Caracteristicas XT
Caracteristicas XT
Caracteristicas XT
1 Notes
1 Rated operational current: Making and breaking conditions to DC-13, L/R constant as stated.
2 IEC 60947 Standard.
1 3 Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30.
90
90
90
1
°
180°
1
1
Ambient temperature 1
Open –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C
[–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F]
1
Enclosed –25 to 40°C –25 to 40°C –25 to 40°C –25 to 40°C
[–13 to 104°F] [–13 to 104°F] [–13 to 104°F] [–13 to 104°F]
Ambient storage temperature –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C
1
[–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F]
Environmental
1
Mechanical shock resistance (IEC/EN 60068-2-27) 1
Half-sinusoidal shock 10 ms
Main contact—NO contact 10g 10g 10g 10g 1
Auxiliary contact—NO contact 7g 7g 7g 7g
Auxiliary contact—NC contact 5g 5g 5g 5g
1
Overvoltage category/pollution degree III/3 III/3 III/3 III/3
1
XT Contactors—Frames C–D
1 Description XTCE018C XTCE025C XTCE032C XTCE040D XTCE050D XTCE065D, XTCE072D
1 General
Standards IEC/EN 60947, IEC/EN 60947, IEC/EN 60947, IEC/EN 60947, IEC/EN 60947, IEC/EN 60947,
1 VDE 0660, UL, CSA,
CCC, RoHS
VDE 0660, UL, CSA,
CCC, RoHS
VDE 0660, UL, CSA,
CCC, RoHS
VDE 0660, UL, CSA,
CCC, RoHS
VDE 0660, UL, CSA,
CCC, RoHS
VDE 0660, UL, CSA,
CCC, RoHS
Weights in kg [lb]
1 AC operated 0.42 [0.93] 0.42 [0.93] 0.42 [0.93] 0.9 [2.0] 0.9 [2.0] 0.9 [2.0]
1 DC operated 0.48 [1.06] 0.48 [1.06] 0.48 [1.06] 1.1 [2.4] 1.1 [2.4] 1.1 [2.4]
Mechanical life—operations 10,000,000 10,000,000 10,000,000 10,000,000 10,000,000 10,000,000
1 Mechanical operating frequency (ops/hr)
AC operated 5000 5000 5000 5000 5000 5000
1 DC operated 5000 5000 5000 5000 5000 5000
Notes
1 1 IEC 60947 Standard.
2 Damp heat, constant, to IEC 60068-2-78; damp heat, cyclic, to IEC 60 068-2-30.
90
90
90
90
90
1
°
°
180°
180°
1
1
Ambient temperature
Open –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C
1
[–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F]
Enclosed –25 to 40°C –25 to 40°C –25 to 40°C –25 to 40°C –25 to 40°C –25 to 40°C
1
[–13 to 104°F] [–13 to 104°F] [–13 to 104°F] [–13 to 104°F] [–13 to 104°F] [–13 to 104°F]
Ambient storage temperature –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C 1
[–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F]
Environmental 1
Mechanical shock resistance
(IEC/EN 60068-2-27) 1
Main contact—NO Contact 10 10 10 10 1 1
Auxiliary contact—NO Contact 7 7 7 7 7 7
1
Auxiliary contact—NC Contact 5 5 5 5 5 5
1
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3
XT Contactors—Frames F–G
1 Description XTCE080F XTCE095F XTCE115G XTCE150G XTCE170G
1 General
Standards IEC/EN 60947, IEC/EN 60947, IEC/EN 60947, IEC/EN 60947, IEC/EN 60947,
VDE 0660, UL, CSA, VDE 0660, UL, CSA, VDE 0660, UL, CSA, VDE 0660, UL, CSA, VDE 0660, UL, CSA,
1 CCC, RoHS CCC, RoHS CCC, RoHS CCC, RoHS CCC, RoHS
Weights in kg [lb]
1 AC operated 2 [4.41] 2 [4.41] 2 [4.41] 2 [4.41] 2 [4.41]
DC operated 2.1 [4.63] 2.1 [4.63] 2.1 [4.63] 2.1 [4.63] 2.1 [4.63]
1 Mechanical life—operations 10,000,000 10,000,000 10,000,000 10,000,000 10,000,000
Mechanical operating frequency (ops/hr)
1 AC operated 3600 3600 3600 3600 3600
1 DC operated
Electrical mechanical operating frequency (ops/hr)—
3600 3600 3600 3600 3600
1 Climatic proofing 2 2 2 2 2
1 Impulse withstand voltage (U imp) Vac 8000 8000 8000 8000 8000
Operational voltage (U e) Vac 690 690 690 690 690
1 Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between coil and contacts (Vac) 690 690 690 690 690
