Manual Book
Manual Book
IM 01C27H01-01EN
4th Edition
Yokogawa Electric Corporation
i
Contents
1. Introduction................................................................................................ 1-1
1.1 Safe Use of This Product ................................................................................. 1-2
1.2 Radio Wave......................................................................................................... 1-3
1.3 Warranty.............................................................................................................. 1-3
1.4 Trademarks......................................................................................................... 1-3
1.5 ATEX Documentation........................................................................................ 1-4
2. Handling Cautions..................................................................................... 2-1
2.1 Model and Specifications Check...................................................................... 2-1
2.2 Unpacking........................................................................................................... 2-1
2.3 Storage................................................................................................................ 2-1
2.4 Selecting the Installation Location ................................................................. 2-2
2.5 Pressure Connection......................................................................................... 2-2
2.6 Restrictions on Use of Radio Transceivers.................................................... 2-3
2.7 Insulation Resistance and Dielectric Strength Test....................................... 2-3
2.8 Installation of an Explosion-Protected Instrument........................................ 2-4
2.8.1 FM Approval........................................................................................ 2-4
2.8.2 CSA Certification................................................................................. 2-4
2.8.3 CENELEC ATEX (KEMA) Certification............................................... 2-5
2.8.4 IECEx Certification.............................................................................. 2-6
2.9 EMC Conformity Standards.............................................................................. 2-7
2.10 Pressure Equipment Directive (PED) ............................................................. 2-7
2.11 Low Voltage Directive........................................................................................ 2-8
2.12 Regulatory Compliance for Radio and Telecommunication......................... 2-8
2.12.1 Radio and Telecommunications Terminal Equipment Directive (R&TTE)
..................................................................................................... 2-8
2.12.2 FCC compliance................................................................................. 2-8
2.12.3 Industry Canada (IC) compliance....................................................... 2-8
3. Component Names................................................................................... 3-1
IM 01C27H01-01EN
iii
7.3.15 Software Write Protect...................................................................... 7-16
7.3.16 Switching to Deep Sleep Mode......................................................... 7-16
7.3.17 Switching to Silence Mode................................................................ 7-16
7.4 Self-Diagnostics............................................................................................... 7-17
7.4.1 Identify Problems by Using the Device Configuration Tool............... 7-17
7.4.2 Checking with Integral Indicator........................................................ 7-19
8. Maintenance............................................................................................... 8-1
8.1 Overview............................................................................................................. 8-1
8.2 Calibration Instruments Selection................................................................... 8-1
8.3 Calibration.......................................................................................................... 8-1
8.4 Disassembly and Reassembly......................................................................... 8-3
8.4.1 Replacing the Integral Indicator.......................................................... 8-3
8.4.2 Replacing the RF Assembly................................................................ 8-4
8.4.3 Replacing the CPU Assembly............................................................. 8-4
8.4.4 Replacing the Battery Pack................................................................ 8-5
8.4.5 Replacing the Batteries....................................................................... 8-5
8.4.6 Handling Batteries............................................................................... 8-6
8.5 Troubleshooting................................................................................................. 8-7
8.5.1 Basic Troubleshooting........................................................................ 8-7
8.5.2 Troubleshooting Flowcharts................................................................ 8-8
8.5.3 Alarms and Countermeasures.......................................................... 8-10
9. Parameter Summary................................................................................. 9-1
10. General Specifications........................................................................... 10-1
10.1 Standard Specifications.................................................................................. 10-1
10.2 Model and Suffix Codes.................................................................................. 10-4
10.3 Optional Specifications ................................................................................10-10
10.4 Dimensions . ..................................................................................................10-12
Revision Information................................................................................................i
IM 01C27H01-01EN
<1. Introduction> 1-1
1. Introduction
Thank you for purchasing the DPharp EJX • Please note that changes in the specifications,
Differential Pressure and pressure transmitter. construction, or component parts of the
instrument may not immediately be reflected
Your EJX Pressure Transmitter was precisely
in this manual at the time of change, provided
calibrated at the factory before shipment. To ensure
that postponement of revisions will not cause
both safety and efficiency, please read this manual
difficulty to the user from a functional or
carefully before you operate the instrument.
performance standpoint.
Model
WARNING
EJX118B
Indicates a potentially hazardous situation which,
EJX438B
if not avoided, could result in death or serious
injury.
Regarding This Manual
• This manual should be provided to the end
user.
CAUTION
• The contents of this manual are subject to
change without prior notice. Indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate
• All rights reserved. No part of this manual may
injury or physical damage. It may also be used to
be reproduced in any form without Yokogawa’s
alert against unsafe practices.
written permission.
• Yokogawa makes no warranty of any kind with
regard to this manual, including, but not limited IMPORTANT
to, implied warranty of merchantability and
fitness for a particular purpose. Indicates that operating the hardware or software
• If any question arises or errors are found, or if in this manner may damage it or lead to system
any information is missing from this manual, failure.
please inform the nearest Yokogawa sales
office.
• The specifications covered by this manual are
NOTE
limited to those for the standard type under the Draws attention to information essential for
specified model number break-down and do not understanding the operation and features.
cover custom-made instruments.
IM 01C27H01-01EN
<1. Introduction> 1-2
1.1 Safe Use of This Product (d) Explosion Protected Type Instrument
For the safety of the operator and to protect the • Users of explosion proof instruments should
instrument and the system, please be sure to follow refer first to section 2.8 (Installation of an
this manual’s safety instructions when handling this Explosion Protected Instrument) of this manual.
instrument. If these instructions are not heeded, • The use of this instrument is restricted to those
the protection provided by this instrument may be who have received appropriate training in the
impaired. In this case, Yokogawa cannot guarantee device.
that the instrument can be safely operated. Please
• Take care not to create sparks when accessing
pay special attention to the following points:
the instrument or peripheral devices in a
hazardous location.
(a) Installation
• Repair or modification to this instrument by
• This instrument may only be installed by an
customer will cause malfunction of explosion
engineer or technician who has an expert
protect function and hazardous situation. If you
knowledge of this device. Operators are not
need to repair or modification, please contact
allowed to carry out installation unless they
the nearest Yokogawa office.
meet this condition.
• With high process temperatures, care must (e) Modification
be taken not to burn yourself by touching the • Yokogawa will not be liable for malfunctions or
instrument or its casing. damage resulting from any modification made
• Never loosen the process connector nuts when to this instrument by the customer.
the instrument is installed in a process. This can
lead to a sudden, explosive release of process
fluids.
• When draining condensate from the pressure
detector section, take appropriate precautions
to prevent the inhalation of harmful vapors and
the contact of toxic process fluids with the skin
or eyes.
• When removing the instrument from a
hazardous process, avoid contact with the fluid
and the interior of the meter.
• All installation shall comply with local installation
requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an
engineer or technician who has an expert
knowledge of this instrument. Operators are not
permitted to carry out wiring unless they meet
this condition.
(c) Maintenance
• Please carry out only the maintenance
procedures described in this manual. If you
require further assistance, please contact the
nearest Yokogawa office.
• Care should be taken to prevent the build up of
dust or other materials on the display glass and
the name plate. To clean these surfaces, use a
soft, dry cloth.
IM 01C27H01-01EN
<1. Introduction> 1-3
1.2 Radio Wave • If any problems are experienced with this
instrument, the customer should contact the
IMPORTANT Yokogawa representative from which this
instrument was purchased or the nearest
- This instrument is equipped with a wireless Yokogawa office.
module which is designated as a certification • If a problem arises with this instrument,
of construction type as a wireless please inform us of the nature of the problem
facility for 2.4 GHz band low-power data and the circumstances under which it
communication system of the Radio Act. developed, including the model specification
Refer to 2.12 “Regulatory Compliance for and serial number. Any diagrams, data and
Radio and Telecommunication” for detail. other information you can include in your
- Due to the designated certification of communication will also be helpful.
construction type, users may be subject to • The party responsible for the cost of fixing the
legal punishment in case of: problem shall be determined by Yokogawa
- Disassembling or modifying the wireless following an investigation conducted by
module or antenna in this instrument Yokogawa.
- Peeling off the certification label attached
• The purchaser shall bear the responsibility for
to the wireless module in this instrument
repair costs, even during the warranty period, if
- Preventing interference with other wireless the malfunction is due to:
stations
The operating frequency bandwidth of this - Improper and/or inadequate maintenance by
instrument may overlap the same range the purchaser.
as industrial devices, scientific devices, - Malfunction or damage due to a failure
medical devices, microwave ovens, licensed to handle, use, or store the instrument in
premises radio stations and non-licensed accordance with the design specifications.
specified low-power radio stations for mobile - Use of the product in question in a location
object identification systems used in factory not conforming to the standards specified by
production lines. Yokogawa, or due to improper maintenance
Before using this instrument, ensure that of the installation location.
neither a premises radio station nor specified - Failure or damage due to modification or
low power radio station for mobile object repair by any party except Yokogawa or an
identification systems is in use nearby. approved representative of Yokogawa.
If this instrument causes radio wave - Malfunction or damage from improper
interference to a wireless station for mobile relocation of the product in question after
object identification systems, promptly delivery.
change the frequency being used or turn - Reason of force majeure such as fires,
off the source of radio wave emissions. earthquakes, storms/floods, thunder/
Then, contact a Yokogawa office regarding lightening, or other natural disasters, or
countermeasures to prevent interference, disturbances, riots, warfare, or radioactive
such as setting up partitions. contamination.
1.4 Trademarks
1.3 Warranty In this document, trademarks or registered
• The warranty shall cover the period noted on trademarks are not marked with “™” or “®”.
the quotation presented to the purchaser at the Product names and company names in this
time of purchase. Problems occurring during document are trademarks or registered trademarks
the warranty period shall basically be repaired of the respective companies
free of charge.
IM 01C27H01-01EN
<1. Introduction> 1-4
1.5 ATEX Documentation
This is only applicable to the countries in European Union.
GB SK
CZ
DK
I LT
E LV
EST
NL
PL
SF
SLO
P
BG
RO
S
M
GR
IM 01C27H01-01EN
<2. Handling Cautions> 2-1
2. Handling Cautions
This chapter provides important information on how 2.2 Unpacking
to handle the transmitter. Read this carefully before
using the transmitter. Keep the transmitter in its original packaging to
prevent it from being damaged during shipment.
EJX Series transmitters are thoroughly tested at the Do not unpack the transmitter until it reaches the
factory before shipment. When taking delivery of an installation site.
instrument, visually check them to make sure that
no damage occurred during shipment.
2.3 Storage
Also check that all transmitter mounting hardware
The following precautions must be observed when
shown in figure 2.1 is included. If the transmitter
storing the instrument, especially for a long period.
is ordered without the mounting bracket and the
process connector, the transmitter mounting (a) Select a storage area which meets the following
hardware will not be included. After checking the conditions:
transmitter, carefully repack it in its box and keep it • It is not exposed to rain or subject to water
there until you are ready to install it. seepage/leaks.
• Vibration and shock are kept to a minimum.
Spacer • It has an ambient temperature and relative
Transmitter humidity within the following ranges.
mounting bolt
Ambient temperature:
–40 to 85°C
U-bolt
–30 to 80°C LCD visible range
Relative humidity:
0% to 100% R.H.
Preferred temperature and humidity:
U-bolt nut Mounting bracket approx. 25°C and 65% R.H.
(Flat type)
F0201.ai (b) When storing the transmitter, repack it carefully in
Figure 2.1 Transmitter Mounting Hardware the packaging that it was originally shipped with.
(c) If the transmitter has been used, thoroughly
clean the chambers inside the cover flanges, so
2.1 Model and Specifications that there is no process fluid remaining inside.
Check Before placing it in storage, also make sure that
the pressure-detector is securely connected to
The model name and specifications are written on
the transmitter section.
the name plate attached to the case.
(d) Preferably remove the batteries for storage. For
CAL
RNG maximum battery life, the storage temperature
should not exceed 30°C.
MODEL STYLE
SUFFIX
SUPPLY V DC
OUTPUT mA DC NO.
NOTE
MWP
Made in Japan : Refer to USER'S MANUAL.
TOKYO 180-8750 JAPAN
F0202.ai
Figure 2.2 Name Plate When storing the instrument with a battery
pack, it is recommended to put the instrument in
Deep Sleep mode to conserve the batteries. For
details on how to switch to Deep Sleep mode,
refer to subsection 8.3.16 “Switching to Deep
Sleep Mode”.
IM 01C27H01-01EN
<2. Handling Cautions> 2-2
2.4 Selecting the Installation (b) Ambient Temperature
Avoid locations subject to wide temperature
Location variations or a significant temperature gradient.
The transmitter is designed to withstand severe If the location is exposed to radiant heat from
environmental conditions. However, to ensure plant equipment, provide adequate thermal
that it will provide years of stable and accurate insulation and/or ventilation.
performance, take the following precautions when (c) Ambient Atmosphere
selecting the installation location. Do not install the transmitter in a corrosive
atmosphere. If this cannot be avoided, there
(a) Wireless Communication
must be adequate ventilation.
WARNING
• Never loosen the process flange bolts when
1.5m or more
IM 01C27H01-01EN
<2. Handling Cautions> 2-3
2.6 Restrictions on Use of Radio 4) Turn ON the insulation tester power and
measure the insulation resistance. The voltage
Transceivers should be applied as briefly as possible to verify
that the insulation resistance is at least 20 MΩ.
IMPORTANT 5) After completing the test and being very careful
not to touch exposed conductors disconnect the
Although the transmitter has been designed to
insulation tester and connect a 100 kΩ resistor
resist high frequency electrical noise, if a radio
between the grounding terminal and the short-
transceiver is used near the transmitter or its
circuiting battery connection terminals. Leave
external wiring, the transmitter may be affected
this resistor connected at least one second to
by high frequency noise pickup. To test this, start
discharge any static potential. Do not touch the
out from a distance of several meters and slowly
terminals while it is discharging.
approach the transmitter with the transceiver
while observing the measurement loop for noise NOTE
effects. Thereafter use the transceiver outside
the range where the noise effects were first When storing the instrument with a battery
observed. pack, it is recommended to put the instrument in
Deep Sleep mode to conserve the batteries. For
details on how to switch to Deep Sleep mode,
2.7 Insulation Resistance and refer to subsection 7.3.16 “Switching to Deep
Sleep Mode”.
Dielectric Strength Test
Since the transmitter has undergone insulation
• Dielectric Strength Test
resistance and dielectric strength tests at the factory
before shipment, normally these tests are not 1) Remove the battery pack. See subsection 9.4.6
required. If the need arises to conduct these tests, for details on how to remove it.
heed the following: 2) Short-circuit the battery connection terminals in
the terminal box.
(a) Do not perform such tests more frequently than
3) Turn OFF the dielectric strength tester. Then
is absolutely necessary. Even test voltages that
connect the tester between the shorted battery
do not cause visible damage to the insulation
connection terminals and the grounding
may degrade the insulation and reduce safety
terminal. Be sure to connect the grounding lead
margins.
of the dielectric strength tester to the ground
(b) Never apply a voltage exceeding 500 V DC
terminal.
(100 V DC with an internal lightning protector)
4) Set the current limit on the dielectric strength
for the insulation resistance test, nor a voltage
tester to 0.1 mA, then turn ON the power and
exceeding 500 V AC (100 V AC with an internal
gradually increase the test voltage from ‘0’ to
lightning protector) for the dielectric strength
the specified voltage.
test.
5) When the specified voltage is reached, hold it
(c) The procedure for conducting these tests is as
for one minute.
follows:
6) After completing this test, slowly decrease the
• Insulation Resistance Test voltage to avoid any voltage surges.
1) Remove the battery pack. See subsection 9.4.6
for details on how to remove it. NOTE
2) Short-circuit the battery connection terminals in
When storing the instrument with a battery
the terminal box.
pack, it is recommended to put the instrument in
3) Turn OFF the insulation tester. Then connect
Deep Sleep mode to conserve the batteries. For
the insulation tester plus (+) lead wire to the
details on how to switch to Deep Sleep mode,
shorted battery connection terminals and the
refer to subsection 7.3.16 “Switching to Deep
minus (–) leadwire to the grounding terminal.
Sleep Mode”.
IM 01C27H01-01EN
<2. Handling Cautions> 2-4
2.8 Installation of an Explosion- Note 2. Installation
• Installation should be in accordance with
Protected Instrument ANSI/ISA RP12.6 “Installation of Intrinsically
If a customer makes a repair or modification to an Safe Systems for Hazardous (Classified)
intrinsically safe instrument and the instrument is Locations” and the National Electric Code
not restored to its original condition, its intrinsically (ANSI/NFPA 70).
safe construction may be compromised and the • Dust-tight conduit seal must be used when
instrument may be hazardous to operate. Please installed in a Class II, III, Group E, F and G
contact Yokogawa before making any repair or environments.
modification to an instrument. • Note a warning label worded
“SUBSTITUTION OF COMPONENTS
MAY IMPAIR INTRINSIC SAFETY,” and
CAUTION “INSTALL IN ACCORDANCE WITH DOC.
