KFD2 S0T2 Ex2

This document provides technical specifications for a 2-channel intrinsically safe barrier model KFD2-SOT2-Ex2. It has two discrete input channels that can accept signals from proximity sensors or switches located in hazardous areas. Each input controls a passive transistor output in the safe area. The device provides isolation between the hazardous and safe areas, and has options for lead breakage and short circuit monitoring. It is suitable for Division 2/Zone 2 installations and complies with various international safety certifications.

Uploaded by

Arun Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
197 views1 page

KFD2 S0T2 Ex2

This document provides technical specifications for a 2-channel intrinsically safe barrier model KFD2-SOT2-Ex2. It has two discrete input channels that can accept signals from proximity sensors or switches located in hazardous areas. Each input controls a passive transistor output in the safe area. The device provides isolation between the hazardous and safe areas, and has options for lead breakage and short circuit monitoring. It is suitable for Division 2/Zone 2 installations and complies with various international safety certifications.

Uploaded by

Arun Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

KFD2-SOT2-Ex2

Technical Data 2-Channel with


POWER SUPPLY Power Rail or terminals 14+, 15-
Nominal voltage 20-30 VDC Passive Transistor
Rated current ≤ 50 mA Output
INPUT 1, 2 (intrinsically safe) Terminals 1+, 2+, 3-; 4+, 5+, 6-
Nominal Data ≈ 8 VDC / ≈ 8 mA Model Number
Switching point/Switching hysteresis 1.2-2.1 mA / ≈ 0.2 mA KFD2-SOT2-Ex2
Lead Breakage (LB) Monitoring Breakage I ≤ 0.1 mA, short-circuit I > 6 mA
• 2-channel
OUTPUT (not intrinsically safe)
• 24 VDC supply/Power Rail compatible
Output 1 Terminal 7, 8
Output 2 Terminal 8, 9
• 1 signal output with 1 passive transistor
per channel
Logic 1 (L+) - 2.5 V max. for 10 mA or 3 V max. for 100 mA
(100 mA, short-circuit proof) @ 40 VDC • Suitable for Division 2/Zone 2 mounting
Logic 0 Switched off (off-state current ≤10 μA) • Optional lead breakage (LB) and short
TRANSFER CHARACTERISTICS circuit (SC) monitoring

K-System Discrete Input


Switching Frequency < 5 kHz • LB/SC collective error messaging via
CERTIFICATES See page 127 for entity parameters Power Rail
No. 116-0035 • SIL 2 according to IEC 61508; SIL 3 in a
redundant structure
No. 116-0047
Zone 0, 1, 2 PTB 00 ATEX 2035, II (1) G D [EEx ia] IIC This device is a dual-channel, galvanically isolated intrinsic
Zone 2 TÜV 99 ATEX 1499X, II 3 G EEx nAC IIC T4 safety barrier with a built-in amplifier that transfers discrete
signals (NAMUR sensors/mechanical contacts) from a
Exida P+F 01/09-02D R002 hazardous area to a safe area. Each proximity sensor or
MECHANICAL switch controls a passive transistor output. The barrier
Housing Type C see page 454 output changes state when the input signal changes state.
Dimensions 4.65" x 0.79" x 4.53" (118 x 20 x 115 mm) The normal output state can be reversed through the mode
of operation switches S1 and S2.
Weight 5.3 oz. (≈ 150 g)
AMBIENT TEMPERATURE -4°F to +140°F (-20°C to +60°C) For a mechanical contact, LB monitoring can be selected
by placing a 10 kΩ resistor across the mechanical contact
in the field and moving switch S3 to position I on the
barrier. SC monitoring is added by placing a 400Ω-2 kΩ
resistor in series with the mechanical contact. NAMUR
proximity sensors, however, are designed with the LB and
Engineer's Guide (page 7) SC functions, making external resistors unnecessary. In
Accessories (page 443) case of a LB/SC fault, the signal output relay reverts to the
Power Supplies (page 401) deenergized state. LB/SC monitoring can be disabled with
Surge Suppression (page 413) S3 in position II. If used in conjunction with P+F's Power
Lastest Info. Avail. Online Rail system, the unique collective error messaging feature
can be utilized.
Connection Diagram
Front View
Class I; Div 1, 2 Removable terminals
Zone 0, 1, 2 blue
Safe Area, Div 2 or Zone 2 Housing type C
Hazardous Area (see system description)
KFD2-SOT2-Ex2
Input 1

}
1 7
Passive Transistor LED yellow:
R2
2 Output 1 Transistor output 1
LED green:

}
R1 8 (+/-)
R1 Power
3 Passive Transistor LED red:
Output 2 LB/SC channel 1
Input 2 9
Switch S1
4 LED yellow:
(Mode of operation channel 1)
R2 Transistor output 2

R1 R1
5

6
14 (+)
15 (–) } Supply
24 VDC LED red:
LB/SC channel 2
Switch S2
(Mode of operation channel 2)

LB/SC LB/SC LB Switch S3


(LB/SC-monitoring)
Collective Error Messaging
Power Rail Connection
Removable terminals
green