1 Between contacts (Vac) 690 690 690 690 690
Making capacity (amps) 1120 1330 1610 2100 2100
1 Breaking capacity (amps)
220/230V 800 950 1150 1500 1500
1 380/400V 800 950 1150 1500 1500
500V 800 950 1150 1500 1500
1 660/690V 650 800 1100 1200 1320
1000V — — — — —
1 Short-circuit protection rating maximum fuse
1 Type 2 coordination 1
400V; gG/gL 500V 160 160 250 25 400
1 Nm
Lb-in
14
123.9
14
123.9
14
123.9
14
123.9
14
123.9
1 Notes
1 IEC 60947 Standard.
1 2 Damp heat, constant, to IEC 60068-2-78; damp heat, cyclic, to IEC 60 068-2-30.
°
90
90
90
90
°
1
180°
180°
1
1
Ambient temperature
Open –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C 1
[–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F]
Enclosed –25 to 40°C –25 to 40°C –25 to 40°C –25 to 40°C –25 to 40°C 1
[–13 to 104°F] [–13 to 104°F] [–13 to 104°F] [–13 to 104°F] [–13 to 104°F]
Ambient storage temperature –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C 1
[–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F]
Environmental 1
Mechanical shock resistance
(IEC/EN 60068-2-27) 1
Half-sinusoidal shock 10 ms
Main contact—NO contact 10g 10g 10g 10g 10g 1
Auxiliary contact—NO contact 7g 7g 7g 7g 7g
Auxiliary contact—NC contact 5g 5g 5g 5g 5g
1
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3
1
1
XT Contactors—Frames H–M
1 XTCE250L, XTCE300L, XTCE400M XTCE500M, XTCE570M
Description XTCE185H XTCE225H XTCS250L XTCS300L XTCS400M XTCS500M XTCS570M
1 General
1 1000V; gG/gL 1000V 160 160 160 160 200 200 200
Degree of protection IP00 IP00 IP00 IP00 IP00 IP00 IP00
1 Protection against direct contact when Finger and back-of-hand proof with terminal shroud or terminal block
actuated from front (IEC 536)
Busbar—width in mm 32 32 25 25 25 30 30
1 Main cable connection screw/bolt M10 M10 M10 M10 M10 M10 M10
Tightening torque
1 Nm 24 24 24 24 2 2 2
Notes
1 1 IEC 60947 Standard.
2 Damp heat, constant, to IEC 60068-2-78; damp heat, cyclic, to IEC 60 068-2-30.
1 3 Screw tightening with flat cable terminal or cable terminal blocks. See terminal capacity for cable terminal blocks.
1
1
1
90
°
180°
1
1
Ambient temperature –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C
1
[–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F]
Ambient storage temperature –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C 1
[–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F]
Environmental 1
Mechanical shock
Resistance (IEC/EN 60068-2-27) 1
Half-sinusoidal shock 10 ms
Main contact—NO contact 10g 10g 10g 10g 10g 10g 10g 1
Auxiliary contact—NO contact 10g 10g 10g 10g 10g 10g 10g
Auxiliary contact—NC contact 8g 8g 8g 8g 8g 8g 8g 1
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3
Switching capacity, kVAR 1 1
Individual compensation
230V — — — — — — — 1
400/420/440V — — — — — — —
525V 220 220 — 307 — — — 1
690V 133 133 — 177 — — —
Group compensation, with choke
1
230V — — 100 — 160 160 160
400/420/440V — — 190 — 280 280 280
1
525V — — 260 — 370 370 370
1
690V — — 340 — 480 480 480
Note 1
1 When using contactors for group compensation, a minimum inductance of approx. 6 uh per capacitor must be available to limit the high
inrush current peaks. This corresponds to an air-cored coil with five windings and a coil diameter of approximately 140 mm. The conductor
cross-section must be selected according to the rated current per phase.
1
1
1
1
1
XT Contactors—Frames N–R
1 XTCE750N, XTCEC16R,
Description XTCE580N XTCE650N XTCE820N XTCEC10N XTCEC14P XTCEC20R
1 General
Insulation voltage (Ui) Vac 1000 1000 1000 1000 1000 1000
1 Impulse withstand voltage (Uimp) Vac 8000 8000 8000 8000 8000 8000
1 Operating voltage (Ue) Vac 1000 1000 1000 1000 1000 1000
Safe isolation to VDE 0106 Part 101 and Part 101/A1
1 Between coil and contacts (Vac) 500 500 500 500 500 500
Between contacts (Vac) 500 500 500 500 500 500
1 Making capacity (amps) 7800 7800 9840 9840 9840 19000, 9840
Breaking capacity (amps)
1 220/230V 6500 6500 8200 8200 8200 16000, 8200
Busbar—width in mm 50 50 50 50 50 50
1 Main cable connection screw/bolt M10 M10 M12 M12 M12 M1
Tightening torque
1 Nm 24 24 35 35 35 35
Lb-in 213 213 311 311 311 311
1
Notes
1 1 IEC 60947 Standard.
