Agc-4 DRH 4189340686 Uk
Agc-4 DRH 4189340686 Uk
Agc-4 DRH 4189340686 Uk
• Functional description
• Display unit and menu structure
• PID controller
• Procedure for parameter setup
• Parameter list
3. Functional descriptions
3.1 Standard functions................................................................................................................................................................................................................. 12
3.1.1 Standard functions.......................................................................................................................................................................................................... 12
3.1.2 Operation modes............................................................................................................................................................................................................. 12
3.1.3 Engine control................................................................................................................................................................................................................... 12
3.1.4 Generator protection (ANSI)....................................................................................................................................................................................... 12
3.1.5 Busbar protection (ANSI)............................................................................................................................................................................................. 12
3.1.6 Display..................................................................................................................................................................................................................................13
3.1.7 M-Logic................................................................................................................................................................................................................................ 13
3.2 Terminal strip overview........................................................................................................................................................................................................ 13
3.2.1 Slot #1, #2, #5 and #6................................................................................................................................................................................................... 14
3.2.2 Slot #3, #4, #7 and #8................................................................................................................................................................................................... 15
3.3 Measurement systems..........................................................................................................................................................................................................15
3.3.1 Three-phase system.......................................................................................................................................................................................................16
3.3.2 Split phase system.......................................................................................................................................................................................................... 16
3.3.3 Single phase system...................................................................................................................................................................................................... 17
3.4 Nominal settings...................................................................................................................................................................................................................... 17
3.4.1 Nominal settings...............................................................................................................................................................................................................17
3.4.2 Switch between the nominal settings...................................................................................................................................................................... 18
3.4.3 Scaling..................................................................................................................................................................................................................................19
3.5 Applications............................................................................................................................................................................................................................... 20
3.5.1 Applications and genset modes................................................................................................................................................................................ 20
3.5.2 AMF (no back synchronisation)................................................................................................................................................................................. 21
3.5.3 AMF (with back synchronisation).............................................................................................................................................................................. 21
3.5.4 Island operation................................................................................................................................................................................................................ 22
3.5.5 Power ramp........................................................................................................................................................................................................................ 22
3.5.6 Q ramp................................................................................................................................................................................................................................. 24
3.5.7 Fixed power/base load.................................................................................................................................................................................................. 24
3.5.8 Warm up ramp.................................................................................................................................................................................................................. 25
6. Additional functions
6.1 Start functions...........................................................................................................................................................................................................................92
6.1.1 Digital feedbacks..............................................................................................................................................................................................................92
6.1.2 Analogue tacho feedback.............................................................................................................................................................................................93
6.1.3 Oil pressure........................................................................................................................................................................................................................ 94
6.1.4 Double starter....................................................................................................................................................................................................................95
6.2 Breaker functions.................................................................................................................................................................................................................... 96
6.2.1 Breaker types.................................................................................................................................................................................................................... 96
6.2.2 Breaker position failure................................................................................................................................................................................................. 97
6.2.3 Breaker spring load time...............................................................................................................................................................................................97
6.2.4 Breaker spring load time Principle............................................................................................................................................................................98
6.2.5 Racked out breaker........................................................................................................................................................................................................ 99
6.3 Alarm inhibit............................................................................................................................................................................................................................ 101
6.3.1 Run status (6160)......................................................................................................................................................................................................... 102
6.4 Access lock.............................................................................................................................................................................................................................. 103
6.5 Overlap....................................................................................................................................................................................................................................... 103
6.6 Digital mains breaker control......................................................................................................................................................................................... 104
6.7 Command timers................................................................................................................................................................................................................... 105
6.8 Running output...................................................................................................................................................................................................................... 105
6.9 Frequency-dependent droop.......................................................................................................................................................................................... 106
6.9.1 Frequency-dependent droop.................................................................................................................................................................................... 106
6.10 Power and cos phi offsets.............................................................................................................................................................................................108
7. Protections
7.1 Voltage-dependent (restraint) over-current............................................................................................................................................................ 178
8. PID controller
8.1 Description of PID controller.......................................................................................................................................................................................... 179
8.2 Controllers................................................................................................................................................................................................................................ 179
8.3 Principle drawing.................................................................................................................................................................................................................. 180
8.4 Proportional regulator........................................................................................................................................................................................................180
8.4.1 Speed range....................................................................................................................................................................................................................180
8.4.2 Dynamic regulation area............................................................................................................................................................................................ 181
8.4.3 Integral regulator........................................................................................................................................................................................................... 181
8.4.4 Derivative regulator...................................................................................................................................................................................................... 182
8.5 Load share controller......................................................................................................................................................................................................... 183
8.6 Synchronising controller.................................................................................................................................................................................................. 184
8.7 Relay control........................................................................................................................................................................................................................... 184
8.7.1 Relay adjustments........................................................................................................................................................................................................ 185
8.7.2 Signal length................................................................................................................................................................................................................... 185
8.8 Droop mode............................................................................................................................................................................................................................. 186
8.8.1 Principle and setup....................................................................................................................................................................................................... 186
8.8.2 Voltage droop example............................................................................................................................................................................................... 187
8.8.3 High droop setting.........................................................................................................................................................................................................187
8.8.4 Low droop setting..........................................................................................................................................................................................................188
8.8.5 Compensation for isochronous governors..........................................................................................................................................................188
10. Synchronisation
10.1 Synchronisation principles...........................................................................................................................................................................................207
10.2 Dynamic synchronisation..............................................................................................................................................................................................207
10.2.1 Close signal.................................................................................................................................................................................................................. 208
10.2.2 Load picture after synchronising.......................................................................................................................................................................... 208
10.2.3 Adjustments.................................................................................................................................................................................................................. 209
10.3 Static synchronisation.................................................................................................................................................................................................... 210
10.3.1 Phase controller...........................................................................................................................................................................................................211
10.3.2 Close signal...................................................................................................................................................................................................................211
10.3.3 Load picture after synchronisation...................................................................................................................................................................... 212
10.3.4 Adjustments.................................................................................................................................................................................................................. 212
10.4 Close before excitation................................................................................................................................................................................................... 213
10.4.1 Flowchart 1, GB handling........................................................................................................................................................................................214
10.4.2 Flowchart 2, TB handling (option G5)................................................................................................................................................................ 215
10.4.3 Genset start actions.................................................................................................................................................................................................. 215
10.4.4 Breaker sequence...................................................................................................................................................................................................... 216
10.4.5 "Close before excitation" failure........................................................................................................................................................................... 217
10.4.6 Close before excitation – additional control parameters............................................................................................................................217
10.5 Separate synchronising relay..................................................................................................................................................................................... 219
10.6 Inhibit conditions before synchronising mains breaker.............................................................................................................................. 220
Throughout this document, a number of warnings and notes with helpful user information will be presented. To ensure that these are
noticed, they will be highlighted as follows in order to separate them from the general text.
Warnings
DANGER!
This highlights dangerous situations. If the guidelines are not followed, these situations could result in death, serious
personal injury, and equipment damage or destruction.
CAUTION
This highlights potentially dangerous situations. If the guidelines are not followed, these situations could result in personal
injury or damaged equipment.
Notes
INFO
Notes provide general information, which will be helpful for the reader to bear in mind.
DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the
engine/generator controlled by the Multi-line 2 unit, the company responsible for the installation or the operation of the set must be
contacted.
INFO
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
The English version of this document always contains the most recent and up-to-date information about the product. DEIF does not
take responsibility for the accuracy of translations, and translations might not be updated at the same time as the English document.
If there is a discrepancy, the English version prevails.
Installing and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore, the installation should
only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment.
DANGER!
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury
or death.
Sufficient care must be taken to protect the terminal against static discharges during the installation. Once the unit is installed and
connected, these precautions are no longer necessary.
The Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average values and are not
necessarily the correct settings for matching the engine/generator set in question. Precautions must be taken to check the settings
before running the engine/generator set.
This Designer's Reference Handbook mainly includes functional descriptions, presentation of display unit and menu structure,
information about the PID controller, the procedure for parameter setup and reference to parameter lists.
The general purpose of this document is to provide useful overall information about the functionality of the unit and its applications.
This document also offers the user the information he needs in order to successfully set up the parameters needed in his specific
application.
CAUTION
Read this document before starting to work with the Multi-line 2 unit and the genset to be controlled. Failure to do this could
result in human injury or damage to the equipment.
This Designer's Reference Handbook is mainly intended for the panel builder designer in charge. On the basis of this document, the
panel builder designer will give the electrician the information he needs in order to install the Multi-line 2 unit, for example detailed
electrical drawings. In some cases, the electrician may use these installation instructions himself.
This document is divided into chapters, and in order to make the structure simple and easy to use, each chapter will begin from the
top of a new page.
2.1 Introduction
This chapter will deal with the unit in general and its place in the DEIF product range.
The AGC is part of the DEIF Multi-line 2 product family. Multi-line 2 is a complete range of multi-function generator protection and
control products integrating all the functions you need into one compact and attractive solution.
The concept of the AGC is to offer a cost-effective solution to genset builders, who need a flexible generator protection and control
unit for medium to large genset applications. Being part of the Multi-line product family, the standard functions can be supplemented
with a variety of optional functions.
It contains all necessary 3-phase measuring circuits, and all values and alarms are presented on the LCD display.
2.3 Options
2.3.1 Options
The Multi-line 2 product range consists of different basic versions which can be supplemented with the flexible options needed to
provide the optimum solution. The options cover e.g. various protections for generator, busbar and mains, voltage/VAr/PF control,
various outputs, power management, serial communication, additional operator display, etc.
INFO
A complete list of available options is included in the data sheet. Please see www.deif.com
CAUTION
It is possible to remote-control the genset from the PC utility software or M-Vision by use of a modem. To avoid personal
injury, make sure that it is safe to remote-control the genset.
This chapter includes functional descriptions of standard functions as well as illustrations of the relevant application types.
Flowcharts and single-line diagrams will be used in order to simplify the information.
• Start/stop sequences
• Run and stop coil
• Relay outputs for governor control
• 3 × over-voltage (59)
• 4 × under-voltage (27)
• 3 × over-frequency (81)
• 4 × under-frequency (81)
• Voltage unbalance (60)
3.1.7 M-Logic
Refer to the data sheet for accurate information about possible configurations for the AGC.
Refer to the input/output lists in the installation instructions for detailed information about the I/Os of the specific
options.
INFO
The hardware shown in slot #3 is option M12 and G3. For a detailed description of these options, please refer to the option
descriptions.
INFO
The settings can be changed using the display. Press the JUMP push-button and go to menu 9130 or use the USW.
The menu for adjustment of the measurement principle looks like this:
multi-line AGC
G 0 0 0V
9130 AC config.
3 phase L1L2L3
RESET SAVE
Use the or push-button to choose between 1-phase, 2-phase or 3-phase. Press the push-button until SAVE is
underscored, and then press to save the new setting.
DANGER!
Configure the AGC-4 to match the correct measuring system. When in doubt, contact the switchboard manufacturer for
information about the required adjustment.
When the AGC is delivered from the factory, the three-phase system is selected. When this principle is used, all three phases must
be connected to the AGC.
The table below contains the parameters to make the system ready for three-phase measuring.
The example below is with 230/400 V AC, which can be connected directly to the AGC's terminals without the use of a voltage
transformer. If a voltage transformer is necessary, the nominal values of the transformer should be used instead.
Adjust to
Setting Adjustment Description
value
6041 G transformer Primary voltage of the G voltage transformer (if installed) 400 V AC
6042 G transformer Secondary voltage of the G voltage transformer (if installed) 400 V AC
6051 BB transformer set 1 Primary voltage of the BB voltage transformer (if installed) 400 V AC
6052 BB transformer set 1 Secondary voltage of the BB voltage transformer (if installed) 400 V AC
INFO
The AGC has two sets of BB transformer settings, which can be enabled individually in this measurement system.
This is a special application where two phases and neutral are connected to the AGC. The AGC shows phases L1 and L3 in the
display. The phase angle between L1 and L3 is 180 degrees. Split phase is possible between L1-L2 or L1-L3.
The table below contains the parameters to make the system ready for split phase measuring.
The example below is with 240/120 V AC, which can be connected directly to the AGC's terminals without the use of a voltage
transformer. If a voltage transformer is necessary, the nominal values of the transformer should be used instead.
6041 G transformer Primary voltage of the G voltage transformer (if installed) 120 V AC
6042 G transformer Secondary voltage of the G voltage transformer (if installed) 120 V AC
6051 BB transformer set 1 Primary voltage of the BB voltage transformer (if installed) 120 V AC
6052 BB transformer set 1 Secondary voltage of the BB voltage transformer (if installed) 120 V AC
INFO
The measurement UL3L1 shows 240 V AC. The voltage alarm set points refer to the nominal voltage 120 V AC, and UL3L1
does not activate any alarm.
INFO
The AGC has two sets of BB transformer settings, which can be enabled individually in this measurement system.
The single phase system consists of one phase and the neutral.
The table below contains the parameters to make the system ready for single phase measuring.
The example below is with 230 V AC, which can be connected directly to the AGC's terminals without the use of a voltage
transformer. If a voltage transformer is necessary, the nominal values of the transformer should be used instead.
Adjust to
Setting Adjustment Description
value
6041 G transformer Primary voltage of the G voltage transformer (if installed) 230 V AC
6042 G transformer Secondary voltage of the G voltage transformer (if installed) 230 V AC
6051 BB transformer set 1 Primary voltage of the BB voltage transformer (if installed) 230 V AC
6052 BB transformer set 1 Secondary voltage of the BB voltage transformer (if installed) 230 V AC
INFO
The voltage alarms refer to UNOM (230 V AC).
INFO
The AGC has two sets of BB transformer settings, which can be enabled individually in this measurement system.
The AGC holds four sets of nominal settings, configured in channels 6001 to 6036. It is possible to switch between the nominal
settings 1 to 4, to match different voltages and frequencies. Nominal settings 1 (6001 to 6007) are the nominal settings that are used
as default. See paragraph "Switch between the nominal settings" for more information about this feature.
The four sets of nominal settings can be individually configured. The AGC is able to switch between the different sets of nominal
settings, which enables the use of a specific set of nominal settings related to a specific application or situation.
INFO
If no busbar voltage transformer is present, the primary and secondary side values can be set to generator nominal value,
and channel 6054 is set to "BB Unom = G Unom".
Typically, it is the rental industry that makes use of the possibility to switch nominal parameter settings. The feature is very useful
with mobile gensets, where switching in frequency and voltage is required. Stationary gensets can make use of this feature as well.
For example, in the event of an AMF situation, it may be desirable to increase the nominal power and current settings to achieve
increased tolerance regarding the protections.
Activation
Manual switching between the nominal set points can be done in three ways: digital input, AOP or menu 6006.
INFO
When using M-Logic, any event can be used to activate an automatic switching of nominal parameter sets.
Digital input
M-Logic is used when a digital input is needed to switch between the four sets of nominal settings. Select the required input among
the input events, and select the nominal settings in the outputs.
Example:
Dig. input no. 23 or Not used or Not used Set nom. parameter settings 1
Not Dig. input no. 23 or Not used or Not used Set nom. parameter settings 2
INFO
See the "Help" file in the PC utility software for details.
AOP
M-Logic is used when the AOP is used to switch between the four sets of nominal settings. Select the required AOP push-button
among the input events, and select the nominal settings in the outputs.
Example:
Menu settings
In menu 6006, the switching between settings 1 to 4 is made simply by choosing the desired nominal setting.
In menu 6006, the selection of nominal setting is made. The nominal setting of GOV/AVR offset will follow the setting in 6006,
meaning: nominal setting 1 (6001 to 6005) will follow the GOV/AVR offset in 2550.
INFO
Switching between the two "BB nominal settings" (6050 and 6060) is done in the same way as explained above (channel
6054).
3.4.3 Scaling
Default voltage scaling is set to range 100 V to 25000 V (parameter 9030). To be able to handle applications above 25000 V and
below 100 V, it is necessary to adjust the input range so it matches the actual value of the primary voltage transformer. This makes it
possible for the unit to support a wide range of voltage and power values. Master password level access is required to change this
parameter.
Changing the voltage scaling will also influence the nominal power scaling:
INFO
All nominal values and the primary VT settings must be corrected after the scaling has been changed in parameter 9030.
3.5 Applications
3.5.1 Applications and genset modes
INFO
This section about applications is to be used for reference using the particular genset mode as starting point. It is not
suitable for reading from beginning to end.
The unit can be used for the applications listed in the table below.
Application Comment
Remote maintenance Requires option H8.x and a remote maintenance box from DEIF A/S
Island operation X X X X X
Peak shaving X X X X X
Load takeover X X X X X
Remote maintenance X X
INFO
For a general description of the available running modes, please refer to the chapter "Running mode description".
The unit automatically starts the genset and switches to generator supply at a mains failure after an adjustable delay time. It is
possible to adjust the unit to change to genset operation in two different ways.
In both cases, the generator breaker will be closed when the generator voltage and frequency is OK, and the mains breaker is open.
When the mains returns, the unit will switch back to mains supply and cool down and stop the genset. The switching back to mains
supply is done without back synchronisation when the adjusted "Mains OK delay" has expired.
When the generator breaker is closed, the unit will use the nominal frequency as the setpoint for the speed governor. If AVR control
(option D1) is selected, then the nominal voltage is used as setpoint.
INFO
For a general description of the available running modes, please refer to the chapter "Running mode description".
The unit automatically starts the genset and switches to generator supply at a mains failure after an adjustable delay time. It is
possible to adjust the unit to change to genset operation in two different ways:
In both cases, the generator breaker will be closed when the generator voltage and frequency is OK, and the mains breaker is open.
When the mains returns, the unit will synchronise the mains breaker to the busbar when the "Mains OK delay" has expired. Then the
genset cools down and stops.
INFO
The automatic mains failure mode can be combined with the "Overlap" function. In that case, the generator breaker and the
mains breaker will never be closed at the same time for a longer period than the adjusted "Overlap" time.
When the generator breaker is closed and the mains breaker is opened, the unit will use the nominal frequency as the setpoint for
the speed governor. If AVR control (option D1) is selected, the nominal voltage is used as the setpoint.
INFO
For a general description of the available running modes, please refer to the chapter "Running mode description".
The unit automatically starts the genset and closes the generator breaker at a digital start command. When the stop command is
given, the generator breaker is tripped, and the genset will be stopped after a cooling down period. The start and stop commands
are used by activating and deactivating a digital input or with the time-dependent start/stop commands. If the time-dependent start/
stop commands are to be used, then the auto mode must also be used.
When the generator breaker is closed, the unit will use the nominal frequency as setpoint for the speed governor. If AVR control
(option D1) is selected, the nominal voltage is used as setpoint.
INFO
For a general description of the available running modes, please refer to the chapter "Running mode description".
"Power ramp up" (channel 261x) and "Power ramp down" (channel 262x) are used when the genset is connected to another supply
source.
Delay point At this point, the ramp up is cancelled until the delay has expired
Delay When this delay has expired, the ramp up is continued from the delay point
Ramp speed 1 Defines the slope of ramp down 1 (used for de-load as well)
Breaker open point The amount of power accepted when opening the breaker
Ramp speed 2 Defines the slope of ramp down 2 (not used for de-load)
Automatic ramp selection When "Auto ramp select" is disabled, ramp 2 can only be enabled with M-Logic
Delay, step 4
Delay, step 1
Delay, step 2
Delay, step 5
Stop signal
Power ramp
[%/s]
Ramp down
From load share
Ramp up, read
line
When the GB is closed, the power set point continues to rise in ramp-up steps, determined by the number of steps in menu 2615. If
the delay point is set to 20 % and the number of load steps is set to 3, the genset will ramp to 20 %, wait the configured delay time,
ramp to 40 %, wait, ramp to 60 %, wait and then ramp to the present power set point.
A way to define the ramp up steps is to use the freeze power ramp command in M-Logic.
The power ramp will stop at any point of the power ramp, and this set point will be maintained as long as the function is active. If the
function is activated while ramping from one delay point to another, the ramp will be fixed until the function is deactivated again.
1. The power ramp will stop at any point of the power ramp, and this set point will be maintained as long as the function is active.
2. If the function is activated while ramping from one delay point to another, the ramp will be fixed until the function is deactivated
again.
3. If the function is activated while the delay timer is timing out, the timer will be stopped and will not continue until the function is
deactivated again.
INFO
The delay starts running when the GB has been closed.
Power ramp 1
This is the primarily used power ramp. Power ramp 1 is only ignored during "frequency-dependent power droop" or if power ramp 2
is activated with M-Logic.
Power ramp 2
3.5.6 Q ramp
A ramp function for reactive power regulation can be activated. This ramp is used when ramping up after the breaker is closed. The
ramp is also used to ramp down during de-loading before the breaker is opened. Configure these parameters in the parameter list.
Q ramp to setp. 2821 2 %/s 0.1 to 20 %/s Ramp up for reactive power
Q ramp to zero 2822 2 %/s 0.1 to 20 %/s Ramp down for reactive power
ON
Q ramp enable 2823 OFF Activation/deactivation of the function
OFF
INFO
There is no ramp for cos phi regulation.
The unit automatically starts the genset and synchronises to the mains when the digital input "auto start/stop" is activated. After the
generator breaker closure, the unit ramps up the load to the set point level. When the stop command is given, the genset is de-
loaded and stopped after the cooling down period. The start and stop commands are used by activating and deactivating a digital
input or with the time-dependent start/stop commands. If the time-dependent start/stop commands are to be used, then the auto
mode must also be used.
kW
t
tRAMP-UP
Start signal
Stop signal
When the generator breaker is closed and the mains breaker is opened, the unit will use the nominal frequency as the set point for
the speed governor. If AVR control (option D1) is selected, the nominal voltage is used as set point.
INFO
The values in menu 7050 set the cos phi. This is not the PF value displayed in the display. Cos phi and PF are only equal if
it is a true sinusoidal wave.
INFO
For a general description of the available running modes, see the chapter "Running mode description".
Warm up ramp is a function that limits the power output until a pre-configured condition has been met, like, for example, the engine
has reached operating temperature which will greatly reduce stress on the engine.
Power [kW]
Power ramp up
set point
Time [sec]
The warm up ramp activation is enabled and the input is configured via "Warm up type" (channel 2961). The activation of the warm
up ramp input limits the available power of the genset to the percentage level configured in "Power ramp up" (channel 2612).
If the type is configured as M-Logic, the input must go low before warm up ramp is deactivated. If the type is configured as a multi-
input or an EIC temperature input, the deactivation occurs when the temperature is above the threshold configured in "Warm up
thresh." (channel 2962).
INFO
When warm up ramp is activated, the standard function "Power ramp up" is replaced, which means that the load/steps and
the timer are disabled.
