FLEX I/O Digital Input Modules: Installation Instructions

Allen Bradley modulo de entradas digitales.

Uploaded by

nicolas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views6 pages

FLEX I/O Digital Input Modules: Installation Instructions

Allen Bradley modulo de entradas digitales.

Uploaded by

nicolas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Installation Instructions

FLEX I/O Digital Input Modules


5 *
 
-+<    
 "
1794-IB8, -IB16, -IB16K and -IB32 WARNING  +
+++ ++%
++ ; 
 

=+
 

 %   


  =- +
%
(Modules with a K in the last position of the catalog number are conformally
coated to meet noxious gas requirements of ISA/ANSI-71.040 1985 Class
G3 Environment.)
>?@2A
   (8
+
  %B
ATTENTION =
+ * +(8
  
Important User Information
 
%(8

,% %
"
Solid state equipment has operational characteristics differing from those of 
+"+%/+ +";

=" + +"+ 
electromechanical equipment. Safety Guidelines for the Application, Installation and 

  

   
%
Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell
Automation sales office or online at http://www.ab.com/manuals/gi) describes some
important differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of uses for solid
state equipment, all persons responsible for applying this equipment must satisfy themselves   
  


  
that each intended application of this equipment is acceptable. ATTENTION

&
 
 

+
+
+ " 
++ 
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or +
   +  
 %> 
consequential damages resulting from the use or application of this equipment. 

  * 
&
 
• +  -7+
+   

+%
The examples and diagrams in this manual are included solely for illustrative purposes. • 5    
 
 %
Because of the many variables and requirements associated with any particular installation, • ( ++ +
 +   -%
Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the • ( ++
+
+   

&
 %
examples and diagrams. • 
-"
+ <
 %
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of European Hazardous Location Approval
Rockwell Automation, Inc. is prohibited.


     !" #
Throughout this manual we use notes to make you aware of safety considerations.   #$%
Identifies information about practices or circumstances that can cause
WARNING an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.      

      
  
 

  !"

&
 

 
  
*; 
 
-*
  B
 (
+
22)%
IMPORTANT
Identifies information that is critical for successful application and ?),?-
)  
+
&/+



understanding of the product. &
 -  + *
 
C 3*
4&
 

 + +
 ) *D&
 
Identifies information about practices or circumstances that can lead to
 
  
*; 
 "
 
1 ;

ATTENTION personal injury or death, property damage, or economic loss. Attentions (
+
%;

  +
+ 
 
 8%!
help you: #!..%
• identify a hazard ) 
 +
 
C 3*4&
 - -*
• avoid a hazard + 
 +
8:..%
• recognize the consequence
A-


  +

+
 &
 %
IMPORTANT
• 
&
 
 
  
+
BE

 %
 
  • + *+   -
ATTENTION

&
 

 
'
 ( 

   +
+
   

)"  
  %
 
  "
 ) * 
+
 ,

 • &
  +* 4
-

) -
+
 #.##/"
 ...

  + 

': +
    


%
)"  
  %
• 
&
 -


 +




&
 
+ 
0 ")1

&
  
-*1  *%
++
)2)3'4'-
+
 %5
  
 • '

 -   
+
 "*-  


+
 
 -
;+-* 
 
- + .F
+ 
++ 
-

*
 
     

)"  
  
+ + 

- +%

&
 
 
6  * 6&
 %-
 

  +

-*

 +

+ 
  + 

 
-   
  
*
    
7*

++
-

*
 %

 +-
++
- *-*%3-& +
 

-
+
 *+ 


 

  
 +

+
 +* 
&
+ *
+

+*+

+
 %
38913  -
+
 :. ) -
+
 #.:"
 
+-";  
   +
  

-*
 *  +%1"  
+
 


 -
+
 " 1  * -
+
 .%
,6 
1
 5

 0 
0

6/"


 

 &
  


&
 %

Publication 1794-IN093B-EN-P - May 2004


2

North American Hazardous Location Approval #$ 4<*


+,/ 
-,/++<
 

 
The following input modules are North American Hazardous Location &

* %
approved: 1794-IB8, -IB16, -IB16K and -IB32. $ 9<+
;-+ +,D/
  *
The following information applies when operating this Informations sur l’utilisation de cet équipement en + +
 
-

-2 %%  

equipment in hazardous locations: environnements dangereux :


    
  
  & 
 $
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with
conviennent qu’à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non '$ 9<
 -
*
markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a
dangereux. Chaque produit est livré avec des marquages sur
sa plaque d’identification qui indiquent le code de

