KNX Shutter Actuator

Download as pdf or txt
Download as pdf or txt
You are on page 1of 145

1473-1-7829 | Rev. 01 | 3.

2012

Product Manual
ABB i-bus® KNX

Shutter actuator 1gang with binary


Inputs, FM
6152/11 U-500

Power and productivity


for a better worldTM
Product Manual
ABB i-bus® KNX

Contents

1 Product definition ................................................................................................................ 3

1.1 Product catalogue ........................................................................................................... 3


1.2 Function .......................................................................................................................... 3

2 Installation, electrical connection and operation ............................................................. 4

2.1 Safety instructions .......................................................................................................... 4


2.2 Device components ........................................................................................................ 5
2.3 Fitting and electrical connection ..................................................................................... 6
2.4 Commissioning ............................................................................................................... 9
2.5 Operation ...................................................................................................................... 12

3 Technical data .................................................................................................................... 13

4 Software description ......................................................................................................... 14


4.1 Software specification ................................................................................................... 14
4.2 Software "Blind, input/1.1" ............................................................................................ 15
4.2.1 Scope of functions ................................................................................................. 15
4.2.2 Software information ............................................................................................. 17
4.2.3 Object table ........................................................................................................... 18
4.2.3.1 Extension input objects .................................................................................. 18
4.2.3.2 Venetian blind output objects ......................................................................... 21
4.2.4 Functional description ........................................................................................... 26
4.2.4.1 General functions for extension inputs .......................................................... 26
4.2.4.2 General functions for the Venetian blind output ............................................. 28
4.2.4.3 Channel-orientated functions for extension inputs ......................................... 29
4.2.4.3.1 Function configuration of the extension inputs ....................................... 29
4.2.4.3.2 Disabling function for extension inputs ................................................... 36
4.2.4.4 Channel-oriented functions for the Venetian blind output .............................. 37
4.2.4.4.1 General settings ..................................................................................... 37
4.2.4.4.2 Movement time settings ......................................................................... 40
4.2.4.4.3 Positioning and feedback settings .......................................................... 44
4.2.4.4.4 Safety function settings .......................................................................... 54
4.2.4.4.5 Sun protection settings ........................................................................... 58
4.2.4.4.6 Settings for automatic heating/cooling ................................................... 79
4.2.4.4.7 Scene function settings ......................................................................... 85
4.2.4.4.8 Forced position settings ......................................................................... 88
4.2.4.4.9 Fabric stretching settings ....................................................................... 91
4.2.4.5 Priorities for the output ................................................................................... 93
4.2.5 Delivery state ........................................................................................................ 94
4.2.6 Parameters ............................................................................................................ 95
4.2.6.1 General parameters ....................................................................................... 95
4.2.6.2 Parameters for the extension inputs .............................................................. 97
4.2.6.3 Parameters for the Venetian blind output .................................................... 110

5 Appendix ........................................................................................................................... 144

5.1 Index ........................................................................................................................... 144

1473-1-7829 | Rev. 01 | 3.2012 Page 2 of 144


 
Product definition

1 Product definition
1.1 Product catalogue
Product name: Shutter actuator 1gang with binary Inputs
Use: Actuator / sensor
Form: UP (concealed)
Art.-No. 6152/11 U-500

1.2 Function
The output (O1) allows the control of electrically-operated Venetian blinds, roller shutters,
awnings, venting louvers or similar blinds for 230 V AC mains voltage. The relay contacts for the
movement directions (up, down) are bistable, meaning that the last switching status set also
remains intact, should the mains voltage fail.

The functionalities that can be preset with the ETS for the Venetian blind output include, for
instance, separately configurable travelling times, enlarged feedback functions, assignment to
up to 5 different safety functions, an extensive sun protection function, and incorporation into
scenes or forced-position applications.

Besides the output, the device possesses three additional inputs, which can have an internal
effect on the Venetian blind output or, alternatively, affect the KNX/EIB separately, depending
on the ETS configuration. The connected potential-free switch or button contacts are
downloaded to the device via a shared reference potential. With the internal effect, inputs 1 and
2 directly operate the Venetian blind output. With the effect on the bus, the inputs can,
independently of one another, transmit telegrams for switching or dimming for Venetian blind
control or value encoder use (dimming value encoder, light scene extension).
The connection of 230 V signals or other external voltages to the extension inputs is not
permitted!

For configuration and commissioning of this device, it is necessary to use ETS3.0 from version
"d" onwards. Advantages with regard to downloading (significantly shorter loading times) and
parameter programming can be expected only if this ETS patch version or later versions are
used.

The device electronics are supplied exclusively from the bus voltage. The device is designed for
installation in concealed switch or device boxes in permanent installations.

1473-1-7829 | Rev. 01 | 3.2012 Page 3 of 144


 
Installation, electrical connection and operation

2 Installation, electrical connection and operation


2.1 Safety instructions
Electrical equipment may only be installed and fitted by electrically skilled persons. The
applicable accident prevention regulations must be observed.
Failure to observe the instructions may cause damage to the device and result in fire and
other hazards.
Before working on the device or exchanging the connected loads, disconnect it from the
power supply (switch off the miniature circuit breaker), otherwise there is the risk of an
electric shock.
The device is not suitable for disconnection from supply voltage.
Make sure during the installation that there is always sufficient insulation between the
mains voltage and the bus and extension inputs. A minimum distance of at least 4 mm
must be maintained between bus/extensions and mains voltage cores.
Do not connect any external voltage to the inputs, since doing so may damage the
device(s), and the SELV potential on the KNX bus line will no longer be available.
For parallel connection of several drives to a shutter / blind output it is indispensable to
observe the corresponding instructions of the manufacturers, and to use a cutoff relay if
necessary. There is otherwise risk of irreparable damage to the drives.
Use only curtains with mechanical or electronic limit switches. Check the limit switches
for correct adjustment.
Do not connect any three-phase motors.
The device may not be opened or operated outside the technical specifications.

1473-1-7829 | Rev. 01 | 3.2012 Page 4 of 144


 
Installation, electrical connection and operation

2.2 Device components

Figure 1: Device components

(1) Control cable (bus connection and extension inputs)


(2) Programming button and programming LED (red).
(3) Connection cables for mains voltage and load

Connection assignment of the control cable (1)


RD (red): KNX bus voltage +
BK (black): KNX bus voltage -
GN (green): Input 1
YE (yellow): Input 2
WH (white): Input 3
BN (brown): Reference potential "COM" for inputs 1...3

Connection assignment for mains voltage and load (3)


BK (black): Mains voltage (L)
BN (brown): Connection for Venetian blind drive (UP, n) - relay output
PK (pink): Connection for Venetian blind drive (DOWN, o) - relay output

1473-1-7829 | Rev. 01 | 3.2012 Page 5 of 144


 
Installation, electrical connection and operation

2.3 Fitting and electrical connection


DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before working on the device, disconnect the power supply and cover up live
parts in the working environment.

DANGER!
When connecting the bus/extensions and mains voltage wires in a shared
appliance box, the KNX bus line may come into contact with the mains voltage.
This endangers the safety of the entire KNX installation. People at remote
devices may also receive an electric shock.
Do not place bus/extensions and mains voltage terminals in a shared
connection compartment. Use an appliance box with a fixed partition wall or
separate boxes.

Connecting and mounting the device


Minimum spacing between the mains voltage and bus/extension wires: 4 mm (Figure 2).
Recommendation: Use an electronics box when installing the device, e.g. with a series switch
(Figure 3).

Figure 2: Minimum cable spacing

1473-1-7829 | Rev. 01 | 3.2012 Page 6 of 144


 
Installation, electrical connection and operation

Figure 3: Installing the device in an electronics box (example)

(4) Device box (e.g. electronics box)


(5) Partition
(6) Series switch
(7) Potential-free contact, e. g. window contact

o Connect the mains voltage and the Venetian blind drive using the included screwless
terminals (Figure 4).

Figure 4: Connection of the mains voltage and the load

o Connect the device to KNX. For this, use a KNX connection terminal.
o If necessary, connect potential-free contacts to the inputs (Figure 5).
i Use suitable terminals to connect potential-free contacts to the control cable.

1473-1-7829 | Rev. 01 | 3.2012 Page 7 of 144


 
Installation, electrical connection and operation

i The reference potential "com" may only be switched together with the reference potentials
of other devices of the same type (!).

Figure 5: Connection of the extension inputs

o Install the device in a concealed box.

i Venting louvers must be connected in such a way that they open in travel direction "UP -
n" and close in travel direction "DOWN – o".
i Do not connect any three-phase motors.
i Insulate unused wires of the 6-pin control cable against each other and outside voltage.
i To avoid interference from EMC radiation, the cables of the extension inputs should not be
run in parallel to cables carrying voltage.

1473-1-7829 | Rev. 01 | 3.2012 Page 8 of 144


 
Installation, electrical connection and operation

2.4 Commissioning
After installation and connection of the bus line, the mains voltage and of all electrical loads, the
device can be put into operation. For output 1 only, special commissioning steps have to be
performed prior to programming with the ETS. The following procedure is generally
recommended...