When the load drops below the maximum mains import set point, the genset will run at min. load again. When the mains import and
the generator load decrease below the stop set point, the genset will cool down and stop.
A 4 to 20 mA transducer is used for indication of the power imported from the mains, see "Mains transducer" description later in this
document.
kW
Peak/total
power
Generator power
tSTOP
When the generator breaker is closed and the mains breaker is opened, the unit will use the nominal frequency as set point for the
speed governor. If AVR control (option D1) is selected, the nominal voltage is used as set point.
When the generator is paralleled to the mains, the generator will be controlled according to the peak shaving set point. So the
maximum mains import will not be exceeded in spite of the semi- auto mode. If AVR control (option D1) is selected, then the setpoint
will either be adjusted power factor or reactive power (7050 Fixed power set).
These settings define the daytime period. The hours outside the daytime period are considered to be the night-time period.
INFO
For a general description of the available running modes, see the chapter "Running mode description".
- Back synchronising ON
The purpose of the load takeover mode is to transfer the load imported from the mains to the genset for operation on generator
supply only.
When the start command is given, the genset will start and synchronise the generator breaker to the busbar that is being supplied by
the mains. When the generator breaker is closed, the imported load is decreased (the power is being transferred to the genset) until
the load is at the open breaker point. Then the mains breaker opens.
When the stop command is given, the mains breaker is synchronised to the busbar and after closure the genset is deloaded, cooled
down and stopped.
A 4-20 mA transducer is used for indication of the power imported from the mains, please see "Mains transducer" description later in
this document.
kW
Mains power
Generator power
t
Start signal
Stop signal
MB opens
GB opens
INFO
The load takeover mode can be combined with the overlap function. In that case, the generator and the mains breakers will
never be closed at the same time for a longer period than the adjusted "overlap" time.
INFO
If the imported load is higher than the nominal genset power, an alarm appears and the load takeover sequence is paused.
When the start command is given, the genset will start. When the frequency and voltage is OK, the mains breaker is opened and the
generator breaker is closed. Now, the generator supplies the load until the stop command is given. Then, the generator breaker
opens and the mains breaker closes. The genset cools down and stops.
INFO
If the imported load is higher than the nominal genset, an alarm appears and the load takeover sequence is paused.
Semi-auto mode
When the generator breaker is closed and the mains breaker is opened, the unit will use the nominal frequency as setpoint for the
speed governor. If AVR control (option D1) is selected, the nominal voltage is used as setpoint.
When the generator is paralleled to the mains, it will be controlled so the imported power from the mains will be kept at 0 kW. If AVR
control (option D1) is selected, then the setpoint will either be adjusted power factor or reactive power (7050 Fixed power set).
INFO
For a general description of the available running modes, please refer to the chapter "Running mode description".
The mains power export mode can be used to maintain a constant level of power through the mains breaker. The power can be
exported to the mains or imported from the mains, but always at a constant level.
INFO
If a fixed level of imported power must be used, it is still the mains power export mode that must be selected! This mode
covers import as well as export.
The genset starts as a result of a digital start command. It synchronises to the mains and will start to export power to the mains. The
amount of power exported will be kept at a fixed level regardless of the load on the busbar (the factory).
The stop command will cause the genset to deload and trip the generator breaker. Afterwards, it will cool down and stop.
A 4-20 mA transducer is used for indication of the power exported from the mains, please see "Mains transducer" description later in
this document.
Stop signal
t
Ramp up
Ramp down
kW
INFO
Please notice that the setpoint of the mains power export can be adjusted to 0 kW. This means that the genset will be
parallel to the mains but no power import or export.
When the generator breaker is closed and the mains breaker is opened, the unit will use the nominal frequency as setpoint for the
speed governor. If AVR control (option D1) is selected, the nominal voltage is used as setpoint.
When the generator is paralleled to the mains, it will be controlled according to the mains power export setpoint. If AVR control
(option D1) is selected, then the setpoint will either be adjusted power factor or reactive power (7050 Fixed power set).
INFO
For a general description of the available running modes, please refer to the chapter "Running mode description".
In applications where export/load takeover is used (mains power export, peak shaving, load takeover), it is necessary to know the
power flow on the primary side of the mains breaker. When one controller is used for the application or if a transducer signal is
preferred in a power management system, it is possible to use multi-input 102 or CIO 308 1.14 for this purpose.
Below is a single line diagram where a TAS-331 DG transducer is used for measuring the voltage and current before the mains
breaker, this is used to calculate the power and based upon this gives a 4-20 mA output.
Transducer
(TAS-331DG)
Mains Controller
breaker
(MB)
Consumers
Generator
breaker
(GB)
How to set up
As mentioned, it is necessary to use multi-input 102 or CIO 308 1.14 for this purpose.
Set up the input for 4-20 mA, and define the range of the transducer in parameter 7261 and 7262. The range is defined with a min.
and max. setting where the min. setting corresponds to 4 mA and the max. setting to 20 mA.
INFO
As soon as transducer max. or min. settings are changed to a value different from 0, the controller will use the transducer
signal, even in a power management system with a mains controller.
It is also possible to use transducers to measure mains voltage or reactive power. To set-up these transducers use menu 7270
(Mains reactive power) and 7280 (Mains voltage).
To be compliant with national grid codes it is often necessary to measure in the grid connection point. Using transducers are the
practical solution in case of long distance. See documentation for option A10 for more information.
Transducer Range 7271 0 kvar -20000 to 20000 kvar Maximum reactive power
Transducer Range 7272 0 kvar -20000 to 20000 kvar Minimum reactive power
Mains U Ext Nom 7284 400 V 100 to 25000 V Nominal grid voltage for the transducer
Set up the input for 4-20 mA, and define the range of the transducer in parameter 7281 and 7282. The range is defined with a min.
and max. setting where the min. setting corresponds to 4 mA and the max. setting to 20 mA.
The unit can be operated in semi-auto mode. Semi-auto means that the unit will not initiate any sequences automatically, as is the
case with the auto mode. It will only initiate sequences, if external signals are given.
INFO
The standard AGC is only equipped with a limited number of digital inputs, please refer to "Digital inputs" in this document
and the data sheet for additional information about availability.
When the genset is running in semi-auto mode, the unit will control the speed governor and the AVR, if option D1 is selected.
The start sequence is initiated and continues until the genset starts or the maximum
Start number of start attempts has been reached. The frequency (and voltage) will be
regulated to make the GB ready to close.
The unit will ramp down and open the generator breaker at the breaker open point if
Open GB the mains breaker is closed. The unit will open the generator breaker instantly if the
mains breaker is open or the genset mode is island mode.
The unit will close the mains breaker if the generator breaker is open, synchronise
Close MB
and close the mains breaker if the generator breaker is closed.
The regulator is deactivated and the governor output is activated as long as the GOV
Manual GOV UP
input is ON.
Manual GOV The regulator is deactivated and the governor output is activated as long as the GOV
DOWN input is ON.
The regulator is deactivated and the governor output is activated as long as the AVR
Manual AVR UP Option D1 is required.
input is ON.
Manual AVR The regulator is deactivated and the governor output is activated as long as the AVR
Option D1 is required.
DOWN input is ON.
The test mode function is activated by selecting test with the MODE push-button on the display or by activating a digital input.
The settings for the test function are set up in menu 7040.
Related parameters:
7040 Test
7041 Set point 1 to 100 % 80 % Load set point when paralleling to mains.
7042 Timer 0.0 to 999.0 min 5.0 min Engine run time during the test period.
INFO
If the timer is set to 0.0 min, the test sequence will be infinite.
INFO
If the DG unit is in the stop sequence in test mode and the mode is changed to semi-auto, the DG will continue to run.
INFO
Test mode in island operation (genset mode selected to island mode) can only run "Simple" and "Full" test.
INFO
Power management (option G4): Test mode is not available.
Simple test
The simple test will only start the genset and run it at nominal frequency with the generator breaker open. The test will run until the
timer expires.
The load test will start the genset and run it at nominal frequency, synchronise the generator breaker and produce the power typed
in the set point in menu 7041. The test will run until the timer expires.
INFO
To run the load test, it is required that ”Sync. to mains” is enabled in menu 7084.
INFO
When running a load test sequence, the overlap function is ignored.
Full test
The full test will start the genset and run it at nominal frequency, synchronise the generator breaker and transfer the load to the
generator before opening the mains breaker. When the test timer expires, the mains breaker will be synchronised, and the load is
transferred back to the mains before the generator breaker is opened and the generator is stopped.
INFO
To run the full test, it is required that ”Sync. to mains” is enabled in menu 7084.
When manual mode is selected, the genset can be controlled from the display and with digital inputs. The following commands are
possible:
The start sequence is initiated and continues until the genset starts or the
Start No regulation.
maximum number of start attempts has been reached.
The genset will be stopped. After disappearance of the running signal, the stop
Stop sequence will continue to be active in the "extended stop time" period. The
genset is stopped with cooling down time.
No regulation.
The unit will close the generator breaker if the mains breaker is open, and
Close GB Sync. failure is
synchronise and close the generator breaker if the mains breaker is closed.
deactivated.
No regulation.
The unit will close the mains breaker if the generator breaker is open, and
Close MB Sync. failure is
synchronise and close the mains breaker if the generator breaker is closed.
deactivated.
Manual GOV UP The unit gives increase signal to the speed governor.
Manual GOV DOWN The unit gives decrease signal to the speed governor.
INFO
It is possible to open and close both the generator breaker and the mains breaker in manual mode.
When block mode is selected, the unit is locked for certain actions. Block mode can either be selected by pressing the MODE button
on the display or by using a digital input. If a digital input is used for block mode, it is important to keep in mind that the input
configured to block mode is a constant signal. This means that when the input is ON the unit is in a blocked state, and when it is
OFF the unit returns to the mode it was in before block mode was selected.
When activating BLOCK mode from the display on an AGC 200, it is as a minimum required to log in as customer.
When changing from BLOCK mode to any other operating modes from the AGC's display, it is as a minimum required to log in as
customer.
If the genset controller is in block mode, it cannot start the genset or perform any breaker operations. If the genset is running when
block mode is selected, the breaker will be opened and the genset will shut down without cooling down.
The purpose of the block mode is to make sure that the genset does not start during maintenance work, for example.
If the mains controller is in block mode, it cannot perform any breaker operations. If any breaker is closed when the mains controller
is put into block mode, the mains breaker will be opened, but the tie breaker will remain closed to ensure the genset's ability to
support the load.
The purpose of block mode is to make sure that the mains breaker cannot close onto a transformer that is momentarily non-
functional due to performance of service. When block mode is used on a mains controller in a power management setup, the system
will know that the blocked mains controller will not be available.
If a genset, which is running in a single DG application with an MB and a GB, is set in block mode, the DG will stop and the GB will
open. When block mode is active the DG, the GB and the MB will not be operational, but if the MB was closed when block mode
was activated, the MB will stay closed.
INFO
If block mode is selected by using the display after the digital block input is activated, the AGC will stay in block mode after
the block input is deactivated. The block mode must now be changed using the display. The block mode can only be
changed locally via display or digital input.
INFO
Alarms are not influenced by block mode selection.
CAUTION
Before the running mode is changed, make sure that nobody is near the genset and that the genset is ready for operation.
CAUTION
The genset can be started from the local engine control panel, if such is installed. Therefore, DEIF recommends to avoid
local cranking and starting of the genset.
INFO
The genset will shut down if block mode is selected while the genset is running.
Load
Controller
Load
Controller
Load
Controller
TRANSDUCER
P/4-20 mA
Load
Controller
TRANSDUCER
P/4-20 mA
Load
Controller
TRANSDUCER
P/4-20 mA
Load
Controller
Load
Controller Controller
G G
Display 1 Display 2
Busbar
CANbus
Controller Controller
Generator Generator
breaker breaker
(GB 1) (GB 2)
G G
Display mains
Mains
Mains
breaker Controller
(MB)
Consumers
Tie
breaker
(TB)
Display 1 Display 2
Busbar
CANbus
G G
Optional Optional
CANbus
CANbus
Mains Mains
breaker Controller breaker Controller
(MB 17) (MB 18)
CANbus
Load Load
Tie Tie
Breaker Breaker
(TB 17) (TB 18)
BTB 33
Busbar Busbar
CANbus CANbus
G G G G
Diesel generator set 1 Diesel generator set 2 Diesel generator set 3 Diesel generator set 4
INFO
The diagram shows four generators, but the system supports up to 32 generators. See the option G4, G5 and G8 manual
for further description of multi mains.
Display
Mains
Mains okay
Controller
ATS
Consumers ON/OFF
Tie
Breaker
(TB)
Busbar
CANbus
G G G
Controller
LOAD
Relay
INFO
The diagram shows a setup using the remote maintenance box. See the operator’s manual of the remote maintenance box
for further description.
3.8 Flowcharts
Using flowcharts, the principles of the most important functions will be illustrated in the next sections. The functions included are:
• Mode shift
• MB open sequence
• GB open sequence
• Stop sequence
• Start sequence
• MB close sequence
• GB close sequence
• Fixed power
• Load takeover
INFO
The flowcharts on the following pages are for guidance only. For illustrative purposes, the flowcharts are simplified in some
extent.
Start
Mode shift No
enabled
Yes
Yes
No
Mains failure
Yes
Initiate AMF
sequence
No
Mains OK timer Yes Initiate mains MB close Continue in
timed out return sequence sequence selected mode
End
Start
No
MB closed
Yes
Load take No
Mains failure
over
Yes
Deload MB
No
Yes
Open MB
No Alarm ”MB
MB open
open failure”
Yes
End
Start
Stop conditions No
OK
Yes
Is GB No
closed
Yes
No Fail class
Soft open
shutdown
Yes
Deload DG
No
No
Load < open Ramp down
set point timer expired
Yes
Yes
Open GB
No
GB open Alarm
Yes
End
Start
Stop conditions No
OK
Yes
GB open No
seq OK
Yes
AUTO No
mode
Yes
No Cooldown
timer run out
Yes
Yes
Genset No
Alarm
stopped
Yes
End
Start
Start condition No
OK
Yes
Start prepare No
timer
Yes
Start relay
ON
Yes
Yes
Yes
Yes Yes
Yes
Start failure
End
alarm
Start
No
Is MB open
Yes
Voltage on No
mains/bus
Yes
Voltage on No
gen
Yes
No
GB closed
No GB open No
Back sync ON
sequence
Yes Yes
No
Synchronised No
Yes
Close MB
No Close failure
MB closed
alarm
Yes
End
Start
No
Is GB open
Yes
No
Start seq OK
Yes
Single DG No
application
Yes No Voltage on
busbar
No No Yes
Island mode All GBs OFF
Yes Yes
No No
Voltage on bus MB close TB Present
No
Yes Yes Yes
No
TB open
Yes Yes
MB open
No
No
Direct closing Yes
Sync GB Time runout
OK
DG freq match No
BB freq Alarm sync
failure
Yes
Close GB
No
GB closed Alarm
Yes
End
Start
Activate start
input
Start
sequence
GB close
sequence
Ramp-up to
Operation
load set point
Deactivate
start input
GB open
sequence
Stop
sequence
End
Start
Activate start
input
Start
sequence
GB close
sequence
No Ramp-up
Mains load = 0 kW
genset load
Yes
MB open Genset
sequence operation
Deactivate
start input
Start
Start input
active
Start
sequence
GB close
Operation
sequence
Start input
deactivated
GB open
sequence
Stop
sequence
End
Start
Mains power
above start
set point
Start
sequence
Operation:
GB close
produce power
sequence
above set point
Mains power
below stop
set point
GB open
sequence
Stop
sequence
End
Start
Activate start
input
Start
sequence
Close GB
sequence
Ramp up to
operation
MPE set point
Deactivate
start input
GB open
sequence
Stop
sequence
End
Start
No
Mains failure
Yes
#7065: start No
eng + open MB
Yes
GB close GB close
sequence sequence
No
Mains ok
Yes
MB close
Time out End
sequence
Start
Select test
mode
Start sequence
Test timer
No
Timer run out Engine running No
Yes Yes
No
Stop sequence Freq/voltage OK
Yes
Sync of GB No
Engine stopped
allowed
No Yes
Return to
running mode, Sync GB
menu 7043
Opening og MB No Ramp up to
allowed P setpoint
Yes
No Yes
End P Mains = 0kW Open MB
3.9 Sequences
The following contains information about the sequences of the engine, the generator breaker and, if installed, the mains breaker.
These sequences are automatically initiated if the auto mode is selected, or if the commands are selected in the semi-auto mode.
In the semi-auto mode, the selected sequence is the only sequence initiated (e.g. press the START push-button: The engine will
start, but no subsequent synchronising is initiated).
• START sequence
• STOP sequence
• Breaker sequences
INFO
Refer to our application notes or installation instructions for information about the required breaker wiring.
INFO
We recommend not using small relays for stop coil output. If small relays are used, a resistor must be mounted across the
relay coil to prevent undesirable closing of the relay. This is caused by the wirebreak function.
The following drawings illustrate the start sequences of the genset with normal start prepare and extended start prepare.
No matter the choice of start prepare function, the running coil is activated 1 sec. before the start relay (starter).
Start sequence:
Normal start prepare
Start prepare
Run coil
1 sec.
Stop coil
Running feedback
Start prepare
Run coil
1 sec.
Stop coil
Running feedback
INFO
Run coil can be activated from 1...600 sec. before crank (starter) will be executed. In the above example, the timer is set to
1 sec. (menu 6150).
• Multi-input 102
• Multi-input 105
• Multi-input 108
This means that if, for example, the oil pressure is not primed to the sufficient value, the crank relay will not engage the starter
motor.
The selection is made in setting 6185. For each of the RMI settings, the rule is that the value (oil pressure, fuel level or water
temperature) must exceed the set point of setting 6186 before starting is initiated.
INFO
If the value in 6186 is set to 0.0, the start sequence is initiated as soon as it is requested.
The diagram below shows an example where the RMI signal builds up slowly and starting is initiated at the end of the third start
attempt.
Start prepare
(3 start attempts) 1 2 3
Stop relay
Crank relay
Run coil
Running feedback
RMI
measurement OK
RMI value
Cranking starts
Different types of running feedback can be used to detect if the motor is running. Refer to menu 6170 for selection of the running
feedback type.
The running detection is made with a built-in safety routine. The running feedback selected is the primary feedback. All configured
running feedbacks are used at all times. If, for some reason, the primary choice is not detecting any running feedback, the starter
relay will stay activated for one additional second. If a running feedback is detected based on one of the secondary choices, the
genset will start. This way, the genset will still be functional even though a tacho sensor is damaged or dirty.
As soon as the genset is running, no matter if the genset is started based on the primary or secondary feedback, the running
detection will be made based on all available types.
Primary running
feedback
Secondary running
feedback
1sec
Alarm
Event Comment
Stop signal
Start failure
Emergency stop
Activating "BLOCK" while running will work in the same way as pushing the emergency stop, but
Running mode
it will also prevent the genset from starting afterwards.
INFO
If the MPU input is to be used to remove the starter, it must be set up in menu 6174.
INFO
The only protections that can stop the genset/interrupt the start sequence when the "shutdown override" input is activated,
are the digital input "emergency stop" and the alarm "overspeed 2". Both of these must have the fail class "shut down".
RPM
6160
Run status
Inhibit status: Not running (0-300 sec)
1500
6165
1000
Frequency
detection level
(20-35 Hz)
6173
800
Running
detection
level
(0-4000 RPM)
400 6174
Remove 6160
starter Run status
300
6351 (0-300 sec)
6180 Running 2740 4560
Cranking
Start detection Delay of Hz/ V failure
6150
prepare within Regulation (1-99 sec)
Run coil
(0-600 sec) (0-1200 sec) (0-9900 sec)
(0-600 sec)
Activate Nominal
Start Starter Remove
regulation speed
starter
(0-2000RPM)
Normal prepare: The start prepare timer can be used for start preparation purposes, for example prelubrication or preglowing. The
start prepare relay is activated when the start sequence is initiated and deactivated when the start relay is activated. If the timer is
set to 0.0 s, the start prepare function is deactivated.
Extended prepare: The extended prepare will activate the start prepare relay when the start sequence is initiated and keep it
activated when the start relay activates, until the specified time has expired. If the extended prepare time exceeds the start ON time,
the start prepare relay is deactivated when the start relay deactivates. If the timer is set to 0.0 s, the extended prepare function is
deactivated.
Start ON time: The starter will be activated for this period when cranking.
The timer for the run coil is a set point that sets how long time the run coil will be activated before cranking the engine. This gives
the ECU time to start up before cranking.
This is the set point where the running detection level is defined in RPM. This will only work, if MPU or EIC RPM is selected in 6172
Run detect type.
This timer can be set to the needed level. This will make sure that the engine goes from the RPM level set in 6174 Remove starter
and 6173 Running detection level. If the timer is exceeded and the level is not reached, the start sequence will start over and will
have used a start attempt. If all start attempts (6190 Start attemps) are used, the 4570 Start failure will occur. This timer will only
be active, if MPU or EIC RPM is selected in 6172 Run detect type.
INFO
If other running detection types than MPU or EIC RPM are used, the starter will be on until 6165 Frequency detection
level is reached.
This set point is in Hz and can be set to the needed level. When the level is reached, the regulators will start working and make sure
to reach the nominal values. The regulators can be delayed using 2740 Delay of regulation. See below.
The timer in this set point is started when 6173 Running detection level is reached, or when 6165 Frequency detection level is
reached. When the timer is exceeded, the inhibit status Not running will be deactivated, and the running alarms and failures will be
enabled (see the related failures below).
By using this timer, the regulation start can be delayed. The timer will start when 6165 Frequency detection level is reached.
INFO
If the setup is running on nominal settings and 2740 Delay of regulation is set to 0, the genset will overshoot the nominal
frequency on start-up, as the regulators start increasing as soon as they are turned on. If this timer is used, the regulation
can wait until the genset is already at nominal frequency before starting to regulate.
If MPU is chosen as the primary running feedback, this alarm will be raised if the specified RPM is not reached before the delay has
expired.
This is an alarm, in case there is no primary running feedback (6172), but the secondary feedback detects running. There is a failure
on the primary running feedback, and therefore this alarm will be raised with a delay. The delay to be set is the time from the
secondary running detection and until the alarm is raised.
If the frequency and voltage are not within the limits set in 2110 Blackout df/dUmax after the running feedback is received, this
alarm is raised when the delay has expired.
The start failure alarm occurs, if the genset has not started after the number of start attempts set in menu 6190.
If running sequence is active and the engine goes below 6173 Running detection and 6165 Frequency detection level without
any command from the AGC, it will set an alarm if this parameter is enabled.