  *
+ +

-%
system, the most adverse temperature code (lowest “T” number) température pour les environnements dangereux. Lorsque
may be used to help determine the overall temperature code of the plusieurs produits sont combinés dans un système, le code
system. Combinations of equipment in your system are subject to de température le plus défavorable (code de température le
investigation by the local Authority Having Jurisdiction at the time
of installation.
plus faible) peut être utilisé pour déterminer le code de
température global du système. Les combinaisons *
 

WARNING
d’équipements dans le système sont sujettes à inspection par
les autorités locales qualifiées au moment de l’installation.
-+<    
 " +
+++ ++%
EXPLOSION HAZARD RISQUE D’EXPLOSION 
++ ; 
 
=
WARNING
• Do not disconnect equipment
AVERTISSEMENT
• Couper le courant ou s’assurer que
+
 

 %   

unless power has been removed or
the area is known to be
l’environnement est classé non
dangereux avant de débrancher

  =-
nonhazardous. l'équipement. +
%%
• Do not disconnect connections to • Couper le courant ou s'assurer que
this equipment unless power has l’environnement est classé non ($ '

 ,/


 -,:/


been removed or the area is known dangereux avant de débrancher les
to be nonhazardous. Secure any connecteurs. Fixer tous les ,#/ 
-%
external connections that mate to connecteurs externes reliés à cet
this equipment by using screws, équipement à l'aide de vis, loquets
sliding latches, threaded connectors, coulissants, connecteurs filetés ou )$ '
*  *

-
%
or other means provided with this
product.
autres moyens fournis avec ce
produit. 
  +
+
,/
+<

• Substitution of components may • La substitution de composants %
impair suitability for Class I, Division peut rendre cet équipement
2. inadapté à une utilisation en
environnement de Classe I, Division
• If this product contains batteries,
they must only be changed in an area
2.  
 * 
 #+,(-./01 -./#2  -./#23 
known to be nonhazardous. • S’assurer que l’environnement est
classé non dangereux avant de #+,(-/'  -/'4
changer les piles.
#$ ) +





 -
 .:
 ,1/

+
-- %
Compatibility
$ ) ++
GE+  

+
The following communication adapters are required to ensure +  

 D: ,)/+

compatibility with the 1794-IB32:

+
-- %,GE  
 ,)/
Remote I/O 1794-ASB series E or later
 *+ + %/
1794-ASB2 series D or later '$ ) ++

+ ,D

+ */
TM 1794-ACN15 series C, firmware revision 4.1 or later +  

 #DD %, /+

ControlNet
1794-ACNR15 series C, firmware revision 4.1 or later

+
-- %,) 
 *+ +
1794-AENT series A, firmware revision 2.4 or later  %/
EthernetTM
($ ) +GE+  
D D: ,)/%
PROFIBUS TM 1794-APB series A, version 1.1 of the GSD file (you can
download the GSD file at www.ab.com/networks/gsd )$ ) +++ 
# #DD , /%
2$ 
*+

   ;
-"+ +7 
ControlLogixTM Family RSLogix5000 programming software, version 11 or later

:,GE+/ 
-

D  ;
-
%
Installing Your Digital Input Module +$ + 

++  ;-
"+ +7 

DD,+ / 
-

# 
;-
%
7
3 1

4 5

  


-%
(
 

+"-
ATTENTION
-
,+
"
 "+%/
< 


%(-


++    
 %

Publication 1794-IN093B-EN-P - May 2004


3

*  
  #+,(-./01 -./#2  -./#23  
 )$ ) ++
  GE
,D":"/
#+,(-/'  -/'4    /  5
"  D: ,)/

+
-- %

Input1 Input Terminal Voltage Terminal Common Terminal2 2$ ) ++


+ 8#8D)A9
Input 0 A-0 C-35 B-17 ,
#"!:./ D: ,)/%
Input 1 A-1 C-36 B-18
Input 2 A-2 C-37 B-19 +$ + 




  8.8: ;

Input 3 A-3 C-38 B-20 -"+ +7 
,GE/ 

-
Input 4 A-4 C-39 B-21 
  
  ;
-
%,4
Input 5 A-5 C-40 B-22 

 
+
  +

+
-
%
Input 6 A-6 C-41 B-23
Input 7 A-7 C-42 B-24 0$ + 




8.8:+  ;

Input 8 A-8 C-43 B-25 -"+ +7 
,)A9/ 


Input 9 A-9 C-44 B-26 -
+ 
  ;
-
%
Input 10 A-10 C-45 B-27
Input 11 A-11 C-46 B-28 ,$ + 