DANGER!
Electrical shock on contact with live parts in the installation environment.
Electrical shocks can be fatal.
Before working on the device, disconnect the power supply and cover up live
parts in the working environment.

Measuring the travelling times


For the purpose of positioning blinds, shutters and awnings or for adjusting the opening angle of
venting louvers, the device needs accurate information about the maximum travelling time for
output 1.
The bus and mains voltage must be switched on.
Recommendation: Device operation using extension inputs (internal effect of input 1 "UP" and 2
"DOWN" on output 1 = as-delivered state).
o If not yet done, move the blind/shutter into the upper end position (open venting louver
completely).
The upper limit-stop position is reached (venting louver opened).
o Start the measuring time and move the blind/shutter by control into the lower end position
(close the venting louver completely).
o Stop the time measurement when the lower limit (when the completely closed) position is
reached.
o Enter the measured value in the ETS (cf. "software description").
i It is wise to perform several time measurements and to take the average of these values.
i The travelling time can also be determined after commissioning with the ETS (bus
operation through communication objects).

Measuring the travelling time extension


When travelling upwards, blinds or shutters have a tendency of moving more slowly due to their
own weight or to external physical influences (e.g. temperature, wind, etc.). The same applies to
venting louvers where opening may take longer than closing.
For this reason, the device takes the configured travelling time extension into account for output
1 when moving upwards or when opening the louvers (MOVE operation / positioning). The
extension is computed as a percentage of the difference of the travelling times in both
directions.
The bus and mains voltage must be switched on.
Recommendation: Device operation using extension inputs (internal effect of input 1 "UP" and 2
"DOWN" on output 1 = as-delivered state).
The blind/shutter (venting louver) must be in the lower end position (venting louver closed).
o If not yet done, move the blind/shutter into the lower end position (close venting louver
completely)
Lower end position reached (venting louver closed).
o Start the measuring time and move the blind/shutter by control into the upper end position
(open the venting louver completely).
o Stop the time measurement when the upper limit (the completely open) position is reached.
o Express the measured value as a percentage of the determined blind/shutter travelling time
and enter the value in the ETS (cf. software description).
i It is wise to perform several time measurements and to take the average of these values.

1473-1-7829 | Rev. 01 | 3.2012 Page 9 of 144


 
Installation, electrical connection and operation

i The travelling time extension can also be determined after commissioning with the ETS
(bus operation through communication objects).

Measuring the slat moving time (only for blinds)


In the case of blinds with slats, the slat moving time is for technical reasons part of the overall
travelling time of the blind. The slat moving time is the time required for a movement between
the slat positions "closed – 100 %" and "open – 0 %". In order to compute the opening angle of
the slats, the device needs an information about the slat moving time.
The slats must be completely closed (as in case of downward travel of the blind).
The bus and mains voltage must be switched on.
Recommendation: Device operation using extension inputs (internal effect of input 1 "UP" and 2
"DOWN" on output 1 = as-delivered state).
o Start the measuring time and open the slats completely by manual control (as in case of
upward travel of the blind).
o Take the measuring time when the completely open position is reached.
o Enter the measured value in the ETS (cf. "software description").
i It is wise to perform several time measurements and to take the average of these values.
i The slat moving time can also be determined after commissioning with the ETS (bus
operation through communication objects).

Commissioning with the ETS


After measuring the times for output 1, the device can be programmed by the ETS.
Commissioning is basically confined to programming of the physical address and the application
data with the ETS.
Project planning and commissioning of the device using the ETS 3.0d with Patch A or newer
versions.
The device is connected and ready for operation.
o Switch on the bus voltage
Check: When the programming button is pressed, the red programming LED must light up.
Switching on the bus voltage causes the device carry out the "Behaviour after bus voltage
return" configured in the ETS. In the state as supplied, this behaviour is set as follows for
the outputs...
Blind output (O1): Drive stop,
O2 (valve output): Close valve. (Valve direction of action: deenergised closed = output
OFF).
o Programming the physical address and the application data with the ETS.

Performing a reference movement (optional)


The device can approach newly preset curtain or louver positions for output 1 only if the current
positions are known. For this purpose, the output must be given the opportunity to synchronise
itself whenever the bus voltage is switched on or after every ETS programming run (physical
address, application program, partial download). This synchronisation is performed by means of
the reference movement.
The bus and mains voltage must be switched on.
o If not yet done, move the curtains to the upper end position (open venting louver
completely).
o Wait until the output relay has switched off (not only the limit switch of the drive).
The reference movement is terminated.

1473-1-7829 | Rev. 01 | 3.2012 Page 10 of 144


 
Installation, electrical connection and operation

i This device stores the curtain, slat or louver positions temporarily. After each bus voltage
failure or after programming with the ETS, the device therefore automatically performs a
reference movement for output 1 before a new position can be approached.
i After bus voltage return, the device generates an "invalid position" message for output 1
which can also be transmitted to the bus, if so configured. The message is withdrawn
(inverted signal value) as soon as a reference movement could be executed.

1473-1-7829 | Rev. 01 | 3.2012 Page 11 of 144


 
Installation, electrical connection and operation

2.5 Operation
In the as-delivered state of the device, extension inputs 1 and 2 have a direct effect on Venetian
blind output 1. In this way, it is possible, for example, for a connected Venetian blind 'on the
building site' to be commissioned and operated simply by applying the bus voltage and without
using additional sensors.
After commissioning using the ETS, extension inputs 1 and 2 behaviour as they are configured
in the ETS. It is also possible to let the inputs internally effect output 1. Alternatively, these
inputs can also affect the bus and control other actuators. The extension inputs then function
like standard KNX/EIB pushbutton interfaces.
i Extension input 3 always behaves independently and, through separate communication
objects, only affects the bus. In the as-delivered state, this extension input is inactive.

If inputs 1 and 2 have an internal effect on output 1, control takes place using the two-area
principle: Input 1 controls the "UP" command and input 2 controls the "DOWN" command.
Venetian blind 1 is controlled according to Table 1...

Input Contact on the input Actuation time Status of output 1


1 Closed (rising flank) Short (< 0.4 s) Short-time operation UP / Stop
1 Closed (rising flank) Long (> 0.4 s) Long time operation UP
2 Closed (rising flank) Short (< 0.4 s) Short-time operation DOWN / Stop
2 Closed (rising flank) Long (> 0.4 s) Long time operation DOWN
1/2 opened Between 0.4 s ... 2.5 s Stop / slat adjustment
(falling flank)
1/2 opened After 2.5 s No reaction
(falling flank)

Table 1: Effect of the extension inputs on output 1

i The times specified in Table 1 and the operating concept "Short - long - short" are preset in
the as-delivered state of the device. However, the appropriate actuation times of inputs 1
and 2 can be configured in the ETS and thus adapted to special requirements (see
page 29). The operating concept cannot be changed when inputs 1 and 2 have an internal
impact.
i After bus voltage return, the device only switches to status change of the extension signals
when the configured time for "delay after bus voltage return" has elapsed (see chapter
4.2.4.1. General functions for extension inputs). Within the delay, any pending flanks or
signals at the inputs are not evaluated and are ignored. The delay time is configured
generally for all the inputs. In the as-delivered state, the time is preset to "0 s".

1473-1-7829 | Rev. 01 | 3.2012 Page 12 of 144


 
Technical data

3 Technical data

General
Mark of approval KNX / EIB
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
Dimensions Ø×H 53×28 mm

KNX/EIB supply
KNX medium TP 1
Commissioning mode S-mode
Rated voltage KNX DC 21 ... 32 V SELV
Power consumption KNX max. 240 mW
Connection mode KNX Connection terminal on control cable

Connection for mains voltage (L)


Connection mode Terminal (enclosed)
Single stranded 1.0 ... 2.5 mm²
Rated voltage AC 110 ... 240 V ~
Mains frequency 50 / 60 Hz

Output 1 (Venetian blind up / down)


Connection mode Terminal (enclosed)
Single stranded 1.0 ... 2.5 mm²
Contact type µ
Switching voltage AC 250 V ~
Switching current AC1 3A
Switch-on current 200 µs max. 90 A
Switch-on current max. 80 A (1 ms)
Minimum switching current AC 100 mA
Motors 230 V 600 VA
Motors 110 V 300 VA

Inputs (I1, I2, I3)


Input type Potential-free
Control cable (preterminated) YY6x0.6
Total length of extension unit cable max. 5 m
Loop resistance max. 500 Ω

1473-1-7829 | Rev. 01 | 3.2012 Page 13 of 144


 
Software specification

4 Software description
4.1 Software specification
ETS search paths: Blind / Switch / Shutter actuator 1gang with binary Inputs

BAU used: ASIC FZE 1066 + µC


KNX/EIB type class: Device with cert. Physical layer + stack
Configuration: S-mode standard
PEI type: "00"Hex / "0" Dec
PEI connector: No connector

Application programs:

No. Short description Name Version from mask


version
1 Multifunctional shutter/blind application. Blind, input/1.1 1.1 705
Additional comprehensive extension for ETS3.0d
function. onwards

1473-1-7829 | Rev. 01 | 3.2012 Page 14 of 144


Software "Blind, input/1.1"
Scope of functions

4.2 Software "Blind, input/1.1"


4.2.1 Scope of functions
General
- 1 x relay output (O1) to control a Venetian blind, roller shutter, awning or venting louver
(mechanical locking of the running directions).
- 3 x extension inputs for potential-free contacts.
- No additional power supply required. The device electronics are supplied fully from the bus
line.
- Actively transmitting feedback or status messages of the output can be delayed globally
after bus voltage return or after ETS programming.
- The delay after bus voltage return can also be set generally for the inputs.
- Effect of the extension inputs can be configured: either internal effect of I1 and I2 on the
Venetian blind output (O1) and I3 on the bus or, alternatively, all three inputs separately on
the bus.
- Debounce time and telegram rate limit can be configured for the extension inputs.