This instrument has been tested and certified No. IFM037-A20”.
as being intrinsically safe. Please note that Note 3. Maintenance and Repair
severe restrictions apply to this instrument’s • The instrument modification or parts
construction, installation, external wiring, replacement by other than authorized
maintenance and repair. A failure to abide by representative of Yokogawa Electric
these restrictions could make the instrument a Corporation is prohibited and will void
hazard to operate. Factory Mutual Intrinsically safe and
Nonincendive Approval.
2.8.1 FM Approval Hazardous Location
IM 01C27H01-01EN
<2. Handling Cautions> 2-5
[For CSA C22.2] 2.8.3 CENELEC ATEX (KEMA)
• Applicable Standard: C22.2 No.0, C22.2 Certification
No.0.4, C22.2 No.25, C22.2 No.94, C22.2
No.157, C22.2 No.213, C22.2 No.61010-1 (1) Technical Data
• Intrinsically Safe for Class I, Division 1, Caution for CENELEC ATEX (KEMA) Intrinsically
Groups A, B, C & D, Class II, Division 1, safe type.(Following contents refer to “Doc No.
Groups E, F & G, Class III, Division 1 IKE037”)
• Nonincendive for Class I, Division2,
Groups A, B, C & D, Class II, Division2, Note 1. Model EJX Series pressure transmitters
Groups F & G, Class III, Division1 with optional code /KS27 for potentially
• Enclosure: Type 4X, explosive atmospheres:
• Temp. Code: T4 • No. KEMA 10ATEX0164 X
• Amb. Temp.:-50 to 70°C • Applicable Standard:
• Process Temperature: 120°C max. EN 60079-0:2009, EN 60079-11:2007,
[For CSA E60079] EN 60079-26:2007
• Applicable Standard: CAN/CSA E60079-0, • Type of Protection and Marking code:
CAN/CSA E60079-11, IEC 60529:2001-02 Ex ia IIC T4 Ga
• Ex ia IIC T4 • Group: II
• Ambient Temperature: -50 to 70°C • Category: 1G
• Max. Process Temp.: 120°C • Ambient Temperature: –50°C to 70°C
• Enclosure: IP66 and 67 • Process Temperature (Tp.): 120°C max.
• Enclosure: IP66 and IP67
Note 2. Installation Note 2. Installation
• Installation should be in accordance with • Installation should be in accordance with
Canadian Electrical Code Part I and Local local installation requirements. (Refer to the
Electrical Code. installation diagram)
• Do not alter drawing without authorization
from CSA. [Installation Diagram]
• The instrument modification or parts Hazardous Location
replacement by other than authorized
representative of Yokogawa Electric
Corporation of America is prohibited and will
void Canadian Standards Intrinsically safe
Transmitter
and nonincendive Certification.
F0206.ai
Hazardous Location
Note 3. Battery Pack
• Use only YOKOGAWA battery pack
F9915MA.
Transmitter
[Intrinsically Safe] [Nonincendive]
Group IIC, Zone 0 Class I, II, Division 2,
Class I, II, III, Division 1, Groups A,B,C,D,F,G
Groups A,B,C,D,E,F,G Class III, Division 1
F0205.ai
IM 01C27H01-01EN
<2. Handling Cautions> 2-6
Note 4. Special conditions for Safe Use MODEL: Specified model code.
• In the case where the enclosure of the STYLE: Style code.
Pressure Transmitter is made of aluminium, SUFFIX: Specified suffix code.
if it is mounted in an area where the use of SUPPLY: Supply voltage.
category 1 G apparatus is required, it must OUTPUT: Output signal.
be installed such, that, even in the event of MWP: Maximum working pressure.
rare incidents, ignition sources due to impact CAL RNG: Specified calibration range.
and friction sparks are excluded. NO.: Serial number and year of production *1.
TOKYO 180-8750 JAPAN:
• Avoid any actions that cause the generation
The manufacturer name and the address *2.
of electrostatic charge on the non-metallic
*1: The first digit in the final three numbers of the serial
parts, such as rubbing with a dry cloth on number appearing after “NO.” on the nameplate indicates
coating face of product. the year of production. The following is an example of a
serial number for a product that was produced in 2010:
91K819857 032
WARNING ↑
The year 2010
Potential electrostatic charging hazard - secure
*2: “180-8750” is a zip code which represents the following
distance of 100mm from antenna. address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
(2) Operation 2.8.4 IECEx Certification
Caution for IECEx Intrinsically safe type.
WARNING (Following contents refer to “Doc No. IKE037”)
Take care not to generate mechanical sparking Note 1. Model EJX Series pressure transmitters
when access to the instrument and peripheral with optional code /SS27 for potentially
devices in a hazardous location. explosive atmospheres:
• No. IECEx KEM 10.0074X
• Applicable Standard:
(3) Maintenance and repair IEC 60079-0: 2007, IEC 60079-11:2006,
IEC 60079-26: 2006
• Type of Protection and Marking code:
WARNING
Ex ia IIC T4 Ga
The instrument modification or parts replacement • Ambient Temperature: –50°C to 70°C
by other than an authorized Representative of • Process Temperature (Tp.): 120°C max.
Yokogawa Electric Corporation is prohibited and • Enclosure: IP66 and IP67
will void the certification. Note 2. Installation
• Installation should be in accordance with
local installation requirements.
(4) Name Plate
(Refer to the installation diagram)
• Name Plate
[Installation Diagram]
CAL
RNG Hazardous Location
MODEL STYLE
SUFFIX
SUPPLY V DC
OUTPUT mA DC NO.
MWP
Made in Japan : Refer to USER'S MANUAL.
TOKYO 180-8750 JAPAN
F0207.ai
Transmitter
• Tag plate for intrinsically safe type F0209.ai
F0208.ai
IM 01C27H01-01EN
<2. Handling Cautions> 2-7
Note 3. Maintenance and Repair 2.10 Pressure Equipment
• The instrument modification or parts
replacement by other than authorized
Directive (PED)
representative of Yokogawa Electric
(1) General
Corporation is prohibited and will void IECEx
Intrinsically safe Certification. EJX Series pressure transmitters are
categorized as piping under the pressure
accessories section of directive 97/23/EC,
WARNING which corresponds to Article 3, Paragraph 3 of
PED, denoted as Sound Engineering Practice
The instrument modification or parts replacement
(SEP).
by other than an authorized Representative of
Yokogawa Electric Corporation is prohibited and (2) Technical Data
will void the certification. Article 3, Paragraph 3 of PED, denoted as
Sound Engineering Practice (SEP).
Note 4. Battery Pack (3) Operation
• Use only YOKOGAWA battery pack
F9915MA.
CAUTION
Note 5. Special conditions for Safe Use
• In the case where the enclosure of the • The temperature and pressure of fluid should
Pressure Transmitter is made of aluminium, be maintained at levels that are consistent
if it is mounted in zone 0, it must be installed with normal operating conditions.
such, that, even in the event of rare incidents, • The ambient temperature should be
ignition sources due to impact and friction maintained at a level that is consistent with
sparks are excluded. normal operating conditions.
• Avoid any actions that cause the generation • Please take care to prevent water hammer
of electrostatic charge on the non-metallic and the like from inducing excessive
parts, such as rubbing with a dry cloth on pressures in pipes and valves. If phenomena
coating face of product. are likely, install a safety valve or take
some other appropriate measure to prevent
pressure from exceeding PS.
WARNING • Take appropriate measures at the device or
system level to protect transmitters if they
• Potential electrostatic charging hazard - are to be operated near an external heat
secure distance of 100mm from antenna. source.
• Take care not to generate mechanical
sparking when access to the instrument and
peripheral devices in a hazardous location.
CAUTION
This instrument is a Class A product, and it is
designed for use in the industrial environment.
Please use this instrument in the industrial
environment only.
IM 01C27H01-01EN
<2. Handling Cautions> 2-8
2.11 Low Voltage Directive 2.12.2 FCC compliance
Applicable standard: EN61010-1 This device complies with Part 15 of FCC
Rules. Operation is subject to the following
(1) Pollution Degree 2
two conditions: (1) this device may not cause
"Pollution degree" describes the degree to interference, and (2) this device must accept
which a solid, liquid, or gas which deteriorates any interference, including interference that
dielectric strength or surface resistivity is may cause undesired operation of this device.
adhering. " 2 " applies to normal indoor
atmosphere. Normally, only non-conductive Co-located:
pollution occurs. Occasionally, however, This transmitter must not be co-located or
temporary conductivity caused by condensation operated in conjunction with any other antenna
must be expected. or transmitter.
(2) Installation Category I
FCC WARNING:
"Overvoltage category (Installation category)"
describes a number which defines a transient Changes or modifications not expressly
overvoltage condition. It implies the regulation approved by the party responsible for
for impulse withstand voltage. " I " applies to compliance could void the user’s authority to
electrical equipment which is supplied from the operate the equipment.
circuit when appropriate transient overvoltage
control means (interfaces) are provided. NOTE
This equipment has been tested and found
2.12 Regulatory Compliance to comply with the limits for a Class A digital
for Radio and device, pursuant to part 15 of the FCC Rules.
Telecommunication These limits are designed to provide reasonable
protection against harmful interference when
Please confirm that a installation region fulfils the equipment is operated in a commercial
a standards, require additional regulatory environment.
information and approvals, contact to This equipment generates, uses, and can radiate
Yokogawa Electric Corporation. radio frequency energy and, if not installed
2.12.1 Radio and Telecommunications and used in accordance with the instruction
Terminal Equipment Directive (R&TTE) manual,may cause harmful interference to radio
communications. Operation of this equipment
in a residential area is likely to cause harmful
We, Yokogawa Electric Corporation hereby interference in which case the user will be
declare that this equipment, model EJX-L series required to correct the interference at his own
is in compliance with the essential requirements expense.
and other relevant provisions of Directive
1999/5/EC.
2.12.3 Industry Canada (IC) compliance
The CE declaration of conformity for R&TTE
for this product can be found at http://www. This Class A digital apparatus complies with
yokogawa.com/fld/ Canadian ICES-003.
French: Cet appareil numérique de la classe A
est conforme à la norme NMB-003 du Canada.
NOTE
Operation is subject to the following two
France restricts outdoor use to 10mW conditions: (1) this device may not cause
(10dBm) EIRP in the frequency range of 2,454 interference, and (2) this device must accept
- 2,483.5MHz. Installation in France must any interference, including interference that
configure the network with the field wireless may cause undesired operation of the device.
configuration tool not to use channel 10 to 14. To
configure the network,
refer to IM 01W01F01-01EN.
IM 01C27H01-01EN
<3. Component Names> 3-1
3. Component Names
EJX118 EJX438B
Transmitter Drain/vent plug Transmitter
section * Flushing section *
connection ring
* See below
for details * See below
Capillary tube
for details
Diaphragm seal
(high pressure side)
Diaphragm seal
(low pressure side) Diaphragm seal
Pressure-
Pressure- detector section
detector section
F0301.ai
Ground terminal
Zero-adjustment screw
Integral indicator
CPU assembly Cover flange
Note 1: Write Protection is set by sliding the hard write protection switch (WR) shown in figure. The hardware write protection switch is
set to the E side (Write enable) for delivery. Set an unused switch to H side.
Note 2: When the switch is D side (write protection setting), provisioning is acceptable. For details of provisioning, refer to section 7.4
“Connecting to Field Wireless Network”.
IM 01C27H01-01EN
<4. Installation> 4-1
4. Installation
4.1 Precautions 4.2 Mounting the Diaphragm
Before installing the transmitter, read the cautionary Seals
notes in section 2.4, “Selecting the Installation
Mount the diaphragm seals using the flanges as
Location.” For additional information on the
shown in Figure 4.1. Figure 4.2 and Figure 4.3
ambient conditions allowed at the installation
shows how to mount the diaphragm seals on a
location, refer to subsection 10.1 “Standard
tank. The mating flange, gasket, bolts and nuts are
Specifications.”
to be procured by the customer.
Flange
Nut
NOTE Bolt Diaphragm
take care not to allow welding currents to Figure 4.1 Mounting the Diaphragm Seals
flow through the transmitter.
• Do not step on this instrument after
installation. IMPORTANT
• For the EJX438B, there is a small hole in the Please use a gasket with an inside diameter
low pressure side cover flange that is used to (ød) that is greater than the diameter of the
measure the atmospheric pressure. diaphragm seal. If a gasket with a smaller
The hole must not face upward. See section inside diameter is used, the diaphragm may not
10.4, “Dimensions,” for the location of the function correctly. (Refer to Subsection 10.4
hole. ‘Dimensions’)
• Never loosen the four bolts securing the
cover flanges (Refer to figure 3.2.) If the seal
liquid leaks, the transmitter cannot be used.
IM 01C27H01-01EN
<4. Installation> 4-2
Low
IMPORTANT IMPORTANT pressure
side
Install the sealed diaphragm
• When measuring the liquid level of the tank, so that the shank positions
the minimum liquid level (zero point) must downward.
be set to a level at least 50 mm above the
center of the high pressure side diaphragm
seal (see Figure 4.2). High
Minimum
• Correctly install the diaphragm seals on the pressure
liquid level
side
high and low pressure sides of the process, 50mm minimum
checking the label on each seal.
• To avoid measuring error duets temperature
difference between the two diaphragm
seals, capillary tube must be bound together. The transmitter should be
installed as low as possible
The capillary tube must be securely fixed below the position where
to the tank wall to prevent movement by the high pressure side
wind or vibration. If the capillary tube is too diaphragm seal is installed.
diameter of 300 mm or more) and secure the Figure 4.2 Installing the Diaphragm Seals to a
coiled tube with a clamp. Tank (differential pressure transmitter)
• During the diaphragm seal installation,
ensure as far as possible that no seal liquid IMPORTANT
head pressure is applied to the diaphragm Install the sealed diaphragm
seals. so that the shank positions
• Exercise care so as not to damage downward.
F0403.ai
IM 01C27H01-01EN
<4. Installation> 4-3
■ When mounting the bracket on the transmitter, ■ When the transmitter can’t be installed at least
tighten the (four) bolts that hold the transmitter 600 mm below the HP process connection.
to a torque of approximately 39 N·m {4 kgf·m}.
IMPORTANT
IMPORTANT
The transmitter should be installed at least
• The transmitter should be installed at least 600 mm below the high pressure (HP) process
600 mm below the high pressure (HP) connection to ensure a positive head pressure
process connection to ensure a positive of fill fluid. Pay special attention to vacuum
head pressure of fill fluid. Pay special applications.
attention to vacuum applications. If it can not be installed at least 600 mm below
Refer to “When the transmitter can’t be the HP process connection, please use the
installed at least 600 mm below the HP equation below:
process connection” if the transmitter can’t (P–P0) × dHg
h= ×7.5×10–3 [mm]
be installed at least 600 mm below. ds
• Never loosen the four bolts securing the h: Vertical height between the HP process
cover flange or the screws at the joints connection and the transmitter (mm)
between the capillary tube and cover flanges h≤0: Install the transmitter at least h (mm)
(Refer to figure 3.2.) If the seal liquid leaks, below the HP process connection
the transmitter cannot be used. h>0: Install the transmitter at most h (mm)
above the HP process connection
Horizontal pipe mounting P: Pressure in the tank (Pa abs)
P0: Minimum working pressure limit of
the transmitter (Pa abs) If the ambient
temperature range is –10 to 50°C.
2951 (Wetted parts material code SW, SE
and SY)
Transmitter
mounting bolt 3185 (Wetted parts material code TW)
4573 (Wetted parts material code HW)
3810 (Wetted parts material code UW)
ds: Specific gravity of fill fluid (at 25°C), refer
to table 10.1 on section 10.1 General
U-bolt nut Specifications.
dHg:Specific gravity of the Mercury 13.6 (at
Mounting 25°C)
Vertical pipe mounting U-bolt
bracket
50mm (2-inch) pipe
Transmitter
mounting bolt
50mm
(2-inch) pipe
U-bolt nut
Mounting
bracket U-bolt
F0404.ai
IM 01C27H01-01EN
<4. Installation> 4-4
F0405.ai
Ring holder
Drain/vent plug
IM 01C27H01-01EN
<4. Installation> 4-5
IMPORTANT
Spiral gasket
Mating flange 1) Position the diaphragm seal so that the
Ring diaphragm is in a upward position.
2) Pour the fluorinated oil on the diaphragm
and gasket area covering it completely
and evenly. Be careful not to scratch the
diaphragm or change the its shape.
3) Affix the teflon film over the diaphragm and
gasket area.
Diaphragm
4) Next, carefully inspect the cover and try
Gasket Pressure-detector to identify any entrapped air between
section
the diaphragm and the teflon film. The
air must be removed to ensure optimum
performance. If air pockets are present, use
your fingers to remove the air by starting at
the center of the diaphragm and work your
F0408.ai way out.
Figure 4.8 Mounting to Process Flange 5) Position the gasket on the Teflon film.
