
0
1 &
2
&
0: Without
1: OR
2: AND
DIST: di/dt
Not Ready, Z2
[ 039 030 ] &
DIST: dv/dt
Not Ready, Z2
[ 039 031 ]
DIST: dphi/dt
Not Ready, Z2
[ 039 032 ]
DIST: Z2Delta
C I(di/dt) SGx
[ * ]
DIST: di/dt
I COMP S 1 Starting, Z2
[ 039 007 ]
R
1 t
&
DIST: Z2Delta
C V(dv/dt) SGx
[ * ]
DIST: dv/dt
V COMP S 1 Starting, Z2
[ 039 008 ]
R
1 t &
DIST: Z2D.
C phi(dphi/dt) SGx
[ * ]
DIST: dphi/dt
COMP S 1 Starting, Z2
[ 039 142 ]
R
1 t &
DIST: Starting
[ 036 135 ]
48Z6338A_UK
This protection function is required for the detection of inadvertent paralleling of phase-
displaced infeeds. A typical example presents the direct feed from the three-phase
system (see figure 3-110). Each catenary section has its own supply. In order to
achieve an optimum load balance in the three-phase system, the catenary sections are
usually supplied from different phases of the three-phase system.
The catenary sections can be connected to allow compensation for the failure of one of the
section supplies. This coupling is permissible only when the supply of a section has
actually failed. If two out-of-phase supplies are inadvertently connected via the catenary,
a short circuit results. The fault (short-circuit) impedance is located on the line
perpendicular to the resultant impedance of catenary and transformers.
A
B
C
Transformer A Transformer B
Catenary
Rail
Section A Section B
X Transformer A
Z Section A + B
X Transformer B
48Z5445A_UK
The settings for the characteristics of the wrong phase coupling protection function have
to be selected such that the fault (short-circuit) impedance is located safely within the
tripping area.
1 2 3 4 5 6 7
X
Tripping zone
WPC:Zmax
WPC:Zmin WPC:β
WPC:α
48Z5448B_UK
Disabling/enabling the
wrong phase coupling
protection
The wrong phase coupling protection function must first be switched to available
(visible). Then this protection function can be disabled/enabled in each setting group.
0: No
1: Yes
DIST: Enabled
[ 036 104 ]
DIST: WPC
& not ready
[039 156]
>1
DIST: Blocking
303 667
3-112 Disabling, enabling and readiness of the wrong phase coupling protection
MAIN: Protection
active
306 001
DIST: WPC t
SGx
[ * ]
Setting DIST: WPC V< SGx DIST: WPC Zmin DIST: WPC Zmax DIST: WPC Beta DIST: WPC Alpha DIST: WPC t
SGx SGx Angle SGx SGx SGx
Group 1 076 132 076 135 076 136 076 134 076 133 076 137
Group 2 077 132 077 135 077 136 077 134 077 133 077 137
Group 3 078 132 078 135 078 136 078 134 078 133 078 137
Group 4 079 132 079 135 079 136 078 134 079 133 079 137
48Z5449A_UK
The starting and trip signals generated by the distance protection function are grouped
together to form multiple (composite) signals.
1 2 3 4 5 6 7
48Z6339A_EN
1 2 3 4 5 6 7
48Z6340A_EN
High impedance protection is designed to detect faults with high transient resistances
and it is based on a continuous monitoring for sudden current changes. The third and
fifth harmonic current components are continuously monitored so as to provide
stabilization during sudden current changes caused by load variations (e.g. a train enters
an adjacent feeder section). The operating range of the high impedance protection
function is characterized by adjustable minimum current and reactance limit values.
The sudden change of the current’s phase angle may additionally be selected as a
stabilization criterion.
Enabling/disabling high
impedance protection
High impedance protection may be disabled or enabled using setting parameters.
Enabling can be carried out separately for each setting group.
1 2 3 4 5 6 7
DELTA: General
Enable USER
[ 022 179 ]
0
1 DELTA: Enabled
& [ 038 054 ]
0: No
1: Yes
DELTA: Enable
SGx
[ * ]
0
1
0: No
1: Yes ** GROUP: Group y * Setting DELTA: Enable
y Active SGx
GROUP: Group y
Active 1 036 090 Group 1 062 030
[ ** ]
2 036 091 Group 2 063 030
3 036 092 Group 3 064 030
4 036 093 Group 4 065 030
48Z6351A_UK
Readiness of high
impedance protection
High impedance protection will issue the D E L T A : N ot Ready signal should one of the
following conditions be met:
1 2 3 4 5 6 7
DELTA: Blocking
by CB Close DELTA: tBlock
[ 022 191 ] SGx
[ * ]
0
1 & 1 t
0: No
1: Yes
MAIN: Close
Command
[ 037 009 ]
MAIN: Manual
Close EXT
[ 036 047 ]
1
2 &
1: Delta I only
2: blocked
C&VTS: VTS Volts
Failure
[ 038 023 ]
MAIN: M.c.b.
Trip V EXT
[ 004 061 ]
DELTA: Vmin
triggered * Setting
310 051 DELTA: tDelta DELTA: tBlock DELTA: Mode w/o
SGx SGx Voltage SGx
DELTA: Delta Phi
Available Group 1 062 039 062 045 062 036
[ 022 189 ]
1: Yes
Group 2 063 039 063 045 063 036
DELTA: X Super.
Available Group 3 064 039 064 045 064 036
[ 022 188 ]
1: Yes
Group 4 065 039 065 045 065 036
48Z6352C_UK
The minimum current trigger for high impedance protection compares the RMS value of
the current to the set value Imin. The pickup of the base point trigger is determined by a
half-cycle RMS calculation of the current in order to ensure a short response time.
After operation, the full-cycle RMS value of the current is monitored. This ensures the
required stability and accuracy of the measuring system.
1 2 3 4 5 6 7
DELTA: Enabled
[ 038 054 ] c
DELTA: Imin
SGx
[ * ]
DELTA: Imin
I Starting
[ 038 059 ]
DELTA: Vmin
V > 0.1 Vnom Triggered
310 051
48Z6353B_UK
The reactance release feature must first be made globally available, i.e. 'visible'. Then
release conditions may be configured selectively for each setting group.
Operation of the
reactance release feature
The P438 checks whether the current value exceeds the minimum current value set at
D E L T A : I m i n S G x and that no fault is apparent in the voltage-measuring circuit.
If such is the case, the P438 will calculate the reactance value. If the resulting reactance
value lies within the set limits then the D E L T A : X - R e l e a s e authorization signal is
issued.
Note: Triggering of high impedance protection will be fairly unlikely when the
minimum value is set in only one direction. In such a case high impedance
protection will operate only in the direction "opposite" to the set reactance limit.
1 2 3 4 5 6 7
DELTA: Enabled
[ 038 054 ] C
DELTA: X Super.
Available
[ 022 188 ]
0: No
1: Yes
DELTA: Imin &
Starting
[ 038 059 ]
C&VTS: VTS Volts
Failure C
[ 038 023 ]
MAIN: M.c.b. DELTA: X,
Trip V EXT Forward SGx
[ 004 061 ] [ * ]
DELTA: Vmin DELTA: X,
Triggered Reverse SGx
310 051
[ * ]
V
DELTA: X-Release
[ 038 065 ]
I
*
Setting DELTA: X, DELTA: X,
Forward SGx Reverse SGx
Group 1 062 032 062 033
Group 2 063 032 063 033
Group 3 064 032 064 033
Group 4 065 032 065 033
48Z6354B_UK
3.22.3 Checking for Changes of the Phase Angle (Sudden Angle Change
Detection)
The P438 will check for sudden angle changes to distinguish between load variations
and high impedance faults. A the phase angle change may be used as a criterion for a
fault.
The monitoring feature for sudden angle changes must first be made globally available,
i.e. 'visible'. Then operate thresholds for the monitoring feature may be configured
selectively for each setting group.
1 2 3 4 5 6 7
DELTA: Enabled
[ 038 054 ] C
0: No
1: Yes
&
DELTA: Imin
Starting
[ 038 059 ]
C&VTS: VTS Volts
Failure
[ 038 023 ]
MAIN: M.c.b.
Trip V EXT
[ 004 061 ] C
DELTA: Vmin
Starting DELTA: Delta
310 051 Phi SGx
[ * ]
V
DELTA: Delta Phi
Starting
[ 038 063 ]
I
The P438 will monitor the third and, selectively, the fifth harmonic current components to
distinguish between load variations and high impedance faults. Sudden current changes
caused by high impedance faults do not create any odd-numbered harmonic
components.
The harmonics stabilization feature must first be made globally available, i.e. 'visible'.
Then operate thresholds for the stabilization feature may be configured selectively for
each setting group.
The P438 will evaluate the ratio to the fundamental of the third and/or fifth harmonic
current components so as to detect load variations. Should these ratios exceed the
threshold values set at D E L T A : I ( 3 f n ) / I ( f n ) S G x or
D E L T A : I ( 5 f n ) / I ( f n ) S G x then the device has detected a load variation.
1 2 3 4 5 6 7
DELTA: Enabled C
[ 038 054 ] &
DELTA: I(3fn)/
DELTA: Imin I(fn) SGx
Starting [ * ]
[ 038 059 ]
MAIN: I(3fn)/ DELTA: I(3fn)
I(fn) Starting
1)
310 054 [ 038 076 ]
DELTA: Superv.
I(5fn)avail
[ 022 193 ]
&
0
1 C
0: No DELTA: I(5fn)/
1: Yes I(fn) SGx
[ * ]
DELTA: I(5fn)
MAIN: I(5fn)/ Starting
I(fn) 1) [ 038 077 ]
310 055
DELTA: Delta I
Blocked
& [ 038 068 ]
DELTA: kST,
I(xfn)/I(fn) SGx
[ * ]
Blocked DELTA: Delta I
Extended
[ 038 066 ]
*
Setting DELTA: I(3fn)/ DELTA: I(5fn)/ DELTA: kST,
I(fn) SGx I(fn) SGx I(xfn)/I(fn) SGx
Group 1 062 040 062 042 062 041
Group 2 063 040 063 042 063 041
Group 3 064 040 064 042 064 041
Group 4 065 040 065 042 065 041
The sudden current change criterion of by the high impedance protection function
monitors the fundamental component of the current during a set sampling interval. With
this feature the setting of the sudden current change criterion can be handled
dynamically according to the harmonics stabilization setting. The high impedance
protection function is either blocked or stabilized (dynamically extended by multiplication
with the set factor) in accordance with the setting of parameter
DELTA: kSt,I(xfn)/I(fn) SGx.
The minimum current threshold enabling the high impedance protection function has
been triggered.
Starting of the high impedance protection function is recorded. Recording is reset when
minimum current enabling and reactance limit monitoring have dropped out. Additionally
recording is reset when both the tDelta time-delay and a 100 ms pulse duration have
elapsed.
Note: When tDelta is set to Blocked then resetting of the recorded start is carried out
after the 100 ms pulse duration.
Inrush stabilization
Depending on the settings of the M A I N : F c t . I n r u s h . R s t r . S G x parameters
T T
starting decisions issued by the high impedance protection function can be cancelled
when the inrush stabilization function has detected an inrush current.
1 2 3 4 5 6 7
DELTA: Enabled
[ 038 054 ] &
DELTA: Not Ready
[ 038 055 ]
DELTA: Imin
Starting
[ 038 059 ]
DELTA: Delta I
Blocked
[ 038 068 ]
MAIN: Inrush
stabil. trigg
306 014
1 &
2
1: Delta I only
2: Blocked
C&VTS: VTS Volts
Failure
[ 038 023 ]
MAIN: M.c.b.
Trip V EXT
[ 004 061 ]
DELTA: Vmin
Triggered
310 051
DELTA: X-Release
[ 038 065 ]
DELTA: X Super.
Available
[ 022 188 ] C
No
DELTA: Delta I
SGx
[ * ]
DELTA: Delta Phi
Starting
[ 038 063 ] DELTA: kST,
I(xfn)/I(fn) SGx
DELTA: Delta Phi [ * ]
Available
[ 022 189 ]
No
fnom
DELTA: Delta I
I S 1 Starting
& [ 038 060 ]
R
DELTA: Delta I
Extended
[ 038 066 ]
t1) 0
DELTA: Block.
tDelta EXT C
[ 038 053 ]
DELTA: tDelta
SGx
[ * ]
DELTA: Trip
t 0 Signal
[ 038 056 ]
Setting DELTA: Mode w/o DELTA: Delta I DELTA: kST, DELTA: tDelta
Voltage SGx SGx I(xfn)/I(fn) SGx SGx
Group 1 062 036 062 037 062 041 062 039
Group 2 063 036 063 037 063 041 063 039
Group 3 064 036 064 037 064 041 064 039
Group 4 065 036 065 037 065 041 065 039
In normal (healthy system) operation, the P438 monitors the measured voltages
continuously. When the supervision detects an a.c. input problem, appropriate
measures are taken to prevent malfunction of the device and the faulty condition is
alarmed.
CHECK
CHECK
CHECK
SGx
Setting CHECK
SGx
Group
Group
Group
Group
The supervision function is blocked for the duration of a system disturbance (general
starting).
Undervoltage monitoring
Fuse failure monitoring
If triggered both sub-functions automatically block all functions using the measured
voltage.
Undervoltage monitoring
If undervoltage monitoring is enabled and it is not blocked by a binary signal input and
there is no general starting, the P438 monitors the voltage for it to fall below the
threshold set at C & V T S : V < , V - M o n i t . S G x . In this case the current must exceed
the threshold set at C & V T S : I > E n a b V < F u s e F S G x . Once the set time delay
has elapsed, the C & V T S : U n d e r v o l t a g e signal is issued.
1 2 3 4 5 6 7
MAIN: General
Start
[ 036 000 ]
C&VTS: Enabled
[ 040 094 ]
C&VTS: Blocking
V< EXT
[ 038 033 ]
C&VTS: VTS/Fuse
F. Enab SGx
[ * ] & C
0
C&VTS: V<, V- C&VTS: tV<, V-
1 monit. SGx monit. SGx
[ * ] [ * ]
0: No C&VTS: Undervoltage
& S1 1
1: Yes t [ 038 038 ]
0 R1
Setting C&VTS: VTS/Fuse C&VTS: V<, V- C&VTS: tV<, V- C&VTS: I> Enab
F. Enab SGx monit. SGx monit. SGx V< FuseF SGx
Group 1 014 225 014 229 014 233 014 188
Group 2 014 226 014 230 014 234 014 237
Group 3 014 227 014 231 014 235 014 238
Group 4 014 228 014 232 014 236 014 239
48Z5520B_UK
1 2 3 4 5 6 7
MAIN: General
Start
[ 036 000]
C&VTS:Enabled
[ 040 094]
C&VTS: Blocking
Fuse F. EXT
[038 037 ]
C&VTS: VTS/Fuse F.
Enab SGx
[ * ]
0
1
C&VTS: Delta V
0: No VTS/Fuse SGx
1: Yes [ * ]
C&VTS: Delta I
VTS/Fuse SGx
[ * ]
Setting C&VTS: VTS/Fuse C&VTS: Delta V C&VTS: Delta I C&VTS: V< VTS/ C&VTS: I> Enab V< C&VTS: V> VTS/
F. Enab SGx VTS/Fuse SGx VTS/Fuse SGx Fuse Fail SGx FuseF SGx Fuse Fail SGx
Group 1 014 204 014 216 014 221 014 208 014 188 014 212
Group 2 014 205 014 217 014 222 014 209 014 237 014 213
Group 3 014 206 014 218 014 223 014 210 014 238 014 214
Group 4 014 207 014 219 014 224 014 211 014 239 014 215
48Z5521B_UK
C&VTS
C&VTS
C&VTS: VTS/FF
V triggered
48Z5470A_UK
Disabling or enabling
BUOC protection
BUOC protection can be disabled or enabled using a setting parameter. Enabling can
be carried out separately for each setting group.
BUOC: General
Enable USER
[ 014 011 ]
0
1
0: No
1: Yes
BUOC: Enable
SGx
[ * ]
BUOC: Enabled
[ 040 093 ]
0
1
Setting BUOC: Enable
0: No SGx
1: Yes Group 1 072 118
Group 2 073 118
Group 3 074 118
Group 4 075 118
48Z5055A_UK
Readiness of backup
time-delayed overcurrent
protection
BUOC protection is ready when it is activated, enabled and at least one stage is
unblocked. If this is the case then BUOC protection will become effective
automatically as soon as the distance protection function is not ready. The latter can
occur, for example, if there is a malfunction in the voltage-measuring circuit or if the
distance protection function is not enabled in the active setting group.
Provided that the backup time-delayed overcurrent protection has started, it remains
active at least until the end of this starting, even when the condition for its activation
disappear (for example M.c.b. trip).
BUOC: Blocking
tI> EXT
BUOC: Blocking
tI>> EXT
BUOC: Active
48Z5056A_EN
Current measurement
When the BUOC protection function is active, it monitors the current I to detect when
the set thresholds are exceeded. When a stage operates and the set time-delays have
elapsed, signals are issued and can be used as criteria for fault recording or tripping.
The timer stages connected in series to the triggers can be blocked by way of
appropriately configured binary signal inputs.
Inrush Stabilization
(Harmonic Restraint)
Depending on the setting at M A I N : F c t . A s g . I n r . R s t r . S G x starting decisions
made by the distance zones can be cancelled when the inrush stabilization function
has detected an inrush current.
BUOC: Enabled
[ 037 021 ]
BUOC: Blocking
tI> EXT
[ 038 127 ]
BUOC: Starting
I>>
MAIN: Inrush [ 036 115 ]
stabil. trigg
306 014
Enable/disable switch on to
fault (short circuit)
protection
Switch on to fault protection can be disabled or enabled using a setting parameter.
Enabling can be carried out separately for each setting group.
SOTF: General
Enable USER
[ 011 068 ]
0
1
0: No
1: Yes
SOTF: Enable
SGx
[ * ]
SOTF: Enabled
[ 040 069 ]
0
1
Setting SOTF Enable
0: No SGx
1: Yes Group 1 011 120
Group 2 011 121
Group 3 011 122
Group 4 011 123
48Z5065A_UK
Blocking of switch on to
fault protection
As of version –606 switch on to fault protection may be blocked if the following
conditions are met:
an external blocking command signal, present at the binary signal input configured at
SOTF: B l o c k i n g E X T
an external auto-reclose signal, present at the binary signal input configured at
SOTF: Par. ARC Running EXT
a reclose command issued by the internal auto-reclose control function
the occurrence of a general start while a timer stage is running shall cause a trip
(S O T F : T r i p s i g n a l )
(See section 'Starting Signals and Tripping Logic' for a definition of general starting)
OR
While this timer is running, a zone 1 extension shall occur (S O T F : Z 1
Extended).
1 2 3 4 5 6 7
SOTF: Enabled
[ 040 069 ] &
SOTF: Par. ARC
running EXT SOTF: Z1extended
& [ 035 076 ]
[ 039 063 ]
SOTF: Blocking EXT
[ 036 098 ]
SOTF: Operating
Mode SGx
[ * ]
4
5
48Z5321A_UK
As of version –606 the auto-reclose control function (RECLS) will cause an automatic
reclosure on a line, previously cleared by a protection device, after certain faults have
occurred.
The auto-reclose control function of the P438 allows triggering of trip times by different
starting signals. Once the trip times have elapsed, a trip signal is generated. The auto-
reclose control function of the P438 permits multiple reclosing sequences. A reclosing
sequence begins with a high-speed reclosure (HSR). If the fault is not cleared after
reclosure by a HSR, then successive attempt(s) can be made to clear the fault with time-
delayed reclosure(s) (TDR).
RECLS:
RECLS:
RECLS:
RECLS:
RECLS:
RECLS:
RECLS:
RECLS:
Setting RECLS:
Group
Group
Group
Group
Auto-reclose blocking
The auto-recloser is blocked and the R E C L S : B l o c k e d signal will be issued if the
following conditions are met:
1 2 3 4 5 6 7
RECLS: Block.
ARC f. I> SGx
[ * ]
RECLS: Block.
I time ext. SGx
[ * ]
1 2 3 4 5 6 7
RECLS: Check CB
Closed? SGx
[ * ]
0 ≥1
1 &
0: No
RECLS: CB closed
1: Yes 303 004
MAIN: CB closed
sig. EXT RECLS: Ready
[ 036 051 ] &
[ 004 068 ]
MAIN: Protection
active
306 001
RECLS: CB drive
ready EXT
[ 004 066 ]
RECLS: Blocked
[ 004 069 ]
RECLS: Cycle
running
[ 037 000 ]
RECLS: Not Ready
RECLS: Recl. Time 2
Running [ 037 008 ]
[ 036 221 ]
48Z5351B_UK
When protection functions operating with auto-reclose control are started, the trip times
(HSR or TDR) are triggered together with operative time 1 and operative time 2. Trip
times may replace timer stages associated with the respective protection functions if the
following conditions are met:
The protection function’s trip signal is set as a criterion for the main-trip command or
re-trip command (only relevant when R E C L S : W i t h R e - T r i p is set to 'Yes'),
The trip time is not set to 'Blocked'.
The auto-recloser is ready to operate at starting time.
Operative time 1 or operative time 2 is running.
If the trip time has elapsed during an active auto-reclose cycle while the operative times
are still running, a trip signal from the associated function is issued. The HSR or TDR
trip time having caused the trip signal also determines when the dead time (HSR or
TDR) is to be started. Once the dead time commences, all trip times already triggered
and the operative times will be reset.
The beginning of the following starts or input signals trigger the trip times, provided that
the starting conditions are met and the respective trip times are not "blocked":
DIST: Starting Z1
DIST: Starting Z2 together with train start-up detection dx/dt Z2
DIST: Starting Z3 together with train start-up detection dx/dt Z3
DELTA: Delta I Starting
DTOC: Starting I>H
DTOC: Starting I>
DTOC: Starting I>>
IDMT: Starting Iref>
BUOC: Starting I>
BUOC: Starting I>>
Start by programmable logic
1 2 3 4 5 6 7
MAIN: Main-Trip
'OR' gate
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signals
MAIN: Re-Trip
'OR' gate
[ 021 025 ]
Signal 1
Signal 2 m out of n
1
Signal n
Selected signals
&
Setting RECLS: HSR trip RECLS: HSR- RECLS: HSR- RECLS: HSR- RECLS: HSR-
time t1 SGx tr.DIST t2S SGx tr.DIST t2L SGx tr.DIST t3S SGx tr.DIST t3L SGx
Group 1 015 072 015 144 015 152 015 160 015 168
Group 2 024 040 015 145 015 153 015 161 015 169
Group 3 025 000 015 146 015 154 015 162 015 170
Group 4 025 060 015 147 015 155 015 163 015 171
48Z5353A_UK
1 2 3 4 5 6 7
MAIN: Main-Trip
’OR’ Gate
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signals
MAIN: Re-Trip
’OR’ Gate
[ 021 025 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signals
&
RECLS: Ready
[ 004 068 ] &
RECLS: TDR
RECLS: Cycle trip time elapsed
Running 303 153
[ 037 000 ]
RECLS: Oper. Time 1
Running
[ 037 005 ]
RECLS: Oper. Time 2 RECLS: TDR-
Running C Tr.DIST t1 SGx
[ 037 065 ] [ * ]
Setting RECLS: TDR- RECLS: TDR- RECLS: TDR- RECLS: TDR- RECLS: TDR-
Tr.DIST t1 SGx Tr.DIST t2S SGx Tr.DIST t2L SGx Tr.DIST t3S SGx Tr.DIST t3L SGx
Group 1 015 073 015 148 015 156 015 164 015 172
Group 2 024 041 015 149 015 157 015 165 015 173
Group 3 025 001 015 150 015 158 015 166 015 174
Group 4 025 061 015 151 015 159 015 167 015 175
48Z5354B_UK
1 2 3 4 5 6 7
MAIN: Main-Trip
'OR' Gate
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected Signals
MAIN: Re-Trip
'OR' Gate
[ 021 025 ]
Signal 1
Signal 2 m out of n
Signal n
RECLS: Ready
[ 004 068 ] &
RECLS: Cycle
Running
[ 037 000 ]
RECLS: Oper. Time 1
Running
[ 037 005 ]
RECLS: Oper. Time 2 RECLS: HSR-
Running C Tr.DELTA tD. SGx
[ 037 065 ] [ * ]
DELTA: Delta I t 0
Starting RECLS: Trip time
[ 038 060 ] HSR elaps
303 152
DELTA: Trip
Signal
[ 038 056 ]
RECLS: TDR-
C Tr.DELTA tD. SGx
[ * ]
3-138 HSR and TDR auto-reclose trip times for high impedance protection
1 2 3 4 5 6 7
MAIN: Main-Trip
'OR' gate
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signals
Signal 1
Signal 2 m out of n
1
Signal n
Selected signals
&
RECLS: HSR-
Ctr.DTOC tI> SGx
[ * ]
RECLS: HSR-
Ctr.IDMT kIrefSGx
[ * ]
48Z5355A_UK
3-139 Auto-reclose trip times for DTOC and IDMT protection HSR
1 2 3 4 5 6 7
MAIN: Main-Trip
'OR' Gate
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signals
MAIN: Re-Trip
'OR' Gate
[ 021 025 ]
Signal 1
Signal 2 m out of n
Signal n
RECLS: With
Re-Trip
[ 015 018 ]
RECLS: Ready
[ 004 068 ] &
RECLS: Cycle
Running
[ 037 000 ] RECLS: TDR Trip
RECLS: Oper. t. Elapsed
303 153
Time 1 Running
[ 037 005 ]
RECLS: TDR-Tr.
RECLS: Oper. C DTOC tI>H SGx
Time 2 Running [ * ]
[ 037 065 ]
DTOC: Starting t 0 DTOC: Trip
I>H signal tI>H
[ 035 022 ] [ 040 076 ]
RECLS: TDR-Tr.
C DTOC tI> SGx
[ * ]
48Z5356A_UK
3-140 Auto-reclose trip times for DTOC and IDMT protection TDR
1 2 3 4 5 6 7
MAIN: Main-Trip
'OR' gate
[ 021 007 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signals
MAIN: Re-Trip
'OR' gate
[ 021 025 ]
Signal 1
Signal 2 m out of n
≥1
Signal n
RECLS: HSR-tr.
C BUOC tI>> SGx
[ * ]
RECLS: TDR-tr.
C BUOC tI> SGx
[ * ]
RECLS: TDR-tr.
C BUOC tI>> SGx
[ * ]
BUOC: Trip signal
≥1 I>>
[ 036 116 ]
t 0
48Z5357B_UK
3-141 Auto-reclose trip times for BUOC protection HSR and TDR
Auto-reclose starting by
programmable logic
(example)
This example (see Figure 3-142) illustrates the possible interconnection and the binary
signal output for starting the trip time using a binary signal input.
By using the programmable logic, a binary signal input with an operate delay and an
AND element is implemented. The R E C L S : T r i p b l o c k e d signal has been
assigned to the second input on this AND element. The output from the AND element
must be included in the configuration of the ‘m out of n’ selection for the main trip
command. The trip time can be triggered by the output signal
RECLS: Start by logic.
In this example, the following list settings need to be set (see section ‘Setting a List
Setting’ in chapter ‘User Interface (HMI)’).
List Parameter
LOGIC: Fct.Assignm. OR e.g. L O G I C : I n p u t 4
Outp. 1 EXT
(address 030 000) (address 034 003)
LOGIC: Fct.Assignm. OR LOGIC: Output 1 (t)
Outp. 2 (address 042 033)
AND NOT RECLS: Not Ready
(address 037 008)
In general, any equation within the programmable logic function can be used to start the
auto-reclose trip time.
1 2 3 4 5 6 7
LOGIC: Fct.
Assignm. Outp. 1
[ 030 000 ]
Signal n
t 0
RECLS: Start by
LOGIC
LOGIC: [ 037 078 ]
Output 1 (t)
LOGIC: Fct.
Assignm. Outp. 2
[ 030 004 ]
m out of n
³1 &
RECLS: Not Ready
[ 037 008 ]
LOGIC: Output 2
48Z5366A_UK
1 2 3 4 5 6 7
MAIN: Re-Trip
'OR' gate
[ 021 025 ]
Signal 1
Signal 2 m out of n
1
Signal n
Selected signals &
RECLS: TDR-tr.
C LOGIC SGx
[ * ]
48Z5358A_UK
3-143 HSR and TDR auto-reclose trip times for programmable logic
Auto-reclose cycle
When the auto-recloser is ready, an auto-reclose cycle is started by one of the following
functions:
Starting of protection functions that have a trip time configured and thus allow
reclosing
Starting or tripping of an external protection device, if it has been configured
accordingly (R E C L S : P a r a l l e l T r i p S G x )
A test HSR
As the auto-reclose cycle runs, the R E C L S : R e a d y signal is no longer taken into
account.
If there is a new protection start during the last reclaim time 1, the auto-recloser is also
blocked for the duration of the starting pulse. The R E C L S : L o c k f . G e n . S t a r t i n g
signal is issued.
If the starting conditions are met then any auto-recloser-relevant protection start will
trigger an auto-reclose cycle. Any start will trigger the associated trip times, operative
time 1 and operative time 2. Operative time 1 and operative time 2 have equal status
when they are running. Starting conditions for an auto-reclose cycle must be released
while operative timer stages are running. This means that the circuit breaker has opened
(start and trip signals of the function have dropped out) so that a dead time may be
triggered. Which dead time is triggered depends on which operative time has elapsed.
Voltage-independent
reclosure
When the start signal is reset, operative time 1 is terminated and the HSR dead time
begins. If there is no starting during the HSR dead time, a reclose command is issued
once the HSR dead time has elapsed. Simultaneously reclaim time 1 is triggered. If
there is no starting during reclaim time 1, the R E C L S : R e c l o s u r e s u c c e s s f u l
signal will be issued when reclaim time 1 has elapsed. The auto-reclose cycle is
complete.
Voltage-dependent
reclosure
Should starting conditions for an auto-reclose cycle drop out after operative time 1 has
elapsed but not before operative time 2 has elapsed, the maximum dead time
(R E C L S : D e a d T i m e M a x S G x ) will be triggered. With the triggering of the
maximum dead time a reclosure of the line from the far end will be expected. A reclose
command is issued and the maximum dead time is reset when the voltage criterion
(R E C L S : V > S G x ) is met and the associated time delay (R E C L S : t V > S G x ) has
elapsed. Simultaneously reclaim time 1 is triggered. If no start occurs during reclaim
time 1, the R E C L S : R e c l o s u r e S u c c e s s f u l signal will be issued when reclaim
time 1 has elapsed. The auto-reclose cycle is complete.
HSR rejection
Reclaim time 1 is triggered should the circuit breaker fail to clear the fault during the
operative times. All protection timer stages are enabled again simultaneously, provided
that their trip time was not set to 'Blocked'.
If operative times elapse without the protection having reached a decision to trip, the
RECLS function is ready again immediately after the relevant starting condition has
dropped out.
Unsuccessful high-speed
reclosure
If the HSR does not succeed and another protection start occurs then a time-delayed
reclosure (TDR) is started if at least one TDR is permitted. If no TDR is permitted after a
HSR then the reclaim time 1 presently running is the last reclaim time 1 of the auto-
reclose cycle. All trip times are reset when reclaim time 1 has elapsed. Simultaneously
all protection timer stages are enabled again. If a trip signal is issued during the last
reclaim time 1 then it will be regarded as a final trip. The auto-reclose cycle is complete
after the last reclaim time 1 has elapsed.
The final trip will trigger reclaim time 2. The auto-reclose control function remains
blocked while reclaim time 2 is running after an unsuccessful reclose attempt.
Auto-reclose blocking may be removed if one of the following conditions is met:
Suppressing CB trip
signals
When the R E C L S : C y c l e R u n n i n g signal appears, the R E C L S : S i g .
I n t e r r . C B T r i p signal (interruption of breaker trip signal) is issued and it is reset
after the final HSR or TDR of the current auto-reclose cycle, once the close command
pulse time has elapsed. When the R E C L S : B l o c k e d signal is issued during an
auto-reclose cycle, the signal is likewise reset immediately.
1 2 3 4 5 6 7
RECLS: Ready
[ 004 068 ]
RECLS: HSR-tr.DIST t1
runn.
310 021 1 1
DIST: t1 running
310 023
6
RECLS: Reclosure
successful
[ 036 062 ]
RECLS: Sig.interr. CB
trip
[ 036 040 ]
1 2 3 4 5 6
Setting RECLS: HSR-tr. RECLS: Operative RECLS: HSR Dead RECLS: Reclaim RECLS: Reclaim DIST: tZ1
DIST t1 SGx Time 1 SGx Time SGx Time 1 SGx Time 2 SGx SGx
Group 1 015 072 015 066 015 056 015 054 015 124 012 028
Group 2 024 040 024 035 024 030 024 028 015 125 012 078
Group 3 025 000 024 095 024 090 024 088 015 126 013 028
Group 4 025 060 025 055 025 050 025 048 015 127 013 078
3-144 Signal sequence for a HSR with a trip during operative time 1, triggered by a trip in distance protection zone 1
1 2 3 4 5 6 7
RECLS: Ready
[ 004 068 ]
RECLS: HSR-tr.DIST t1
runn. 1 1
310 021
DIST: t1 running
310 023
RECLS: Reclosure
successful
[ 036 062 ]
RECLS: Sig.interr. CB
trip
[ 036 040 ]
1 2 3 4 5 6
Setting RECLS: HSR-tr. RECLS: Operative RECLS: Dead Time RECLS: V> SGx RECLS: tV> SGx RECLS: Reclaim
DIST t1 SGx Time 2 SGx Max SGx Time 1 SGx
Group 1 015 072 015 083 015 084 015 128 015 140 015 054
Group 2 024 040 024 042 024 043 015 129 015 141 024 028
Group 3 025 000 025 002 025 003 015 138 015 142 024 088
Group 4 025 060 025 062 025 063 015 139 015 143 025 048
3-145 Signal sequence for a HSR with a trip during operative time 2, triggered by a trip in distance protection zone 1
Test HSR
Triggering a test HSR is possible only if the auto-recloser is ready. Once a test HSR has
been triggered, a trip signal of defined duration is issued. The subsequent sequence
corresponds to a successful HSR (open and reclose command when the HSR dead time
has elapsed). Once the close command pulse time has elapsed, further triggering during
the reclaim time does not result in a further HSR.
A test HSR can be triggered either from the front panel user interface (HMI) or using a
binary signal input and it will add an increment to the R E C L S : N o . o f H S R
R e c l o s e s counter.
For each ‘Test HSR’ request that does not result in a HSR test, the R E C L S : R e j e c t
T e s t H S R signal i s generated.
1 2 3 4 5 6 7
0
1 1 1 80 ms & RECLS: Test HSR
[ 034 023 ]
0: don't execute
1: execute
48Z5361A_UK
Multiple reclosures using TDRs are possible if the operating mode is set accordingly.
A TDR may be performed after a HSR if reclosure has occurred as the result of the HSR.
This is possible only if the setting f o r R E C L S : N o . P e r m i t . T D R S G x (number
of permitted TDRs) is not zero.
If the starting conditions are met then any start by a protection function associated with
the auto-recloser will trigger the associated trip times. Simultaneously operative time 1
and operative time 2 are also triggered.
Voltage independent
reclosure
When the start signal is reset, operative time 1 is terminated and the TDR dead time
begins. If there is no starting during the TDR dead time, a reclose command is issued
once the TDR dead time period has elapsed. Simultaneously reclaim time 1 is triggered.
If there is no starting during reclaim time 1, the R E C L S : R e c l o s u r e s u c c e s s f u l
signal will be issued when reclaim time 1 has elapsed. The auto-reclose cycle is
complete.
Voltage-dependent
reclosure
Should starting conditions for an auto-reclose cycle drop out after operative time 1 has
elapsed but not before operative time 2 has elapsed, the maximum dead time
(R E C L S : D e a d T i m e M a x S G x ) will be triggered. With the triggering of the
maximum dead time a reclosure of the line from the far end will be expected. A reclose
command is issued and the maximum dead time is reset when the voltage criterion
(R E C L S : V > S G x ) is met and the associated time delay (R E C L S : t V > S G x ) has
elapsed. Simultaneously reclaim time 1 is triggered. If no start occurs during reclaim
time 1, the R E C L S : R e c l o s u r e S u c c e s s f u l signal will be issued when reclaim
time 1 has elapsed. The auto-reclose cycle is complete.
