JDICON 400/500: Universal Process Controllers
JDICON 400/500: Universal Process Controllers
JDICON 400/500: Universal Process Controllers
JDICON 400/500
Universal process controllers
Brief description
This series of universal, freely configurable process controllers is available in the formats
96 mm x 96mm and 96 mm x 48mm (portrait and landscape format).
The instruments feature two 4-digit 7-segment displays, five or eight LEDs for indication of
the switching status and operating modes, an 8-digit matrix display, as well as six keys for
operation and configuration.
The user has flexibility in assigning the slots of the controller according to the block structure. JDICON 500
Additional functions include self-optimisation, parameter set switching, and up to eight limit Type 703570/0…
comparators.
Linearisations for conventional transducers are held in the memory; a customized linearisa-
tion table can be programmed.
The process controller can be adapted to a variety of tasks with the aid of a maths module.
The instruments can be integrated into a data network via a serial interface, or can be ex-
panded through an external relay module.
A setup program is available for easy configuration from a PC.
The electrical connection is at the rear by screw terminals.
JDICON 400
Type 703575/1…
Block structure
JDICON 400
Type 703575/2…
Features
Switchable displays
Text or bar graph display
5.00/00367438
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Data Sheet 70.3570 Page 2/11
J Start-up software
The J start-up software is an integral
part of the setup program and is available
for conveniently adapting the controller to
the process.
Different process variables (e. g. setpoint,
process value, control deviation, signals
from the controller outputs) can be dis-
Fuzzy logic played graphically. The controller parame-
In addition to the standard parameters, the controller software also contains a fuzzy logic ters can be altered and transferred to the
software module. This can be used to improve both the control and the disturbance action controller via the setup or RS422/485 inter-
via two parameters. faces.
Customized linearisation
As well as the linearisations for conventional transducers, a customer-specific linearisa-
tion can be created.
Programming is performed via the setup program, in the form of a table of values.
5.00/00367438
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Data Sheet 70.3570 Page 3/11
(3)
Functions of the logic
inputs
– Start/cancel self-optimisation
(6)
– Changeover to manual mode
– Manual mode inhibit
– Ramp stop
– Ramp off
– Setpoint switching
– Process value switching
(1) configurable 7-segment display (4) Setup interface
– Parameter set switching 4 digits, red (for position, see dimensional drawings)
– Key/level inhibit
– Text display Type Height
– All displays off 703570 13mm
– Profile program start/stop 703575 10mm
5.00/00367438
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Data Sheet 70.3570 Page 4/11
Parameter level
The table below lists all the parameters, as well as their meaning. Depending on the controller type, certain parameters are irrelevant or
not applicable. Two parameter sets can be stored for specific applications.
Parameters Display Value range factory-set Meaning
Controller structure Structure 1 P, I, PD, PI, PID PID Structure 2 refers to the second output
Structure 2 P, I, PD, PI, PID PID in the case of a double-setpoint controller
Proportional band Xp1 0—9999 digit 0 digit Size of the proportional band
Xp2 0 — 9999 digit 0 digit At Xp =0 the controller structure is not
effective!
Derivative time Tv1 0—9999 sec 80 sec Influences the differential component
Tv2 0—9999 sec 80 sec of the controller output signal
Reset time Tn1 0—9999 sec 350 sec Influences the integral component of the
Tn2 0—9999 sec 350 sec controller output signal
Switching cycle time Cy1 0—9999 sec 20 sec For a switching output, the cycle time
Cy2 0—9999 sec 20 sec should be selected so that the energy
supply to the process is virtually continu-
ous while the switching devices are not
overloaded.
Contact spacing Xsh 0—9999 sec 0 digit Spacing between the two control contacts
for double-setpoint controllers, modulat-
ing controllers and proportional controllers
with integral actuator driver.
Switching differential Xd1 0—999 digit 1 digit Differential of switching controllers
Xd2 0—999 digit 1 digit for Xp = 0.
Stroke time TT 5—3000 sec 60 sec Utilised stroke time of the control valve on
modulating controllers and proportional
controllers with integral actuator driver.
Working point Y0 -100 to +100% 0% Output on P and PD controllers
(y = Y0 at x = w).