  8#8D ;

Input 12 A-12 C-47 B-29 -"+ +7 
,GE/ 

-
Input 13 A-13 C-48 B-30 
  
  ;
-
%,4
Input 14 A-14 C-49 B-31 

 
+
  +

+
-
%
Input 15 A-15 C-50 B-32
+V dc C-34 thru C-51 #6$ + 




8#8D+  ;

Common B-16 thru B-33 -"+ +7 
:.,)A9/ 


11794-IB8 - Inputs 0 thru 7; 1794-IB16, -IB16K - Inputs 0 thru 15 -
+ 
  ;
-
%
2
3-wire devices use input, supply and common; 2-wire devices use input and
supply
*  #+,(-./'  
 #+,(-/'  -/'4   
#+,(-/'  -/'4    /  *  #+,(-./01 -./#2 /  5
"
 -./#23 Input Signal Input Signal
IN 0 A-0 IN 16 B-17
Inputs
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 IN 1 A-1 IN 17 B-18
A IN 2 A-2 IN 18 B-19
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 IN 3 A-3 IN 19 B-20
B IN 4 A-4 IN 20 B-21
-V Commons -V
Common Common IN 5 A-5 IN 21 B-22
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
IN 6 A-6 IN 22 B-23
C
IN 7 A-7 IN 23 B-24
Voltage Voltage
Voltage IN 8 A-8 IN 24 B-25
In +V Out +V
Connect V common to terminals B-16 (1794-TB3 shown) IN 9 A-9 IN 25 B-26
Connect +V to terminal C-34 IN 10 A-10 IN 26 B-27
Use B-33 and C-51 to daisy-chaining to the next terminal base unit
IN 11 A-11 IN 27 B-28
  '-* .
*  #+,(-./01 -./#2  -./#23 IN 12 A-12 IN 28 B-29
IN 13 A-13 IN 29 B-30
0-15 A IN 14 A-14 IN 30 B-31
16-33 B
IN 15 A-15 IN 31 B-32
34-51 C
+V1 dc power1 Power terminals 35, 37, 39 and 41 for IN0-IN15.
A = Sink input (inputs IN0-IN15) +V1 connected to terminals 35, 37, 39 and 41
2-Wire Device 3-Wire Device
B = Common Com1 dc Return Common terminals 36, 38, 40 and 42 for IN0-IN15.
(Sourcing Output) (Sourcing Output)
C = +V dc (inputs IN0-IN15) V1 Return connected to terminals 36, 38, 40 and 42
+V2 dc power Power terminals 43, 45, 47 and 49 for IN16-IN31.
 
 * 
 #+,(-./'  #+,(-/'  (inputs IN16-IN31) +V2 connected to terminals 43, 45, 47 and 49
-/'4 Com2 dc Return
(inputs IN16-IN31)
Common terminals 44, 46, 48 and 50 for IN16-IN31.
V2 Return connected to terminals 44, 46, 48 and 50
12-wire input devices use signal and supply terminals; 3-wire devices use signal, return and
#$ ) +





,8.8:/ -
 supply terminals
 .: ,1/

+
-- %

$ ) ++
  GE
,D:"D"D/
 D: ,)/

+
-- %

'$ ) ++
+ 8.8:)A9,

D#"D!"./ D: ,)/

+
-- %

($ ) +





,8#8D/ -

 #DD , /

+
-- %
 
 


  #2  ''$

Publication 1794-IN093B-EN-P - May 2004


4

#+,(-/'  -/'4    /  * 


 #+,(-./' .
7
 

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Bits Description - Filter Time Filter Time
Inputs
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
02 01 00 Inputs 0 thru 07 (-IB8) 1794-IB8, -IB16,
02 01 00 Inputs 0 thru 11 (-IB16, -IB16K) -IB16K, -IB32
Inputs
NC NC 05 04 03 Inputs 12 thru 15 (-IB16, -IB16K)
10 09 08 Inputs 0 thru 31 (-IB32) Off to On/On to Off
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
NC +V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC
0 0 0 Filter time 0 (default) 0.25ms
+V1 = Terminals 35, 37, 39 and 41
0 0 1 Filter time 1 0.5ms
(1794-TB32 shown)
+V2 = Terminals 43, 45, 47 and 49 0 1 0 Filter time 2 1ms
COM1 = Terminals 36, 38, 40 and 42 0 1 1 Filter time 3 2ms
COM2 = Terminals 44, 46, 48 and 50
1 0 0 Filter time 4 4ms
NC = No connections (terminals 16, 33, 34 and 51)
1 0 1 Filter time 5 8ms
1 1 0 Filter time 6 16ms
Configuring Your Input Module 1 1 1 Filter time 7 32ms