6) Mount the transmitter onto the process
flange.
IMPORTANT
Teflon film
• Confirm that there is no gap between the ring PART No. Process flange size
and the process-detector section after they F9347XA For 3inch (80 mm)
are mounted on the process flange. A gap F9347YA For 2inch (50 mm)
can lead to a sudden, explosive release of Fluorinated oil
process fluids. [PART No.: F9145YN]
• When mounting or removing the ring,
take care not to tilt the pressure detector
downward as the ring can slip off and cause Diaphragm
injury.
• When re-mounting the ring, use the new Gasket area
spiral gasket as shown in below table.
IM 01C27H01-01EN
<4. Installation> 4-6
The transmitter section can be rotated 4.8 Changing the direction of
approximately 360° (180° to either direction or
360° to one direction from the original position at
the antenna
shipment, depending on the configuration of the Adjust the direction of the antenna to be in the
instrument.) It can be fixed at any angle within upright position. Figure 4.11 shows factory setup
above range. antenna position. If the transmitter is installed to
vertical impulse piping, follow the procedure below
1) Remove the five setscrews that fasten the
and change the antenna position.
transmitter section and capsule assembly,
using the Allen wrench. 1) Loosen the two mounting screws at the bottom
2) Rotate the transmitter section slowly and stop it of the antenna by using a 2.5 mm Allen wrench
at designated position. (see Figure 4.11).
3) Tighten the five setscrews to a torque of 1.5 The screws might come off and be lost if
N·m. loosened too much; loosen the screws by about
three rotations.
IMPORTANT 2) Press forward and down 90 degrees by rotating
the axis at the bottom of the antenna.
Do not rotate the transmitter section more than 3) Tighten the two screws to a torque of 1.5 N·m
the above limit. by using a torque wrench. When doing this, be
careful not leave a gap between the antenna
Transmitter section and housing.
Rotate 180°segments
F0411.ai
Pressure-detector section
F0410.ai
WARNING
F0412.ai
Intrinsic safe type transmitters must be, as a
Figure 4.12 Adjusting Antenna Position
rule, remove a battery pack in non-hazardous
area before open/close the Amplifier Cover or
disassembling and reassembling the Integral
Indicator.
IM 01C27H01-01EN
<5. Grounding> 5-1
5. Grounding
Always ground the transmitter case in accordance
with national and local electrical codes. The most
effective transmitter case grounding method is
a direct connection to earth ground with minimal
impedance.
Ground terminal
F0501.ai
CAUTION
Grounding is recommended for safe operation.
IM 01C27H01-01EN
<6. Operation> 6-1
6. Operation
6.1 Preparation for Starting
Operation
This section describes the operation procedure
for the EJX118B as shown in Figure 6.1 when Diaphragm seal
measuring liquid level in a closed tank, and
EJX438B as shown in Figure 6.2 when measuring
pressure in a tank.
Capillary tube
NOTE
Pressure transmitter
It is required to set security and network
information to enable the transmitter to be
connected to the Field Wireless Network. For
more details, refer to section 6.4 “Connecting to
the Field Wireless Network”. Transmitter
mounting pipe
50mm (2 inches)
F0602.ai
Diaphragm seal
(low pressure side)
Figure 6.2 Pressure Measurement
Figure6.1 Liquid Level Measurement in a Closed Integral Indicator’s indication can be used to
Tank confirm that the transmitter is operating properly.
For details on how to confirm, refer to subsection
7.4 “Self-Diagnostics”.
ISA100 devices display self-diagnostic information
in an easy-to-understand manner using four
categories (Check function, Maintenance required,
Failure, and Off specification) according to NAMUR
NE107*.
* NAMUR NE107 “Self-Monitoring and Diagnosis of Field
Devices”
IM 01C27H01-01EN
<6. Operation> 6-2
■ Confirm that transmitter is operating (1) When you can obtain the Low Range Value
properly by integral indicator. from the actual measured value of 0%
(0 kPa, atmospheric pressure);
• If the transmitter is faulty, an error code is
displayed.
■ Using the transmitter’s zero-adjustment
screw
Before adjusting zero point, make sure
followings.
• The External zero trim parameter
(External Zero Trim) is “Trim on”. For details,
refer to section 7 “Setting Parameters”.
• Use a slotted screwdriver to turn the zero
adjustment screw. Turn the screw clockwise
to increase the output or counterclockwise to
Self-diagnostic error on integral indicator
decrease the output.
(Faulity transmitter) • The zero point adjustment can be made with
F0603.ai a resolution of 0.01% of the setting range.
Figure 6.3 Integral Indicator with Error Code The degree of zero adjustments varies with
the screw turning speed; turn the screw
slowly to make a fine adjustment, quickly to
NOTE make a rough adjustment.
IMPORTANT
Do not turn off the power to the transmitter
immediately after performing a zero point
adjustment. Powering off within 30 seconds of
performing this procedure will return the zero
point to its previous setting.
IM 01C27H01-01EN
<6. Operation> 6-3
■ Using the Device Configuration Tool 6.4 Connecting to the Field
Refer to subsection 7.3.14 “Zero-point Wireless Network
Adjustment and Span Adjustment”.
■ Preparation work prior to connecting to a
(2) When you cannot obtain the Low Range Field Wireless Network
Value from the actual measured value of
This transmitter does not need to be connected
0%;
with a physical wire. Instead of physical wiring, it
Adjust the transmitter output to the actual measured is necessary to set the field wireless devices to
value obtained by a glass gauge, etc. communicate with before installing the transmitter.
[Example] This procedure is called a provisioning.
The measuring range of 0 to 2m; the actual This transmitter supports provisioning via infrared
measured value of 0.8m communication using a provisioning device and
can be securely connected to a network. If the
0.8 provisioning information is not set, the transmitter
Actual measured value= x100=40.0%
2 cannot be connected to the field wireless network.
IMPORTANT
• Close the terminal box cover and the
amplifier cover. Screw each cover in tightly
until it will not turn further.
• Tighten the zero-adjustment cover mounting F0605.ai
IM 01C27H01-01EN
<6. Operation> 6-4
■ Provisioning work ■ Connecting to a field wireless network
This subsection describes provisioning work using The action after installing the battery pack varies
FieldMate as the provisioning device. depending on the silence setting.
Provisioning work performs provisioning for each Mounting the battery pack automatically starts a
field wireless device using FieldMate and an search for the field wireless network. When the
infrared adapter. Field Wireless Integrated Gateway is found, the
If Yokogawa-recommended infrared device is instrument enters the join status. When the Field
used for provisioning, distance between the Wireless Integrated Gateway is not found and a
transmitter glass window and the infrared device specified time has elapsed, a cycle of a one-hour
should be within 30cm. For details of Yokogawa- pause and six-minutes search is repeated until the
recommended infrared device, refer to subsection instrument can join the field wireless network.
8.2 “Calibration Instruments Selection”. Perform the For details on the procedure to switch to silence
following provisioning tasks. mode, refer to subsection 7.3.17 “Switching to
Silence Mode.”
• Setting provisioning information
• Creating a provisioning information file
Mounting battery pack
1) Setting provisioning information
Set the device tag and network ID using a
Boot
FieldMate provisioning function. The device
tag, network ID, and join key are set in the field Provisioning Device
Silence mode OFF
Tool or Device
wireless device. It is not necessary to input Configuration Tool
a join key because FieldMate automatically Silence mode ON
generates it.
Deep Sleep Ready and
Setting device tag Ready(b)
(a) pause(b)
The device tag is used for the user to
recognize the Field Wireless Device. (Search start) (Search start)
(Search failure) (Search failure)
Setting network ID
This is the network ID for the field wireless
network to which the field wireless device is Confirm connecting
Device Configuration
status(c)
connected. Set a value from 2 to 65535. Tool
The field wireless device is connected to the (Disconnect)
field wireless network corresponding to the (Connect)
network ID set by provisioning work.
2) Creating a provisioning information file Join(d)
F0606.ai
The following provisioned information is stored
in the provisioning information file. Figure 6.6 Wireless Connection Process
IM 01C27H01-01EN
<6. Operation> 6-5
(b) Ready and pause 6.5 Shutting Down The
Transmitter
When shut down the transmitter, remove the battery
pack or set the transmitter to deep sleep mode by
the Device Configuration Tool.
NOTE
Whenever shutting down the transmitter for a
long period, detach the transmitter (diaphragm
F0608.ai
seals) from the tank
(c) Confirm connecting status • Refer to subsection 8.4.4 “Replacing the
Battery Pack” for the battery pack removing.
• When storing the instrument with a battery
pack inserted, it is recommended to put the
instrument into deep sleep mode to conserve
battery power. For details on how to switch to
deep sleep mode, refer to subsection 7.3.16
“Switching to the Deep Sleep Mode”.
F0609.ai
6.6 Venting or Draining
Transmitter Process-
(d) Join
Detector Section
If condensate (or gas) collects in the transmitter
process-detector section, the measured pressure
may be in error. If it is not possible to configure the
piping for self draining (or self-venting) operation,
you will need to loosen the drain (vent) screw on the
flushing connection ring to completely drain (vent)
any stagnated liquid (gas).
However, since draining condensate or bleeding off
F0610.ai
gas gives the pressure measurement disturbance,
this should not be done when the loop is in
operation.
NOTE
If the transmitter searches the Field Wireless WARNING
Network for long time at low ambient
temperature condition, sometimes error “AL.70 Since the accumulated liquid (or gas) may be
LOW.BAT” is displayed on the Integral Indicator. toxic or otherwise harmful, take appropriate care
Even though using new batteries, it can occur. It to avoid contact with the body, or inhalation of
occurs because of battery characteristics. vapors.
After joining to the Field Wireless Network, this
error will be cleared within one hour if battery has
no failure.
IM 01C27H01-01EN
<6. Operation> 6-6
6.6.1 Draining Condensate for Flushing
Connection Ring
1) Gradually open the drain screw to drain from
the flushing connection ring.(See figure 6.7.)
2) When the flushing connection ring is completely
drained, close the drain screw.
3) Tighten the drain screw to a torque of 10 N·m
{1 kgf·m}.
When you loosen the drain screw,
the accumulated liquid(or gas)
will be expelled in the direction of
the arrow.
Drain screw
F0611.ai
F0612.ai
IM 01C27H01-01EN
<7. Setting Parameters> 7-1
7. Setting Parameters
This transmitter can remotely handle range CF (Capabilities File)/DD (Device Description)
changes, Tag No. setup, monitoring of self-
A CF file contains information, such as the
diagnostic results, and zero point adjustment, etc.
vendor of the field device, its model and
according to communication with the field wireless
revision, available types of process data (flow
configuration tool or the device configuration tool.
rate, temperature, pressure, etc.), and number
of data items. A DD file contains the information
7.1 Environment for parameter on parameters, such as data structures and
attributes.
setting
DeviceDTM
After installing the battery pack, perform
provisioning and have the instrument join the field DeviceDTM (Device Type Manager), is driver
wireless network. software for field devices provided based on the
This transmitter supports the OOB (out-of-band) FDT (Field Device Tool) technology.
method using the infrared communication as a The field wireless configuration tool or the
provisioning method. device configuration tool allows confirming the
Refer to Subsection 6.4 “Connecting to the Field device information. For details on how to confirm
Wireless Network” for details of the provisioning. the device information using the field wireless
configuration tool or the device configuration tool,
refer to YFGW710 Field Wireless Integrated
Gateway (IM01W01F01-01EN).
Refer to Subsection 8.2 “Calibration Instruments
Selection” for the field wireless configuration
tool or the device configuration tool of our
recommendation.
Infrared port
7.2.2 Software Download
F0701.ai
Figure 7.1 Infrared port of the transmitter Software download function permits to update
wireless field device software via ISA100.11a
wireless communication. For details, refer to
7.2 Preparing Software YFGW710 Field Wireless Integrated Gateway (IM
01W01F01-01EN).
7.2.1 Softwares for the Field Wireless
Configuration Tool and the Device 7.3 Setting Parameters
Configuration Tool
Before using the device configuration tool,
7.3.1 Parameter Usage and Selection
confirm that CF/DD and DeviceDTM for your Before setting a parameter, please see the following
transmitter (wireless EJX) are installed in the device table for a summary of how and when each
configuration tool. parameter is used.
CF/DD and DeviceDTM are provided by DVD-ROM
attached to YFGW710 Field Wireless Integrated IMPORTANT
Gateway.
After setting and sending data with the field
Refer to YFGW710 Field Wireless Integrated
wireless configuration tool or the device
Gateway (IM 01W01F01-01EN) for details.
configuration tool, wait 30 seconds before
turning off the transmitter. If it is turned off
too soon, the settings will not be stored in the
transmitter.
IM 01C27H01-01EN
<7. Setting Parameters> 7-2
Table 7.1 Parameter Usage and Selection
Item Description
Tag No. Sets the tag No. as Device Tag (Software Tag). Sixteen characters
(alphanumeric characters, including - and •) can be set.
Output The process variable and the diagnostic result can be output.
Either or all of differential pressure (AI1:Process Value), static pressure
(AI2:Process Value), temperature(AI3:Process Value) of capsule or
amplifier and self-diagnostic information (UAPMO:Diagnostic Status) can
be set to the output
Range Adjust the range corresponding for 0% to 100%.
The unit of the range, input value at 0% (LRV) and input value at 100%
(URV) is set.
Note: LRV and URV can be set within the range of -32000 to 32000.
Damping time constant Adjust the output response speed for 0% to 100%.
It can be set within the range of 0.00 to 100.00 seconds.
The setting becomes invalid in the intermittent mode.
Output signal and integral indicator mode Sets mode for output signal and integral indicator to “linear mode”
(proportional to input differential pressure) or to “Square root mode”
(proportional to flow).
Output signal low cut mode Used mainly to stabilize output near 0 if output signal is the square root
mode. Two modes are available: forcing output to 0% for input below a
specific value, or changing to proportional output for input below a specific
value.
Integral indicator range of scale and unit Sets one of differential pressure/pressure value, static pressure value, or
temperature value for the integral indicator scale.
Note: LRV and URV can be set within the range of -32000 to 32000.
Unit for displayed temperature Sets a temperature unit to be displayed.
Unit for displayed static pressure Sets a pressure unit for the static pressure to be displayed
Direction of impulse piping connection Used where installation conditions makes it imperative to connect high
(which is high pressure, L side or R side) pressure side impulse line to low pressure side of transmitter.
Normally, correspond by replacing impulse line, and use this function only
when unavoidable.
Range with actual input applied Range corresponding for 0% to 100% signal is set with actual input
applied.
The output setting can be done just 100% to user’s reference pressure
output.
However, when shipping it, the calibration is done in high accuracy as for
DPharp. Please do the span setting by a usual range setting.
Zero Point Adjustment and Span Adjustment Handle Zero Point Adjustment and Span Adjustment.
There are two methods of Zero Point Adjustment, using external zero-
adjustment screw and using the device configuration tool.
Reset adjustment The amount of the adjustment set by user can be cleared.
Software write protect Prohibit writing the setting data.
Operational mode Set the operational mode of the sensor and integral indicator, etc.
Note: Some of the parameter settings are in the dialogue form called method, the on-line instructions you can configure the parameters
easily.
IM 01C27H01-01EN
<7. Setting Parameters> 7-3
7.3.2 Function Block and Menu Tree
F0802-1.ai
IM 01C27H01-01EN
<7. Setting Parameters> 7-4
Online Menu (continued)
(Simulate Valu)
•Simulate.Simulate Status
•Simulate.Simulate Value
(Scale)
•Scale.EU at 100% *
•Scale.EU at 0% *
•Scale.Units Index *
•Scale.Decimal *
F0702-2.ai
*: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).
**: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.
IM 01C27H01-01EN
<7. Setting Parameters> 7-5
Online Menu (continued)
(Simulate Value)
•Simulate.Simulate Status
•Simulate.Simulate Value
F0702-3.ai
*: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).
**: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.
IM 01C27H01-01EN
<7. Setting Parameters> 7-6
(Simulate Value)
•Simulate.Simulate Status
•Simulate.Simulate Value
(Scale)
•Scale.EU at 100% *
•Scale.EU at 0% *
•Scale.Units Index *
•Scale.Decimal *
*: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).
**: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.
IM 01C27H01-01EN
<7. Setting Parameters> 7-7
(2) Menu Tree
The menu tree of the device configuration tool of our recommendation is shown below. Refer to Subsection 8.2
“Calibration Instruments Selection” for the device configuration tool of our recommendation.