Blind output (O1)


- Operating mode configurable: control of blinds with slats, shutters, awnings or venting
louvers.
- Separately configurable blind travelling times with travelling time extension for moves into
the upper end position.
- For blinds with slats, a slat moving time can be independently configured
- Travel direction change-over time and the times for short and long-time operation (Step,
Move) presettable.
- Blind or slat position feedback telegram. In addition, an invalid blind position or an invalid
travel movement can be reported back. Active (transmitting after changes or cyclically to
the bus) or passive (object readout) feedback functions.
- Assigning of outputs to up to 5 different safety functions (3 wind alarms, 1 rain alarm, 1
frost alarm) optionally with cyclical monitoring.
- An extensive sun protection function with fixed and variable blind or slat positions at the
beginning and at the end of the function can be activated separately for each output.
Dynamic slat offset for slatted blinds included. Also with extended sun protection feature for
integration into sophisticated shading control programs (operated via separate automatic
and disabling object). Optionally also with automatic heating/cooling and presence
detection function.
- Forced position function can be implemented.
- Up to 8 internal scenes configurable.

Extension inputs (I1, I2, I3)


- With separate impact on bus:
Free allocation of the functions switching, dimming, Venetian blind and value encoder.
- Disable object for disabling individual inputs (polarity of the disable object is adjustable).
- Behaviour on bus voltage return can be configured separately for each input.
- Scope of detail for the "Switching" function:
Two independent switching objects available for each input (switching commands can be
configured individually).
Command can be set independently for rising and falling flank (ON, OFF, TOGGLE, no
reaction).
Independent cylical transmission of the switching objects can be selected depending on the
flank or depending on the object value.
- Scope of detail for the "Dimming" function:
Single-surface and double-surface operation possible.
Time between dimming and switching and dimming increments is adjustable.
Telegram repetition and stop telegram transmission possible.

1473-1-7829 | Rev. 01 | 3.2012 Page 15 of 144


Software "Blind, input/1.1"
Scope of functions

- Scope of detail for the "Venetian blind" function:


Command can be set independently for rising flank (no function, UP, DOWN, TOGGLE).
Operation concept configurable (short – long – short or long – short).
Time adjustable between short-time and long-time operation (only for short – long – short)
Adjustable slat adjustment time (time during which a MOVE command can be terminated
by releasing a pushbutton on the input).
- Scope of detail for the "Value encoder" function:
Flank (pushbutton as NO contact, pushbutton as NC contact, switch) and value for flank
can be configured.
Value adjustment for pushbutton long key-press possible for value encoder.
For light scene extension with memory function, the scene can also be saved without prior
recall.

1473-1-7829 | Rev. 01 | 3.2012 Page 16 of 144


Software "Blind, input/1.1"
Software information

4.2.2 Software information


ETS project design and commissioning
For configuration and commissioning of this device, it is necessary to use ETS3.0 from version
"d" onwards. Advantages with regard to downloading (significantly shorter loading times) and
parameter programming can be expected only if this ETS patch version or later versions are
used. The advantages are gained through the use of the mask version 7.5.
The product database required for the ETS3.0 from version "d" or more recent versions is
offered in the *.VD4 format. The corresponding application program has the version number
"1.1".
Safe-state mode
If the device - for instance as a result of errors in the configuration or during commissioning -
does not work properly, the execution of the loaded application program can be halted by
activating the safe-state mode. The safe-state mode does not permit control of the outputs via
the bus or evaluation of the inputs. The device remains passive since the application program is
not being executed (state-of-execution: terminated). Only the system software is still functional
so that the ETS diagnosis functions and also programming of the device continue to be
possible.

Activating the safe-state mode


o Switch off the bus voltage (e.g. by disconnecting the device from the bus line).
o Press and hold down the programming button.
o Switch on the bus voltage (e.g. by connecting the device to the bus line). Release the
programming button only after the programming LED starts flashing slowly.
The safe-state mode is activated. With a new brief press of the programming button, the
programming mode can be switched on and off as usual also in the safe-state mode. The
programming LED will nevertheless continue to flash independently of the programming
mode as long as the safe-state mode is active.
i The safe-state mode can be terminated by switching off the bus voltage or by programming
with the ETS.

Unloading the application program


The application program can be unloaded with the ETS. In this case, the internal effect of the
extension inputs on the Venetian blind output as part of the application program is not available
either. The device does not then function.

1473-1-7829 | Rev. 01 | 3.2012 Page 17 of 144


Software "Blind, input/1.1"
Object table

4.2.3 Object table


Number of communication objects: 28
(max. object number 55 - gaps in between)
Number of addresses (max): 254
Number of assignments (max): 255
Dynamic table management Yes
Maximum table length 255

4.2.3.1 Extension input objects

Function: Switching
Object Function Name Type DPT Flag
10, Switching object X.1 Input 1 ... 3 1 1-bit 1.001 C, W, T 2
h 11,
12

Description 1-bit object for the transmission of switching telegrams (ON, OFF)
(first switching object)

Function: Switching
Object Function Name Type DPT Flag
14, Switching object X.2 Input 1 ... 3 1 1-bit 1.001 C, W, T 2
h 15,
16

Description 1-bit object for the transmission of switching telegrams (ON, OFF)
(second switching object)

Function: Dimming
Object Function Name Type DPT Flag
10, Switching Input 1 ... 3 1 1-bit 1.001 C, W, T 2
h 11,
12

Description 1-bit object for the transmission of switching telegrams (ON, OFF) for the
dimming function.

Function: Dimming
Object Function Name Type DPT Flag
14, Dimming Input 1 ... 3 1 4-bit 3.007 C, W, T 2
h 15,
16

Description 4-bit object for change of relative brightness between 0 and 100 %.

1: The objects for inputs 1 and 2 are not available when inputs have an internal effect on the
Venetian blind output.
2: Each communication object can be read out. For reading, the R-flag must be set.

1473-1-7829 | Rev. 01 | 3.2012 Page 18 of 144


Software "Blind, input/1.1"
Object table

Function: Venetian blind


Object Function Name Type DPT Flag
10, Short time operation Input 1 ... 3 1 1-bit 1.008 C, -, T 2
h 11,
12

Description 1-bit object for short-time operation of a blind.

Function: Venetian blind


Object Function Name Type DPT Flag
14, Long time operation Input 1 ... 3 1 1-bit 1.007 C, W, T 2
h 15,
16

Description 1-bit object for long-time operation of a blind.

Function: Value encoder (dimming value encoder)


Object Function Name Type DPT Flag
10, Value Input 1 ... 3 1 1 byte 5.001 C, -, T 2
h 11,
12

Description 1 byte object to transmit value telegrams (0 ... 255).

Function: Value encoder (temperature value encoder)


Object Function Name Type DPT Flag
10, Temperature value Input 1 ... 3 1 2 byte 9.001 C, -, T 2
h 11,
12

Description 2-byte object for transmission of temperature value telegrams (0 °C ... 40 °C).

Function: Value encoder (brightness value encoder)


Object Function Name Type DPT Flag
10, Brightness value Input 1 ... 3 1 2 byte 9.004 C, -, T 2
h 11,
12

Description 2-byte object for transmission of brightness value telegrams


(0 Lux ... 1,500 Lux).

Function: Value encoder (light scene extension)


Object Function Name Type DPT Flag
10, Light scene extension Input 1 ... 3 1 1 byte 18.001 C, -, T 2
h 11,
12

Description 1-byte object for opening or saving light scenes (1 ... 64).

1: The objects for inputs 1 and 2 are not available when inputs have an internal effect on the
Venetian blind output.
2: Each communication object can be read out. For reading, the R-flag must be set.

1473-1-7829 | Rev. 01 | 3.2012 Page 19 of 144


Software "Blind, input/1.1"
Object table

Function: Disabling function


Object Function Name Type DPT Flag
18, Disabling switching object Input 1 ... 3 1 1-bit 1.003 C, S, - 2
h 19,
20 X.1
Description 1-bit object for disabling the first switching object of an extension input
(polarity configurable).
Only for the "Switching" function!