6160
Run status
Inhibit status: Not running (0-300 sec)
1500
6165
1000
Frequency
detection level
(20-35 Hz)
6173
800 Running detection level
(0-4000 RPM)
6290
Idle run 6160
400 6174 Run status
Remove
(0-300 sec)
300 starter
6351 2740 4560
6180 Running Delay of
Cranking
Start detection Regulation Hz/ V failure
6150
prepare within (0-9900 sec) (1-99 sec)
Run coil
(0-600 sec) (0-600 sec) (0-1200 sec)
Start Starter Remove Idle start Idle Activate Nominal
starter finished regulation speed
(0-2000RPM)
The set points and failures in this overview are the same as described in the chapter "Start-up overview", except for the idle run
function. This function is described in the chapter "Idle running".
tstop
Run coil
Running feedback
Sequence initiated
Stop sequence
Stop coil
Running feedback
Sequence initiated
The stop sequence will be activated if a stop command is given. The stop sequence includes the cooling down time if the stop is a
normal or controlled stop.
Remove "auto start/stop" X X Auto mode: Island operation, fixed power, load takeover, mains power export.
The stop sequence can only be interrupted during the cooling down period. Interruptions can occur in these situations:
Event Comment
Mains failure AMF mode selected (or mode shift selected ON) and auto mode selected.
Start button is pressed Semi-auto mode: Engine will run in idle speed.
Binary start input Auto mode: Island operation and fixed power, load takeover or mains power export.
INFO
The stop sequence can only be interrupted during the cooling down period.
INFO
When the engine is stopped, the analogue speed governor output is reset to the offset value. Please refer to the mentioned
option descriptions.
A stop failure alarm will appear if the primary running feedback or the generator voltage and frequency are still present after the
delay in this menu has expired.
Cooling down:
Extended stop:
The delay after the running feedback has disappeared until a new start sequence is allowed. The extended stop sequence is
activated any time the Stop button is pressed.
The engine temperature-controlled cool down is to ensure that the engine is cooled down below the set point in menu 6214 "Cool
down temperature" before the engine is stopped. This is particularly beneficial if the engine has been running for a short period of
time and therefore not reached normal cooling water temperature, as the cool down period will be very short or none at all. If the
engine has been running for a long period, it will have reached normal running temperature, and the cool down period will be the
exact time it takes to get the temperature below the temperature set point in menu 6214.
If, for some reason, the engine cannot get the temperature below the temperature set point in 6214 within the time limit in parameter
6211, the engine will be shut down by this timer. The reason for this could be high ambient temperature.
INFO
If the cooling down timer is set to 0.0 s, the cooling down sequence will be infinite.
INFO
If the cooling down temperature is set to 0 deg., the cooling down sequence will be entirely controlled by the timer.
INFO
If the engine stops unexpectedly, please refer to the chapter "Running feedback".
Before closing the breakers it must be checked that the voltage and frequency are OK. The limits are adjusted in menu 2110 Sync.
blackout.
7080 MB control
When enabled, the AGC will perform the AMF sequence in case of a mains failure regardless of the
Mode shift:
actual genset mode.
MB close delay: The time from GB OFF to MB ON when back synchronisation is OFF.
After opening of the breaker, the MB ON sequence will not be initiated before this delay has expired.
Load time:
Please refer to the description of "Breaker spring load time".
INFO
If no MB is represented, then the relays and inputs normally used for MB control become configurable. The power plant
constructor (USW) is used for configuration of the plant design if the application does not include an MB.
INFO
AGC without back synchronisation: The GB can only be closed if the mains breaker is open. The MB can only be closed if
the generator breaker is open.
INFO
AGC with back synchronisation: If the GB or MB push-button is activated, the AGC will start synchronising if the generator
or mains voltage is present. The GB can close directly if the MB is open. The MB can close directly if the GB is open.
It is possible to select the functionality of the mains breaker opening function. This is necessary if the unit operates in Automatic
Mains Failure (AMF).
When a mains failure occurs, the engine starts. When the generator is running and the frequency
Start engine
and voltage are OK, the MB opens and the GB closes.
The time charts describe the functionality at a mains failure and at mains return. Back synchronisation is deactivated. The timers
used by the AMF function are indicated in the table below:
Example 1:
Mains OK
tMBC
MB On
GB On
Gen running
Gen f/U OK
tFU
Mains failure Mains OK
detected
Example 2:
MB On
tMBC
GB On
tGBC
Gen start seq
tFD
Gen stop seq
tFOD
Gen running
Gen f/U OK
tFU
Mains failure Mains OK
detected
The timers must have some set points to indicate when they are to start. The Multi-line 2 product has different set points for the
different situations. The limits that the mains voltage must be within before the failure timer starts, are set in parameters 7063 and
7064. There is a low (7063) and a high (7064) limit. Furthermore, the Multi-line 2 product has limits for the frequency. This also has a
low limit (7073) and a high limit (7074). If the mains voltage or frequency has exceeded one of these limits and the relevant fail timer
has expired, the AMF sequence will be started.
When the mains voltage/frequency has returned, some hystereses can be adjusted. The Multi-line 2 controller has four separate
hystereses which are located in menu 7090. The first hysteresis is for the “low voltage limit”. If the mains “low voltage” is set at 90 %
(7063), the Multi-line 2 will start the “Automatic Mains Failure” sequence when the voltage is lower than 90 % of the nominal voltage.
By default, the hysteresis is set at 0 % (7091), which means, in this example, that when the voltage has increased above 90 %, it is
allowed to feed the load from the grid again. If the hysteresis had been set at 2 %, it would not be allowed to go back to grid until the
mains voltage had increased above 92 %.
If, for example, the “mains low voltage” was set at 85 % and the hysteresis was set at 20 %, the calculation would imply that it was
not allowed to go back to grid operation until the mains voltage was 105 %. The Multi-line 2 controller can be 100 % of nominal at
the most. This is the same for “mains high voltage” and both frequency limits. The hysteresis can be at 100 % nominal at the most.
The breaker sequences react depending on the breaker positions and the frequency/voltage measurements.
The conditions for the ON and OFF sequences are described in the table below:
Sequence Condition
Running feedback
GB ON, direct closing Generator frequency/voltage OK
MB open
Mains frequency/voltage OK
MB ON, direct closing
GB open
Running feedback
Generator frequency/voltage OK
GB ON, synchronising
MB closed
No generator failure alarms
GB closed
No generator failure alarms
Sequence Condition
The AGC holds four sets of nominal settings, configured in channels 6001 to 6036. It is possible to switch between the nominal
settings 1 to 4, to match different voltages and frequencies. Nominal settings 1 (6001 to 6007) are the nominal settings that are used
as default. See paragraph "Switch between the nominal settings" for more information about this feature.
The AGC holds two sets of nominal settings for the busbar, configured in channels 6051 to 6063. Each set consists of a nominal as
well as a primary and secondary voltage value. The "U primary" and "U secondary" are used to define the primary and secondary
voltage values, if any measurement transformers are installed. If no voltage transformer is installed between generator and busbar,
select "BB Unom = G Unom" in channel 6054. With this function activated, none of the BB nominal settings will be considered.
Instead, the nominal BB voltage will be considered equal to nominal generator voltage.
The four sets of nominal settings can be individually configured. The AGC is able to switch between the different sets of nominal
settings, which enables the use of a specific set of nominal settings related to a specific application or situation.
INFO
If no busbar voltage transformer is present, the primary and secondary side values can be set to generator nominal value,
and channel 6054 is set to "BB Unom = G Unom".
Typically, it is the rental industry that makes use of the possibility to switch nominal parameter settings. The feature is very useful
with mobile gensets, where switching in frequency and voltage is required. Stationary gensets can make use of this feature as well.
For example, in the event of an AMF situation, it may be desirable to increase the nominal power and current settings to achieve
increased tolerance regarding the protections.
Activation
Manual switching between the nominal set points can be done in three ways: digital input, AOP or menu 6006.
INFO
When using M-Logic, any event can be used to activate an automatic switching of nominal parameter sets.
Digital input
Example:
Dig. input no. 23 or Not used or Not used Set nom. parameter settings 1
Not Dig. input no. 23 or Not used or Not used Set nom. parameter settings 2
INFO
See the "Help" file in the PC utility software for details.
AOP
M-Logic is used when the AOP is used to switch between the four sets of nominal settings. Select the required AOP push-button
among the input events, and select the nominal settings in the outputs.
Example:
INFO
See the "Help" file in the PC utility software for details.
Menu settings
In menu 6006, the switching between settings 1 to 4 is made simply by choosing the desired nominal setting.
In menu 6006, the selection of nominal setting is made. The nominal setting of GOV/AVR offset will follow the setting in 6006,
meaning: nominal setting 1 (6001 to 6005) will follow the GOV/AVR offset in 2550.
INFO
Switching between the two "BB nominal settings" (6050 and 6060) is done in the same way as explained above (channel
6054).
Default voltage scaling is set to range 100 V to 25000 V (parameter 9030). To be able to handle applications above 25000 V and
below 100 V, it is necessary to adjust the input range so it matches the actual value of the primary voltage transformer. This makes it
possible for the unit to support a wide range of voltage and power values. Master password level access is required to change this
parameter.
Changing the voltage scaling will also influence the nominal power scaling:
INFO
All nominal values and the primary VT settings must be corrected after the scaling has been changed in parameter 9030.
4.1 General
The protections are all of the definite time type, that is a set point and time is selected.
If, for example, the function is over-voltage, the timer will be activated if the set point is exceeded. If the voltage value falls below the
set point value before the timer runs out, the timer will be stopped and reset.
Timer setting
Measured
value
Setpoint
Time
Timer Timer Timer Alarm
start reset start
When the timer runs out, the output is activated. The total delay will be the delay setting + the reaction time.
INFO
When parameterising the DEIF controller, the measuring class of the controller and an adequate "safety" margin
must be taken into consideration.
An example:
A power generation system must not reconnect to a network when the voltage is 85 % of Un +/-0 % < U < 110 %
+/-0 %. In order to ensure reconnection within this interval, a control unit’s tolerance/accuracy (Class 1 of the
measuring range) has to be taken into consideration. It is recommended to set a control unit’s setting range 1 to 2
% higher/lower than the actual set point, if the tolerance of the interval is +/-0 %, to ensure that the power system
does not reconnect outside the interval.
If the voltage alarms are to work based on phase-neutral measurements, you must adjust menus 1200 and 1340 accordingly.
Depending on the selections, either phase-phase voltages or phase-neutral voltages will be used for the alarm monitoring.
Phase-neutral Phase-phase
UL UL
-N 2-N -N 2-N
U L3 U L3
UL2-L3 UL2-L3
As indicated in the vector diagram, there is a difference in voltage values at an error situation for the phase-neutral voltage and the
phase-phase voltage.
Phase-neutral Phase-phase
The alarm will occur at two different voltage levels, even though the alarm set point is 10 % in both cases.
Example
The below 400 V AC system shows that the phase-neutral voltage must change 20 %, when the phase-phase voltage changes 40
volts (10 %).
Example: 20%
UNOM = 400/230 V AC
UL1-N = 185 V AC -N
UL
U L3 2-N
ΔUPH-N = 20 %
UL2-L3
INFO
Phase-neutral or phase-phase: both the generator protections and the busbar/mains protections use the selected voltage.
A single DG application is able to handle up to one genset, one generator breaker and one mains breaker. An application like this is
shown below:
Genset Load
Mains
G
GB MB
INFO
The table above is only for Single DG application!
In the AGC there are two different alarms concerning the phase sequence error, and hereby two different failclasses. The alarm for
phase sequence error and phase rotation is set in parameter 2150. The menu numbers is described in the table below:
Menu/parameter
Menu text Description
no.
2151 Output A Relay output if the AGC detecs a phase sequence error on the genset voltage terminals.
2152 Output B Relay output if the AGC detects a phase sequence error on the genset voltage terminals.
Determines how the AGC reacts if the AGC sees a phase sequence error on the genset voltage
2153 Failclass
terminals.
Determines the rotation of the voltages the AGC is measuring on. This is both for the Genset
2154 Rotation
voltages and Mains voltages.
Relay output if the AGC detects a phase sequence error on the mains voltage terminals. Since
2155 Output A
there is no output B on this alarm, it has been configured that output B is the same as output A.
Determines how the AGC reacts if the AGC sees a phase sequence error on the mains voltage
2156 Failclass
terminals.
Example
In a SingleDG application with GB and MB (like the application shown on previous page), the parameters are set like in the table
below:
INFO
An alarm is activated if no relay output A/B is selected. Do not chose Limits/Limit relay if you want that an alarm is raised
together with a relay output A/B.
If the controller is set to Load Take Over (LTO) and the start signal is given the genset will start up. If there have been performed a
service of the alternator, and two of the phases have been switched when the alternator has been assembled again, the AGC will
now discover a phase sequence fail. Since this is on the genset voltage terminals, the failclass set in parameter 2153 will be used.
The failclass is set to Trip+Stop, which will trip the breaker (If the breaker is not closed, the controller will not send a trip signal), and
then afterwards go into the stop sequence. If the alarm is acknowledged, the genset will start up again, if the start signal is still
present.
In these applications there are different types of controllers. The three different types are: Genset, Bus Tie Breaker (BTB) and Mains.
The phase sequence alarms are located at parameter 2150. From here it is possible to configure both the alarms for phase
sequence errors and also the phase rotation.
The alarms refer to different voltage terminals. The different types and models of controllers have different terminals. To know which
voltage terminals the different alarms refers to, the drawing and tables below can be helpful.
MB 17 MB 18
Mains controller
TB 17 TB 18
BTB 33 BTB 34
BTBcontroller
GB 1 GB 2
Genset controller
G G
INFO
The table above is only for Mains controllers in standard plants!
INFO
The table above is only for BTB controllers in standard plants!
INFO
The table above is only for Genset controllers in standard plants!
Parameter 2150 is consisting of two alarms, and the phase rotation direction setting. The phase rotation setting is the same for the
both terminal sets. The two alarms refer to the voltage terminals. To know which alarm refers to voltage measurement, the table
below has been made to make an overview:
The diagram made earlier, can be helpful in locating where the different location of each voltage measurement is made.
The table above shows on which terminal set the phase sequence error occurs to activate the failclass set in the parameter 2153
and 2156. This can also be shown in a diagram like this:
MB 17 MB 18
Mains controller
TB 17 TB 18
2156 2156
BTB 33 BTB 34
2153 2156 2153 2156
BTBcontroller
2156 2156
GB 1 GB 2
Genset controller
2153 2153
G G
When setting up the phase sequence alarms, it can be helpful to activate MB fail start (8181) in some of the mains controllers. This
gives the possibility if e.g. the phase sequence error for mains voltage (2153) appears, and the failclass is Trip MB, then the gensets
will start. If then autoswitch is enabled also (8184) the other grid connection can supply as backup load, before the gensets will start.
If the other mains do not have a phase sequence error, the other mains will keep on supplying the load, and the gensets will not
start.
Example
On genset 1, parameter 2153 is set to trip+stop. Genset 1 has recently been out for service, and two phases has accidently been
switched. A mains fail now occurs on mains 17, and genset 1 will start up. The controller for genset 1 sees a phase sequence error
here, and activates its failclass. GB1 will never be closed. BTB33 will now close, and genset 2 will start up and supply the load. If
there also is a phase sequence error on the B side of BTB33, and 2156 in BTB 33 is set to trip BTB, the system will close BTB34
instead, since this is a system with wrapped busbar.
The percentage set in parameter 1521 is the maximum percentage of imported kvar compared to the nominal kW of the genset.
To set the percentage correctly, a calculation must be made. For this purpose, the operating chart for the generator is needed. An
operating chart for a generator is shown below.
The alternator 100 % load is the outer circle, and the engine 100 % load is the blue dotted line. With the operating chart it is possible
to see where the alternator-safe line is closest to the 1.0 PF line. This is marked with a red arrow. In this operating chart each
vertical line represents 10 %, and by this, the dot closets to 1.0 PF has been read to 18 %. With the nominal alternator values and
the nominal engine values, the calculations can be made.
Example: The reading of 18 % is used. The alternator has a nominal power of 2500 kVA, and the engine has a nominal power of
2000 kW. The distance between the dot and the 1.0 PF line represents a power, and this is calculated to: 2500 kVA*18 % = 450 kvar
The setting of parameter 1521 can now be calculated: 450 kvar/2000 kW = 22.5 %
The parameters for this are 1101 to 1115. The set points for the different levels are set in parameters 1101 to 1106. The set point
refers to six different current levels and voltage levels. All values are in percentage to the rated values that are set in parameters
6000 to 6030. The six voltage levels are already determined, so only the current levels must be set. The six set points will create a
curve, which will be explained by an example:
The six different set points have been set to the values shown in the table below.
Voltage level
50 60 70 80 90 100
(Fixed/not adjustable)
Current level
50 55 65 80 100 130
(Set point/adjustable)
The six values can then be transferred to a curve, which is more readable:
Timer, outputs, enable and fail class are set in parameters 1111 to 1115. The timer in 1111 decides how long the fault will exceed the
limits, before an action will take place. The action/fail class is decided in parameter 1115 and can be set from a warning to a
shutdown. As a default, this will be set to trip the generator breaker. The outputs can be used to activate a relay. This will make it
possible to send a signal to external equipment regarding this specific alarm. It is possible to configure two relay outputs for the
alarm. The protection function is activated as a default, but can be disabled in parameter 1114.
If parameter 1203 is set to nominal, the AGC uses the maximum and the minimum current and subtracts the values. Then it will
compare this to the nominal current typed in parameter 6003, 6013, 6023 or 6033, depending on which of the nominal settings is
activated. The comparison to the nominal current will give a percentage that is related to parameter 1501.
Example: A genset is rated at 400 A and is supplying a load. The currents of the three phases are: 115 A, 110 A and 100 A. The
AGC will use the maximum and the minimum current, in this case 115 A and 100 A. The calculation will now be: ((115 -
100)*100)/400 = 3.75 %. If parameter 1501 is set to 4 %, the genset will keep running. If parameter 1501 is set to 4 %, and the
genset's rated current is 400 A, it can be calculated how unbalanced the genset is allowed to be: (4*400)/100 = 16 A. When the
phases are loaded more than 16 A, the generator breaker will be tripped. This is independent of the size of the load.
Parameter 1203 can also be set to average. The AGC will then calculate an average of the phases and compare how unbalanced
the load is between them.
Example: An genset is rated at 400 A and is supplying a load. The currents of the three phases are: 115 A, 110 A and 100 A. The
AGC will now calculate an average of these currents, take the one that differs most from the average and calculate a percentage of
deviation: (115 + 110 + 100)/3 = 108.3 A. Then the AGC will analyse which of the currents that differs most. In this example, it will be
the 100 A. The maximum difference will be compared to the average current: ((108.3 - 100)*100)/108.3 = 7.7 %. If the load had been
bigger, this calculated percentage would have been smaller. If the phase currents were 315 A, 310 A and 300 A, the average would
be: (315 + 310 + 300)/3 = 308.3 A. This would give a deviation of:
The percentage set in parameter 1511 is a percentage of deviation compared to the average voltage in the three phases. The
average comparison is described with an example below.
Example: Phase L1 to L2 is 431 V, phase L2 to L3 is 400 V and phase L3 to L1 is 410 V. The three voltages must be added up to
find an average voltage: (431 + 400 + 410)/3 = 414 V. Now the voltage with the biggest voltage difference must be subtracted, in this
case L1 to L2: 431 - 414 = 17 V. Now the biggest voltage deviation in percent can be calculated: (17/414)*100 = 4.1 %.
This means that if parameter 1511 is set to 4.1 %, it is allowed to have a voltage difference of 31 V in this application, before the
unbalanced voltage protection can be activated.
In the example, phase-phase measurements have been used. Phase-phase is selected as default, but it can also be phase-neutral
measurements, and this can be changed in parameter 1201. (Parameter 1201 will be described later).
INFO
Be aware that when parameter 1201 is changed, it will influence other protections.
In parameter 1512 the timer can be set, and in parameter 1515 this protection is enabled. In parameter 1516 the fail class is
decided. It is also possible to enable two relay outputs when the alarm occurs. The two relay outputs can be set in parameters 1513
and 1514.
4.7 Over-excitation
When heavy inductive loads are connected, over-excitation of the generator can occur. Alternatively, over-excitation can occur if the
load of a generator quickly changes from inductive to capacitive. Over-excitation can also occur in an application with more than one
generator if one of the generators' exciter fails. Over-excitation can overheat windings in the generator and create a failure over
time.
Use the kvar to calculate the percentage for parameter 1531: kvar/kW = 1500/2000 = 75 %.
When parameter 1531 is 75 %, the genset can export up to 1500 kvar. The alarm is activated when the load has crossed
the set point for the time in parameter 1532.
INFO
Option C2 includes capability curve protection with 12 configurable points. If this simple over-excitation protection is not
good enough, use Option C2.
In parameter 1201 it can be set how the voltage measurements should be done for example on generator voltage protection. It can
be set to either phase-phase or phase-neutral; by default it is set to phase-phase. When this parameter is set, it should be taken into
account how the loads in the application are connected. If many of the loads are connected as phase-neutral, the setting of
parameter 1201 should be set to phase-neutral. On a generator unit it will be the voltage measurements on the generator side of a
breaker, and on a mains unit it will be the voltage measurements on the mains feeder side of the mains breaker.
Parameter 1202 is similar to 1201. It is also considering how the measurements should be made. But this parameter refers to the
other voltage measurements. On a generator unit it will be the busbar voltage measurements, and on a mains unit it will be the
voltage measurements after the mains breaker. This parameter can also be set to phase-phase measurement or phase-neutral
measurement.
Parameter 1203 refers to the current measurement as described earlier in this chapter, under "Unbalanced current".
5.1 Presentation
This chapter deals with the display unit including the push-button and LED functions. In addition, the unit menu structure will be
presented.
INFO
Display dimensions are H x W = 115 x 220 mm (4.528” x 9.055”).
The display unit holds a number of push-button functions which are described below:
1 2 3 4
Self check ok
Alarm multi-line AGC
Alarm Inh.
15 INFO AMF SEMI-AUTO VIEW
Load
BACK
12 STOP G MODE
11 10 9 8 7
1. Shifts the first line displaying in the setup menus. Push 2 seconds to switch to master display in case more than one display is
connected.
2. Moves the cursor left for manoeuvring in the menus.
3. Increases the value of the selected set point (in the setup menu). In the daily use display, this button function is used for scrolling
the view lines in V1 or the second line (in the setup menu) displaying of generator values.
4. Selects the underscored entry in the fourth line of the display.
5. Moves the cursor right for manoeuvring in the menus.
6. Decreases the value of the selected set point (in the setup menu). In the daily use display, this button function is used for
scrolling the second line displaying of generator values.
7. Changes the menu line (line four) in the display to mode selection.
8. Jumps one step backwards in the menu (to previous display or to the entry window).
9. Displays the LOG SETUP window where you can choose between the Event, Alarm and Battery logs. The logs are not deleted
when the auxiliary supply is switched off.