Online Menu (Device Configuration) (UAPMO) (Configuration)
•Device Configuration •UAPMO •Configure/Setup •UAP Option
•Diagnostic •TRANSDUCER •Hardware Write Protect
•Process Variable •AI1 DP •Static Revision
•AI2 SP •Reset Energy Left
•AI3 Temp •Radio Silence
(Identification)
•Version Revision
•CTS Version
•ITS Version
•Identification Number
(TRANSDUCER) (Block Info)
•Configure/Setup •Tag Description
(Configuration/Calibration)
•Auto Recovery
•Model
•Sensor Serial Number
•Measurement Rate
•Measurement Mode
•Wireless Status
•Display Selection
•LCD Mode
•Special Order ID
•Unit Sel1
•Display Unit1
•EJX Key
•Test Key 1
•Test Key 2
•Test Key 3
(Others)
•Special Cmd
(AI1 DP) (Block Info)
•Configure/Setup •Tag Description
(Block Mode)
(Block Mode)
•Mode.Target
•Mode.Target
•Mode.Actual
•Mode.Actual
•Mode.Permitted
•Mode.Permitted
•Mode.Normal
•Mode.Normal
(Configuration) (Scale)
•Block Mode •Scale.EU at 100% *
•Concentrator OID •Scale.EU at 0% *
•Scale * •Scale.Units Index *
•Process Value Filter Time •Scale.Decimal *
(Calibration) (Block Mode)
•Block Mode •Mode.Target
•Cal Cmd * •Mode.Actual
•Cal Status •Mode.Permitted
•Calibration Highest Point * •Mode.Normal
•Calibration Lowest Point *
•Calibration Minimum Span
•External Zero Trim *
(Others) (PV Range)
•Upper Limit •PV Range.EU at 100% *
•Lower Limit •PV Range.EU at 0% *
•PV Range * •PV Range.Units Index *
•Linerization Type * •PV Range.Decimal*
•Flow Constant *
•Lower cutoff
•Low Cut Mode *
•H/L Swap *
•T Zero Cmp *
•Temp Zero *
•Temp Select *
F0803-1.ai
*: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).
IM 01C27H01-01EN
<7. Setting Parameters> 7-8
Online Menu (continued) Device Configuration (continued)
(Block Mode)
•Mode.Target
•Mode.Actual
•Mode.Permitted
•Mode.Normal
(Scale)
•Scale.EU at 100% *
•Scale.EU at 0% *
•Scale.Units Index *
•Scale.Decimal *
(AI3 Temp)
(Block Info)
•Configure/Setup •Tag Description
(Block Mode)
•Mode.Target
•Mode.Actual
•Mode.Permitted
•Mode.Normal
(Scale)
•Scale.EU at 100% *
•Scale.EU at 0% *
•Scale.Units Index *
•Scale.Decimal *
*: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to O/S (Out of Service).
IM 01C27H01-01EN
<7. Setting Parameters> 7-9
Online Menu (continued)
(Power Status)
•Energy Left
•Power Supply Status
(Dynamic
(Process Variable) (AI1 DP) Variables) (Process Value)
•AI1 DP •Process Variable •Process Value •Process Value.Status
•AI2 SP •Simulation •Process Value.Value**
•AI3 Temp
(Simulation) (Transducer Value)
•Simulate Switch •Transducer Value.
•Transducer Value Transducer Status
•Simulate Value •Transducer Value.
Transducer Value
(Simulate Value)
•Simulate.
Simulate Status
•Simulate.
Simulate Value
(Dynamic
(AI2 SP) Variables) (Process Value)
•Process Variable •Process Value •Process Value.Status
•Simulation •Process Value.Value**
(Dynamic
(AI3 Temp) Variables) (Process Value)
•Process Variable •Process Value •Process Value.Status
•Simulation •Process Value.Value**
F0703-3.ai
**: When the data of these parameters is rewritten, it is necessary to set the operational mode of the block to Manual.
IM 01C27H01-01EN
<7. Setting Parameters> 7-10
7.3.3 Parameters for Wireless (6) LCD display mode
Communication TRANSDUCER block: LCD Mode
(1) Network Information 1. LCD Intermittent (On/Off of display)
When this parameter is selected, the LCD
Concentrator object block : Configuration
first displays a set of screens to be shown
Allows confirming the network information. and then turns off for a minute, and the
(2) Update Time display keeps the cycle repeatedly. Not
selecting this parameter turns the LCD off.
CO block : Data publication period 2. LCD Continue (On/Off of continuous display)
Sets the update time value to 1 to 3,600 When this parameter is selected, the LCD
seconds. The setting affects the battery life. displays for 5 minutes continuously then
When update time is set 0 seconds, the transits to the setting in the LCD Intermittent.
transmitter is stopped to update process 3. LCD Bargraph ON (On/Off of bargraph)
variables by way of the field wireless network. Select this parameter when the bargraph is
And the transmitter continues to measure required.
process variables with special interval time When the wireless connection process is in
internally. “ready” or “pause”, the LCD display stays on
(3) Measurement Mode regardless of the status in LCD mode.
IM 01C27H01-01EN
<7. Setting Parameters> 7-11
7.3.4 Tag and Device Information 7.3.6 Range Change
If these are specified when ordering, the designated The range values are factory-set as specified by
Tag No. and device information are set and the customer. To change the range, follow the steps
shipped. Tag No. and device information can be below.
checked as follows. The measurement span is determined by the upper
and lower range values. In this method, the upper
• Procedure to call up the tag No. and device
and lower range values can be set independently,
information
and the span changes according to the range limit
- Device Tag ( Software Tag ) values sent to the transmitter.
This is specified when writing characters (up
• Procedure to call up the PV Range display.
to 16 characters) of amplifiers TAG that differ
AI1, AI2 block : PV Range
from characters specified in Tag No.
Refer to section 7.4 “Connection to the Field Select the AI1 block for the differential pressure
Wireless Network” for confirmation. and the AI2 block for the static pressure, then
select “EU at 0%” and “EU at 100%” displayed
- Tag Description
in the PV Range parameters, and input the
This is a universal parameter to store the
lower range and upper range values for the
comment that describes the content of the
range, respectively.
tag located in the TRANSDUCER and AI
blocks.
7.3.7 Output Mode
The AI1, AI2, and AI3 blocks of the AI blocks
correspond to the differential pressure, static The output mode of the output signal can be set as
pressure, and temperature, respectively. No Linearization or Sq root.
• When changing the device information, input • Procedure to call up the Linearization Type
the information based on the following limitation display
on the number of characters. AI1, AI2 block : Linearization Type
- Message function (up to 32 characters) Select the AI1 block for the differential pressure
TRANSDUCER block : Tag Description and the AI2 block for the static pressure, and
AI1-AI3 block : Tag Description then select No Linearization or Sq root for the
Linearization Type parameter.
7.3.5 Unit
The unit parameter is set at the factory before
shipment if specified at the time of order. Follow the
procedure below to change the unit parameter.
• Procedure to call up the Unit display (Units
Index)
Al1 - Al3 block : Scale. Units Index
To change the Unit display, choose desired
unit among the list of displayed unit selecting
AI1 block as for the differential pressure, AI2
as for the static pressure and AI3 block as for
temperature in the AI blocks.
IM 01C27H01-01EN
<7. Setting Parameters> 7-12
7.3.8 Output Signal Low Cut Mode Setup The low cut point has hysterisis so that the output
around the point is behaved as below figure.
Low cut mode can be used to stabilize the output
signal near the zero point. <Example>
( There is 10% of hysteresis at only point of Output mode: Linear
transition from low to high.) Low cut mode: Zero
[Setup Low Cut Value] Low cut: 20.00%
Low
• Procedure to call up the Lower cutoff display cut
Output point
AI1 block : Lower cutoff
(20%)
Example: setup LOW_CUT of output to 15%
Lower cutoff 0%
Input 2%
= (“Eu at 100%” - “Eu at 0%”)* 0.15 + “Eu at 0%”
Setting range: Hystrersis fixed at 10%
[Setup Low Cut Mode] 0 to 20% of the cut point
• Procedure to call up the Low Cut Mode display F0705.ai
50
(%)
50
(%) Follow the procedure below to assign the high
pressure impulse line connection to the L side of the
Output
Output
transmitter.
20 Example: Low cut 20% 20 Example: Low cut 20%
• Procedure to call up the H/L Swap display
TRANSDUCER block : H/L Swap
0 Input 50 (%) 0 Input 50 (%)
Select Reverse among two choices ( Normal /
Reverse) in a H/L Swap parameter.
[ Linear output ]
Normal is chosen at the time of shipment.
For low cut in Linear mode
50
(%)
7.3.10 Integral Indicator Display Mode
Output
IM 01C27H01-01EN
<7. Setting Parameters> 7-13
7.3.11 Integral Indicator Scale Setup 7.3.12 Unit for Displayed Temperature
The following three displays are available for When the instrument is shipped, the temperature
the integral indictor: differential pressure, static units are set to C (Centigrade). Follow the
pressure, and temperature. The following three procedure below to change this setting.
variables can be displayed on the integral indicator:
• Procedure to call up the Sensor Range.Units
% of differential pressure range, % of static
Index display
pressure range, and % of temperature range.
AI3 block : Sensor Range.Units Index
Description Confirm that °C(deg C) is selected in the
Available displays
and related parameters
Sensor Range.Units Index parameter for the
% of range Indicates input pressure in –10 to
(PRES %) 110% range depending on the set temperature (AI3 block).
range (LRV and URV). Note: When the unit is changed by Sensor Range.Units Index
parameter in temperature ( Al3 block) , units of capsule
PRES % 45.6 %
temperature is also changed.
IM 01C27H01-01EN
<7. Setting Parameters> 7-14
7.3.14 Zero Point Adjustment and Span b. To match current input and output value,
Adjustment follow procedure
Each EJX-B Series Differential Pressure/Pressure Like tank level measurement that is impossible to
Transmitter is characterized by factory. But there set actual level to zero, output value is adjustment
are some errors caused by environment and to actual level by other measurement using
installed posture. glassgage.
There are Zero and Span Adjustments to fine-tune Example:
those errors. Differential Pressure and Pressure
Zero Adjustment is adjustment for one point to Transmitter’s span is 0 to 25.00kPa, current
adjust the bottom value of the measurement range level is 13.50kPa, current output is 13.83kPa.
as 0 % of output.
. • Procedure to call up the lower limit adjustment
The Span Adjustment defines input and output parameter (Calibration Lowest Point).
characteristic between two points that’s one side AI1 block : Calibration Lowest Point
.
assumed as standard.
Set the actual level value of 13.50 kPa to the
This is used when there is doubt of span drift or
Calibration Lowest Point parameter for the
when it is impossible to make zero at absolute
differential pressure (AI1 block). Apply an
pressure with adjustment for user’s pressure
actual input and confirm the value specified in
standard.
Calibration Lowest Point as the output value.
(1) Zero Point Adjustment
• Procedure to call up the calibration adjustment
parameter (Cal Cmd).
a. To set 0% at current input, perform
AI1 block : Cal Cmd : CAL_LOW
following procedure.
The present output is changed from 13.83 kPa
This method is used only when the pressure at
to 13.50 kPa in CAL_LOW of the differential
bottom of measurement range is zero.
pressure (AI1 block) Cal Cmd parameter.
• Procedure to call up the lower limit adjustment
• Procedure to call up the calibration status
parameter (Calibration Lowest Point).
parameter (Cal Status).
AI1 block : Calibration Lowest Point
AI1 block : Cal Status
Set 0 to Calibration Lowest Point parameter for
Confirm the value of CAL_SUCCESS (1) using
differential pressure (Al1 block).
the Cal Status parameter.
• Procedure to call up the calibration adjustment
DPharp span:0~25.00 kPa
parameter (Cal Cmd). Actual level:13.50 kPa 25.00 kPa
IM 01C27H01-01EN
<7. Setting Parameters> 7-15
c. Using External Zero-adjustment Screw • Procedure to call up the calibration adjustment
parameter (Cal Cmd).
External Zero-adjustment parameter (External
AI1 block : Cal Cmd : CAL_LOW
Zero Trim) can set permission or prohibition to
adjustment by External Zero-adjustment Screw. Confirm the lower limit of the measurement
range in CAL_LOW of the differential pressure
Set “Trim on” to use the External Zero-adjustment
(AI1 block) Cal Cmd parameter.
Screw. (“Trim on” at shipment)
• Procedure to call up the calibration status
Use a slotted screwdriver to turn the zero-
parameter (Cal Status).
adjustment screw. Equalize the transmitter, then
AI1 block : Cal Status
turn the screw clockwise to increase the output or
counterclockwise to decrease the output. The zero Confirm the value of CAL_SUCCESS (1) using
point adjustment can be made with a resolution the Cal Status parameter.
of 0.01% of the setting range. The degree of zero
• Procedure to call up the upper limit adjustment
adjustments varies with the screw turning speed;
parameter (Calibration Highest Point).
turn the screw slowly to make a fine adjustment,
AI1 block : Calibration Highest Point
quickly to make a rough adjustment.
Set the upper limit adjustment value for the
differential pressure (AI1 block) Calibration
Highest Point parameter. Apply a reference
pressure corresponding to the upper limit of the
measurement range to the differential pressure/
pressure transmitter and confirm the reference
pressure when it has stabilized.
• Procedure to call up the calibration adjustment
Zero-adjustment Screw parameter (Cal Cmd).
F0707.ai
AI1 block : Cal Cmd : CAL_HIGH
Figure 7.5 Zero-adjustment Screw Confirm the upper limit of the measurement
range in CAL_HIGH of the differential pressure
(AI1 block) Cal Cmd parameter.
(2) Span Adjustment
• Procedure to call up the calibration status
Span Adjustment is function to change the input and
parameter (Cal Status).
output characteristic that assumed the bottom value
AI1 block : Cal Status
(zero point) of measurement range a standard.
Therefore, perform span adjustment (adjustment Confirm the value of CAL_SUCCESS (1) using
of the upper limit value) after zero adjustment the Cal Status parameter.
(adjustment of bottom limit value).
(3) Adjustments for Static Pressure
After adding the pressure at point of adjustment and
For the EJX differential transmitters, zero point and
setting pressure value as parameter, the transmitter
span adjustments of static pressure is performed in
calculates quantity of adjustment and performs
the same way as with the primary process variable
adjustment automatically.
(PV).
• Procedure to call up the lower limit value Adjustment should be performed using the static
parameter (Calibration Lowest Point). pressure (AI2 block) Cal Cmd parameter. After
AI1 block : Calibration Lowest Point calibration, confirm the status by using the static
pressure (AI2 block) Cal Status.
Set the lower limit adjustment value on the
• Procedure to call up the calibration adjustment
differential pressure (AI1 block) Calibration
parameter (Cal Cmd).
Lowest Point parameter screen. Apply a
AI2 block : Cal Cmd
reference pressure corresponding to the
Perform differential pressure zero/span adjustment
lower limit of the measurement range to the
before static pressure zero/span adjustment.
differential pressure/pressure transmitter and
confirm the reference pressure when it has
stabilized.
IM 01C27H01-01EN
<7. Setting Parameters> 7-16
(4) Reset Adjustment • Procedure to call up the switch-to-deep-sleep
parameter
Reset Adjustment clear the amount of adjustment.
TRANSDUCER block : Special Cmd
Reset Ajustment can be performed using CAL_
CLEAR of the differential pressure (AI1 block) Cal Set Deep Sleep mode(Standby) to the Special
Cmd parameter for the input pressure and using Cmd parameter for the TRANSDUCER
CAL_CLEAR of the static pressure (AI2 block) Cal block. To start from deep sleep mode, either
Cmd parameter for the static pressure. After Reset remove and insert the battery pack, or using
Adjustment, confirm the status by using Cal Status the provisioning device tool or the device
of the cleared block. configuration tool via infrared communication.
The amount of adjustment made by the external
zero-adjustment screw can be reset to the initial
setting as well.
CAUTION
• Procedure to call up the calibration adjustment After setting the deep sleep mode by infrared
parameter (Cal Cmd). device configuration tool, keep the infrared port
AI1, AI2 block : Cal Cmd : CAL_CLEAR of device away from any other infrared signals.
IM 01C27H01-01EN
<7. Setting Parameters> 7-17
7.4 Self-Diagnostics UAPMO block : Diagnostic Status
Any of the four categories (Check function,
7.4.1 Identify Problems by Using the Maintenance required, Failure, and Off
Device Configuration Tool specification) according to NAMUR NE107* is
First, check Diagnostic Status of the self-diagnostic supplied to Diagnostic Status of each diagnostic
result. result.
Example
Bits Contents NAMUR NE107
Categorization
Bit31 (MSB) F: Failure status ---
Bit30 C: Function check status ---
Bit29 O: Out of specification status ---
Bit28 M: Maintenance required status ---
Bit27 Faults in electronics F
Bit26 Faults in sensor or actuator element F
Bit25 Installation, calibration problem C
Bit24 Out of service C
Bit23 Outside sensor limits O
Bit22 Environmental conditions out of device specification O
Bit21 Fault prediction: Maintenance required M
Bit20 Power is critical low: maintenance need short-term M
Bit19 Power is low: maintenance need mid-term M
Bit18 Software update incomplete C
Bit17 Simulation is active C
Bit16-Bit08 reserved by WCI ---
Bit07-Bit01 vendor specific area ---
Bit00 Detail information available ---
1: available
0: no available
Checking the Diagnostic Status category allows The contents of diagnostic status are defined either
taking the proper action. The Diagnostic Status valid or invalid at Diagnostic Switch parameter.
contents are common for all ISA devices, and the Follow the example below to change “Out of
setting for the Diagnostic Status category can be Service” to invalid.
changed. For further details, refer to Diagnostic
a) UAPMO block: UAP Option, select enable.
