Environmental Associates Limited: A Summary of The Effluent Treatment
Environmental Associates Limited: A Summary of The Effluent Treatment
Environmental Associates Limited: A Summary of The Effluent Treatment
LIMITED
Page 1 of 11
Contents
1. Dissolved Air Floatation Clarifier........................................................................................................... 3
2. DAF Microbubble Generator................................................................................................................. 5
3. Multi- Media Treatment Unit ............................................................................................................... 7
4. Pre-treatment Retension Unit .............................................................................................................. 9
5. Diesel Engine Power Generators ........................................................................................................ 10
6. Recovered Oil Storage Skip ................................................................................................................. 11
Page 2 of 11
1. Dissolved Air Floatation Clarifier
The Dissolve Air Floatation Clarifier is a vertical cylinder of Stainless steel material
for the seperation and removal of Fats, Oil, Grease and other suspended materials from
the Produce Water. The separation is through Floatation by Dissolved Air Produced by
a Microbubble Generator and the removal is through a Skimming mechanism at the
top of the Clarifier.
Page 3 of 11
Specifications of the DAF Clarifier
Height = 20 ft
Legnth = 8ft
Width = 8ft
Base Width = 11ft by 11ft
Tare weight = 7 tons
Tank Volume = 20,000 litre (118 bbls)
Magnetic Level control switch
Tank level Indicator
Tube Skimmer for Oil Recovery
25 hp Produce Water Pump
Power Requirement
3 Phase, 15kw (25 hp) / 50/60 Hz, (17 Amps at 400kva)
Page 4 of 11
2. DAF Microbubble Generator
Page 5 of 11
Specifications of the Microbubble Generator
• Model: KTM80F
• height= 7ft. length= 6ft, width=4ft
• weight= 2.0 tons
• Wetted Part Material: Cast Iron / SS
• Pressurised Water Flow Rate: 254GPM = 967L/min = 58.0m3 /h= 11,611bbl/d
= 484bbl/h
• Max. Pressure = 65psi
• Air Flow Rate: 77NL/min, 4.64Nm3/h, 20NGPM
• Required Motor Power kW (HP): 30kW (40HP), 4-Pole
• Discharge pressure setting is in the range from 3 bar to 4 bar ( 43.5 to 58psi)
• Suction pressure setting in in the minus range from - 0.2 to -0.3 bar
Power Requirement
3 Phase, 30kw (40 hp) / 50/60 Hz, (27 Amps at 400kva)
Page 6 of 11
3. Multi- Media Treatment Unit
This unit is the Secondary stage for the clarification / treatment of the effluent Water
through the process of Filtration, Absorption, Adsorption and biochemical transformation
to further eliminate traces or residual contaminants (eg FOG) and to recondition the
treated effluent before discharge
Page 7 of 11
Specifications of the Multi-Media Treatment Unit
Dimensions
Height = 10ft
Lenght = 7ft
Width = 4ft
Weight = 2 tons
Max. Pressure = 150 psi
Power Requirement
3 Phase, 30kw (40 hp) / 50/60 Hz, (27 Amps at 400kva)
Page 8 of 11
4. Pre-treatment Retension Unit
This unit is a horizontal cylinder of Stainless steel material with 2 Compartments. One
Compartment is for receiving and conditioning the raw effluent prior to transfer into the
Clarifier and the second Compartment is for receiving and conditioning the Clarified
water from the Clarifier
Page 9 of 11
5. Diesel Engine Power Generators
The entire effluent treatment system will be ran by 2 Diesel Engine Powered Electric
Generators
Model:
250kva Scania Engine (3 phase, 50/60Hz, 400volts Alternator)
220kva Perkins Engine (3 phase, 50/60Hz, 400volts Alternator)
Dimensions
Height = 8 ft
Legnth = 14 ft
Width = 6ft
Weight = 5 tons
Page 10 of 11
6. Recovered Oil Storage Skip
The recovered Oil Skip, as shown below will be for the temporary storage of skimmed
oil from the Clarifier
Dimensions
Height = 4 ft
Legnth = 6 ft
Width = 4ft
Weight = 1.3 tons