10. Manual activation of close breaker and open breaker sequence if "SEMI-AUTO" is selected.
11. Manual activation of close breaker and open breaker sequence if "SEMI-AUTO" is selected.
The display unit holds 10 LED functions. The colour is green or red or a combination in different situations. The display LEDs are
indicating as follows:
JUMP
G 0.90I PF 150kW LOG
SETUP V1 V2 V3
Run On On Auto
START
4
Load
BACK
STOP G MODE
9 8 7 6 5
In the AGC there are configured two colour schemes for the display LEDs. In parameter 6082 it is possible to toggle between the to
schemes. In the table below are the LEDs and their interpretation in the two colour schemes.
When the unit is powered up, an entry window appears. The entry window is the turning point in the menu structure and as such the
gateway to the other menus. It can always be reached by pressing the BACK push-button three times.
INFO
The event and alarm list will appear at power up if an alarm is present.
INFO
The priority "P00", shown in the lower right corner, is related to the power management option G4 and G5.
The view menus (V1, V2 and V3) are the most commonly used menus of the unit.
multi-line AGC
1 G 400 400 400V
2 G-L1 50 Hz 440V
3 G-L1 50 Hz 440V
4 SETUP V3 V2 V1
The menu navigating starts from the fourth display line in the entry window and is carried out using the , , and
push-buttons.
INFO
The factory settings for view 1 and view 2 are identical.
The setup menu system is used for parameter setup of the unit, and if the user needs detailed information that is not available in the
view menu system. So, this menu can be used for both daily use and setup purposes. The menu is entered from the entry window
by selecting the entry SETUP in the fourth display line.
multi-line AGC
1 G 400 400 400V
2 f-L1 50.00HZ
3 PROTECTION SETUP
4 PROT CTRL I/O SYST
Voltage angle between L1-L2 (deg.) Voltage angle between L1-L2 (deg.)
Voltage angle between L2-L3 (deg.) Voltage angle between L2-L3 (deg.)
Voltage angle between L3-L1 (deg.) Voltage angle between L3-L1 (deg.)
BB U-L1N BB U-L1N
BB U-L2N BB U-L2N
BB U-L3N BB U-L3N
BB U-L1L2 BB U-L1L2
BB U-L2L3 BB U-L2L3
BB U-L3L1 BB U-L3L1
BB U-MAX BB U-MAX
BB U-Min BB U-Min
BB f-L1 BB f-L1
BB AngL1L2-180.0deg BB AngL1L2-180.0deg
Start attempts
P available P available
P mains P mains
Service timer 1
Service timer 2
MPU
Multi-input 1 Multi-input 1
Multi-input 2 Multi-input 2
Multi-input 3 Multi-input 3
Setup structure
AGC V.4.00.0
2010-01-02 09.35.54
SETUP V3 V2 V1
BACK SEL
G 400 400 400V G 400 400 400V G 400 400 400V G 400 400 400V
f-L1 50.00HZ f-L1 50.00HZ f-L1 50.00HZ f-L1 50.00HZ
PROTECTION SETUP CONTROL SETUP INPUT/OUTPUT SETUP SYSTEM SETUP
PROT CTRL I/O SYST PROT CTRL I/O SYST PROT CTRL I/O SYST PROT CTRL I/O SYST
G 400 400 400V G 400 400 400V G 400 400 400V G 400 400 400V
1000 G -P> 1 CONTROL SETUP INPUT/OUTPUT SETUP SYSTEM SETUP
Setpoint -5.0% SYNCHRONISE SETUP BINARY INPUT SETUP GENERAL SETUP
SP DEL OA OB ENA FC SYNC REG BIN AIN OUT GEN MAINS COMM PM
Setup example
The following example illustrates how a specific setting is changed in the setup menu. In this case Reverse power is the selected
parameter.
BACK
BACK
NO
Auto
In auto mode the unit will operate automatically, and the operator cannot initiate any sequences manually.
Semi-auto
In semi-auto mode the operator has to initiate all sequences. This can be done via the push-button functions, Modbus commands or
digital inputs. When started in semi-automatic mode, the genset will run at nominal values.
Test
The test sequence will start when the test mode is selected.
Manual
When manual mode is selected, the binary increase/decrease inputs can be used (if they have been configured) as well as the start
and stop push-buttons. When starting in manual mode, the genset will start without any subsequent regulation.
Block
When the block mode is selected, the unit is not able to initiate any sequences, e.g. the start sequence.
INFO
Block mode must be selected when maintenance work is carried out on the genset.
INFO
The genset will shut down if block mode is selected while the genset is running.
Pushing the MODE push-button will change the displayed text. After pushing "MODE", the fourth display line indicates the selectable
modes. In the third display line, the underscored (fourth line) selection will be displayed.
If "BACK" is pushed, the display returns to the original text without changing the mode.
1. push 2. push
AGC V 4.00.0 MODE
AGC V 4.00.0
2010-01-02 13:45:18 2010-01-02 13:45:18 BACK
or
If "SEL" is pushed, the underlined mode is selected, and the display returns to the original text. In this example the SEMI-AUTO
mode is selected.
or
5.6 Password
5.6.1 Password
The unit includes three password levels. All levels can be adjusted in the PC software.
Customer 2000 X
Service 2001 X X
Master 2002 X X X
A parameter cannot be entered with a password that is ranking too low. But the settings can be displayed without password entry.
Each parameter can be protected by a specific password level. To do so, the PC utility software must be used. Enter the parameter
to be configured and select the correct password level.
The password level can also be changed from the parameter view in the column "Level".
To gain access to adjust the parameters, the password level must be entered:
INFO
The customer password can be changed in jump menu 9116. The service password can be changed in jump menu 9117.
The master password can be changed in jump menu 9118.
INFO
The factory passwords must be changed if the operator of the genset is not allowed to change the parameters.
INFO
It is not possible to change the password at a higher level than the password entered.
The reason for having two possibilities to deactivate the start relay is to be able to delay the alarms with run status.
If it is not possible to activate the run status alarms at low revolutions, the remove starter function must be used.
An example of a critical alarm is the oil pressure alarm. Normally, it is configured according to the shutdown fail class. But if the
starter motor has to disengage at 400 RPM, and the oil pressure does not reach a level above the shutdown setpoint before 600
RPM, then, obviously, the genset would shut down if the specific alarm was activated at the preset 400 RPM. In that case, the
running feedback must be activated at a higher number of revolutions than 600 RPM.
RPM
RPM
1000
600
400
t
Oil pressure
Running
Remove starter
If an external running relay is installed, then the digital control inputs for running detection or remove starter can be used.
Running feedback
When the digital running feedback is active, the start relay is deactivated and the starter motor will be disengaged.
RPM
RPMNOM
RPM
Run. feedback
t
Firing speed
Remove starter
When the digital remove starter input is present, the start relay is deactivated and the starter motor will be disengaged.
RPM
RPMNOM
RPM
Run. feedback
Remove starter
t
Firing speed Running
The diagram illustrates how the remove starter input is activated when the engine has reached its firing speed. At the running speed,
the digital running feedback is activated.
INFO
The remove starter input must be configured from a number of available digital inputs.
INFO
The running feedback is detected by either the digital input (see diagram above), frequency measurement above 32 Hz,
RPM measured by magnetic pick-up or EIC (option H5/H7).
When a magnetic pick-up (MPU) is being used, the specific level of revolutions for deactivation of the start relay can be adjusted.
Running feedback
The diagram below shows how the running feedback is detected at the firing speed level. The factory setting is 1000 RPM (6170
Running detect.).
RPM
RPMNOM
RPM
Run. feedback,
menu 6173
t
Firing speed
CAUTION
Notice that the factory setting of 1000 RPM is higher than the RPM level of starter motors of typical design. Adjust this
value to a lower value to avoid damage of the starter motor.
RPM
RPMNOM
RPM
Run. feedback,
menu 6173
Remove starter,
menu 6174
t
Firing speed Running
INFO
The number of teeth on the flywheel must be adjusted in menu 6170 when the MPU input is used.
The multi-inputs on terminals 102, 105 and 108 can be used for the detection of running feedback. The terminal in question must be
configured as a RMI input for oil pressure measurement.
When the oil pressure increases above the adjusted value (6175 Pressure level) then the running feedback is detected and the
start sequence is ended.
Running feedback
RPMNOM
RPM
Run detection
Oil pressure
menu 6175
t
Firing speed
The drawing below shows how the setpoint of the "remove starter input" is detected at the firing speed level. The factory setting is
400 RPM (6170 Running detect.).
RPMNOM
RPM
Run detection
Oil pressure
menu 6175
Remove starter,
menu 6174
t
Firing speed Running
INFO
The remove starter function can use the MPU or a digital input.
In some emergency installations, the prime mover is equipped with an extra start motor. Dependent on the configuration, the
"Double starter" function can toggle between the two starters or try several attempts with the standard starter before switching to the
"Double starter".
The "Double starter" function is set up in channel 6191-6192, and a relay for cranking with the alternative starter is chosen in the
configuration of inputs/outputs.
INFO
Remember to write the settings when changing the I/O configuration.
6191 Standard attempts Accepted total number of start attempts before a "start failure" alarm is activated
6192 Double attempts The number of start attempts before redirecting the start signal
The "Double starter" function is enabled by choosing a value higher than zero in channel 6192. This value determines the amount of
attempts on each starter before switching to the next. The "standard starter" has first priority. When the maximum allowed number of
attempts, defined in channel 6191, is reached, the start attempts stop and the alarm "Start failure" appears.
- A value of 1 in channel 6192 results in a toggle function with 1 attempt on each starter between toggling.
- A value of 2 in channel 6192 results in a toggle function with 2 attempts on each starter between toggling.
Examples:
6191 Std attempts 6192 Dbl attempts 1st attempt 2nd attempt 3rd attempt 4th attempt 5th attempt
There are five possible selections for the setting of breaker type for both mains breaker and generator breaker.
This type of signal is most often used combined with a contactor. When using this type of signal, the AGC will only use the close
breaker relays. The relay will be closed for closing of the contactor and will be opened for opening of the contactor. The open relay
can be used for other purposes. Continuous NE is a normally energised signal, and Continuous ND is a normally deenergised
signal.
Pulse
This type of signal is most often used combined with circuit breaker. With the setting pulse, the AGC will use the close command
and the open command relay. The close breaker relay will close for a short time for closing of the circuit breaker. The open breaker
relay will close for a short time for opening of the breaker.
External/ATS no control
This type of signal is used to indicate the position of the breaker, but the breaker is not controlled by the AGC.
Compact
This type of signal will most often be used combined with a compact breaker, a direct controlled motor driven breaker. With the
setting compact, the AGC will use the close command and the open command relay. The close breaker relay will close for a short
time for the compact breaker to close. The breaker off relay will close for the compact breaker to open and hold it closed long
enough for the motor in the breaker to recharge the breaker. If the compact breaker is tripped externally, it is recharged automatically
before next closing.
At any time, the controller must receive the feedback from the breaker regarding its position whether it is in opened or in closed
position. When the controller fails to receive a position feedback from the breaker, the alarm “Position Failure” is generated.
When a controller has position failure alarm on its breaker, the symbolic representation of breaker in the application supervision will
be disappeared stating it is a position failure as the picture below illustrates.
INFO
The fail class of alarm "breaker Pos. fail" is configured to warning as standard which allows the breaker to retry the action
that it was previously doing before the alarm occurred.
To avoid breaker close failures in situations where breaker ON command is given before the breaker spring has been loaded, the
spring load time can be adjusted for GB/TB and MB.
The following describes a situation where you risk getting a close failure:
1. The genset is in auto mode, the auto start/stop input is active, the genset is running and the GB is closed.
2. The auto start/stop input is deactivated, the stop sequence is executed and the GB is opened.
Different breaker types are used, and therefore there are two available solutions:
1. Timer-controlled
A load time setpoint for the GB/TB and MB control for breakers with no feedback indicating that the spring is loaded. After the
breaker has been opened it will not be allowed to close again before the delay has expired. The setpoints are found in menus 6230,
7080 and 8190.
INFO
On the AGC mains unit (option G5), the spring load feedback from the tie breaker can be connected instead of the GB
spring load feedback.
2. Digital input
Two configurable inputs to be used for feedbacks from the breakers: One for GB/TB spring loaded and one for MB spring loaded.
After the breaker has been opened it will not be allowed to close again before the configured inputs are active. The inputs are
configured in the ML-2 utility software. When the timers are counting, the remaining time is shown in the display.
If the two solutions are used together, both requirements are to be met before closing of the breaker is allowed.
To alert the user that the breaker close sequence has been initiated but is waiting for permission to give the close command, the
LED indication for the breaker will be flashing yellow in this case.
If the breaker needs time to reload the spring after it has opened, then the AGC can take this delay into account. This can be
controlled through timers in the AGC or through digital feedbacks from the breaker, depending on the breaker type.
The diagram shows an example where a single AGC in island mode is controlled by the AUTO start/stop input.
This is what happens: When the AUTO start/stop input deactivates, the GB opens. The AUTO start/stop is reactivated immediately
after the GB has opened, for example by the operator through a switch in the switchboard. However, the AGC waits a while before it
issues the close signal again, because the spring load time must expire (or the digital input must be activated - not shown in this
example). Then the AGC issues the close signal.
GB closed
GB open
Auto Start/stop ON
Racked out breaker is a function which is used when the breaker's test mode is active or when the breaker is out for maintenance.
The feature “racked out breaker” informs the system that the physical position of the breaker is open no matter the position feedback
of the actual breaker, which makes it possible to operate the racked out breaker without interfering with the rest of the system.
INFO
When the feature "Racked Out Breaker" is activated, the specific controller expects the breaker to physically be
disconnected from the busbar, and thereby the breaker can be opened and closed instantly without any synchronisation
check no matter the busbar state.
When the breaker is out for maintenance, the position feedback might not be present on the controller which causes a "position
failure" alarm, and while the breaker is in test mode, the technician might operate the breaker manually which causes a "breaker Ext.
tripped" alarm.
If the above mentioned alarms are triggered while the “racked out breaker” is active, alarms are suppressed by changing the fail
class of the specific alarms to "Warning". This ensures that the alarm will not interfere with other breakers in the system.
A DG or mains controller that has the "breaker racked out" feature active, will inform the other controllers in the system that the
breaker is open but also that the power source is not available on the busbar.
In the input list from the USW, the tag “breaker racked out” is assigned to specific inputs. See screenshot below.
INFO
Depending if it is a DG, mains or BTB controller, GB, TB, MB or BTB -"racked out" is shown in the input list.
Several conditions have to be fulfilled before the “Racked out breaker” function will come active.
If all the above conditions are fulfilled, the status text and the USW will show “BREAKER RACKED OUT”.
INFO
If a "position failure" or "breaker ext. trip" occurs while the breaker is racked out and the input for the feature is high, the
alarms will show but the fail class will be inhibited.
The pictures below show an illustration of a mains with both MB, and TB racked out, 1 feedback ON and 1 feedback OFF still it is
recognised as an open signal while the breaker racked out input is high.
INFO
When a genset controller is in racked out breaker mode it will not be possible to use ground relay function. See
documentation for option G4, G5 and G8 for more information about ground relay.
Function Description
Inhibit 1
Inhibit 3
Run status Running detected and the timer in menu 6160 expired
Not run status Running not detected or the timer in menu 6160 not expired
INFO
The timer in 6160 is not used if binary running feedback is used.
Inhibit of the alarm is active as long as one of the selected inhibit functions is active.
In this example, inhibit is set to Not run status and GB ON. Here, the alarm will be active when the generator has started. When the
generator has been synchronised to the busbar, the alarm will be disabled again.
INFO
The inhibit LED on the unit and on the display will activate when one of the inhibit functions is active.
INFO
Function inputs such as running feedback, remote start or access lock are never inhibited. Only alarm inputs can be
inhibited.
INFO
The tie breaker unit has no running detection that can be configured, so the only inhibit functions are the binary input and
the TB position.
Alarms can be adjusted to activate only when the running feedback is active and a specific time delay has expired.
The diagram below illustrates that after activation of the running feedback, a run status delay will expire. When the delay expires,
alarms with Run status will be activated.
t
Alarms active
INFO
The timer is ignored if digital running feedback is used.
The input to be used for the access lock function is defined in the ML-2 PC utility software (USW).
Access lock will typically be activated from a key switch installed behind the door of the switchboard cabinet. As soon as access lock
is activated, changes from the display cannot be made.
Access lock will only lock the display and will not lock any AOP or digital input. AOP can be locked by using M-Logic.
It will still be possible to read all parameters, timers and the state of inputs in the service menu (9120).
It is possible to read alarms, but not any alarms when access lock is activated. Nothing can be changed from the display.
This function is ideal for a rental generator, or a generator placed in a critical power segment. The operator does not have the
possibilitiy to change anything. If there is an AOP-2, the operator will still be able to change up to 8 different predefined things.
INFO
The stop push-button is not active in semi-auto mode when the access lock is activated. For safety reasons it is
recommended to install an emergency stop switch.
INFO
AOP buttons are not locked when access lock is activated.
6.5 Overlap
The purpose of the overlap function is to be able to define a maximum paralleling time between the generator and the mains supply.
The function is typically used if there are local requirements to maximum allowed paralleling time.
INFO
The overlap function is only available in the automatic mains failure and load takeover genset modes.
GB
The diagram shows that when the generator breaker is synchronised, the mains breaker will be opened automatically after a time
delay (t). Later the mains breaker is synchronised, and the generator breaker is opened after the time delay (t).
The time delay is measured in seconds and can be adjusted from 0.10 to 99.90 seconds.
INFO
The same time delay is used for both generator and mains breaker synchronisation.
INFO
If the function is used in a Power Management (option G5) application, then the overlap will occur between the mains
breaker and the tie breaker on the AGC mains.
INFO
The time delay typed in the setpoint is a maximum time. This means that if 0.10 seconds are used, the two breakers will
never be closed at the same time for a longer delay than the setpoint.
The flowchart below shows that if the input is configured, it needs to be activated (by a pulse) in order to initiate the mains return
sequence. The load will continue on generator supply if the input is not activated.
The mains OK delay is not used at all when the "Mains OK" input is configured.
No MB input Yes
configured
Mains OK MB control
delay input
No No
Expired ON
Yes Yes
MB and GB
operation
Sequence
INFO
To start in AUTO mode, the "Auto start/stop" command can be programmed in M-Logic or in the input settings.
INFO
The time-dependent commands are flags that are raised when the command timer is in the active period.
INFO
If the relay function is not changed to "limit" function, an alarm will appear at every running situation.
This droop function is a mains aid function. It can be used when the genset is running parallel to the mains in the following modes:
"Fixed power", "Mains power export" and "Peak shaving". In case the frequency drops or rises due to instability of the mains, the
curve for frequency-dependent droop is made to compensate the power set point. The power set point will be reduced with greater
mains frequency and increased when the mains frequency is lower than specified.
This example and diagram is based on the parameters from the table below. With a nominal frequency of 50 Hz and an actual
frequency of 51.5 Hz, there is a deviation of 1.5 Hz which is equal to a 3 % deviation from the nominal setting. The genset will then
droop to 400 kW according to the below diagram.
P [KW]
MAX
DBH
HYSH
SLPL
SLPH
HYSL
DBL
MIN
(Fnom-fact)*100/fact [%]
10% 9% 8% 7% 6% 5% 4% 3% 2% 1% 0% 1% 2% 3% 4% 5% 6% 7% 8% 9% 10%
Hysteresis low in percentages of nominal frequency. If HYSL is set above DBL, the hysteresis low
7123 1 HYSL[%]
is disabled.
Hysteresis high in percentages of nominal frequency. If HYSH is set above DBH, the hysteresis
7124 1 HYSH[%]
high is disabled.
Slope low. The setting determines the increase/decrease of power reference per percentage the
7133 50 SLPL[kW/%]
actual frequency drops below nominal frequency.
Slope high. The setting determines the increase/decrease of power reference per percentage the
7134 -50 SLPH[kW/%]
actual frequency rises above nominal frequency.
INFO
AGC-4: The frequency dependent droop curve is not configured in "parameters", but in "Advanced protections" under the
tab "Droop curve 1". Compliance with new grid code rules are possible with a combination of AGC-4 and option A10. See
option A10 documentation for more information.
This droop function is performed based on the actual value for the power set point in the moment the droop is activated. If the
function for an example is activated during ramping and the actual power value at this moment is 200 kW, the droop is performed
based on 200 kW as the "Fixed Power Setpoint" stated in the diagram.
When drooping, the slopes will be scaled based on size of the actual power at the droop start, compared to the specified nominal
power. For example, if a DG of nominal 1000 kW is producing 500 kW when droop is activated, then only 50 % of the slope values
will be used. To achieve a nominal droop of 40 % per Hz, a 1000 kW (50 Hz) DG should be configured with slopes of 200 kW/%. If
DG then only is producing 500 kW when droop is activated, the actual slope will be experienced as 100 kW/%.
If "Auto ramp selection" is enabled (channel 2624), the secondary pair of ramps will be used during frequency-dependent power
droop. In order to prevent a new situation with faulty mains, it may be advantageous to use slower ramps in or after a situation with
an unstable mains. The secondary ramps will automatically be disabled again when the frequency-dependent power droop is no
longer active, and the specified power set point is reached. If "Auto ramp selection" is disabled, it is only possible to activate the
secondary ramps using M-Logic. Parameters used for the secondary ramps are stated in the table below.
2623 0.1[%/s] Ramp down speed 2 Slope of ramp 2 when ramping down (not used for deload)
2624 ON Auto ramp selection Activate or disable automatic selection of secondary ramps
This function is for making a power offset from Pnom, 3 offsets are available. It is possible to enable offsets in M-Logic, where
offsets can be used as an event or an output where offsets can be activated or deactivated. The offset can be set in menu
7220-7225. The enabled power offsets will be added/subtracted from the fixed power setpoint in menu 7051, which refers to Pnom.
INFO
The adjusted fixed power setpoint will be limited to be inside the values in menu 7023 "Minimum load", and maximum value
is Pnom.
This function is for making a power offset from Pnom, 3 offsets are available. It is possible to enable offsets via M-Logic, where
offsets can be used as an event or an output where offsets can be activted or deactivated. The cos phi offsets can be set in menu
7241-7245. The enabled cos phi offsets will be added/subtracted from the fixed cos phi setpoint in menu 7052.
INFO
The adjusted fixed cos phi setpoint will be limited to be inside the values in menu 7171 "Cos phi (x2)", and maximum value
is in menu 7173 "Cos phi (x2)".
INFO
The values in menu 7050 set the cos phi. This is not the PF value displayed in the display. cos phi and PF are only equal if
it is a true sinusoidal wave.
Input Comment
0-5V DC
Multi-input (M16.X) 4-20 mA
Pt100
Water temp.