Status Detail.
b) UAPMO block: Diagnostic Switch, turn ON
In Diagnostic Status Contents that can be
Turn off “Out of Service”. Out of Service.
diagnosed by the EJX, the alert category set in Out
c) UAPMO block: UAP Option, select disable.
of Service can be changed to Check function. To do
Note: Be careful when changing the alert category and turning
so, follow one of the procedures below. detection on and off as described above. Be sure to set
UAP OPTION to disable again to prevent setting errors.
a) UAPMO block: UAP Option, select enable.
* NAMUR NE107 “Self-Monitoring and Diagnosis of Field
b) UAPMO block: Diagnostic Configuration, Devices”
change Out of Service from Failure to Check In Diagnostic Configuration setting, select one from the
function. followings; F: Failure status, C: Function check status, O:
Out of specification status, or M: Maintenance required
c) UAPMO block: UAP Option, select disable. status.
IM 01C27H01-01EN
<7. Setting Parameters> 7-18
Table 7.4 Diagnostic Results Summary
NAMUR
Diagnostic Status Contents NE107 Diagnostic Status Detail Description
Category
AMP_T_SENSOR_FAIL Amplifier temperature sensor failure
AMP_EEPROM_FAIL Amplifier EEPROM failure
AMP_EEP_IRREGULAR AMP EEPROM version not correct
AMP_F1_ERROR F1 error
Faults in electronics F G_A_COMM_FAIL G/A failure
FC_DELTA_T_FAIL C-side delta T circuit failure
FR_DELTA_T_FAIL R-side delta T circuit failure
Battery voltage not detected (AMP
WL_AD_FAIL
failure)
FC_SENSOR_FAIL C sensor frequency failure
FR_SENSOR_FAIL R sensor frequency failure
CAP_T_SENSOR_FAIL Capsule temperature sensor failure
Faults in sensor or actuator
F CAP_EEPROM_FAIL Capsule EEPROM failure
element
CAP_EEP_IRREGULAR CAP EEPROM version not correct
FC_UNOSC_FAIL C sensor oscillation stop failure
FR_UNOSC_FAIL R sensor oscillation stop failure
Pressure span adjustment variable
DP_TRIM_SPAN_OUTSIDE
outside of range
Pressure zero adjustment variable
DP_TRIM_ZERO_OUTSIDE
outside of range
Installation, calibration problem C Static pressure span adjustment
SP_TRIM_SPAN_OUTSIDE
variable outside of range
Static pressure zero adjustment
SP_TRIM_ZERO_OUTSIDE
variable outside of range
LCD_OUTSIDE_LIMIT LCD display outside of limits
AI1_OUT_OF_SERVICE AI1 O/S mode
Out of service O AI2_OUT_OF_SERVICE AI2 O/S mode
AI3_OUT_OF_SERVICE AI3 O/S mode
DP_OUTSIDE_LIMIT Pressure outside of range
SP_OUTSIDE_LIMIT Static pressure outside of range
Outside sensor limits C
CAPT_OUTSIDE_LIMIT Capsule temperature outside of range
AMPT_OUTSIDE_LIMIT Amplifier temperature outside of range
DP_OUTSIDE_RANGE Pressure setting outside of range
Environmental conditions out
O Static pressure setting outside of
of device specification. SP_OUTSIDE_RANGE
range
Power is critical low:
M WL_DEEPSLP_ALM Deep sleep due to low battery
maintenance need short-term.
Power is low:
M WL_LOWBAT_ALM Low battery
maintenance need mid-term
AI1_SIMULATION_ACTIVE AI1 Simulation mode
Simulation is active C AI2_SIMULATION_ACTIVE AI2 Simulation mode
AI3_SIMULATION_ACTIVE AI3 Simulation mode
IM 01C27H01-01EN
<7. Setting Parameters> 7-19
7.4.2 Checking with Integral Indicator
NOTE
If an error is detected by running self-diagnostics,
an error number is displayed on the integral
indicator. If there is more than one error, the error
number changes at three-second intervals. See
table 8.3 regarding the alarm codes.
F0708.ai
IM 01C27H01-01EN
<8. Maintenance> 8-1
8. Maintenance
8.1 Overview 8.3 Calibration
Use the procedure below to check instrument
WARNING operation and accuracy during periodic
maintenance or troubleshooting.
Since the accumulated process fluid may be
1) Insert the battery pack and then perform
toxic or otherwise harmful, take appropriate care
provisioning to have the transmitter join the
to avoid contact with the body or inhalation of
field wireless network or preparing the infrared
vapors when draining condensate or venting gas
communication for calibration.
from the transmitter pressure-detector section
and even after dismounting the instrument from 2) Set the update period to 1 second using
the process line for maintenance. the field wireless configuration tool to set
Continuous for the transmitter.
Maintenance of the transmitter is easy due to its 3) Connect the devices as shown in Figure 8.1
modular construction. This chapter describes the and allow the transmitter to warm up for at least
procedures for calibration, adjustment, and the 5 minutes.
disassembly and reassembly procedures required
for component replacement. IMPORTANT
Transmitters are precision instruments. Please
If the measurement range 0% point is 0 kPa
carefully and thoroughly read the following sections
or shifted in the positive direction (suppressed
for information on how to properly handle them
zero), the reference pressure should be applied
while performing maintenance.
as shown in the figure.
If the measurement range 0% point is shifted
IMPORTANT in the negative direction (elevated zero), the
• As a rule, maintenance of this transmitter reference pressure should be applied using a
should be done in a maintenance room that vacuum pump.
has all the necessary tools.
• The CPU assembly, RF assembly and 4) Apply reference pressures of 0%, 50%,
integral indicator contain sensitive parts that and 100% of the measurement range to the
can be damaged by static electricity. transmitter. Calculate the errors (differences
Take precautions such as using a grounded between the device configuration tool readings
wrist strap when handling electronic parts or and reference pressures) as the pressure is
touching the board circuit patterns. Also be increased from 0% to 100% and is decreased
sure to place the removed CPU assembly, from 100% to 0%, and confirm that the errors
RF assembly and integral indicator into a are within the required accuracy.
bag with an antistatic coating. (Note) When the output mode is set to “Sg root,” apply reference
pressures of 0, 6.25, 25, 56.25, and 100% instead.
IM 01C27H01-01EN
<8. Maintenance> 8-2
Table 8.1 Instruments Required for Calibration
Name Yokogawa-recommended Instrument Remarks
Provisioning • FieldMate (R2.02.01 or later)
device tool • Provisioning Device Tool
• Infrared Adapter certified by Yokogawa
Supplier: ACTiSYS
Product name: IrDA InfraRed USB Adaptor
Product number: IR224UN
Field wireless • Field Wireless Integrated Gateway attached Software
configuration Field Wireless Configurator
tool Field Wireless Management Tool
• Field Wireless System related Product
Plant Resource Manager (PRM) (R3.05 or later)
• Device Configuration Tool via Wireless Communication
FieldMate(R2.02.01 or later)
DeviceFile(R3.01.01 or later)
• Device Configuration Tool via Infrared Communication
FieldMate(R2.03.00 or later)
DeviceFile(R3.02.01 or later)
Digital Model MT220 precision digital manometer Select a manometer having
manometer 1) For 10 kPa class a pressure range close to
Accuracy: ±(0.015% of rdg + 0.015% of F.S.) for 0 to 10 kPa that of the transmitter.
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: ±0.02% of rdg . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
±5digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
3) For 700 kPa class
Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . . for 100 to 700 kPa
±5 digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits) . . . . . . . . . . for 0 to 3000 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ±(0.03% of rdg + 6 digits) . . . . . . . . . . . for 0 to 130 kPa abs
Pressure Model MC100 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25 Requires air pressure
generator kPa {2500 mmH2O} supply.
Accuracy: ±0.05% of F.S.
Dead weight gauge tester 25 kPa {2500 mmH2O} Select the one having a
Accuracy: ±0.03% of setting pressure range close to that
of the transmitter.
Pressure Model 6919 pressure regulator (pressure pump) Prepare the vacuum pump
source Pressure range: 0 to 133 kPa {1000 mmHg} for negative pressure
ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
or higher level, there may be difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa
representatives from which the instrument was purchased or the nearest Yokogawa office.
Mating If a pressure source
Pressure and a manometer
High pressure side calibration gauge
diaphragm seal flange are combined:
P
Pressure
source
Supply
P
Reference pressure
pressure Pressure
generator If a pressure
generator is used:
F0801.ai
IM 01C27H01-01EN
<8. Maintenance> 8-3
8.4 Disassembly and
Reassembly CAUTION
Always remove Battery pack and shut off
CAUTION pressures before disassembly and assembly.
Use proper tools for all operations.
Precautions for the intrinsic safety explosion
prevention type instrument
8.4.1 Replacing the Integral Indicator
Intrinsic safe type transmitters must be, as
This subsection describes the procedure for
a rule, removed to a non-hazardous area
replacing an integral indicator. (See figure 8.2)
for maintenance and be disassembled and
reassembled to the original state. Check and
■ Removing the Integral Indicator
confirm the insulation when it is reassembled to
the original state. 1) Remove the cover.
Check and confirm the insulation when it is 2) While supporting the integral indicator with one
reassembled to the original state. hand, loosen its two mounting screws.
Refer to section 2.7 “Insulation Resistance and 3) Dismount the integral indicator from the RF
Dielectric Strength Test” for details of Resistance assembly.
Test. When doing this, carefully pull the integral
indicator straight forward so as not to damage
the connector pins between it and the RF
IMPORTANT assembly.
■ Attaching the Integral Indicator
• Perform the provisioning when replacing the
RF assembly. Refer to 6.4 Connecting to the 1) Align both the integral indicator and RF
Field Wireless Network for details. assembly connectors and engage them.
• Replace the batteries and perform the 2) Insert and tighten the two mounting screws.
parameter settings when replacing the CPU 3) Replace the cover.
assembly. Refer to 8.4.5 Replacing the
Batteries. Power
cable
IM 01C27H01-01EN
<8. Maintenance> 8-4
8.4.2 Replacing the RF Assembly 4) Use a socket driver (width across flats, 5.5 mm)
to loosen the two bosses.
This subsection describes how to replace the RF
5) Carefully pull the CPU assembly straight
assembly (see Figure 8.2).
forward to remove it.
■ Removing the RF assembly 6) Disconnect the flat cable (cable with white
connector at the end) that connects the CPU
1) Remove the cover. assembly and the capsule.
2) Remove the integral indicator (refer to
subsection 8.4.1). NOTE
3) Remove the two stud bolts by using a socket
driver (width across flats: 5.5 mm). Be careful not to apply excessive force to the
4) Disconnect the RF assembly from the CPU CPU assembly when removing it.
assembly. When doing this, carefully pull the RF
assembly straight forward so as not to damage ■ Mounting the CPU assembly
the connector pins between it and the CPU
assembly. 1) Connect the flat cable (with white connector)
5) Disconnect the antenna cable that connects the between the CPU assembly and the capsule.
RF assembly and the antenna. 2) Connect the power cable (with brown
connector) to the CPU assembly.
NOTE
NOTE
Be careful not to apply excessive force to the
RF assembly and the connector of the antenna Make certain that the cables do not get pinched
cable when removing it. between the case and the edge of the CPU
assembly.
IM 01C27H01-01EN
<8. Maintenance> 8-5
8.4.4 Replacing the Battery Pack 8.4.5 Replacing the Batteries
The batteries in the battery pack can be replaced.
■ Removing
Batteries are not installed when shipped from the
1) Remove the terminal box cover. factory. Assemble the battery pack as follows.
2) Loosen the two battery pack mounting screws
(see Figure 8.3).
3) Pull out the Battery pack. WARNING
Be sure to replace the batteries or disassemble
and assemble the battery pack in a safe location.
Doing so in an explosive area could cause an
explosion.
■ Disassembling
Figure 8.3 Removing the Battery Pack
1) Loosen the two battery case mounting screws
(Figure 8.4).
■ Remounting
2) Separate the battery case into two parts.
1) Insert the new battery pack lightly. 3) Remove the old batteries.
2) Push the center of the battery pack and insert it
securely. ■ Assembling
3) Tighten the two battery pack mounting screws 1) Insert new batteries into the battery case. Be
to a torque of approximately 0.7 N·m. careful of the orientation of the batteries.
4) Replace the terminal box cover. 2) Attach the two parts of the battery case to each
5) Initialize the battery calculation. other.
How to initialize the battery calculation, refer 3) Tighten the two battery case mounting screws
to subsection 7.3.3 “Parameters for Wireless to a torque of approximately 0.7 N·m.
Communication”.
The battery pack mounting screws
cannot be separated from battery
pack so as to prevent drop-off.
F0804.ai
IM 01C27H01-01EN
<8. Maintenance> 8-6
8.4.6 Handling Batteries ■ Transportation of products containing
lithium batteries:
This battery pack uses two primary lithium/
thionyl chloride batteries. Each battery contains Batteries used for this transmitter contain
approximately 5 grams of lithium, for a total of 10 lithium. Primary lithium batteries are regulated
grams in each pack. Under normal conditions, in transportation by the U.S. Department of
the battery materials are self-contained and are Transportation, and are also covered by the
not reactive as long as the batteries and the pack International Air Transport Association (IATA), the
integrity are maintained. Care should be taken to International Civil Aviation Organization (ICAO), and
prevent thermal, electrical or mechanical damage. the European Ground Transportation of Dangerous
Protect the electrode of the battery pack to avoid Goods (ARD). It is the responsibility of the shipper
rapid electrical discharge. Discharged a battery may to ensure compliance with these or any other local
lead to fluid leakage and excessive heat. Batteries requirements. Consult current regulations and
should be stored in a clean and dry area. For requirements before shipping. When transporting
maximum battery life, storage temperature should this transmitter with the battery pack inserted, keep
not exceed 30°C. it in deep sleep mode in order to conserve battery
power. For details on how to switch to deep sleep
mode, refer to subsection 7.3.16 “Switching to Deep
WARNING Sleep Mode.”
Handling the battery pack ■ How to replace and dispose of the
The following precautions must be observed batteries:
in order to safely and effectively use a battery
This is an explanation about the new EU Battery
pack. Improper use may lead to fluid leakage,
Directive(DIRECTIVE 2006/66/EC). This directive is
excessive heat, ignition, or explosion.
only valid in the EU.
• Never charge it.
Batteries are used for in this product. When you
• Do not short-circuit it.
remove batteries from this product and dispose
• Do not disassemble, transform, or modify it.
them, discard them in accordance with domestic
• Do not heat it or throw it into a fire.
law concerning disposal.
• Do not soak it in fresh water or seawater.
Take a right action on waste batteries, because the
collection system in the EU on waste batteries are
regulated.
CAUTION Battery type: Primary lithium-thionyl chloride battery
Observe the following precautions for the safe
disposal of batteries.
• Do not incinerate the battery, and do not
expose it to a high temperature of 100°C CAUTION
or more. This may lead to fluid leakage or
explosion. The symbol (see above), which is marked on the
• Dispose of the battery according to laws and batteries, means they shall be sorted out and
regulations. collected as ordained in ANNEX II in DIRECTIVE
2006/66/EC.
Use the following dedicated parts for the battery
pack and batteries.
■ Procedure to remove the batteries safely:
■ Battery Pack
Part number: F9915NQ (with batteries) Refer to subsection 8.4.6 “Replacing the Battery
Part number: F9915NK (without batteries) Pack” and subsection 8.4.7 “Replacing the
Batteries.”
■ Batteries
Part number: F9915NR
Alternatively, Tadiran TL-5930/S batteries may
be purchased and used.
IM 01C27H01-01EN
<8. Maintenance> 8-7
8.5 Troubleshooting : Areas where self-diagnostic offers support
measurement system.
If the problem is in the measurement system,
isolate the problem and decide what corrective
action to take. YES Does problem exist in
receiving instrument?
This transmitter is equipped with a self-diagnostic
function which will be useful in troubleshooting,
NO
and the transmitter equipped with an integral Inspect receiver.
indicator will show an alarm code as a result of self-
diagnosis.
See subsection 8.5.3 for the list of alarms. Environmental conditions Transmitter itself
See also each communication manual.
Check/correct
Check transmitter.
environmental conditions.
Operating conditions
Check/correct operating
conditions.
F0805.ai
IM 01C27H01-01EN
<8. Maintenance> 8-8
8.5.2 Troubleshooting Flowcharts Output travels beyond 0% or 100%.
Are high
Does the self-diagnostic YES
and low pressure side NO
indicate problem location? diaphragm seals correctly
connected to the
process?