2 Damp heat, constant, to IEC 60068-2-78; damp heat, cyclic, to IEC 60 068-2-30.
3 Screw tightening with flat cable terminal or cable terminal blocks. See terminal capacity for cable terminal blocks.
1
90
°
1
180°
1
1
Ambient temperature –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C –25 to 60°C
[–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F] [–13 to 140°F] 1
Ambient storage temperature –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C –40 to 80°C
[–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F] [–40 to 176°F]
1
Environmental
Mechanical shock resistance (IEC/EN 60068-2-27) 1
Half-sinusoidal shock 10 ms (g)
Main contact—NO contact 10 10 10 10 10 10 1
Auxiliary contact—NO contact 10 10 10 10 10 10
Auxiliary contact—NC contact 8 8 8 8 8 8
1
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 1
Switching capacity, kVAR 1
Individual compensation 1
230V 175 — — — — —
400/420/440V 300 — — — — —
1
525V 400 — — — — —
1
690V 300 — — — — —
Note 1
1 When using contactors for group compensation, a minimum inductance of approx. 6 uh per capacitor must be available to limit the high
inrush current peaks. This corresponds to an air-cored coil with five windings and a coil diameter of approximately 140 mm. The conductor
cross-section must be selected according to the rated current per phase.
1
1
1
1
1
1
1
1 Pickup (x Uc)
AC operated 0.8–1.1 0.8–1.1 0.8–1.1 0.8–1.1 0.8–1.1 0.8–1.1 0.8–1.1 0.8–1.1 0.8–1.1 0.8–1.1
1 DC operated 0.8–1.1 1 0.8–1.1 1 0.8–1.1 1 0.8–1.1 1 0.7–1.2 2 0.7–1.2 2 0.7–1.2 2 0.7–1.2 2 0.7–1.2 2 0.7–1.2 2
Dropout (x Uc)
1 AC operated 0.3–0.6 0.3–0.6 0.3–0.6 0.3–0.6 0.3–0.6 0.3–0.6 0.3–0.6 0.3–0.6 0.3–0.6 0.3–0.6
DC operated 0.15–0.6 0.15–0.6 0.15–0.6 0.15–0.6 0.15–0.6 0.15–0.6 0.15–0.6 0.15–0.6 0.15–0.6 0.15–0.6
1 Power Consumption of the Coil at Cold State and 1.0 x Uc
1 AC operated
Single-voltage coil 50 Hz
1 AC operated
Closing delay (ms) <21 <21 <21 <21 <22 <22 <22 <18 <18 <18
1 Opening delay (ms) <18 <18 <18 <18 <14 <14 <14 <13 <13 <13
DC operated
1 Closing delay (ms) <31 <31 <31 <31 <47 <47 <47 <54 <54 <54
Opening delay (ms) <12 <12 <12 <12 <30 <30 <30 <24 <24 <24
1 Arcing time (ms) 10 10 10 10 10 10 10 10 10 10
1 Notes
1 0.7–1.3 without additional auxiliary contact modules and ambient temperature +40°C [104°F].
2 Coil Suffix TD: U
min 24 Vdc/Umax 27 Vdc.
1 Coil Suffix WD: Umin 48 Vdc/Umax 60 Vdc.
Coil Suffix AD: Umin 110 Vdc/Umax 130 Vdc.
Coil Suffix BD: Umin 200 Vdc/Umax 240 Vdc.