Function: Disabling function


Object Function Name Type DPT Flag
22, Disabling switching object Input 1 ... 3 1 1-bit 1.003 C, S, - 2
h 23,
24 X.2
Description 1-bit object for disabling the second switching object of an extension input
(polarity configurable).
Only for the "Switching" function!

Function: Disabling function


Object Function Name Type DPT Flag
18, Disabling Input 1 ... 3 1 1-bit 1.003 C, S, - 2
h 19,
20

Description 1-bit object for disabling an extension input (polarity configurable).


Only for the "Dimming", "Venetian blind" and "Value encoder" functions.

1: The objects for inputs 1 and 2 are not available when inputs have an internal effect on the
Venetian blind output.
2: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.

1473-1-7829 | Rev. 01 | 3.2012 Page 20 of 144


Software "Blind, input/1.1"
Object table

4.2.3.2 Venetian blind output objects

Function: Safety function


Object Function Name Type DPT Flag
3 Wind alarm 1 Output 1 1-bit 1.005 C, S, - 1
h
Description 1-bit object for activation or deactivation of the first wind alarm
("0" = wind alarm deactivated / "1" = wind alarm activated).

Function: Safety function


Object Function Name Type DPT Flag
4 Wind alarm 2 Output 1 1-bit 1.005 C, S, - 1
h
Description 1-bit object for activation or deactivation of the second wind alarm
("0" = wind alarm deactivated / "1" = wind alarm activated).

Function: Safety function


Object Function Name Type DPT Flag
5 Wind alarm 3 Output 1 1-bit 1.005 C, S, - 1
h
Description 1-bit object for activation or deactivation of the third wind alarm
("0" = wind alarm deactivated / "1" = wind alarm activated).

Function: Safety function


Object Function Name Type DPT Flag
6 Rain alarm Output 1 1-bit 1.005 C, S, - 1
h
Description 1-bit object for activation or deactivation of the rain alarm
("0" = rain alarm deactivated / "1" = rain alarm activated).

Function: Safety function


Object Function Name Type DPT Flag
7 Frost alarm Output 1 1-bit 1.005 C, S, - 1
h
Description 1-bit object for activation or deactivation of the frost alarm
("0" = frost alarm deactivated / "1" = frost alarm activated).

Function: Long time operation


Object Function Name Type DPT Flag
36 Long time operation Output 1 1-bit 1.008 C, S, - 1
h
Description 1-bit object for activation of long time operation

1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.

1473-1-7829 | Rev. 01 | 3.2012 Page 21 of 144


Software "Blind, input/1.1"
Object table

Function: Short time operation


Object Function Name Type DPT Flag
37 Short time operation Output 1 1-bit 1.007 C, S, - 1
h
Description 1-bit object for activation of short time operation or for stopping a drive
movement.

Function: Forced position


Object Function Name Type DPT Flag
38 Forced position Output 1 2-bit 2.008 C, S, - 1
h
Description 2-bit object for forced control. The object state after bus voltage return can be
predefined by means of a parameter.

Function: Light scene function


Object Function Name Type DPT Flag
39 Scene extension Output 1 1 byte 18.001 C, S, - 1
h
Description 1-byte object for recalling scenes or for storing new scene values.

Function: Sun protection function


Object Function Name Type DPT Flag
41 Automatic mode Output 1 1-bit 1.003 C, S, - 1
h
Description 1-bit object for activation or deactivation of the automatic sun protection in the
extended sun protection mode
("1" = automatic mode activated / "0" = automatic mode deactivated). The
object is only visible, if the automatic sun protection is to be tracked
immediately when the state of the automatic object changes (parameter
setting).

Function: Sun protection function


Object Function Name Type DPT Flag
42 Automatic mode disable Output 1 1-bit 1.003 C, S, - 1
h
Description 1-bit object for disabling of the automatic sun protection in the extended sun
protection mode. The polarity can be configured. The object is only visible, if
the automatic sun protection is to be tracked immediately when the state of
the automatic object changes (parameter setting).

1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.

1473-1-7829 | Rev. 01 | 3.2012 Page 22 of 144


Software "Blind, input/1.1"
Object table

Function: Sun protection function


Object Function Name Type DPT Flag
42 Automatic mode Output 1 1-bit 1.003 C, S, - 1
h
Description 1-bit object for activation or deactivation of the automatic sun protection in the
extended sun protection mode. The polarity can be configured. The object is
only visible, if the automatic sun protection is to be tracked only when the state
of the automatic object changes next time (parameter setting).

Function: Sun protection function


Object Function Name Type DPT Flag
43 Direct operation disable Output 1 1-bit 1.003 C, S, - 1
h
Description 1-bit object for disabling direct operation in the extended sun protection mode
(direct operation = Move / Step / Position / Scene). The polarity can be
configured.

Function: Sun protection function


Object Function Name Type DPT Flag
44 Sunshine / shading facade Output 1 1-bit 1.002 C, S, - 1
h
Description 1-bit object for activation or deactivation of sun shading in the simple or
extended sun protection mode (sun / no sun). The polarity can be configured.

Function: Sun protection function


Object Function Name Type DPT Flag
45 Sunsh./shading position2 Output 1 1 byte 5.001 C, S, - 1
h
Description 1-byte object for presetting a variable position value (0…255) for the height of
the Venetian blind or roller shutter height or the venting louver position when
the sun protection is active.

Function: Sun protection function


Object Function Name Type DPT Flag
46 Slat pos. Sunshine / shading Output 1 1 byte 5.001 C, S, - 1
h
Description 1-byte object for presetting a variable slat position value (0…255) when the
sun protection is active.

1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
2: The object designation varies with the type of blind (Venetian blind, roller shutter / awning,
venting louver).

1473-1-7829 | Rev. 01 | 3.2012 Page 23 of 144


Software "Blind, input/1.1"
Object table

Function: Sun protection function


Object Function Name Type DPT Flag
47 Sunshine slat position offset Output 1 1 byte 6.001 C, S, - 1
h
Description 1-byte object for presetting a slat position angle (- 100 % … +100 % / smaller
or larger position angles are treated as + or – 100 %) for 'manual'
readjustment of the slat position during active sun protection.

Function: Sun protection function – automatic heating/cooling


Object Function Name Type DPT Flag
48 Heating/cooling presence Output 1 1-bit 1.018 C, S, - 1
h
Description 1 -bit object for activation of the presence mode during
automatic heating/cooling. The polarity can be configured. This object is
generally linked with presence detectors.

Function: Sun protection function – automatic heating/cooling


Object Function Name Type DPT Flag
49 Heating/cooling switchover Output 1 1-bit 1.100 C, S, - 1
h
Description 1-bit object for switching over between heating and cooling operation during
automatic heating/cooling. The polarity can be configured. This object is
generally linked with room temperature controllers
(object "heating/cooling switchover").

Function: Position feedback


Object Function Name Type DPT Flag
50 Position feedback 2 Output 1 1 byte 5.001 C, -, T, R3
h
Description 1-byte object for position feedback of the Venetian blind or roller shutter height
or louver position (0…255).

Function: Position feedback


Object Function Name Type DPT Flag
51 Slat position feedback Output 1 1 byte 5.001 C, -, T, R 3
h
Description 1-byte object for position feedback of the slat position (0…255) if one shutter
is controlled.

1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
2: The object designation varies with the type of blind (Venetian blind, roller shutter / awning,
venting louver).
3: The communication flags are set automatically depending on the configuration. "T" flag for
active signalling object; "R" flat for passive status object.

1473-1-7829 | Rev. 01 | 3.2012 Page 24 of 144


Software "Blind, input/1.1"
Object table

Function: Position feedback


Object Function Name Type DPT Flag
52 Invalid position feedback Output 1 1-bit 1.002 C, -, T, R 1
h
Description 1-bit object for reporting back an invalid position of the Venetian blind or roller
shutter height or louver position ("0" = position valid / "1" = position invalid).

Function: Drive movement feedback


Object Function Name Type DPT Flag
53 Drive movement feedback Output 1 1-bit 1.002 C, -, T, R 1
h
Description 1-bit object for feedback of an active drive movement
(output energised - up or down).
("0" = no drive movement / "1" = drive movement).

Function: Presetting the position


Object Function Name Type DPT Flag
54 Position 2 Output 1 1 byte 5.001 C, S, - 3
h
Description 1-byte object for presetting a position value (0…255) for the height of the
Venetian blind or roller shutter or the venting louver position in direct
operation.

Function: Presetting the position


Object Function Name Type DPT Flag
55 Slat position Output 1 1 byte 5.001 C, S, - 3
h
Description 1-byte object for presetting a slat position value (0…255) in direct operation.

1: The communication flags are set automatically depending on the configuration. "T" flag for
active signalling object; "R" flat for passive status object.
2: The object designation varies with the type of blind (Venetian blind, roller shutter / awning,
venting louver).
3: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.