NO Refer to Alarm Message Summary in
Subsection 8.5.3. Correct the connections.
YES
YES
Is there any pressure leak?
NO
Is the liquid level as specified?
NO
Is the Field Wireless Network
setting correct? Is zero point NO
adjusted correctly?
IM 01C27H01-01EN
<8. Maintenance> 8-9
Does
the ambient
temperature significantly YES
differ between the high and low
pressure side
capillaries?
Are excess NO
capillaries secured?
Is transmitter
installed where there is YES
marked variation in
temperature?
Were appropriate NO
instruments used for
calibration?
NO
Is output adjusted correctly?
IM 01C27H01-01EN
<8. Maintenance> 8-10
8.5.3 Alarms and Countermeasures
Table 8.3 Alarms Message Summary (Causes and Actions)
Release/
Factory
recovery
Integral NAMUR Diagnostic
Bit Diagnostic Status Detail Cause conditions Action
indicator category Status
(except
restart)
FC_SENSOR_FAIL Recovers only
FR_SENSOR_FAIL when AUTO
RECOVER is
ON and within
the range
Pressure sensor
FC_UNOSC_FAIL Recovers only
failure
FR_UNOSC_FAIL when AUTO
Faults RECOVER
AL. 01 is ON and
in sensor or Replace the
CAP. ERR F Bit 26 oscillation does
actuator capsule.
(*2)
element not stop
CAP_T_SENSOR_FAIL Capsule None
temperature
sensor failure
CAP_EEPROM_FAIL Capsule Recovers
EEPROM when returns to
memory failure normal.
CAP_EEP_IRREGULAR None
AMP_T_SENSOR_FAIL Amplifier
AMP_EEPROM_FAIL temperature None
sensor failure
AL. 02 AMP_EEP_IRREGULAR
Faults in FC_DELTA_T_FAIL Replace the
AMP. ERR F Bit 27
electronics Amplifier amplifier.
(*2) FR_DELTA_T_FAIL None
EEPROM failure
AMP_F1_ERROR
G_A_COMM_FAIL
WL_AD_FAIL Amplifier failure None
DP_OUTSIDE_LIMIT Pressure Recovers when Check
AL. 10 outside of input pressure the input
PRESS specified range returns within pressure.
the range.
SP_OUTSIDE_LIMIT Static pressure Recovers when Check
AL. 11 outside of static pressure the input
ST. PRSS specified range returns within pressure.
the range.
CAPT_OUTSIDE_LMIT Capsule Recovers when Retain heat
temperature temperature or insulate
Outside sensor outside of range returns within so that
AL. 12 C Bit 23
limits (-50 to 130°C) the range. temperature
CAP. TMP
returns within
the specified
range.
AMPT_OUTSIDE_LIMIT Amplifier Recovers when Retain heat
temperature temperature or insulate
outside of range returns within so that
AL. 13
(-50 to 95°C) the range. temperature
AMP. TMP
returns within
the specified
range.
IM 01C27H01-01EN
<8. Maintenance> 8-11
Release/
Factory
recovery
Integral NAMUR Diagnostic
Bit Diagnostic Status Detail Cause conditions Action
indicator category Status
(except
restart)
DP_TRIM_SPAN_OUTSIDE Pressure span Recovers Check
adjustment when span the span
AL.53 variable outside adjustment adjustment
P. SDEV of range variable/point variable for
returns within the Pressure.
Installation,
the range.
C Bit 25 calibration
DP_TRIM_ZERO_OUTSIDE Pressure zero Recovers Check
problem
adjustment when zero the zero
AL.53 variable outside adjustment adjustment
P. ZDEV of range variable/point variable for
returns within the Pressure.
the range.
SP_TRIM_SPAN_OUTSIDE Static pressure Recovers Check
span adjustment when span the static
AL. 55 variable outside adjustment pressure
SP. SDEV of range variable /point span
returns within adjustment
the range. variable.
SP_TRIM_ZERO_OUTSIDE Static pressure Recovers Check
Installation,
zero adjustment when zero the static
C Bit 25 calibration
AL. 55 variable outside adjustment pressure zero
problem
SP. ZDEV of range variable/point adjustment
returns within variable.
the range.
LCD_OUTSIDE_LIMIT LCD display Recovers when Check the
AL. 79 outside of display value display
OV. DISP specified range returns within setting.
the range.
DP_OUTSIDE_RANGE Input pressure Recovers when Check the
AL. 30 setting outside setting returns input pressure
RANGE Environmental of range within the setting.
conditions out range.
O Bit 22
of device SP_OUTSIDE_RANGE Static pressure Recovers when Check
AL. 31 specification setting outside setting returns the static
SP. RNG of range within the pressure
range. setting.
Power is critical WL_DEEPSLP_ALM Low remaining
low: battery power
AL. 70 Replace the
M Bit 20 maintenance results in None
LOW. BAT batteries.
need short - switching to
term deep sleep.
Power is WL_LOWBAT_ALM Low remaining
AL. 70 low: battery power Replace the
M Bit 19 None
LOW. BAT maintenance batteries.
need mid - term
AI1_OUT_OF_SERVICE AI1 block is O/S Returns when Set the mode
AL. 60 mode. the mode target target to
AI OOS of AI1 block is AUTO.
other than O/S.
AI2_OUT_OF_SERVICE AI2 block is O/S Returns when Set the mode
AL. 61 mode. the mode target target to
C Bit 24 O/S
AI OOS of AI2 block is AUTO.
other than O/S.
AI3_OUT_OF_SERVICE AI3 block is O/S Returns when Set the mode
AL. 62 mode. the mode target target to
AI OOS of AI3 block is AUTO.
other than O/S.
IM 01C27H01-01EN
<8. Maintenance> 8-12
Release/
Factory
recovery
Integral NAMUR Diagnostic
Bit Diagnostic Status Detail Cause conditions Action
indicator category Status
(except
restart)
SimulationActive AI1 block is Returns when Check the
(AI1) simulate mode. the simulate simulate
AL. 63 mode of AI1 mode of AI1
AI SIM block is set block.
to disable. 1
Simulation is (Disable)
C Bit 17
active SimulationActive AI2 block is Returns when Check the
(AI2) simulate mode. the simulate simulate
AL. 64 mode of AI2 mode of AI2
AI SIM block is set block.
to disable. 1
(Disable)
SimulationActive AI3 block is Returns when Check the
(AI3) simulate mode. the simulate simulate
AL. 65 Simulation is mode of AI3 mode of AI3
C Bit 17 block is set block.
AI SIM active
to disable. 1
(Disable)
*1: “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off
specification) according to NAMUR NE107*.
*2: When the device detects "AL01 CAP.ERR" and "AL02 AMP.ERR", the LCD display stays on regardless of the status in LCD mode.
IM 01C27H01-01EN
<8. Maintenance> 8-13
Table 8.4 Alarm Message Summary (Output Actions)
Output actions
Factory
Integral Diagnostic Capsule Amp
NAMUR Bit Diagnostic Status Detail Static
Indicator Status Pressure Temp Temp
category Pressure
Value Value
FC_SENSOR_FAIL Output value Output value
FR_SENSOR_FAIL (hold value) (hold value)
FC_UNOSC_FAIL Output status Output status Normal action
(BAD: Sensor (BAD: Sensor
FR_UNOSC_FAIL
Failure) Failure)
CAP_T_SENSOR_FAIL Output value Output value Output value Normal action
(calculated in (calculated in (calculated in
Faults
AL. 01 a normal way) a normal way) a normal way)
in sensor or
CAP. ERR F Bit 26 Output status Output status Output status
actuator
(*2) (UNCERTAIN: (UNCERTAIN: (BAD: Sensor
element
Subnormal) Subnormal) Failure)
CAP_EEPROM_FAIL Output value Output value Output value Output value
(hold value) (hold value) (calculated in (calculated in
Output status Output status a normal way) a normal way)
CAP_EEP_IRREGULAR (BAD: Device (BAD: Device Output status Output status
Failure) Failure) (BAD: Device (BAD: Device
Failure) Failure)
AMP_T_SENSOR_FAIL Output value
(calculated in
a normal way)
Normal action Normal action Normal action
Output status
(BAD: Sensor
Failure)
AMP_EEPROM_FAIL Output value Output value Output value Output value
(hold value) (hold value) (calculated in (hold value)
Output status Output status a normal way) Output status
(BAD: Device (BAD: Device Output status (BAD: Device
AMP_EEP_IRREGULAR
Failure) Failure) (BAD: Device Failure)
Failure)
AL. 02
Faults in FC_DELTA_T_FAIL Output value Output value Output value
AMP.ERR F Bit 27
electronics (hold value) (hold value) (hold value)
(*2)
output status Output status output status
(BAD: Device (BAD: Device Normal action (BAD: Device
FR_DELTA_T_FAIL Failure) Failure) Failure)
IM 01C27H01-01EN
<8. Maintenance> 8-14
Output actions
Factory
Integral Diagnostic Capsule Amp
NAMUR Bit Diagnostic Status Detail Static
Indicator Status Pressure Temp Temp
category Pressure
Value Value
DP_OUTSIDE_LIMIT Output value Output value
(calculated in (calculated in
a normal way) a normal way)
AL. 10 Output status Output status
Normal action Normal action
PRESS (UNCERTAIN: (UNCERTAIN:
Sensor Subnormal)
Conversion
not Accurate)
SP_OUTSIDE_LIMIT Output value Output value
(calculated in (calculated in
a normal way) a normal way)
AL. 11 Output status Output status
Normal action Normal action
ST. PRSS (UNCERTAIN: (UNCERTAIN:
Subnormal) Sensor
Conversion
Outside sensor not Accurate)
C Bit 23
limits CAPT_OUTSIDE_LIMIT Output value Output value Output value
(calculated in (calculated in(calculated in
a normal way) a normal way) a normal way)
AL. 12 Output status Output status Output status
Normal action
CAP. TMP (UNCERTAIN: (UNCERTAIN: (UNCERTAIN:
Subnormal) Subnormal) Sensor
Conversion
not Accurate)
AMPT_OUTSIDE_LIMIT Output value
(calculated in
a normal way)
AL. 13 Output status
Normal action Normal action Normal action
AMP. TMP (UNCERTAIN:
Sensor
Conversion
not Accurate)
DP_TRIM_SPAN_ Output value
OUTSIDE (calculated in
a normal way)
AL. 53 Output status
Normal action Normal action Normal action
P. SDEV (UNCERTAIN:
Engineering
Unit Range
Violation)
Installation,
AL. 53 C Bit 25 calibration DP_TRIM_ZERO_
Normal action Normal action Normal action Normal action
P. ZDEV problem OUTSIDE
AL. 55 SP_TRIM_SPAN_
Normal action Normal action Normal action Normal action
SP. SDEN OUTSIDE
AL. 55 SP_TRIM_ZERO_
Normal action Normal action Normal action Normal action
SP.ZDEN OUTSIDE
LCD_OUTSIDE_LIMIT
AL. 79
Normal action Normal action Normal action Normal action
OV. DISP
IM 01C27H01-01EN
<8. Maintenance> 8-15
Output actions
Factory
Integral Diagnostic Capsule Amp
NAMUR Bit Diagnostic Status Detail Static
Indicator Status Pressure Temp Temp
category Pressure
Value Value
Power is WL_LOWBAT_ALM
low:
AL. 70
M Bit 19 maintenance Normal action Normal action Normal action Normal action
LOW. BAT
need
mid - term
AL. 60 AI1_OUT_OF_SERVICE
Normal action Normal action Normal action Normal action
AI OOS
AL. 61 AI2_OUT_OF_SERVICE
C Bit 24 O/S Normal action Normal action Normal action Normal action
AI OOS
AL. 62 AI3_OUT_OF_SERVICE
Normal action Normal action Normal action Normal action
AI OOS
AL. 63 SimulationActive
Normal action Normal action Normal action Normal action
AI SIM (AI1)
AL. 64 Simulation is SimulationActive
C Bit 17 Normal action Normal action Normal action Normal action
AI SIM active (AI2)
AL. 65 SimulationActive
Normal action Normal action Normal action Normal action
AI SIM (AI3)
*1: “Factory NAMUR category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off
specification) according to NAMUR NE107*.
* NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”
*2: When the device detects "AL01 CAP.ERR" and "AL02 AMP.ERR", the LCD display stays on regardless of the status in LCD mode.
IM 01C27H01-01EN
<9. Parameter Summary> 9-1
9. Parameter Summary
Table 9.1 Parameter
Object Attribute Default
Label Description Handling
ID ID value
1. 1 Version Revision Indicates the application revision of EJX This revision --- R
UAPMO when the application software is downloaded.
block 10 Static Revision Indicates the revision level of the fixed parameters of 0 R
UAP Used, for example, to check whether parameters
have been change.
64 Identification Indicates the vender ID, model ID, and revision of the --- R
Number device.
65 CTS Version Indicates the version of the communication stack test 0 R
system (CTS).
66 ITS Version Indicates the version of the inter operability test system 0 R
(ITS).
67 Diagnostic Status Indicates the diagnostic results of the device based on 0 R
the NAMUR NE0107* model.
Setting Diagnostic Status to ON allows turning OFF
and ON the display of the diagnostic results for each
summary, and changing Categorize For Categorize at
the time of shipment, refer to tables 7.3 and 9.2.
68 UAP Option Allows setting the Diagnostic Status and write protection 0 W
of UAP.
Enable diagnostic status configuration
1: Enable, 0: Disable (default)
Enable hardware write protect
1: Enable, 0: Disable (default)
Software write protect
1: On, 0: Off
The following table shows the relationship between the
hardware write protection and software write protection.
Enable
Hardware Software
hardware Write
write write
write protect
protect protect
protect
Disable Off or On Off No
Disable Off or On On Protected
Enable Off Off or On No
Enable On Off or On Protected
69 Diagnostic Switch Allows setting On/Off for each summary of Diagnostic 0 W
Status when UAP Option is set to Enable and Diagnostic
Status is set to Enable.
70 Diagnostic Allows Categorize for each summary of Diagnostic Refer to Table W
Configuration Status when UAP Option is set to Enable and Diagnostic 9.2.
Status is set to Enable.
102 Diagnostic Status Detailed information on Diagnostic Status. For Refer to Table R
Detail [2] Categorize at the time of shipment, refer to Table 9.2. 9.2.
103 Energy Left Indicates the number of days of remaining battery life --- R
assuming ambient temperature condition as 23 degrees
Celsius.
The unit is day.
104 Reset Energy Left Initialize the remaining battery life (Energy Left) and 0 (reading value W
reset it as new batteries. is always 0)
Perform the battery replacement.
0 = Continue
1 = Reset
105 Power Supply Indicates the battery level and the power supply R
Status method.
0 = external power supply
1 = battery level 75% or more
2 = battery level 25% ~ 75%
3 = battery level 25% or less
IM 01C27H01-01EN
<9. Parameter Summary> 9-2
Object Attribute Default
Label Description Handling
ID ID value
1.UAPMO 110 Hardware Write Allows recognizing the status of the hardware write R
block Protect protection switch.
(continued) (Switch Off, Switch On)
111 Radio Silence Repeats a cycle of a 1-hour pause and 6-minute 28800 W
search if the instrument cannot join the network after a
time specified in Radio Silence has elapsed.
2. 2 DESCRIPTION Indicates the version and model information of the --- R
UDO downloaded data.
block 3 STATE Indicates the present transition state. --- R
5 MAX_BLOCK_ Maximum block size. This value is smaller than the --- R
SIZE maximum data size of APDU.
14 LAST_BLOCK_ Indicates the last downloaded block number. --- R
DOWNLOADED 0 means that no block has been downloaded.
16 ERROR_CODE Indicates the error codes for DLError. --- R
0 = noError
1 = Timeout
2 = ClientAbort
64 = Apply failure
3. 1 REVISION Indicates the version level of COMM_ENDPOINT, etc. --- R
CO 2 COMM_ Indicates the Endpoint information. The following --- W
block ENDPOINT shows the components.
1. Network address of remote endpoint
2. Transport layer port at remote endpoint
3. Object ID at remote endpoint
4. Stale data limit
5. Data publication period
6. Ideal publication phase
7. PublishAutoRetransmit
8. Configuration status
3 COMM_ Indicates the Contract information. The following --- R
CONTRACT shows the components.
1. ContractID
2. Contract_Status
3. Actual_Phase
4 PUB_ITEM_MAX Maximum PUB_ITEM value --- R
5 PUB_ITEM_NUM PUB_ITEM number --- R
6 PUB_ITEM Indicates the PUB_ITEM information. The following --- W
shows the components
1. ObjectID
2. AttributeID
3. AttributeIndex
4. Size
4. 1 Tag Description Memo field available to write anything. Transducer W
TRANSDUCER 2 Auto Recovery Allows specifying the action when the cause of a ON W
block sensor failure is removed.
OFF (=0): AL continues to be indicated
even after the cause of the sensor
error is removed, and the BURN
OUT state is not released.