EIC (only with option H5/H7/H13)
Oil temp.
M-Logic
INFO
Refer to the type label for information about engine interface selection.
The parameters that define the derate characteristics are the following:
This is the setting where the derating must start. The setting can be in mA (max. 20 mA) or in centigrades ºC (max. 200ºC).
Adjust the derating speed. The adjustment is in percent per unit, i.e. if the 4-20 mA input is used, then the derating will be in
%/mA, and if the Pt100/Pt1000/RMI input is used, then the derating will be in %/C.
INFO
Be aware that the 4-20 mA input can be configured with different minimum and maximum settings. In this case the settings
"start derate point" and "slope" use these new settings.
PNOM
PLIMIT
mA
0 10 16 20
Start
derate
It can be selected whether the characteristic of the derating should be proportional or inverse proportional. The drawing above
shows the inverse characteristic.
PNOM
PLIMIT
mA
0 10 16 20
Start
increase
The genset is derated when the control value is lower than the setpoint (in the example above the control value is an mA signal).
It is possible to use the idle run function with or without timers. Two timers are available. One timer is used in the start sequence,
and one timer is used in the stop sequence.
INFO
The speed governor must be prepared for the idle run function if this function is to be used.
The function is typically used in installations where the genset is exposed to low temperatures which could generate starting
problems or damage the genset.
6.12.1 Description
The function is enabled and configured in 6290 Idle running. It has to be noted that the governor itself must handle the idle speed
based on a digital signal from the unit (see the principle diagram below).
When the function is enabled, two digital inputs are used for control purposes:
This input is used to change between idle speed and nominal speed. This input does not prevent
1 Low speed input
the genset from stopping - it is only a selection between idle and nominal speed.
Temperature control When this input is activated, the genset will start. It will not be able to stop as long as this input is
2
input activated.
INFO
If the idle run function is selected by means of timer, the low speed input is overruled.
INFO
The input must be configured through the PC software at commissioning.
INFO
One extra relay output must be available on the unit. Notice that this is option-dependent.
INFO
Turbo chargers not originally prepared for operating in the low speed area can be damaged if the genset is running in "idle
run" for too long.
High/low
Start/stop
speed
gen-set
selection
Low speed
input Idle run input
relay
Multi-line 2 GOVERNOR
Temperature
control input
Actuator
6.12.2 Examples
The start and stop sequences are changed in order to let the genset stay at the idle level before speeding up. It also decreases the
speed to the idle level for a specified delay time before stopping.
RPM
1500
tSTART tSTOP
300
t
Start Stop
In this example, both timers must be deactivated. The idle speed with low speed activated will run in idle speed until the low speed
input is deactivated, and subsequently the genset will regulate to nom. values.
If the genset is to be prevented from stopping, then the digital input "temp control" must be left ON at all times. In that case the
characteristic looks like this:
RPM
1500
300
t
Start Stop
INFO
The oil pressure alarm (RMI oil) will be enabled during idle run if set to "ON".
This is an example of how to set up a system that will start up in idle speed, if the coolant temperature is below a specified value.
When the temperature exceeds the specified value, the genset will ramp up to nominal values.
Example
The function is made with delta analogue 1 (menus 4601, 4602 and 4610) and one M-Logic line. After starting, when the coolant
temperature is below 110 degrees, the unit will idle. Once the temperature reaches 110 degrees, the unit will automatically ramp up
to full speed. See the settings below.
6.12.5 Inhibit
The alarms that are deactivated by the inhibit function are inhibited in the usual manner, except for the oil pressure alarms; RMI oil
102, 105 and 108 which are active during "idle run" as well.
The running feedback must be activated when the genset is running in idle mode.
INFO
The running detection level (parameter 6173) must be below the idle speed. See Start-up overview with idle run.
The flowcharts illustrate the starting and stopping of the genset by use of the inputs "temp control" and "low speed".
6.12.8 Start
Start
Auto
No
start/stop
ON
Yes No
Temp control ON No starting
Start the
Genset
Yes
No Yes
Timer expired
Yes
Genset running
Genset running at f Nom
at idle speed
End
Start
Auto
No Temp control No Genset running
start/stop
OFF at Nom. speed
OFF
Yes Yes
No Idle timer on
Lowspeed ON No Yes
Yes
Yes
Genset stop
sequence
End
Set point: This set point +/- the hysteresis is the start and stop points for the engine heater.
Hysteresis: This decides how big a deviation from the set point is needed to activate/deactivate the engine heater.
Principle diagram:
37°C
Engine heater
relay
Start attempt
DG running
INFO
The engine heater function is only active when the engine is stopped.
If the temperature keeps dropping after the start set point has been exceeded, an alarm will be raised if configured in menu 6330.
INFO
This function can only be used if island operation is selected.
In a 50 Hz system one period lasts 20 ms. If this changes, e.g. due to the dead band setting of the frequency controller, a difference
will exist between the actual number of periods and the theoretical number of periods.
Equipment that works based on the zero crossings will be affected by the surplus or missing zero crossings. The most common
example of such equipment is alarm clocks.
The unit’s internal clock is a timekeeper which is included in the battery backed memory circuit. The timekeeper function works
based on an oscillating crystal instead of zero crossings of the AC measurements. Due to the accuracy of the timekeeper, it is
recommended to synchronise the clock on a regular basis, e.g. once every month.
INFO
The compensation frequency must be adjusted to a value higher than the dead band setting.
The time for the compensation can easily be calculated at a given adjustment of 6403 and 6404 (example):
• 6403 = 30 seconds
• 6404 = +/- 0.1 Hz
If a mains failure occurs during the battery test sequence, the test will automatically be interrupted, and the automatic mains failure
start up sequence will be activated.
During the test, the battery voltage will decrease and an alarm will occur if it drops to the set point that has been configured in
"Battery test" (channel 6411).
UBATTERY
Alarm
Cancel test
t
Test 1 Test 2
The drawing shows that test #1 is carried out without a large voltage drop of the battery voltage, whereas test #2 reaches the alarm
set point.
As there is no reason to wear the battery down even more, the test stops when the battery test alarm occurs.
The test is typically used at periodical intervals, for example, once every week. The engine must be at a standstill when the test is
started. Otherwise, the test command will be ignored.
The drawing below shows that when the test is started, the start relay activates, making the engine turn.
The engine will turn in the time period that has been configured in "Battery test" (channel 6412).
Stop coil
or
Run coil
Start test
If the set point in "Battery test" (channel 6413) has been configured to "X + Start sequence", the genset will run the defined start
attempts (without activating run coil). This function is used to test that the battery can withstand more than one start attempt.
Battery test
X + Start Sequence
Start Prepare 1 2 3
(3 start attempts)
Start relay
A battery test configured as “X + Start sequence”, as shown in the above example, will use: “Start prepare” timer, “Start on time” and
“Start off time”. In this example, the genset will crank three times with “Start prepare” and “Start off time” delay in between each
crank. When the test has finished, a start failure alarm will be present.
If at any point the battery voltage is lower than the set point “Battery test” (channel 6411), the test will be cancelled.
Description Comments
CAUTION
For normal operation, the start failure alarm must be acknowledged after the test has ended.
If this function is to be used, it is necessary to configure a digital input that initiates the function. This is done in the dialogue box
below.
INFO
If AUTO mode is selected, the mains failure sequence will be initiated if a mains failure occurs during the battery test.
If the automatic battery test is used, the function must be enabled in menu 6420. When the function is enabled, the battery test will
be carried out with a specified interval, for example, once a week. Completed battery tests will be logged in a separate battery test
log.
INFO
The factory setting in menu 6424 is 52 weeks. This means that the automatic battery test will be executed once a year.
INFO
If "Battery test" (channel 6413) is configured to "X + Start sequence", the alarm "Start failure" (channel 4570) will occur at
the end. If the alarm is left unacknowledged, the genset will not be operational.
The reason for making the battery asymmetry test is to determine if one of the batteries is getting weak. The battery asymmetry is a
combination of measurements and calculations.
The following seven battery applications are supported. The shown applications are merely examples – the choice of multi-input (MI)
or power supply input is configurable in menu 6410.
- + - +
- + - +
- + - +
Start/Manoeuvre
battery Start/Manoeuvre
battery
Application 3:
Application 4:
Multi-line 2 Multi-line 2
AUX AUX
MI 1 MI 3 MI 1
A E B C D A E B
- + - + - + - + - + - +
Manoeuvre battery Start battery
Manoeuvre battery
Application 5:
Multi-line 2
AUX
MI 2
MI 1
A E F B
- + - +
- + - +
Manoeuvre battery
Multi-line 2 Multi-line 2
MI 3 AUX
MI 2 MI 2
AUX MI 1 MI 1 MI 3
A B C EF D A E F B C D
- + - + -+ -+ - + - + - + - +
- + - + -+ -+ - + - + - + - +
Manoeuvre battery Start battery Manoeuvre battery Start battery
Application 1:
Multi-line 2
AUX
MI 1
A E B
- + - +
Start/Manoeuvre
battery
The power supply measurement is used as the reference RF1 (points A and B) in menu 6432 and multi-input 1 is used as the type
T1 (points A and E) in menu 6431. By making these measurements, it is possible to calculate the voltage between E and B. This
gives a full picture of battery voltages, for example:
INFO
If application 3, 6 or 7 is used, it is expected that one of the multi-inputs is used for the battery test of the starter battery.
INFO
It is expected that the multi-inputs used for the battery asymmetry are configured to "0 to 40 V DC".
INFO
The selection power supply is referring to the supply on terminals 1 and 2.
Alarms for battery asymmetry 1 and 2 are set up in menus 6440 and 6450.
6.16 Ventilation
This function can be used to control the cooling of the engine. The purpose is to use a multi-input for measuring the cooling water
temperature and that way activate an external ventilation system to keep the engine below a maximum temperature. The
functionality is shown in the below diagram.
Set point: The limit for activation of the relay set in OA.
Output A (OA): The relay activated when the set point is exceeded.
The number of degrees the temperature has to be below the set point in order to deactivate the relay set in
Hysteresis:
OA.
INFO
The type of input to use for the temperature measurement is selected in menu 6323 Engine heater.
95°C
85°C
Relay
Two alarms can be set up in menu 6470 and menu 6480 to activate if the temperature keeps rising after the start set point has been
reached.
INFO
The function only supports the Danish rules.
When activated, this function will block the start sequence of the genset in case the genset is not running.
Setpoints available:
Delay: When the input is active, the alarm will be activated when this delay has expired.
OFF: Only AMF start sequence is blocked when the input is active.
Parallel:
ON: All start sequences, regardless of running mode, are blocked when the input is active.
When activated, this function will stop the genset if the genset is running in Auto mode.
Setpoints available:
When the input is active and the delay has expired, the genset will trip the breaker, cool down and stop. The
Delay:
function is active regardless of the "Enable" setting.
6551 Fuel pump log. start Fuel transfer pump start point in percentage.
6552 Fuel pump log. stop Fuel transfer pump stopping point in percentage.
6553 Fuel fill check Delay timer before activating fuel fill check alarm.
The output relay to be used for control of the fuel pump. The selected relay activates below the
6554 Output A
start limit and deactivates above the stop level.
The multi-input or external analogue input to be used for the fuel level sensor.
6555 Type Choose multi-input if 4-20 mA is used.
Choose "auto detection" if an RMI is used.
6556 Fail class The fail class of the fuel fill alarm.
INFO
The fuel pump relay can be activated via M-Logic.
INFO
The output relay should be configured as a limit relay. Otherwise, an alarm will be raised whenever the output is activated.
The below drawing shows how the fuel pump is activated when the level reaches 20% and stopped again when the level has
reached 80%.
Fuel level
Fuel service tank level
80%
20%
Time
When the fuel pump is running, the fuel level must increase by 2% within the fuel fill check timer set in menu 6553. If the fuel level
does not increase by 2% within the adjusted delay time, then the fuel pump relay deactivates and a Fuel fill alarm occurs.
∆ level, 2%
tFill check
INFO
The level of increase is fixed at 2% and cannot be changed.
All activated alarms must be configured with a fail class. The fail classes define the category of the alarms and the subsequent
alarm action.
Nine different fail classes can be used. The tables below illustrate the action of each fail class when the engine is running or
stopped.
INFO
All fail classes trigger the alarm "Warning", which is shown in the active alarm log.
1 Block X X
2 Warning X X
3 Trip GB X X X
4 Trip + stop X X X X X
5 Shutdown X X X X
6 Trip MB X X X
9 Controlled stop* X X X X X X
INFO
* In the table above, Safety stop and Controlled stop are illustrated to be identical, but they will act differently: Safety stop
will de-load and stop the genset if other power sources are able to take the load; if not, the genset will not stop. Controlled
stop will de-load the genset, but if no other power sources are available to take the load, the genset will trip the breaker and
stop. This means that Controlled stop will prioritise protection of the genset, whereas Safety stop will prioritise the load.
INFO
The fail class "Safety stop" will only de-load the genset before opening the breaker if option G4 or G5 (power management)
is used. If power management is not active, the "Safety stop" will have the same function as "Trip and stop".
INFO
The fail class "Trip MB/GB" will only trip the generator breaker if there is no mains breaker present.
Fail class Action Block engine start Block MB sequence Block GB sequence
1 Block X
2 Warning
3 Trip GB X X
4 Trip + stop X X
5 Shutdown X X
6 Trip MB X
7 Safety stop X
9 Controlled stop X X
INFO
In addition to the actions defined by the fail classes, it is possible to activate one or two relay outputs if additional relays are
available in the unit.
INFO
The fail class "Trip MB/GB" will only block engine start and GB sequence if there is no mains breaker present.
The fail class can be selected for each alarm function either via the display or the PC software.
To change the fail class via the PC software, the alarm function to be configured must be selected. Select the desired fail class in the
fail class roll-down panel.
INFO
The two terms "trip of non-essential load" and "load shedding" describe the same functionality.
The trip of Non Essential Load (NEL) groups (load shedding) is carried out in order to protect the busbar against an imminent
blackout situation due to either a high load/current or overload on a generator set or a low busbar frequency.
• the measured load of the generator set (high load and overload)
• the measured current of the generator set
• the measured frequency at the busbar
The load groups are tripped as three individual load groups. This means that the trip of load group no. 1 has no direct influence on
the trip of load group no. 2. Only the measurement of either the busbar frequency or the load/current on the generator set is able to
trip the load groups.
Trip of the NEL groups due to the load of a running generator set will reduce the load on the busbar and thus reduce the load
percentage on the running generator set. This may prevent a possible blackout at the busbar caused by an overload on the running
generator set. The current trip will be selected in case of inductive loads and unstable power factor (PF <0.7) where the current is
increased.
Trip of the NEL groups due to a low busbar frequency will reduce the real power load at the busbar and thus reduce the load
percentage on the generator set. This may prevent a possible blackout at the busbar.
The function is based on running hours. When the adjusted time expires, the unit will display an alarm. The running hours is
counting when the running feedback is present.
The number of running hours to activate the alarm. The service timer alarm will be activated as soon as the
Running hours:
running hours have been reached.
The number of days to activate the alarm – if the running hours are not reached before this number of
Day: days, the alarm will still be activated. The service timer alarm will be activated at 8:00 AM on the day the
alarm expires.
Reset: Enabling this will reset the service timer to zero. This must be done when the alarm is activated.
0-40V DC ≤ 0V DC - N/A
Principle
The illustration below shows that when the wire of the input breaks, the measured value will drop to zero. Then the alarm will occur.
Input signal
(mA, °C,b, %)
Wire failure
Upper failure
limit
Lower failure
limit
Wire failure
t
Wire break
The MPU wire break function is only active when the genset is not running. In this case an alarm will be raised if the wire connection
between the AGC and MPU breaks.
The alarm will occur when the stop coil is not activated (generator is running) and the input is deenergised.
Engine interface card Available digital inputs – not configurable Available digital inputs – configurable
M4 (standard) 1 6
Input function Auto Semi Test Man Block DG Mains BTB Input type
4 Semi-auto X X X X X X X Pulse
5 Test X X X X X X Pulse
6 Auto X X X X X X X Pulse
7 Manual X X X X Constant
8 Block X X X X X X X Constant
11 Remote MB ON X X X X X Pulse
Remote alarm
13 X X X X X X X X Constant
acknowledge
15 Mains OK X X X X X X X Pulse
43 Deload X X Constant
49 Secured ON X X X X X X Pulse
INFO
From software version 4.70.0 onwards, AGC-4 does not have dedicated heavy consumer inputs and outputs. Use an
ALC-4 to control heavy consumers.
1. Shutdown override
This input deactivates all protections except the overspeed protection and the emergency stop input. The number of start attempts is
seven by default, but it can be configured in 6180 Start. Also a special cool down timer is used in the stop sequence after an
activation of this input.
2. Remote start
This input initiates the start sequence of the genset when semi-auto or manual mode is selected.
3. Remote stop
This input initiates the stop sequence of the genset when semi-auto or manual mode is selected. The genset will stop without
cooling down.
4. Semi-auto
5. Test
6. Auto
7. Manual
8. Block
INFO
When block mode is selected, the running mode cannot be changed by activating the digital inputs.
GB: The generator breaker ON sequence will be initiated and the breaker will synchronise if the mains breaker is closed, or close
without synchronising if the mains breaker is opened.
TB: The Tie breaker ON sequence will be initiated and the breaker will synchronise if the mains and generator breaker are closed, or
close without synchronising if the generator breaker is open.
BTB: The bus tie breaker ON sequence will be initiated and the breaker will synchronise if voltage is available on either or both sides
of the breaker, or close without synchronising if both sides of the busbar are dead.
GB: The generator breaker OFF sequence will be initiated. If the mains breaker is opened, then the generator breaker will open
instantly. If the mains breaker is closed, the generator will be deloaded to the breaker open limit followed by a breaker opening.
TB: The tie breaker will be opened irrespective of the mains and generator breaker positions.
BTB: The bus tie breaker will be open instantly dividing the busbar into two different sections.
11. Remote MB ON
The mains breaker ON sequence will be initiated and the breaker will synchronise if the generator breaker is closed, or close without
synchronising if the generator breaker is opened.
The mains breaker OFF sequence will be initiated, and the breaker will open instantly.
Acknowledges all present alarms, and the alarm LED on the display stops flashing.
The genset will start when this input is activated. The genset will be stopped if the input is deactivated. The input can be used when
the unit is in island operation, fixed power, load takeover or mains power export and the AUTO running mode is selected.
15. Mains OK
Disables the "mains OK delay" timer. The synchronisation of the mains breaker will happen when the input is activated.
The nominal frequency set point will be controlled from the analogue inputs terminal 40/41. The internal set point will not be used.
Note that a -10 V to 10 V signal is used to control and that the nominal frequency value will be located at 0 V.
INFO
With M-Logic "Gov/AVR control" it is possible to change the analogue input source to CIO 308 1.8 (4-20mA)
The power set point in fixed power will be controlled from the analogue inputs terminal 40/41. The internal set point will not be used.
Note that a 0 V - 10 V is used for control.
The nominal voltage set point will be controlled from the analogue inputs terminal 41/42. The internal set point will not be used. Note
that a -10 V to 10 V signal is used for control.
INFO
With M-Logic "Gov/AVR control" it is possible to change the analogue input source to CIO 308 1.11 (4-20mA)
The cos phi set point will be controlled from the analogue inputs terminal 41/42. The internal set point will not be used. Note that a 0
V to 10 V signal is used for control.
INFO
With M-Logic "Gov/AVR control" it is possible to change the analogue input source to CIO 308 1.11 (4-20mA)
The reactive power set point will be controlled from the analogue inputs terminal 41/42. The internal set point will not be used. Note
that a -10 V to 10 V signal is used for control.
INFO
With M-Logic "Gov/AVR control" it is possible to change the analogue input source to CIO 308 1.11 (4-20mA)
The start sequence is deactivated. This means the start relay deactivates, and the starter motor will disengage.
INFO
All analogue controller outputs are reset. That is the governor output and the AVR output if option D1 is selected.
If an offset has been adjusted in the control setup, then the reset position will be the specific adjustment.
INFO
The manual governor and AVR increase and decrease inputs can only be used in manual mode.
Activates the starter without starting the genset. If the battery is weak, the test will cause the battery voltage to drop more than
acceptable, and an alarm will occur.
When this input is activated, then the mains breaker cannot close.
Disables the regulators and keeps the genset running at a low RPM.
INFO
The governor must be prepared for this function.
This input is part of the idle mode function. When the input is high, then the genset starts. It starts at high or low speed, depending
on the activation of the low speed input. When the input is deactivated, then the genset goes to idle mode (low speed = ON), or it
stops (low speed = OFF).
The input activates the mode shift function, and the AGC will perform the AMF sequence in case of a mains failure. When the input
is configured, the setting in menu 7081 (mode shift ON/OFF) is disregarded.
When the input is activated, the AGC is allowed to close the generator on a black busbar, providing that the frequency and voltage
are inside the limits set up in menu 2110.
Activating this input will split the breaker close and breaker synchronisation functions into two different relays. The breaker close
function will remain on the relays dedicated for breaker control. The synchronisation function will be moved to a configurable relay
dependent on the options configuration.
INFO
This function is option-dependent. Option M12 or M14.x is required.
The input is used as a running detection of the engine. When the input is activated, the start relay is deactivated.
Activating the access lock input deactivates the control display push-buttons. It will only be possible to view measurements, alarms
and the log.
This input is used to simulate an AMF failure and this way run a full AMF sequence without a mains failure actually being present.
The input will stop or block the genset depending on running status.
This input will be logged in the event log to indicate that a planned mains failure has been made.
INFO
When the genset is started, the input can be removed.
The AGC will not send a close signal before this feedback is present.
The AGC will not send a close signal before this feedback is present.
43. Deload
The generator breaker will open, the genset will activate the stop sequence and when the genset is stopped, it will be blocked for
start.
Secured mode adds an extra generator to the system, i.e. one generator too many will be running when comparing with the actual
power requirement.
The generator set will run base load (fixed power) and not participate in frequency control. Should the plant power requirement drop,
the base load will be lowered so the other generator(s) on line produces at least 10 % power.
When this input is activated , the generator controller is informed by the group controller to activate close before excitation.
(Redundant of CBE AVR two)
INFO
This function is option-dependent. Option G7 is required
When this input is activated, the generator controller is informed by the group controller to activate close before excitation.
(Redundant of CBE AVR one)
INFO
This function is option-dependent. Option G7 is required
The breaker will be considered as racked out when pre-requirements are met and this input is activated (for more info, see Racked
out breaker)
The breaker will be considered as racked out when pre-requirements are met and this input is activated (for more info, see Racked
out breaker)
INFO
The input functions are set up with the PC utility software. Please refer to the "Help".