TDR rejection
Reclaim time 1 is triggered should the circuit breaker fail to clear the fault during the
operative times. All protection timer stages are enabled again simultaneously, provided
that their trip time was not set to 'Blocked'. The auto-reclose cycle is complete when
reclaim time 1 has elapsed.
If operative times elapse while the protection function has not reached a trip decision,
reclaim time 1 is triggered. The auto-reclose cycle is complete when reclaim time 1 has
elapsed.
Unsuccessful time-delayed
reclosure
If there is a new protection start during reclaim time 1 and at least one TDR is still
permitted, then reclaim time 1 is terminated and, when the trip time has elapsed, another
trip command is issued to begin a new reclosure attempt. If no further TDR is permitted
then the reclaim time 1 presently running is the last reclaim time 1 of the auto-reclose
cycle. All trip times are reset when reclaim time 1 has elapsed. Simultaneously all
protection timer stages are enabled again. If a trip signal is issued during the last
reclaim time 1 then it will be regarded as a final trip. The auto-reclose cycle is complete
after the last reclaim time 1 has elapsed.
The final trip will trigger reclaim time 2. The auto-reclose control function remains
blocked while reclaim time 2 is running after an unsuccessful reclose attempt.
Auto-reclose blocking may be removed if one of the following conditions is met:
Reclaim time 1 is triggered should the circuit breaker fail to clear the fault during the
operative times. Simultaneously all protection timer stages are enabled again.
If operative times are elapsing without the protection having reached a decision for a trip
command, the RECLS function is immediately ready again after the relevant starting has
dropped out.
Suppressing CB trip
signals
When the R E C L S : C y c l e r u n n i n g signal appears, the
R E C L S : S i g . i n t e r r . C B t r i p signal (interruption of breaker trip signal) is issued
and it is reset after the final HSR or TDR of the current auto-reclose cycle, once the
close command pulse time has elapsed. When the R E C L S : B l o c k e d signal is
issued during an auto-reclose cycle, the signal is likewise reset immediately.
1 2 3 4 5 6 7
RECLS: Ready
[ 004 068 ]
RECLS: HSR-tr.DIST t1
runn.
310 021 1
RECLS: TDR-tr.DIST t1
runn.
310 022 2 2
RECLS: Reclosure
successful
[ 036 062 ]
RECLS: Sig.interr. CB
trip
[ 036 040 ]
1 2 3 4 5 6
Setting RECLS: HSR-tr. RECLS: TDR-tr. RECLS: Operative RECLS: HSR Dead RECLS: TDR Dead RECLS: Reclaim
DIST t1 SGx DIST t1 SGx Time 1 SGx Time SGx Time SGx Time 1 SGx
Group 1 015 072 015 073 015 066 015 056 015 057 015 054
Group 2 024 040 024 041 024 035 024 030 024 031 024 028
Group 3 025 000 025 001 024 095 024 090 024 091 024 088
Group 4 025 060 025 061 025 055 025 050 025 051 025 048
3-147 Signal sequence of a failed HSR followed by a failed TDR and then by a final successful TDR with a trip during operative time 1,
triggered by a trip in distance protection zone 1
A zone extension of impedance zone 1 generally occurs when the respective parameters
have been enabled. The extension is made for impedance and resistance values of the
forward and reverse directional zone settings.
High-speed reclosures and time-delayed reclosures will enable different zone extension
factors.
The thermal overload protection trip signal may be included in the auto-reclose functional
sequence.
The thermal overload protection’s trip signal is set as a criterion for the main-trip
command or re-trip command (only relevant when R E C L S : W i t h R e - T r i p is set
to 'Yes').
The auto-recloser is ready to operate at starting time.
The trip signal from a second protection device operating in parallel to the P438 may be
included in the auto-reclose functional sequence.
In order to have a protection device, operating in parallel, trigger the RECLS function,
binary signal inputs have to be configured appropriately and the parameter
R E C L S : P a r a l l e l t r i p S G x must be set. When this parameter is set to 'With Start
ARC' the starting or the trip command issued by the protection device, operating in
parallel, is included in the auto-reclose functional sequence. In addition the following
conditions apply to have the RECLS function triggered by the protection device,
operating in parallel:
The trip signal of the parallel protection device is set as a criterion for the main-trip
command or re-trip command (only relevant when R E C L S : W i t h R e - T r i p is set
to 'Yes').
The auto-recloser is ready to operate at starting time.
Operative time 1 or operative time 2 is running.
Depending on the configured binary signal inputs, operative times are triggered by the
starting or the trip command issued by the protection device, operating in parallel.
1 2 3 4 5 6 7
Trigger with RECLS: General Starting EXT Trigger with MAIN: Parallel trip EXT
RECLS: Ready
[ 004 068 ]
RECLS: Cycle
Running
[ 037 000 ]
RECLS: General
Starting EXT
[ 037 096 ]
MAIN: Parallel
Trip EXT
[ 037 019 ]
MAIN: Main-Trip
Command
[ 039 011 ]
Terminated Terminated
RECLS: Oper.
Time 1 Running
[ 037 005 ]
2 2
MAIN: Close
Command
[ 037 009 ]
7 7
RECLS: Recl.
Time 1 Running
[ 036 042 ]
4 4
RECLS: Reclosure
Successful
[ 036 062 ]
RECLS: Sig.
Interr. CB Trip
[ 036 040 ]
1 2 3 4 5 6
Setting RECLS: HSR-Tr. RECLS: Operative RECLS: HSR Dead RECLS: Reclaim RECLS: Reclaim RECLS: tZ1
DIST t1 SGx Time 1 SGx Time SGx Time 1 SGx Time 2 SGx SGx
Group 1 015 072 015 066 015 056 015 054 015 124 012 028
Group 2 024 040 024 035 024 030 024 028 015 125 012 078
Group 3 025 000 024 095 024 090 024 088 015 126 013 028
Group 4 025 060 025 055 025 050 025 048 015 127 013 078
48Z5363A_UK
3-148 Signal sequence for a HSR with a trip during operative time 1, triggered by a trip from a protection device, operating in parallel
1 2 3 4 5 6 7
RECLS: Operative
Time 1 SGx
[ * ]
RECLS: Operative
Time 2 SGx
[ * ]
Setting RECLS: Operative RECLS: Operative RECLS: HSR Dead RECLS: Dead Time RECLS: No.
Time 1 SGx Time 2 SGx Time SGx max SGx Permit. TDR SGx
Group 1 015 066 015 083 015 056 015 084 015 068
Group 2 024 035 024 042 024 030 024 043 024 037
Group 3 024 095 025 002 024 090 025 003 024 097
Group 4 025 055 025 062 025 050 025 063 025 057
Setting RECLS: TDR Dead RECLS: Reclaim RECLS: Reclaim RECLS: Parallel RECLS: RC f.
Time SGx Time 1 SGx Time 2 SGx Trip SGx THERM Trip SGx
Group 1 015 057 015 054 015 124 015 053 015 176
Group 2 024 031 024 028 015 125 024 027 015 177
Group 3 024 091 024 088 015 126 024 087 015 178
Group 4 025 051 025 048 015 127 025 047 015 179
48Z6367A_UK
RECLS: Reset
Counters USER
[ 003 005 ]
1
0: Don't Execute
1: Execute
48Z6365A_UK
Enabling or disabling
DTOC protection
DTOC protection can be disabled or enabled using a setting parameter.
Enabling can be carried out separately for each setting group.
DTOC: General
Enable USER
[ 031 068 ]
0
1 DTOC: Enabled
[ 040 120 ]
0: No
1: Yes
DTOC: Enable
SGx
[ * ]
0
1
0: No **
1: Yes y GROUP: Group y Setting DTOC: Enable
Active SGx
1 036 090 Group 1 072 098
GROUP: Group y
Active 2 036 091 Group 2 073 098
[ ** ]
3 036 092 Group 3 074 098
4 036 093 Group 4 075 098
48Z63AKA_UK
Current measurement
Definite-time overcurrent protection measures the current I to determine whether it
exceeds the set thresholds.
Stage I>H can be used as an instantaneous high-current stage. In this case, it operates
if two consecutive sampled values (instantaneous values) exceed the operate threshold.
If the Triac-assisted output relays are employed, a tripping time ≤ 3 ms can be achieved
(otherwise, the contact closure time must be added).
When a timer stage operates and the set operate delays have elapsed, signals are
issued and can be used as criteria for fault recording or tripping. The timer stages
connected in series to the triggers can be blocked by way of appropriately configured
binary signal inputs.
Inrush Stabilization
(harmonic restraint)
Depending on the setting for the M A I N : F c t . A s g . I n r . R s t r . S G x parameters,
starting decisions made by the distance zones can be cancelled when the inrush
stabilization function has detected an inrush current.
DTOC: Enabled
[ 040 120 ]
DTOC: Blocking
tI> EXT
[ 041 060 ]
MAIN: Protection
active
306 001
DTOC: I> DTOC: tI>
SGx SGx DTOC: Trip
[ * ] [ * ] Signal tI>
[ 041 020 ]
DTOC: Starting
I>
[ 035 020 ]
DTOC: Blocking
tI>> EXT
[ 041 061 ]
DTOC: I>> DTOC: tI>>
SGx SGx
[ * ] [ * ] DTOC: Trip Signal
tI>>
[ 040 011 ]
DTOC: Starting
I>>
[ 035 021 ]
DTOC: Blocking
tI>H EXT
[ 041 062 ]
DTOC: I>H DTOC: tI>H
SGx SGx
[ * ] [ * ]
DTOC: Starting
I>H
MAIN: Inrush [ 035 022 ]
stabil. trigg
306 014
Setting DTOC: I> DTOC: I>> DTOC: I>H DTOC: tI> DTOC: tI>> DTOC: tI>H
SGx SGx SGx SGx SGx SGx
Group 1 072 007 072 008 072 009 072 019 072 020 072 021
Group 2 073 007 073 008 073 009 073 019 073 020 073 021
Group 3 074 007 074 008 074 009 074 019 074 020 074 021
Group 4 075 007 075 008 075 009 075 019 075 020 075 021
48Z5464A_UK
Direction measurement
The short-circuit direction determination function is available in the P438 as ofsoftware
version –604.
It is enabled at D T O C : D i r e c t i o n m e a s u r e m . All settings relevant to short-circuit
direction determination can be set separately for stages I> and I>>. When a starting
signal is issued by I> or I>> and the measured voltage level has dropped below the
value for V< the fault angle ϕ is calculated and the short-circuit direction is determined.
The short-circuit characteristic is defined by the angles β and γ. The algorithm decides
that the fault direction is forward when the calculated angle ϕ lies within the range given
by γ ≤ ϕ ≤ β.
In order for direction measurement to function correctly, even at very small fault voltage
values, the information stored in the voltage memory is also put to use in these cases.
The direction determination and the starting of the respective stage are only enabled if
the measured voltage value is below a settable undervoltage threshold V<. Setting the
undervoltage threshold V< to Blocked will disable this voltage scan and tripping will be
permanently enabled.
For very low fault voltages, the voltage from the voltage memory is used in place of the
measured voltage in order to avoid erroneous direction decisions. The direction decision
is dependent on the following conditions:
VF > 0.1 Vn
The direction decision is issued on the basis of the fault current and the measured
fault voltage Vf.
VF < 0.1 Vn
Voltage memory enabled:
The direction decision is issued on the basis of the fault current and the voltage
values stored in the voltage memory.
Voltage memory not enabled:
The direction decision is issued on the basis of the fault current and the measured
fault voltage down to a minimum value of 1 V. If the fault voltage drops to a value of
less than approximately 1 V, an accurate direction determination is no longer
possible. In this case, a Fault forward decision is issued - independently of the actual
fault direction.
Another setting is used to determine whether a failure of the voltage-measuring circuit
will either lead to the DTOC protection operating non-directionally or to it becoming
blocked.
The starting direction may be freely set.
When a permanent current enable value is exceeded the load angle ϕ is calculated and
the load flow direction is determined according to the short-circuit characteristic selected.
The load flow direction is displayed for as long as there is no fault (short-circuit) condition
apparent, which would be characterized by the starting of the current stages and the
enabling of the undervoltage stage.
Forward direction
Reverse direction
68Z50ABB_UK
1 2 3 4 5 6 7
DTOC: Timer
Start tI> SGx
[ * ]
1
2
1: With starting
2: With direction
DTOC: Blocking DTOC: tI>
tI> EXT C SGx
[ 041 060 ] [ * ]
DTOC: Enabled
[ 040 120 ] & DTOC: I>
C SGx DTOC: tI>
[ * ] & Elapsed
MAIN: Protection [ 040 010 ]
active
306 001
DTOC: Starting
I I>
[ 035 020 ]
&
DTOC: Direction
I> forw.
402 412
DTOC: Direction
I> rev. DTOC: I>
402 413
Triggered
DTOC: Trip I> 310 049
Non-direct. DTOC: Trip
402 414
& Signal tI>
DTOC: Direction [ 041 020 ]
Measurem.
[ 031 131 ]
Without
&
DTOC: Timer
Start tI>> SGx
[ * ]
1
2
1: With starting
2: With direction
DTOC: Blocking DTOC: tI>>
tI>> EXT C SGx
[ 041 061 ] [ * ]
DTOC: I>>
C SGx DTOC: tI>>
[ * ] Elapsed
& [ 040 106 ]
DTOC: Starting
I>>
[ 035 021 ]
&
Setting
Parameter- DTOC: Timer DTOC: I> DTOC: tI> DTOC: Timer DTOC: I>> DTOC: tI>>
Start tI> SGx SGx SGx Start tI>> SGx SGx SGx
Group 1 071 146 072
07 007 072 019 072 245 072 008 072 020
Group 2 071 147 073 007 073 019 073 044 073 008 073 020
Group 3 071 148 074 007 074 019 074 044 074 008 074 020
Group 4 071 149 075 007 075 019 075 044 075 008 075 020
48Z6370A_UK
1 2 3 4 5 6 7
V
&
DTOC: Direct.
& Using Memory
[ 036 136 ]
I
C2
DTOC: Fault
K Φ1 & I> Forward
[ 035 137 ]
DTOC: Fault
S Φ 2 & I> Reverse
V(stored) [ 035 140 ]
DTOC: I>
triggered
310 049 DTOC: I> Fwd.
DTOC: V < V< (I>) & w/o Meas.
403 410 [ 041 198 ]
DTOC: beta
(I>>) SGx
[ * ]
DTOC: gamma
(I>>) SGx
[ * ]
C1
C2
DTOC: I>>
triggered
310 050 DTOC: I>> Fwd.
& w/o Meas.
DTOC: V < V< (I>>) [ 041 199 ]
403 411
Setting
Setting- DTOC: beta (I>) DTOC: gamma DTOC: beta DTOC: gamma
SGx (I>) SGx (I>>) SGx (I>>) SGx
Group 1 076 068 076 073 076 069 076 074
Group 2 077 068 077 073 077 069 077 074
Group 3 078 068 078 073 078 069 078 074
Group 4 079 068 079 073 079 069 079 074
48Z6371A_UK
1 2 3 4 5 6 7
1
V
2
3
Setting Blocked
1: Forward
Directional
2: Reverse
Directional
3: Non-
Directional DTOC: Direction
& I> forw.
DTOC: Fault 402 412
I> Forward
[ 035 137 ]
DTOC: Direction
& I> rev.
DTOC: Fault 402 413
I> Reverse
[ 035 140 ]
Setting
Setting- DTOC: Mode w/o DTOC: V< (I>) DTOC: Direction
V (I>) SGx SGx (I>) SGx
Group 1 076 128 076 131 076 080
Group 2 077 128 077 131 077 080
Group 3 078 128 078 131 078 080
Group 4 079 128 079 131 079 080
48Z63ACA_UK
1 2 3 4 5 6 7
1
V
2
3
Setting Blocked
1: Forward
Directional
2: Reverse
Directional
3: Non- DTOC: Direction
Directional & I>> forw..
DTOC: Fault I>> 402 415
Forward
[ 035 147 ]
DTOC: Direction
& I>> rev.
DTOC: Fault I>> 402 416
Reverse
[ 035 148 ]
Setting
Setting- DTOC: Mode w/o DTOC: V< (I>>) DTOC: Direction
V (I>>) SGx SGx (I>>) SGx
Group 1 076 129 076 150 076 088
Group 2 077 129 077 150 077 088
Group 3 078 129 078 150 078 088
Group 4 079 129 079 150 079 088
48Z63ADA_UK
Disabling or enabling
IDMT protection
IDMT protection can be disabled or enabled using a setting parameter. Enabling can be
carried out separately for each setting group.
1 2 3 4 5 6 7
IDMT: General
enable USER
[ 017 096 ]
0
1 IDMT: Enabled
& [ 040 100 ]
0: No
1: Yes
IDMT: Enable
PSx
[ * ]
0
1
0: No ** *
1: Yes PSS: PS y Parameter IDMT: Enable
Y active PSx
PSS: PS y
active
[ ** ] 1 036 090 set 1 072 000
2 036 091 set 2 073 000
3 036 092 set 3 074 000
4 036 093 set 4 075 000
48Z6377A_EN
Inrush stabilization
(Harmonic restraint)
Depending on the settings for M A I N : F c t . A s g . I n r . R s t r . S G x starting decisions
made by the distance zones can be cancelled when the inrush stabilization function has
detected an inrush current.
Time-dependent characteristics
The user can select from a large number of characteristics (see table below).
The measured value is current I.
The tripping characteristics available for selection are shown in figures Fehler!
Verweisquelle konnte nicht gefunden werden. to Fehler! Verweisquelle konnte
nicht gefunden werden..
1000 1000
100 100
k=10
10 10 k=10
t/s k=1
t/s
1 1 k=1
k=0.1
0.1 0.1
k=0.1
k=0.01
0.01 0.01 k=0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
D5Z50K1A D5Z50K2A
1000 1000
100 100
k=10
10 10
k=1
t/s t/s
k=10
1 1
k=0.1
k=1
0.1 0.1
k=0.01
k=0.1
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
k=0.01
I/Iref I/Iref
D5Z50K3A D5Z50K4A
100 100
10 k=10 10
k=10
t/s t/s
1 k=1 1
k=1
I/Iref I/Iref
D5Z50K5B D5Z50K6B
1000
100
10
t/s
k=10
1
k=1
0.1
k=0.1
0.01 k=0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
D5Z50K7B
Characteristic No. 7
1000 1000
100 100
10 10
t/s t/s
k=10
1 1
k=10
k=1
0.1 0.1
k=1
k=0.1
0.01 k=0.01 0.01 k=0.1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
D5Z50K8B D5Z50K9B
1000
100
k=10
10
t/s k=1
1
k=0.1
0.1
k=0.01
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
D5Z50KAB
Characteristic No. 10
1000 1000
100 100
k=10
k=10
10 10
t/s k=1 t/s
k=1
1 1
k=0.1
k=0.1
0.1 0.1
k=0.01
k=0.01
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
D5Z50KBA D5Z50KCA
The inverse time-delayed stage may be blocked using an appropriately configured binary
signal input.
MAIN: Protection
active
306 001
IDMT: Enabled
[ 040 100 ]
IDMT: Iref
Rating SGx
[ * ]
1.05 * Iref
IDMT: Starting
IB>
[ 040 080 ]
IDMT: Block. IDMT: Charac-
tIref> EXT teristic SGx
[ * ] [ * ]
IDMT: Memory
clear
[ 040 110 ]
IDMT: Hold time
running
[ 040 053 ]
I/Iref IDMT: tIref>
elapsed
[ 040 082 ]
IDMT: Trip
Signal tIref>
[ 040 084 ]
Setting
IDMT: Characteristic SGx
0: Definite Time
1: IEC Standart Inverse
2: IEC Very Inverse
3: IEC Extr. Inverse
4: IEC Long Time Inv.
5: IEEE Moderately Inv.
6: IEEE Very Inverse
7: IEEE Extremely Inv.
8: ANSI Normally Inv.
9: ANSI Short Time Inv. Setting
10: ANSI Long Time Inv. IDMT: Reset SGx
11: RI-Type Inverse
12: RXIDG-Type Inverse 1: Instantaneous
2: Delayed as per Char.
Setting IDMT: Iref Rating IDMT: Charac- IDMT: kt Time IDMT: Min. trip IDMT: Hold time IDMT: Reset SGx
SGx teristic SGx Dial/TMS SGx time SGx SGx
Group 1 072 050 072 056 072 053 072 077 072 071 072 059
Group 2 073 050 073 056 073 053 073 077 073 071 073 059
Group 3 074 050 074 056 074 053 074 077 074 071 074 059
Group 4 075 050 075 056 075 053 075 077 075 071 075 059
48Z5472B_UK
Direction measurement
The short-circuit direction determination function is available in the P438 as of software
version –604. It is enabled with I D M T : D i r e c t i o n M e a s u r e m . When a starting
signal is issued and the measured voltage level has dropped below the value for V<, the
fault angle ϕ is calculated and the fault direction is determined. The short-circuit
characteristic is defined by the angles β and γ. The software decides that the fault
direction is ”forward“ when the calculated angle ϕ lies within the range given by γ ≤ ϕ ≤ β.
In order for direction measurement to function correctly, even at very small fault voltage
values, the information stored in the voltage memory is also put to use in these cases.
Direction determination and starting are enabled only if the measured voltage value is
below a settable undervoltage threshold, V<. Setting undervoltage threshold V< to
Blocked will disable this voltage scan and tripping will be permanently enabled.
For very low fault voltages, the voltage from the voltage memory is used in place of the
measured voltage in order to avoid erroneous direction decisions. The directional
decision is dependent on the following conditions:
VF > 0.1 Vn
The directional decision is issued on the basis of the fault current and the measured
fault voltage VF.
VF < 0.1 Vn
Voltage memory enabled:
The directional decision is issued on the basis of the fault current and the voltage
value stored in the voltage memory.
Voltage memory not enabled:
The directional decision is issued on the basis of the fault current and the measured
fault voltage down to a minimum value of 1 V. If the fault voltage drops to a value of
less than approximately 1 V, an accurate direction determination is no longer
possible. In this case, a Fault forward decision is issued - independently of the actual
fault direction.
Another setting is used to determine whether a failure of the voltage measuring circuit
will either lead to DTOC protection operating non-directionally or to it becoming blocked.
The starting direction may be freely set.
When a permanent current enable value is exceeded the load angle ϕ is calculated and
the load flow direction is determined according to the selected short-circuit characteristic.
The load flow direction is displayed for as long as there is no fault (short-circuit) condition
apparent, which would be characterized by the starting of the current stages and the
enabling of the undervoltage stage.
Forward direction
Reverse direction
68Z50ABB_UK
1 2 3 4 5 6 7
1
1.05 * Iref
2
1: With starting
2: With direction
IDMT: Enabled C
[ 040 100 ] & IDMT: Starting
Iref>
& [ 040 080 ]
MAIN: Protection
active
306 001
I
&
MAIN: Inrush
stabil. trigg
306 014
IDMT: Direction
forward
307 104
Parameter IDMT: Charac- IDMT: Char. IDMT: Min. trip IDMT: Hold time IDMT: Reset
teristic PSx factor kt PSx time PSx PSx PSx
set 1 072 056 072 053 072 077 072 071 072 059
set 2 073 056 073 053 073 077 073 071 073 059
set 3 074 056 074 053 074 077 074 071 074 059
set 4 075 056 075 053 075 077 075 071 075 059
48Z6375A_EN
1 2 3 4 5 6 7
V
&
IDMT: Direct.
& Using Memory
[ 041 014 ]
IDMT: beta
SGx
[ * ]
> 0.05 Inom IDMT: gamma
SGx
[ * ]
C1
I
C2
IDMT: Fault
K Φ1 & Forward
[ 041 008 ]
IDMT: Fault
S Φ2 & Reverse
V(stored) [ 041 009 ]
IDMT: Power
Forward direction 30 ms 0 & Flow Forward
[ 041 017 ]
IDMT: Power
MAIN: VMemory Reverse direction 30 ms 0 & Flow Reverse
enable [ 041 018 ]
305 049
IDMT: Iref>
triggered IDMT: Fwd. w/o
310 038
& Measurem.
IDMT: V < V< [ 041 189 ]
307 108
*
Setting
Setting- IDMT: beta IDMT: gamma
SGx SGx
Group 1 072 046 072 047
Group 2 073 046 073 047
Group 3 074 046 074 047
Group 4 075 046 075 047
48Z6376A_UK
1 2 3 4 5 6 7
1
V
2
3
Setting Blocked
1: Forward
Directional
2: Reverse
Directional
3: Non-
Directional IDMT: Forward
& direction
IDMT: Fault 307 104
Forward
[ 041 008 ]
IDMT: Reverse
& direction
307 105
IDMT: Fault
Reverse
[ 041 009 ]
IDMT: Non-
& directional trip
307 106
Setting
Setting- IDMT: Mode w/o IDMT: V< IDMT: Direction
Voltage SGx SGx (I>) SGx
Group 1 072 119 072 081 072 048
Group 2 073 119 073 081 073 048
Group 3 074 119 074 081 074 048
Group 4 075 119 075 081 075 048
48Z63AJA_UK
Holding time
The P438 determines the trip time according to the current flow, and a timer stage is
started. The setting for the holding time defines the period for the IDMT starting time to
be stored after the starting signal has dropped out. Should the starting signal return
while the holding timer elapses, then the new starting time value is added to the stored
starting time. If the sum of the starting times reaches the trip time determined by the
P438, then the appropriate signal is issued. If the starting signal does not return while
the holding timer elapses, then the memory storing the sum of the starting times will – in
accordance with the setting – be cleared either without delay or according to the set
characteristic. The phase current stage serves as an example to illustrate the effect of
the holding time in Figure Fehler! Verweisquelle konnte nicht gefunden werden..
Under certain operating conditions (no load, cold winter nights) catenaries can ice over.
In order to prevent this, two catenaries each are connected in series and heated with a
comparatively low current. The defrost protection function measures the feed and return
current and processes these current values in a differential protection function for
sensitive short-circuit protection.
Enabling or disabling
defrost protection
Defrost protection may be disabled or enabled using setting parameters. Enabling can
be carried out separately for each setting group.
DFRST: General
Enable USER
[ 019 096 ]
0
1
0: No
1: Yes
DFRST: Enable
SGx
[ * ]
DFRST: Enabled
[ 041 203 ]
0
1
0: No Setting DFRST: Enable
SGx
1: Yes Group 1 019 130
Group 2 019 131
Group 3 019 132
Group 4 019 133
48Z5058A_UK
Transformer matching
Current transformers for the acquisition of the catenary and defrost currents can be
dimensioned within a certain range. From the CT transformation ratio data, the P438
calculates a matching factor.
I X ,prim
f =
IOL,prim
The matching factor is limited to a range of 1/32 at the minimum and 32 at the maximum.
If it is outside these limits, the P438 generates an error message.
Differential protection
characteristics
The P438 generates a differential current (Id) and a restraining current (IR) from the
primary values of the catenary current and the defrost current:
⎛ ⎞
I H = 0,5 ⋅ ⎜⎝ I prim + I dfrst , prim ⎟⎠
I n CT . prim
Enabled I prim = I
I nDevice
I dfrst , nCT . prim
I dfrst , prim = I dfrst
I dfrst , nDevice
Id >
and IH ,m1 = m
1
Operating zone
Blocking zone
46Z5066A_EN
Functional blocking
The elapsing of the operate delay may be blocked using an appropriately configured
binary signal input.
DFRST: General
Enable USER
[ 019 096 ]
0
DFRST: Enabled
1 [ 041 203 ]
0: No
1: Yes
MAIN: In C.T.
prim.
[ 010 001 ]
MAIN: Idfrst,nom
C.T. prim
[ 010 016 ]
CHECK:Match.fact.
DFRSTinv.
[ 098 033 ]
COMP
DFRST: Mismatch
[ 041 207 ]
DFRST: Scaling
factor
[ 004 203 ]
DFRST: Blocking t
EXT
[ 041 206 ]
I
DFRST: Trip
Signal
[ 041 205 ]
Idfrst
DFRST: Starting
[ 041 204 ]
Disabling or enabling
thermal overload protection
Thermal overload protection may be disabled or enabled using setting parameters.
Moreover, enabling can be carried out separately for each setting group.
1 2 3 4 5 6 7
THERM: General
Enable USER
[ 022 050 ]
0
1 THERM: Enabled
& [ 040 068 ]
0: No
1: Yes
THERM: Enable
SGx
[ * ]
0
1
0: No
1: Yes ** GROUP: Group y * Setting THERM: Enable
y Active SGx
GROUP: Group y
Active 1 036 090 Group 1 072 175
[ ** ]
2 036 091 Group 2 073 175
3 036 092 Group 3 074 175
4 036 093 Group 4 075 175
48Z5331B_UK
Readiness of thermal
overload protection
Thermal overload protection will issue the T H E R M : N o t R e a d y signal if one of the
following conditions applies:
1 2 3 4 5 6 7
THERM: Enabled
[ 040 068 ] ≥1 THERM: Not Ready
[ 040 035 ]
THERM: Block.
by CTA Fail
305 200
&
THERM: Replica
Block EXT
[ 041 074 ] ≥1
THERM: Setting
Error,Block.
[ 039 110 ]
48Z5332B_UK
3-173 T H E R M : N o t r e a d y signal
Operating modes
Two operating modes can be selected for thermal overload protection.
Relative Replica
Absolute Replica
Either operating mode can be enabled or disabled individually. Only one of the operating
modes at a time may be enabled for thermal overload protection. However, if both
operating modes are enabled at the same time, the thermal overload protection is
blocked and an error message is generated by the P438:
THERM: Setting Error,Block.
No.Parall.Lines
ParallLine
ParallLine
parallel
ParallLine
parallel
parallel
Select Select 3
2 Paral/L EXT Paral/L EXT
Select
3 Paral/L EXT
Iref Rating
SGx
Factor 2
Parall. SGx
Factor 3
Parall. SGx
Influence of coolant
temperature
To permit ambient temperature correction, the analog I/O module Y must be fitted.
There are two possible means available to measure coolant temperatures:
The thermal model uses these signals as a criterion to determine a fault in the coolant
temperature measurement. A fault at the selected measuring point will lead to the
issuance of the T H E R M : C T A E r r o r signal.
All relevant parameters for coolant temperature acquisition are hidden if the analog
module Y has not been fitted to the P438. The trip time is calculated by including the
setting for T H E R M : C o o l a n t t e m p . S G x .
Minimum coolant
temperature
A setting for a minimum coolant temperature is provided for catenary sections where
coolant temperatures may differ strongly from measured values. For instance in winter
months the temperature measured in a tunnel will be higher than the ambient
temperature measured at the feeder point. In such cases the measured coolant
temperature is limited to a low value set at T H E R M : M i n i m u m T e m p e r a t . S G x .
Thermal overload
protection operation
without coolant
temperature acquisition
In order to guarantee thermal overload protection, without considering an offset because
of a variable coolant temperature, it is recommended to set the parameter
T H E R M : C T A m b S G x to the maximum permitted coolant temperature.
1 2 3 4 5 6 7
THERM: Select
CT AmbientSGx
[ * ]
0
1 ≥1 THERM: with CTA
303 201
2
0: Default Temp.
Value
1: From PT 100
2: From 20 mA
input
THERM: Enabled ≥1
[ 040 068 ] & ≥1 THERM: CTA Error
[ 039 111 ]
RTDmA: Enabled
[ 035 008 ] CHECK: CTA Error
& [ 098 034 ]
THERM: Funct.
f.CTA fail.SGx
[ * ]
0
THERM: Block.by
1 & CTA Fail
305 200
2
0: Default Temp.
Value
1: Last Meas.
Temperat
2: From 20 mA
input
Relative replica
The rated operating current of the protected object and its overload tolerance for
maximum coolant (ambient) temperature are the basis of the relative thermal replica.
In the "Relative replica" operating mode, the following settings have to be made for
thermal overload protection:
Absolute replica
The thermal limit current of the protected object is the reference current of the absolute
thermal replica. For this limit current, an over-temperature results at the maximum
coolant temperature.
In the "Absolute replica" operating mode, the following parameters have to be set for
thermal overload protection:
Note: The maximum permissible coolant temperature Θa,max is derived from the
difference between the settings for T H E R M : M a x . p e r m . o b j . t m p . S G x
and T H E R M : O / T f . I r e f p e r s . S G x
Tripping characteristics
The maximum r.m.s. phase current I is used to track a first-order thermal replica as
specified in IEC 255-8. In addition to the operating mode-dependent settings, the
following parameters will govern the trip time:
2
⎛ I ⎞
⎜ ⎟ − ΘP
⎜f ⎟
⎝ PL,x ⋅ Iref ⎠
t = τ ⋅ ln 2
⎛ I ⎞ ⎛ Θ a − Θ a,max ⎞
⎜ ⎟ − Δϑ trip ⋅ ⎜1 − ⎟
⎜f ⎟ ⎜ Θ max − Θ a,max ⎟
⎝ PL,x ⋅ Iref ⎠ ⎝ ⎠
The tripping threshold Δϑtrip is set to a fixed value of 100 % ( = 1 ) if the operating mode
is 'Absolute replica'.
θ/%
10000
200
1000
110
τ/min
50
100
200
110
10 1000
50
t/min 200
1
110
50 30
0,1
0,01
0,001
0 1 2 3 4 5 6 7 8 9 10
I/IB
D5Z50BEA
3-176 Tripping characteristics of thermal overload protection (tripping characteristics apply to Δϑ0 = 0 % and identical settings for the maximum
permissible coolant temperature and coolant temperature)
Alarm
Depending on the selected operating mode, a warning signal can be set at one of the
following parameters:
Additionally, a pre-trip time limit can be set; when the time left until tripping falls below
this pre-trip limit, a warning will be issued.
Trip
The trip threshold is set according to the selected operating mode with the following
parameters:
If a trip command is issued, the trip signal is maintained until the status of the thermal
replica has decreased by the value T H E R M : T r i p H y s t e r e s i s S G x , at least for
a fixed time of 5 s.
Cooling
If the current falls below the default threshold of 0.1 Iref, the thermal replica is applied with
the set time constant T H E R M : T i m . C o n s t . 2 ( C o o l ) S G x . This element in the
thermal model takes into account the cooling characteristics of stopped motors.
Note: These two time constants should be set to the same value for transformers and
power lines.
1 2 3 4 5 6 7
THERM: I
305 202
Group 1 072 180 072 187 072 188 072 167 072 153 072 182 072 185
Group 2 073 180 073 187 073 188 073 167 073 153 073 182 073 185
Group 3 074 180 074 187 074 188 074 167 074 153 074 182 074 185
Group 4 075 180 075 187 075 188 075 167 075 153 075 182 075 185
Setting THERM: T> Alarm THERM: T> Trip THERM: Default THERM: Minimum THERM: Trip THERM: Pre-Trip
Reset,% SGx Reset,% SGx CT Amb SGx temperat.SGx Hysteresis SGx Alarm SGx
Group 1 072 184 072 181 072 186 076 178 072 183 072 191
Group 2 073 184 073 181 073 186 077 178 073 183 073 191
Group 3 074 184 074 181 074 186 078 178 074 183 074 191
Group 4 075 184 075 181 075 186 079 178 075 183 075 191
48Z5334A_UK
Reset
The thermal replica may be reset either using a setting parameter or an appropriately
configured binary signal input. Resetting is possible even when thermal overload
protection is disabled. Thermal overload protection can be blocked using an
appropriately configured binary signal input.
1 2 3 4 5 6 7
THERM: Reset
Replica USER
[ 022 061 ]
0
1 THERM: Reset Replica
1 [ 039 061 ]
0: don't execute
1: execute
THERM: Enabled
[ 040 068 ]
THERM: Reset Replica EXT
[ 038 061 ]
48Z5335A_UK
The P438 provides a two-stage time-delayed voltage protection function for over- and
undervoltage monitoring.
Disabling or enabling
V<> protection
V<> protection can be disabled or enabled using a setting parameter. Enabling can be
carried out separately for each setting group.
SGx
C&VTS:
Setting SGx
Group
Group
Group
Group
Voltage monitoring
The P438 checks the voltage to determine whether it exceeds or falls below set
thresholds. The triggers are followed by timer stages that can be blocked using
appropriately configured binary signal inputs.