) 
*
-*
-

+ 

  
, 
 /% Specifications
Dec. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Specifications - 24V dc 8 Input Module, Cat. No. 1794-IB8
Oct. 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Number of Inputs 8, nonisolated, sinking
Read 1 (-IB16, I I I I I I I9 I8 I7 I6 I5 I4 I3 I2 I1 I0 Module Location Cat. No. 1794-TB3, -TB3S Terminal Base Unit
-IB32) 15 14 13 12 11 10
On-state Voltage 10V dc minimum
Read 1 (-IB8) Not used I7 I6 I5 I4 I3 I2 I1 I0 24V dc nominal
Read 2 (-IB16) C = Counter Input value of input 15 31.2V dc maximum
Read 2 I I I I I I I I I I I I I I I I On-state Current 2.0mA minimum
(1794-IB32) 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 8.0mA nominal at 24V dc
Write 1 (-IB8) Not used Input Filter 0-07 12.0mA maximum
Write 1 Not used CF C Not used Input Filter Input Filter 0-11 Off-state Voltage 5.0V dc maximum
(-IB16) R 12-15
Write 1 Not used Input Filter FT Not used
Off-state Current 1.5mA minimum
(1794-IB32) 0-31 Input Impedance 4.6K ohms
Where I = Input Isolation Voltage Tested at 850V dc for 1s between user and system
D = Diagnostic data (1794-IB8S only)
C = Counter value for input 15 No isolation between individual channels
FT = Input filter time Flexbus Current 20mA
CR = Counter reset
CF = Counter fast - where 1 = fast input (raw data), 0 = standard input filtered data Power Dissipation 3.5W maximum @ 31.2V dc
NOTE: C, CR and CF not available when used with any series 1794-ASB or 1794-ASB2 remote I/O adapter modules.
Thermal Dissipation Maximum 11.9 BTU/hr @ 31.2V dc


 .
7
 
Specifications - 24V dc 16 Input Module, Cat. No. 1794-IB16 and



"+
-

 
 - 1794-IB16K
,+  * / Number of Inputs 16 (1 group of 16), nonisolated, sinking
Module Location Cat. No. 1794-TB3, -TB3S Terminal Base Unit
%
Mounting Refer to the derating curve.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Dec. On-state Voltage 10V dc minimum
24V dc nominal
17
15 16 13
14 15 14
12 13 10
11 12 911 810 7 6 5 4 3 2 1 0 Octal 31.2V dc maximum
O:010 On-state Current 2.0mA minimum
8.0mA nominal at 24V dc
12.0mA maximum
FT = 0-31 FT = 0-7 (1794-IB8)
FT = 12-15 FT = 0-11 (1794-IB16) Off-state Voltage 5.0V dc maximum
1794-IB32
Off-state Current 1.5mA minimum
1794-IB16 Input Impedance 4.6K ohms
Isolation Voltage Tested at 850V dc for 1s between user and system
>; "
+ 


 No isolation between individual channels
+<"  .",
 D ; /"-
  Flexbus Current 30mA
Power Dissipation 6.1W maximum @ 31.2V dc
  - %
Thermal Dissipation Maximum 20.8 BTU/hr @ 31.2V dc

Write filter time on system startup.


FLL
Write FT to complement Specifications - 24V dc 32 Input Module, Cat. No. 1794-IB32
I:000 of input module.
Fill File Number of Inputs 32 (2 groups of 16), nonisolated within groups, sinking
Source Module Location Cat. No. 1794-TB32, -TB32S Terminal Base Unit
Destination #O:010
00
Length 1 On-state Voltage 19.2V dc minimum
24V dc nominal
31.2V dc maximum
7 6 5 4 3 2 1 0
1794-IB8 = 4 Octal or 4 Decimal On-state Current 2.0mA minimum
1 0 0 4.1mA nominal at 24V dc
6.0mA maximum
7 6 5 4 3 2 1 0
= 44 Octal or 36 Decimal Off-state Voltage 5.0V dc maximum
11 0 00 1 0 0
1794-IB16 Off-state Current 1.5mA minimum
15 14 13 12 11 10 09 08 Input Impedance 6.0K ohms
= 4 Octal or 4 Decimal
1 0 0 1 0 0 Isolation Voltage Tested to withstand 2121V dc for 1s between input and backplane
1794-IB32
Flexbus Current 35mA
4 >