ON (=1): The AL indication for sensor
failure disappears and normal
action is resumed when the cause
of the sensor failure is removed.
3 Model Indicates the model name of the transmitter. --- R
4 Sensor Serial Indicates the device number of the transmitter. --- R
Number
5 Measurement Indicates the measurement period of process values. --- R
Rate
IM 01C27H01-01EN
<9. Parameter Summary> 9-3
Object Attribute Default
Label Description Handling
ID ID value
4. 6 Measurement Measurement mode selects continuous mode or intermittent W
TRANSDUCER Mode intermittent mode. mode
block When the update time is set to 1 in intermittent mode,
(continued) the mode is automatically switched to continuous
mode.
When the update time is set to 1 second, the
computation process is in continuous mode,
regardless of the measurement mode.
7 Wireless Status Indicate the communication status. 1. idle status R
1. Indicates the initial idle status or join status. 2. not
(idle status, join status) estabilishment
2. Indicates whether Contract(Pub) is established. 3. not
(not establishment, establishment) esabilishment
3. Indicates whether Contract(R/W) is
established.
(not establishment, establishment)
8 Display Selection Select the LCD display contents. 1. displayed W
1. Indicates display status of PV Value of AI1 2. not
(displayed, not displayed) displayed
2. Indicates display status of PV Value of AI2 3. not
(displayed, not displayed) displayed
3. Indicates display status of PV Value of AI3
(displayed, not displayed)
9 LCD Mode Select the LCD mode 1. OFF W
1. Indicates the ON mode. (off, intermittent) 2. continuous
2. Indicates whether continuous or not. OFF
(continuous off, continuous on) 3. bar graph
3. Indicates the bar graph display. not displayed
(bar graph not displayed, bar graph displayed)
10 Special Cmd Special function parameter. 0 W
0 = initialize value at READ (None)
1 = EJX does not use.
2 = deep sleep status
To start from deep sleep mode, either remove and
insert the battery pack, or the provisioning device
tool or the device configuration tool via infrared
communication.
11 Special Order ID Displays the special order number, if applicable. --- R
12 Unit Sel1 Selects whether to automatically apply the unit to the Auto W
word for the parameter for which the unit display is
selected, or apply the characters that are written to
Display Unit1. (Auto, Custom)
13 Display Unit1 When Custom is selected in Unit Sel1, set the display NULL W
unit using 6 characters or less.
5. 1 Process Value AL1 is a pressure output object. 1. Value = --- W
AI1 block Indicates the primary analog value (or corresponding 2. Status = ---
process value) and status used to execute this
function.
Allows updating data by specifying this for the
Concentrator object.
1. Value: output value of Al object
2. Status: Specify output status of Al object.
2 Block Mode A universal parameter to indicate the block’s operation 1. W
status. Each O/S, Auto, and Man can select from. Target=O/S
1. Target : Specify Al object mode. 2.
2. Actual : Indicates current mode of Al object. Actual=O/S
3. Permitted : Indicates the mode selected by 3.
Target of Al object. Permitted=
4. Normal : Indicate normal status mode of Al O/S
object. 4.
Normal=O/S
IM 01C27H01-01EN
<9. Parameter Summary> 9-4
Object Attribute Default
Label Description Handling
ID ID value
5. 3 Concentrator OID Indicates the Concentrator object value that 3 R
AI1 corresponds to the data update of the PV value.
block 4 Scale Allows specifying the upper or lower limit for the PV 1. EU at 100% W
(continued) scaling, unit code, etc. = 100
1. EU at 100% : Indicate the upper limit of the PV 2. EU at 0%
value. =0
2. EU at 0% : Indicate the lower limit of the PV value. 3. Units Index
3. Units Index : Indicate the setting unit used for the =%
PV value. 4. Decimal = 2
4. Decimal : Indicate the digit number below the
decimal point displayed in the LCD indicator.
26 Tag Description A universal parameter to store the comment that Al1: W
describes the tag Differential
Pressure
27 Process Value Allows adjusting the time constant for filtering the PV 0 sec W
Filter Time value. Setting unit: Second. This is enabled for the
Continuous mode.
28 Simulate Switch A simulation function switch for the AI object test 1 (Disable) W
(Disable, Enable)
29 Transducer Value When Simulate Switch is set to Disable, this value Disable R
is used as the input value for the AI object. Refer to
Figure 9.1.
30 Simulate Value When Simulate Switch is set to Enable, this value is --- W
used as the input value for the AI object.
The input value can be changed.
51 Upper Limit Indicates the upper limit (URL) for the pressure. --- R
52 Lower Limit Indicates the lower limit (LRL) for the pressure. --- R
53 PV Range Sets the measurement range. EU at 100% W
1. EU at 100% : Indicates input value of the upper = 100
limit. EU at 0%
2. EU at 0% : Indicates input value of the lower limit. =0
3. Units Index : Indicates the units of the Units Index
measurement range. = kPa (1133)
4. Decimal : Indicates the digit number below the Decimal
decimal point. =2
54 Linearization Type Select either No Linearization or Square root as a 0 W
setting of the output range.
0 = No Linearization :
Provides an output value scaled according to the
PV Range and Scale range settings.
(To use Direct with FF, set the same value for PV
Range and Scale)
10 = Square root :
Provides a square root output computed for the
value scaled according to the PV Range and Scale
range settings.
55 Flow Constant Indicates the flow coefficient, which shows the 1.0 W
correlation between the flow rate value and square root
value of the differential pressure.
56 Lower cutoff Specifies the low cut value. The unit is subject to 10 W
Scale.Units Index.
IM 01C27H01-01EN
<9. Parameter Summary> 9-5
Object Attribute Default
Label Description Handling
ID ID value
5. 57 Cal Cmd Specifies the calibration method. 0 (reading W
AI1 0 = CAL_NONE : Initial state in which calibration is value is
block not performed always 0)
(continued) 1 = CAL_LOW : Applies an actual input and adjusts
the lower limit using the value specified in
Calibration Lowest Point.
2 = CAL_HIGH : Applies an actual input and adjusts
the higher limit using the value specified in
Calibration Highest Point.
5 = CAL_CLEAR : Clears the adjustment variable.
58 Cal Status Indicates the calibration status. --- R
0 = CAL_NONE : Start-up and default value
1 = CAL_SUCCESS : Indicates that calibration was
successful.
7 = CAL_BAD_TRIM_POINT : Indicates this status
when the adjustment variable is outside of range.
59 Calibration Highest Specifies the higher limit adjustment variable for --- W
Point adjustment between two points.
60 Calibration Lowest Specifies the lower limit adjustment variable for the --- W
Point adjustment between two points.
61 Calibration Indicates the minimum span of the adjustment --- R
Minimum Span variable.
104 External Zero Trim Allows performing external zero adjustment. Trim on W
(Trim on, Trim off)
105 Low Cut Mode Specifies the low cut mode. Linear W
(Linear, Zero)
106 H/L Swap Allows performing reverse connection of the impulse Normal W
line.
(NORMAL, REVERSE : reverse connection)
Used when the lower pressure side and higher
pressure side of the impulse line were connected
wrongly when installing the pressure transmitter.
107 T Zero Cmp Parameter to select the temperature zero shift Off w
compensation mode
0 = OFF : Does not perform temperature zero shift
compensation.
1 = ON : Performs temperature zero shift
compensation.
108 Temp Zero Parameter to set the temperature gradient value for the 0 w
temperature zero shift compensation
109 Temp Select Parameter to select the temperature (amplifier-side 1 w
/ capsule-side) used for the temperature zero shift
compensation.
0 = AMP TEMP : the value of the amplifier-side
temperature sensor is used.
1 = CAP TEMP : the value of the capsule-side
temperature sensor is used.
IM 01C27H01-01EN
<9. Parameter Summary> 9-6
Object Attribute Default
Label Description Handling
ID ID value
6. 1 Process Value AI2 is a static pressure output object. --- W
AI2 Indicates the primary analog value (or corresponding
block process value) and status used to execute this
function.
Allows updating data by specifying this for the
Concentrator object.
1. Value: output value of Al object
2. Status: Specify output status of Al object.
2 Block Mode A universal parameter to indicate the block’s operation 1.Target W
status. O/S, Auto, and Man can be selected. = O/S
1. Target : Specify Al object mode. 2.Actual
2. Actual : Indicates current mode of Al object. = O/S
3. Permitted : Indicates the mode selected by Target 3.Permitted
of Al object. = O/S
4. Normal : Indicate normal status mode of Al object. 4.Normal
= O/S
3 Concentrator OID Indicates the Concentrator object value that 3 R
corresponds to the data update of the PV value.
4 Scale Allows specifying the upper or lower limit for the PV 1. EU at 100% W
scaling, unit code, etc. = 100
1. EU at 100% : Indicate the upper limit of the PV 2. EU at 0%
value. =0
2. EU at 0% : Indicate the lower limit of the PV value. 3. Units Index
3. Units Index : Indicate the setting unit used for the =%
PV value. 4. Decimal
4. Decimal : Indicate the digit number below the =2
decimal point displayed in the LCD indicator.
26 Tag Description A universal parameter to store the comment that AI2: Static W
describes the tag. Pressure
27 Process Value Allows adjusting the time constant for filtering the PV 0 sec W
Filter Time value. Setting unit: Second. This is enabled for the
Continuous mode.
28 Simulate Switch A simulation function switch for the AI object test Disable W
(Disable, Enable)
29 Transducer Value When Simulate Switch is set to Disable, this value is --- R
used as the input value for the AI object.
30 Simulate Value When Simulate Switch is set to Enable, this value is --- W
used as the input value for the AI object.
The input value can be changed.
51 Upper Limit Indicates the upper limit (URL) for the pressure. --- R
52 Lower Limit Indicates the lower limit (LRL) for the pressure. --- R
53 PV Range Sets the measurement range. 1. EU at W
1. EU at 100% : Indicates input value of the upper 100% =
limit. 25000.000000
2. EU at 0% : Indicates input value of the lower limit. EU at 0%
3. Units Index : Indicates the units of the =0
measurement range. Units Index
4. Decimal : Indicates the digit number below the = kPa
decimal point. Decimal
=2
IM 01C27H01-01EN
<9. Parameter Summary> 9-7
Object Attribute Default
Label Description Handling
ID ID value
6. 54 Linearization Type Select either No Linearization or Square root as a 0 W
AI2 setting of the output range.
block 0 = No Linearization :
(continued) Provides an output value scaled according to the
PV Range and Scale range settings.
(To use Direct with FF, set the same value for PV
Range and Scale.)
55 Flow Constant Indicates the flow coefficient, which shows the 1.0 W
correlation between the flow rate value and square root
value of the pressure.
56 Lower cutoff Specifies the low cut value. The unit is subject to 10 W
Scale.Units Index.
57 Cal Cmd Specifies the calibration method. 0 (reading W
0 = CAL_NONE : Initial state in which calibration is value is
not performed always 0)
1 = CAL_LOW : Applies an actual input and adjusts
the lower limit using the value specified in
Calibration Lowest Point.
2 = CAL_HIGH : Applies an actual input and adjusts
the higher limit using the value specified in
Calibration Highest Point.
5 = CAL_CLEAR : Clears the adjustment variable.
58 Cal Status Indicates the calibration status. R
0 = CAL_NONE : Start-up and default value
1 = CAL_SUCCESS : Indicates that calibration was
successful.
7 = CAL_BAD_TRIM_POINT : Indicates this status
when the adjustment variable is outside of range.
59 Calibration Highest Specifies the higher limit adjustment variable for --- W
Point adjustment between two points.
60 Calibration Lowest Specifies the lower limit adjustment variable for the --- W
Point adjustment between two points.
61 Calibration Indicates the minimum span of the adjustment --- R
Minimum Span variable.
102 Static Process Selects the gauge pressure or the absolute pressure. Abs W
Type
103 SP Select Parameter to select the High-side pressure or the Low- High W
side pressure as the static pressure output.
0 = High : Displays the H-side pressure as the static
pressure
1 = Low : Displays the L-side pressure as the static
pressure
IM 01C27H01-01EN
<9. Parameter Summary> 9-8
IM 01C27H01-01EN
<9. Parameter Summary> 9-9
AI algoritm
IM 01C27H01-01EN
<10. General Specifications> 10-1
2400 - 2483.5 MHz license free ISM band Zero Adjustment Limits
Zero can be fully elevated or suppressed, within
Radio security the lower and upper range limits of the capsule.
AES 128 bit codified External Zero Adjustment
RF Transmitter power External Zero is continuously adjustable with
0.01% incremental resolution of span. Re-range
Max. 11.6 dBm (fixed)
can be done locally using the digital indicator
Antenna with range-setting switch.
+2 dBi Omni directional monopole type Integral Indicator (LCD display)
5-digit numerical display, 6-digit unit display and
Span and range limits
bar graph.
EJX118B The indicator is configurable to display one
Measurement
or up to three of the following variables
kPa inH2O(/D1) mbar(/D3) mmH2O(/D4)
Span/Range periodically.; Differential pressure, static
M
Span 2 to 100 8 to 400 20 to 1000 200 to 10000 pressure, temperature.
Range –100 to 100 –400 to 400 –1000 to 1000 –10000 to 10000
Span 10 to 500 40 to 2000 100 to 5000 0.1 to 5 kgf/cm2 Self Diagnostics
H
Range –500 to 500 –2000 to 2000 –5000 to 5000 –5 to 5 kgf/cm2 Capsule failure, amplifier failure, configuration
T01E.ai
error, battery alarm, wireless communication
EJX438B alarm and over-range error for process
Measurement
variables.
MPa psi (/D1) bar (/D2) kgf/cm2 (/D3)
Span and Range
Capillary Fill Fluid Density Compensation
Span 0.035 to 3.5 5 to 500 0.35 to 35 0.35 to 35
A*1
Range –0.1 to 3.5 –14.5 to 500 –1 to 35 –1 to 35
Compensation of the zero shift by the ambient
Flush Span 0.16 to 16 23 to 2300 1.6 to 160 1.6 to 160 temperature effect on the capillary tube.
type*1 Range –0.1 to 16 –14.5 to 2300 –1 to 160 –1 to 160
B Ambient Temperature Limits
Extended Span 0.16 to 7 23 to 1000 1.6 to 70 1.6 to 70
type*1 Range
-40 to 85°C (-40 to 185°F)
–0.1 to 7 –14.5 to 1000 –1 to 70 –1 to 70
T02E.ai -30 to 80°C (-22 to 176°F) LCD visible range
*1: Measurement range is within the flange rating. Note: The ambient temperature limits must be within the fill fluid
operating temperature range, see table 10.1.
Performance specifications
Refer to GS01C27 B01-01EN Process Temperature Limits
See table 10.1.
Output
Wireless (ISA100.11a protocol) 2.4 GHz signal. Ambient Humidity Limits
Output mode for EJX118B, linear or square 0 to 100% RH
root, is selectable. Working Pressure Limits
See table 10.1.
For atmospheric pressure or below, see figure
10.1 and 10.2.
IM 01C27H01-01E
<10. General Specifications> 10-2
Table 10.1 Process temperature, Ambient temperature, and Working pressure
Code Process temperature*1 Ambient temperature*2 Working pressure Specific gravity*3
–10 to 250°C *4 –10 to 60°C
Silicone oil (general use) A 1.07
(14 to 482°F) (14 to 140°F)
2.7 kPa abs
–30 to 180°C –15 to 60°C (0.38 psi abs) to
Silicone oil (general use) B 0.94
(–22 to 356°F) (5 to 140°F) flange rating pressure
*1: See figure 10-1 and 10-2 ‘Working Pressure and Process Temperature.
*2: This ambient temperature is the transmitter ambient temperature.
*3: Approximate values at a temperature of 25°C (77°F)
*4: In case of wetted parts material code TW (Tantalum), process temperature limit is up to 200°C (392°F).
Note: The differential pressure transmitter should be installed at least 600 mm below the high pressure (HP) process connection.
However, this value (600 mm) may be affected by ambient temperature, operating pressure, fill fluid or material of the wetted
diaphragm. Contact YOKOGAWA when the transmitter can not be installed at least 600 mm below the HP process connection..