If the decisions of undervoltage monitoring are to be included in the trip commands, then
it is recommended that transient signals be used. Otherwise the trip command would
always be present when the system voltage were disconnected, and thus it would not be
possible to reclose the circuit breaker.
Furthermore, the undervoltage protection function provides a window function.
The windows are defined by the settings for V < > : V m i n S G x and by the set
thresholds V < or V < < , respectively. The setting for V < > : V m i n S G x defines the
lower threshold for both windows. With an appropriate setting of the successive timer
stages, this provision can be used to bridge short periods of voltage failure as
encountered in switching operations.
Main-trip and re-trip circuits can be monitored by the integrated circuit breaker failure
protection function.
Disabling or enabling
circuit breaker failure
protection
Circuit breaker failure protection may be disabled or enabled using setting parameters.
Enabling can be carried out separately for each setting group.
CBF: General
Enable USER
[ 022 100 ]
0
1 CBF: Enabled
[ 040 055 ]
0: No
1: Yes
CBF: Enable
SGx
[ * ]
0
1
0: No
1: Yes
GROUP: Group y
Active
[ ** ]
Readiness of circuit
breaker failure protection
Circuit breaker failure protection will not be available under the following conditions :
Circuit breaker failure protection is not enabled.
The protection function is not enabled.
Circuit breaker failure protection is blocked using an appropriately configured binary
signal input.
CBF: Enabled
[ 040 055 ]
CBF: Blocking
EXT
[ 038 058 ]
48Z5062B_UK
3-183 C B F : N o t R e a d y signal
CB failure protection
Circuit breaker failure protection is started by the main-trip command or by the trip
command of an external protection device (wired to an appropriate binary input).
These commands start a timer stage. Once this has elapsed, a re-trip results unless the
current monitored by the circuit breaker failure protection function has fallen below the
set threshold. Only the fundamental component of the current is monitored here.
If the fault is still present once the first timer stage (C B F : t B F 1 I n i t R e T r i p S G x )
has elapsed, the signal C B F : R e - T r i p s i g n a l is issued to trigger the re-trip.
If the fault is still present once the second timer stage (C B F : t B F 2 I n i t
B a c k T r . S G x ) has elapsed, the signal C B F : B a c k - T r i p s i g n a l is issued to
trigger the trip of an upstream circuit breaker ("back-trip").
CB monitoring
Additionally, the circuit breaker auxiliary contact can be monitored. This is only possible
if a binary signal input has been set to M A I N : C B C l o s e d S i g . E X T . The pickup
of the circuit breaker auxiliary contact starts a timer stage. If the monitored current
exceeds C B F : I m i n < , then a C B F : C B S u p e r v . S i g n a l alarm results.
Auxiliary contact supervision is active only for the set operative time. This ensures that
no C B F : C B S u p e r v . S i g n a l (which might lead to switching off the entire plant)
will be issued during protection injection testing.
1 2 3 4 5 6 7
CBF: Imin<
SGx
[ * ]
f0
I
CBF: tImin<
SGx
[ * ] CBF: CB Superv.
Signal
& [ 039 000 ]
& t 0
MAIN: CB Closed
Sig. EXT
[ 036 051 ]
CBF: Operative
Time SGx
[ * ]
* Setting CBF: Imin< CBF: tBF1 Init CBF: tBF2 Init CBF: tImin< CBF: Operative
SGx ReTrip SGx BackTr.SGx SGx Time SGx
Group 1 072 112 072 115 072 116 072 113 072 114
Group 2 073 112 073 115 073 116 073 113 073 114
Group 3 074 112 074 115 074 116 074 113 074 114
Group 4 075 112 075 115 075 116 075 113 075 114
48Z6263A_UK
As of version -606 the P438 features a circuit breaker monitoring function. This function
supports state-controlled maintenance of circuit breakers.
Enabling/disabling circuit
breaker monitoring
Circuit breaker monitoring may be disabled or enabled using setting parameters.
1 2 3 4 5 6 7
CBM: Enabled
USER
[ 022 010 ]
0
1 CBM: Enabled
[ 044 130 ]
0: No
1: Yes
48Z5404B_EN
Variants
The wear condition of a circuit breaker may be determined by a variety of methods:
CB wear characteristic
Manufacturers of circuit breakers usually provide wear characteristics displaying the
maximum number of permissible CB operations in relation to the ruptured current.
Figure 3-186 displays the wear characteristics for a circuit breaker with a nominal current
X X
of 2000 A and a maximum ruptured current of 63 kA. The mean ruptured current is
48 kA.
100000
10000
Number of permissible CB operations
1000
100
10
0.1 1 10 100
Ruptured current in kA
48Z5341A_UK
The knee points in figure 3-186 are necessary to set the wear characteristic for the circuit
X X
breaker:
The mean ruptured current is not available for all types of circuit breakers. In such a
case the parameters for this knee-point are to be set to 'Blocked'. A knee-point is not
considered in the characteristic when at least one of the parameters for the knee-point is
set to 'Blocked'.
For proper performance of circuit breaker monitoring it should be observed that the
knee-points must be applied in a logically correct sequence (continuously descending).
When setting currents and numbers of CB operations that are not plausible according to
the characteristic, the P438 will issue the C B M : S e t t i n g e r r o r C B M error
message and block circuit breaker monitoring.
n (I nom ,CB )
n rem (I nom ,CB ) = n rem,0 (I nom,CB ) −
n (I d ,CB )
With:
disconnection
nrem,(Inom,CB): Number of remaining CB operations at Inom,CB after U U
disconnection
Operating modes
The condition under which the function will be triggered is selected using the
C B M : O p e r a t i n g m o d e parameter:
C
These correction values can be set to determine the exact trip time:
The cycle is started by a trigger criterion. Definition for the end of a cycle: The remaining
time of a power cycle duration has elapsed after the last detected current zero crossing.
The signal C B M : C a t C u r r e n t D e a d or C B M : F d r C u r r e n t D e a d is then
issued.
The maximum cycle time duration is defined with 220 ms. The start of the cycle time is
corrected by the settable correction times. A fault on a CB pole is considered to be
apparent if further current zero crossings are detected after the maximum cycle time has
elapsed. Measured values from the respective CB tripping are cancelled and the signal
C B M : t m a x > C a t or C B M : t m a x > F d r is issued.
1 2 3 4 5 6 7
0
1
2
0: With Trip Cmd.
Only
1: With CB Sig.EXT
Only
2: CB Sig.EXT or
Trip
CBM: Blocked C
[ 044 199 ]
CBM: Corr.
³1 C1 Acqu.T. Trip
[ 022 153 ]
CBM: Corr.
³1 C2 Acqu.T.CB Sig.
[ 022 018 ]
³1
Ix
Pole-selective measured
values and counter values
Depending on the set operating mode, the P438 evaluates the conductor currents
separately and generates an individual wear presentation for each circuit breaker or CB
pole.
The following measured values are presented pole selectively, and per-unit values refer
to the CB’s nominal current:
The ruptured current is derived from the r.m.s. current value generated during the
function cycle.
The integral of the current-time area is calculated during the function cycle. An example
for calculation of the current-time integral is displayed in figure 3-188. X X
1 2 3 4 5 6 7
Current-time integral
1 cycle
MAIN: Main-Trip
Command
[ 039 011 ]
48Z5401B_UK
3-188 Calculation of the pole-selective current-time integrals when CBM is triggered by the main-trip command
1 2 3 4 5 6 7
CBM: Inom,CB
[ 022 012 ]
CBM: Set
SItrip x CBM: Itrip x
[ * ] [ * ]
R
CBM: Set CBM: I*t x
SItrip**2 x [ * ]
[ * ] R
CBM: Itrip, prim
x
CBM: Set R [ * ]
SI*t x
[ * ] CBM: Itrip**2 x
[ * ]
R
CBM: SItrip x
[ * ]
S
CBM: SItrip**2 x
[ * ]
S
CBM: SI*t x
[ * ]
S
CBM: Anz.
No. of CB oper. x
S [ * ]
CBM: Remain.
No. of CB oper. x
S [ * ]
Phase x / CBM: Cycle CBM: Set CBM: Set CBM: Set CBM: Set CBM: Set
Current Ix running x No. CB oper. x remain.CB op.x SItrip x SItrip**2 x SI*t x
A / IA (cat) 044 205 022 131 022 134 022 137 022 140 022 143
B / IB (fdr) * 044 206 022 132 022 135 022 138 022 141 022 144
Phase x / CBM: No. of CB CBM: Remain.No. CBM: Itrip x CBM: I*t x CBM: Itrip, prim CBM: Itrip**2 x
Current Ix oper. x of CB oper. x x
A / IA (cat) 008 011 008 014 009 047 009 061 009 212 009 051
B / IB (fdr) * 008 012 008 015 009 048 009 062 009 213 009 052
Note: Only such measured values and counter values in the P438 may be set to
new values that do not have their default values set to ‘Blocked‘.
The stored value will remain unchanged if the default value is set to ‘Blocked‘.
Executing the set command results in initializing all default values in the P438
to ‘Blocked‘.
An alarm is issued should the number of remaining CB operations for a CB contact drop
below this threshold.
1 2 3 4 5 6 7
* Settings are represented only with "Autotransformer feed" operating mode 48Z5344A_UK
At the same time each switching operation will increment the P438’s counter for the
number of CB operations. The number of CB operations ">" carried out for each CB
contact is displayed. A threshold value can be set using the
C B M : N o . C B O p e r a t i o n s > parameter. An alarm is issued should the number
C
1 2 3 4 5 6 7
CBM: No. CB
operations >
[ 022 019 ]
Monitoring ruptured
currents
In addition to the evaluation of the CB wear state and monitoring of the number of CB
operations carried out, the P438 features the means to accumulate and display ruptured
current values and the square of these values. Threshold values can be set using the
parameters C B M : Σ I t r i p > , C B M : Σ I t r i p * * 2 > and C B M : Σ I * t . An alarm is
C C C
issued should the accumulated current values exceed any of these thresholds.
1 2 3 4 5 6 7
&
CBM: Blocking
USER
[ 022 150 ]
0
1
0: No
1: Yes
48Z5346C_UK
Disabling/enabling and
readiness of limit value
monitoring
Limit value monitoring can be disabled or enabled using setting parameters. Enabling
can be carried out separately for each setting group.
Limit value monitoring will not be available under the following conditions:
Limit value monitoring is not enabled.
Protection is not enabled.
LIMIT: General
Enable USER
[ 014 010 ]
1
0: No
1: Yes
LIMIT: Enable
SGx
[ * ]
LIMIT: Enabled
[ 040 074 ]
0
1
0: No
1: Yes
MAIN: Protection LIMIT: Not Ready
active [ 041 043 ]
306 001
If measured values exceed or fall below one of the set upper or lower limit values,
respectively, a signal is issued once a set time-delay has elapsed.
LIMIT: Enabled
[ 040 074 ] LIMIT: I> LIMIT: tI>
SGx SGx
[ * ] [ * ]
MAIN: Protection
active
306 001
I LIMIT: tI>
Elapsed
[ 004 062 ]
LIMIT: tI>>
Elapsed
[ 040 157 ]
LIMIT: Enabled
[ 040 074 ] LIMIT: Icat> LIMIT: tIcat>
SGx SGx
[ * ] [ * ]
MAIN: Protection
active
306 001
LIMIT: tIcat>>
Elapsed
[ 040 233 ]
LIMIT: tIfdr>>
Elapsed
[ 040 235 ]
Defrost current
monitoring
The defrost current value is monitored by two stages to determine whether it exceeds set
thresholds. If any of the thresholds are exceeded a signal is issued after a set time-
delay has elapsed.
LIMIT: Enabled
[ 040 074 ] LIMIT: Idfrst> LIMIT: tIdfrst>
SGx SGx
[ * ] [ * ]
MAIN: Protection
active
306 001
LIMIT: tIdfrst>>
Elapsed
[ 040 237 ]
Voltage monitoring
The voltage is monitored by two stages to determine whether it exceeds or falls below
set thresholds. If it exceeds or falls below the thresholds a signal is issued once a set
time-delay has elapsed. In addition a multiple signal is issued if any of the tV> or tV>>
(tV< or tV<<) time-delays have elapsed.
LIMIT: Enabled
[ 040 074 ] LIMIT: V> LIMIT: tV>
SGx SGx
[ * ] [ * ]
MAIN: Protection
active
306 001
V LIMIT: tV>
Elapsed
[ 040 140 ]
LIMIT: tV>>
Elapsed
[ 040 141 ]
LIMIT: tV<
Elapsed
[ 040 142 ]
LIMIT: tV>>&tV<<
Elapsed
[ 040 145 ]
LIMIT: V<< LIMIT: tV<<
SGx SGx
[ * ] [ * ]
LIMIT: tV<<
Elapsed
[ 040 143 ]
Monitoring catenary
and feeder voltages
The catenary and feeder voltages are monitored by two stages to determine whether
they exceed or fall below set thresholds. If it exceeds or falls below the thresholds a
signal is issued once a set time-delay has elapsed. In addition a multiple signal is issued
if either of the tVcat> or tVcat< time-delays (or, respectively, stages tVcat>> or tVcat<<,
tVfdr> or tVfdr<, tVfdr>> or tVfdr<<) have elapsed.
LIMIT: Enabled
[ 040 074 ]
LIMIT: Vcat> LIMIT: tVcat>
SGx SGx
[ * ] [ * ]
MAIN:
Protection
active
306 001
LIMIT: tVcat>
Vcat Elapsed
[ 040 240 ]
LIMIT: tVcat>&
LIMIT: Vcat>> tVcat< elap.
Setting LIMIT: Vcat> LIMIT: tVcat> LIMIT: tVcat>> [ 040 244 ]
SGx SGx SGx SGx
[ * ] [ * ]
Group 1 076 208 076 210
Group 2 077 208 077 210
Group 3 078 208 078 210
Group 4 079 208 079 210 LIMIT: tVcat>>
Elapsed
[ 040 241 ]
Setting LIMIT: Vcat>> LIMIT: tVcat>>
SGx SGx
Group 1 076 209 076 211
Group 2 077 209 077 211
LIMIT: Vcat< LIMIT: tVcat<
Group 3 078 209 078 211 SGx SGx
Group 4 079 209 079 211 [ * ] [ * ]
LIMIT: tVfdr>
Vfdr Elapsed
[ 040 246 ]
LIMIT: tVfdr>&
Setting LIMIT: Vfdr> LIMIT: tVfdr> tVfdr< elap.
LIMIT: Vfdr>> LIMIT: tVfdr>> [ 040 250 ]
SGx SGx SGx SGx
Group 1 076 212 076 214 [ * ] [ * ]
Group 2 077 212 077 214
Group 3 074 212 074 214
Group 4 075 212 075 214 LIMIT: tVfdr>>
Elapsed
[ 040 247 ]
Setting LIMIT: Vfdr>> LIMIT: tVfdr>>
SGx SGx
Group 1 076 213 076 215
Group 2 077 213 077 215
Group 3 078 213 078 215 LIMIT: Vfdr< LIMIT: tVfdr<
Group 4 079 213 079 215 SGx SGx
[ * ] [ * ]
48Z5408A_UK
Frequency monitoring
The frequency is monitored by two stages to determine whether it exceeds or falls below
set thresholds. If it exceeds or falls below the thresholds a signal is issued once a set
time-delay has elapsed.
LIMIT: Enabled
[ 040 074 ] LIMIT: f> LIMIT: tf>
SGx SGx
[ * ] [ * ]
MAIN: Protection
active
306 001
f LIMIT: tf>
Elapsed
[ 040 196 ]
LIMIT: tf>>
Elapsed
[ 040 197 ]
LIMIT: tf<
Elapsed
[ 040 198 ]
LIMIT: tf<<
Elapsed
[ 040 199 ]
Programmable (or user-configurable) logic enables the user to link binary signals within
a framework of Boolean equations.
Binary signals in the P438 may be linked by logical 'OR' or 'AND' operations with the
option of additional NOT operations by setting L O G I C : F c t . A s s i g n m . O u t p . n ,
where n = 1 to 32. The Boolean equations need to be defined without the use of
brackets. The following rule applies to the operators: ‘NOT’ before ‘AND’ before ‘OR’.
Logical operations can be controlled through the binary signal inputs in different ways.
Binary input signals L O G I C : I n p u t n E X T (n = 1 to 16) have an updating function,
whereas input signals L O G I C : S e t n E X T (n = 1 to 8) are latched. The logic can
only be controlled from the binary signal inputs configured for L O G I C : S e t n E X T
if the corresponding reset input (L O G I C : R e s e t n E X T ) has been configured for a
binary signal input. If only one or neither of the two functions is configured, then this is
interpreted as ‘Logic externally set’. If the input signals of the two binary signal inputs
are implausible (such as when they both have a logic value of ‘ 1 ’), then the last
plausible state remains stored in memory.
When using the programmable logic, the user must carry out a functional type test to
conform with the requirements of the relevant protection/control application. In particular,
it is necessary to verify that the requirements for the implementation of logic linking (by
setting) as well as the time performance during device startup, during operation and
when there is a fault (device blocking) are fulfilled.
3-202 Control of logic operations using setting parameters or stored input signals
3-203 Setting options for programmable logic (shown here for output 1)
The output signal of an equation can be fed into a further, higher order, equation as an
input signal thus creating a sequence of interlinked Boolean equations. The equations
are processed in the sequence defined by the order of each equation. It should be noted
that in the case of overlapping equations, the result is provided by the equation with the
highest order.
The output signal of each equation is fed to a separate timer stage with two timer
elements and a choice of operating modes. This offers the possibility of assigning a
freely configurable time characteristic to the output signal of each Boolean equation.
In the Minimum Dwell operating mode, the setting of timer stage tZ2 has no effect.
Figures 3-204 to 3-208 show the time characteristics for the various timer stage
operating modes.
Note: If the device is switched to "offline" the equations are not processed and all
outputs are set to the ' 0 ' logic level.
4 Design
The P438 is available in different types of cases and with different combinations of
modules.
The P438 – like all other device types in the MiCOM Px30 range – is equipped with the
standard user interface (HMI). Depending on the order the user interface (HMI) is fitted
either permanently to the case front panel or is detachable. The user interface is
covered with a tough film so that the specified degree of IP protection will be maintained.
In addition to the essential control and display elements, a parallel display consisting of a
total of 17 LED indicators is also incorporated. The designation of the various LED
indicators is shown in plain text on a label strip.
The PC interface (9-pin D-Sub female connector) is located under the hinged cover at
the bottom of the user interface.
The P438 is available either as surface-mounted case or a flush-mounted case with case
widths of 40TE and 84TE. The user interface (HMI) is either fitted permanently to the
case front panel or detachable.
12Z61TDA
4-1 Basic unit with flush-mounted 40TE case – front view, user interface (HMI) is fitted permanently to the case front panel
12Z61ABA
4-2 Basic unit with flush-mounted 40TE case and detached user interface (HMI) – front view
The detached user interface (HMI) on the 84TE basic unit also has a width of 40TE
49Z6202A
Electrical connections for both designs (surface-mounted and flush-mounted case) are
made via plug-in threaded terminal blocks. The threaded terminal blocks in the surface-
mounted case are accessible from the front of the device after unscrewing the crosshead
screws on the sides (see Figure 4-4, ) and removing the user interface (HMI). The
user interface (HMI) can then be secured by inserting the tabs in the slots in the left side
wall (see Figure 4-4, ). The flush-mounted case is connected at the back of the case.
The secondary circuit of operating current transformers must not be opened. If the
secondary circuit of an operating current transformer is opened, there is the danger that
the resulting voltages will endanger personnel and damage the insulation.
In units for pin terminal connection, the threaded terminal block for current transformer
connection is not a shorting block. Therefore always short-circuit current transformers
before loosening the threaded terminals.
4-4 Surface-mounted case, removal of user interface (HMI), illustrated here for a device with graphic display in a 40TE case
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod .
147,5
177,5
184,5
213,4 257,1
242,6
260,2
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod.
147,5
177,5
184,5
434,8 257,1
464,0
481,6
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod .
177,5
213,4 227,9
253,6
203,0
155,4
159,0
168,0
5,0
5,0
181,3
4-7 Panel cutout for the 40TE flush-mounted case, flush-mount method 1 (without angle brackets and frame)
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod .
177,5
101,6
213,4 227,9
253,6
242,6
260,2
6,4
101,6
186,5
224,5
242,6
4-8 Panel cutout for the 40TE flush-mounted case, flush-mount method 2 (using the angle brackets and frame)
Note: The P438 has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on this page)
is used for the flush-mounted cases.
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod .
177,5
434,8 227,9
253,6
284,9
259,0
25,9
159,0
168,0
5,0
5,0
410,0
4-9 Panel cutout for the 84TE flush-mounted case, flush-mount method 1 (without angle brackets and frame)
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod .
177,5
101,6
434,8 227,9
253,6
464,0
481,6
6,4
101,6
186,5
445,9
464,0
4-10 Panel cutout for the 84TE flush-mounted case, flush-mount method 2 (using the angle brackets and frame)
Note: The P438 has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on this page) is
used for the flush-mounted cases.
4.2.3 Device View of Connection for the Detached User Interface (HMI)
40TE device view of connection for the detached user interface (HMI):
Aus-Kommando
Warnung
Block./ Stör ung
Betr ieb
ACHTUNG:
84TE device view of connection for the detached user interface (HMI):
Aus- Kommando
War nung
Block./ Störung
Betr ieb
ACHTUNG:
Aus- Kommando
War nung
107,3
Block./ Störung
Betr ieb
Änder ungsmod
.
177,5
206,0 20,7
46,3
197,5
192,5
148,0
168,0
3,0
181,3
4-11 Panel cutout and device view of connection for the detachable user interface (HMI)
Note: Connection of protective grounding conductor: See Chapter 5
4.3 Modules
The P438 is constructed from standard hardware modules. The following table gives an
overview of the modules relevant for the P438
(*: modules that are not shown in the location diagrams, : optional, : standard
equipment, : depending on order).
The space available to fit the modules measures 4 H in height by 40TE or 84TE in width
(H = 44.45 mm, TE = 5.08 mm). The location of the individual modules and the position
of the threaded terminal blocks in the P438 are shown in the installation diagrams to be
found at the end of Chapter 5.
Only qualified personnel, familiar with content on the "Warning" page at the beginning of
this operating manual, may work on or operate this device.
The instructions given in the “Protective and Operational Grounding” section should be
noted. In particular, check that the protective ground connection is secured with a tooth
lock washer, as per the diagram “Installing the protective grounding conductor terminal”.
If a cable screen is added to this connection or removed from it, then the protective
grounding should be checked again.
The RJ45 twisted wire and glass fiber SC connector on the Ethernet module may not be
both connected at the same time. (The setting at I E C : E t h e r n e t M e d i a must be
observed.)
All P438 units are packaged separately in their own cartons and shipped inside outer
packaging. Use special care when opening cartons and unpacking units, and do not use
force. In addition, make sure to remove supporting documents and the type
identification label supplied with each individual device from the inside carton.
The design revision level of each module included in the unit when shipped can be
determined from the list of components (assembly list). This list should be carefully
saved.
After unpacking each unit, inspect it visually to make sure it is in proper mechanical
condition.
If the P438 needs to be shipped, both inner and outer packaging must be used. If the
original packaging is no longer available, make sure that packaging conforms to
DIN ISO 2248 specifications for a drop height ≤ 0.8 m.
The nominal data and design type of the P438 can be determined by checking the type
identification label (see Figure 5-1). One rating label is located under the hinged cover
at the top of the user interface (HMI). Another copy of the type identification label is
affixed to the outside of the P438 packaging.
The P438 design version can be determined from the order number. A breakdown of the
order number is given in Chapter 14.
The P438 is designed to be conform to DIN 57 435 Part 303. Therefore it is important
when choosing the installation location to make certain that it provides the operating
conditions as specified in above DIN norm sections 3.2 to 3.4. Several important
conditions are listed below.
Climatic conditions
Ambient temperature: -5 °C to +55 °C [+23 °F to +131 °F]
Relative humidity: The relative humidity must not result in the formation of
either condensed water or ice in the P438.
Ambient air: The ambient air must not be significantly polluted by dust,
smoke, gases or vapors, or salt.
Solar Radiation: Direct solar radiation on the front of the device must be
avoided to ensure that the LC-display remains readable.
Mechanical conditions
Vibration stress: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
or 10 to 60 Hz, 0.075 mm and 60 to 150 Hz, 1.0 g
depending on the installation type (see Chapter 2, paragraph 'Mechanical robustness')
Electromagnetic conditions
Appropriate measures taken in substations must correspond to the best of modern
practices.
5.4 Installation
The dimensions and mounting dimensions for surface-mounted cases are given in
Chapter 4. When the P438 is surface-mounted on a panel, the leads to the P438 are
normally run along the front side of the mounting plane. If wiring is to run to the rear a
cutout opening can be provided above and below the surface-mounted case, as shown
in the two figures below. The figures only show the bottom cutout. The same
considerations also apply to the upper cutout.
For connection of the protective ground/earth terminal see section 5.5 'Protective
Grounding'.
If the units are to be installed in accordance with flush-mount method 1 (without the
angle brackets and frame), follow the steps described below.
Before the P438 can be installed in the control panel, the user interface (HMI) must be
removed. The procedure is as follows:
Remove the hinged covers at the top and bottom of the user interface. (Open the
hinged covers by flipping them up or down 180°. Hold them in the middle and bend
them slightly. The side mountings of the covers can then be disengaged.)
Remove the M3 screws (see Figures 5-3 and 5-4).
Then remove the lower M4 screws and loosen the upper M4 screws (see Figures 5-3
and 5-4). Insert the P438 into the panel opening from the rear so that the upper M4
screws fit into the corresponding slots. Then tighten all the M4 screws. After this,
replace the user interface (HMI).
Note: If the control panel thickness is ≥ 2 mm, longer M3 and M4 bolts must be
used. Longer screws are enclosed within the device packing.
5-3 Installation of a 40TE case on a panel, flush-mount method 1 (without angle brackets and frame).
The P438 has increased mechanical robustness if either the surface-mounted case or – for the flush-mounted case – flush-mount
method 2 (with angle brackets and frame) is used see Figure 5-6.
5-4 Installation of a 84TE case on a panel, flush-mount method 1 (without angle brackets and frame)
The P438 has increased mechanical robustness if either the surface-mounted case or – for the flush-mounted case – flush-mount
method 2 (with angle brackets and frame) is used see Figure 5-6.
Remove the screws as shown in Figure 5-5 Mounting the angle brackets, c and
mount the enclosed angle brackets using these same screws.
Slide the unit into the panel opening from the front.
Secure the device to the control panel by using the enclosed M6 screws
(see Figure 5-6).
Assemble the cover frame and snap it onto the mounting bolts.
Angle brackets
M6
B6
6.4
M6 x 15
Height: 204 mm
for the
Frame 80 mm
W idt h: 2 n d cas
te e
s h-m ou
40T E flu
12Y6183 B_EN
5-6 Installation of a case into a control panel, flush-mount method 2 (with angle brackets and frame).
Example for a device in a 40TE case
The width of the frame for the 84TE case comes to 486 mm
The device has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on this page) is used
for the flush-mounted cases.
The 84TE flush-mounted cases – with angle brackets mounted – are also suitable for
installation in enclosures or control cabinets equipped with a 19" mounting rack.
5-7 Installing the P438 into a control cabinet equipped with a 19" mounting rack
Two rack mounting kits can be used to combine a flush-mounted 40TE case to form a
19" mounting rack (see Figure 5-8). The second sub-rack can for instance consist of
another device or an empty sub-rack with a blank front plate.
In addition, a protective ground connection at the terminal contact on the power supply
module (identified by the letters "PE" on the terminal connection diagram) is also
required for proper operation of the device. The cross-sectional area of this ground
conductor must also conform to applicable national standards. A minimum cross section
of 1.5 mm2 is required.
19Y5220A_EN
The protective grounding (earth) conductor must always be connected to the protective grounding conductor terminal, so as to
ensure the safety provided by the device’s design.
The bracket on the terminal is marked with the protective ground symbol: .
5.6 Connection
The P438 must be connected in accordance with the terminal connection diagram
indicated on the type identification label. Terminal connection diagrams relevant for the
P438 can be found at the end of this chapter.
Copper leads having a 2.5 mm2 cross-section are generally suitable as the connecting
leads between the current transformers and the P438. To reduce CT knee-point voltage
requirements, it may be necessary to install shorter copper conductors with a greater
cross section between the system current transformers and the current inputs on the
P438. Copper leads having a 1.5 mm2 cross section are adequate for connecting the
binary signal inputs, the signaling and triggering circuits, and the power supply input.
All connections run into the system must always have a defined potential. Connections
that are pre-wired but not used should preferably be grounded when binary inputs and
output relays are isolated. When binary inputs and output relays are connected to a
common potential, the pre-wired but unused connections should be connected to the
common potential of the grouped connections.
Power supply
Before connecting the auxiliary voltage VA for the P438 power supply, it must be ensured
that the nominal value of the auxiliary device voltage corresponds with the nominal value
of the auxiliary system voltage.
Current-measuring inputs
When connecting the system transformers, it must be ensured that the secondary
nominal currents of the system and the device correspond.
The secondary circuit of operating current transformers must not be opened. If the
secondary circuit of an operating current transformer is opened, there is the danger that
the resulting voltages will endanger personnel and damage the insulation.
In units for pin terminal connection, the threaded terminal block for current transformer
connection is not a shorting block. Therefore always short-circuit current transformers
before loosening the threaded terminals.
Supply
Catenary
I>
MAIN: Feeding
Mode
[ 010 135 ]
1
2
1: Classic Single
Feed
2: Auto-
Transformer Feed
MAIN: Vn VT.
c Sec.
[ 010 009 ]
1U
2U V
Catenary
Rail
48Z5411A_UK
5-10 Connecting the P438 measuring circuits in the 'Classic single feed' operating mode
Supply Catenary
Supply Feeder
MAIN: Feeding
Mode
[ 010 135 ]
1
2
I>
1: Classic Single
Feed
2: Auto-
Transformer Feed
MAIN: Vn VT.
I> c Sec.
[ 010 009 ]
1U
2U Vcat
3U Vfdr
4U
S
+ V
-
1: Standard
(Y = 1)
2: Opposite
(Y = -1) S
+ I
-
Feeder
Catenary
Rail
48Z5412A_UK
5-11 Connecting the P438 measuring circuits in the 'Autotransformer feed' operating mode
In addition to the protection of the catenary in normal train operation, the P438 also
provides defrost protection. An additional current transformer must be connected when
the device is in the operating mode 'Defrost operation'. Figure 5-12 shows the
connection with 'Defrost operation'. In this operating mode, circuit breakers Q1, Q3 and
Q4 are closed whereas circuit breaker Q2 is open. It is important to ensure - from the
installation side - that the circuit breaker Q2 is opened before circuit breakers Q3 and Q4
are closed.
Supply
Catenary
Q1 Q2
MAIN: Line CT MAIN: In Device
Orientation [ 010 003 ]
[ 010 004 ]
Icat
X X.Y I
1: Standard
(Y = 1)
2: Opposite
(Y = -1)
1: Standard
(Y = 1)
2: Opposite
(Y = -1)
Catenary 1
Q3
Catenary 2
Q4
Rail
48Z5413A_UK
Connecting a resistance
thermometer
If the analog I/O module Y is fitted, a resistance thermometer can be connected.
This analog I/O module input is designed to connect a PT 100 resistance thermometer.
The PT 100 should be connected using the 3-wire method (see Figure 5-13). No supply
conductor compensation is required in this case.
The terminal connection diagrams give a polarity for connection of the binary signal
inputs. However, this is only a recommendation. Connection to binary inputs can be
made as desired.
PC interface
The PC interface is provided in order to operate the unit from a personal computer (PC).
Communication interfaces
Communication interfaces are provided for permanent connection of the unit to a control
system for substations or to a central substation unit. Depending on the type,
communication interface 1 on the device is connected either by a special fiber-optic
connector or a RS 485 interface with twisted pair copper wires. Connection to channel 2
is always by way of an RS 485 interface.
The selection and assembly of a properly cut fiber-optic connecting cable requires
special knowledge and expertise and is therefore not covered in this operating manual.
The fiber-optic interface may only be connected or disconnected when the supply voltage
for the unit is shut off.
The RS 485 interface available on the P438 was designed so that data transfer in a full
duplex transmission mode is possible using a 4-wire data link between devices.
However, communication through the RS 485 interface is always in the half-duplex mode
of operation. To connect the RS 485 communication interface the following must be
observed:
Always use twisted-pair shielded cables only, the kind used for telecommunications
systems.
At least one symmetrically twisted core pair will be required.
Strip cable cores and cable shield right at the connection point and connect properly
in accordance with specifications.
Ground all shields at both ends (large-area grounding).
Ground free (unshielded) cores at one end only.
As another option, a 2-wire or 4-wire connection is also possible. For the 4-wire
connection, a cable with two symmetrically twisted core pairs is required. A 2-wire data
link is shown in Figure 5-14, and a 4-wire data link is shown in Figure 5-15 as an
example for channel 2 on the communication module. If channel 1 of the communication
module is designed as an RS 485 interface, then the same arrangement would apply.
P438
P438
48Z5480A_EN
P438
P438
48Z5481A_EN
01 02 03 04 05 06 07 08 09 10
P A A T X X Y V X
CH1 CH3 3J 6I 6I 4I 4I
CH2 2V 8O 8O 8O 6O
alt. alt.
A X
ETH
CH2 4H
01 02 03 04 05 06 07 08 09 10
5-16 P438 in 40TE case, transformer module with ring-terminal connection, other modules with pin-terminal connection, diagram P438-305-409
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A A T Y X X X X X V
CH1 CH3 3J 4I 6I 6I 6I 6I 4I
CH2 2V 8O 8O 8O 8O 6O 8O
alt. alt.
A X
ETH
CH2 4H
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A A T Y X X X X X V
CH1 CH3 3J 4I 6I 6I 6I 6I 4I
CH2 2V 8O 8O 8O 8O 6O 8O
alt. alt.
A X
ETH
CH2 4H
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
Ring Pin Voltage measuring Ring Pin Ring Pin Ring Pin
X041 X041 inputs X_1 X_1 Output relays X_1 X_1 Output relays X_1 X_1 Measuring outputs
1 1 1 1 1 1
13 1 VA T5 2 2 K_01 2 2 K_01 2 2 K_01
14 2 3 3 3 3 3 3 valid
15 3 4 4 4 4
16 4 5 5 5 5 4 4
U
17 5 VB T6 6 6 K_02 6 6 K_02 5 5
6
#
18 7 7 7 7 6 6
8 8 8 8 0..20 mA U_08
9 9 K_03 9 9 K_03 7 7
11 7 8 8 K_02
12 8 X_2 X_2 9 9 valid
10 1 10 1
11 2 K_04 11 2 K_04 X_2
12 3 K_05 12 3 K_05 10 1
U
Current measuring 13 4 K_06 13 4 K_06 11 2
#
X042 inputs 14 5 K_07 14 5 K_07 12 3
1 1 IA T1 15 6 15 6 0..20 mA U_09
2 2 16 7 K_08 16 7 K_08
3 3 IB T2 17 8 17 8
4 4 Signal and
5 5 Idfrst T3 Signal inputs Signal inputs measuring inputs
6 6 18 9 18 9 13 4
Vin Vin Vin U_01
7 7 U_01 U_01 14 5
U
8 8 X_3 X_3 15 6
Vin _02
19 1 19 1 16 7
20 2 20 2 U_02 17 8
Vin Vin Vin U_03
21 3 U_02 21 3
22 4 22 4 U_03 18 9
Vin Vin Vin U_04
U_03
23 5 23 5 U_04 X_3
Vin Vin
24 6 U_04 24 6 19 1
25 7 U_05 20 2
U
U_05
Vin 0..20 mA
Power supply 21 3
#
25 7 + V 26 8 U_06 22 4 U U_06
aux Vin
26 8 - U100 27 9 23 5 PT100
27 9 PE 24 6 #
Communication Type A Communication Type A Communication Type A Binary Type X Binary Type X
module CH1 / CH2 module ETH / CH2 module CH3 module 6O module 4H
1
X10 RJ45 M5[DCD]
X//Y 2
D2[R]
1 X_3 X_3
3
2 D2[R] D1[T] 19 1 1) 19 1
COMM2 4 K_03
3 E U27 20 2 K_04 20 2 +
U20 wire link 5
E2[G]
4 21 3 21 3
5 D1[T] 22 4 1) 22 4
7
X10
X//Y +UB 23 5 K_05 23 5
1
RS 485 24 6 24 6
2 D2[R]
RS 232 25 7 25 7
3
IRIG-B U20 26 8 K_06 26 8 K_04
4
time synchronization D1[T] 27 9 27 9 +
5
X11
1 # U21 RS 485
#
01 02 03 04 05 06 07 08 09 10
P A A T X X Y V X
CH1 CH3 3J 6I 6I 4I 4I
CH2 2U 8O 8O 8O 6O
alt. alt.