1 Example:
Uc = 0.7 x Umin—1.2 x Umax
1 Uc = 0.7 x 24V—1.2 x 27 Vdc
1 Pickup (x Uc)
XTCE185H–XTCEC20R 0.8 x Ucmin–1.15 x Ucmax 0.7 x Ucmin–1.15 x Ucmax 0.7 x Ucmin–1.15 x Ucmax 0.7 x Ucmin–1.15 x Ucmax
1 XTCS250L–XTCS500M — 0.85 x Ucmin–1.1 x Ucmax 0.85 x Ucmin–1.1 x Ucmax 0.85 x Ucmin–1.1 x Ucmax
Dropout (x Uc)
1 XTCE185H–XTCEC20R 0.2 x Ucmin–0.6 x Ucmax 0.2 x Ucmin–0.6 x Ucmax 0.2 x Ucmin–0.6 x Ucmax 0.2 x Ucmin–0.6 x Ucmax
XTCS250L–XTCS500M — 0.2 x Ucmin–0.4 x Ucmax 0.2 x Ucmin–0.4 x Ucmax 0.2 x Ucmin–0.4 x Ucmax
1 Power Consumption of the Coil at Cold State and 1.0 x Uc
XTCE185H–XTCEC20R
1 Pickup VA 210 1 250 1 380 1 450 1
Pickup W 180 200 250 350
1 Sealing VA 2.6 4.3 4.3 4.3
1 Voltage dips
(0.2–0.6 x Ucmin) <12 ms Time is bridged successfully Time is bridged successfully Time is bridged successfully Time is bridged successfully
1 (0.2–0.6 x Ucmin) >12 ms Contactor remains switched on Contactor remains switched on Dropout of the contactor Contactor remains switched on
(0.6–0.7 x Ucmin) Contactor remains switched on Contactor remains switched on Contactor remains switched on Contactor remains switched on
1 Excess voltage
(1.15–1.3 x Ucmax) Contactor remains switched on Contactor remains switched on Contactor remains switched on Contactor remains switched on
1 (>1.3 x Ucmax) <3s Contactor remains switched on Contactor remains switched on Contactor remains switched on Contactor remains switched on
1 (>1.3 x Ucmax) >3s Dropout of the contactor Dropout of the contactor Dropout of the contactor Dropout of the contactor
Pickup phase
1 (0–0.7 x Ucmin) Contactor does not switch on Contactor does not switch on Contactor does not switch on Contactor does not switch on
(0.7 x Ucmin –1.15 x Ucmax) Contactor switches on with certainty Contactor switches on with certainty Contactor switches on with certainty Contactor switches on with certainty
1 (>1.15 x Ucmax) Contactor switches on with certainty Contactor switches on with certainty Contactor switches on with certainty Contactor switches on with certainty
Note
1 1 Control transformer with U <6%.
k
1
1
1
1
1 Voltage interruptions
(0–0.2 x Ucmin) <10 ms Time is bridged Time is bridged Time is bridged Time is bridged Time is bridged
successfully successfully successfully successfully successfully
1 (0–0.2 x Ucmin) >10 ms Dropout of the contactor Dropout of the contactor Dropout of the contactor Dropout of the contactor Dropout of the contactor
1 Voltage dips
(0.2–0.6 x Ucmin) <12 ms Time is bridged Time is bridged Time is bridged Time is bridged Time is bridged
1 successfully successfully successfully successfully successfully
(0.2–0.6 x Ucmin) >12 ms Dropout of the contactor Dropout of the contactor Dropout of the contactor Dropout of the contactor Dropout of the contactor
1 (0.6–0.7 x Ucmin) Contactor remains Contactor remains Contactor remains Contactor remains Contactor remains
switched on switched on switched on switched on switched on
1 Excess voltage
(1.15–1.3 x Ucmax) Contactor remains Contactor remains Contactor remains Contactor remains Contactor remains
1 switched on switched on switched on switched on switched on
(>1.3 x Ucmax) <3s Contactor remains Contactor remains Contactor remains Contactor remains Contactor remains
1 switched on switched on switched on switched on switched on
(>1.3 x Ucmax) >3s Dropout of the contactor Dropout of the contactor Dropout of the contactor Dropout of the contactor Dropout of the contactor
1 Pickup phase
(0–0.7 x Ucmin) Contactor does not Contactor does not Contactor does not Contactor does not Contactor does not
1 switch on switch on switch on switch on switch on
(0.7 x Ucmin –1.15 x Ucmax) Contactor switches on Contactor switches on Contactor switches on Contactor switches on Contactor switches on
1 with certainty with certainty with certainty with certainty with certainty
(>1.15 x Ucmax) Contactor switches on Contactor switches on Contactor switches on Contactor switches on Contactor switches on
1 with certainty with certainty with certainty with certainty with certainty
Permissible contact resistance (of the external <500 <500 <500 <500 <500
1 command device with actuation of A11), ohms
<1 <1 <1 <1 <1
Permissible residual current (with actuation of A11
by the electronics with 0 signal)
1 SPS signal level (A3–A4) to IEC/EN 61131-2 (Type 2)
1 Note
1 This product is designed for operation in industrial environments. Usage in domestic areas can cause radio frequency interference (RFI).