2.7 (0.38)
2.7 (0.38)
1 (0.14)
1(0.14)
0.1(0.014)
0.1(0.014) -50 0 50 100 150 200 250 300 350
-50 0 50 100 150 200 250 300 350 Process Temperature (°C)
F02E.ai
Process Temperature (°C)
F01E.ai
Figure 10.1 Working Pressure and Process Figure 10.2 Working Pressure and Process
Temperature (Fill fluid : silicone oil for Temperature (Fill fluid : fluorinated
general and high temperature use) oil for oil-prohibited use and ethylene
glycol for low temperature use)
IM 01C27H01-01E
<10. General Specifications> 10-3
Process connections Housing
See the following table. Low copper cast aluminum alloy with
polyurethane, mint-green paint (Munsell
Table 10.2 Flange size and rating
5.6BG 3.3/2.9 or its equivalent)
Process
Size Flange
connection style Degrees of Protection
3-inch
JIS 10K, 20K, 40K, 63K*2 IP66/IP67, NEMA4X
ANSI Class 150, 300, 600
Flush type 2-inch
JPI Class 150, 300, 600 Name plate and tag
11/2-inch*1
DIN PN10/16, 25/40, 64 304 SST tag plate wired onto transmitter
JIS 10K, 20K, 40K*2
4-inch ANSI Class 150, 300 Diaphragm seal section:
Extended type
3-inch JPI Class 150, 300 Process Flange
DIN PN10/16, 25/40
JIS S25C, JIS SUS304, or JIS SUS316
High pressure JIS 10K, 20K
Combination type
side: 4-inch ANSI Class 150, 300 Capillary tube
(Extended and
Flush)*3
Low pressure JPI Class 150, 300 316 SST
side: 3-inch DIN PN10/16, 25/40
Protection tube
T07E.ai
IM 01C27H01-01E
<10. General Specifications> 10-4
10.2 Model and Suffix Codes
Instruction
The model and suffix codes for EJX118B and EJX438B consist of two parts; a transmitter body section (I) and
a diaphragm seal section (II). This specification sheet introduces these two parts separately. The transmitter
body section is shown in one table, and the diaphragm seal section specifications are listed according to the
process connection style. First select the model and suffix codes of transmitter body section and then continue
on one of the diaphragm seal section.
EJX118B
EJX438B
The “►” marks indicate the most typical selection for each specification.
*1: When specified process connection style code E, maximum range and span are 7 MPa (1000 psi.)
*2: Applicable for EJX118B
*3: Applicable for EJX438B
IM 01C27H01-01E
<10. General Specifications> 10-5
II. Diaphragm seal section (Flush type)
EJX118B 3
W
EJX438B 2
F07E.ai
EJX438B
EJX118B
EJX118B . . . . . . . . . . . . . . . . . . . . Transmitter body section (I)
EJX438B
Process connection style -W . . . . . . . . . . . . . . . . . . . . . Flush type
Flange rating J1 . . . . . . . . . . . . . . . . . . . . JIS 10K
J2 . . . . . . . . . . . . . . . . . . . . JIS 20K
J4 . . . . . . . . . . . . . . . . . . . . JIS 40K
J6 . . . . . . . . . . . . . . . . . . . . JIS 63K –
A1 . . . . . . . . . . . . . . . . . . . . ANSI class 150 P1 . . . . . . . . . JPI class 150
A2 . . . . . . . . . . . . . . . . . . . . ANSI class 300 P2 . . . . . . . . . JPI class 300
A4 . . . . . . . . . . . . . . . . . . . . ANSI class 600 P4 . . . . . . . . . JPI class 600
D2 . . . . . . . . . . . . . . . . . . . . DIN PN10/16
D4 . . . . . . . . . . . . . . . . . . . . DIN PN25/40
D5 . . . . . . . . . . . . . . . . . . . . DIN PN64
The “►” marks indicate the most typical selection for each specification. Example: EJX118B-LMSCG-97JDN-WA13B1SW00-BA25/□
EJX438B-LASCG-97JDN-WA13B1SW00-BA25/□
*1: See table 10-3 ‘Gasket contact surface.’
*2: When specified flushing connection ring code 1, 2, A, or B, exclusive gasket is provided for transmitter side.
*3: In case of wetted parts material code TW (Tantalum), the process temperature limit is –10 to 200˚C.
*4: Wetted parts material code TW (Tantalum) cannot be applied.
*5: Even in case where fill fluid code D (fluorinated oil) is selected, if degrease cleansing treatment or both degrease cleansing and
dehydrating treatment for the wetted parts is required, specify option code K1 or K5.
IM 01C27H01-01E
<10. General Specifications> 10-6
*6: In case of wetted parts material code HW (Hastelloy C), TW (Tantalum), and UW (Titanium) for 2-inch pressure flange, specify
capillary length from 1 to 5 m.
*7: Not applicable for flashing connection ring code 1 and 2.
*8: Not applicable for gasket contact surface code 1.
*9: Hastelloy C-276 or N10276.
*10: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant
facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid
can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite,
and high-temperature steam (150˚C [302˚F] or above). Contact Yokogawa for detailed information of the wetted parts material.
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316
SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details
IM 01C27H01-01E
<10. General Specifications> 10-7
II. Diaphragm seal section (Flush type)
Process connection size: 1 1/2-inch (40 mm)
EJX118B
W 8
EJX438B
F08E.EPS
EJX438B
EJX118B
EJX118B Transmitter body section (I)
....................
EJX438B
Process connection style -W . . . . . . . . . . . . . . . . . . Flush type
Flange rating J1 . . . . . . . . . . . . . . . . . JIS 10K
J2 . . . . . . . . . . . . . . . . . JIS 20K
J4 . . . . . . . . . . . . . . . . . JIS 40K
A1 . . . . . . . . . . . . . . . . . ANSI class 150
A2 . . . . . . . . . . . . . . . . . ANSI class 300
A4 . . . . . . . . . . . . . . . . . ANSI class 600
P1 . . . . . . . . . . . . . . . . . JPI class 150
P2 . . . . . . . . . . . . . . . . . JPI class 300
P4 . . . . . . . . . . . . . . . . . JPI class 600
Process connection size 8................. 1 1/2-inch (40 mm)
(Process flange size)
Flange material A............... JIS S25C
►B............... JIS SUS304
C............... JIS SUS316
Gasket contact surface*1 1.............. Serration (for ANSI flange only)
2.............. Flat (no serration)
Wetted parts material*5 [Diaphragm] [Others]
SW . . . . . . . . . . . JIS SUS316L JIS SUS316L
Flushing connection ring*2 [Ring] [Drain/Vent plugs] [Material]
3............ Reducer type R 1/4 connections*4 JIS SUS316 # –
4............ Reducer type 1/4 NPT connections JIS SUS316 # –
C............ Reducer type R 1/4 connections*4 JIS SUS316 # –
D............ Reducer type 1/4 NPT connections JIS SUS316 # –
The “►” marks indicate the most typical selection for each specification. Example: EJX118B-LMSCG-97JDN-WA18B1SW40-BA25/□
EJX438B-LASCG-97JDN-WA18B1SWD0-BA25/□
*1: See table 10-3 ‘Gasket contact surface.’
*2: When specified flushing connection ring code 3, 4, C, or D, exclusive gasket is provided for transmitter side.
*3: Even in case where fill fluid code D (fluorinated oil) is selected, if degrease cleansing treatment or both degrease cleansing and
dehydrating treatment for the wetted parts is required, specify option code K1 or K5.
*4: Not applicable for gasket contact surface code 1.
*5: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant
facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid
can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite,
and high-temperature steam (150˚C [302˚F] or above). Contact Yokogawa for detailed information of the wetted parts material.
IM 01C27H01-01E
<10. General Specifications> 10-8
II. Diaphragm seal section (Extended type)
EJX118B 4
E
EJX438B 3
F09E.EPS
EJX438B
EJX118B
EJX118B
Transmitter body section (I)
EJX438B
....................
Process connection style -E . . . . . . . . . . . . . . . . . . Extended type
Flange rating J1 . . . . . . . . . . . . . . . . . JIS 10K
J2 . . . . . . . . . . . . . . . . . JIS 20K
J4 . . . . . . . . . . . . . . . . . JIS 40K –
A1 . . . . . . . . . . . . . . . . . ANSI class 150
A2 . . . . . . . . . . . . . . . . . ANSI class 300
P1 . . . . . . . . . . . . . . . . . JPI class 150
P2 . . . . . . . . . . . . . . . . . JPI class 300
D2 . . . . . . . . . . . . . . . . . DIN PN10/16
D4 . . . . . . . . . . . . . . . . . DIN PN25/40
Process connection size 4................. 4-inch (100 mm)
(Process flange size) 3................. 3-inch (80 mm)
Flange material A............... JIS S25C
► B............... JIS SUS304
C............... JIS SUS316
Gasket contact surface*1 1.............. Serration (for ANSI flange only)
2.............. Flat (no serration)
Wetted parts material*4 [Diaphragm] [Pipe] [Others]
SE . . . . . . . . . . . . JIS SUS316L JIS SUS316 JIS SUS316
Flushing connection ring 0............ None
Extension 1........... Length (X2) = 50 mm –
2........... Length (X2) = 50 mm –
3........... Length (X2) = 100 mm –
4........... Length (X2) = 100 mm –
5........... Length (X2) = 150 mm –
6........... Length (X2) = 150 mm –
Fill fluid [Process temp.] [Ambient temp.]
-A . . . . . . . . . For general use (silicone oil) –10 to 250°C –10 to 60°C
► -B . . . . . . . . . For general use (silicone oil) –30 to 180°C –15 to 60°C
-C . . . . . . . . . For high temperature use (silicone oil) 10 to 310°C 10 to 60°C
-D . . . . . . . . . For oil-prohibited use (fluorinated oil)*2 –20 to 120°C –10 to 60°C
-E . . . . . . . . . For low temperature use (ethylene glycol) –50 to 100°C –40 to 60°C
Capillary connection B........ Back of diaphragm seal unit
— 2....... Always 2
Capillary length*3 1..... 1m
2..... 2m
3..... 3m
4..... 4m
5..... 5m
6..... 6m
7..... 7m
8..... 8m
9..... 9m
A..... 10 m
Option codes / Optional specification
T12E.ai
The “►” marks indicate the most typical selection for each specification. Example: EJX118B-LMSCG-97JDN-EA14B1SE02-BB25/□
EJX438B-LASCG-97JDN-EA14B1SE01-BB25/□
*1: See table 10-3 ‘Gasket contact surface.’
*2: Even in case where fill fluid code D (fluorinated oil) is selected, if degrease cleansing treatment or both degrease cleansing and
dehydrating treatment for the wetted parts is required, specify option code K1 or K5.
*3: The specified capillary length includes the extension length (X2) and the flange thickness (t).
*4: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant
facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid
can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite,
and high-temperature steam (150˚C [302˚F] or above). Contact Yokogawa for detailed information of the wetted parts material.
IM 01C27H01-01E
<10. General Specifications> 10-9
Process connection size: High pressure side; 4-inch (100 mm) • • • Extended type
Low pressure side; 3-inch (80 mm) • • • Flush type
EJX118B Y W
F10E.EPS
The “►” marks indicate the most typical selection for each specification. Example: EJX118B-LMSCG-97JDN-YA1WB1SY01-BC25/□
*1: See table 10-3 ‘Gasket contact surface.’
*2: Even in case where fill fluid code D (fluorinated oil) is selected, if degrease cleansing treatment or both degrease cleansing and
dehydrating treatment for the wetted parts is required, specify option code K1 or K5.
*3: The specified capillary length of high pressure side (extended side) includes the extension length (X2) and the flange thickness (t).
*4: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant
facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid
can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite,
and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
IM 01C27H01-01E
<10. General Specifications> 10-10
10.3 Optional Specifications
OPTIONAL SPECIFICATIONS (For Explosion Protected type)
IM 01C27H01-01E
<10. General Specifications> 10-11
OPTIONAL SPECIFICATIONS (Others)
Item Description Code
Color change Amplifier cover only P
Painting
Coating change Anti-corrosion coating *1 X2
Oil-prohibited use Degrease cleansing treatment K1
Oil-prohibited use
Degrease cleansing treatment and dehydrating treatment K5
with dehydrating treatment
P calibration (psi unit) D1
(See table for Span and
Calibration units *3 bar calibration (bar unit) Range Limits.) D3
M calibration (kgf/cm2 unit) D4
Diaphragm protection from sticky process fluid by FEP Teflon film attached with
Teflon film *2 *7 fluorinated oil. TF1
Operation range: 20 to 150°C, 0 to 2 MPa (Not applicable for vacuum service).
Operating temperature correction *4 Adjusting range : 80°C to Maximum temperature of specified fill fluid R
Capillary without PVC sheaths When ambient temperature exceeds 100°C, or use of PVC is prohibited V
Inside of isolating diaphragms (fill fluid side) are gold plated, effective for hydrogen
Gold-plated diaphragm *5 permeation. A1
Pressure test/
JIS 20K, 40K, 63K 3.5 MPa (500 psi)
For
EJX438B
JIS 40K *8 10 MPa (1450 psi) T57
JIS 40K *9 7 MPa (1000 psi) T55
JIS 63K *8 16 MPa (2300 psi) T58
ANSI/JPI Class 150 3 MPa (435 psi) T52
ANSI/JPI Class 300 *8 8 MPa (1160 psi) T56
ANSI/JPI Class 300 *9 7 MPa (1000 psi) T55
ANSI/JPI Class 600 *8 16 MPa (2300 psi) T58
T14E.ai
IM 01C27H01-01E
<10. General Specifications> 10-12
10.4 Dimensions
<Transmitter body section> Unit: mm (approx. inch)
For EJX118B For EJX438B
Zero adjustment 191 (7.52)
122 (4.80)
24
(0.94)
40
(1.57) Integral indicator 39 64
(1.54) (2.52)
331 (13.03)
Ø110 (4.33)
181 (7.13)
472 (18.58)
211 (8.31)
140 Open to
Ground terminal
(3.58)
(5.51) atmosphere
91
Ø5 (0.20)
Mounting bracket
(Flat-type, optional)
2-inch pipe
(O. D. 60 mm)
<Diaphragm seal section>
Flush type
No ring (Flushing connection ring code 0) With ring
(EJX118B: Flushing connection ring code 1, 2, 3, and 4)
(EJX438B: Flushing connection ring code A, B, C, and D)
k
Diaphragm seal j*1
t
t 25*1
(0.98) Flushing*5 f*3*4
n-øh
f*3*4 connection ring
(4.41)
112*6
ød*2 ød*2
øg
øD
øC
øg
øD
øC
n-øh
Capillary Capillary
length length
Drain/vent plug
Spiral Spiral
ø44
ød
gasket gasket
IM 01C27H01-01E
<10. General Specifications> 10-13
Unit: mm (approx. inch)
14(0.55)
øA 4 100(3.94)
6 150(5.91)
X2
(4.72)
120
f*3*4
t
n-øh
Capillary
ø30 length*1
(ø1.18)
øD
øC
øg
14(0.55)
t 25
n-øh (0.98)
øA f*3*4
n-øh
ød*2
X2
(4.72)
f*3*4
120
øD
øC
øg
t
ø30 Capillary
(ø1.18) length*1
Capillary
length
F12E.ai
IM 01C27H01-01E
<10. General Specifications> 10-14
Unit: mm (Approx.: inch)
Process flange size: 4 inch (100 mm)
*3 *4 Bolt holes
Code Flange rating øD øC øg ød t f j k øA
No.(n) Dia.(øh)
J1 JIS 10K 210 (8.27) 175 (6.89) 155 (6.10) — 18 (0.71) 0 8 19 (0.75) — — 96±0.5 (3.78±0.02)
J2 JIS 20K 225 (8.86) 185 (7.28) 155 (6.10) — 24 (0.94) 0 8 23 (0.91) — — 96±0.5 (3.78±0.02)
A1 ANSI class 150 228.6 (9.00) 190.5 (7.50) 155 (6.10) — 23.9 (0.94) 1.6 (0.06) 8 19.1 (0.75) — — 96±0.5 (3.78±0.02)
A2 ANSI class 300 254 (10.00) 200.2 (7.88) 155 (6.10) — 31.8 (1.25) 1.6 (0.06) 8 22.4 (0.88) — — 96±0.5 (3.78±0.02)
P1 JPI class 150 229 (9.02) 190.5 (7.50) 155 (6.10) — 24 (0.94) 1.6 (0.06) 8 19 (0.75) — — 96±0.5 (3.78±0.02)
P2 JPI class 300 254 (10.0) 200.2 (7.88) 155 (6.10) — 32 (1.26) 1.6 (0.06) 8 22 (0.87) — — 96±0.5 (3.78±0.02)
D2 DIN PN10/16 220 (8.66) 180 (7.09) 155 (6.10) — 20 (0.79) 0 8 18 (0.71) — — 96±0.5 (3.78±0.02)
D4 DIN PN25/40 235 (9.25) 190 (7.48) 155 (6.10) — 24 (0.94) 0 8 22 (0.87) — — 96±0.5 (3.78±0.02)
*1: When wetted parts material code UW (titanium) is selected, value is 34 (1.34).
*2: Indicates inside diameter of gasket contact surface.
*3: In case where process flange material is JIS S25C, value of f is 0.
*4: In case where process flange material is JIS SUS304 in ANSI/JPI flange, value of f is included in t.
T15E.ai
IM 01C27H01-01E
<10. General Specifications> 10-15
Infrared Configuration
Infrared port
F13E.ai
IM 01C27H01-01E
i
Revision Information
Title : EJX118B and EJX438B
Diaphragm Sealed Differential Pressure and Pressure Transmitters
Manual No. : IM 01C27H01-01EN
IM 01C27H01-01EN