A X
ETH 6I
CH2 3O
alt. alt.
A X
Red.
ETH 4H
CH2
01 02 03 04 05 06 07 08 09 10
5-21 P438 in 40TE case, transformer module with ring-terminal connection, other modules with pin-terminal connection, diagram P438-307-412
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A A T Y X X X X X V
CH1 CH3 3J 4I 6I 6I 6I 6I 4I
CH2 2U 8O 8O 8O 8O 6O 8O
alt. alt.
A X
ETH 6I
CH2 3O
alt. alt.
A X
Red.
ETH 4H
CH2
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A A T Y X X X X X V
CH1 CH3 3J 4I 6I 6I 6I 6I 4I
CH2 2U 8O 8O 8O 8O 6O 8O
alt. alt.
A X
ETH 6I
CH2 3O
alt. alt.
A X
Red.
ETH 4H
CH2
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
Transformer Type T Power supply Type V Binary Type X Binary Type X Binary Type X
module 3J / 2V module 4I / 8O module 6O module 6I / 8O module 4H
Ring Pin Voltage measuring Ring Pin Ring Pin Ring Pin Ring Pin
X041 X041 inputs X_1 X_1 Output relays X_1 X_1 Output relays X_1 X_1 Output relays X_1 X_1 High-break
1 1 1 1 1 1 contacts
13 1 VA T5 2 2 K_01 2 2 K_01 2 2 K_01
14 2 3 3 3 3 3 3 4 4
K_01
15 3 4 4 4 4 4 4 5 5 +
16 4 5 5 5 5 5 5
17 5 VB T6 6 6 K_02 6 6 6 6 K_02
18 6 7 7 7 7 7 7
8 8 8 8 K_02 8 8 X_2
9 9 K_03 9 9 9 9 K_03
11 2 K_02
X_2 X_2 12 3 +
10 1 X_2 10 1
11 2 K_04 10 1 1) 11 2 K_04
12 3 K_05 11 2 12 3 K_05
Current measuring 13 4 K_06 12 3 13 4 K_06 X_3
X042 inputs 14 5 K_07 13 4 1) 14 5 K_07 19 1
K_03
1 1 IA T1 15 6 14 5 K_03 15 6 20 2 +
2 2 16 7 K_08 15 6 16 7 K_08
3 3 IB T2 17 8 16 7 17 8
4 4 17 8
5 5 Idfrst T3 Signal inputs 18 9 Signal inputs 26 8 K_04
6 6 18 9
Vin
18 9
Vin
27 9 +
U_01 U_01
X_3 X_3 X_3
19 1 19 1 1) 19 1
20 2 20 2 K_04 20 2 U_02
Vin Vin
21 3 U_02 21 3 21 3
22 4 22 4 1) 22 4 U_03
Vin Vin
U_03 23 5 K_05
23 5 24 6 23 5 U_04
Vin Vin
24 6 U_04 25 7 24 6
26 8 K_06 25 7 U_05
Vin
Power supply 27 9
25 7 + V 26 8 U_06
aux Vin
26 8 - U100 27 9
27 9 PE
4 4
5 5 4 4
U
6 6 K_02 5 5
#
7 7 6 6
8 8 0..20 mA U_08
9 9 K_03 7 7
8 8 K_02
X_2 9 9 valid
10 1
11 2 K_04 X_2
12 3 K_05 10 1
U
13 4 K_06 11 2
#
14 5 K_07 12 3
15 6 0..20 mA U_09
16 7 K_08
17 8
Signal and
Signal inputs measuring inputs
18 9 13 4
Vin Vin U_01
U_01 14 5
U
X_3 15 6
Vin _02
19 1 16 7
20 2 U_02 17 8
Vin Vin U_03
21 3
22 4 U_03 18 9
Vin Vin U_04
23 5 U_04 X_3
Vin
24 6 19 1
25 7 U_05 20 2
U
U_05
Vin 0..20 mA
21 3
#
26 8 U_06 22 4 U U_06
Vin
27 9 23 5 PT100
24 6 #
Control through the PC interface is also possible. This requires a suitable PC and
operating program (MiCOM S1).
Then there are seven keys with permanently assigned functions situated below the LCD
and six additional freely configurable function keys situated to the right of the LCD.
Furthermore the user interface (HMI) is fitted with 23 LED indicators, where 17 are
mounted vertically and situated on the left side of the LCD, and six are situated on the
right side of the six freely configurable function keys.
Additional information pertaining to function keys and their application can be found in
Chapter 3, section 'Configurable Function Keys (Function Group F_KEY)' and section
'Resetting Actions' and in this chapter, section 'Configurable Function Keys F1 to Fx
(general)'.
H4 TRIP H5
H3 ALARM H6
H2 OUT OF SERVICE H7
H1 HEALTHY H8
C = CLEAR
C H10
= READ G H11
= ENTER H12
H13
G
H14
H15
H16
64Z6000B_EN
6-1 View of the user interface (HMI) with positioning of the LED indicators
Display levels
All data relevant for operation and all device settings are displayed on two levels. At the
Panel level, data such as measurements are displayed in Panels that provide a quick
overview of the current state of the bay. The menu tree level below the panel level
allows the user to select all data points (settings, signals, measured variables, etc.) and
to change them, if appropriate. To access a selected event recording from either the
panel level or from any other point in the menu tree, press the READ key .
Display panels
The P438 can display 'Measured Value Panels' which are selected automatically by the
device according to system conditions.
Selected measured values are displayed on the Measured Value Panels. The system
condition determines which Panel is called up (examples are the Operation Panel and
the Fault Panel). Only the Measured Value Panels relevant for the particular design
version of the given device and its associated range of functions are actually available.
The Operation Panel is always provided.
Keys
/
G
‘Up’ and ‘Down’ Keys
Panel Level:
The ‘up’/‘down’ keys switch between the pages of the Measured Value Panel.
Menu Tree Level:
Press the ‘up’ and ‘down’ keys to navigate up and down through the menu tree in a
vertical direction. If the unit is in input mode, the ‘up’ and ‘down’ keys have a different
function.
Input mode:
Settings can only be changed in the input mode, which is signaled by the LED
indicator labeled EDIT MODE. Press the ‘up’ and ‘down’ keys in this mode to change
the setting value.
(‘Up’ key: the next higher value is selected.
‘Down’ key: the next lower value is selected.)
With list settings, press the ‘up’ and ‘down’ key to change the logic operator of the
value element.
ENTER Key
G
Panel Level:
Press the ENTER key at the Panel level to go to the menu tree.
Menu Tree Level:
Press the ENTER key to enter the input mode. Press the ENTER key a second time
to accept the changes as entered and exit the input mode. The LED indicator labeled
EDIT MODE signals that the input mode is active.
CLEAR Key C
Press the CLEAR key to reset the LED indicators and clear all measured event data.
The records in the recording memories are not affected by this action.
Input mode:
Press the CLEAR key to reject the changes entered and exit the input mode.
READ Key
Press the READ key to access a selected event recording from either the Panel level
or from any other point in the menu tree.
F1 F6
Function keys to
By pressing a function key the assigned function is triggered. More details on
assigning functions to function keys can be found in section "Configurable Function
Keys (Function Group F_KEY)". More details pertaining to the use of function keys
can be found in this chapter, section 'Configurable Function Keys F1 to Fx (general)'.
The following tables, which show the individual control steps, specify the displays that
can be changed by pressing specific keys. A small black square to the right of the
ENTER key indicates that the LED indicator labeled EDIT MODE is on. The examples
shown here do not necessarily apply to the device type described in this manual; they
merely serve to illustrate the control principles involved.
1 First press the ‘up’ key and hold it down C Voltage A-B prim.
G
+
20.7 kV
while pressing the CLEAR key. Voltage B-C prim.
20.6 kV
Note:
It is important to press the ‘up’ key first and
release it last in order to avoid unintentional
resetting of stored data.
Going from the panel level to
the menu tree level 0 Example of a Measured Value Panel. Voltage A-B prim.
20.7 kV
Voltage B-C prim.
20.6 kV
After the set "hold" time has elapsed (setting in menu tree: 'Set/Conf/HMI'), the display
will automatically switch to the Panel level if a Measured Value Panel has been
configured.
If none of the control keys is pressed, the display illumination will switch off once the set
"hold" time has elapsed (‘Backlight time’ setting in the menu tree at ‘Set/Conf/HMI’).
The backlight is turned on again by pressing one of the control keys. In this case, the
control action that is normally triggered by the key will not be executed. Reactivation of
the backlight is also possible using a binary input.
If continuous illumination is desired, the user can set the ‘Backlight time’ function to
Blocked.
The function keys F1 to Fx can each have a password assigned (see section 'Changing
the Password' in this chapter). If such is the case, they will only be enabled after the
respective password has been entered. The default setting (as of version -613) however
requires no password entry when pressing a function key.
It is assumed for the remainder of this section that the function key F1 is enabled only
after the password - as assigned at F _ K E Y : P a s s w o r d F u n c t . K e y 1 - has
been entered. After the password has been entered the function key will remain active
for the time period set at F _ K E Y : F c n K e y R e t u r n T i m e . Thereafter, the
function key is disabled until the password is entered again.
'Down' G
G
'Right' G
G
'Up' G
G
column on the right.
*
4 When function keys are pressed while the Fx Voltage A-B prim.
20.7 kV
return time period of the function key is Voltage B-C prim.
elapsing, then the configured function is carried 20.6 kV
out directly, e.g. without again checking for the
password.
(With the default setting this step is void as no
password is required and the function key is
available at all times.)
The measured values that will be displayed on the Measured Value Panels can first be
selected in the menu tree under Set/Conf/HMI. The user can select different sets of
measured values for the Operation Panel, the Overload Panel, the Ground Fault Panel,
and the Fault Panel. Only the Measured Value Panels relevant for the particular design
version of the given device and its associated range of functions are actually available.
The menu for the Operation Panel is always present. The remarks in "Setting a List
Setting" apply to this selection. If the M A I N : D i s a b l e d setting has been selected for
a given panel, then that panel is disabled.
The Measured Value Panels are called up according to system conditions. If, for
example, the device detects an overload or a ground fault, then the corresponding
Measured Value Panel will be displayed as long as the overload or ground fault situation
exists. If the device detects a fault, then the Fault Panel is displayed and remains active
until the measured fault values are reset, by pressing the CLEAR key, for example.
or 20.8 kV
been selected, they can be viewed one page at Current A prim.
a time by pressing the ‘up’ or ’down’ keys. The 415 A
device will also show the next page of the
Measured Value Panel after the set Panel
Hold-time (setting in menu tree:
"Set/Conf/HMI") has elapsed.
At the root of the menu tree is the unit type; the tree branches into the three main folders
‘Settings’, ‘Measurements & Tests’ and ‘Fault & Event Records’, which form the first
folder level. Up to two further folder levels follow so that the entire folder structure
consists of three main branches and a maximum of three folder levels.
At the end of each branch of folders are the various function groups in which the
individual data points (settings) are combined.
PX yyy
Unit
type
Oper/
Folder Cyclic measurements
level 2
Oper/Cycl/
Folder Meas. operating data
level 3
Oper/Cycl/Data/
Function MAIN
groups
Oper/Cycl/Data/MAIN
Data Date
points 01.01.99 dd.mm.yy
The display on the user interface (HMI) can be switched between address mode and
plain text mode. In the address mode the display shows settings, signals, and measured
values in numerically coded form, that is, as addresses. In plain text mode the settings,
signals, and measured values are displayed in the form of plain text descriptions.
In either case, control is guided by the menu tree. The active branch of the menu tree is
displayed in plain text in both modes. In the following examples, the display is shown in
plain text mode only.
Although it is possible to select any data point in the menu tree and read the associated
value by pressing the keys, it is not possible to switch directly to the input mode. This
safeguard prevents unintended changes in the settings.
This setup is designed to prevent accidental output and applies even when the global
change-enabling function has been activated. The following example is based on the
factory-set password. If the password has been changed by the user (see the section
entitled 'Changing the Password'), the following description will apply accordingly.
No
*
‘right’ G
M+T/C+Test/HMI
Setting Change enabl
G
No
*
‘up’ G
M+T/C+Test/HMI
Setting Change enabl
G
No
*
‘down’ G
M+T/C+Test/HMI
The display will change as shown in the Setting Change enabl
G
G
Yes
G
Setting Change enabl
indicator will go out. The unit is enabled for Yes
further setting changes.
The same procedure applies to any setting change unless the global change-enabling
function has been activated. This method is recommended for a single setting change
only. If several settings are to be changed, then the global change-enabling function is
preferable. In the following examples, the global change-enabling function has been
activated.
Automatic return
The automatic return function prevents the change-enabling function from remaining
activated after a change of settings has been completed. Once the set return time (menu
tree ‘Set/Conf/HMI’) has elapsed, the change-enabling function is automatically
deactivated, and the display switches to a Measured Value Panel corresponding to the
current system condition. The return time is restarted when any of the control keys is
pressed.
Forced return
The return described above can be forced from the user interface (HMI) by first pressing
the ‘up’ key and then holding it down while pressing the CLEAR key.
Note: It is important to press the ‘up’ key first and release it last in order to avoid
unintentional deletion of stored data.
Even when the change-enabling function is activated, not all settings can be changed.
For some settings it is also necessary to disable the protective function (menu tree:
Set/Func/Glob/MAIN, 'Protection Enabled'). Such settings include the configuration
settings, by means of which the device interfaces can be adapted to the system.
If all the conditions for a value change are satisfied (see above), the desired setting can
be entered.
G
50000 s
50000 s
50010 s
meantime the device will continue to operate
with the old value.
Using list settings, the user is able to select several elements from a list in order to
perform tasks such as defining a trip command or defining the measurements that will be
displayed on Measured Value Panels. As a rule, the selected elements are linked by an
‘OR’ operator. Other operators (NOT, OR, AND, NOT OR and NOT AND) are available
in the LOGIC function group for linking the selected list items. In this way binary signals
and binary input signals can be processed in a Boolean equation tailored to meet user
requirements. For the DNP 3.0 communication protocol, the user defines the class of a
setting instead of assigning operators. The definition of a trip command shall be used
here as an illustration.
OR #02 DIST
Trip signal Z2/t2L
#02 DIST
mode. Trip signal Z3/t3S
OR #02 DIST
only the ‘OR’ operator can be selected. There Trip signal Z3/t3S
is no limitation on the selection of classes.
G
Main-Trip 'OR' gate
will go out. The assignment has been made. OR #02 DIST
The unit will now operate with the new settings. Trip signal Z3/t3S
7 Press the ‘up’ key to exit the list at any point Set/Func/Glob/MAIN
G
G
8 If you wish to reject the new setting while C Set/Func/Glob/MAIN
Main-Trip 'OR' gate
you are still entering it (LED indicator labeled OR #02 DIST
EDIT MODE is on), press the CLEAR key. The Trip signal Z2/t2L
LED indicator labeled EDIT MODE will go out.
Memories can be read out after going to the corresponding entry point. This does not
necessitate activating the change-enabling function or even disabling the protective
functions. Inadvertent clearing of a memory at the entry point is not possible.
G
Enabled USER
No
G
Enabled USER
order. Once the end of the operating data Yes
memory has been reached, pressing the ‘left’
key again will have no effect.
G
Enabled USER
No
point.
1 Press the ‘down’ key to enter the monitoring Mon. Signal Record.
G
G
Checksum Sett Error
3 Press the ‘left’ key to display the previous Mon. Signal Record.
G
point.
OSCIL
memory. First, the fault number is shown. In
G
Event
this example it is the 22nd fault since the last 22
reset.
200 ms FT_DA
the measured fault data and then the binary G
Running Time
signals in chronological order. The time shown 0.17 s
in the second line is the time, measured from
the onset of the fault, at which the value was
measured or the binary signal started or G
Fault Recording 1
ended. 0 ms OSCIL
Record. in Progress
G
241 ms OSCIL
G
Record. in Progress
End
0 ms OSCIL
measured value or the previous signal.
G
Record. in Progress
Start
Fault Recording 1
fault memory to return to the entry point.
G
01.01.99 10:00:33
6.6.7 Resetting
All information memories – including the event memories and the monitoring signal
memory – as well as the LED indicators can be reset manually. In addition, the LED
indicators are automatically cleared and initialized at the onset of a new fault – provided
that the appropriate operating mode has been selected – so that they always indicate the
latest fault.
The LED indicators can also be reset manually by pressing the CLEAR key, which is
always possible in the standard control mode. This action also triggers an LED indicator
test and an LCD display test. The event memories are not affected by this action, so that
inadvertent deletion of the records associated with the reset signal pattern is reliably
prevented.
Because of the ring structure of the event memories, the data for eight consecutive
events are updated automatically so that manual resetting should not be necessary, in
principle.
However, in the event memories need to be cleared completely, as would be the case
after functional testing, then this can be done after selecting the appropriate parameter,
and in this case group resetting for several memories may also be configured. An
overview on all available resetting methods can be found in Chapter 3, section 'Resetting
Actions'.
The method for resetting a single memory from the front panel user interface is
described in the following with the example of a fault memory. In this example the global
change-enabling function has already been activated.
Reset Recording
setting to ‘Execute’.
G
10
Execute
Reset Recording
labeled EDIT MODE will go out. The value in 0
line 3 is reset to ‘0’.
Certain actions from the user interface (HMI) (such as a manual trip command for testing
purposes) can only be carried out by entering a password.
This setup is designed to prevent accidental output and applies even when the global
change-enabling function has been activated. The password consists of a pre-defined
sequential key combination entered within a specific time interval. If the password has
been changed by the user (see the section entitled 'Changing the Password'), the
following description will apply accordingly.
G
Man.M-trip cmd USER
appear in the fourth line of the display. Don't execute
********
Don't execute
*
‘right’ G
M+T/C+Test/MAIN
Man.M-trip cmd USER
G
Don't execute
*
‘up’ G
M+T/C+Test/MAIN
Man.M-trip cmd USER
G
Don't execute
*
‘down’ G
M+T/C+Test/MAIN
The display will change as shown in the Man.M-trip cmd USER
G
Execute
The password consists of a combination of keys that must be entered sequentially within
a specific time interval. The ‘left’, ’right’, ‘up’ and ‘down’ keys may be used to define the
password and represent the numbers 1, 2, 3 and 4, respectively:
3
G
1 G 2
The password can be changed by the user at any time. The procedure for this change is
described below. The starting point is the factory-set password.
G
Password
appear in the fourth line of the display. ********
********
Password
to enter the valid password. The display will
G
********
change as shown in the column on the right. *
Set/Conf/HMI
G
G Password
********
*
Set/Conf/HMI
G
Password
G
********
*
Set/Conf/HMI
G
Password
G
********
*
Password
example is done by pressing the UP key
G
*
followed by the DOWN key.
Set/Conf/HMI
G
Password
G
**
Password
G
**
*
Set/Conf/HMI
G
Password
G
**
**
G
Password
password has been re-entered correctly, the ********
LED indicator labeled EDIT MODE goes out
and the display appears as shown on the right.
The new password is now valid.
Operation from the user interface (HMI) without password protection is also possible.
To select this option, immediately press the ENTER key a second time in steps 4 and 6
without entering anything else. This will configure the user interface (HMI) without
password protection, and no control actions involving changes will be possible until the
global change-enabling function has been activated (see the section entitled ‘Change-
Enabling Function’).
If the configured password has been forgotten, it can be called up on the LCD display as
described below. The procedure involves turning the device off and then on again.
G
TEST
directional keys (‘left’, ‘right’, ‘up’ and ‘down’) at ˜˜˜˜˜˜˜˜
the same time and hold them down.
Password
startup, the password is displayed.
G
1234
˜˜˜˜˜˜˜˜˜˜˜˜˜˜˜˜
7 Settings
7.1 Parameters
The P438 must be adjusted to the system and to the protected equipment by appropriate
settings. This chapter gives instructions for determining the settings, which are located
in the folder entitled ‘Settings’ in the menu tree. The sequence in which the settings are
listed and described in this chapter corresponds to their sequence in the menu tree.
The default settings given in the Address List are activated after a cold restart.
The P438 is blocked in that case. All settings must be re-entered after a cold restart.
Note:
In the following tables (except for function group DVICE) the location of the
corresponding function description is indicated in the right hand side column.
"Figure: 3-xxx" refers to a logic diagram which displays the address, "Figure*: 3-xxx" to a
figure subtitle or figure report sheet, "Page: 3-xxx" to a page.
The device identification settings are used to record the ordering information and the
design version of the P438. They have no effect on the device's functions.
These settings should be changed only if the design version of the P438 is modified.
The description text of the settings can be changed by the "text replacement
tools" of the operating program and can be loaded into the device. These
user-specific data models obtain a setting which is defined by the setting of
the data model created by the user and displayed at this location. Standard
data models are marked with a ‘0’ (delivery condition).
DVICE: Language Version 002 123
Setting for the change level of the data model text. This display cannot be
altered.
DVICE: Serial Number 002 124
The Serial Number is the serial number of the device. This display cannot
be altered.
DVICE: AFS Order No. 001 000
Order number for the device. This number cannot be altered by the user.
DVICE: Order Ext. No. 1 000 003
Index letter specifying the version of the module inserted in the respective
slot.
DVICE: Variant of Module A 086 047
Network hardware MAC address for the Ethernet module. This read-only
address is assigned during production.
DVICE: Variant of Module L 086 048
The value Yes shows that the device is fitted with the integrated front panel
user interface (HMI).
The password to be used for changing settings from the user interface
(HMI) can be defined here. Further information on changing the password
is given in Chapter 6.
HMI: Fct. Reset Key 005 251 Fig. 3-69
Selecting such counters or protocols that are to be reset when the "CLEAR"
key (C) is pressed.
HMI: Fct. Read Key 080 110
Selection of the event log that will be displayed when the READ key is
pressed.
HMI: Fct. Menu Jmp List 1 030 238
Setting for the time period for which a panel is displayed before the unit
switches to the next panel. This setting is only relevant if more values are
selected than can be shown on the LC-Display.
HMI: Auto Return Time 003 014 Fig. 3-2
If the user does not press a key on the user interface (HMI) during this set
time period, the change-enabling function is deactivated.
HMI: Backlight Time 003 023
If the user does not press a key on the user interface (HMI) during this set
time period, then the backlighting of the LCD display is switched off.
Set the same parity that is set at the interface of the PC connected to the
P438.
PC: Spontan. Sig. Enable 003 187 Fig. 3-5
Enable for the cyclic transmission of measured values via the PC interface.
PC: Cycl. Data ILS Tel. 003 185 Fig. 3-5
The active power value is transmitted via the PC interface if it differs by the
set delta quantity from the last measured value transmitted.
PC: Delta f 003 057 Fig. 3-5
All measured values are transmitted again via the PC interface after this
time period has elapsed – provided that transmission has not been triggered
by the other delta conditions.
PC: Time-Out 003 188 Fig. 3-5
Setting for the time that will elapse after the last telegram traffic via the PC
interface before the second communication channel of communication
module A is activated.
Interface
Cancelling function group COMM1 or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
COMM1: General Enable USER 003 170 Fig. 3-7,
3-12
Enabling/disabling communication interface 1.
COMM1: IEC870-5 Enabled 003 215 Fig. 3-6
Enabling additional settings that are relevant for the protocol based on
IEC 870-5-101.
COMM1: Addit. ILS Enable 003 217 Fig. 3-6
Enabling additional settings that are relevant for the ILS protocol.
COMM1: MODBUS Enable 003 220 Fig. 3-6
Enabling settings that are relevant for the DNP 3.0 protocol.
COMM1: COURIER Enable 103 040 Fig. 3-6
The user may select either the Private or the Compatible variant of the
MODBUS protocol.
Note:
This setting is hidden unless the MODBUS protocol is enabled.
The Compatible variant corresponds to the MODBUS implementation of
MiCOM Px20 and Px40 devices. The Private variant corresponds to the
first implementation of the MODBUS protocol.
In the DNP 3.0 protocol, a 16-bit address is used to identify devices. The
address that can be set here is the higher-order octet, whereas the address
set at C O M M 1 : O c t e t C o m m . A d d r e s s is the lower-order octet of
the DNP address.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Test Monitor On 003 166 Fig. 3-7,
3-8, 3-9,
3-10, 3-11,
3-12
Setting specifying whether data shall be recorded for service activities.
Setting for the length of the common address for identification of telegram
structures.
Note:
This setting is hidden unless the IEC 870-5-101 protocol is enabled.
"ASDU": Application Service Data Unit
COMM1: Octet 2 Addr. ASDU 003 194 Fig. 3-8
Setting for the length of the common higher-order address for identification
of telegram structures.
Note:
This setting is hidden unless the IEC 870-5-101 protocol is enabled.
"ASDU": Application Service Data Unit
COMM1: Addr. Length Inf.Obj 003 196 Fig. 3-8
Setting for the length of the higher-order address for information objects.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
COMM1: Inf.No.<->Funct.Type 003 195 Fig. 3-8
Setting for the transmission direction. Normally this value will be set to ' 1 '
at the control center and to ' 0 ' at the substation.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
Setting for the maximum time that will elapse until the status signal for the
acknowledgment command is issued.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
COMM1: Reg.Asg. Selec. Cmds 003 210 Fig. 3-10
Number of bits that must pass between the receipt of the 'request' and the
start of sending the 'response'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Number of bits that may be missing from the telegram before receipt is
terminated.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Link Confirm. Mode 003 243 Fig. 3-11
Setting the time period within which the master must acknowledge at the
link layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Link Max. Retries 003 245 Fig. 3-11
Number of repetitions that are carried out on the link layer if errors have
occurred during transmission (such as failure to acknowledge).
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Appl Confirm.Timeout 003 246 Fig. 3-11
Setting the time period within which the master must acknowledge at the
application layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Appl Need Time Del. 003 247 Fig. 3-11
Time interval within which the slave requests time synchronization cyclically
from the master.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./Cl. Bin. Inputs 003 232 Fig. 3-11
Selection of data points and data classes for object 1 – binary inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./Cl. Bin.Outputs 003 233 Fig. 3-11
Selection of data points and data classes for object 10 – binary outputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Selection of data points and data classes for object 30 – analog inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./Cl. Analog Outp 003 236 Fig. 3-11
Selection of data points and data classes for object 40 – analog outputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ph-Ph Meas V.(DNP3) 003 250 Fig. 3-11
Selecting the commands that can be issued via the COURIER protocol.
Note: This setting is hidden unless the COURIER protocol is enabled.
COMM1: Signal Selection 103 043 Fig. 3-12
Selecting the signals that can be transmitted via the COURIER protocol.
Note: This setting is hidden unless the COURIER protocol is enabled.
COMM1: Meas. Val. Selection 103 044 Fig. 3-12
Selecting the measured values that can be transmitted via the COURIER
protocol.
Note: This setting is hidden unless the COURIER protocol is enabled.
COMM1: Parameter Selection 103 045 Fig. 3-12
Selecting the settings that can be changed via the COURIER protocol.
Note: This setting is hidden unless the COURIER protocol is enabled.
COMM1: Delta t (COURIER) 103 046 Fig. 3-12
A selected measured value is re-transmitted after this cycle time period has
elapsed.
Note: This setting is hidden unless the COURIER protocol is enabled.
Setting the same parity that is set at the interface of the control system
connected to the P438.
COMM2: Dead Time Monitoring 103 176 Fig. 3-14
The time between two polling calls from the communication master must be
less than the time set here.
COMM2: Positive Ackn. Fault 103 203
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
COMM2: Manufacturer 103 161 Fig. 3-14
Setting for the name of the manufacturer. This setting can be changed to
any free text to ensure compatibility. The default value is SE. However, it
can be necessary in special cases to set the value to something different.
Note:
This parameter can be changed to any text of max. 8 characters length.
Any longer text entered is truncated to 8 characters internally.
However, changes can be carried out only via the operating program, not
using the integrated local control panel.
COMM2: Octet Address ASDU 103 073 Fig. 3-14
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
All measured values are transmitted again via the communication interface
after this time period has elapsed – provided that transmission has not been
triggered by the other delta conditions.
Adjustment of the baud rate for telegram transmission via the teleprotection
interface (InterMiCOM interface) so as to meet the requirements of the
transmission carrier.
COMM3: Source Address 120 031
Name of the device (IED has server function). This device name serves as
device identification in the IEC 61850 system, it is included in the Logical
Device Name in the IEC data model and must therefore be unambiguous.
All devices logged-on to the network should have non-recurring IED names.
The subnet mask defines which part of the IP address is addressed by the
sub-network and which part by the device that is logged-on to the network.
Note:
The complete IP address is shown in the S&R-103 operating program at
I E C : S u b n e t M a s k . The device’s front panel display only shows the IP
address distributed to these four data model addresses
IEC: Gateway Address 104 011
Device (IED) poll cycle time for time synchronization when the operating
mode is set to Request from Server.
IEC: SNTP Server 1 IP 104 202
Time difference between UTC and local time at the devices' substation
(IED).
IEC: Diff. Dayl.Sav. Time 104 207
These three parameters define the date (e.g. at what day of the year) for
switching from standard time over to daylight saving time. Available for
I E C : D a y l . S a v . T i m e S t a r t are the values "first", "second", "third",
"fourth", and "last"; for I E C : D a y l . S a v . T i m e S t . d the seven
weekdays are available so that for example a setting like "on the last
Sunday in March" may be used.
IEC: Dayl.Sav.t.St.0:00 + 104 223
This defines the time difference and the time of day (on the specific
changeover day) when the clock is to be switched to daylight saving time.
The time is given in the number of minutes after midnight, e.g. when the
clock changeover to 3:00 AM always occurs at 2:00 AM, then the value to
be entered at I E C : D a y l . S a v . t . S t . 0 : 0 0 + is 120 [minutes] and at
I E C : D i f f . D a y l . S a v . T i m e it is 60 [minutes].
IEC: Dayl.Sav.Time End 104 225
This parameter defines the date and time of day for the clock changeover
from daylight saving time to standard time. The setting is similar to that for
the clock changeover to daylight saving time.
IEC: Update Measurements 104 229
Setting to calculate the filter value for all IP Report Control Blocks (RCB).
Should a change occur in one of the IP measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • setting I E C : D e a d B a n d I P
Setting to calculate the filter value for all IN Report Control Blocks (RCB).
Should a change occur in one of the IN measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • setting I E C : D e a d B a n d I N
IEC: Dead Band VPP 104 232
Setting to calculate the filter value for all VPP Report Control Blocks (RCB).
Should a change occur in one of the VPP measured values, which is
greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • setting I E C : D e a d B a n d V P P
IEC: Dead Band VPG 104 233
Setting to calculate the filter value for all VPG Report Control Blocks (RCB).
Should a change occur in one of the VPG measured values, which is
greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • setting I E C : Dead Band VPG
IEC: Dead Band f 104 234
Setting to calculate the filter value for all f Report Control Blocks (RCB).
Should a change occur in one of the f measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • setting I E C : D e a d B a n d f
IEC: Dead Band P 104 235
Setting to calculate the filter value for all P Report Control Blocks (RCB).
Should a change occur in one of the P measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • setting I E C : D e a d B a n d P
IEC: Dead Band Phi 104 236
Setting to calculate the filter value for all ϕ Report Control Blocks (RCB).
Should a change occur in one of the ϕ measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • setting I E C : D e a d B a n d P h i
IEC: Dead Band Z 104 237
Setting to calculate the filter value for all Z Report Control Blocks (RCB).
Should a change occur in one of the Z measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • setting I E C : D e a d B a n d Z
IEC: Dead Band Min/Max 104 238
Setting to calculate the filter value for all min/max Report Control Blocks
(RCB). Should a change occur in one of the min/max measured values,
which is greater than the filter value, the RCB is again sent to all clients.
The filter value for each measured value is calculated according to this
formula:
step size measured value • setting I E C : D e a d B a n d M i n / M a x
Setting to calculate the filter value for all ASC Report Control Blocks (RCB).
Should a change occur in one of the ASC measured values, which is
greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • setting I E C : D e a d B a n d A S C
IEC: Dead Band Temp. 104 240
Setting to calculate the filter value for all temperature Report Control Blocks
(RCB). Should a change occur in one of the temperature measured values,
which is greater than the filter value, the RCB is again sent to all clients.
The filter value for each measured value is calculated according to this
formula:
step size measured value • setting I E C : D e a d B a n d T e m p .
IEC: Dead Band 20ma 104 241
Setting to calculate the filter value for all 20mA Report Control Blocks
(RCB). Should a change occur in one of the 20mA measured values, which
is greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • setting I E C : D e a d B a n d 2 0 m A
IEC: Update Cycle Energy 104 060
Cycle time to send energy value by Report Control Block (RCB). No RCB
transmission with setting to Blocked!
Goose ID being sent by this device (IED). GOOSE includes a Dataset with
32 binary and configurable virtual outputs and 10 two-pole states to the
maximum of 10 monitored external devices
VLAN identifier of GOOSE being sent by this device (IED). The VLAN
identifier makes it possible to have switches in the network filter messages,
if the switches support such a function. Because so-called multicast MAC
addresses are applied, switches are unable to filter messages in the
network if they do not include a VLAN identifier.
GOOSE: VLAN Priority 106 007 Fig. 3-18
VLAN priority of the GOOSE which is transmitted from this device (IED).
GOOSE: DataSet Reference 106 008 Fig. 3-18
Goose ID for GOOSE, which is to be received by this device (IED) for the
virtual binary GOOSE input.
Default for the virtual binary GOOSE input. The state of a virtual two-pole
GOOSE input will revert to default as soon as the continuously monitored
communication link to a GOOSE sending device (IED situated on the
opposite side) is in fault or has disappeared altogether.
Substation Event
Cancelling function group GSSC or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting. The
parameters of this function group are active only if function group IEC has
been configured and is active, and if the parameters of this function group
have been activated through the I E C : E n a b l e C o n f i g u r a t i o n
parameter or by switching the device off-line/on-line.
GSSE: General Enable USER 104 049
Minimum value for the GSSE repetition cycle time in ms. The repetition
cycle time for a GSSE message is calculated, according to a standard, with
this formula:
Repetition cycle time = Min. cycle + (1 + (increment/1000))N-1 [ms]
The repetitions counter N will be restarted at count 1 after each state
change of a GSSE bit pair.
GSSE: Max. Cycle 104 053
Maximum value, in seconds, for the GSSE repetition cycle time period.
See Min. Cycle for the formula to calculate the GSSE repetition cycle time
period. Should the calculated value for the repetition cycle time be equal to
or greater than the set maximum value then the GSSE message will be sent
repeatedly at the set maximum value time.
GSSE: Increment 104 054
Increment for the GSSE repetition cycle. For the formula to calculate the
repetition cycle time see Min. Cycle.
Setting with which GSSE bit pair the configured binary signal of the virtual
GSSE outputs is to be transmitted. A GSSE is always transmitted
consisting of a fixed number of 96 bit pairs, of which a maximum of 32 are
used by this device (IED) during a send operation.
GSSE: Output 1 Fct.Assig. 104 102
Setting which GSSE bit pair is assigned to which virtual GSSE input.
A GSSE message is always received, consisting of a fixed number of 96 bit
pairs of which a maximum of 32 are processed by this device (IED).
GSSE: Input 1 IED name 105 002
IED name for the virtual GSSE input used to identify a GSSE received.
GSSE: Input 1 Default 105 003
Default for the virtual binary GSSE input. The state of a virtual two-pole
GSSE input will revert to default as soon as the continuously monitored
communication link to a GSSE sending device (IED situated on the opposite
side) is in fault or has disappeared altogether.
GSSE: Input 1 Fct.Assig. 105 004
After the password has been entered the function keys will remain active for
the time period set. When this set time period has elapsed the password
must again be entered.
Binary Inputs
The P438 has optocoupler inputs for processing binary signals from the system. The
number and connection schemes for the available binary inputs are shown in the
terminal connection diagrams.