6.26 Outputs
The unit has a number of output functions which can be configured to any available relay.
Output function Auto Semi Test Man Block Configurable Output type
Trip NEL 1
Trip NEL 3
INFO
For more information, see Trip of NEL.
For all alarm functions, it is possible to activate one or two output relays as shown below. This paragraph explains how to use an
alarm function to activate an output without any indication of alarm. ON and OFF delay timers are described as well.
In the example below, the relay will close when the generator voltage is above 103 % for 10 seconds, and no alarm will appear on
the screen because both output A and output B are configured to relay 5, which is configured as "Limit relay".
The timer configured in the alarm window is an ON delay that determines the time during which the alarm conditions must be met
before activation of any alarms or outputs.
When a relay is selected (relay on terminal 5 in this example), it must be set up as a limit relay as shown below, otherwise an alarm
indication will still appear.
6.28 Multi-inputs
The AGC unit has three multi-inputs which can be configured to be used as the following input types:
1. 4 to 20 mA
2. 0 to 40 V DC
3. Pt100
4. Pt1000
5. RMI oil
6. RMI water
7. RMI fuel
8. Digital
INFO
The function of the multi-inputs can only be configured in the PC utility software.
Two alarm levels are available for each input, the menu numbers of the alarm settings for each multi-input is controlled by the
configured input type as seen in the following table.
INFO
Only one alarm level is available for the digital input type.
6.28.1 4 to 20 mA
If one of the multi-inputs has been configured as 4 to 20 mA, the unit and range of the measured value corresponding to 4 to 20 mA
can be changed in the PC utility software in order to get the correct reading in the display.
6.28.2 0 to 40 V DC
The 0 to 40 V DC input has primarily been designed to handle the battery asymmetry test.
6.28.3 Pt100/1000
This input type can be used for heat sensor, for example cooling water temp. The unit of the measured value can be changed from
Celsius to Fahrenheit in the PC utility software in order to get the desired reading in the display.
The unit can contain up to three RMI inputs. The inputs have different functions, as the hardware design allows for several RMI
types.
These various types of RMI inputs are available for all multi-inputs:
For each type of RMI input it is possible to select between different characteristics including a configurable.
Bar psi Ω Ω Ω
0 0 10.0 10.0
0.5 7 27.2
1.5 22 62.9
2.5 36 99.2
4.5 65 168.3
6.0 87 124.3
INFO
The configurable type is configurable with eight points in the range 0 to 480 Ω. The resistance as well as the pressure can
be adjusted.
INFO
If the RMI input is used as a level switch, then be aware that voltage must not be connected to the input. If any voltage is
applied to the RMI input, it will be damaged. Refer to the Application Notes for further wiring information.
RMI sensor
type
°C °F Ω Ω Ω Ω
INFO
The configurable type is configurable with eight points in the range 0 to 480 Ω. The temperature as well as the resistance
can be adjusted.
INFO
If the RMI input is used as a level switch, then be aware that voltage must not be connected to the input. If any voltage is
applied to the RMI input, it will be damaged. Refer to the Application Notes for further wiring information.
Type 1
Value Resistance
0% 78.8 Ω
100 % 1.6 Ω
Type 2
Value Resistance
0% 3Ω
100 % 180 Ω
INFO
If the RMI input is used as a level switch, then be aware that voltage must not be connected to the input. If any voltage is
applied to the RMI input, it will be damaged. Refer to the Application Notes for further wiring information.
% Resistance
10
20
30
40
50
60
70
80
90
100
INFO
The configurable type is configurable with eight points in the range 0 to 480 Ω. The value as well as the resistance can be
adjusted.
Resistance
(Ω)
Setpoint 8
Setpoint 7
Setpoint 6
Setpoint 5
Setpoint 4
Setpoint 3
Setpoint 2
Setpoint 1 Value
(bar, °C or %)
1 2 3 4 5 6 7 8
Setpoints
6.28.9 Configuration
The eight curve settings for the configurable RMI inputs cannot be changed in the display, but only in the PC utility software. The
alarm settings can be changed both in the display and in the PC utility software. In the PC utility software, the configurable inputs
are adjusted in this dialogue box:
The scaling of the analogue inputs is made to ensure that the readout of the inputs is made with a resolution that fits the connected
sensor. It is recommended to follow the list below when changing the scaling of the analogue inputs.
1. Set up the multi-input for 4 to 20 mA. This is done in menus 10980-11000 for multi-inputs 102-108 and in menus 11120-11190 for
option M15 or M16.
2. Now the scaling parameters are available in menus 11010-11110.
3. Activate the AUTO SCALE enable checkbox when setting up the inputs. This means that the reading remains the same - but
decimals are added.
4. Deactivating AUTO SCALE will make the reading smaller by a factor of 10 for each decimal added.
5. Then the alarm parameters for the multi-inputs can be configured.
6. A parameter file (usw file) should always be saved without the AUTO SCALE enabled.
INFO
The setup of the multi-inputs and alarm parameters must be done in the above order. If not, the alarm levels will be wrong.
Setting up decimals:
No decimals:
Decimals = 0
Without use of decimals, the set point can only be adjusted in steps of one bar, which gives a very rough range of setting.
One decimal:
Decimals = 1
INFO
Regarding AUTO SCALE: if the number of decimals is changed without enabling the set point, the 4 to 20 mA will be
presented as 0.4 to 2.0 mA (0.0 to 0.5 bar). In other words, the "Auto scaling" bit decides where the decimal point is
placed.
The measuring range of the multi-input is set up inside the actual alarm:
The three dots to the left of the figures is a button. Scale the input as required, for example 0 to 5 bar:
In order to get the alarm input to work again after changing the "decimal setting", it is necessary to make a readjustment of the
alarm:
Therefore, when selecting decimals, the selection of AUTO SCALE depends on whether the alarm inputs are already set up. If they
are set up, it is a good idea to select AUTO SCALE. If they are not set up, it is voluntary if AUTO SCALE is selected.
Reload parameters:
It is necessary to upload the parameters from the device to the computer after changing the scale (no decimal/one decimal/two
decimal) settings. This is in order to refresh the parameter list so the alarm settings present the correct value:
In the example shown above, the value can be adjusted with one decimal. If the parameters were not refreshed, it would still only be
possible to adjust the set point without decimals.
A parameter file (usw file) should always be saved without the AUTO SCALE enabled.
After having set up the 4 to 20 mA inputs (HW as well as alarms), the parameter file should be uploaded from the device to the PC
and then saved. In this way, the AUTO SCALE is deactivated (automatically cleared by the device), and the settings will not be
modified again if the parameters are reloaded to the device.
If the file is saved with the AUTO SCALE enabled, the minimum and maximum values of the alarm will be affected (multiplied by 10
or 100) at the next use of the parameter file (under certain conditions).
6.28.11 Digital
If the multi-inputs are configured to "Digital", they become available as a configurable input.
The manual governor and AVR control function can be activated by pressing more than two seconds, or by activating the
digital inputs or AOP buttons for governor or AVR control in semi-auto mode. The intention of this function is to give the
commissioning engineer a helpful tool for adjustment of the regulation.
When using the display arrows for increasing or decreasing, the output will change as long as the button is active. For the digital
input and AOP buttons, there is a timer so that it is possible to choose how long one pulse should be; the timer can be set to 0.1 to
10 sec. For the governor, the timer parameter is 2782 and for AVR, it is 2784. If for example the timer is set to 5 sec., then one push
on the AOP or one pulse from digital input will give 5 sec. increase or decrease of the output.
G 0 0 0V
P-Q Setp 100 % 100 %
P-Q Reg. 50 % 60 %
GOV AVR
In manual mode the regulation is deactivated. When activating the up or down arrows, the output value to GOV or AVR is changed,
this is the Reg. value in the display. The up and down arrows have the same function as the digital inputs or AOP buttons for
governor and AVR control when the window is open. To exit the regulation window press "back".
As in manual mode, the up and down arrows have the same function as the digital inputs or AOP buttons for governor or AVR
control when the window is open.
The value Setp can be changed by pressing the arrow up or down. When GOV is underlined, the governor setpoint will be changed,
and vice versa when the AVR is underlined. When changing the Setp value, an offset will be added to or subtracted from the
nominal value. The Reg. value is the output value from the regulator. If the genset is running in parallel, the active or reactive
nominal power setpoint value will be changed. If it is a stand-alone genset not parallel to the mains, the nominal frequency or
voltage setpoint will be changed and also displayed. When the "back" button is activated, the regulation setpoint returns to nominal.
INFO
If the digital inputs or AOP buttons are activated in semi-auto, the regulation window is automatically opened.
Like semi-auto, except from the fact that activating the digital inputs or AOP buttons for governor or AVR control will change the
regulation setpoint but not open the regulation window. When the digital inputs or AOP buttons are deactivated, the regulation
setpoint returns to nominal.
INFO
AVR setpoint manipulation requires option D1.
INFO
Regarding AOP setup, please refer to "Help" in the PC utility software.
This will initiate an alarm when the signal on the digital input disappears.
2. Digital input alarm configured to NO, normally open
This will initiate an alarm when the signal on the digital input appears.
INFO
The relay output function can be selected to be ND (Normally Deenergised), NE (Normally Energised), Limit or Horn.
+ V DC
Alarm
input
Multi-line 2
Dig in
Relayout
Com
The languages are selected in the system setup menu 6080. The language can be changed when connected to the PC utility
software. It is not possible to make language configuration from the display, but the already configured languages can be selected.
SIMPLE TEST
FULL TEST
LOAD TEST ###.#min Test mode activated and test timer counting down
FIXED POWER MAN Genset stopped or running and no other action taking
FIXED POWER SEMI place
PEAK SHAVING MAN Genset stopped or running and no other action taking
PEAK SHAVING SEMI place
LOAD TAKEOVER MAN Genset stopped or running and no other action taking
LOAD TAKEOVER SEMI place
MAINS P EXPORT MAN Genset stopped or running and no other action taking
MAINS P EXPORT SEMI place
DG BLOCKED FOR START Generator stopped and active alarm(s) on the generator
The "Idle run" function is active. The genset will not stop
IDLE RUN
until a timer has expired
IDLE RUN ###.#min The timer in the "Idle run"’ function is active
START RELAY OFF The start relay is deactivated during the start sequence
COOLING DOWN Cooling down period is activated and infinite Cooling down timer is set to 0.0 s
GENSET STOPPING This info is shown when cooling down has finished
SETUP IN PROGRESS The new AGC is being added to the existing application
Another generator breaker is closed on to the busbar This indicates that other breakers
UNEXPECTED GB ON BB (due to a GB position failure) while no voltage is present cannot close to the busbar because of
on the busbar position failure on one or more GBs
MB RACKED OUT
DG unit
SYNCHRONISING TB XX TB XX is synchronising.
SYNCHRONISING MB XX MB XX is synchronising.
Mains unit
BTB unit
BTB unit in Auto and ready for breaker operation (no active
READY AUTO OPERATION
BTB trip" alarm).
BTB unit in Auto, but not ready for breaker operation (active
AUTO OPERATION
"BTB trip" alarm).
## is replaced by A or B depending
BTB## BLOCKED BB
on where the problem is located.
All units
BB BLOCKED MB##
This status text is shown when a pos. failure connected to a The ID of the specific controller
BB BLOCKED GB##
power source is present in the section. replaces the ##
BB BLOCKED TB##
When changing the internal battery for the memory, all settings will be lost. The memory backup feature gives the possibility to back
up the controller settings, and after replacing the battery the settings can be restored.
DEIF recommends that a backup is made at least when the commissioning is tested and done. The following settings will be stored
in the backup:
Type Stored
Identifiers X
Counters X
Views configuration X
Inputs configuration X
Outputs configuration X
Translations
M-Logic configuration X
AOP-1 configuration X
AOP-2 configuration X
Application configuration X
Parameters X
Modbus configuration X
Permissions X
Logs
INFO
If new firmware is flashed to the controller, the backup will be erased.
INFO
The controller will reboot after a backup has been restored.
The backup is found in parameter 9230 Memory backup with the jump menu. In this parameter you are able to backup or restore.
If the internal battery is dismounted during operation, a failure will appear on the display.
Use the service menu for easy troubleshooting in connection with the event log.
Entry window
multi-line AGC
Available selections:
Time
Shows the alarm timer and the remaining time. The indicated remaining time is minimum remaining time. The timer will count
downwards when the setpoint has been exceeded.
multi-line AGC
multi-line AGC
multi-line AGC
MISC (miscellaneous)
multi-line AGC
INFO
There are 500 event and alarm logs in application 4.40.x or later, and in USW 3.36 or later. If older SW is used, it is only
150 event and 30 alarm logs.
The logs can be viewed in the display or in the PC utility software. When the individual logs are full, each new event will overwrite
the oldest event following the "first in - first out" principle.
6.35.2 Display
In the display it looks like this when the "LOG" push-button is pressed:
The specific alarm or event is shown in the second line. In the example above the fuel level alarm has occurred. The third line shows
the time stamp.
If the cursor is moved to "INFO", the actual value can be read when pressing "SEL":
The first event in the list will be displayed if the cursor is placed below "FIRST" and "SEL" is pressed.
The last event in the list will be displayed if the cursor is placed below "LAST" and "SEL" is pressed.
The keyUP and keyDOWN push-buttons are used for navigating in the list.
6.36 Counters
Counters for various values are included, and some of these can be adjusted if necessary, for instance if the unit is installed on an
existing genset or a new circuit breaker has been installed.
The table shows the adjustable values and their function in menu 6100:
6101 Running time Offset adjustment of the total running hours counter. Counting when the running feedback is present.
6106 Start attempts Offset adjustment of the number of start attempts. Counting at each start attempt.
Scaling of pulse input can be set in menu 6851/6861. It is possible to determine the scale value to be pulse/unit or unit/pulse.
Counter values can be read out in display, and the number of decimals can be adjusted in menu 6853/6863.
20 kWh
21 kvarh
22 Common terminal
The number of pulses depends on the actual adjusted setting of the nominal power:
INFO
The kWh measurement is shown in the display as well, but the kvarh measurement is only available through the transistor
output.
INFO
Be careful - the maximum burden for the transistor outputs is 10 mA.
The quick setup menu is made to provide easy setup of a plant. Entering the quick setup menu 9180 via the DU-2 display gives the
possibility to add or remove e.g. mains and MB without using the utility software. It is only possible to do the same basic setup as via
the application configuration in the utility software.
9181: Mode.
OFF: When the mode menu is set to "OFF", the existing application of the genset will not be changed.
INFO
Please refer to the option G5 manual.
Setup stand- When the mode menu is set to "Setup stand-alone", the AGC will change the application configuration.
alone: The settings in menu 9182-9185 are used for the new configuration.
INFO
If "Setup stand-alone" is activated while the genset is running, an info text, "Quick setup error", will appear.
6.40 Parameter ID
This parameter can be used to identify which parameter file is used in the unit.
M-Logic is used to execute different commands at predefined conditions. M-Logic is not a PLC but substitutes one, if only very
simple commands are needed.
M-Logic is a simple tool based on logic events. One or more input conditions are defined, and at the activation of those inputs, the
defined output will occur. A great variety of inputs can be selected, such as digital inputs, alarm conditions and running conditions. A
variety of the outputs can also be selected, such as relay outputs, change of genset modes and change of running modes.
INFO
The M-Logic is part of the PC utility software, and as such, it can only be configured in the PC utility software and not via
the display.
The main purpose of M-Logic is to give the operator/designer more flexible possibilities of operating the generator control system.
INFO
Refer to the "Help" function in the PC utility software for a full description of this configuration tool.
External
antenna
Controller
GSM
Modem
Serial connection
The serial connection to the GSM modem is done via the null-modem cable (option J3).
GSM GSM PIN code Set PIN code for GSM modem None
GSM 12345678901 Set phone no. for SMS to cellular phone 1 None
GSM 12345678901 Set phone no. for SMS to cellular phone 2 None
GSM 12345678901 Set phone no. for SMS to cellular phone 3 None
GSM 12345678901 Set phone no. for SMS to cellular phone 4 None
GSM 12345678901 Set phone no. for SMS to cellular phone 5 None
INFO
For calling a foreign number type "+" and country code instead of "00", for example dial +45 99999999 for a Danish
number.
INFO
The phone number can only be dialed using the PC utility software.
INFO
The SIM card used in the cellular telephone must support data transfer.
After each auxiliary supply power up, the unit will send the required PIN code to the modem if this is necessary. The PIN code is
adjusted in the PC utility software.
CAUTION
It is possible to remote control the genset from the PC utility software if a modem is used. Take precautions that it is safe to
remote operate the genset to avoid personal injury or death.
Serial connection
The serial connection to the GSM modem is via the null-modem cable (option J3).
INFO
Because of the RS232 communication the GSM function is only available with option H9.2.
Setup
9021 Service port Setpoint 0 (normal USW) 1 (modem USW) 0 (normal USW)
INFO
If setting 9020 is set to 1, the PC utility software cannot communicate with the unit when it is connected directly to the PC
and a modem is not used.
Application settings
Safety
If communication fails, the unit will operate according to the received data. If e.g. only half of the parameter file has been
downloaded when the communication is interrupted, the unit will use this actual data.
In certain cases, the use of a generator with step-up transformer (called a block) is required. This may be to adapt to the closest grid
voltage or to step up the voltage to minimise the losses in cables and also to bring down the cable size. The applications where a
step-up transformer is needed, is supported by the ML-2. The functions available in this application are:
Generator/transformer block:
Typically the synchronising breaker is on the high voltage (HV) side, and there is no breaker (or only a manually operated one) on
the low voltage (LV) side. In some applications, the breaker could also be placed on the LV side. But this does not influence on the
setting in the ML-2, as long as the breaker and the step-up transformer are both placed between the generator and busbar, and
mains voltage measuring points for the ML-2. The measuring points are shown as black dots in the figures above and below.
INFO
When voltage measurement transformers are used, these must be included in the total phase angle compensation.
When an ML-2 is used for synchronising, the device uses the ratio of the nominal voltages for the generator and the busbar, to
calculate a set point for the AVR and the voltage synchronising window (dUMAX).
Example:
A 10000 V/400 V step-up transformer is installed after a generator with the nominal voltage of 400 V. The nominal voltage of the
busbar is 10000 V. Now, the voltage of the busbar is 10500 V. The generator is running 400 V before synchronising starts, but when
attempting to synchronise, the AVR set point will be changed to:
The first letter is an upper case D or Y, defining if the HV side windings are in delta or wye configuration.
The second letter is a lower case d, y or z, defining if the LV side windings are in delta, wye or zigzag configuration.
The number is the vector group number, defining the phase angle shift between HV and LV side of the step-up transformer. The
number is an expression of the LV side lag compared to the HV side voltage. The number is an expression of the lag angle divided
by 30 degrees.
Example:
Dy11 = HV side: Delta, LV side: Wye, vector group 11: Phase shift = 11 × (–30) = -330 degrees.
LV lag degrees
Vector group Clock notation Phase shift
compared to HV
0 0 0° 0°
1 1 -30 ° 30 °
2 2 -60 ° 60 °
4 4 -120 ° 120 °
5 5 -150 ° 150 °
7 7 150 ° 210 °
8 8 120 ° 240 °
10 10 60 ° 300 °
11 11 30 ° 330 °
Yy0 example:
Connections:
LV HV GB
2L1 Busbar
1L1
2L2
Generator 1L2
2L3
1L3
AGC 200 61 63 65 68 70 72
INFO
The connection shown in the diagram should always be used when an ML-2 is used for a genset.
Vector group 1
Dy1 example:
2L3
Connections:
LV HV GB
2L1 Busbar
1L1
2L2
Generator 1L2
2L3
1L3
AGC 200 61 63 65 68 70 72
INFO
The connection shown in the diagram should always be used when an ML-2 is used for a genset.
Vector group 11
Dy11 example:
2L2
1L3 1L2
2L3
Connections:
LV HV GB
2L1 Busbar
1L1
2L2
Generator 1L2
2L3
1L3
AGC 200 61 63 65 68 70 72
The connection shown in the diagram should always be used when an ML-2 is used for a genset.
Vector group 6
Yy6 example:
Connections:
LV HV GB
2L1 Busbar
1L1
2L2
Generator 1L2
2L3
1L3
AGC 200 61 63 65 68 70 72
INFO
The connection shown in the diagram should always be used when an ML-2 is used for a genset.
INFO
Select 179 degrees in parameter 9141 when vector group 6 is used.
LV lag degrees
Vector group Clock notation Phase shift LV side lagging LV side leading
compared to HV
0 0 0° 0° 0°
1 1 -30 ° 30 ° 30 °
2 2 -60 ° 60 ° 60 °
10 10 60 ° 300 ° 60 °
11 11 30 ° 330 ° 30 °
2 Dd2, Dz2 60 °
INFO
DEIF does not take responsibility that the compensation is correct. Before closing the breaker, DEIF recommends that
customers always measure the synchronisation themselves.
INFO
If voltage measurement is connected incorrectly, the setting in parameter 9141 will be wrong.
INFO
The setting shown in the table above does not include any phase angle twist made by measurement transformers.
INFO
The settings shown in the table above are not correct if a step-down transformer is used. These settings are shown later.
If the HV side of the transformer is transforming the voltage up to a voltage level higher than 690 V AC, it will be necessary with
measurement transformers. The setup of all these parameters can be done from the utility software, and will be explained by an
example:
Measurement
Dz4 transformer
10/0.4 kV 10/0.1 kV
Controller
400 V AC
direct input
Current transformer
300/5 A
UGEN = 400 V
IGEN = 250 A
The transformer is a Dz4 step-up transformer, with nominal settings of 10/0.4 kV.
The generator has a nominal voltage of 0.4 kV, nominal current of 250 A, and a nominal power of 140 kW.
The measurement transformer has a nominal voltage of 10/0.1 kV, and no phase angle twist.
Because the generator’s nominal voltage is 400 V, there is no need for a measurement transformer on the LV side in this example.
The ML-2 can handle up to 690 V. But it is still required to set up current transformers on the LV side. In this example, the current
transformers have a nominal current of 300/5 A.
Due to the fact that the step-up transformer is a Dz4, there will be a phase angle twist of -120 °.
These settings can be programmed via the display or the utility software. These settings must be put into the parameters shown in
the table below:
INFO
The ML-2 controller can directly handle voltage levels between 100 and 690 V. If the voltage level in the application is
higher or lower, it is required to use measurement transformers that transform the voltage into a number between 100 and
690 V.
In some applications, there may also be a step-down transformer. This could be to transform a grid voltage down, so the load can
handle the voltage level. The ML-2 controller is able to synchronise the busbar with the mains, even if there is a step-down
transformer with a phase angle twist. The transformer must be between the measuring points for ML-2. If a step-down transformer is
used, these settings will must be set in parameter 9141 to compensate the phase angle twist.