1473-1-7829 | Rev. 01 | 3.2012 Page 25 of 144


Software "Blind, input/1.1"
Functional description

4.2.4 Functional description

4.2.4.1 General functions for extension inputs

Effect of the extension inputs


The device possesses extension inputs, which can have an internal effect on the Venetian blind
output or, alternatively, affect the KNX/EIB separately, depending on the ETS configuration.
With the internal effect, inputs 1 and 2 directly operate the Venetian blind output. This
configuration also corresponds to the as-delivered status (unprogrammed device). In this way, it
is possible, for example, for a connected Venetian blind 'on the building site' to be
commissioned and operated simply by applying the bus voltage and without using additional
sensors.
With the effect on the bus, the inputs can, independently of one another, transmit telegrams for
switching or dimming for Venetian blind control or value encoder use (dimming value encoder,
light scene extension). They then function like a pushbutton interface.
The parameter "Effect of the extension inputs" on the "General" parameter page defines the use
of the inputs.

o Set the parameter to "I1 & I2 internally on O1, I3 separately on the bus".
The extension inputs 1 and 2 only directly affect the internal Venetian blind output of the
device. For two-area operation, input 1 operates the "UP" command and input 2 the
"DOWN" command. Input 3 behaves independently and, through separate communication
objects, only affects the bus.
Venetian blind output 1 is controlled according to Table 2...

Input Contact on the input Actuation time Status of output 1


1 Closed (rising flank) Short (< 0.4 s) Short-time operation UP / Stop
1 Closed (rising flank) Long (> 0.4 s) Long time operation UP
2 Closed (rising flank) Short (< 0.4 s) Short-time operation DOWN / Stop
2 Closed (rising flank) Long (> 0.4 s) Long time operation DOWN
1/2 opened Between 0.4 s ... 2.5 s Stop / slat adjustment
(falling flank)
1/2 opened After 2.5 s No reaction
(falling flank)

Table 2: Effect of the extension inputs on output 1

i The times specified in Table 2 and the operating concept "Short - long - short" are preset in
the as-delivered state of the device. However, the appropriate actuation times of inputs 1
and 2 can be configured in the ETS and thus adapted to special requirements (see
page 29). The operating concept cannot be changed when inputs 1 and 2 have an internal
impact.
i After bus voltage return, the device only switches to status change of the extension signals
when the configured time for "delay after bus voltage return" has elapsed (see chapter
4.2.4.1. General functions for extension inputs). Within the delay, any pending flanks or
signals at the inputs are not evaluated and are ignored. The delay time is configured
generally for all the inputs. In the as-delivered state, the time is preset to "0 s".
It is also possible to configure a general telegram rate limit. In this case no more telegrams
are transmitted to the bus in 17 seconds (permanently defined, cyclical time interval) than
are specified in the ETS.

o Set the parameter to "I1, I2 & I3 separately on the bus".

1473-1-7829 | Rev. 01 | 3.2012 Page 26 of 144


Software "Blind, input/1.1"
Functional description

The three inputs of the device affect the KNX/EIB independently of the Venetian blind
output and each other. Depending on the ETS configuration, the functions "Switching",
"Dimming", "Venetian blind" or "Value encoder" can be set (see chapter 4.2.4.3.1. Function
configuration of the extension inputs).
The "No function" setting deactivates the appropriate input. With the "Venetian blind"
setting, the input objects can be connected to the objects of the Venetian blind output using
group objects. This allows control of the device using its own inputs, even if the extensions
are affecting the bus (e.g. with group control of multiple actuators during installation).

Delay after bus voltage return


It is possible to specify separately for each input whether a reaction should take place after a
device reset (bus voltage return or ETS programming operation). This means that a defined
telegram can be transmitted to the bus according to the input signal or with forced control. The
configured" Delay after bus voltage return" for the extension inputs on the "General" parameter
page must have elapsed fully by the time the set reaction is executed. Within the delay, any
pending flanks or signals at the inputs are not evaluated and are ignored. The delay time is
configured generally for all the inputs. In the as-delivered state of the device, the time is preset
to "0 s".

Telegram rate limit


It is possible to configure a general telegram rate limit using the parameter of the same name
on the "General" parameter page. If the telegram rate limit is enabled, no more telegrams are
transmitted to the bus in 17 seconds (permanently defined, cyclical time interval) than is
specified in the ETS. This avoids fast flank changes at the inputs causing an unpermissibly high
bus load.

i A telegram rate limit does not influence a configured delay after bus voltage return. These
two functions can be combined in any way.

1473-1-7829 | Rev. 01 | 3.2012 Page 27 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.2 General functions for the Venetian blind output


Delay after bus voltage return
To reduce telegram traffic on the bus line after bus voltage activation (bus reset), after
connection of the device to the bus line or after programming with the ETS, it is possible to
delay all actively transmitted feedback telegrams of the actuator output. For this purpose, a
channel-independent delay can be specified for the output 1 using the parameter "Delay after
bus voltage return" on the "General" parameter page. Only after the configured time elapses are
feedback telegrams for initialisation transmitted to the bus.
Which of the telegrams is actually delayed and which is not can be specified for each signalling
or status function separately.

i The delay has no effect on the behaviour of the output. Only the bus telegrams for
feedback are delayed. The output can also be controlled over the bus during the delay after
bus voltage return.
i A setting of "0" for the delay after bus voltage return deactivates the delaying function
altogether. In this case, any messages, if actively transmitted, will be transmitted to the bus
without any delay.

1473-1-7829 | Rev. 01 | 3.2012 Page 28 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.3 Channel-orientated functions for extension inputs

4.2.4.3.1 Function configuration of the extension inputs


The following section contains descriptions of the various functions that can be configured in the
ETS independently for each input. The functions "Switching", "Dimming", "Venetian blind" or
"Value encoder" can be set.
It should be noted that the extension inputs 1 and 2 can optionally affect the internal Venetian
blind output of the device (see page 26-27). In this case, inputs 1 and 2 do not have separate
communication objects and are permanently configured to the Venetian blind function in the
ETS. These inputs can only be given a limited configuration.
i Extension input 3 always behaves independently and, through separate communication
objects, only affects the bus.

Internal effect of the extension inputs 1 and 2


Inputs 1 and 2, can either have an internal effect on the Venetian blind output or, alternatively,
affect the KNX/EIB separately. The parameter "Effect of the extension inputs" on the "General"
parameter page defines the effect of the inputs (see page 26-27).
With the internal effect, inputs 1 and 2 directly operate the Venetian blind output. This
configuration corresponds to the as-delivered state (unprogrammed device). With an internal
effect, the operating concept (evaluation of short time and long time operation) is set
permanently to "Short - long - short". However, the appropriate actuation times of inputs 1 and 2
can be configured in the ETS and thus adapted to special requirements. This means that it is
possible, on parameter pages "I1 - General" and "I2 - General" to configure the "Time between
short and long time operation" (T1) and the "Slat adjustment time" (T2) (Figure 6).

Figure 6: Operating concept "Short - long - short" when inputs 1 and 2 have an internal impact

With a rising flank, input 1 always operates the movement direction "UP". Input 2 operates the
movement direction "DOWN". After bus voltage return, unoperated inputs do not show any
special behaviour.

i In the as-delivered state, the times between short and long time operation and the slat
adjustment times of the inputs are matched to the time of short time operation and the
movement time (long time operation) of the Venetian blind output. If the times at the inputs
are changed, then it should be observed that, for flawless operation of the blind or venting
louver at output 1, the times of the output may also need to be adjusted.
i It is not possible to actuats the inputs simultaneously.
i After bus voltage return, the device only switches to status change of the extension signals
when the configured time for "delay after bus voltage return" has elapsed (see page 27).
Within the delay, any pending flanks or signals at the inputs are not evaluated and are
ignored. The delay time is configured generally for all the inputs. In the as-delivered state,
the time is preset to "0 s".
Switching function
For each input whose function is set to "Switching", the ETS displays two 1-bit communication
objects (switching object X.1 and X.2). It is possible to use these two objects to transmit
different switching telegrams to the bus depending on the signal flank at the input. The input

1473-1-7829 | Rev. 01 | 3.2012 Page 29 of 144


Software "Blind, input/1.1"
Functional description

parameter on the parameter page "Ix - General " (x = 1, 2, 3) can be used to define which object
value is transmitted to the bus when there is a rising or falling flank at the input (no reaction,
ON, OFF, TOGGLE - switchover of the object value). No distinction is made between a brief or
long signal flank/actuation in the "Switching" function.

Response to bus voltage return


After a device reset (bus voltage return or ETS programming operation), the communication
objects of the input can be initialised. For this, the "Behaviour on bus voltage return" parameter
should be configured to the required reaction. In the settings "On telegram" or "Off telegram"
telegrams are transmitted actively to the bus according to this requirement. In the "Transmit
current input status" setting, the device evaluates the static signal status of the input and,
according to this, transmits the appropriately configured telegram to the bus (contact closed at
the input = telegram as with rising flank; contact open at input = telegram as with falling flank).
If, in this case, the flank command dependent on the current status is configured to "No
reaction", the device does not transmit a telegram to the bus on initialisation.
If, in the ETS, a delay is set for the extension inputs after bus voltage return, the device only
transmits the telegrams when the delay has elapsed.