The P438 identifies the fitted modules during startup. If a given binary I/O module is not
fitted or has fewer binary signal inputs than the maximum number possible at this slot,
then the configuration addresses for the missing binary signal inputs are automatically
hidden in the menu tree.
When configuring binary signal inputs, one should keep in mind that the same function
can be assigned to several signal inputs. Thus one function can be activated from
several control points having different signal voltages.
In order to ensure that the device will recognize the input signals, the triggering signals
must persist for at least 30 ms.
The operating mode for each binary signal input can be defined. The user can specify
whether the presence (active 'high' mode) or absence (active 'low' mode) of a voltage
shall be interpreted as the logic ‘ 1 ’ signal.
Input filter which is activated when either the mode 'Active "High", Filt.' or
'Active "Low", Filt.' has been selected. In order to suppress transient
interference peaks at the logic signal inputs it is suggested to set this
parameter to 6 [steps]. For additional information see Chapter 3.
INP: Fct. U 301 Assign 152 217 Fig. 3-21,
3-31
INP: Fct. U 302 Assign 152 220
Setting the minimum current that must flow in order for the P438 to display a
measured value > 0 (zero suppression).
RTDmA: IDC< Open Circuit 037 191 Fig. 3-25
If the input current falls below the set threshold, the P438 will issue an ‘open
circuit’ signal.
RTDmA: IDC 1 037 150 Fig. 3-25
Setting for the input current that will correspond to a linearized value that
has been set accordingly.
Setting for the linearized current that will correspond to an input current that
has been set accordingly.
RTDmA: Scaled Val. IDC,lin1 037 192 Fig. 3-26
Binary Outputs
The P438 has output relays for the output of binary signals. The number of available
output relays and their connection schemes are shown in the terminal connection
diagrams.
The P438 identifies the fitted modules during startup. If a given binary I/O module is not
fitted or has fewer binary output relays than the maximum number possible at this slot,
then the configuration addresses for the missing binary output relays are automatically
hidden in the menu tree.
The contact data of the relay used permit the use as command relay and as signal relay.
For multiply contacts, a signal can be assigned to several output relays simultaneously.
An operating mode can be defined for every output relay. Depending on the set
operating mode, the output relay is in closed circuit operation or in open circuit operation,
latching or not. The setting of the operating mode defines when the latch will be
cancelled for latched output relays.
Setting the time period for transmission of the selected measured value in
BCD form.
mA_OP: Scale BCD 016 082 Fig. 3-33
Scaling factor setting for the measured value to be transmitted in BCD form.
The scaling factor is calculated according to the following formula:
M
Scaling factor = x,max
M x,scal
where:
M x,scal : scaled measured value
Mx,max maximum transmitted value for the selected measured value
mA_OP: Function A-1 Assign 053 000 Fig. 3-35
mA_OP: Function A-2 Assign 053 001
Setting the time period for output of the selected measured value.
mA_OP: Scaled Min. Val. A-1 037 104 Fig. 3-35
Setting for the minimum scaled measured value to be output. The value to
be set is calculated according to the following equation:
M x,min
M x,scal,min =
M x,RL
where:
Mx,min : minimum transmitted value
for the selected measured value
M x,RL : range limit of the selected measured value
Setting for the scaled measured value for output that defines the knee point
of the characteristic. The value to be set is calculated according to the
following equation:
M x,knee
M x,scal,knee =
M x,RL
where:
M x,knee : knee point value to be transmitted for selected measured
value
M x,RL : range limit of the selected measured value
mA_OP: Scaled Max. Val. A-1 037 106 Fig. 3-35
Measurands Range
Measurands of the
variable Mx Mx, RL1 ... Mx, RL2
Associated scaled measurands 0 ... 1
Setting for the output current that is output for measured values smaller
than or equal to the minimum measured value setting.
mA_OP: AnOut Knee Point A-1 037 108 Fig. 3-35
Setting for the output current that is output if the measured value is on the
knee point of the characteristic.
mA_OP: AnOut Max. Val. A-1 037 109 Fig. 3-35
mA_OP: AnOut Max. Val. A-2 037 115
with:
Mx,min ... Mx,max : measured values to be issued
mA_OP: Output Value 1 037 120 Fig. 3-35
LED Indicators
The P438 has a total of 23 LED indicators to simultaneously display binary signals. LED
indicator H 1 is not configurable. It indicates the working readiness of the device (supply
voltage exists). LED indicators H 2 and H 3 are also not configurable. H 2 is labeled
"OUT OF SERVICE" and signals a blocking or malfunction; H 3 is labeled "ALARM" and
signals a warning alarm. LED indicator H 17 signals that the device is in the "EDIT
MODE".
The layout of the LED indicators and the factory setting for LED indicator H 4 can be
seen in section 6.1. At this point it is specifically emphasized that there is no permanent
association given between the freely configurable function keys and the LED indicators
H 18 to H 23 situated directly next to these function keys.
An operating mode can be defined for each LED indicator. Depending on the set
operating mode, the LED indicator in either energize-on-signal (ES) mode ('open-circuit
principle') or normally-energized (NE) mode ('closed-circuit principle') and in either
latching or non-latching mode, flashing or not flashing.
For LED indicators operating in latching mode, the operating mode setting also
determines when latching will be cancelled.
With the multi-color LED indicators (H 4 to H 16, H 18 to H 23) the red and green colors
can be independently assigned to functions. The third color, amber, is a combination of
red and green, i.e. when both functions assigned to the LED indicator are simultaneously
present.
Selecting the primary source for date and time synchronization. Available
are: COMM1, COMM2/PC, IRIG-B or a binary input for minute signal
pulses.
MAIN: BackupSourceTimeSync 103 211
Selecting the back-up source for date and time synchronization. Available
are: COMM1, COMM2/PC, IRIG-B or a binary input for minute signal
pulses. The back-up source will become active when the time delay set at
M A I N : T i m e S y n c . T i m e - O u t has elapsed and no synchronization
by the primary source has occurred.
MAIN: Time Sync. Time-Out 103 212
The user specifies the channel for which disturbance waveforms are
recorded.
Cancelling Protection
Functions
The degree of protection may be adapted to meet the requirements of a specific high-
voltage system by configuring the available function range.
The following conditions must be met before a protection function can be cancelled:
Protection
Cancelling function group BUOC or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
Protection
Cancelling function group DTOC or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
Protection
Cancelling function group IDMT or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
Protection
Cancelling function group CBF or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
7.1.3.1 Global
This prevents any settings or commands from being sent to the relay from
the PC interface.
PC: Sig/Meas. Val.Block 003 086 Fig. 3-5
Rear Port Communications COMM1: USER Command Block 003 172 Fig. 3-6
Interface 1
This prevents any settings or commands from being sent to the relay from
the COMM1 interface.
COMM1: USER Sig/Meas Block 003 076 Fig. 3-7,3-
8,3-9
When signal and measured value blocking user is activated, no signals or
measured data are transmitted through communication interface COMM1.
Rear Port Communications COMM2: USER Command Block 103 172 Fig. 3-14
Interface 2
This prevents any settings or commands from being sent to the relay from
the COMM2 interface.
COMM2: USER Sig/Meas Block 103 076 Fig. 3-14
Binary Output OUTP: USER Outp Rel Block 021 014 Fig. 3-28
Switching the device off-line or on-line. Some settings can be changed only
when the device is off-line (i.e. set to 'No (Disabled)').
MAIN: USER Test Mode 003 012 Fig. 3-71
When the test mode user is activated, signals or measured data for PC and
communication interfaces are labeled 'test mode'.
MAIN: Frequency fn 010 030 Fig. 3-44,
3-46, 3-47
Setting for the nominal frequency of the protected system.
MAIN: In C.T. Prim. 010 001 Fig. 3-41,
3-42, 3-188
Setting for the primary nominal current of the main current transformers for
measurement of phase currents.
MAIN: Idfrst,nom C.T. Prim 010 016 Fig. 3-170
Setting for the primary nominal current of the main current transformer for
measurement of defrost current.
Setting for the primary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.
MAIN: In Device 010 003 Fig. 3-38,
3-39, 3-40
Setting for the secondary nominal current of the line CT for measurement of
phase currents. This also corresponds to the nominal device current.
MAIN: Idfrst,nom Device 010 017 Fig. 3-40
Setting for the minimum voltage that must be exceeded so that measured
operating values of the phase-to-ground voltages, phase-to-phase voltages,
and, if applicable, derived voltages are displayed.
MAIN: Fct.Assign. Reset 1 005 248 Fig. 3-69
Setting Group Selection GROUP: Control via USER 003 100 Fig. 3-72
If setting group selection is to be handled from the HMI panel rather than via
the binary signal inputs, set to ‘Yes’.
GROUP: Setting Grp Sel USER 003 060 Fig. 3-72
Selection of the setting group from the local control HMI panel.
GROUP: Hold Timer 003 063 Fig. 3-72
The setting of this timer stage is relevant only if setting group selection is
carried out via the binary signal inputs. Any voltage-free pause that may
occur during selection is bridged. If, after this time period has elapsed, no
binary signal input has yet been set, then the setting group selected from
the user interface (HMI) shall apply.
Selection of the signals whose appearance shall result in the signals ‘Alarm
(LED)’ and ‘Alarm (relay) and in the activation of the LED indicator labeled
‘ALARM’. Signals caused by faulty hardware and leading to blocking of the
device are not configurable. They always result in the above signals and
indication.
CHECK: Mon. Sig. Retention 021 018 Page: 3-107
This setting defines the signals that will trigger disturbance recording.
OSCIL: I> 016 013 Fig. 3-88
This setting defines the threshold value of the phase current that will trigger
disturbance recording.
OSCIL: Pre-Fault Time 003 078 Fig. 3-90
Setting for the time during which data will be recorded before the onset of a
fault (pre-fault recording time).
OSCIL: Post-Fault Time 003 079 Fig. 3-90
Setting for the time during which data will be recorded after the end of a
fault (post-fault recording time).
OSCIL: Max Record Time 003 075 Fig. 3-90
Setting for the maximum recording time per fault. This includes pre-fault
and post-fault recording times.
Distance Protection DIST: General Enable USER 031 073 Fig. 3-91
Making the 3rd and 4th distance protection zones "visible", i.e. available.
DIST: WPC Zone Available 022 002 Fig. 3-111
Making the setting parameters for wrong phase coupling "visible", i.e.
available.
DIST: Control via USER 022 008 Fig. 3-99
VT and CT Supervision C&VTS: General Enable USER 014 001 Fig. 3-122
Backup Overcurrent-Time BUOC: General Enable USER 014 011 Fig. 3-127
Protection
Enabling/disabling BUOC protection.
Switch on to Fault Protection SOTF: General Enable USER 011 068 Fig. 3-130
Auto-Reclose Control RECLS: General Enable USER 015 060 Fig. 3-132
Definite-Time Overcurrent DTOC: General Enable USER 031 068 Fig. 3-150
Protection
Enabling/disabling the definite-time overcurrent protection function.
DTOC: Direction Measurem. 031 131
Inverse-Time Overcurrent IDMT: General Enable USER 017 096 Fig. 3-157
Protection
Enabling/disabling the inverse-time overcurrent protection function.
IDMT: Direction Measurem. 017 109
Defrost Protection DFRST: General Enable USER 019 096 Fig. 3-168
Thermal Overload Protection THERM: General Enable USER 022 050 Fig. 3-171
Setting for the number of parallel lines via the user interface (HMI).
THERM: No. of Parall. Lines 022 069
Time-Delayed Voltage V<>: General Enable USER 023 030 Fig. 3-178
Protection
Enabling/disabling time-delayed voltage protection.
Circuit Breaker Failure CBF: General Enable USER 022 100 Fig. 3-181
Protection
Enabling/disabling circuit breaker failure protection.
Circuit Breaker Monitoring CBM: General Enable USER 022 010 Fig. 3-184
Setting for start criteria for circuit breaker condition monitoring. Set to ’With
Trip Cmd. Only’ in order to view all trip signals issued by the catenary
protection device. Set to ‘CB Sig. EXT or Trip’ and use a CB auxiliary
contact to obtain the additional view of trip signals issued because of
excessive catenary overloading.
CBM: Inom,CB 022 012 Fig. 3-188
Setting for the warning stage threshold for the number of remaining CB
operations at CB nominal current.
CBM: ΣItrip> 022 022 Page: 3-265
Setting for the warning stage threshold for the accumulated ruptured current
values.
CBM: ΣItrip**2> 022 081 Page: 3-265
Setting for the warning stage threshold for the second power of the
accumulated ruptured current values.
CBM: ΣI*t> 022 096 Page: 3-265
Setting for the warning stage threshold for the sum of the current-time
integral of the ruptured currents.
CBM: Corr. Acqu.t. Trip 022 153 Fig. 3-186
Correction of the delay period between the forming of the device internal trip
command and the actual opening of the CB contacts.
CBM: Corr. Acqu.t.CB Sig. 022 018 Fig. 3-186
Limit Value Monitoring LIMIT: General Enable USER 014 010 Fig. 3-192
Setting for operate threshold IDC,lin> for monitoring the linearized direct
current.
LIMIT: IDC,lin>> 014 111 Fig. 3-199
Setting for operate threshold IDC,lin>> for monitoring the linearized direct
current.
LIMIT: tIDC,lin> 014 112 Fig. 3-199
Setting for operate threshold IDC,lin< for monitoring the linearized direct
current.
LIMIT: IDC,lin<< 014 115 Fig. 3-199
Setting for operate threshold IDC,lin<< for monitoring the linearized direct
current.
LIMIT: tIDC,lin< 014 116 Fig. 3-199
These settings define the static input conditions for the logic function.
LOGIC: Fct.Assignm. Outp. 1 030 000 Fig. 3-202
LOGIC: Fct.Assignm. Outp. 2 030 004 Fig. 3-141
LOGIC: Fct.Assignm. Outp. 3 030 008
These settings define the operating modes for the output timer stages.
LOGIC: Time t1 Output 1 030 002 Fig. 3-202
LOGIC: Time t1 Output 2 030 006
These settings assign the function of a binary input signal to the output of
the logic equation.
These settings assign the function of a binary input signal to the output of
the logic equation.
Main Function MAIN: Inr. I(2fn)/I(fn)SGx 017 098 001 091 001 092 001 093 Fig. 3-49,
3-50
Setting for the operate threshold of inrush stabilization.
MAIN: I> Enab.Inr.Rest.SGx 017 058 017 113 017 254 017 255 Fig. 3-50
MAIN: I> Lift Inr.Rstr.SGx 017 095 001 085 001 086 001 087 Fig. 3-50
A maximum hold time for inrush stabilization can be set using this
parameter.
MAIN: Fct.Inrush Rstr. SGx 017 093 017 064 017 082 017 083 Fig. 3-51
Fault Data Acquisition FT_DA: Line Length 1 SGx 010 005 010 006 010 007 010 008 Fig. 3-86
FT_DA: Line Length 7 SGx 008 135 008 136 008 137 008 138
This setting defines the length - in km - of line section 10, on which the
calculation of fault location is based. (If less than ten line sections are to be
used for calculation then this parameter must be set to 'Blocked'.)
FT_DA: Line ReactXSec 1 SGx 010 012 010 013 010 014 010 015 Fig. 3-86
This setting defines line reactance X1, on which the calculation of fault
location is based. (A maximum of 10 line sections may be defined; line
distance and line reactance for line sections not needed are to be set to
'Blocked'.)
FT_DA: Line ReactXSec 2 SGx 008 151 008 152 008 153 008 154
This setting defines line reactance X2, on which the calculation of fault
location for the second line section is based. (If only one line section is to
be used for calculations then this parameter must be set to 'Blocked'.)
FT_DA: Line ReactXSec 3 SGx 008 155 008 156 008 157 008 158
This setting defines line reactance X3, on which the calculation of fault
location for the third line section is based. (If less than three line sections
are to be used for calculations then this parameter must be set to 'Blocked'.)
FT_DA: Line ReactXSec 4 SGx 008 159 008 164 008 165 008 166
This setting defines line reactance X4, on which the calculation of fault
location for the fourth line section is based. (If less than four line sections
are to be used for calculation then this parameter must be set to 'Blocked'.)
FT_DA: Line ReactXSec 5 SGx 008 167 008 168 008 169 008 170
This setting defines line reactance X5, on which the calculation of fault
location for the fifth line section is based. (If less than five line sections are
to be used for calculation then this parameter must be set to 'Blocked'.)
FT_DA: Line ReactXSec 6 SGx 008 171 008 172 008 173 008 174
This setting defines line reactance X6, on which the calculation of fault
location for the sixth line section is based. (If less than six line sections are
to be used for calculation then this parameter must be set to 'Blocked'.)
FT_DA: Line ReactXSec 7 SGx 008 175 008 176 008 177 008 178
This setting defines line reactance X7, on which the calculation of fault
location for the seventh line section is based. (If less than seven line
sections are to be used for calculation then this parameter must be set to
'Blocked'.)
FT_DA: Line ReactXSec 8 SGx 008 179 008 180 008 181 008 182
This setting defines line reactance X8, on which the calculation of fault
location for the eighth line section is based. (If less than eight line sections
are to be used for calculation then this parameter must be set to 'Blocked'.)
FT_DA: Line ReactXSec 9 SGx 008 183 008 184 008 185 008 186
This setting defines line reactance X9, on which the calculation of fault
location for the ninth line section is based. (If less than nine line sections
are to be used for calculation then this parameter must be set to 'Blocked'.)
FT_DA: Line ReactXSec10 SGx 008 187 008 188 008 189 008 190
This setting defines line reactance X10, on which the calculation of fault
location for the tenth line section is based. (If less than ten line sections are
to be used for calculation then this parameter must be set to 'Blocked'.)
FT_DA: Outp. Fault Loc. SGx 010 032 010 033 010 034 010 035 Fig. 3-82
Setting for the conditions under which fault location output occurs.
Distance Protection DIST: Enable SGx 072 200 073 200 074 200 075 200 Fig. 3-91
DIST: Z4 Forward Reach SGx 080 015 081 015 082 015 083 015
DIST: Z1 Reverse Reach SGx 076 100 077 100 078 100 079 100 Fig. 3-101,
3-104
DIST: Z2 Reverse Reach SGx 076 101 077 101 078 101 079 101 Fig. 3-102,
3-105
DIST: Z3 Reverse Reach SGx 076 102 077 102 078 102 079 102
DIST: Z4 Reverse Reach SGx 080 017 081 017 082 017 083 017
DIST: Z1' Dynamic Fwd SGx 076 096 077 096 078 096 079 096 Fig. 3-101,
3-104
DIST: Z2' Dynamic Fwd SGx 076 097 077 097 078 097 079 097 Fig. 3-102,
3-105
DIST: Z3' Dynamic Fwd SGx 076 098 077 098 078 098 079 098
DIST: Z4' Dynamic Fwd SGx 080 016 081 016 082 016 083 016
DIST: Z1' Dynamic Rev SGx 076 103 077 103 078 103 079 103 Fig. 3-101,
3-104
DIST: Z2' Dynamic Rev SGx 076 104 077 104 078 104 079 104 Fig. 3-102,
3-105
DIST: Z3' Dynamic Rev SGx 076 105 077 105 078 105 079 105
DIST: Z4' Dynamic Rev SGx 080 018 081 018 082 018 083 018
DIST: R4,Fwd.Res.(Poly)SGx 080 019 081 019 082 019 083 019
DIST: R1,Rev.Res.(Poly)SGx 076 121 077 121 078 121 079 121 Fig. 3-104
DIST: R2,Rev.Res.(Poly)SGx 076 122 077 122 078 122 079 122 Fig. 3-105
DIST: R3,Rev.Res.(Poly)SGx 076 123 077 123 078 123 079 123
DIST: R4,Rev.Res.(Poly)SGx 080 021 081 021 082 021 083 021
DIST: R1',Dyn.Fwd(Poly)SGx 076 118 077 118 078 118 079 118 Fig. 3-104
DIST: R2',Dyn.Fwd(Poly)SGx 076 119 077 119 078 119 079 119 Fig. 3-105
DIST: R3',Dyn.Fwd(Poly)SGx 076 120 077 120 078 120 079 120
DIST: R4',Dyn.Fwd(Poly)SGx 080 020 081 020 082 020 083 020
DIST: R1',Dyn.Rev(Poly)SGx 076 124 077 124 078 124 079 124 Fig. 3-104
DIST: R2',Dyn.Rev(Poly)SGx 076 125 077 125 078 125 079 125 Fig. 3-105
DIST: R3',Dyn.Rev(Poly)SGx 076 126 077 126 078 126 079 126
DIST: R4',Dyn.Rev(Poly)SGx 080 022 081 022 082 022 083 022
DIST: Rg4, Forward SGx 080 023 081 023 082 023 083 023
DIST: Rg1, Reverse SGx 076 144 077 144 078 144 079 144 Fig. 3-101,
3-104
DIST: Rg2, Reverse SGx 076 145 077 145 078 145 079 145 Fig. 3-102,
3-105
DIST: Rg3, Reverse SGx 076 146 077 146 078 146 079 146
DIST: Rg4, Reverse SGx 080 025 081 025 082 025 083 025
DIST: Rg1', Forward SGx 076 141 077 141 078 141 079 141 Fig. 3-101,
3-104
DIST: Rg2', Forward SGx 076 142 077 142 078 142 079 142 Fig. 3-102,
3-105
DIST: Rg3', Forward SGx 076 143 077 143 078 143 079 143
DIST: Rg4', Forward SGx 080 024 081 024 082 024 083 024
DIST: Rg1', Reverse SGx 076 147 077 147 078 147 079 147 Fig. 3-101,
3-104
DIST: Rg2', Reverse SGx 076 148 077 148 078 148 079 148 Fig. 3-102,
3-105
DIST: Rg3', Reverse SGx 076 149 077 149 078 149 079 149
DIST: Rg4', Reverse SGx 080 026 081 026 082 026 083 026
Setting for the limit resistance for simultaneous load blinding of zones 1 to 4
(or 1´ to 4´) of the circular and polygonal characteristics, in forward and
reverse directions, in secondary values.
Note:
The maximum setting value Rg is set to the same value as that of
impedance reach Z of the respective zone.
If Rg is higher, the signal “Setting Error Distance Protection” is issued and
the protection function is blocked.
DIST: Alpha_L 1 (Poly) SGx 012 013 012 063 013 013 013 063 Fig. 3-104
DIST: Alpha_L 2 (Poly) SGx 012 014 012 064 013 014 013 064 Fig. 3-105
DIST: Alpha_L 3 (Poly) SGx 012 015 012 065 013 015 013 065
DIST: Alpha_L 4 (Poly) SGx 080 010 081 010 082 010 083 010
DIST: beta 4 Angle SGx 080 013 081 013 082 013 083 013
DIST: Alpha 4 SGx 080 014 081 014 082 014 083 014
Angle setting for load blinding (directional line) in the first or third quadrant
of impedance zones 1 to 3 of the circular characteristic.
DIST: gamma 1 Angle SGx 076 247 077 247 078 247 079 247 Fig. 3-101,
3-104
DIST: gamma 2 Angle SGx 076 248 077 248 078 248 079 248 Fig. 3-102,
3-105
DIST: gamma 3 Angle SGx 076 249 077 249 078 249 079 249
DIST: gamma 4 Angle SGx 080 027 081 027 082 027 083 027
DIST: tZ2L Long Delay SGx 012 190 012 191 012 192 012 193 Fig. 3-107
DIST: tZ3L Long Delay SGx 012 194 012 195 012 196 012 197 Fig. 3-107
DIST: tZ4L Long Delay SGx 080 012 081 012 082 012 083 012 Fig. 3-107
Setting for the timer stage of switch on to fault protection or external zone
extension.
DIST: Z2 Op.Mode dx/dt SGx 072 107 073 107 074 107 075 107 Fig. 3-108
DIST: Z3 Op.Mode dx/dt SGx 072 197 073 197 074 197 075 197
DIST: Z4 Op.Mode dx/dt SGx 080 029 081 029 082 029 083 029
DIST: Z4Delta I(di/dt) SGx 080 030 081 030 082 030 083 030
Setting for the current increase required to detect a short circuit operation in
the zone 2, 3 or 4.
It must be set to 'Blocked' in order to disable sudden current change
monitoring.
DIST: Z2Delta V(dv/dt) SGx 072 139 073 139 074 139 075 139 Fig. 3-106,
3-108
DIST: Z3Delta V(dv/dt) SGx 072 108 073 108 074 108 075 108
DIST: Z4Delta V(dv/dt) SGx 080 028 081 028 082 028 083 028
Setting for the voltage drop required to detect a short circuit operation in the
zone 2, 3 or 4.
It must be set to 'Blocked' in order to disable sudden voltage change
monitoring.
DIST: Z2D.phi(dphi/dt) SGx 072 206 073 206 074 206 075 206 Fig. 3-106,
3-108
DIST: Z3D.phi(dphi/dt) SGx 072 227 073 227 074 227 075 227
DIST: Z4D.phi(dphi/dt) SGx 080 031 081 031 082 031 083 031
Setting for the angle change required to detect a short circuit operation in
the zone 2, 3 or 4.
It must be set to 'Blocked' in order to disable sudden angle change
monitoring.
DIST: WPC Enable SGx 076 130 077 130 078 130 079 130 Fig. 3-111
DIST: WPC Zmin SGx 076 135 077 135 078 135 079 135 Fig. 3-112
Setting for the internal limit impedance of the wrong phase coupling
protection zone.
DIST: WPC Zmax SGx 076 136 077 136 078 136 079 136 Fig. 3-112
Setting for the external limit impedance of the wrong phase coupling
protection zone.
DIST: WPC alpha SGx 076 133 077 133 078 133 079 133 Fig. 3-112
Setting for the left limit angle of the wrong phase coupling protection zone.
DIST: WPC beta Angle SGx 076 134 077 134 078 134 079 134 Fig. 3-112
Setting for the right limit angle of the wrong phase coupling protection zone.
DIST: WPC t SGx 076 137 077 137 078 137 079 137 Fig. 3-112
Setting for the timer stage of the wrong phase coupling protection zone.
High Impedance Protection DELTA: Enable SGx 062 030 063 030 064 030 065 030 Fig. 3-115
This setting defines the setting group in which high impedance protection is
enabled.
DELTA: Imin SGx 062 031 063 031 064 031 065 031 Fig. 3-117
Setting for the minimum current trigger for high impedance protection.
DELTA: Delta I SGx 062 037 063 037 064 037 065 037 Fig. 3-121
During a defined sampling interval should the angle (with sudden angle
change monitoring enabled) change by more than the value set for this
parameter, then this signal is issued: D E L T A : D e l t a P h i S t a r t i n g .
DELTA: I(3fn)/I(fn) SGx 062 040 063 040 064 040 065 040 Fig. 3-120
Setting for the ratio of the third harmonic current component to the
fundamental. This value is used as the operate threshold for the harmonics
stabilization feature.
DELTA: I(5fn)/I(fn) SGx 062 042 063 042 064 042 065 042 Fig. 3-120
Setting for the ratio of the fifth harmonic current component to the
fundamental. This value is used as the operate threshold for the harmonics
stabilization feature.
DELTA: kSt,I(xfn)/I(fn) SGx 062 041 063 041 064 041 065 041 Fig. 3-121
VT and CT Supervision C&VTS: Enable SGx 014 200 014 201 014 202 014 203 Fig. 3-122
Setting for the minimum voltage change for the detection of a “fuse failure”
condition.
C&VTS: Delta I VTS/Fuse SGx 014 221 014 222 014 223 014 224 Fig. 3-124
Setting for the maximum current change for the detection of a “fuse failure”
condition.
Backup Overcurrent-Time BUOC: Enable SGx 072 118 073 118 074 118 075 118 Fig. 3-127
Protection
This setting defines the setting group in which backup overcurrent-time
protection is enabled.
BUOC: I> SGx 010 058 010 078 010 098 011 018 Fig. 3-129
Setting for operate threshold I> of the current of the backup overcurrent-
time protection.
BUOC: I>> SGx 010 127 010 129 010 131 010 133 Fig. 3-129
Setting for operate threshold I>> of the current of the backup overcurrent-
time protection.
BUOC: tI> SGx 010 059 010 079 010 099 011 019 Fig. 3-129
Setting for the operate delay of stage I> of the backup overcurrent-time
protection.
BUOC: tI>> SGx 010 128 010 130 010 132 010 134 Fig. 3-129
Setting for the operate delay of stage I>> of the backup overcurrent-time
protection.
Switch on to Fault Protection SOTF: Enable SGx 011 120 011 121 011 122 011 123 Fig. 3-130
This setting defines the setting group in which switch on to fault protection is
enabled.
SOTF: Operating Mode SGx 011 061 011 114 011 115 011 116 Fig. 3-131
The setting of the operating mode defines whether a general start shall
cause a trip while a timer stage is running ("trip with starting") or if the
measuring range of the impedance zone 1 is extended by the set zone
extension factor D I S T : k z e E x t e n d e d H S R S G x ("trip with
overreach").
SOTF: Man. Close Timer SGx 011 060 011 111 011 112 011 113 Fig. 3-131
Setting for the timer stage which is started by the manual close signal.
Auto-Reclose Control RECLS: Enable SGx 015 046 015 047 015 048 015 049 Fig. 3-132
This setting defines whether the CB closed position will be scanned or not.
If the setting is 'Enabled', a binary signal input must be configured
accordingly.
RECLS: Parallel Trip SGx 015 053 024 027 024 087 025 047 Fig. 3-148
Setting for the HSR tripping timer stage initiated by a distance protection
zone 1 start.
RECLS: HSR-Tr.DIST t2S SGx 015 144 015 145 015 146 015 147 Fig. 3-135
RECLS: HSR-Tr.DIST t2L SGx 015 152 015 153 015 154 015 155 Fig. 3-135
Setting for the HSR tripping timer stage initiated by a distance protection
zone 2 start together with train start-up detection dx/dt in zone 2.
RECLS: HSR-Tr.DIST t3S SGx 015 160 015 161 015 162 015 163 Fig. 3-135
RECLS: HSR-Tr.DIST t3L SGx 015 168 015 169 015 170 015 171 Fig. 3-135
Setting for the HSR tripping timer stage initiated by a distance protection
zone 3 start together with train start-up detection dx/dt in zone 3.
RECLS: HSR-Tr.DIST t4S SGx 015 180 015 181 015 182 015 183
RECLS: HSR-Tr.DIST t4L SGx 015 188 015 189 015 190 015 191
Setting for the HSR tripping timer stage initiated by a distance protection
zone 4 start together with train start-up detection dx/dt in zone 4.
RECLS: HSR-Tr.DELTA tD. SGx 008 192 008 193 008 194 008 195 Fig. 3-137
Setting for the HSR tripping timer stage initiated by a start of the high
impedance protection.
RECLS: HSR-Tr.DTOC tI>H SGx 015 069 024 052 024 053 024 054 Fig. 3-138
Setting for the HSR tripping timer stage initiated by a start of the DTOC
high-current stage.
RECLS: HSR-Tr.DTOC tI> SGx 015 105 020 105 021 105 022 105 Fig. 3-138
RECLS: HSR-Tr.DTOC tI>> SGx 015 074 020 107 021 107 022 107 Fig. 3-138
Setting for the HSR tripping timer stage initiated by a start of the DTOC 1st
or 2nd high-current stage.
RECLS: HSR-Tr.IDMT kIrefSGx 015 094 020 113 021 113 022 113 Fig. 3-138
Setting for the HSR tripping timer stage initiated by a start of the IDMT Ikref
stage.
RECLS: HSR-Tr.BUOC tI> SGx 015 109 020 109 022 109 023 109 Fig. 3-140
RECLS: HSR-Tr.BUOC tI>> SGx 015 111 020 111 021 111 022 111 Fig. 3-140
Setting for the HSR tripping timer stage initiated by a start of the BUOC 1st
or 2nd high-current stage.
RECLS: HSR-Tr. LOGIC SGx 015 098 024 110 024 160 025 110 Fig. 3-142
Setting for the HSR tripping timer stage initiated by a programmable logic
start.
RECLS: HSR Dead Time SGx 015 056 024 030 024 090 025 050 Fig. 3-148
Setting for the number of time-delayed reclosures permitted. With the ‘0’
setting, only one HSR is carried out.
RECLS: TDR-Tr.DIST t1 SGx 015 073 024 041 025 001 025 061 Fig. 3-136
Setting for the TDR tripping timer stage initiated by a distance protection
zone 1 start.
RECLS: TDR-Tr.DIST t2S SGx 015 148 015 149 015 150 015 151 Fig. 3-136
RECLS: TDR-Tr.DIST t2L SGx 015 156 015 157 015 158 015 159 Fig. 3-136
Setting for the TDR tripping timer stage initiated by a distance protection
zone 2 start together with train start-up detection dx/dt in zone 2.
RECLS: TDR-Tr.DIST t3S SGx 015 164 015 165 015 166 015 167 Fig. 3-136
RECLS: TDR-Tr.DIST t3L SGx 015 172 015 173 015 174 015 175 Fig. 3-136
Setting for the TDR tripping timer stage initiated by a distance protection
zone 3 start together with train start-up detection dx/dt in zone 3.
RECLS: TDR-Tr.DIST t4S SGx 015 184 015 185 015 186 015 187
RECLS: TDR-Tr.DIST t4L SGx 015 192 015 193 015 194 015 195
Setting for the TDR tripping timer stage initiated by a distance protection
zone 4 start together with train start-up detection dx/dt in zone 4.
RECLS: TDR-Tr.DELTA tD. SGx 008 196 008 197 008 198 008 199 Fig. 3-137
Setting for the TDR tripping timer stage initiated by a start of the high
impedance protection.
RECLS: TDR-Tr.DTOC tI>H SGx 015 070 024 055 024 056 024 057 Fig. 3-139
Setting for the TDR tripping timer stage initiated by a start of the DTOC
high-current stage.
RECLS: TDR-Tr.DTOC tI> SGx 015 106 020 106 021 106 022 106 Fig. 3-139
RECLS: TDR-Tr.DTOC tI>> SGx 015 075 020 108 022 108 023 108 Fig. 3-139
Setting for the TDR tripping timer stage initiated by a start of the DTOC 1st
or 2nd high-current stage.
RECLS: TDR-Tr.IDMT kIrefSGx 015 095 020 114 021 114 022 114 Fig. 3-139
Setting for the TDR tripping timer stage initiated by a start of the IDMT Ikref
stage.
RECLS: TDR-Tr.BUOC tI> SGx 015 110 020 110 021 110 022 110 Fig. 3-140
RECLS: TDR-Tr.BUOC tI>> SGx 015 112 020 112 021 112 022 112 Fig. 3-140
Setting for the TDR tripping timer stage initiated by a start of the BUOC 1st
or 2nd high-current stage.
RECLS: TDR-Tr. LOGIC SGx 015 099 024 122 024 172 025 122 Fig. 3-142
Setting for the TDR tripping timer stage initiated by a programmable logic
start.
RECLS: TDR Dead Time SGx 015 057 024 031 024 091 025 051 Fig. 3-148
Setting for the current threshold via which the auto-recloser is blocked.
RECLS: Block. Time Int. SGx 015 043 024 021 024 081 025 041 Fig. 3-133
Setting for the time that will elapse before the auto-recloser will be ready
again after cancellation of the blocks set by the P438.
RECLS: Block. Time Ext. SGx 015 058 024 032 024 092 025 052 Fig. 3-133
Setting for the time that will elapse before the auto-recloser will be ready
again after blocking by a binary signal input.
RECLS: Zone Ext.Dur. RC SGx 015 088 024 047 025 007 025 067 Page: 3-205
RECLS: RC f. THERM Trip SGx 015 176 015 177 015 178 015 179 Fig. 3-148
Definite-Time Overcurrent DTOC: Enable SGx 072 098 073 098 074 098 075 098 Fig. 3-150
Protection
This setting defines the setting group in which definite-time overcurrent
protection is enabled.
DTOC: I>H SGx 072 009 073 009 074 009 075 009 Fig. 3-151
This setting defines whether timer stage tI> is started with triggering of
current thresholds I> or, additionally, with a directional signal.
DTOC: beta (I>) SGx 076 068 077 068 078 068 079 068 Fig. 3-154
Angles β and γ set the range in which the I> starting signal logic determines
that the direction is "forward".