Output limiting Y1 0—100% 100% Maximum output limit
Y2 -100 to +100 % -100% Minimum output limit
Minimum relay Tk1 0—60 sec 0 sec Limitation of the switching rate on
ON time Tk2 0—60 sec 0 sec switching outputs
Isolation
5.00/00367438
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Data Sheet 70.3570 Page 5/11
Technical data
Thermocouple input
Designation Range Meas. accuracy Ambient
temperature error
Fe-Con L -200 +900 °C ≤0.25% 100 ppm per °C
Fe-Con J EN 60 584 -210 +1200 °C ≤0.25% 100 ppm per °C
Cu-Con U -200 +600 °C ≤0.25% 100 ppm per °C
Cu-Con T EN 60 584 -270 +400°C ≤0.25% 100 ppm per °C
NiCr-Ni K EN 60 584 -270 +1372 °C ≤0.25% 100 ppm per °C
NiCr-Con E EN 60 584 -270 +1000 °C ≤0.25% 100 ppm per °C
NiCrSi-NiSi N EN 60 584 -270 +1300°C ≤0.25% 100 ppm per °C
Pt10Rh-Pt S EN 60 584 -50 +1768°C ≤0.25% 100 ppm per °C
Pt13Rh-Pt R EN 60 584 -50 +1768 °C ≤0.25% 100 ppm per °C
Pt30Rh-Pt6Rh B EN 60 584 0 — 1820°C ≤0.25% 100 ppm per °C
W5Re-W26Re 0 — 2320°C ≤0.25% 100 ppm per °C
W3Re-W25Re 0 — 2400°C ≤0.25% 100 ppm per °C
Cold junction Pt100 internal, external or constant
Standard version
5.00/00367438
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Data Sheet 70.3570 Page 6/11
Outputs
Relay changeover contact
contact rating 3A at 250VAC resistive load
contact life 150 000 operations at rated load
Logic 0/5V or 0/22V
current limiting 20 mA 30mA
Solid-state relay
contact rating 1A at 230V
Voltage
output signals -10 to +10V/0 — 10V / 2 — 10 V
load resistance Rload 50 0Ω min.
Current
output signals -20 to +20 mA/0 — 20 mA / 4 — 20mA
load resistance Rload 450 Ω max.
Supply for
2-wire transmitter
voltage 22V
current 30mA
Controller
Controller type single-setpoint controller,
double-setpoint controller, modulating controller, proportional controller,
proportional controller with integral actuator driver
Controller structures P/PD/PI/PID
A/D converter resolution better than 15 bit
Sampling time 210 msec
Electrical data
Supply (Switched mode power supply) 110 — 240V AC -15/+10%, 48 — 63 Hz
20 — 30V AC/DC, 48 — 63Hz
Test voltages (type test) to EN 61 010, Part 1
overvoltage category II, pollution degree 2
Power consumption 10VA max. for Type 703570
7VA max. for Type 703575
Data backup EEPROM
Electrical connection At rear by screw terminals,
conductor cross-section up to 2.5 mm2
and core-end sleeve (length: 10 mm)
Electromagnetic compatibility EN 50 081-1, EN 50 082-2, NAMUR recommendation NE21
Safety standards to EN 61 730-1 for Type 703570
to EN 61 010-1 for Type 703575
Housing
Housing type plastic housing for panel mounting to DIN 43 700
Standard version
5.00/00367438
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Data Sheet 70.3570 Page 7/11
Connection diagrams
Type 703570/0…
5.00/00367438
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Data Sheet 70.3570 Page 8/11
5.00/00367438
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Data Sheet 70.3570 Page 9/11
5.00/00367438
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Data Sheet 70.3570 Page 10/11
Dimensions
Type 703570/0… Type 703575/1… (portrait format)
Setup plug
Setup plug
Edge-to-edge mounting
Setup
plug Minimum distances of the panel cut-outs
Type horizontal vertical
without setup plug:
703570/0… 11mm 30mm
703575/1… (portrait) 11mm 30mm
703575/2… (landscape) 30mm 11mm
with setup plug:
703570/0… 11mm 65mm
panel cut-out to DIN 43 700 703575/1… (portrait) 11mm 65mm
703575/2… (landscape) 65mm 11mm
5.00/00367438
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Data Sheet 70.3570 Page 11/11
Ordering details
Basic type
703570 JDICON 500: Universal process controller in 96mm x 96mm format
703575 JDICON 400: Universal process controller in 96mm x 48mm and 48mm x 96mm formats
1. 2. 3. 4. Analogue input
0 0 not assigned (analogue inputs 1 + 2 available as standard)
1 1 1 1 Universal input (all listed transducers, except voltage -10 to +10V / 0 — 10V / 2 — 10V)
2 2 2 2 Voltage -10 to +10V / 0 — 10V / 2 — 10V
1. 2. 3. 4. 5. 6. Slot for output/two logic inputs (two logic inputs available as standard)
0 0 0 0 0 0 not assigned
1 1 1 1 1 1 Relay (changeover contact)
2 2 2 2 2 2 Solid-state relay 230V 1A
3 3 3 3 3 3 Logic 0/5V
4 4 4 4 4 4 Logic 0/22V
5 5 5 5 5 5 Analogue output
6 6 6 6 6 6 Supply for 2-wire transmitter
7 7 7 Two logic inputs (logic inputs 3+4, 5+6, 7+8; only possible on slots 1, 2 and 3)
Supply
2 3 110 — 240V AC -15/+10% 48 — 63Hz
2 5 20 — 30V AC/DC, 48 — 63Hz
Interface
0 0 not assigned
5 4 RS422/RS485 with MODbus/Jbus protocol
6 4 PROFIBUS-DP
Approvals
0 0 0 none
0 5 6 DIN 3440*
0 6 1 Underwriters Laboratories Inc. (UL)
0 6 2 Germanischer Lloyd (GL)*
0 6 3 DIN 3440 and GL*
0 6 4 DIN 3440 and UL*
0 6 5 GL and UL*
0 6 6 DIN 3440, GL and UL*
* for Type 703570 only
703570/ 0 – – – – / ,
703575/ – 0 0 – 0 0 0 – – / ,
Stock versions
Accessories vpage 10