Cyclical transmission
Optionally, the object values can be transmitted cyclically to the bus for the "Switching" function.
For this, the transmission criteria must first be defined in the ETS. The "Transmit cyclically ?"
parameter on the parameter page "Ix - Transmit cyclically" (x = 1, 2, 3) specifies with which
value cyclical transmission should take place. Depending on requirements, it is possible to
transmit cyclically via both or just one switching object(s). In addition, it is possible to define the
cycle time separately for both switching objects in the ETS.
The object value entered in the switching objects by the device on a flank change or externally
by the bus is always transmitted cyclically. The object value is then also transmitted cyclically
when "no reaction" is assigned to a rising or falling flank. Cyclical transmission also takes place
directly after bus voltage return, if the reaction after bus voltage return corresponds to the
transmission criterion for cyclical transmission. During an active disable, no cyclical
transmissions take place via the disabled input.

Dimming function
For each input whose function is set to "Dimming", the ETS indicates a 1-bit "Switching" and a
4-bit "Dimming" object. In general, the device transmits a switching telegram on a short time
input signal (triggered by the rising flank of a closed contact) and a dimming telegram on a long
signal. In the standard configuration, the device transmits a telegram for stopping the dimming
action after a long signal.
The length of time the input signal (closed pushbutton or switch) must last until a long actuation
is detected can be set using the parameter "Time between switching and dimming" on the
parameter page "Ix - General" (x = 1, 2, 3).

Operating principle
The "Operation" parameter specifies the operating principle. In the presetting of the dimming
function, two-surface operation is specified here. This means that the input transmits a telegram
for switching on after a short signal length and a telegram for increasing the brightness after a
long signal length ("Brighter"). Alternatively, the device can transmit a telegram for switching off
after a short signal length and a telegram for reducing the brightness after a long signal length
("Darker").
With a single-surface dimming function, the input transmits switch-on and switch-off telegrams
("TOGGLE") in an alternating pattern for each short signal. After long signals, the device
transmits "brighter" and "darker" telegrams in an alternating pattern.

1473-1-7829 | Rev. 01 | 3.2012 Page 30 of 144


Software "Blind, input/1.1"
Functional description

i With single-surface dimming, the following should be observed: if a dimming actuator is to


be controlled from several locations, a faultless single-surface operation requires that the
addressed actuator reports its switching state back to the 1-bit object of the input and that
the 4-bit objects of all the sensors are interlinked. The sensor device would otherwise not
be able to detect that the actuator has been addressed from another sensor, in which case
it would have to be actuated twice during the next use in order to produce the desired
reaction.
The additional input parameters on the parameter page "Ix - General" can be used to specify in
which increments brighter or darker dimming take place, whether a stop telegram is transmitted
on a falling flank or whether the dimming telegram is to be repeated cyclically.

Response to bus voltage return


After a device reset (bus voltage return or ETS programming operation), the communication
object "Switching" of the input can be initialised. For this, the "Behaviour on bus voltage return"
parameter should be configured to the required reaction. In the settings "On telegram" or "Off
telegram" telegrams are transmitted actively to the bus.
If, in the ETS, a delay is set for the extension inputs after bus voltage return, the device only
transmits the telegrams when the delay has elapsed.
After a device reset, the "Dimming" object is always initialised with "0".

Venetian blind function


For each input, whose function is set to "Venetian blind", the ETS indicates the two 1-bit objects
"Short time operation" and "Long time operation".
For the control of Venetian blind, roller shutter, awning or similar drives, the device supports two
operation concepts for the Venetian blind function in which the telegrams are transmitted in
different time sequences. The device can therefore be used to operate a wide variety of drive
configurations. In the ETS, the operating concept of an input is defined using the parameter of
the same name on the parameter page "Ix - General" (x = 1, 2, 3). The following settings are
possible...

Figure 7: Operation concept "short – long – short"

Operation concept for the Venetian blind function


Operation concept "short – long – short":
In the operation concept "short – long – short", the input shows the following behaviour:
- Immediately after a rising flank (closed pushbutton or switch) the input transmits a short
time telegram onto the bus. Pressing the button stops a running drive and starts time T1
("time between short time and long time operation"). If the a falling flank is detected within
T1 (closed pushbutton or switch), no further telegram will be transmitted. This short time
serves the purpose of stopping a continuous movement.
The "Time between short time and long time command" in the input parameters should be
selected shorter than the short time operation of the actuator to prevent a jerky movement
of the shutter.
- If the button is kept depressed longer than T1, the input transmits a long time telegram
after the end of T1 for starting up the drive and time T2 ("slat adjusting time") is started.

1473-1-7829 | Rev. 01 | 3.2012 Page 31 of 144


Software "Blind, input/1.1"
Functional description

- If a falling flank is detected within the slat adjustment time, the input transmits an additional
short time telegram. This function is used for adjusting the slats of a blind. The function
permits stopping the slats in any position during their rotation.
The "slat adjusting time" should be chosen as required by the drive for a complete rotation
of the slats. If the "slat adjusting time" is selected longer than the complete running time of
the drive, a pushbutton function is possible as well. This means that the drive is active only
when a button connected to the input is kept depressed.
- If the button is kept depressed longer than T2, the input transmits no further telegram. The
drive remains on until the end position is reached.

Figure 8: Operation concept "long – short"

Operation concept "long – short":


In the operation concept "long – short", the input shows the following behaviour:
- Immediately on pressing the button, the input transmits a long time telegram. The drive
begins to move and time T1 ("slat adjusting time") is started.
- If a falling flank is detected within the slat adjustment time, the input transmits a short time
telegram. This function is used for adjusting the slats of a blind. The function permits
stopping the slats in any position during their rotation.
The "slat adjusting time" should be chosen as required by the drive for a complete rotation
of the slats. If the "slat adjusting time" is selected longer than the complete running time of
the drive, a pushbutton function is possible as well. This means that the drive is active only
when a button connected to the input is kept depressed.
- If the button is kept depressed longer than T1, the input transmits no further telegram. The
drive remains on until the end position is reached.

Flank evaluation
The parameter "Command on rising flank" on the parameter page "Ix - General" (x = 1, 2, 3)
specifies the direction of movement of the short time or long time telegram. In the "TOGGLE"
setting (single-surface operation) the input switches the direction of the short and long time
telegram each time there is a new signal. Several short time telegrams in succession have the
same direction.
i If the actuator is to be controlled from several locations, a faultless single-surface actuation
requires that the all long time objects of the sensor devices are interlinked. A sensor device
would otherwise not be able to detect that the actuator has been addressed from another
sensor, in which case it would have to be actuated twice during the next use in order to
produce the desired reaction.

Response to bus voltage return


After a device reset (bus voltage return or ETS programming operation), the communication
object "Long time operation" of the input can be initialised. For this, the "Behaviour on bus
voltage return" parameter should be configured to the required reaction. In the settings "Up" or
"Down", telegrams are transmitted actively to the bus.
If, in the ETS, a delay is set for the extension inputs after bus voltage return, the device only
transmits the telegrams when the delay has elapsed.
After a device reset, the "Short time operation" object is always initialised with "0".

1473-1-7829 | Rev. 01 | 3.2012 Page 32 of 144


Software "Blind, input/1.1"
Functional description

Value transmitter function


For each input whose function is set to "Value encoder", the ETS indicates either a 1-byte or a
2-byte object. The data format of the value object is dependent on the set function of the value
encoder. The "Function as" parameter on the parameter page "Ix - General" (x = 1, 2, 3) defines
the function on one of the following value encoder applications...
- Dimming value encoder (1-byte),
- Temperature value encoder (2-bytes),
- Brightness value encoder (2-bytes),
- Light scene extension without memory function (1-byte),
- Light scene extension with memory function (1-byte).
The dimming value encoder, temperature and brightness value encoder different in data format
and in the range of values. The independent function of the light scene extension is special and
is described below.

Dimming value encoder, temperature and brightness value encoder


In the function as a dimming value encoder, the input can transmitted unformatted integers in
the range 0 ... 255 to the bus. As a brightness value encoder, the input transmits formatted
floating point values in the range 0 … 1500 Lux and, as a temperature value encoder, in the
range 0 … 40 °C. Table 3 shows a summary of the value ranges of the value encoders. The
values to be transmitted are configured in the ETS and can be adjusted later during device
operation (see value adjustment below).
The flank evaluation of the device means that it can transmit values only on a rising flank, only
on a falling flank or on a rising and falling flank. In this way, it is possible to make adjustments to
the contact connected at the input (pushbutton as NC contact or NO contact and switch).