DTOC: gamma (I>) SGx 076 073 077 073 078 073 079 073 Fig. 3-154
Angles β and γ set the range in which the I> starting signal logic determines
that the direction is "forward".
DTOC: Direction (I>) SGx 076 080 077 080 078 080 079 080 Fig. 3-155
Setting for the measuring direction for which a tI> trip signal is sent: forward,
reverse or non-directional.
DTOC: V< (I>) SGx 076 131 077 131 078 131 079 131 Fig. 3-155
The tI> trip signal is enabled only if the voltage is lower than the set value.
Enabling is permanent if it is set to 'Blocked'.
DTOC: Mode w/o V (I>) SGx 076 128 077 128 078 128 079 128 Fig. 3-155
This setting defines whether, for a voltage measuring circuit failure, the I>
overcurrent stage should operate non-directionally or should be blocked.
DTOC: Timer Start tI>> SGx 072 245 073 044 074 044 075 044 Fig. 3-153
This setting defines whether timer stage tI>> is started with the triggering of
current thresholds I>> or, additionally, with a directional signal.
DTOC: beta (I>>) SGx 076 069 077 069 078 069 079 069 Fig. 3-154
Angles β and γ set the range in which the I>> starting signal logic
determines that the direction is "forward".
DTOC: gamma (I>>) SGx 076 074 077 074 078 074 079 074 Fig. 3-154
Angles β and γ set the range in which the I>> starting signal logic
determines that the direction is "forward".
DTOC: Direction (I>>) SGx 076 088 077 088 078 088 079 088 Fig. 3-156
Setting for the measuring direction for which a tI>> trip signal is sent:
forward, reverse or non-directional.
DTOC: V< (I>>) SGx 076 150 077 150 078 150 079 150 Fig. 3-156
The tI>> trip signal is enabled only if the voltage is lower than the set value.
Enabling is permanent if it is set to ’Blocked’.
DTOC: Mode w/o V (I>>) SGx 076 129 077 129 078 129 079 129 Fig. 3-156
This setting defines whether, for a voltage measuring circuit failure, the I>>
overcurrent stage should operate non-directionally or should be blocked.
Inverse-Time Overcurrent IDMT: Enable SGx 072 000 073 000 074 000 075 000 Fig. 3-157
Protection
This setting defines the setting group in which IDMT protection is enabled.
IDMT: Iref Rating SGx 072 050 073 050 074 050 075 050 Fig. 3-162,
3-164
Setting for the reference current of the curve.
IDMT: Characteristic SGx 072 056 073 056 074 056 075 056 Fig. 3-162,
3-164
Setting for the tripping characteristic.
IDMT: kt Time Dial/TMS SGx 072 053 073 053 074 053 075 053 Fig. 3-162,
3-164
Setting for the characteristic time multiplier.
IDMT: Min. Trip Time SGx 072 077 073 077 074 077 075 077 Fig. 3-162,
3-164
Setting for the minimum trip time.
IDMT: Hold Time SGx 072 071 073 071 074 071 075 071 Fig. 3-162,
3-164, 3-167
Setting for the hold time or intermittent faults.
IDMT: Reset SGx 072 059 073 059 074 059 075 059 Fig. 3-162,
3-164
Setting for the release or reset characteristic.
IDMT: Timer Sta. tIref>SGx 006 061 006 062 006 063 006 064 Fig. 3-164
This setting defines whether timer stage tIref> is started with the triggering of
IDMT protection or, additionally, with a directional signal.
IDMT: beta SGx 072 046 073 046 074 046 075 046 Fig. 3-165
Angles β and γ set the range in which the inverse-time overcurrent starting
signal logic determines that the direction is "forward".
IDMT: gamma SGx 072 047 073 047 074 047 075 047 Fig. 3-165
Angles β and γ set the range in which the inverse-time overcurrent starting
signal logic determines that the direction is "forward".
IDMT: Direction (I>) SGx 072 048 073 048 074 048 075 048 Fig. 3-166
Setting for the measuring direction for which a tIref> trip signal is sent:
forward, reverse or non-directional.
IDMT: V< SGx 072 081 073 081 074 081 075 081 Fig. 3-166
The tIref> trip signal is enabled only if the voltage is lower than the set value.
Enabling is permanent if it is set to ’Blocked’.
IDMT: Mode w/o Voltage SGx 072 119 073 119 074 119 075 119 Fig. 3-166
This setting defines whether, in case of voltage measuring circuit failure, the
definite-time overcurrent protection function should operate non-directionally
or should be blocked.
Defrost Protection DFRST: Enable SGx 019 130 019 131 019 132 019 133 Fig. 3-168
This setting defines the setting group in which defrost protection is enabled.
DFRST: Id> SGx 019 134 019 135 019 136 019 137 Fig. 3-170
Thermal Overload Protection THERM: Enable SGx 072 175 073 175 074 175 075 175 Fig. 3-171
This setting defines the setting group in which thermal overload protection is
enabled.
THERM: Iref Rating SGx 072 179 073 179 074 179 075 179 Fig. 3-173
Setting for the thermal time constants of the protected object with current
flow (heating time constant).
THERM: Tim.Const 2(Cool)SGx 072 188 073 188 074 188 075 188 Fig. 3-176
Setting for the thermal time constants of the protected object without current
flow (cooling time constant).
Note: This setting option is only relevant when machines are running.
In all other cases, time constant 2 must be set equal to time constant 1.
THERM: O/T f.Iref Pers. SGx 072 167 073 167 074 167 075 167 Fig. 3-176
THERM: T> Trip Reset,% SGx 072 181 073 181 074 181 075 181 Fig. 3-176
Setting for the default coolant temperature to be used for calculation of the
trip time if coolant temperature is not measured.
THERM: Funct.f.CTA Fail.SGx 076 177 077 177 078 177 079 177 Fig. 3-174
This setting specifies how the thermal overload protection function will
continue to operate in the event of faulty coolant temperature acquisition.
THERM: Minimum Temperat.SGx 076 178 077 178 078 178 079 178 Fig. 3-176
An alarm will be raised in advance of the trip. The time difference between
the alarm and the trip time is set here.
THERM: Factor 2 Parall. SGx 072 173 073 173 074 173 075 173 Fig. 3-173
THERM: Factor 3 Parall. SGx 072 174 073 174 074 174 075 174 Fig. 3-173
Setting for the parallel line factors for 2- or 3-parallel line operation.
Time-Delayed Voltage V<>: Enable SGx 076 000 077 000 078 000 079 000 Fig. 3-178
Protection
This setting defines the setting group in which V<> protection is enabled.
V<>: V> SGx 076 003 077 003 078 003 079 003 Fig. 3-179
V<>: tV>> SGx 076 006 077 006 078 006 079 006 Fig. 3-179
Setting for the time limit of the signals generated by the undervoltage
stages.
V<>: Hyst. V<> Meas. SGx 076 048 077 048 078 048 079 048 Fig. 3-179
Setting for the hysteresis of the trigger stages for monitoring measured
voltages.
Circuit Breaker Failure CBF: Enable SGx 072 110 073 110 074 110 075 110 Fig. 3-181
Protection
This setting defines the setting group in which breaker failure protection is
enabled.
CBF: Imin< SGx 072 112 073 112 074 112 075 112 Fig. 3-183
Setting for the Imin< current threshold. Current falling below this threshold
will be interpreted as breaker opening, and reset the CBF timers.
CBF: tImin< SGx 072 113 073 113 074 113 075 113 Fig. 3-183
Setting for the monitoring time of the main-trip command before issuing a
re-trip.
CBF: tBF2 Init BackTr.SGx 072 116 073 116 074 116 075 116 Fig. 3-183
Setting for the monitoring time of the re-trip command before issuing a back-
trip.
Limit Value Monitoring LIMIT: Enable SGx 072 240 073 240 074 240 075 240 Fig. 3-192
This setting defines the setting group in which the limit value monitoring
function is enabled.
LIMIT: I> SGx 072 241 073 241 074 241 075 241 Fig. 3-193
LIMIT: tI>> SGx 072 244 073 244 074 244 075 244 Fig. 3-193
Setpoint limit value of the second overcurrent stage of the catenary current.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer feed'.
LIMIT: tIcat> SGx 076 202 077 202 078 202 079 202 Fig. 3-194
Setting for the operate delay of the first overcurrent stage of the catenary
current.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer feed'.
LIMIT: tIcat>> SGx 076 203 077 203 078 203 079 203 Fig. 3-194
Setting for the operate delay of the second overcurrent stage of the
catenary current.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer feed'.
LIMIT: Ifdr> SGx 076 204 077 204 078 204 079 204 Fig. 3-194
Setpoint limit value of the first overcurrent stage of the feeder current.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer feed'.
LIMIT: Ifdr>> SGx 076 205 077 205 078 205 079 205 Fig. 3-194
Setpoint limit value of the second overcurrent stage of the feeder current.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer feed'.
LIMIT: tIfdr> SGx 076 206 077 206 078 206 079 206 Fig. 3-194
Setting for the operate delay of the first overcurrent stage of the feeder
current.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer feed'.
LIMIT: tIfdr>> SGx 076 207 077 207 078 207 079 207 Fig. 3-194
Setting for the operate delay of the second overcurrent stage of the feeder
current.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer feed'.
LIMIT: Idfrst> SGx 076 224 077 224 078 224 079 224 Fig. 3-195
Setting for the operate delay of the first overcurrent stage of the defrost
current.
LIMIT: Idfrst>> SGx 076 225 077 225 078 225 079 225 Fig. 3-195
Setting for the operate delay of the first overcurrent stage of the defrost
current.
LIMIT: tIdfrst> SGx 076 226 077 226 078 226 079 226 Fig. 3-195
Setting for the operate delay of the first overcurrent stage of the defrost
current.
LIMIT: tIdfrst>> SGx 076 227 077 227 078 227 079 227 Fig. 3-195
Setting for the operate delay of the second overcurrent stage of the defrost
current.
LIMIT: V> SGx 072 247 073 247 074 247 075 247 Fig. 3-196
Setting for the operate threshold of the first overvoltage stage of the
catenary voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: Vcat>> SGx 076 209 077 209 078 209 079 209 Fig. 3-197
Setting for the operate threshold of the second overvoltage stage of the
catenary voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: tVcat> SGx 076 210 077 210 078 210 079 210 Fig. 3-197
Setting for the operate delay of the first overvoltage stage of the catenary
voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: tVcat>> SGx 076 211 077 211 078 211 079 211 Fig. 3-197
Setting for the operate delay of the second overvoltage stage of the
catenary voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: Vcat< SGx 076 216 077 216 078 216 079 216 Fig. 3-197
Setting for the operate threshold of the first undervoltage stage of the
catenary voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: Vcat<< SGx 076 217 077 217 078 217 079 217 Fig. 3-197
Setting for the operate threshold of the second undervoltage stage of the
catenary voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: tVcat< SGx 076 218 077 218 078 218 079 218 Fig. 3-197
Setting for the operate delay of the first undervoltage stage of the catenary
voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: tVcat<< SGx 076 219 077 219 078 219 079 219 Fig. 3-197
Setting for the operate delay of the second undervoltage stage of the
catenary voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: Vfdr> SGx 076 212 077 212 078 212 079 212 Fig. 3-197
Setting for the operate threshold of the first overvoltage stage of the feeder
voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: Vfdr>> SGx 076 213 077 213 078 213 079 213 Fig. 3-197
Setting for the operate threshold of the second overvoltage stage of the
feeder voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: tVfdr> SGx 076 214 077 214 078 214 079 214 Fig. 3-197
Setting for the operate delay of the first overvoltage stage of the feeder
voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: tVfdr>> SGx 076 215 077 215 078 215 079 215 Fig. 3-197
Setting for the operate delay of the second overvoltage stage of the feeder
voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: Vfdr< SGx 076 220 077 220 078 220 079 220 Fig. 3-197
Setting for the operate threshold of the first undervoltage stage of the feeder
voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: Vfdr<< SGx 076 221 077 221 078 221 079 221 Fig. 3-197
Setting for the operate threshold of the second undervoltage stage of the
feeder voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: tVfdr< SGx 076 222 077 222 078 222 079 222 Fig. 3-197
Setting for the operate delay of the first undervoltage stage of the feeder
voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: tVfdr<< SGx 076 223 077 223 078 223 079 223 Fig. 3-197
Setting for the operate delay of the second undervoltage stage of the feeder
voltage.
Note: Valid only with setting
M A I N : F e e d i n g M o d e ‘Autotransformer feed’.
LIMIT: f> SGx 072 211 073 211 074 211 075 211 Fig. 3-198
The P438 generates a large number of signals, processes binary input signals, and
acquires measured data during fault-free operation of the protected object as well as
fault-related data. A number of counters are maintained for statistical purposes.
This information can be read out from the integrated user interface.
All this information can be found in the ‘Operation’ and ‘Events’ folders in the menu tree.
Note:
8.1 Operation
While the hold time is running, the loop-back test results can be checked by
reading out these values.
Measured Data Input RTDmA: Current IDC 004 134 Fig. 3-25
Date display.
Note: The date can also be set here.
MAIN: Time 003 091 Fig. 3-67
Display of the updated value for the catenary voltage as a primary quantity.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer feed'.
MAIN: Voltage Vfdr Prim. 006 042 Fig. 3-43
Display of the updated value for the feeder voltage as a primary quantity.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer feed'.
MAIN: Active Power P Prim. 004 050 Fig. 3-44,
3-45
Display of the updated active power value as a primary quantity.
MAIN: Reac. Power Q Prim. 004 052 Fig. 3-44,
3-45
Display of the updated reactive power value as a primary quantity.
MAIN: Load Imped Z Prim. 005 005 Fig. 3-46
Display of the updated value for the load angle referred to ϕn = 100°.
MAIN: Active Power Factor 004 054 Fig. 3-44
Display of the updated value for the load impedance as secondary quantity.
MAIN: Load Reactance X Sec 005 195 Fig. 3-46
Display of the updated value for the load reactance as secondary quantity.
MAIN: Load Resist. R Sec 005 197 Fig. 3-46
Display of the updated value for the load resistance as secondary quantity.
MAIN: kHarm, ΣI(xfn)/I(fn) 008 216 Fig. 3-42
The ratio of the second, third and fifth harmonic current components to the
fundamental component of the current.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer Feed'
and with the optional processor module with an integrated DSP
coprocessor fitted,
and with the harmonics adaptation feature enabled in the
distance protection.
Thermal Overload Protection THERM: Status Therm.Replica 004 016 Fig. 3-176
Substation Event
GOOSE: Output 2 State 106 012
Status Events
GSSE: Output 2 State 104 103
'High': Energized.
This display appears regardless of the binary signal input mode set.
This signal shows that the backlighting for the front panel LCD is switched
on.
Communication Interface 1 COMM1: Command Block. EXT 003 173 Fig. 3-6
COMM1: Sig/Meas. Block EXT 037 074 Fig. 3-7,
3-8, 3-9
COMM1: Command Blocking 003 174 Fig. 3-6
COMM1: Sig/Meas. Val.Block 037 075 Fig. 3-7,
3-8, 3-9
COMM1: IEC 60870-5-103 003 219 Fig. 3-7
COMM1: IEC 60870-5-101 003 218 Fig. 3-8
COMM1: IEC 60870-5,ILS 003 221 Fig. 3-9
COMM1: MODBUS 003 223 Fig. 3-10
COMM1: DNP3 003 230 Fig. 3-11
COMM1: COURIER 103 041
Display when an Ethernet module has not initiated properly, i.e. if the MAC
address is missing or there is an implausible setting!
Substation Event
Display if the continuously monitored communication link to a GOOSE
sending device (IED situated on the opposite side) is in fault or has
disappeared altogether. The GOOSE sending device will attach a validity
stamp to each GOOSE message, up to which a repetition of GOOSE will be
carried out independently of a change of state. Thus the device monitors
the time at which the next state signal must be received.
Status Events
Display if the continuously monitored communication link to a GSSE
sending device (IED situated on the opposite side) is in fault or has
disappeared altogether. The GSSE sending device will attach a validity
stamp to each GSSE message, up to which a repetition of GSSE will be
carried out independently of a change of state. Thus the device monitors
the time at which the next state signal must be received.
Binary Output OUTP: Block Outp.Rel. EXT 040 014 Fig. 3-28
OUTP: Reset Latch. EXT 040 015 Fig. 3-28
Fig.*: 3-69
OUTP: Outp. Relays Blocked 021 015 Fig. 3-28
OUTP: Latching Reset 040 088 Fig. 3-28
Measured Data Output mA_OP: Output Enabled EXT 036 085 Fig. 3-31
mA_OP: Reset Output EXT 036 087 Fig. 3-32
Fig.*: 3-69
mA_OP: Enabled 037 102 Fig. 3-30
mA_OP: Output Reset 037 117 Fig. 3-32
mA_OP: Valid BCD Value 037 050 Fig. 3-33
mA_OP: 1-Dig. Bit 0 (BCD) 037 051 Fig. 3-33
mA_OP: 1-Dig. Bit 1 (BCD) 037 052 Fig. 3-33
mA_OP: 1-Dig. Bit 2 (BCD) 037 053 Fig. 3-33
mA_OP: 1-Dig. Bit 3 (BCD) 037 054 Fig. 3-33
mA_OP: 10-Dig. Bit 0 (BCD) 037 055 Fig. 3-33
mA_OP: 10-Dig. Bit 1 (BCD) 037 056 Fig. 3-33
mA_OP: 10-Dig. Bit 2 (BCD) 037 057 Fig. 3-33
mA_OP: 10-Dig. Bit 3 (BCD) 037 058 Fig. 3-33
mA_OP: 100-Dig. Bit 0 (BCD) 037 059 Fig. 3-33
mA_OP: 100-Dig. Bit 1 (BCD) 037 060 Fig. 3-33
mA_OP: Value A-1 Valid 069 014 Fig. 3-35
mA_OP: Value A-1 Output 037 118 Fig. 3-35
mA_OP: Value A-2 Valid 069 015
Setting Group Selection GROUP: Control Via User EXT 036 101 Fig. 3-72
GROUP: Activate Grp 1 EXT 065 002 Fig. 3-72
GROUP: Activate Grp 2 EXT 065 003 Fig. 3-72
GROUP: Activate Grp 3 EXT 065 004 Fig. 3-72
GROUP: Activate Grp 4 EXT 065 005 Fig. 3-72
GROUP: Control Via User 036 102 Fig. 3-72
GROUP: Ext.sel. Settg. Grp 003 061 Fig. 3-72
GROUP: Grp1 Activated Ext. 036 094 Fig. 3-72
GROUP: Grp2 Activated Ext. 036 095 Fig. 3-72
GROUP: Grp3 Activated Ext. 036 096 Fig. 3-72
GROUP: Grp4 Activated Ext. 036 097 Fig. 3-72
GROUP: Actual Setting Group 003 062 Fig. 3-72
GROUP: Group 1 Active 036 090 Fig. 3-72
GROUP: Group 2 Active 036 091 Fig. 3-72
GROUP: Group 3 Active 036 092 Fig. 3-72
GROUP: Group 4 Active 036 093 Fig. 3-72
Signal indicating that the line sections have been incorrectly set for the
calculation of fault location.
CHECK: Setting Error CBM 098 020
Operating Data Recording OP_RC: Reset Record. EXT 005 213 Fig. 3-69
Monitoring Signal Recording MT_RC: Reset Record. EXT 005 240 Fig.*: 3-69
Overload Recording OL_RC: Reset Record. EXT 005 241 Fig.*: 3-69
OL_RC: Record. in Progress 035 003 Fig. 3-78
OL_RC: Overl. Mem. Overflow 035 007 Fig. 3-79
Fault Recording OSCIL: Reset Record. EXT 005 243 Fig.*: 3-69
OSCIL: Trigger EXT 036 089 Fig. 3-88
OSCIL: Trigger 037 076 Fig. 3-88
OSCIL: I> Starting 035 013 Fig. 3-88
OSCIL: Record. in Progress 035 000 Fig. 3-88
OSCIL: System Disturb. Runn 035 004 Fig. 3-88
OSCIL: Fault Mem. Overflow 035 001 Fig. 3-89
OSCIL: Faulty Time Tag 035 002
Distance Protection DIST: Control Via User EXT 038 171 Fig. 3-99
DIST: Z1' Enabled EXT 038 067 Fig. 3-99
DIST: Z2' Enabled EXT 038 069 Fig. 3-99
DIST: Z3' Enabled EXT 036 123 Fig. 3-99
DIST: Z4' Enabled EXT 036 129
The full-cycle r.m.s. value of the current has exceeded the set minimum
current value.
DELTA: Delta I Starting 038 060 Fig. 3-121
Indicates that the sudden current change criterion is met. This signal is
used as a starting for high impedance protection.
DELTA: Delta Phi Starting 038 063 Fig. 3-119
This signal is issued if the angle (with sudden angle change monitoring
enabled) changes by more than the value set for
D E L T A : D e l t a P h i S G x within a defined sampling interval.
DELTA: X-Release 038 065 Fig. 3-118
Indicates that the measured reactance value is within the set limits.
DELTA: I(3fn) Starting 038 076 Fig. 3-120
Indicates that the ratio of the third harmonic current component to the
fundamental has exceeded the starting value set for
DELTA: I(3fn)/I(fn) SGx.
DELTA: I(5fn) Starting 038 077 Fig. 3-120
Indicates that the ratio of the fifth harmonic current component to the
fundamental has exceeded the starting value set for
DELTA: I(5fn)/I(fn) SGx.
Backup Overcurrent-Time BUOC: Blocking tI> EXT 038 127 Fig. 3-128
Protection
BUOC: Blocking tI>> EXT 038 128 Fig. 3-128
BUOC: Enabled 040 093 Fig. 3-127
BUOC: Not Ready 040 030 Fig. 3-128
BUOC: Active 037 021 Fig. 3-128
BUOC: Gen Trip Signal 036 122 Fig. 3-129
BUOC: Trip Signal I> 036 014 Fig. 3-129
BUOC: Trip Signal I>> 036 116 Fig. 3-129
BUOC: Starting I> 036 013 Fig. 3-129
BUOC: Starting I>> 036 115 Fig. 3-129
Auto-Reclose Control RECLS: Reset Counters EXT 005 244 Fig.*: 3-69
RECLS: Enable EXT 037 010 Fig. 3-132
RECLS: Disable EXT 037 011 Fig. 3-132
RECLS: Ext./User Enabled 037 013 Fig. 3-132
RECLS: Enabled 015 064 Fig. 3-132
RECLS: Ready 004 068 Fig. 3-134
RECLS: Not Ready 037 008 Fig. 3-134
RECLS: Lock f. Gen.Starting 036 229 Fig. 3-148
RECLS: CB Drive Ready EXT 004 066
Definite-Time Overcurrent DTOC: Blocking tI>H EXT 041 062 Fig. 3-148,
Protection 3-151
DTOC: Blocking tI> EXT 041 060 Fig. 3-151
DTOC: Blocking tI>> EXT 041 061 Fig. 3-151
DTOC: Enabled 040 120 Fig. 3-150
DTOC: Not Ready 040 027
Thermal Overload Protection THERM: Control Via User EXT 038 169 Fig. 3-173
THERM: Select 2 Paral/L EXT 038 072 Fig. 3-173
THERM: Select 3 Paral/L EXT 038 074 Fig. 3-173
THERM: Replica Block EXT 041 074 Fig. 3-176
THERM: CTA Error EXT 038 062 Fig. 3-174
THERM: Reset Replica EXT 038 061 Fig. 3-177
Fig.*: 3-69
THERM: Enabled 040 068 Fig. 3-171
THERM: Not Ready 040 035 Fig. 3-172
THERM: Control Via User 038 170
Time-Delayed Voltage V<>: Blocking tV> EXT 041 068 Fig. 3-179
Protection
V<>: Blocking tV>> EXT 041 069 Fig. 3-179
V<>: Blocking tV< EXT 041 070 Fig. 3-180
V<>: Blocking tV<< EXT 041 071 Fig. 3-180
V<>: Enabled 040 066 Fig. 3-178
V<>: Ready 042 003 Fig. 3-178
V<>: Not Ready 042 004 Fig. 3-178
V<>: General Start 041 135
Circuit Breaker Failure CBF: Blocking EXT 038 058 Fig. 3-182
Protection CBF: Enabled 040 055 Fig. 3-181
CBF: Not Ready 040 025 Fig. 3-182
CBF: CB Superv. Signal 039 000 Fig. 3-183
CBF: Failure Main-Trip 039 021 Fig. 3-183
CBF: Failure Re-Trip 036 056 Fig. 3-183
CBF: Re-Trip Signal 039 022 Fig. 3-183
CBF: Back-Trip Signal 039 023 Fig. 3-183
CBF: Timer tBF1 Running 036 066 Fig. 3-183
CBF: Timer tBF2 Running 036 110 Fig. 3-183
CBF: CB Failure 036 017 Fig. 3-183
Circuit Breaker Monitoring CBM: Reset Meas.Val.EXT 005 247 Fig.*: 3-69
CBM: Blocking EXT 044 128 Fig. 3-191
CBM: Enabled 044 130 Fig. 3-184,
3-186
CBM: Cycle Running Cat 044 205 Fig. 3-188
CBM: Cycle Running Fdr 044 206 Fig. 3-188
CBM: Blocked 044 199 Fig. 3-191
CBM: Sig. No. CB Op. > 044 135 Fig. 3-190
CBM: Sig. Rem. No.CB Op.< 044 136 Fig. 3-189
CBM: Signal ΣItrip> 044 137
Trigger for the transmission of the selected signal (as signal ‘start‘).
COMM1: Test Spont.Sig. End 003 186 Fig. 3-13
Trigger for the transmission of the selected signal (as signal ‘end‘).
Trigger for the transmission of the selected signal (as signal ‘start‘).
COMM2: Test Spont.Sig. End 103 186 Fig. 3-15
Trigger for the transmission of the selected signal (as signal ‘end‘).
Status Events
Command to reset monitoring counters as listed below.
GSSE: Enroll. IEDs Flags L 105 160
Bar with state bits for all GSSE inputs, showing whether the corresponding
GSSE sending device has logged-on and is transmitting free of fault (input 1
to 16).
GSSE: Enroll. IEDs Flags H 105 161
Bar with state bits for all GSSE inputs, showing whether the corresponding
GSSE sending device has logged-on and is transmitting free of fault (input
17 to 32).
GSSE: Tx Message Counter 105 162
State of the continuous counter sequence for the message counter sent
with each GSSE.
GSSE: Tx Last Message 105 166
State of the continuous counter sequence for state changes sent with each
GSSE.
GSSE: No. Reject. Messages 105 167
Setting for which GSSE sending device the following statistics information is
to be displayed.
GSSE: IED Receiv. Messages 105 172
State of the continuous counter sequence for the message counter received
with each GSSE.
GSSE: IED Rx Last Message 105 174
State of the continuous counter sequence for state changes received with
each GSSE.
GSSE: IED Missed Messages 105 175
Number of GSSE received after validity time period has elapsed. This
counter is reset by G S S E : R e s e t C o u n t e r s .
Binary Output OUTP: Reset Latch. USER 021 009 Fig. 3-28
The relay selected for testing is triggered for the duration set at
OUTP: Hold-time for Test.
Setting for the time period for which the selected output relay is triggered for
functional testing.
Measured Data Output mA_OP: Reset Output USER 037 116 Fig. 3-32
Main Function MAIN: General Reset USER 003 002 Fig. 3-68
Group-resetting commands.
Setting the enable for the issue of a trip command from the user interface.
MAIN: Man.M-Trip Cmd USER 003 065 Fig. 3-62
A trip command is issued from the front panel HMI for the 100 ms. This
setting is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
MAIN: Man.Re-Trip Cmd USER 003 066 Fig. 3-62
A trip command is issued from the front panel HMI for the 100 ms. This
setting is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
Note:
This command is not executed unless the manual trip has been configured
as re-trip command.
MAIN: Man.B-Trip Cmd USER 003 067 Fig. 3-62
A trip command is issued from the front panel HMI for the 100 ms. This
setting is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
Note:
This command is not executed unless the manual trip has been configured
as back-trip command.
MAIN: En.Man.Clos.Cmd.USER 003 105 Fig. 3-55
Setting the enable for the issue of a close command from the user interface
(enables manual breaker close operations).
MAIN: Man. Close Cmd. USER 018 033 Fig. 3-55
A close command is issued from the user interface for the set reclose
command time. This setting is password-protected (see section entitled
'Password-Protected Control Operations' in Chapter 6).
MAIN: Warm Restart 003 039
A warm restart is being carried out. The device functions as it does when
the power supply is turned on.
MAIN: Cold Restart 000 085
Operating Data Recording OP_RC: Reset Record. USER 100 001 Fig. 3-74
The operating data memory and the counter for operation signals are reset.
Monitoring Signal Recording MT_RC: Reset Record. USER 003 008 Fig. 3-75,3-
149
Reset of the monitoring signal memory.
Overload Recording OL_RC: Reset Record. USER 100 003 Fig. 3-79
To manually trigger fault recording from the user interface for a "fault"
window of 500 ms.
OSCIL: Reset Record. USER 003 006 Fig. 3-89
The auto-reclosing control function is enabled from the user interface (HMI).
RECLS: Disable USER 003 133 Fig. 3-132
The auto-reclosing control function is disabled from the user interface (HMI).
RECLS: Test HSR USER 011 066 Fig. 3-145
The reset of the reclaim time 2 (which has been triggered after the final trip)
removes the auto-reclose blocking.
RECLS: Reset Counters USER 003 005 Fig. 3-149
Thermal Overload Protection THERM: Reset Replica USER 022 061 Fig. 3-177
Circuit Breaker Monitoring CBM: Initialize Values 003 011 Fig. 3-188
Operating Data Recording OP_RC: Operat. Data Record. 003 024 Fig. 3-74
Monitoring Signal Recording MT_RC: Mon. Signal Record. 003 001 Fig. 3-75
8.2 Events
Main Function MAIN: No. General Start. 004 000 Fig. 3-57
Operating Data Recording OP_RC: No. Oper. Data Sig. 100 002 Fig. 3-74
Monitoring Signal Recording MT_RC: No. Monit. Signals 004 019 Fig. 3-75
Number of faults.
OSCIL: No. System Disturb. 004 010 Fig. 3-88
Auto-Reclose Control RECLS: No. of HSR Recloses 004 004 Fig. 3-149
Circuit Breaker Monitoring CBM: No. of CB Oper. Cat 008 011 Fig. 3-188
CBM: No. of CB Oper. Fdr 008 012 Fig. 3-188
Overload Data Acquisition OL_DA: Overload Duration 004 102 Fig. 3-76
Display of the load current used by the thermal overload protection function
to calculate the tripping time.
OL_DA: Object Temp. THERM 004 035 Fig. 3-77
Fault Data Acquisition FT_DA: Fault Duration 008 010 Fig. 3-80
Display of the fault location of the last fault (in %) referred to the setting at
FT_DA: Line ReactXSec 1 SGx.
FT_DA: Fault Location 004 022 Fig. 3-86
Displays the ratio of the second, third and fifth harmonic current
components to the fundamental component of the current.
Note: Valid only with setting
M A I N : F e e d i n g M o d e 'Autotransformer Feed'
and with the optional processor module with an integrated DSP
coprocessor fitted,
and with the harmonics adaptation feature enabled in the
distance protection.
FT_DA: Vcat p.u. 004 183 Fig. 3-84
Circuit Breaker Monitoring CBM: Itrip,Prim Cat 009 212 Fig. 3-188
CBM: Itrip,Prim Fdr 009 213 Fig. 3-188
Current-time integral of the per-unit ruptured current for each circuit breaker
contact.
CBM: ΣItrip Cat 009 071 Fig. 3-188
CBM: ΣItrip Fdr 009 073 Fig. 3-188
Sum of the per-unit ruptured currents for each circuit breaker contact.
CBM: ΣItrip**2 Cat 009 077 Fig. 3-188
CBM: ΣItrip**2 Fdr 009 078 Fig. 3-188
Sum of the squared per-unit ruptured currents for each circuit breaker
contact.
CBM: ΣI*t Cat 009 087 Fig. 3-188
Sum of the current-time integrals of the per-unit ruptured currents for each
circuit breaker contact.
9 Commissioning
Only qualified personnel, familiar with content on the "Warning" page at the beginning of
this operating manual, may work on or operate this device.
The warning notices at the beginning of Chapter 5 must be observed during installation
and connection of this device.
The device must be reliably grounded before auxiliary voltage is turned on.
The surface-mounted case is grounded using the appropriate bolt and nut as the ground
connection. The flush-mounted case must be grounded in the area of the rear
sidepieces at the location provided. The cross-sectional area of this ground conductor
must also conform to applicable national standards. A minimum conductor cross section
of 2.5 mm2 is required.
In addition, a protective ground connection at the terminal contact on the power supply
module (identified by the letters "PE" on the terminal connection diagram) is also
required for proper operation of the device. The cross-sectional area of this ground
conductor must also conform to applicable national standards. A minimum cross section
of 1.5 mm2 is required.
Before working on the device itself or in the space where the device is connected, always
disconnect the device from the power supply.
The secondary circuit of operating current transformers must not be opened. If the
secondary circuit of an operating current transformer is opened, there is the danger that
the resulting voltages will endanger personnel and damage the insulation.
In units for pin terminal connection, the threaded terminal block for current transformer
connection is not a shorting block. Therefore always short-circuit current transformers
before loosening the threaded terminals.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock.
The fiber-optic interface may only be connected or disconnected when the supply voltage
for the unit is shut off.
The PC interface is not designed for permanent connection. Consequently, the female
connector does not have the extra insulation from circuits connected to the system that is
required per VDE 0106 Part 101. Therefore, when connecting the prescribed connecting
cable, technicians must be careful not to touch the socket contacts.
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see chapter entitled 'Technical
Data')
When using the programmable logic (function group LOGIC), the user must carry out a
functional type test to conform with the requirements of the relevant protection/control
application. In particular, it is necessary to verify that the requirements for the
implementation of logic linking (by setting) as well as the time performance during device
startup, during operation and when there is a fault (device blocking) are fulfilled.
Preparation
After the P438 has been installed and connected as described in Chapter 5, the
commissioning procedure can begin.
Before turning on the power supply voltage, the following items must be checked again:
Is the protection device connected to the protective ground at the specified location?
Does the nominal voltage of the battery agree with the nominal auxiliary voltage of
the protection device?
Are the current and voltage transformer connections, grounding, and phase
sequences correct?
After the wiring work is completed, check the system to make sure it is properly isolated.
The conditions given in VDE 0100 must be satisfied.
Once all checks have been made, the power supply voltage may be turned on. After
voltage has been applied, the device starts up. During startup, various startup tests are
carried out (see section entitled ‘Self-Monitoring’ in Chapter 3). The LED indicators for
‘Operation’ (H1) and ‘Blocked/Faulty’ (H2) will light up. After approximately 15 s, the
P438 is ready for operation. Upon delivery or when the device is energized after a cold
restart the device type, "P438", and the time of day are shown on the first line of the front
panel LCD.
Once the change enabling command has been issued (see section entitled ‘Change-
Enabling Function’ in Chapter 6), all settings can be entered. The procedure for entering
settings from the integrated user interface (HMI) is described in Chapter 6.
If either the PC interface or the communication interfaces will be used for setting the
P438 and reading out event records, then the following settings must first be made from
the integrated user interface (HMI).
‘Set/DvID/’ folder:
DVICE: Password Level 1
DVICE: Password Level 2
‘Set/Conf/’ folder:
PC: Manufacturer
PC: Bay Address
PC: Relay Address
PC: Baud Rate
PC: Parity Bit
COMM1: Remote Comms Port1
COMM1: General Enable USER
COMM1: Manufacturer
COMM1: Line Idle State
COMM1: Baud Rate
COMM1: Parity Bit
COMM1: Communicat Protocol
COMM1: Octet Comm. Address
COMM1: Octet Address ASDU
COMM2: Remote Comms Port2
COMM2: General Enable USER
COMM2: Manufacturer
COMM2: Line Idle State
COMM2: Baud Rate
COMM2: Parity Bit
COMM2: Octet Comm. Address
COMM2: Octet Address ASDU
COMM3: Function Group COMM3
COMM3: General Enable USER
COMM3: Baud Rate
‘Set/Func/Glob/’ folder:
PC: Command Blocking
PC: Sig/Meas. Val.Block
COMM1: USER Command Block
COMM1: USER Sig/Meas Block
COMM2: USER Command Block
COMM2: USER Sig/Meas Block
Note: The settings given above apply to the IEC 60870-5-103 communication
protocol. If another protocol is being used for the communication interface,
additional settings may be necessary. See Chapter 7 for further details.