+- -

% Power Dissipation 6.0W maximum @ 31.2V dc
Thermal Dissipation Maximum 20.5 BTU/hr @ 31.2V dc

Publication 1794-IN093B-EN-P - May 2004


5

Derating Chart for the 1794-IB16 and -IB16K


General Specifications 31.2
Input Filter Time1 30
Off to On 0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms 28.5
On to Off 0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms 27.5
0.25ms default - Selectable using configuration word 3
Terminal Base Screw 7 pound-inches (0.8Nm) 25
Torque V in
On-State
Dimensions (with module 3.7H x 3.7W x 2.7D inches Voltage
installed) 94H x 94W x 69D mm (V dc) 20
Indicators (field side 1794-IB8 - 8 yellow status indicators
indication, customer 1794-IB16, -IB16K - 16 yellow status indicators
device driven) 1794-IB32 - 32 yellow status indicators
15
External dc power
Supply voltage 24V dc nominal
Voltage range 1794-IB8, -IB16, -IB16K - 10 to 31.2V dc (includes 5% ac ripple)
1794-IB32 - 19.2 to 31.2V dc (includes 5% ac ripple) 10
0 10 20 30 32 37 40 50 55 60
Environmental Conditions AmbientTemperature oC
Operating IEC 60068-2-1 (Test Ad, Operating Cold), The area within the curve represents the safe operating range for the module under
Temperature IEC 60068-2-2 (Test Bd, Operating Dry Heat), various conditions of user supplied 24V dc supply voltages and ambient temperature.
IEC 60068-2-14 (Test Nb, Operating Thermal Shock): = Normal mounting safe operating range, (includes ).
0 to 55°C (32 to 131°F) = Other mounting positions (including inverted horizontal) safe operating range
Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), Normal Mounting – Horizontal
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85°C (–40 to 185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Other Mounting (including Vertical, and Inverted Horizontal Mounting
Damp Heat):
5 to 95% non-condensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz
Shock IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g Temperature Voltage Temperature
Voltage (max.) (max.) (max.)
Non-operating 50g (max.)
Emissions CISPR 11: Normal Other Normal Other
Group 1, Class A (with appropriate enclosure) 31.2 37 32 29.0 51 45
ESD Immunity IEC 61000-4-2:
30.5 41 36 28.5 48
4kV contact discharges
8kV air discharges 30.0 45 39 28.0 55 51
Radiated RF Immunity IEC 61000-4-3: 29.5 48 42 27.5 55
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz
EFT/B Immunity IEC 61000-4-4:
±2kV at 5kHz on signal ports
Surge Transient IEC 61000-4-5:
Immunity ±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports
Conducted RF IEC 61000-4-6:
Immunity 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 30MHz
Enclosure Type Rating None (open-style)
Conductors Wire Size 12AWG (4mm2) stranded copper wire rated at 75°C or higher
3/64 inch (1.2mm) insulation maximum
2
Category 2
Certifications (when UL UL Listed Industrial Control Equipment (all)
product is marked)3 CULUS UL Listed Industrial Control Equipment, certified for US and
Canada (1794-IB32)
CULUS UL Listed for Class I, Division 2, Groups A, B, C and D
Hazardous locations certified for US and Canada (1794-IB16,
-IB16K, -IB32)
CSA CSA certified for Class I, Division 2, Groups A, B, C and D
Hazardous locations (1794-IB8, -IB16, -IB16K)
EEx3 European Union 94/9/EEC ATEX Directive, compliant with:
EN 50021; Potentially Explosive Atmospheres,
Protection “n” (Zone 2) - (1794-IB8, -IB16, -IB16K)
CE3 European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity (all)
C-Tick3 - Australian Radiocommunications Act compliant with
AS/NZS CISPR 11, Industrial Emissions (all)
1 Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off filter
time is time from the input signal dropping below the valid level to recognition by the module.
2 You use this category information for planning conductor routing as described in Allen-Bradley
publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.
3 For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of
Conformity, Certificates and other certification details. For notification of any additional release notes, refer to
www.ab.com/manuals/.

Publication 1794-IN093B-EN-P - May 2004


Publication 1794-IN093B-EN-P - May 2004 6 PN 957831-40
Supersedes Publication 1794-IN093A-EN-P - April 2003 and 1794-RN061A-EN-P - January 2002 Copyright © 2004 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.