Value encoder type Function Lower numerical Upper numerical


limit limit
Dimming value encoder 0 ... 255 0 255
Temperature value Temperature 0 °C 40 °C
transmitter value
Brightness value transmitter Brightness value 0 lux 1,500 lux

Table 3: Value ranges of dimming value encoder, temperature and brightness value encoder

Value adjustment for dimming value encoder, temperature and brightness value encoder
With the dimming value encoder and the temperature and brightness value encoder, the value
to be transmitted can be adjusted at any time during device operation. A value adjustment can
only be configurable in the ETS when the value is to be transmitted only on a rising flank or only
on a falling flank, i.e. a pushbutton is connected to the input.
A value adjustment is introduced by a long signal at the input (> 5 s) and continues for as long
as the signal is detected as active, i.e. the pushbutton is actuated. With the first adjustment after
commissioning, the value programmed by the ETS is increased cyclically by the step width
configured for the dimming value encoder and transmitted. The step width of the
temperature value encoder (1 °C) and the brightness value encoder (50 Lux) is permanently
defined. The previously transmitted value is saved after releasing the pushbutton. The next long
pushbutton actuation adjusts the saved value and the direction of the value adjustment
changes.
The time between two telegrams on adjusting values can be configured in the ETS.

Example of value adjustment (Figure 9):


- Function as dimming value encoder
- Transmit value on = Rising flank
- Value configured in the ETS for rising flank = 17
- Step width = 5

1473-1-7829 | Rev. 01 | 3.2012 Page 33 of 144


Software "Blind, input/1.1"
Functional description

Figure 9: Example to change the value for dimming value encoder

i There is no value over- or underrun on adjustment. If, during an adjustment, the maximum
or minimum value is reached (see Table 3), no more telegrams are transmitted.
i To ensure that, during a value adjustment, for example the controlled lighting switches off
or switches on at the maximum, the limit values (e.g. the values "0" or "255") are always
transmitted when the limits of the adjustable range are reached. This also takes place
when the configured step width of these values is not immediately taken into account (see
example above: step width = 5; value "2" is transmitted, then value "0").
In this case, to ensure that the original starting value can be reset on resetting with a
change to the adjustment direction, the first value jump is not equal to the preset step width
(see example above: step width = 5; value "0" is transmitted, then values "2"; "7" etc.).
i The newly adjusted values are stored in RAM. After a device reset (bus voltage failure or
ETS programming operation), the adjusted values are replaced by the values originally
configured in the ETS.

Light scene extension


With a configuration as a light scene extension without a memory function, it is possible to recall
a light scene, which is stored in an external bus subscriber (e.g. light scene pushbutton sensor)
With a rising, falling or rising and falling flank, the light scene number configured in the ETS is
immediately transmitted to the bus.
With a configuration as a light scene extension with a memory function, it is possible to
generate a memory telegram according to the light scene to be transmitted. For this, the
appropriate memory telegram is transmitted for a long signal according to the configured flank
evaluation (pushbutton as NC contact or NO contact - not as switch!). In this case, the time for
long actuation can be configured (but not to below 5 s). With short actuation < 1 s, the
configured light scene number (without memory telegram) is transmitted. If the actuation last
longer than 1 s but less than 5 s, no telegram is triggered.
In addition, there is the option of only transmitting a memory telegram without prior light scene
recall. In this case, the parameter "Only memory function ?" must be set to "Yes".

Examples for a light scene extension with memory function (Figure 10):
1.) Only memory function = No
2.) Only memory function = Yes

1473-1-7829 | Rev. 01 | 3.2012 Page 34 of 144


Software "Blind, input/1.1"
Functional description

Figure 10: Example of scene storage

"Only memory function = No":


If a rising or falling flank is detected at the input (according to the configuration), the time
recording operation begins. If actuation ceases during the first second, the appropriate light
scene recall takes place immediately. If the signal length is longer, then the memory telegram is
transmitted after 5 s.

"Only memory function = Yes":


The memory telegram is transmitted immediately after detection of the appropriate signal flank.

Behaviour on bus voltage return for value encoder and light scene extension
After a device reset (bus voltage return or ETS programming operation), the communication
object of the value encoder or light scene extension can be initialised. For this, the "Behaviour
on bus voltage return" parameter should be configured to the required reaction. The setting is
dependent on the value encoder function and flank evaluation selected in the ETS. In the
settings "Reaction as rising flank" or "Reaction as falling flank", telegrams are transmitted
actively to the bus according to the configuration in the ETS. In the "Transmit current input
status" setting, the device evaluates the static signal status of the input and, according to this,
transmits the appropriately configured telegram to the bus (contact closed at the input =
telegram as with rising flank; contact open at input = telegram as with falling flank). This setting
can only be configured with "Transmit value on = rising and falling flank (switch)".
If, in the ETS, a delay is set for the extension inputs after bus voltage return, the device only
transmits the telegrams when the delay has elapsed.

1473-1-7829 | Rev. 01 | 3.2012 Page 35 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.3.2 Disabling function for extension inputs


The extension inputs can be separately disabled via the bus using 1-bit objects. With the
"Switching" function, it is possible to disable the two switching objects of an input independently
of each other.
With an active disabling function, signal flanks at the input are ignored by the device related to
the affected objects.

Each input or each switching object can execute a specific independent reaction at the
beginning or end of a disable. This reaction is specified on the parameter page
"Ix - disable" (x = 1, 2, 3) in the ETS and is dependent on the flank evaluation defined for the
affected input. In so doing, it is possible to configure to "No reaction". Only in this case are
dimming or Venetian blind control operations or value adjustments completed during an active
disable and only then the input locked. In all other cases, the configured disabling command is
executed immediately at the beginning of disabling.
In the "Transmit current input status" setting, the device evaluates the current static signal
status of the input and, according to this, transmits the appropriately configured telegram to the
bus (contact closed at the input = telegram as with rising flank; contact open at input = telegram
as with falling flank).

A disabling function is activated or deactivated by the corresponding 1-bit object. The telegram
polarity can be set in the ETS for each disabling object. The disabling object is always inactive
after a device reset. Even with an inverted polarity "Disabling = 0 (Enabling = 1)", a "0" telegram
must first be received after a reset until the appropriate disabling function is activated.

i Updates to disabling objects with the same telegram polarity (disabling -> disabling or
enabling -> enabling) do not show a reaction.
i With cyclical transmission in the "Switching" function: during an active disable, cyclical
transmission does not take place via the disabled input switching object. Cyclical
transmission is continued immediately at the end of the disabling with the last object value
written to the object, providing that the transmit criterion for cyclical transmission is fulfilled
(transmit on ON, on OFF or on ON and OFF).

1473-1-7829 | Rev. 01 | 3.2012 Page 36 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.4 Channel-oriented functions for the Venetian blind output

4.2.4.4.1 General settings


Operating mode
Output 1 of the device can be independently configured for the drive type connected by defining
the operating mode. The device permits controlling slatted Venetian blinds, roller shutters,
awnings and also venting louvers. Depending on the preset operating mode, the ETS adapts
the parameters and communication objects for all functions of an output.
For example, in the "Venetian blind" operation mode, there are also parameters and objects for
slat control. There is no slat control in the "Roller shutter / awning" operating mode, but a fabric
stretching function can be configured for awning use. In the "Venting louver" operation mode, a
distinction is made between the "Closing" and "Opening" drive movements, instead of an up or
down movement for Venetian blinds or roller shutters.
In this documentation, Venetian blinds, roller shutters or awnings are also designated with the
term "blind", if the text does not explicitly refer to a particular function (e.g. slat control).
In all modes it is possible to specify positions.

Presetting the operating mode


The parameter "Operating mode" exists on the parameter page "O1 - General".
o Select the required operating mode in the "Operating mode" parameter.
i The "Operating mode" parameter has an influence on many channel-oriented parameters
and communication objects. When the operating mode is changed in the ETS, the
parameters are adapted dynamically so that settings already made or links between group
addresses can be reset. For this reason, the required operating mode should be configured
at the beginning of the channel-oriented device configuration.
i Venting louvers must be connected to the outputs in such a way that they are opened in
the movement direction "up - n" and closed in the movement direction "down - o".
i An awning travels upwards when it is rolled up.

Behaviour in case of bus voltage failure, after bus voltage return or after programming
with the ETS
The preferred contact positions of output 1 after bus voltage return or after ETS programming
can be set. Since the device is equipped with bistable relays, the relay switching state at bus
voltage failure can be defined as well.

Presetting the behaviour after ETS programming


The parameter "Behaviour after ETS programming operation" can be preset on the parameter
page "O1 - General". This parameter can be used to configure the relay behaviour of the output
irrespective of the behaviour after a bus or mains voltage return.
Depending on the selected operating mode, the ETS adapts the designations of the parameter
settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing the louver).
o Set the parameter to "stop".
After programming with the ETS, the device switches the relays of the output to the "stop"
position. A drive movement, if any, will be interrupted.
o Set the parameter to "raising" or "opening the louver".
After programming with the ETS, the device raises the blind or opens the venting louver.
o Set the parameter to "lowering" or "closing the louver".
After programming with the ETS, the device lowers blind or closes the venting louver.

