INTRODUCTION: The function of BFP is to transfer the condensate water from deaerator to
the economizer. There are three pumps (1*50% capacity MDBFP) & (2*50% capacity TDBFP).
15 Weight kg 37000
16 Cooling method air-water
17 Rotating(From Motor to pump) Clockwise
3|Page
7 Pump suction Filter drain and pump casing drains are closed
after proper draining.
5|Page
8 Main and booster pump discharge vent are crack open and
close it only after water comes properly through it.
9 HPH’s tube side vent are crack open and close it only after
water comes properly.
11 Lube oil cooler and working oil cooler, oil and water line
normalized or not.
17 Motor cooler cooling water line and bearing lube oil line
normalized.
6|Page
OPERATING PROCEDURE -
Sr. RESPONSIBILITY
Description
No. UCE DE FE EE
START PERMISSIVE :
7|Page
1. PLANNED SHUTDOWN :
3 AOP will start in auto(At Lube Oil Pressure 0.1Mpa,),If AOP not start √
in auto start manually.
4 When M-BFP is running,M-BFBP outlet feed water flow low low and
M-BFP minimum flow recirculation valve position<60%, delay 8s
9|Page
INTERLOCKS : Remarks
1 Interlock will stop the auxiliary oil pump when M-BFP is running and
M-BFP hydraulic coupler header lube oil pressure>0.22Mpa(delay
30s)
10 | P a g e
2 Interlock will start the MDBFP auxiliary oil pump when interlock is cut
in and any of below conditions occurs
a). MDBFP hydraulic coupler header lube oil pressure<0.15Mpa
b). MDBFP stops
3 If MDBFP trips (1MDBFP & 1 TDBFP running), then runback will act
and load will come to 180 MW and all superheater spray valve will
close.
4 When interlock is cut in and any T-BFP trips, interlock will start MD-
BFP
5 When MDBFP is at stopping status, the MDBFP inlet motorized valve
will be closed
6 Interlock will open the MDBFP inlet motorized valve when MDBFP in
interlock
7 When MDBFP stops, interlock will close the MDBFP outlet motorized
valve
8 Interlock will open the MDBFP outlet motorized when MDBFP in
interlock
ABBREVIATIONS / NOTATIONS:-
o SOP: Standard Operating Procedure
o UCE: Unit Control Engineer
o DE: Desk Engineer
o FE: Field Engineer
o DCS: Distributed Control System
o EE: Electrical Shift Engineer
o MFT: Main Fuel Trip.
o RB : Run Back