After the settings have been made, the following checks should be carried out again
before the blocking is canceled:
Does the function assignment of the binary signal inputs agree with the terminal
connection diagram?
Has the correct operating mode been selected for the binary signal inputs?
Does the function assignment of the output relays agree with the terminal connection
diagram?
Has the correct operating mode been selected for the output relays?
Have all settings been made correctly?
M A I N : P r o t e c t i o n E n a b l e d 'yes (on)'
Tests
By using the signals and displays generated by the P438, it is possible to determine
whether the P438 is correctly set and properly interconnected with the station. Signals
are signaled by output relays and LED indicators and entered into the event memory. In
addition, the signals can be checked by selecting the appropriate signal in the menu
tree.
If the user does not wish the trip coils of the circuit breaker or the higher-level protection
device to operate during testing, the trip commands can be blocked through
M A I N : T r i p C m d . B l o c k U S E R (‘Set/Func/Glob/’ folder) or an appropriately
configured binary signal input. Furthermore, it is possible to block each trip command
separately for testing purposes. This is implemented using the parameters
M A I N : B l o c k M a i n T r i p U S E R , M A I N : B l o c k R e T r i p U S E R or
M A I N : B l o c k B a c k T r i p U S E R ('Set/Func/Glob/' folder) or through the
appropriately configured binary signal inputs.
If a test of the individual commands is required, there is the option of issuing each
individual command for a set time after activating a M A I N : E n . M a n . T r i p
C m d . U S E R enable (in the 'M+T/C+Test/' folder) for a limited time. The parameters
M A I N : M a n . M - t r i p U S E R , M A I N : M a n . R e - t r i p U S E R or
M A I N : M a n . B - t r i p U S E R ('M+T/C+Test/' folder) are used. Simultaneously, the
individual commands can be issued via appropriately configured signal inputs.
Selection of the trip command from the integrated user interface (HMI) is password-
protected (see section entitled ‘Password-Protected Control Operations’ in Chapter 6).
Note: The manual trip commands are executed whether or not they have been
configured via selection tables for main trip, re-trip or back-trip.
If the P438 is connected to a control station, the user is advised to activate the test mode
via M A I N : U S E R T e s t M o d e (folder ‘Set/Func/Glob’) or an appropriately
configured binary signal input. The telegrams are then identified accordingly (reason for
transmission: test mode).
This display appears regardless of the binary signal input mode selected.
Note: Checking the output relays is possible only if the P438 has been switched
off-line at M A I N : P r o t e c t i o n E n a b l e d [JE47] ('Set/Func/Glob/' folder)
beforehand.
Before starting the test, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
Checking the
communications interfaces
signals
When using the IEC 60870-5-103, IEC 870-5-101 or ILS-C interface protocols, each
signal generated in the P438 can be transmitted to the connected control station for test
purposes. First select the signal to be tested (C O M M x : S e l . S p o n t a n . S i g . T e s t ,
‘M+T/C+Test/’ folder). The relevant signal is transmitted according to C O M M x : T e s t
S p o n t . S i g . S t a r t or C O M M x : T e s t S p o n t . S i g . E n d (‘M+T/CtrlTest/’ folder).
Signal generation is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
Checking distance
protection
Before checking the distance protection function, set an adequate pre-fault time
(> 11 periods at nominal voltage) in order to ensure exact synchronization of the voltage
memory.
In order to check the distance protection function the value at D I S T : I > S G x must
be exceeded. Commonly, double the operate threshold is used. At the same time, one
needs to take into account that, at low voltages, the load blinding by the angles
D I S T : B e t a n A n g l e S G x and D I S T : G a m m a n A n g l e S G x is reduced.
Characteristics
With the P438, the user may choose between a polygonal and a circular tripping
characteristic. This selection of the tripping characteristic will then govern calculation of
the testing impedances. Functional testing at significant fault angles (for example, 0°,
line impedance angle, 90°), in each case at the zone boundary (tripping impedances
+5% or -5%), is recommended.
The voltage memory is enabled if the following two conditions are satisfied for at least
11 periods (minimum synchronization time):
With the starting, the voltage memory is decoupled and the stored voltage can be used
for directional measurement for 6 s maximum.
Checking VT and CT
Supervision
The voltage-measuring circuit are monitored. Operation of the monitoring functions can
be observed by selecting the logic state signals C & V T S : V T S V o l t s F a i l u r e
(M+T/Meas/Log/' folder). The monitoring signals can also be entered into the monitoring
signal memory and identified by reading out the monitoring signal memory.
When checking the function, the current operate value of D I S T : I > S G x should not
be exceeded.
Checking backup
overcurrent-time protection
The switch to backup overcurrent-time protection (BUOC) – provided it has been
appropriately set – is brought about by the internal measuring-circuit monitoring function
or, if the voltage transformer miniature circuit breaker trips, by the binary input signal
MAIN: M.c.b. Trip V EXT.
If the current exceeds the threshold operate value set at B U O C : I > S G x , then the
timer stage is started. After the set time delay (B U O C : t I > S G x ) has elapsed, the
P438 trips. The second stage of the BUOC function operates in the same manner.
Checking definite-time
overcurrent protection
In order to check definite-time overcurrent protection, appropriate test currents are
applied. If the current exceeds the threshold operate value set at D T O C : I > S G x ,
then the timer stage is started. Once the set delay D T O C : t I > S G x has elasped, the
P438 issues a trip. The second DTOC stage is equivalent.
Checking inverse-time
overcurrent protection
In order to check inverse-time overcurrent protection, appropriate test currents are
applied. The tripping times are determined by the set tripping characteristics (see
Chapter 3 'Operation').
If using the window function for the undervoltage is used, the voltage must not fall below
the set minimum value V < > : V m i n S G x .
The test should be carried out with maximum coolant temperature. The test current
(value ≥ 0.1 Iref) should be applied abruptly. In accordance with the set test current,
tripping by the thermal overload protection function is issued in keeping with the
calculations set out in Chapter 3 'Operation'.
Completion of
commissioning
Before the protection device is released for operation, the user should make sure that
the following steps have been taken:
After completion of commissioning, only the green LED indicator signaling ‘Operation’
(H 1) should be on.
10 Troubleshooting
This chapter describes problems that might be encountered, their causes, and possible
methods for their elimination. It is intended as a general orientation only, and in cases of
doubt it is better to return the P438 to the manufacturer. Please follow the packaging
instructions in the section entitled ‘Unpacking and Packing’ in Chapter 5 when returning
equipment to the manufacturer.
Problem:
Before checking further, disconnect the P438 from the power supply.
If the fuse is defective, it should not be replaced without determining the cause of
failure. If a fuse is replaced without eliminating the problem, there is the danger
that the damage will spread.
Required Fuses:
Identify the specific problem by reading out the monitoring signal memory (see the
section entitled ‘Monitoring Signal Memory Readout’ in Chapter 6). The table below
lists possible monitoring or alarm indications (provided that a configuration setting
has been entered at C H E C K : F c t A s s i g n . F a u l t , the faulty area, the P438
response, and the mode of the output relay configured for 'Alarm' and
'Blocked/Faulty'.
Key
-:
-: No reaction and/or no output relay triggered.
Updating: The output relay configured for 'Alarm' starts only if the monitoring
signal is still present.
1)
: The 'Blocked/Faulty' output relay only operates if the signal has been
configured at M A I N : F c t A s s i g n F a u l t .
2)
: The 'Alarm' output relay only operates if the signal has been
configured at C H E C K : F c t . A s s i g n . A l a r m .
A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: Cold Rest /SW Update 093 025
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: Blocking /HW Failure 090 019
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: +15V Supply Faulty 093 081
The +15 V internal supply voltage has dropped below a minimum value.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: +24V Supply Faulty 093 082
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: -15V Supply Faulty 093 080
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: Defect.Module Slot 1 097 000
CHECK: Defect.Module Slot 2 097 001
CHECK: Defect.Module Slot 3 097 002
CHECK: Defect.Module Slot 4 097 003
CHECK: Defect.Module Slot 5 097 004
CHECK: Defect.Module Slot 6 097 005
CHECK: Defect.Module Slot 7 097 006
CHECK: Defect.Module Slot 8 097 007
CHECK: Defect.Module Slot 9 097 008
CHECK: Defect.Module Slot10 097 009
CHECK: Defect.Module Slot11 097 010
CHECK: Defect.Module Slot12 097 011
CHECK: Defect.Module Slot13 097 012
CHECK: Defect.Module Slot14 097 013
CHECK: Defect.Module Slot15 097 014
CHECK: Defect.Module Slot16 097 015
CHECK: Defect.Module Slot17 097 016
CHECK: Defect.Module Slot18 097 017
CHECK: Defect.Module Slot19 097 018
CHECK: Defect.Module Slot20 097 019
CHECK: Defect.Module Slot21 097 020
The checksum feature of analog I/O module Y has detected a fault in the
data transmission of the Dual-Port-RAM.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: Invalid Op. 093 011
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: Undefined Interrupt 093 012
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: Exception Oper.Syst. 093 013
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: Checksum Sett Error 090 003
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: Clock Sync. Error 093 041
Faulty test pattern in the RAM. This can occur, for example, if the
processor module or the power supply module is removed from the bus
module (digital). This fault is only detected during device startup. After the
fault is detected, the software initializes the RAM. This means that all
records are deleted.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Alarm' output relay: Yes / Yes
‘Blocked/Faulty’ output relay: Yes / Yes
CHECK: Overflow MT_RC 090 012
Software overloaded.
Incorrect or invalid software for analog I/O module has been downloaded.
The set value Rg is too high and no closed tripping characteristic can be
determined.
The fuse failure monitoring function has detected a fault in the voltage-
measuring circuit.
An invalid characteristic has been set for the circuit breaker monitoring
function.
The maximum number of the circuit breaker operations has been exceeded.
The maximum opening time of a circuit breaker contact has been exceeded.
The opening time is not calculated for this contact
An invalid characteristic has been set for one of the analog output channels
of analog I/O module Y.
An invalid characteristic has been set for the analog input channel of analog
I/O module Y.
The P438 has detected an open circuit in the connection of the resistance
thermometer.
The P438 has detected an open circuit in the connection of the 20 mA input.
Since the last complete and correct message was received the time period
set at C O M M 3 : T i m e - O u t C o m m . F a u l t has been exceeded and
the signals received are returned to their user-defined default values.
Incorrect or invalid software to operate the detachable serial HMI has been
downloaded.
The line section used to determine the fault location was configured
incorrectly.
1st device reaction / 2nd device reaction: The fault location is not
determined, the measured
value is issued as
Not Measured.
'Alarm' output relay: Yes / Yes
'Blocked/Faulty' output relay: -/-
CHECK: Output 30 098 053
CHECK: Output 30 (t) 098 054
CHECK: Output 31 098 055
CHECK: Output 31 (t) 098 056
CHECK: Output 32 098 057
CHECK: Output 32 (t) 098 058
These logic outputs can be included in the list of alarm signals by selection
at C H E C K : F c t A s s i g n . A l a r m . The alarm signals are also
recorded in the monitoring signal memory.
11 Maintenance
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
The P438 is a low-maintenance device. The components used in the units are selected
to meet exacting requirements. Recalibration is not necessary.
Maintenance procedures in
the power supply area
Electrolytic capacitors are installed in the power supply area because of dimensioning
requirements. The useful life of these capacitors is significant from a maintenance
standpoint. When the equipment is operated continuously at the upper limit of the
recommended temperature range (+55°C or 131°F), the useful life of these components
is 80,000 hours, or more than 9 years. Under these conditions, replacement of the
electrolytic capacitors is recommended after a period of 8 to 10 years. With operating
temperatures of +45 °C inside the device the required maintenance interval may be
extended by one year.
The P438 is equipped with a lithium battery for non-volatile storage of fault data and for
keeping the internal clock running in the event of failure of the auxiliary power supply.
Loss of capacity due to module-internal self-discharging amounts to less than 1% per
year over a period of availability of 10 years. Since the terminal voltage remains virtually
constant until capacity is exhausted, usefulness is maintained until a very low residual
capacity is reached. With a nominal capacity of 850 mAh and discharge currents of only
a few µA during device storage or in the range of the self-discharge current during
device operation, the result is a correspondingly long service life. It is therefore
recommended that the lithium battery only be replaced after the maintenance interval
cited above.
Always turn off the power (supply voltage) before removing a hardware module.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock!
Electrolytic capacitor:
on power supply module V.
Lithium battery:
on power supply module V.
There is a danger of explosion if the electrolytic capacitor and battery are not properly
replaced. Always check to make sure that the polarity of the electrolytic capacitor and the
battery is correct.
After the maintenance procedures described above have been completed, new
commissioning tests as described in Chapter 9 must be carried out.
The P438 incorporates in its system a very extensive self-monitoring function for
hardware and software. The internal structure guarantees, for example, that
communication within the processor system will be checked on a continuing basis.
Nonetheless, there are a number of sub-functions that cannot be checked by the self-
monitoring feature without injection testing from the device terminals. The respective
device-specific properties and settings must be observed in such cases.
In particular, none of the control and signaling circuits that are run to the device from the
outside are checked by the self-monitoring function.
The best way to carry out a static test of the analog input circuits is to check the primary
measured operating data using the operating data measurement function or to use a
suitable testing instrument. A "small" measured value (such as the nominal current in
the current path) and a "large" measured value (such as the nominal voltage in the
voltage path) should be used to check the measuring range of the A/D converter. This
makes it possible to check the entire dynamic range.
Additional analog testing of such factors as the impedance characteristic or the starting
characteristic is not necessary, in our opinion, since information processing is completely
digital and is based on the measured analog current and voltage values. Proper
operation was checked in conjunction with type testing.
Binary outputs
With respect to binary outputs, the integrated self-monitoring function includes even two-
phase triggering of the relay coils of all the relays. There is no monitoring function for
the external contact circuit. In this case, the all-or-nothing relays must be triggered by
way of device functions or integrated test functions. For these testing purposes,
triggering of the output circuits is integrated into the software through a special control
function (‘M+T/C+Test/’ folder).
Before starting the test, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
Serial interfaces
The integrated self-monitoring function for the PC or communication interface also
includes the communication module. The complete communication system, including
connecting link and fiber-optic module (if applicable), is always totally monitored as long
as a link is established through the control program or the communication protocol.
12 Storage
If the units are stored without being connected to auxiliary voltage, then the electrolytic
capacitors in the power supply area need to be recharged every 4 years. Recharge the
capacitors by connecting auxiliary voltage to the P438 for approximately 10 minutes.
If the units are stored during a longer time, the battery of the power supply module is
used for the continuous buffering of the event data in the working memory of the
processor module. Therefore the battery is permanently required and discharges
rapidly. In order to avoid this continuous discharge, it is recommended to remove the
power supply module from the mounting rack during long storage periods. The contents
of the event memory should be previously read out and stored separately!
The P438 is supplied with standard labeling for the LED indicators. LED indicators that
are not already configured and labeled can be labeled using the label strips supplied.
Affix the label strips to the front of the unit at the appropriate location.
The label strips can be filled in using a Stabilo brand pen containing water-resistant ink
(Type OH Pen 196 PS).
14 Order Information
The P438 (as described here with software version -615) is available with two different
hardware variants. The order information is given separately in sections 14.1 and 14.2
below.
Notice
2) Switching is by parameter, the default setting is underlined!
4) Second language provided is in brackets.
5) For the 84TE version only
8) The standard variant is recommended where a higher switching threshold is not
expressly required
17) High impedance protection (DELTA) function requires fitting of the optional
processor module with an integrated DSP coprocessor
Design options
Rail catenary protection device P438- 0 2 -305 -4xx -615 -46x -9x x -9x x -8xx
Basic device:
Basic device 40TE, CT/VT ring-, I/O pin-terminal connection, 5 -409
Basic device 84TE, pin-terminal connection, 7 -410
Basic device 84TE, ring-terminal connection, 8 -411
basic complement with 4 binary inputs, 8 output relays
and 6 function keys
Further options
Rail catenary protection device P438- 0 2 -305 -4xx -615 -46x -9x x -9x x -8xx
Design options
Rail catenary protection device P438- 0 2 -307 -4xx -615 -46x -9x x -9x x -8xx
Basic device:
Basic device 40TE, CT/VT ring-, I/O pin-terminal connection, 5 -412
Basic device 84TE, pin-terminal connection, 7 -413
Basic device 84TE, ring-terminal connection, 8 -414
basic complement with 4 binary inputs, 8 output relays
and 6 function keys
Further options
Rail catenary protection device P438- 0 2 -307 -4xx -615 -46x -9x x -9x x -8xx
A Glossary
B Signal List
C Overview of Changes
A Glossary A-1
A1 Function Groups A-1
A2 Modules A-2
A3 Symbols A-3
A4 Examples of Signal Names A-10
A5 Symbols Used A-11
A1 Function Groups
A2 Modules
A: Communication module
B: Bus module
L: HMI Module
P: Processor module
T: Transformer module
V: Power supply module
X: Binary I/O module
Y: Analog I/O module
A3 Symbols
Graphic symbols for block diagrams
Binary elements in compliance with DIN 40900 part 12, September 1992, IEC 617-12:
modified 1991
Analog information processing in compliance with DIN 40900 part 13, January 1981
To document the linking of analog and binary signals, additional symbols have been
used, taken from several DIN documents.
As a rule, direction of the signal flow is from left to right and from top to bottom. Other
flow directions are marked by an arrow. Input signals are listed on the left side of the
signal flow, output signals on the right side.
Note:
This rule does not necessarily apply to configurations
with two or more signal flow directions, such as for
symbols with a control block and an output block.
Components of a symbol
A symbol consists of a contour or contour combination
and one or more qualifiers.
Control block
A control block contains an input function common to
several symbols. It is used for the collective setting of
several trigger elements, for example.
Output block
An output block contains an output function common
to several symbols.
D5Z08X6B
State input
Only the state of the binary input variable is read.
Negation of an output
The value up to the boundary line is negated at the
output.
Negation of an input
The input value is negated before the boundary line.
AND element
The output variable will be 1 only if all input variables
are 1.
OR element
The output variable will be 1 only if at least one input
variable is 1.
Threshold element
The output variable will be 1 only if at least two input
variables are 1. The number in the symbol may be
replaced by any other number.
(m out of n) element
The output variable will be 1 only if just one input
variable is 1.
Delay element
The transition from value 0 to 1 at the output occurs
after a time delay of t1 relative to the corresponding
transition at the input.
The transition from value 1 to 0 at the output occurs
after a time delay of t2 relative to the corresponding
transition at the input.
Monostable flip-flop
The output variable will be 1 if the input variable
changes to 1. The output variable will remain 1 for
100 ms, regardless of the duration of the input value
1 (non-retriggerable).
Analog-digital converter
An analog input signal is converted to a binary
signal.
Subtractor
The output variable is the difference between the
two input variables.
A summing element is obtained by changing the
minus sign to a plus sign at the symbol input.
Memory, general
Storage of a binary or analog signal.
Non-stable flip-flop
When the input variable changes to 1, a pulse
sequence is generated at the output.
Amplifier
The output variable is 1 only if the input variable is
also 1.
Counter
At the + input the input variable transitions from 0 to
1 are counted and stored in the function block.
At the R(eset) input a transition of the input variable
from 0 to 1 resets the counter to 0.
Electromechanical drive
in general, here a relay, for example.
Input transducer
with conductor and device identifiers
(according to DIN EN 60445)
Change-over contact
with device identifier
Special symbol
Output relay in normally-energized arrangement
(‘closed-circuit operation’).
PC interface
with pin connections
Multiplier
The output variable is the result of the multiplication
of the two input variables.
Divider
The output variable is the result of the division of
the two input variables.
Comparator
The output variable becomes 1 only if the input
variable(s) are equal to the function in the function
block.
Formula block
The output variable becomes 1 only if the input
variable(s) satisfy the equation in the function block
OSCIL: Fault recording n Internal signal names are not coded by a data model
305 100
address. In the block diagrams they are marked with a
diamond. The small figure underneath the signal
name represents a code that is irrelevant to the user.
The internal signal names used and their origins are
listed in Appendix B.
DIST: VNG>> triggered Signal names coded by a data model address are
[ 036 015 ] represented by their address (shown in square
brackets). Their origin is given in Chapters 7 and 8.
MAIN: General Reset BED A specific setting to be used later on is shown with its
[ 003 002 ] signal name, address, and the setting preceded by
1: Execute the setting arrow.
A5 Symbols Used
Symbol Meaning
t Time duration
V Complex voltage
I Electrical current
I Complex current
Z Complex impedance
f Frequency
δ Temperature in °C
Σ Sum, result
α Angle
τ Time constant
This section incorporates Section 8 of EN 60870-5-101 (1996), which includes a general definition of the telecontrol
interface for substation control systems.
B 2.1 Interoperability
This application-based standard (companion standard) specifies parameter sets and other options from which subsets
are to be selected in order to implement specific telecontrol systems. Certain parameters such as the number of bytes
(octets) in the COMMON ADDRESS of the ASDU are mutually exclusive. This means that only one value of the defined
parameter is allowed per system. Other parameters, such as the listed set of different process information in the
command and monitor direction, permit definition of the total number or of subsets that are suitable for the given
application. This section combines the parameters given in the previous sections in order to facilitate an appropriate
selection for a specific application. If a system is made up of several system components supplied by different
manufacturers (“equipment stemming”), then it is necessary for all partners to agree on the selected parameters.
Note: The overall definition of a system may also require individual selection of certain parameters for specific
parts of a system such as individual selection of scaling factors for individually addressable measured
values.
1
See National Preface of EN 60870-5-101.
P438/EN M/Ad7 // AFSV.12.10470 D /// P438-305-409/410/411-613 + P438-307-412/413/414-613 B-3
Appendix B - Signal List
(continued)
1
See National Preface of EN 60870-5-101.
2
The transmission rates for control direction and monitor direction must be identical.
B-4 P438/EN M/Ad7 // AFSV.12.10470 D /// P438-305-409/410/411-613 + P438-307-412/413/414-613
Appendix B - Signal List
(continued)
Frame format FT 1.2, single character 1, and the fixed time-out interval are used exclusively in this companion
standard.
x Two octets 2
1
See National Preface of EN 60870-5-101.
2
Balanced only.
P438/EN M/Ad7 // AFSV.12.10470 D /// P438-305-409/410/411-613 + P438-307-412/413/414-613 B-5
Appendix B - Signal List
(continued)
Mode 1 (least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is used exclusively in this companion
standard.
x Three octets
1
See National Preface of EN 60870-5-101.
B-6 P438/EN M/Ad7 // AFSV.12.10470 D /// P438-305-409/410/411-613 + P438-307-412/413/414-613
Appendix B - Signal List
(continued)
<14> = Measured value, short floating point value with time tag M_ME_TC_1
x <18> = Packed start events of protection equipment with time tag ME_EP_TB_1
x <19> = Packed output circuit information of protection equipment with time tag M_EP_TC_1
1
Incorrectly identified with control direction in IEC 870-5-101.
P438/EN M/Ad7 // AFSV.12.10470 D /// P438-305-409/410/411-613 + P438-307-412/413/414-613 B-9
Appendix B - Signal List
(continued)
1
The command procedure is formally processed, but there is no change in the local time in the station.
2
See National Preface of EN 60870-5-101.
B-10 P438/EN M/Ad7 // AFSV.12.10470 D /// P438-305-409/410/411-613 + P438-307-412/413/414-613
Appendix B - Signal List
(continued)
<122> = Call directory, select file, call file, call section F_SC_NA_1
1
B 2.1.5 Basic Application Functions
x Remote initialization
x Global
x Group 5 x Group 11
x Clock synchronization
1
See National Preface of EN 60870-5-101.
B-12 P438/EN M/Ad7 // AFSV.12.10470 D /// P438-305-409/410/411-613 + P438-307-412/413/414-613
Appendix B - Signal List
(continued)
Direct set point command transmission Select and execute set point command
x No additional definition
Persistent output
x Threshold value
Smoothing value
This section incorporates Section 8 of IEC 60870-5-103, including definitions applicable to the P438.
B 3.1 Interoperability
x EIA RS 485
Note: EIA RS 485 defines the loads in such a way that 32 of them can be operated on one line. For detailed information
see EIA RS 485, Section 3.
x Glass fiber
x Plastic fiber
x F-SMA connector
x BFOC/2.5 connector
x 9 600 bit/s
x 19 200 bit/s
Mode 1 (least significant octet first) as defined in clause 4.10 of IEC 60870-5-4 is used exclusively in this companion
standard.
x <3> Reset CU
<5> Power on
P438 Designations
INF General Description Address Description
P438 Designations
INF General Description Address Description
x <36>1 Trip circuit supervision 041 200 CHECK: Relay Kxx Faulty
1
The message content is formed from the OR operation of the individual signals
B-18 P438/EN M/Ad7 // AFSV.12.10470 D /// P438-305-409/410/411-613 + P438-307-412/413/414-613
Appendix B - Signal List
(continued)
P438 Designations
INF General Description Address Description
P438 Designations
INF General Description Address Device Description
<69> Trip L1
<70> Trip L2
<71> Trip L3
x <72> Trip I>> (back-up operation) 036 122 BUOC: Gen Trip Signal
<79> Level 2
<80> Level 3
<81> Level 4
<82> Level 5
<83> Level 6
P438 Designations
INF General Description Address Device Description
P438 Designations
INF General Description Address Description
<128> CB ‘on’ by AR
<130> AR blocked
P438 Designations
INF General Description Address Description
<144> Measurand I
<145> Measurands I, V
<146> Measurands I, V, P, Q
P438 Designations
INF General Description Address Description
x <23>1 Activate characteristic 1 003 060 GROUP: Setting Grp Sel USER
x <24>2 Activate characteristic 2 003 060 GROUP: Setting Grp Sel USER
x <25>3 Activate characteristic 3 003 060 GROUP: Setting Grp Sel USER
x <26>4 Activate characteristic 4 003 060 GROUP: Setting Grp Sel USER
1
Switches GROUP: Setting Grp Sel USER to "Setting Group SG1"
2
Switches GROUP: Setting Grp Sel USER to "Setting Group SG2"
3
Switches GROUP: Setting Grp Sel USER to "Setting Group SG3"
4
Switches GROUP: Setting Grp Sel USER to "Setting Group SG4"
B-24 P438/EN M/Ad7 // AFSV.12.10470 D /// P438-305-409/410/411-613 + P438-307-412/413/414-613
Appendix B - Signal List
(continued)
x Test mode
x Disturbance data
Generic services
x Private data
B 3.1.3.6 Miscellaneous
Measured values are transmitted both with ASDU 3 and ASDU 9. As defined in Sec. 7.2.6.8, the maximum MVAL can
be either 1.2 or 2.4 times the rated value. In ASDU 3 and ASDU 9, different ratings may not be used; in other words,
there is only one choice for each measurand.
Current L2
Current L3
Voltage L1-E
Voltage L2-E
Voltage L3-E
Active power P
Reactive power Q
Frequency f
Voltage L1-L2
Version Changes
P438-301-401/402-601 Initial product release
Released: 03.12.2001
P438-301-401/402-602 Hardware No changes
Released: 13.02.2002 Diagram No changes
Software
THERM The operating mode setting has been changed.
The setting 022 063 T H ER M : O p e r a ti n g m o d e is replaced by the
following 'yes/no'-selection parameters:
022 064 T H ER M : R e l a ti ve R e p l i c a
022 065 T H ER M : Ab s o l u te R e p l i c a
Thus operating mode-dependent visibility control of the parameters is
possible.
If the absolute replica is used, the alarm threshold can now be set as
absolute temperature (T H ER M : Al a r m te m p e r a tu r e PSx) .
P438-301-401/402-603 Hardware No changes
Released: 14.03.2003 Diagram No changes
Software
COMM1 If an IEC 60870-5 protocol is used, the T H ER M : T r i p Si g n a l
spontaneous signal is now transmitted via the ASDU 1 (spontaneous
signal without relative time).
FT_DA The calculation of the short circuit impedance and reactance and of the
fault location is now also carried out correctly for In = 5 A.
OSCIL The selection table for record triggering has been extended to include
036 2 5 1 M A I N : G e n T r i p S i g n a l .
MAIN Binary signals
036 051 M AIN : C B C l o s e d Si g . EXT
039 014 M AIN : Sta r t. PIR M a i n - T r i p
039 015 M AIN : Sta r t. PIR R e - T r i p
were initialized every time that the protection device had been switched
to on-line. If the device was, for example, switched to off-/on-line for a
short time, a faulty operation of circuit breaker supervision resulted and
possibly also a start of the testing functions in the substation control
system.
Version Changes
DIST New addresses for the visibility control of the characteristics:
022 001 D IST : C i r c l e C h a r Ava i l a b .
022 002 D IST : W PC Z o n e A v a i l a b l e
Modification of the designation text of the angle set values according to
the system requirement of the railway companies:
Old designation New designation
012 013 D IST : a l p h a 1 P S 1 Alpha_L 1 (Poly) SG1
072 208 D IST : b e ta 1 PS1 Be ta 1 An g l e SG 1
076 090 D IST : g a m m a 1 PS1 Al p h a 1 ( C i r c l e ) SG1
076 247 D IST : r h o 1 PS1 G a m m a 1 An g l e SG 1
The characteristic definitions have been changed. If the characteristic
parameters are only relevant for one characteristic type, this is marked
by the addition of “(Circle)” or “(Polygon)” in the designation text.
The tripping area that is defined by Rg is valid only for the circular
characteristic. When making settings, the maximum setting for this value
that has to be taken into account is now the same that the impedance
reach Z of the respective zone in the respective direction. The checking
of the setting limit now takes only place for unblocked zones (Z and Z’) in
all setting groups. The fault in the calculation of the maximum
permissible Rg of the 3rd zone has thus also been eliminated.
The discontinuity recognition functions d/dt have been revised:
The number of parameters has been drastically reduced:
- The sampling interval duration t is now permanently 1.5 cycles.
- Setting the delta value to 'blocked' now disables the respective
measuring system.
Also in the operate mode 'OR' the short time is active if there is a
simultaneous blocking of all three measuring systems.
The dphi/dt measuring has been corrected.
Signals of individual measuring systems are only issued if the
operating mode dx/dt of the zone is also not set to 'disabled'.
The direction stability has been improved and the tripping time for the
faults in zone 1 has been reduced to 40 ms (if setting t1 = 0 s).
The required minimum voltage for the synchronization of the voltage
memory has been reduced to 0.55 Vn.
The hysteresis for the decision 'direction measurement with voltage
memory' has been extended in order to ensure a stable direction
measurement if there are fault voltages of 10 1 V.
Setting parameter 012 202 D IST : V< L o a d b l i n d e r P S 1 has been
replaced by a permanent threshold of 0.1 Vn.
If the polygonal characteristic is used, a tripping for fault impedances in
the quadrant 4 (in the forward range of the characteristic) is now also
issued even if the reverse direction is blocked.
The maximum reach of the third zone has been extended to 700.0 .
Version Changes
C&VTS Fuse failure monitoring has been accelerated so that unwanted distance
protection operation can also be prevented when the load current has
exceeded the low-end threshold I> of the distance measuring system.
The default set value of the enabling threshold
(C &VT S: V< VT S/F u s e F a i l SG x) has been increased to 0.65 Vn.
The 038 023 C &VT S: VT S Vo l ts F a i l u r e signal is issued when the
M.C.B. trip of the binary input is triggered, even if C&VTS is disabled or
not enabled in the active setting group.
NOT When the current threshold is exceeded the start of the timer stages only
takes place after the enabling of the backup overcurrent-time protection.
SOTF Processing of the function in the 'trip with start' operating mode has been
optimized so that shorter typical tripping times, < 45 ms, are obtained.
DTOC The time tagging of the signals resulting from instantaneous high-current
tripping has been improved. This concerns the following signals:
035 022 D T O C : Sta r ti n g I> H
040 076 D T O C : T r i p Si g n a l t I > H
036 000 M AIN : G e n e r a l S t a r t
036 251 M AIN : G e n T r i p Si g n a l
039 101 M AIN : M a i n - T r i p Si g n a l
039 011 M AIN : M a i n - T r i p C o m m a n d
The reset mode has been improved so that reset times represent a
maximum of one cycle (measured in the event of a current decrease
from double the operate value to 0).
DFRST The setting range of operate values D IF _ X: Id > SG x has been
extended to 0.01...1.00 In.
THERM The function's competition problem at start-up initialization has been
corrected. The incorrectly issued 039 110
T H ER M : Se tti n g Er r o r ,Bl o c k . alarm is no longer displayed.
LOGIC Signals L O G IC : R e s e t 6 EXT and L O G IC : R e s e t 8 EXT are
now available in the selection table for the configuration of the binary
inputs.
Version Changes
P438-301-401/402-603-701 Hardware No changes
Released: 14.08.2003 Diagram No changes
Software
C&VTS The minimum current enabling threshold of the undervoltage and fuse
failure monitoring has been unified to 0.05 In.
The current discontinuity recognition now operates even when the
current decreases.
A detected fuse failure condition is only reset if the measured voltage
exceeds the C &VT S: V> VT S/F u s e F a i l SG x threshold and if
simultaneously a minimum current of 0.05 In flows.
THERM The competition problem of the function in the start-up initialization has
been corrected. The incorrectly issued alarm 039 110
T H ER M : Se tti n g Er r o r ,Bl o c k . is no longer displayed.
P438-301-401/402-603-702 Hardware No changes
Released: 18.09.2003 Diagram No changes
Software
C&VTS Bug fixing:
Fuse failure monitoring was enabled too early during device initialization,
which caused unwanted starting.
THERM The dead time for very fast alterations of the coolant temperature has
been extended to 1.5 s in order to correct competition problems with
measuring-circuit monitoring of the analog module (for example the 040
190 R T D m A: PT 1 0 0 F a u l t y signal was not always issued in time in
order to exclude an unwanted operation).
P438-301-401/402-603-703 Hardware No changes
Released: 04.11.2003 Diagram No changes
Software
CHECK Bug fixing:
When using the analog module, the 093 112 C H EC K: T i m e - o u t
M o d u l e Y time-out fault occurred after approx. 24.8 days.
Version Changes
P438-301-401/402-604 Hardware No changes
Released: 03.12.2003 Diagram No changes
Software
OP_RC The list of the following entries has been modified as follows.
Those added:
038 073 T H ER M : 2 PL Se l e c t. Exte r n .
040 145 L IM IT : tV> > & tV< < El a p s e d
040 197 L IM IT : tf> > El a p s e d
004 062 L IM IT : tI> > El a p s e d
Those removed:
039 076 M AIN : Po w e r F l o w F o r w a r d
039 077 M AIN : Po w e r F l o w R e ve r s e
041 085 D IST : W r o n g S e t t i n g R g , x
040 170 L IM IT : Sta r ti n g T >
040 171 L IM IT : Sta r ti n g T > >
040 174 L IM IT : Sta r ti n g T <
040 175 L IM IT : Sta r ti n g T < <
040 180 L IM IT : Sta r ti n g ID C ,l i n >
040 181 L IM IT : Sta r ti n g ID C ,l i n > >
040 184 L IM IT : Sta r ti n g ID C ,l i n <
040 185 L IM IT : Sta r ti n g ID C ,l i n < <
Thus the LIMIT stages do not enter starting signals, but only the
signal “timer stage elapsed”.
MAIN Bug fixing:
The nominal current setting value for 010 017
M AIN : Id fr s t,n o m D e vi c e was initialized to the default set value of
1 A at each start-up of the device.
DTOC The DTOC Protection is now able to operate in directional mode.
IDMT The IDMT Protection is now able to operate in directional mode.
P438-301-401/402-604-704 Hardware No changes
Released: 19.12.2003 Diagram No changes
Software
CHECK Bug fixing:
The monitoring timer of the analog module was incorrectly initialized in
version –604 when switching the nominal frequency, which caused the
093 112 C H EC K: T i m e - o u t M o d u l e Y alarm to be issued.
Version Changes
P438-301-401/402-604-705 Hardware No changes
Released: 31.01.2005 Diagram No changes
Software
RTDmA Open-circuit monitoring of the 20 mA input and the “PT 100” input has
been improved. The plausibility check of displayed measured variables
was extended.