10 Dd10, Dz10 60 °
INFO
If a step-down transformer is mounted with an ML-2 genset unit, the settings shown in the table above should also be used.
If a step-down transformer and an ML-2 for the mains breaker are mounted, note how the measurements are mounted on the ML-2.
The correct connection is shown below.
TB
Load Optional
MB
Mains HV LV Busbar
1L1 2L1
1L2 2L2
1L3 2L3
AGC 200 61 63 65 68 70 72
INFO
The connection shown in the picture should always be used when an ML-2 is used for a mains breaker.
If the HV side of the transformer has a voltage level higher than 690 V AC, it will be necessary with measurement transformers. In
this example, the HV side is 690 V, and therefore there is no need for a measurement transformer. The step-down transformer can
have a phase angle twist, which must be compensated for. The setup of all the parameters can be done from the utility software,
and will be explained by an example:
Busbar 400 V
Dy1 400 V
690/400 V
Controller
690 V AC
direct input
Current transformer
500/1 A
UGEN = 690 V
IGEN = 500 A
The generator has a nominal voltage of 690 V, nominal current of 500 A and a nominal power of 480 kW.
There is no measurement transformer in this application, because the ML-2 is able to handle the voltage levels directly.
It is still required to set up current transformers. In this example, the current transformers have a nominal current of 500/1 A.
Due to the fact that the step-down transformer is a Dy1, there will be a phase angle twist of +30 °.
These settings can be programmed via the display or the utility software. These settings must be put into the parameters shown in
the table below:
6051 LV (BB) measurement transformer primary side (There is none here) 400
6052 LV (BB) measurement transformer secondary side (There is none here) 400
This measurement is used to simulate a bimetallic system, known from the Maximum Demand ammeter, which is specifically suited
for indication of thermal loads in conjunction with cables, transformers, and so on.
It is possible to have two different readouts shown in the display. The first readout is called I thermal demand. This readout shows
the average maximum peak current over an adjustable time interval.
INFO
Be aware that the calculated average is NOT the same as the average current over time. The I thermal demand value is an
average of the MAXIMUM PEAK current in the adjustable time interval.
The measured peak currents are sampled once every second, and every 6 seconds an average peak value is calculated. If the peak
value is higher than the previous maximum peak value, it is used to calculate a new average. The thermal demand period will
provide an exponential thermal characteristic.
The time interval in which the average maximum peak current is calculated can be adjusted in parameter 6840. The value can also
be reset. If the value is reset, it will be logged in the event log and the readout in the display is reset to 0.
The second readout is called I maximum demand, and shortened in the unit, I max. demand. The readout displays the newest
maximum peak current value. When a new maximum peak current is detected, the value is saved in the display. The value can be
reset in menu 6843. If the value is reset, it will be logged in the event log.
INFO
The two reset functions will also be available as commands through M-Logic.
INFO
Display readout is updated with an interval of 6 seconds.
A priority routine ensures that the running hours of the available fans are evened out and the priority shifts between them.
The functionality behind the temperature-dependent start/stop is that the AGC measures a temperature, for example cooling water
temperature, and based on this temperature it switches on and off relays that must be used for engaging the fan(s) itself.
INFO
The fan control function is active as long as running feedback is detected.
Each fan has a group of parameters that defines their scheme of operation. It is recommended to use the PC utility SW for the
setup, because then it is possible to see all parameters. The setup of the fan control is done in the menus 6561-6620 and by using
M-Logic in the PC utility SW.
Parameters:
M-Logic:
The fan control requires a temperature input in order to start and stop the fans based on a temperature measurement.
The multi-inputs can be configured to e.g. a Pt100 sensor that measures an engine- or ambient temperature. If EIC is selected, this
is defined as the highest measured temperature of either cooling water or oil temperatures.
Based on the measurement of the selected input, the fan(s) is (are) started and stopped.
The start and stop settings of the fan(s) are set up in parameters 6563 to 6574. With the settings in the table below, the illustrative
curve can be observed.
A hysteresis (abbreviation: hyst.) ensures that there is a range between the start and stop.
At parameter 6581 to 6584, the output relays for fans A to D are selected. The purpose of these relays is to issue a signal to the fan
starter cabinet. The relay must be energised for the fan to run.
If two or more fans are requested to be started at the same time, it is possible to add a start delay between each fan start. The
reason for this is to limit the peak start current, so all fans will not contribute with a start current at the same time. This delay is
adjusted in the menu 6586.
To make sure that the fan is running, it is possible to assign a digital input as a running feedback. The running feedback has to be
programmed through M-Logic, below is an example of how to programme it.
The "Fan A/B/C/D running command" output tells the AGC that the fan is running. The output is found under Output and Command
as shown in the screenshot above.
It is possible to activate an alarm if the fan does not start. The fan failure alarm appears if the running feedback from the fan does
not appear. In parameters 6590 to 6620, the fan failure alarms are set up for fans A to D.
The priority of the fans A to D rotates automatically from 1st to 4th priority. This is done automatically, because the running hours of
the fans are detected and are used for the rearranging.
M-Logic setup:
If the fan unit is raising a signal that is led to a digital input on the AGC when it is running, the following M-Logic must be
programmed:
When it is not possible to get a running feedback from the fan unit, the internal relay of the AGC must be used to indicate that the
fan is running. If, for example, R57 is the relay for FAN A, the following M-Logic must be programmed:
The running hour can be reset by entering parameter 6585 and then selecting the desired fan hours to be reset.
In parameter 6562, the priority update rate (hours between priority rearrange) is selected:
If the fan priority update is set to 0 hours, the order of priority will be fixed at: Fan A, fan B, fan C and fan D.
The time interval between the oil changes is assumed to be 1000 hours of operation. The renewal function will read the engine
hours from the engine interface communication (EIC). The running hours counter in the AGC is only used if the EIC counter is not
available.
The function in the AGC is to activate a relay under defined conditions. Then the relay must be used for the oil renewal system (not
part of the DEIF scope of supply) where lubricating oil is removed and added to the engine. Any freely configurable relay is available
When the running hours counter has reached 1000 hours, the AGC will reset the hours just for the oil renewal function. If for
example the setpoint has been set to 750 hours and inverse is not enabled, the relay will close at 750 hours and remain closed until
1000 hours is reached, and then the hours counter starts from 0 hours again.
With the differential measurement function, it is possible to compare two analogue inputs and trigger on the difference between the
two values.
If the differential function is for example air filter check, the timer will be activated if the set point between PA (analogue A) and PB
(analogue B) is exceeded. If the differential value drops below the set point value before the timer runs out, then the timer will be
stopped and reset.
∆ P=PA-PB
PA After filter
Timer
value
Six different differential measurements between two analogue input values can be configured.
Inputs are selected from the input list as shown below, avaible inputs are:
• Multi-inputs
• EIC measurements
The relevant alarm set point is chosen in parameters 4610-4660 and 4680-4730. Each alarm can be configured in two alarm levels
for each differential measurement between analogue input A and input B. The figure below shows the two parameters to configure
alarm level 1 and 2, for differential measurement 1.
This function is intended for giving an alarm if the average of a specific measurement exceeds a set point in a certain time frame.
There are two levels of alarms in U> L-L, U< L-L, U> L-N, U< L-N, f>, f< and I>.
In principle, the average calculation is done, for example, every time the main voltage measurement updates.
The average is calculated based on the RMS value of the three phases.
Parameter Item
INFO
It is not possible to configure the alarms from the display, only from the USW.
The protection will be activated based on the overcurrent setpoint as a function of the measured voltage on the generator voltage
terminals.
The result can be expressed as a curve function where the voltage setpoints are fixed values and the current setpoints can be
adjusted (menu 1100). This means that if the voltage drops, the overcurrent setpoint will also drop.
200
190
180
% Nominal Current
170
160
150
140
130
120
110
100
50 60 70 80 90 100
% Nominal Voltage
INFO
The voltage values for the six points on the curve are fixed; the current values can be adjusted in the range 50-200%.
INFO
Voltage and current % values refer to the nominal settings.
INFO
Timer value can be adjusted in the range 0.1- 60.0 sec.
INFO
See "General Guidelines for Commissioning".
8.2 Controllers
There are three controllers for the governor control and, if option D1 is selected, also three controllers for the AVR control.
Q load sharing (option D1) X X Controls the reactive power load sharing
The table below indicates when each of the controllers is active. This means that the controllers can be tuned in when the shown
running situations are present.
X X G
GB MB
X X G
GB MB
X X G
GB
G
X X
GB
G
INFO
Load sharing mode is option-dependent (option G3/G5).
P-part I-part + +
Set point Σ Σ Output
(Kp) (Ti) +
-
D-part
(Td)
As illustrated in the above drawing and equation, each regulator (P, I and D) gives an output which is summarised to the total
controller output.
The adjustable settings for the PID controllers in the AGC unit are:
The diagram shows how the output of the P regulator depends on the Kp setting. The change of the output at a given Kp setting will
be doubled if the regulation deviation doubles.
P regulator
100 4% 2%
80
Output (%)
1%
60
40
0.5 %
20
0
0 10 20 30 40 50 60
Kp
Because of the characteristic above it is recommended to use the full range of the output to avoid an unstable regulation. If the
output range used is too small, a small regulation deviation will cause a rather big output change. This is shown in the drawing
below.
kP
mA
5 10 15 20 25
A 1% regulation deviation occurs. With the Kp setting adjusted, the deviation causes the output to change 5 mA. The table shows
that the output of the AGC changes relatively much if the maximum speed range is low.
Max. speed range Output change Output change in % of max. speed range
10 mA 5 mA 5/10*100% 50
20 mA 5 mA 5/20*100% 25
The drawing below shows the dynamic regulation area at given values of Kp. The dynamic area gets smaller if the Kp is adjusted to
a higher value.
100
Kp=50
Kp=10
75
50
25
Kp=1
Frequency 0
[Hz] 44 45 46 47 48 49 50 51 52 53 54 55 56
-25
-50
-75
-100
Output [%]
The main function of the integral regulator is to eliminate offset. The integral action time Ti is defined as the time the integral
regulator uses to replicate the momentary change of the output caused by the proportional regulator.
In the drawing below the proportional regulator causes an immediate change of 2.5 mA. The integral action time is then measured
when the output reaches 2 x 2.5 mA = 5 mA.
5 Ti = 10 s Ti = 20 s
mA 3
0
0 5 10 15 20 25 30 35
sec
As shown in the drawing, the output reaches 5 mA twice as fast at a Ti setting of 10 s than with a setting of 20 s.
The integrating function of the I-regulator is increased if the integral action time is decreased. This means that a lower setting of the
integral action time Ti results in a faster regulation.
INFO
If the Ti is adjusted to 0 s, the I-regulator is switched OFF.
INFO
The integral action time, Ti, must not be too low. This will make the regulation hunt similar to a too high proportional action
factor, Kp.
The main purpose of the derivative regulator (D-regulator) is to stabilise the regulation, thus making it possible to set a higher gain
and a lower integral action time Ti. This will make the overall regulation eliminate deviations much faster.
In most cases, the derivative regulator is not needed. However, for very precise regulation situations, for example, static
synchronisation, it can be very useful.
The output from the D-regulator can be explained with the equation:
D = Regulator output
Kp = Gain
de/dt = Slope of the deviation (how fast does the deviation occur)
This means that the D-regulator output depends on the slope of the deviation, the Kp and the Td setting.
Example:
6
Output/deviation
5 Deviation 2
3
D-output 2, Td=1s
2 Deviation 1
D-output 2, Td=0.5 s
1
D-output 1, Td=0.5 s
0
0 0.5 1 1.5 2 2.5
Time [s]
The example shows that the bigger deviation and the higher Td setting, the bigger output from the D-regulator. Since the D-regulator
is responding to the slope of the deviation, it also means that when there is no change the D-output will be zero.
INFO
When commissioning, please keep in mind that the Kp setting has influence on the D-regulator output.
INFO
If the Td is adjusted to 0 s, the D-regulator is switched OFF.
INFO
The derivative action time, Td, must not be too high. This will make the regulation hunt similar to a too high proportional
action factor, Kp.
Adjustment of the load share controller is done in menu 2540 (analogue control) or 2590 (relay control).
The primary purpose of the PID controller is always frequency control because frequency is variable in a load sharing system as well
as the power on the individual generator. Since the load sharing system requires power regulation as well, the PID controller can be
affected by the power regulator. For this purpose a so-called weight factor is used (PWEIGHT).
The regulation deviation from the power regulator can therefore have great or less influence on the PID controller. An adjustment of
0% means that the power control is switched off. An adjustment of 100% means that the power regulation is not limited by the
weight factor. Any adjustment in between is possible.
The difference between adjusting the weight value to a high or low value is the speed at which the power regulation deviation is
eliminated. So if a firm load sharing is needed, the weight factor must be adjusted to a higher value than if an easy load sharing is
required.
Dynamic synchronising
When dynamic synchronising is used, the controller "2050 fSYNC controller" is used during the entire synchronising sequence. One of
the advantages of dynamic synchronising is that it is relatively fast. In order to improve the speed of the synchronising further, the
generator will be sped up between the points of synchronisation (12 o’clock to 12 o’clock) of the two systems. Normally a slip
frequency of 0.1 Hz gives synchronism each 10 seconds, but with this system on a steady engine the time between synchronism is
reduced.
Static synchronising
When synchronising is started, the synchronising controller "2050 fSYNC controller" is activated and the generator frequency is
controlled towards the busbar/mains frequency. The phase controller takes over when the frequency deviation is so small that the
phase angle can be controlled. The phase controller is adjusted in the menu 2070 ("2070 phase controller").
Regulator
output
The regulation is active, but the increase relay will be constantly activated because of the
1 Static range Fix up signal
size of the regulation deviation.
The regulation is active, and the increase relay will be pulsing in order to eliminate the
2 Dynamic range Up pulse
regulation deviation.
In this particular range no regulation takes place. The regulation accepts a predefined dead
3 Dead band area No reg.
band area in order to increase the lifetime of the relays.
The regulation is active, and the decrease relay will be pulsing in order to eliminate the
4 Dynamic range Down pulse
regulation deviation.
The regulation is active, but the decrease relay will be constantly activated because of the
5 Static range Fix down signal
size of the regulation deviation.
As the drawing indicates, the relays will be fixed ON if the regulation deviation is big, and they will be pulsing if it is closer to the
setpoint. In the dynamic range the pulses get shorter and shorter when the regulation deviation gets smaller. Just before the dead
band area the pulse is as short as it can get. This is the adjusted time "GOV ON time"/("AVR ON time"). The longest pulse will
appear at the end of the dynamic range (45 Hz in the example above).
The time settings for the regulation relays can be adjusted in the control setup. It is possible to adjust the "period" time and the "ON
time". They are shown in the drawing below.
Period time Maximum relay time The time between the beginnings of two subsequent relay pulses.
The minimum length of the relay pulse. The relays will never be activated for a shorter time
ON time Minimum relay time
than the ON time.
As it is indicated in the drawing below, the length of the relay pulse will depend on the actual regulation deviation. If the deviation is
big, then the pulses will be long (or a continued signal). If the deviation is small, then the pulses will be short.
Relay ON
ON ON ON ON ON
t [sec]
The signal length is calculated compared to the adjusted period time. In the drawing below the effect of the proportional regulator is
indicated.
100 4% 2%
80
Output (%)
1%
60
40
0.5 %
20
0
0 10 20 30 40 50 60
Kp
In this example we have a 2 percent regulation deviation and an adjusted value of the Kp = 20. The calculated regulator value of the
unit is 40%. Now the pulse length can be calculated with a period time = 2500 ms:
The length of the period time will never be shorter than the adjusted ON time.
Droop mode can be used when a new genset is installed together with existing gensets which operate in droop mode in order to
make equal load sharing with the existing gensets. This regulation mode can be used where it is required/allowed that the generator
frequency drops with increasing load.
The droop mode parameters can be adjusted between 0-10% droop. If the value is different from 0%, the droop percentage will be
applied on top of the regulation output of the governor (f) or AVR (U).
2514 f droop Droop setting for frequency regulator with analogue output
2573 f droop relay Droop setting for frequency regulator with relay regulation
2644 U droop Droop setting for voltage regulator with analogue output
2693 U droop relay Droop setting for voltage regulator with relay regulation
INFO
When using droop mode, the frequency PID (f) and voltage PID (U) is active
The following M-Logic commands are used to activate droop regulation. This gives more options to activate the regulation i.e. a
digital input, AOP button or an event.
GOV/AVR control Act. frequency droop regulation Activates the use of frequency droop parameters mentioned above
GOV/AVR control Act. voltage droop regulation Activates the use of voltage droop parameters mentioned above
Application configuration
When operating in droop mode, the AGC has to be configured with a Single DG application drawing. This is done through the utility
software or with quick setup.
Please see the utility software help function (F1) for details about application configuration.
The diagram below shows an example for one generator where the voltage droop setting is 4% and 10% in proportion to the
reactive power, Q (kVAr). As it is shown in the example, the voltage drops as the load increases. The principle is the same with
generators in parallel where the generators will use the droop to share the load and allow the voltage/frequency to drop accordingly.
U [V]
400
4% droop
380
0 % Q [kVAr]
0 50% 100%
To illustrate the influence of a high droop setting, the diagram below shows how a frequency variation gives a change in the load, the
principle is the same with voltage regulation. The load change is marked as ΔP.
Freq (Hz)
fNOM
P(kW)
∆P
INFO
This can be used if the generator must operate base-loaded.
To illustrate the influence of a low droop setting, the diagram below shows how a frequency variation gives a change in the load, the
principle is the same with voltage droop regulation. The load change is marked as ΔP.
In this diagram, the load change (ΔP) is larger than before. This means that the generator will vary more in loading than with the
higher droop setting.
Freq (Hz)
fNOM
P(kW)
∆P
INFO
This can be used if the generator must operate as a peak load machine.
When the genset is equipped with a governor only providing isochronous operation, the droop setting can be used to compensate
for the missing droop setting possibility on the governor.
9.1 Introduction
The general purpose PID controllers are principally similar to the PID controllers for AVR and governor output. They consist of a
proportional, integral and derivative part, and the integral and derivative parts are dependent on the proportional gain. A functional
description of the principle can be found in the chapter about controllers for AVR and governor. The GP PIDs are slightly less
responsive, though. They are meant for purposes such as temperature regulation, controlling fans, valves, and so on. The principle
of relay control is also described in the chapter about AVR/governor control. Configuration of the GP PIDs is documented by
describing the possibilities of the GP PID interface, and with examples of configuration for different purposes.
Acronyms:
The analogue regulation in the general purpose PIDs is handled by a PID loop. The diagram below shows which elements the PID
loop consists of.
1 2 3 4 5 6 7 8
1
+
Reference + + Output
Kp Ti ∑ Offset
-1
- +
Td
Input
1. Input: This is the analogue input that measures the process the controller is trying to regulate. See under Input later in this
document for more details.
2. Reference: This is the set point that the controller is trying to bring the input to match. See under Input later in this document for
more details.
3. Kp: The proportional gain of the PID loop. See under Output later in this document for more details.
4. Ti: The integral gain of the PID loop.
5. Td: The derivative gain of the PID loop.
6. Inverse: Enabling inverse will give the output a negative sign. See under Output later in this document for more details.
7. Offset: The offset is added on the function and displaces the regulation range. See under Output later in this document for more
details.
8. Output: This is the final output from the PID, controlling the transducer.
Configuration of the GP PID’s input and output settings is done with the “PID” interface in the DEIF USW, it cannot be done from the
display of the controller.
9.2 Inputs
9.2.1 Inputs
Each output holds the possibility of up to three inputs. Only one input at a time is used for calculation of output signal. It is described
in “Dynamic input selection” how the selection is handled.
1: Activation drop-down
2: Top drop-down
4: “Reference 1”
5: “Weight 1”
6: Bottom drop-down
On: This input will be evaluated. Off: This input will not be evaluated.
Each GP PID holds the possibility of up to three active inputs. All activated inputs are evaluated constantly, and the input causing the
greatest or smallest output is selected. Priority of great or small output is selected in the output settings.
Ventilation of a container fitted with a genset inside is a realistic example for use of the dynamic input selection. The following three
variables depend on the ventilation, hence it makes sense to let them share the output.
• The container is fitted with a temperature sensor for internal container temperature. Due to lifetime of electronics inside the
container, maximum maintained temperature is desired to be 30 °C. (Input 1).
• The engine air intake is located inside the container, hence turbo compressor inlet temperature depends on the air temperature
in the container. Maximum maintained intake air temperature is 32 °C. (Input 2).
• The alternator is cooled by air in the container, hence the alternator winding temperature depends on the air temperature in the
container. Maximum maintained winding temperature is 130 °C. (Input 3).
This is the data that is used to configure the inputs in the screenshot in the previous paragraph (Inputs). All inputs are configured
with both full range of measurement (0 to 100 %) and a weight factor of 1. The common output to the ventilator speed drive is
configured to prioritise maximum output as explained in the next chapter, “Output”. This configuration is meant to ensure that none
of the input set points are continuously exceeded, unless maximum ventilation is reached.
A scenario of operation could be that the controller has been using input 1, and a temperature of 30 °C is maintained in the
container. At a point, the air filter housing is heated by radiation from the engine, causing input 2 to rise more above 32 °C than input
1 is above 30 °C. This means that input 2 now has the greatest positive deviation. All inputs are configured with a weight factor of 1
and maximum output is prioritised, hence the greatest positive deviation results in maximum output, or, to put it in another way, input
2 is now the one selected.
The genset is running at full load with a maximum of reactive load, and the alternator windings heat up beyond the 130 °C set point
due to high currents. At some point, input 3 will result in maximum output and hence be selected as the input used in output
calculation. Ventilation is increased and the winding temperature may reach a steady state of 130 °C with a container room
temperature of 27 °C and a compressor inlet temperature of 30 °C. As long as this is the situation, input 3 will remain the selected
input, as this is the input causing the greatest output.
In case of high ambient temperatures, the ventilation might not be able to influence the temperature enough, and the temperatures
start to rise above set point. The output will stay at 100 % as long as any of the inputs are continuously above their set points.
Weight factor applies to dynamic input selection as well. In the event that different weight factors have been configured for any of the
three inputs, maximum deviation cannot be equated to maximum output. If two inputs with similar deviation to their respective set
points are configured with weight factors of 1 and 2 respectively, the latter will result in twice the output as the first.
1: Priority
This setting determines whether it is min. or max. output that is prioritised. This setting is used for the dynamic input selection
feature. “Maximum output” results in selection of the input that gives the greatest output. “Minimum output” results in selection of the
input that gives the smallest output.
2: Output type
Choose between relay or analogue output. The following parameters marked “analogue” only apply to the use of analogue
regulation, in the same way as parameters marked “relay” only apply to relay regulation.
3: Analogue Kp
This is the proportional gain value. Increasing this value gives a more aggressive reaction. Adjusting this value also affects the
integral and derivative output. If Kp needs adjustment without affecting the Ti or Td part, adjust these accordingly.
5: Analogue Td
6: Analogue output
Setpoint
0 t
Direct error = SP - PV
Inverse error = PV - SP
Direct output is used in applications where a rise in analogue output increases the process variable.
Inverse output is used in applications where a rise in analogue output decreases the process variable.
Typically, heating applications use direct output and cooling applications use inverse output. Imagine a container of water, which
must be kept at a set point of 20 °C at all times. The container can be exposed to temperatures between 0 and 40 °C, hence it is
fitted with both a heating coil and a cooling coil. See the illustrations of this below here.
Controller output
Controller output
Process Variable
Controller
Set point
For this application, two controllers must be configured: one with direct output for the heating pump and one with inverse output for
the cooling pump. To achieve the illustrated inverse output, an offset of 100 % is needed. See the sections about “Analogue offset”
and “Example of inverse output with 100 % offset” for more information regarding offset.
Temperatures below 20 °C then result in a positive output for the heating pump, in the same way as temperatures above 20 °C
result in a positive output for the cooling pump, and the temperature is maintained around the set point.
20 °C Set point
0 °C
Direct Inverse
Output Output Output
(Heating) (Cooling)
100 %
0% Time
8: Analogue offset
Determines the output starting point. The full range of output can be seen as values in the range between 0 and 100 %. The offset
displaces this range. 50 % offset centres the range of output at the set point. 0 and 100 % offset result in having the full range of
output above or below the set point. See the table below for illustration of how the output behaves according to the input and with
different offsets.
Setpoint 100 % 50 % 0% 50 %
0% 100 %
100 % 0%
100 % offset is commonly used with inverse output, like in the previous cooling example. For an example of other use, see “Example
of inverse output with 0 % offset”.
11: Relay Db
12: Relay Kp
13: Relay Td
Minimum output time for relay control. Set this to the minimum time that is able to activate the controlled actuator.
Total time for a relay activation period. When the regulation output is above this period time, the relay output is constantly activated.
Choose the terminal for the relay used for negative activation.
This document describes the functionality regarding the “Kp gain compensation”, so it is possible to utilise the function parameters
and help with setting up the function. This function is intended to be used when the AGC is controlling the cooling water system for
the genset.
As it is today, there are two situations in which the engine is in danger of ending in an oscillation that could shut down the engine:
1. Load impacts
2. Cold start of engine
In both situations, it is desired to have a higher gain when the change is needed, but a lower gain when the system has to stabilise.
Without "Kp gain compensation", the PID settings need to be balanced between reaction and stability. The “Kp gain compensation”
function allows slower PID settings for when there are no changes or stabilising, and when there are significant changes in the
system it will increase the reaction of the PID.
These two functions, the load-dependent compensation and the set point deviation compensation, can be used separately or
together. If they are used together, it is always the one with the highest returned gain that is used.
In case of large load impacts or rejections, it can create large deviation in the need of cooling, and thereby create some instability in
the cooling system. To alleviate some of this instability, the load change gain compensation will instantaneously increase the gain in
relation to the load gain. Larger load changes give a bigger increase in gain. This increase in gain will decrease over a set time till it
reaches the nominal gain.
Explanation of settings
Load change limit. The controller needs to detect a load change larger than this limit before activating the gain compensation. For
example, if the limit is set for 10 %, there must be a load impact or rejection of at least 10 % of the genset nominal power before this
function activates.
The gain increase is based on the load change compared to nominal, and this ratio is multiplied by the load weight.
The gain increase will be instantaneous, but it will decrease linearly over the set time until it reaches nominal gain.
100
0 Sec.
0 5 10 15 20 25 30 35 40 45 50
Load%
PID gain
The diagram above shows the reaction of the gain, based on two load changes.
In the first situation, there is a large load impact that triggers the load change gain compensation and increases the gain
instantaneously. This increase will decrease, in this case over 15 seconds, and bring the gain back to nominal.
After some seconds, the system drops some load again, but only half of the former impact. Gain is again instantaneously increased,
but this time only half as much because the load change is only half as big. The increase will still decrease over 15 seconds.
This function is intended to help minimise overshoots. Especially in a cooling water system where the set point is often very close to
the shutdown limit, it is difficult for a slow system to react in time to avoid a shutdown. This function will drastically increase the gain
when the actual value overshoots the set point more than the set deadband, but the further the actual value is from the set point, it
will decrease. If the value drops below the set point, the function works reversed. Close to set point, the gain increase is small, but
the further the actual value is from the set point, it will increase. This is to avoid that the system starts hunting.
Explanation of settings
Deviation deadband. As long as the actual value does not deviate more than the deadband in this parameter, the function is not
activated.
The gain increase is based on the set point deviation compared to nominal, and this ratio is multiplied by the weight factor.
100
90
0
Time
Temperature Deadband
Set point Gain
The diagram above shows how the reaction to a set point deviation could look.
This situation could be rising cooling water temperature in a genset. Below the set point, the gain is very high, but as the
temperature is getting closer to the set point, it decreases the gain compensation. Within the activation limit, the gain is at nominal
value.
As the temperature keeps rising, it exceeds the activation limit again, and when it is above set point the gain is increased
instantaneously. As the temperature keeps rising, the gain compensation decreases again.
9.5 M-Logic
9.5.1 Introduction
All functions of the GP PIDs can be activated and deactivated by means of M-Logic. In the following, events and commands
regarding the GP PIDs are described.
9.5.2 Events
PID active
This event is active when the output is below the output parameter “M-Logic min event set point”.
This event is active when the output is above the output parameter “M-Logic max event set point”.
This event is active when dynamic input selection has selected input 2 for output calculation.
This event is active when dynamic input selection has selected input 3 for output calculation.
This event is active when remote Modbus control of this PID is requested.
9.5.3 Commands
PID activate
This command forces the output to the value set in the output parameter “Analogue min outp.”
This command forces the output to the value set in the output parameter “Analogue max outp.” (for example, for post-cooling
purposes).
PID reset
This command forces the output to the value set in the output parameter “Analogue offset”.
PID Freeze
9.6 Example
An example for use of a GP PID could be analogue fan control. The fan in this example is mounted on a radiator “sandwich”
construction. The fan drags air through two radiators, one for cooling of the intercooler coolant and one for cooling of the jacket
water. As these two systems have different temperature set points, the dynamic set point selection is used. PID2 is used in this
example, and the picture shows an example of input settings.
EIC Intercool temp. is selected as input 1, and EIC Cooling water temp. as input 2. Min. and max. values are configured for full
range. Input 1 reference set point is set at 500 to achieve a temperature set point of 50.0 °C for intercooler coolant. Input 2 has a
reference set point set at 900 to achieve a set point of 90.0 °C jacket water coolant. To achieve equal weighting of the inputs when
calculating the output, both weight factors are set to a value of 1. Both desired inputs are activated, leaving input 3 to be
deactivated.
In this example, “Analogue” is selected as output type, and the physical output is selected to be “transducer 68”. Inverse output is
activated to obtain a rise in analogue output to the fan when the temperature rises.
Full range of output is selected. As this is output for a fan, it may be preferred to use a minimum output.
Below is an example of M-Logic lines for this application. Logic 1 makes sure that the regulation is active and the output is
calculated as long as the engine is running. Logic 2 forces the fan to maximum speed during cool-down to ensure efficient cool-
down.
When the engine is started and running, the regulation is activated and an output is calculated. When either the intercooler or jacket
water coolant exceeds their set point, the output starts to increase from 0 %. The input that results in calculation of greatest output is
prioritised at all times, making sure that both systems are supplied with adequate cooling. During stop sequence, the fan is forced to
max. output, ensuring most possible cooling. The output remains at 0 % until the engine is started again.
This is an example that uses inverse output combined with 0 % offset. The application is an engine with electric thermostat control.
During engine start-up, it is preferred to start the output before the set point is reached, to help avoid overshooting the set point too
much. This is obtained by using inverse output with no offset. The diagram below illustrates this function if the controller is
configured as straight proportional without integral or derivative action. With these settings, the output is 100 % when the set point is
reached, and the beginning of the output is determined by the proportional gain.
Temp. Output
90° C 100 %
0%
Time
INFO
In the following, the term "synchronisation" means "synchronising and closing of the synchronised breaker".
LOAD
GB
GB
Speed: Speed:
L1 L1
L1 L3 L2 L3 L2 L3 L2 L3 L2 L3 L2
L3 L2
Angle
L1gen/L1bus
[deg]
Synchronised
180°
90°
0° ∆t [s]
0s 2.5 s 5.0 s 7.5 s
In the example above, the synchronising genset is running at 1503 RPM ~ 50.1 Hz. The generator on load is running at 1500 RPM ~
50.0 Hz. This gives the synchronising genset a positive slip frequency of 0.1 Hz.
The intention of the synchronising is to decrease the phase angle difference between the two rotating systems. These two systems
are the three-phase system of the generator and the three-phase system of the busbar. In the illustration above, phase L1 of the
busbar is always pointing at 12 o’clock, whereas phase L1 of the synchronising genset is pointing in different directions due to the
slip frequency.
When the generator is running with a positive slip frequency of 0.1 Hz compared to the busbar, the two systems will be synchronised
every 10 seconds.
INFO
Observe the chapter regarding PID controllers and the synchronising controllers.
In the illustration above, the difference in the phase angle between the synchronising set and the busbar gets smaller and will
eventually be zero. Then the genset is synchronised to the busbar, and the breaker will be closed.
The unit always calculates when to close the breaker to get the most accurate synchronisation. This means that the close breaker
signal is actually issued before being synchronised (read L1 phases exactly at 12 o’clock).
The breaker close signal will be issued depending on the breaker closing time and the slip frequency (response time of the circuit
breaker is 250 ms, and the slip frequency is 0.1 Hz):
INFO
The synchronisation pulse is always issued, so the closing of the breaker will occur at the 12 o’clock position.
The length of the synchronisation pulse is the response time of the breaker + 20 ms.
When the incoming genset has closed its breaker, it will take a portion of the load dependent on the actual position of the fuel rack.
Illustration 1 below indicates that at a given positive slip frequency, the incoming genset will export power to the load. Illustration 2
below shows that at a given negative slip frequency, the incoming genset will receive power from the original genset. This
phenomenon is called reverse power.
INFO
To avoid nuisance trips caused by reverse power, the synchronising settings can be set up with a positive slip frequency.
PGen1 GB
0% 100%
G1
LOAD
FUEL INDEX
PGen2 GB
0% 100%
G2
______________________________________________________________________________________
FUEL INDEX
PGen1 GB
0% 100%
G1
LOAD
FUEL INDEX
PGen2 GB
0% 100%
G2
Reverse power
10.2.3 Adjustments
The dynamic synchroniser is selected in 2000 Sync. type in the control setup and is adjusted in 2020 Synchronisation.
Maximum voltage difference (+/- The maximum allowed voltage difference between the busbar/
"Sync dUMAX" (channel 2023)
value) mains and the generator.
Minimum voltage difference (+/- The minimum allowed voltage difference between the busbar/
"Sync dUMIN" (channel 2024)
value) mains and the generator.
"Sync tGB" (channel 2025) Generator breaker closing time Adjust the response time of the generator breaker.
"Sync tMB" (channel 2026) Mains breaker closing time Adjust the response time of the mains breaker.
The speed of the slip frequency is determined by two settings, "Sync dfMAX" and "Sync dfMIN". The calculation from the examples
below illustrates why it is important to configure the slip frequency speed correctly.
Example 1: The slip frequency speed of the genset is 0.15 Hz faster than the frequency of the busbar or the grid that the genset is
trying to synchronise to.
This means that the phase angle difference between the genset and the busbar or the grid will decrease and eventually be within the
GB closing window.
It is obvious that this type of synchronisation is able to synchronise relatively fast because of the adjusted minimum and maximum
slip frequencies. This actually means that when the unit is aiming to control the frequency towards its set point, synchronising can
still occur as long as the frequency is within the limits of the slip frequency adjustments.
INFO
Dynamic synchronisation is recommended where fast synchronisation is required, and where the incoming gensets are
able to take load just after the breaker has been closed.
INFO
Static and dynamic synchronisation can be switched by using M-Logic.
INFO
It is not recommended to use the static synchronisation principle when relay regulation outputs are used. This is due to the
slower nature of the regulation with relay outputs.
LOAD
GB
GB
Speed:
Speed:
1500.3 RPM 1500 RPM
50.01 Hertz G G 50.00 Hertz
L3 L3
L3
L3 L2 L3 L2 L3 L2 L3 L2 L3 L2
L2 L2 L2
Angle
L1gen/L1bus
[deg]
Synchronised
30°
20°
10°
0° t [s]
When the static synchronisation is used and the synchronising is activated, the frequency controller will bring the genset frequency
towards the busbar frequency. When the genset frequency is within 50 mHz of the busbar frequency, the phase controller takes
over. This controller uses the angle difference between the generator system and the busbar system as the controlling parameter.
This is illustrated in the example above where the phase controller brings the phase angle from 30 deg. to 0 deg.
The close signal will be issued when phase L1 of the synchronising generator is close to the 12 o’clock position compared to the
busbar which is also in 12 o’clock position. It is not relevant to use the response time of the circuit breaker when using static
synchronisation, because the slip frequency is either very small or non-existing.
To be able to get a faster synchronisation, a "close window" can be adjusted. The close signal can be issued when the phase angle
UGENL1-UBBL1 is within the adjusted setpoint. The range is +/-0.1-20.0 deg. This is illustrated in the drawing below.
Max. dU difference
UBB Direction of
Max. dU difference rotation
UGEN
The synchronisation pulse is sent dependent on the settings in menu 2030. It depends on whether it is the GB or the MB that is to
be synchronised.
The synchronised genset will not be exposed to an immediate load after the breaker closure if the maximum df setting is adjusted to
a low value. Since the fuel rack position almost exactly equals what is required to run at the busbar frequency, no load jump will
occur.
If the maximum df setting is adjusted to a high value, then the observations in the section about "dynamic synchronisation" must be
observed.
After the synchronising, the unit will change the controller setpoint according to the requirements of the selected genset mode.
INFO
Static synchronisation is recommended where a slip frequency is not accepted, for instance if several gensets synchronise
to a busbar with no load groups connected.
INFO
Static and dynamic synchronisation can be switched by using M-logic.
10.3.4 Adjustments
The following settings must be adjusted if the static synchroniser is selected in menu 2000:
2033 The size of the window where the synchronisation pulse can
+/- value.
Closing window be released.
The purpose of the "close before excitation" is that the gensets are able to be ready for the load very quickly. All of the gensets will
be connected to the busbar as soon as they are started, and as soon as the excitation is switched on, the gensets are ready for
operation. This is faster than the normal synchronising, because in that case the breakers will not be closed until the generator
voltage is in the synchronised position, and it takes some time to achieve that position.
The "close before excitation" function can also be used if the load requires a "soft" start. This can be the case when the gensets
connect to a transformer.
As soon as the excitation is activated, the generators will equalise the voltage and frequency and will eventually run in a
synchronised system. When the excitation is activated, the regulators of the AGC will be switched on after an adjustable delay.
The function can be used in the single AGC but also the AGC with option G4 or G5.
INFO
The excitation must be increased slowly when this function is used.
INFO
This function can only be used with a magnetic pickup (MPU) or EIC speed signal.
Flowchart abbreviations
Start
Start DG(s)
No
No
RPM > SP1 Delay 1 expired
Yes
Close GB Yes
No
No Yes Start
RPM > SP2 Delay 1 expired Trip GB
excitation
Yes
Delay 1 expired
on all DG(s) No
Yes No
No Yes
Activate
Delay 3 expired UBUS OK
regulators
No
Yes No
Yes
”Close before UBUS OK Delay 3 expired
excitation” No
failure Yes Yes
”Close before
End Sync GB excitation”
failure
Start
No TB Open
Yes
Any GB closed
No
Yes
Yes
”GB + TB” No
Yes
MB OFF No
Yes
Close TB Sync TB
End
The start sequence of the AGC is changed in order to achieve the function "close before excitation". The following parameters must
be adjusted:
The generator breaker will close at the adjusted level. The range is from 0-400 RPM. If it is adjusted
RPM set point for
2251 to 0, the breaker will be closed when the start command is given.
breaker closing
In the example below the setting is adjusted to 400.
The genset must reach the set point (menu 2263) within the adjusted delay.
2252 RPM timer When the delay expires and the RPM is above the set point, the excitation will be started. If the
RPM is below the set point, the GB will be tripped.
Select the relay output that must be used to start the excitation.
2253 Output A Configure the relay to be a limit relay in the I/O setup.
For best possible CBE behaviour, it is recommended to use relay 5, 8 or 11.
RPM
Vo lt age
Nom in al RPM
Nom in al Voltage
Hz an d V OK
Exc. st art RPM (2263)
t [s]
GB clo se
AVR ON relay (2253) The relay will not be act ivat ed im mediately in
Power M anagement system s. All DGs will need
t o have 2252 expired and 2263 reached.
Regu lat io n ON
In one of the applications a tie breaker is present, and it must be adjusted in the menu 2261 whether only the generator breaker
must be closed or both the generator breaker and also the tie breaker.
The timer defines the period from the excitation is started and until the regulation is activated. The
2262 Timer
alarms with inhibit set to "Not run status" will be activated after this timer has expired.
2263 Excitation start level The setting defines at what minimum level of RPM the excitation can be started.
This timer delays the closing of the GB after removing excitation. The intention of this delay is to let
2264 Voltage discharge the voltage of the generator discharge, so that only remanence voltage is present when the GB is
closed.
If the starting of the genset does not succeed, then the alarm menu 2270 "Cl.bef.exc.fail" will occur, and the selected fail class will be
executed.
If the application has been configured to use “Close Before Excitation” (CBE) during start, the Multi-line 2 unit can do additional
things to handle the sequence correctly.
If, for example, the application is made for backup power (AMF), it can be chosen what the Multi-line 2 unit should do during
cooldown. The Multi-line 2 unit is able to make a rerun, which means that if a new start request comes during cooldown, the
genset(s) can perfom the CBE sequence again without stopping the genset(s). To handle the functionality for the rerun and
cooldown, some parameters must be set correctly.
Excitation control during cooldown: At parameter 2266, it is possible to decide how the Multi-line 2 unit should react during
cooldown. At this parameter, it is possible to select between three settings:
Excitation follow busbar: By default, the parameter is set to “Excitation follow busbar”. This means that if there is voltage on the
busbar during cooldown of the specific genset, the excitation is ON. If the voltage on the busbar disappears, the excitation is shut
OFF.
Excitation constant OFF: If the parameter is set to “Excitation constant OFF”, the excitation will be switched OFF, as soon as the GB
is open during cooldown. This feature can be handy if the genset fans are pulled mechanically by the genset. Then the genset will
be able to make a rerun faster.
Excitation constant ON: If the parameter is set to “Excitation constant ON”, the excitation will be ON until the genset stops or a new
start request comes. This feature can be handy if the genset fans are driven by the voltage from the genset.
At parameter 2265, it is set how low the voltage must be, before it is allowed to close the breaker during the rerun. If the voltage is
not below the “voltage rerun level” before the “voltage discharge timer” has expired, the specific genset will be excluded from the
CBE rerun sequence.
The timer can be found at parameter 2264 and represents how long time it takes from the excitation is removed until the voltage is
below “voltage rerun level”. The voltage discharge timer can be started either from a new start request or from when the generator
breaker opens. The different reactions are dependent on the selection of “excitation control during cooldown”. The two rerun
sequences shown below may enhance the understanding:
New start
% of nominal request
voltage CBE Break Lim
GB open GB close (2252) expired
100
Voltage
discharge
(2264)
Voltage rerun
level (2265)
0 Time
In the diagram above, the excitation is shut off as soon as the breaker is opened. Shortly after the breaker is opened, a new start
request appears. The Multi-line 2 unit will wait with the closing of the GB until the “voltage discharge timer” has expired.
100
Voltage
discharge
(2264)
Voltage rerun
level (2265)
0 Time
In the diagram above, the excitation is ON during cooldown. Then a new start request is made, which means that the excitation will
be shut off. When the excitation is shut off, the voltage discharge timer starts.
Comparing the two situations shows that the first example is the fastest. This is because the excitation is already off when the next
start request appears. If the new start request had appeared a little later, the voltage discharge timer could already have expired.
This means that the generator breaker could have closed very shortly after the new start request.
This default function can be modified using a digital input and extra relay outputs depending on the required function. The relay
selection is made in the menu 2240, and the input is selected in the input settings in the utility software.
Synchronising:
Synchronising:
The breaker ON relay activates when
The breaker ON relay and the sync. relay activate at the same time
synchronising is OK.
when synchronising is OK.
Not used Blackout closing:
Blackout closing:
The breaker ON relay activates when the
The breaker ON relay and the sync. relay activate at the same time
voltage and frequency are OK.
when the voltage and frequency are OK.
DEFAULT selection
Synchronising: Synchronising:
Not possible. Not possible.
Low Blackout closing: Blackout closing:
The breaker ON relay and the sync. relay activate at the same time The breaker ON relay activates when the
when the voltage and frequency are OK. voltage and frequency are OK.
Synchronising:
The relays will activate in two steps when the synchronising is
selected: Synchronising:
1. Breaker ON relay activates. Not possible.
High 2. When synchronised the sync. relay activates. Blackout closing:
See note below! The breaker ON relay activates when the
Blackout closing: voltage and frequency are OK.
The breaker ON relay and the sync. relay activate at the same time
when the voltage and frequency are OK.
DANGER!
When two relays are used together with the separate sync. input, then please notice that the breaker ON relay will
be activated as soon as the GB ON/synchronising sequence is activated.
Care must be taken that the GB ON relay cannot close the breaker, before the sync. signal is issued by the sync.
relay.
INFO
The selected relay for this function must have the "limit" function. This is adjusted in the I/O setup.
No
Mains condition
Ok 2281-2284
Yes
Close Mains
breaker
If the "Delay activate recovery 2" timer runs out, the long interruption timer (menu 2294 "Recovery del. 2") will start to run.
Examples:
Menu 2291 = 3 s
Menu 2292 = 5 s
That means: if the short interruption timer is set to < 3 s, and the grid is back and voltage and frequency are inside the acceptable
range stated above, then after 5 s the MB can be closed.
Menu 2291 = 3 s
Menu 2294 = 60 s
The long interruption timer will allow the MB to reconnect as soon as the mains voltage and frequency have been uninterrupted
within the timer setting in menu 2294 ("Recovery del. 2"). Then the MB can be closed.
INFO
The inhibit parameters for synchronising the MB are disabled by default.
For further information, please see the separate parameter list, document number 4189340688.