THERM The plausibility check of the “PT 100” measurement was cancelled and
now occurs exclusively in function group RTDmA.
P438-301-401/402-605 Hardware No changes
Released: 04.07.2005 Diagram No changes
Software
MAIN An inrush detection function, operating with the second harmonic of the
phase current, has been added in order to prevent unwanted tripping
signals issued by the catenary protection device when autotransformers
are switched on or circuit breakers on locomotives are closed. Blocking
of each protection function may be set individually, when an inrush
occurrence is detected.
DIST Bug fixing:
Up to version –604-70x a starting of the protection caused by wrong
phase coupling was not evaluated and signaled. The protection did not
issue a trip signal.
C&VTS The minimum current enable thresholds for undervoltage protection and
fuse failure monitoring are now set via mutual parameters at 014 188
C&VTS: I> Enab V< FuseF SGx.
External blocking of undervoltage protection and fuse failure monitoring
have been added.
Minimum hold-time for fuse failure monitoring is now set at 125 ms
(previously 250 ms).
Version Changes
P438-301-401/402-605-706 This version has no release!
Release: ----
P438-301-401/402-605-707 Hardware No changes
Released: 27.07.2005 Diagram No changes
Software
MAIN Bug fixing:
Up to version –605 there was an occasional changeover to In = 5 A
which was observed when the secondary nominal current was set to
In = 1 A, without this changeover being apparent from the device
parameter setting. The fact that such a changeover had taken place
could only be observed by reading the measured operating values.
In order to suppress this mal-functioning a cyclic refreshing of the
secondary nominal current, according to the device parameter setting,
has been introduced.
COMM1(2) The new communication software version 3.17 has been introduced.
With this version the intermittent interruptions of telegrams during
communication per IEC 60870-5-101 protocol no longer occur.
P438-301-401/402-605-708 Hardware No changes
Released: 10.02.2006 Diagram No changes
Software
C&VTS Bug fixing:
Up to version –605–707 undervoltage protection was blocked when no
current was measured and the 014 188 C &VT S: I> E n a b V <
F u s e F SG x minimum current enabling threshold was set to 0.00 x In.
P438-301-401/402-606 Hardware No changes
Release: 27.01.2006 Diagram No changes
Software
MAIN The close command to the circuit breaker may now be generated from
the front panel user interface (HMI) or via binary signal inputs as well as
through auto-reclose control (RECLS).
It is now possible to select whether the close command is to be
terminated by the 'Closed' position status signal by setting 015 042
MAIN: ClCmd Inhib.by CB Cl.
The binary input function 044 131 M AIN : C B T r i p EXT has been
implemented.
Version Changes
CHECK A number of device bugs previously led to a blocking with the second
entry to the monitoring signal memory (i.e. if the recurring fault was
already stored in the monitoring signal memory – see Chapter 10 in the
Technical Manual). This reaction was changed in such a manner that
device blocking will only occur if a renewed appearance of the same
device fault lies within a set "memory retention time" (021 018
C H E C K : M o n . S i g . R e t e n t i o n ). This makes it possible to tolerate
sporadic faults, resulting from control actions, without having to clear the
monitoring signal memory in the interim.
The significance of the time stamp was modified to accommodate this
new feature. The time stamp now represents the last appearance of the
fault.
DIST Factors for the zone extension function
D I S T : k z e E x t e n d e d H S R S G x and
D I S T : k z e E x t e n d e d T D R S G x are now only applied in conjunction
with auto-reclose control RECLS.
Setting D IST : k z e SO T F /EXT SG x was introduced in order to
enable zone extension via a binary signal input (036 046
D I S T : Z o n e E x t e n s i o n E X T ) or the switch on to fault protection
(SOTF) function.
SOTF This function may now be blocked by a binary signal input,
SOTF: Blocking EXT.
Additionally a blocking signal is sent to auto-recloser (RECLS) during the
manual close time period.
RECLS Auto-reclose control, function group RECLS, has been implemented. It
is now possible to have automatic reclosures consisting of one high-
speed reclosure and up to 9 time-delayed reclosures.
For each tripping function the RECLS function range allows the selection
that the type of fault will permit reclosure or not. Moreover it is possible
to block the function for high current faults.
THERM All parameters associated with coolant temperature acquisition are
hidden if analog module Y has not been fitted to the device. The function
operates with a default coolant temperature.
The further operation may now be selected when there is a CTA failure.
076 177 T H ER M : F u n c t . f . C T A F a i l . S G x
A minimum coolant temperature may be set for the power feed of
catenary sections situated in long tunnels:
076 178 T H ER M : M i n i m u m T e m p e r a t.SG x
The following parameter has been deleted:
072 178 T H ER M : Bl k fo r C T A F a i l SG x
CBM Circuit breaker monitoring, function group CBM, has been implemented.
The permitted remaining number of CB operations at nominal current is
calculated and presented phase selectively and within the framework of
CB state evaluation according to the settable circuit breaker wear
characteristic.
The disconnection currents (ruptured current, and also its square) and
the current-time area integrals for each disconnection are phase-
selectively evaluated and accumulated.
Version Changes
mA_OP The listing of possible entries for the analog measured data output with
either BCD or 20 mA (outputs A-1 & A-2) has been extended.
The following measured values may now be additionally output:
005 004 MAIN: L o a d I m p e d a n c e Z p . u
005 005 MAIN: L o a d I m p e d Z P r i m .
005 000 MAIN: L o a d I m p e d a n c e Z S e c
005 196 MAIN: L o a d R e a c t X P r i m .
005 195 MAIN: L o a d R e a c t a n c e X S e c
005 198 MAIN: L o a d R e s i s t . R P r i m .
005 197 MAIN: L o a d R e s i s t . R S e c
004 053 MAIN: R e a c . Po w e r Q p .u .
004 052 MAIN: R e a c . Po w e r Q p r i m .
004 070 MAIN: F r e q u e n c y f p . u .
004 166 MAIN: L o a d F l o w D i r e c t i o n
004 167 MAIN: L o a d A n g l e p h i
004 078 MAIN: L o a d A n g l e p h i p . u .
004 113 MAIN: Vo l t a g e V p . u .
004 112 MAIN: Vo l t a g e V P r i m .
004 111 MAIN: C u r r e n t I p .u .
004 110 MAIN: C u r r e n t I Pr i m .
004 051 MAIN: Ac ti ve Po w e r P p .u .
005 040 MAIN: Ac ti ve Po w e r P Pr i m .
004 054 MAIN: Ac ti ve Po w e r F a c to r
009 087 CBM: I * t C a t
009 061 CBM: I* t C a t
009 088 CBM: I * t F d r
009 062 CBM: I* t F d r
009 071 CBM: I t r i p C a t
009 047 CBM: Itr i p C a t
009 073 CBM: I t r i p F d r
009 048 CBM: Itr i p C a t
009 077 CBM: I t r i p * * 2 C a t
009 051 CBM: Itr i p * * 2 C a t
009 078 CBM: I t r i p * * 2 F d r
009 052 CBM: Itr i p * * 2 C a t
009 212 CBM: Itr i p ,Pr i m C a t
009 213 CBM: Itr i p ,Pr i m F d r
004 221 RTDmA: T e m p e r a tu r e p .u .
004 022 FT_DA: F a u l t L o c a ti o n
004 027 FT_DA: F a u l t L o c a t. Pe r c e n t
004 177 FT_DA: Id fr s t p .u .
004 176 FT_DA: F a u l t Im p e d a n c e , P r i m
004 023 FT_DA: F a u l t Im p e d a n c e , S e c .
004 029 FT_DA: F a u l t R e a c ta n c e ,Pr i m
004 028 FT_DA: F a u l t R e a c ta n c e ,Se c .
004 026 FT_DA: F a u l t Vo l t a g e p . u .
004 025 FT_DA: F a u l t C u r r e n t p .u .
004 023 FT_DA: F a u l t L o o p A n g l e
004 198 FT_DA: F a u l t D e te r m i n a ti o n
004 178 THERM: C o o l a n t T e m p . p .u .
004 179 THERM: O b j e c t T e m p . p .u .
004 017 THERM: T h e r m . R e p l i c a p .u .
Version Changes
P438-302-403/404/405-607 Hardware The device’s case size 40TE has been released.
Released: 01.06.2006 Binary signal inputs with a higher switching threshold are now available.
Installation is only recommended if the application specifically requires
such binary signal inputs.
Diagram The new terminal connection diagram is now available for device variant
40TE.
Designation texts for binary signal inputs and output relays have been
changed to comply to the Px3x standard, i.e. a designation is now made
up out of the slot number (1 or 2 digits) and a listing number (2 digits).
Example: K2001 instead of K201 (= first output relay at slot number 20).
These new connection diagrams are now valid:
P438.403 (for 40TE case,
transformer module: ring-terminal connection
other modules: pin-terminal connection)
P438.404 (for 84TE case, with pin-terminal connection)
P438.405 (for 84TE case, with ring-terminal connection)
Software
OUTP Bug fixing:
Up to version –606 it was not possible to check the function of output
relay -K208 (now –K2008) during a relay test run.
CBF: The designation for this signal has been altered:
Old designation: 0 3 9 0 0 0 C B F : C B f a i l u r e
New designation: 0 3 9 0 0 0 C B F : C B S u p e r v . S i g n a l
The 036 017 C BF : C B F a i l u r e multiple signal is now generated as a
spontaneous signal when a trip signal is triggered on the back-up CB or
the upstream CB. This new multiple signal is transmitted using the
IEC 60870-5-103 communication protocol as follows:
Type: 8A, Inf: 80
ASDU: 2, GA: No
CBM Two independent correction values are now available in order to
determine the trip time. Timing tolerances caused by leading or lagging
auxiliary contacts on the CB may now be compensated by applying
parameter 022 018 C BM : C o r r . Ac q u .T .C B Si g . A time-delay
between the internal forming of the trip command and the actual opening
of the CB contacts may now be set at 022 153 C BM : C o r r .
Acqu.T. Trip.
LIMIT: The new 041 043 L IM IT : N o t R e a d y signal now indicates that the
function has been globally enabled but that it has not been enabled in the
active setting group itself. This new multiple signal is transmitted using
the IEC 60870-5-103 communication protocol as follows:
Type: 8A, Inf: 3D
ASDU: 1, GA: Yes
Version Changes
P438-302-403/404/405-608 Hardware No changes
Released: 28.03.2007 Diagram No changes
Software
MAIN The primary source for date and time synchronization may now be
selected. Available are COMM1, COMM2/PC, IRIG-B or a binary input
for minute signal pulses. Available are COMM1, COMM2/PC, IRIG-B or a
binary input for minute signal pulses. Additionally a back-up source can
now be selected.
M AIN : Pr i m .So u r c e T i m e Syn c (103 210)
M AIN : Ba c k u p So u r c e T i m e Syn c (103 211)
COMM2/PC With the new C O M M 2 : Po s i ti ve Ac k n . F a u l t setting (103 203) it is
possible to set whether or not faults can be acknowledged positively after
transmission (and consequently deleted from the fault overview at the
COMM2/PC interface).
MAIN Bug fixing:
Up to version –607 a faulty triggering of inrush stabilization was
observed when major current variations occurred.
An external blocking feature for inrush stabilization has been
implemented:
MAIN: Block.Inrush RstrEXT (039 169)
A maximum hold-time for inrush stabilization has been implemented:
M AIN : t L i ft In r .R s tr . SG x (019 001, 019 002, 019 003, 019 004)
C&VTS Bug fixing:
Up to version –607 triggering of the voltage-measuring-circuit monitoring
was cancelled when the overcurrent functions DTOC and IDMT had
been started.
Version Changes
P438-303-406/407/408-610 Hardware For all model versions there is now a variant available that features an
optional extended detachable, serially-connected, HMI and provides the
Released: 12.03.2008
following new functions:
6 freely configurable function keys as well as 6 freely configurable
LED indicators (H 18 to H 23) each situated next to a function key.
The freely configurable LED indicators (H 4 to H 16 and H 18 to
H 23) are provided as multi-color LEDs.
To disconnect inductive loads there is a module available with 4 heavy-
duty contacts fitted to slot 10 on the 40TE case or slot 18 on the 84TE
case devices.
The new Ethernet communications module for communication per
IEC 61850 is now available and may be fitted to slot 2 as an alternative
to communication module A. For the optical interface (100 Mbit/s) on the
Ethernet communications module the user may either select the ordering
option ST connector or SC connector.
Diagram The updated terminal connection diagrams include the wiring
configuration for the new heavy-duty binary I/O module as well as the
new Ethernet communications module.
The following numbers have been generated for the new terminal
connection diagrams:
P438.406 (for 40TE case, pin-terminal connection)
P438.407 (for 84TE case, pin-terminal connection)
P438.408 (for 84TE case, ring-terminal connection)
Software Note:
Software version -610 is compatible with all previous hardware releases.
DVICE As the new detachable serial HMI is now available, the following
parameters have been added:
D VIC E: SW Ve r s i o n D H M I (002 131)
DVICE: SW Version DHMI DM (002 132)
The order numbers:
DVICE: AFS Order No. (001 000)
DVICE: PCS Order No. (001 200)
may now be entered as an alphanumeric variable
containing up to 20 characters.
LED The new detachable, serially-connected, HMI provides the following
extended display functions:
The operating mode for the LED indicators has been extended by
the operating mode LED flashing.
Two differing signals may now be assigned to the freely configurable
LED indicators (H 4 to H 16 and H 18 to H 23) to emit either red or
green light. If both assigned signals are active the resulting LED
color will be 'amber' (yellow).
Configuration, operating mode and physical state of the permanently
configured LED indicators H 1 and H 17 are now displayed via
configuration parameters and physical state signals.
Version Changes
F_KEY The new detachable serial HMI provides 6 freely configurable function
keys operated either as a key or switch Each function key is provided
with configurable password protection.
HMI As the new detachable, serially-connected, HMI is now available and its
presence is indicated by this additional device identification parameter:
H M I: L o c a l H M I Exi s ts (221 099).
The setting range for parameter
H M I : F c t . R e a d K e y (080 110)
has been extended. Instead of selecting only one assigned protocol by
pressing the "READ" key there are now up to 16 different addresses
assigned which can be triggered in sequence by repeated pressing of
the "READ" key (menu jump function).
Now it is possible to configure two menu jump lists:
H M I : F c t . M e n u J m p L i s t 1 (030 238)
H M I : F c t . M e n u J m p L i s t 2 (030 239)
These menu jump lists make it possible to select individual menu points
(e.g. set values, counters, triggering functions, event logs) in a freely
configurable sequence via function keys, binary signal inputs etc.
CHECK The outputs of Boolean equations 30, 31 and 32 may now be used to
form specific alarm signals.
IEC Initial implementation of the IEC 61850 communication protocol.
GSSE In conjunction with the IEC 61850 communication protocol a
communication procedure has been implemented that is compatible with
previous UCA2 GOOSE for the exchange of binary information within an
Ethernet network section.
GOOSE For the exchange of binary information in an Ethernet network section
the IEC 61850 communication procedure (IEC-GOOSE) has been
implemented.
HMI / Corresponding binary signal inputs (if previously unavailable) are
MAIN assigned to all default reset functions. Together with the already
identified configuration options these binary input functions are now
made available in a configuration list for the two newly implemented
group resetting functions as well as the extended functional assignment
for the "CLEAR" key ('C'):
M AIN : F c t.As s i g n . R e s e t 1 (005 248)
M AIN : F c t.As s i g n . R e s e t 2 (005 249)
H M I: F c t. R e s e t Ke y (005 251)
Version Changes
MAIN The primary source for date and time synchronization may now be
selected. Available are COMM1, COMM2/PC, IRIG-B or a binary input
for minute signal pulses. Available are COMM1/IEC, COMM2/PC, IRIG-
B or a binary input for minute signal pulses. Additionally a back-up
source can now be selected. Switching over to the back-up source will
occur according to a settable monitoring time period:
M AIN : Pr i m . So u r c e T i m e Syn c (103 210)
M AIN : Ba c k u p So u r c e T i m e Syn c (103 211)
M AIN : T i m e Syn c . T i m e - O u t (103 212)
Version Changes
P438 -304 Hardware No changes
-409/410/411
-611-709 Diagram No changes
Version Changes
RECLS The voltage criterion for a reclose command to be issued after the
maximum dead time period (015 128) has been extended.
CBF The CB trip monitoring function has been removed from the circuit
breaker failure protection. The function will now be enabled only if no trip
command has been issued by the protection device.
P438-305-409/410/411-613 Hardware As an option the processor module with an integrated DSP coprocessor
is now available. This module offers an enhanced feature and the high-
Released: 14.09.2009
speed processing of the device’s additional functions. Such high-speed
processing is the pre-condition for the successful application of the new
high impedance protection function (DELTA).
Diagram No changes
Software Note:
Software version -613 is compatible with all previous hardware releases.
Some of the functional enhancements are only visible and available if the
optional processor module with an integrated DSP coprocessor is fitted.
HMI The functional assignment for the "CLEAR" key ('C') has been extended.
The reset of the reclaim time for the RECLS function at parameter
R EC L S: R e s e t R e c l .T i m e 2 EXT (036 223) may now be selected
from the selection table for H M I: F c t. R e s e t Ke y (005 251).
F_KEY The default setting of passwords for the function keys have been
changed. Now no password entry is required when a function key is
pressed.
Enabling a password may still be configured for each function key.
MAIN When the optional processor module with an integrated DSP
coprocessor is fitted the second, third and fifth harmonic current
components are determined and issued as measured operating data.
The following measured values are now additionally available
MAIN: Current I(2fn) Prim (008 095)
MAIN: Current I(3fn) Prim (008 097)
MAIN: Current I(5fn) Prim (008 099)
MAIN: Current I(2fn) p.u. (008 096)
MAIN: Current I(3fn) p.u. (008 098)
MAIN: Current I(5fn) p.u. (008 100)
Version Changes
The inrush stabilization has been extended by the addition of the high
impedance protection function blocking (DELTA, only when the optional
processor module with an integrated DSP coprocessor is fitted).
The voltage memory function is now comprehensively available for the
distance protection function and the directional overcurrent stages.
The following signals have been shifted within the function groups:
Previously: D IST : tVm e m o r y Ac ti ve (040 034)
Now: M AIN : tVm e m o r y Ac ti ve (040 034)
Synchronization of the voltage memory is now terminated by a General
Start.
OSCIL The selection of starting conditions for fault recording has been extended
by the conditions for enabling, starting and tripping from the high
impedance protection function (DELTA, only when the optional processor
module with an integrated DSP coprocessor is fitted).
FT_DA The setting of the fault location determination has been extended.
Line reactance and line length can now be configured in 10 successive
sections.
DELTA The DELTA function group has been implemented. This function is
available only when the optional processor module with an integrated
DSP coprocessor is fitted.
High impedance errors are detected by sudden current change
monitoring and stabilized by monitoring odd-numbered harmonic current
components. Additional stabilization by sudden angle change monitoring
or reactance limits can be configured.
DIST The accuracy of timer stages of individual zones has been enhanced.
Load blinding has be extended to the polygonal (quadrilateral) tripping
characteristics. Angle Alpha and reactance limit Rg can now be used to
set this feature. Up to the previous version these parameters were
available only for the circular characteristic.
The following parameters have been renamed:
Previously: DIST: Rgy Circle Fwd SGx
Now: D IST : R g y, F o r w a r d SG x
Previously: DIST: Rgy Circle Rev SGx
Now: D I S T : R g y, R e ve r s e S G x
Previously: D I S T : a l p h a y ( C i r c l e ) F w d S G x
Now: DIST: Alpha y SGx
The visibility control for circular characteristics has been cancelled.
The D IST : C i r c l e C h a r Ava i l a b . (022 001) parameter has been
removed.
A fourth distance stage with train start-up detection dx/dt has been
implemented.
Version Changes
A visibility control for zones 3 and 4 has been added. Parameters:
D I S T : Z o n e 3 A v a i l a b l e (022 195)
DIST: Zone 4 Available (022 196)
are used to render visible input, output and setting parameters for the
respective zones.
Zones are always without effect unless their respective availability has
been set.
Bug fixing:
Up to the previous version the WPC zone was processed even when the
corresponding availability had been not set.
When the optional processor module with an integrated DSP
coprocessor is fitted then the distance protection measured values (Z, R,
X) may be corrected by harmonics factor kHarm, I(xfn)/I(fn). Distance
zone reaches are reduced dynamically according to the second, third
and fifth harmonic current components.
DTOC / Starting timer stages in the directional mode can now be freely selected.
IDMT It is now possible to select whether a time delay is started when a stage
start is issued or with an additional directional criterion.
Direction determination by overcurrent stages are now stabilized by the
voltage memory function (function group MAIN).
If voltage memory is not enabled a Fault forward decision is issued,
independently of the actual fault direction, when the short-circuit voltages
are < 1.0 V.
A load flow direction is now displayed when the short-circuit direction
determination function is available.
Version Changes
P438-306-412/413/414-6xx This is a test version and for internal purposes only.
Released: —
P438-307-412/413/414-6xx This is a test version and for internal purposes only.
Released: —
P438-305-409/410/411-613 Hardware No changes
-711
Diagram No changes
Software
DIST In the case of load blinder blocking (V < 10V) the evaluation of Rg and
alpha is now skipped.
DELTA Internal use of parameters was optimized.
P438-305-409/410/411-613 Hardware No changes
-713
Diagram No changes
Software
FT_DA The calculation of Vmax now takes into account the feeder mode
(Classic Single Feed or Autotransformer Feed).
OSCIL Bug fixing:
The messages (004 181) F T _ D A : I c a t p . u . ,
(004 182) F T _ D A : I f d r p . u . , (004 183) F T _ D A : V c a t p . u . ,
(004 184) F T _ D A : V f d r p . u . were not written into the buffer.
P438-305-409/410/411-614 This is a test version and for internal purposes only.
Release: ―
Hardware No changes
Diagram No changes
Software
DIST The resolution for the settings of R and Z of zones 3 and 4 has been
reduced from 0.01 Ω to 0.1 Ω.
Version Changes
P438-305-409/410/411-615 Hardware New Schneider-Electric design for the local control panel (HMI).
Diagram No changes
Release: 23.02.2011 Software
PC The following menu point has been removed:
P C : M a n u f a c t u r e r (003 183)
Note:
Compatibility even with older versions of the operating program
continues to be guaranteed.
COMM1 The menu point C O M M 1 : M O D B U S V a r i a n t (003 214) may now
be used to set the MODBUS protocol to the variant Private or
Compatible.
The protocol variant Compatible corresponds to the MODBUS
implementation in the MiCOM Px20 and Px40 protection devices.
The protocol variant Private corresponds to the first implementation of
the MODBUS protocol.
Note:
As before this setting is hidden unless the MODBUS protocol is enabled.
COMM1, The menu points C O M M 1 : M a n u f a c t u r e r (003 161) and
COMM2 C O M M 2 : M a n u f a c t u r e r (103 161) can no longer be set by using a
selection list but, for reasons of compatibility, they may now be defined
as free text. The default is SE but, in individual cases, it may become
necessary to enter texts differing from the default.
Notes:
These parameters can only be set using the operating program and it is
not possible to set them locally using the integrated local control panel
(HMI).
The maximum text length is 8 characters and designations exceeding
this will be truncated.
The parameter C O M M 1 : M a n u f a c t u r e r is hidden unless an
IEC 60870-5 protocol is enabled.
DIST The resolution for the settings of R and Z of zones 3 and 4 has been
reduced from 0.01 Ω to 0.1 Ω. Moreover, the maximum setting value for
the reactance of zones 3 and 4 has been increased from 650 Ω to 750 Ω.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P438/UK M/De7 10/2014
MiCOM P438
P438/EN AD/Af8
Upgrade Documentation
2 P438/EN AD/Af8 // AFSV.12.11390 EN /// P438-308-415/416/417-616
P438, Changes in Software Version -615 to -616
In the new versions of the Rail Catenary Protection Device MiCOM P438,
several enhanced features and changes on existing features have been
included. These are described with reference to the documentation listed
below:
References
Released Version Documentation
23.02.2011 P438 -305 Technical Manual
-409/410/411 P438/UK M/Be7
-615
1 Overview
Version Changes
P438 -305 Hardware No changes.
-409/410/411
-615 -714
Release: 17.08.2011
Diagram No changes.
Software
DIST, HMI Bug fixing:
In the previous version the distance zone settings were
displayed with values one hundred times lower than the actual
values.
P438 -308 Hardware The P438 is now fitted with an improved power supply module.
-415/416/417 Note that the voltage range has changed for DC input:
-616
For the DC / AC variant, the range is now
Release: 07.09.2012 60 … 250 VDC / 100 ... 230 VAC
(previously 48 … 250 VDC / 100 ... 230 VAC).
For the DC-only variant, the range is now
24 … 60 VDC
(previously 24 VDC).
A new communication module (“REB” = “Redundant Ethernet
Board”) is now available as an ordering option. This module
can be used for redundant communication via IEC 61850 and
may be fitted to slot 2, as an alternative to the other
communication modules. The following communication
protocols are supported:
SHP (Self-Healing Protocol).
RSTP (Rapid Spanning Tree Protocol).
DHP (Dual-Homing Protocol).
A detailed description of the module and the appropriate
network connections is available as a separate document
(“Redundant Ethernet Board, Application Guide”).
The binary module X(6I 3O) with 6 binary signal inputs and 3
output relays is now optionally available and may be fitted to
slot 10 (40 TE case) or 18 (84 TE cases).
Diagram The diagrams have been adapted to the new selection of
modules:
P438 -412: Case 40TE,
transformer module for ring-terminal connection,
other modules for pin-terminal connection
P438 -413: Case 84TE, pin terminal connection
P438 -414: Case 84TE, ring terminal connection
Version Changes
Software Note: Software version -616 is compatible with all previous
hardware releases. However, some of the functional
enhancements are only visible and available if the processor
variant with an integrated DSP coprocessor (order option) is
fitted.
IEC Bug fixing:
In a few cases a data change report was not transferred when
a cyclic report was generated at the same time.
FT_DA The determination of the fault location has been enhanced for
the operating mode “Autotransformer feed”. It is now possible
to set the section lengths and reactances separately for the
catenary and the feeder line.
Therefore there are now parameters
F T _ D A : L i n e l e n g t h z - y P S x (for the line feeds z with
z=A / ”catenary line” and z=B / ”feeder line”), instead of the
previously available parameters
F T _ D A : L i n e l e n g t h y P S x (y = 1,…,10). The same
holds for the reactances, so there are now parameters
F T _ D A : L i n e r e a c , s e c z - y P S x instead of the
previously available F T _ D A : L i n e r e a c t , s e c y P S x .
In operating mode “Classic single feed” only the parameters
for line feed A are available.
The new parameter (011 225)
F T _ D A : B l o c k i n g f a u l t l o c . allows for blocking the
determination of the fault location via binary signal, e.g. in
case the autotransformers are still connected.
DIST The parameter (076 132, 077 132, 078 132, 079 132)
D I S T : W P C V < P S x can now be set to Blocked. In this
case, protection against wrong phase coupling is performed
without voltage supervision.
DTOC, Two new DTOC function groups, DTOCA and DTOCB, have
DTOCA, been implemented. These function groups provide a definite
DTOCB time phase current (IA, IB) supervision in the operating mode
“Autotransformer feed”. If the operating mode is set to
“Classic single feed” both function groups are inactive.
The DTOC function group is still available and unchanged. In
both operating modes it supervises the total current
independently of the DTOCx function groups.
The parameters (130 079) D T O C A : B l o c k i n g E X T and
(130 099) D T O C B : B l o c k i n g E X T allow for blocking
these new DTOCx functions, e.g.if the supervision is needed
only in the case of disconnected autotransformers.
Version Changes
IDMT, Two new IDMT function groups, IDMTA and IDMTB, have
IDMTA, been implemented. These function groups provide an inverse-
IDMTB time phase current (IA, IB) supervision in the operating mode
“Autotransformer feed”. If the operating mode is set to
“Classic single feed” both function groups are inactive.
The IDMT function group is still available and unchanged. In
both operating modes it supervises the total current
independently of the IDMTx function groups.
The parameters (130 116) I D M T A : B l o c k i n g E X T and
(130 136) I D M T B : B l o c k i n g E X T allow for blocking these
new IDMTx functions, e.g. if the supervision is needed only in
the case of disconnected autotransformers.
ARC The ARC function group has been extended to include the
new overcurrent supervision functions DTOCx and IDMTx.
Parameter Address
Default Value Min. Max. Unit
Device DVICE: SW vers.Chin.DHMI DM 008 233
Parameter Address
Default Value Min. Max. Unit
Definite-time overcurrent DTOCA: Function group DTOCA 056 079
Note: The function group DTOCA is active only with the setting MAIN: Feeder mode =
Autotransformer feed. It is blocked in case of the setting Classic single feed.
Note: The function group DTOCB is active only with the setting MAIN: Feeder mode =
Autotransformer feed. It is blocked in case of the setting Classic single feed.
Note: The function group IDMTA is active only with the setting MAIN: Feeder mode =
Autotransformer feed. It is blocked in case of the setting Classic single feed.
Note: The function group IDMTB is active only with the setting MAIN: Feeder mode =
Autotransformer feed. It is blocked in case of the setting Classic single feed.
Parameter Address
Default Value Min. Max. Unit
Definite-time overcurrent DTOCA: General enable USER 130 065
protection
Values from table 6, default:
0: No
Enable/disable the definite-time overcurrent protection function for CT A.
Note: The function group DTOCA is active only with the setting MAIN: Feeder mode =
Autotransformer feed. It is blocked in case of the setting Classic single feed.
Note: The function group DTOCB is active only with the setting MAIN: Feeder mode =
Autotransformer feed. It is blocked in case of the setting Classic single feed.
protection
Values from table 6, default:
0: No
Enabling or disabling the inverse-time overcurrent protection function for CT A.
Note: The function group IDMTA is active only with the setting MAIN: Feeder mode =
Autotransformer feed. It is blocked in case of the setting Classic single feed.
Note: The function group IDMTB is active only with the setting MAIN: Feeder mode =
Autotransformer feed. It is blocked in case of the setting Classic single feed.
Parameter Address
Default Value Min. Max. Unit
FT_DA: Line length A-6 PSx 008 131 008 132 008 133 008 134
A maximum of 10 line sections may be defined; line distance and line reactance for line sections
not needed are to be set to Blocked.
FT_DA: Line reac,secA-1 PSx 010 012 010 013 010 014 010 015
Parameter Address
Default Value Min. Max. Unit
FT_DA: Line reac,secA-10PSx 008 187 008 188 008 189 008 190
A maximum of 10 line sections may be defined; line distance and line reactance for line sections
not needed are to be set to Blocked.
FT_DA: Line length B-1 PSx 011 145 011 146 011 147 011 148
A maximum of 10 line sections may be defined; line distance and line reactance for line sections
not needed are to be set to Blocked.
Parameter Address
Default Value Min. Max. Unit
FT_DA: Line reac,secB-1 PSx 011 185 011 186 011 187 011 188
Parameter Address
Default Value Min. Max. Unit
FT_DA: Line reac,secB-10PSx 011 221 011 222 011 223 011 224
A maximum of 10 line sections may be defined; line distance and line reactance for line sections
not needed are to be set to Blocked.
Note: Valid only with setting MAIN: Feeder mode = Autotransformer feed.
Auto-reclosing control ARC: HSR-tr.DTOCA tI> PSx 015 196 020 196 021 196 023 196
Note: The function groups DTOCA and DTOCB analyze only CT A or CT B, respectively, and
therefore they are active only with the setting MAIN: Feeder mode = Autotransformer feed. It is
blocked in case of the setting Classic single feed.
ARC: HSR-tr.IDMTAkIrefPSx 015 217 020 217 021 217 023 217
Note: The function groups IDMTA and IDMTB analyze only CT A or CT B, respectively, and
therefore they are active only with the setting MAIN: Feeder mode = Autotransformer feed. It is
blocked in case of the setting Classic single feed.
ARC: TDR-tr.DTOCA tI> PSx 015 198 020 198 021 198 023 198
Parameter Address
Default Value Min. Max. Unit
ARC: TDR-tr.DTOCB tI>>PSx 015 216 020 216 021 216 023 216
Note: The function groups DTOCA and DTOCB analyze only CT A or CT B, respectively, and
therefore they are active only with the setting MAIN: Feeder mode = Autotransformer feed. It is
blocked in case of the setting Classic single feed.
ARC: TDR-tr.IDMTAkIrefPSx 015 218 020 218 021 218 023 218
Note: The function groups IDMTA and IDMTB analyze only CT A or CT B, respectively, and
therefore they are active only with the setting MAIN: Feeder mode = Autotransformer feed. It is
blocked in case of the setting Classic single feed.
Definite-time overcurrent DTOCA: Enable PSx 130 060 131 060 132 060 133 060
protection
Values from table 6, default:
0: No
DTOCB: Enable PSx 130 080 131 080 132 080 133 080
DTOCA: I> PSx 130 061 131 061 132 061 133 061
DTOCA: I>> PSx 130 062 131 062 132 062 133 062
DTOCA: tI> PSx 130 063 131 063 132 063 133 063
Parameter Address
Default Value Min. Max. Unit
DTOCA: tI>> PSx 130 064 131 064 132 064 133 064
Inverse-time overcurrent IDMTA: Enable PSx 130 100 131 100 132 100 133 100
protection
Values from table 6, default:
0: No
IDMTB: Enable PSx 130 120 131 120 132 120 133 120
IDMTA: Iref PSx 130 101 131 101 132 101 133 101
IDMTA: Characteristic PSx 130 102 131 102 132 102 133 102
IDMTA: Char. factor kt PSx 130 103 131 103 132 103 133 103
IDMTA: Min. trip time PSx 130 104 131 104 132 104 133 104
Parameter Address
Default Value Min. Max. Unit
IDMTA: Hold time PSx 130 105 131 105 132 105 133 105
IDMTA: Reset PSx 130 106 131 106 132 106 133 106
DIST: WPC V< PSx 076 132 077 132 078 132 079 132
Parameter Address
Default Value Min. Max. Unit
Fault data acquisition FT_DA: Blocking fault loc. 011 225
Note: FT_DA: Fault location A, FT_DA: Fault location B are available only with the setting
MAIN: Feeder mode = Autotransformer feed.
protection
Values from table 6, default:
0: No
DTOCB: Blocking EXT 130 099
Note: Blocking DTOCx via binary input signal can be required, e.g. for the case that the
overcurrent supervision is needed only in case of disconnected autotransformers.
Parameter Address
Default Value Min. Max. Unit
DTOCA: Blocking tI> EXT 130 066
Note: The function groups DTOCx are never ready with the setting MAIN: Feeder mode = Classic
single feed.
Parameter Address
Default Value Min. Max. Unit
DTOCB: Starting I> 130 089
protection
Values from table 6, default:
0: No
IDMTB: Block. tIref> EXT 130 128
Note: Blocking IDMTx via binary input signal can be required, e.g. for the case that the
overcurrent supervision is needed only in case of disconnected autotransformers.
Parameter Address
Default Value Min. Max. Unit
IDMTA: Not ready 130 117
Note: The function groups IDMTx are never ready with the setting MAIN: Feeder mode = Classic
single feed.
Parameter Address
Default Value Min. Max. Unit
FT_DA: Fault current A p.u. 004 181
Note: This measurement value is available only with the setting MAIN: Feeder mode =
Autotransformer feed.
Note: This measurement value is available only with the setting MAIN: Feeder mode =
Autotransformer feed.
Parameter Address
Default Value Min. Max. Unit
FT_DA: Fault imped.,pri A 235 207
Note: This measurement value is available only with the setting MAIN: Feeder mode =
Autotransformer feed.
Note: This measurement value is available only with the setting MAIN: Feeder mode =
Autotransformer feed.
Note: This measurement value is available only with the setting MAIN: Feeder mode =
Autotransformer feed.
Parameter Address
Default Value Min. Max. Unit
FT_DA: Fault loc. percent A 235 204
Note: This measurement value is available only with the setting MAIN: Feeder mode =
Autotransformer feed.
Note: This measurement value is available only with the setting MAIN: Feeder mode =
Autotransformer feed.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P438/EN AD/Af8 09/2012
Customer Care Centre
http://www.schneider-electric.com/CCC
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P438/EN M/Cf8 Version: -615 -616 10/2014