1473-1-7829 | Rev. 01 | 3.2012 Page 37 of 144


Software "Blind, input/1.1"
Functional description

i At the beginning of each ETS programming cycle, the device always executes a "stop"
command for the output.
i The "Behaviour after ETS programming" as configured will be executed after every ETS
application or parameter download. A simple download of the physical address alone or
partial programming of only the group addresses has the effect that this parameter is
disregarded and that the configured "Behaviour after bus or mains voltage return" will be
executed instead.
i After programming with the ETS, the safety functions, the forced positions and the sun
protection function are always deactivated.

Presetting the behaviour in case of bus voltage failure


The parameter "Behaviour in case of bus voltage failure" can be preset under "O1 - General".
The parameter defines the behaviour of the shutter output if only the bus voltage fails.
Depending on the selected operating mode, the ETS adapts the designations of the parameter
settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing the louver).
o Set the parameter to "stop".
In case of bus voltage failure, the device switches the relays of the output to the "stop"
position. A drive movement, if any, will be interrupted.
o Set the parameter to "no reaction".
In the event of bus voltage failure, the relay of the output shows no reaction. Movements
still in progress at the time of failure will still be completed as long as the mains voltage is
still on.
i As the device is supplied solely by the bus voltage, it is not ready for operation between a
bus failure and the setting of the appropriate reaction up to the bus voltage return.
i When there is a bus voltage failure, the current position data is permanently saved
internally, so that these position values can be accurately repositioned after bus voltage
return, should this be configured. The data is stored before the configured reaction for bus
voltage failures takes place and only if the bus voltage has been available before without
interruption for at least 20 seconds after the last reset (storage capacitors sufficiently
charged for storage purposes). The data will not be stored, if the position data is unknown.

The following rules apply for the position data to be stored:


The current blind, slat and louver positions are stored. With Venetian blinds, the height to
be stored is always referred to a slat position of 100 %(cf. "Calculating the slat position").
Positions temporarily approached will be stored also for those outputs that are involved in a
travel movement at the time of data storage. On account of the fact that position data is
stored as integer percentage values (0...100), a minor deviation from the positions reported
back later during bus voltage return (number range 0..255) cannot be avoided.

In case of ETS programming, the saved position data is not lost.


i In case of bus voltage failure, the current states of the forced position control or – if
configured – also the slat offsets of the sun protection positions are stored as well.

Setting the behaviour after bus voltage return


The parameter "Behaviour after bus voltage return" can be preset on parameter page
"O1 - General".
Depending on the selected operating mode, the ETS adapts the designations of the parameter
settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing the louver).
o Set the parameter to "stop".
In case of bus voltage return, the device switches the relays of the output to the "stop"
position. A drive movement, if any, will be interrupted.
o Set the parameter to "raising" or "opening the louver".
After bus voltage return, the device raises the blind or opens the venting louver.

1473-1-7829 | Rev. 01 | 3.2012 Page 38 of 144


Software "Blind, input/1.1"
Functional description

o Set the parameter to "lowering" or "closing the louver".


After bus voltage return, the device lowers the blind or closes the venting louver.
o Set the parameter to "position on bus failure".
After bus voltage return, the forced position value (including slat position for Venetian
blinds) last selected and internally stored before bus voltage failure will be tracked. Before
the positioning movement, the device executes a reference movement.
o Set the parameter to "position approach".
In case of bus voltage return, the connected drive can approach a position (0...100 %)
specified by further parameters. If Venetian blinds are controlled with the device, the slats
can be positioned independently. Before the positioning movement, the device executes a
reference movement.
i "Position on bus failure" setting: If no position values could be stored in case of bus failure
because the position data was unknown (no reference movement executed), the device
shows no reaction with this configuration either.
i The forced position communication object can be initialised separately after bus voltage
return. This has an effect on the reaction of the output when the forced position is
activated.
The configured "Behaviour on bus voltage return" is only executed when no forced position
after a bus voltage return is activated.
i The device only executes the configured "Behaviour on bus voltage return" only if the last
ETS programming of the application or of the parameters ended at least approx. 20 s prior
to switching on the bus voltage. Otherwise (TETS< 20 s), the
"Behaviour after ETS programming" will be adopted also in case of bus voltage return.

1473-1-7829 | Rev. 01 | 3.2012 Page 39 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.4.2 Movement time settings


Determining and configuring short time and long time operation
Short time operation(Step) permits adjusting the slat tilting angle of a blind or the
'slit opening width' of a roller shutter. In most cases, short-time operation is activated by
pressing a Venetian blind pushbutton sensor permitting manual intervention in the blind
controller. When the device receives a short time command while the Venetian blind, roller
shutter, awning or louver is in motion, the drive movement is stopped immediately by the
device.
A long-time operation (Move) is determined by the movement time of the connected Venetian
blind, roller shutter/awning or louver and must therefore not be preset separately. The
movement time must be measured 'manually' and entered into the ETS parameters. The control
of an output by means of a long time or a short time telegram is also designated as 'direct
operation'.
To ensure that the curtain or the louver has definitely reached its end position at the end of long
time operation, the device always prolongs the long time movement by 20 % of the configured
or learnt movement time.
The configured travelling time extension will moreover be taken into account by the device for
all upward movements or all movements into the open position as the drive motors are then
generally not as fast due to the weight of the blind or external physical influences (e.g.
temperature, wind, etc.). Thus, it is ensured that the upper end position is always reached even
in case of uninterrupted long time travel movements.
i A long time or a short time operation can be retriggered by a new incoming long time or
short time telegram.
i A drive movement activated by a safety function is always a long time operation. The
"raising" or "lowering" commands configured in the ETS will equally activate the long time
operation.

Presetting the short time operation


The short time operation is configured independent of the movement time of the blind or of the
louver. The project designer can specify in the ETS whether the output executes only a "stop"
for a travel movement on reception of a short time telegram or whether the output is activated
for a specific duration.
o Set the parameter "Short time operation" on parameter page "O1 - Time settings" to "Yes".
The device activates the output for the time specified under
"Duration of short time operation" when a short time telegram is received and when the
output is not in the process of executing a movement. If the output is executing a travel
movement at the time of telegram reception, the output will only just stop.
o Set the "Short time operation" parameter to "No (only stop)".
The device will only stop the output on reception of a short time telegram, if the output is in
the process of executing a movement. There will be no reaction, if the output is not
executing a movement at the time of telegram reception.
i The configured "Duration of short time operation" should correspond, for a Venetian blind,
to approx. ¼ of the complete slat moving time and for a roller shutter to the full time needed
for opening the roller shutter segments.
i The short time operation is always executed without a movement time extension.

Determining and configuring movement times


For computing positions and also for executing long time operation, the device needs the exact
movement time of the connectedVenetian blind, roller shutter/awning or louver. The movement
time must be measured 'manually' and entered into the ETS configuration. It is important to
determine the movement time accurately to permit positions to be approached with good
precision. Therefore, it is recommended to make several time measurements and to take the
average of these values before entering them into the corresponding parameter. The movement
time corresponds to the duration of a drive movement from the completely open position

1473-1-7829 | Rev. 01 | 3.2012 Page 40 of 144


Software "Blind, input/1.1"
Functional description

(upper end position / awning rolled up) to the completely closed position
(lower end position / awning completely unrolled). Not vice-versa! The movement times are to
be determined as a function of the different types of drives.

Figure 11: Determining the movement time according to the drive type

Setting the movement time of Venetian blinds, roller shutters/awnings and louvers
The measurement of the movement time is described in detail in chapter "Commissioning".
o Enter the exact movement times determined in the course of the commissioning procedure
into the parameters "Venetian blind movement time" or
"Roller shutter/awning movement time" or "Venting louver movement time" on parameter
page "O1 – Times". The maximum travelling time is '59 minutes 59 seconds. The working
principle does not allow longer movement times.
i The configured movement time extension will also be taken into account by the device for
all upward movement or all movements into the open position as the drive motors are then
generally not as fast due to the weight of the blind or external physical influences (e.g.
temperature, wind, etc.).

Determining and configuring the slat moving time (only with slatted Venetian blinds)
If Venetian blinds are controlled, the slats can be positioned independently. To enable the
device to compute slat positions and to report them back to the bus, it is necessary that the
device gets precise information about the time required for a slat rotation. The slat moving time
must in each case be determined and configured 'manually'.
The device is designed in such a way that it can control single-motor Venetian blind drives
without a working position. In this drive mode, the slats are directly adjusted by way of
mechanical linkage when the height of the Venetian blind is changed. The device assumes that
the slats are completely closed when the Venetian blind moves downwards. The actuator
assumes that the slats are completely closed when the Venetian blind moves downwards
(Figure 12). These Venetian blinds are the most common type on the market.

1473-1-7829 | Rev. 01 | 3.2012 Page 41 of 144


Software "Blind, input/1.1"
Functional description

Figure 12: Type 1 - Slatted Venetian blinds with oblique slat position in both travel directions

There are also single-motor Venetian blind systems without a working position the slats of which
are horizontal during an upward travel and oblique during a downward travel. Such Venetian
blind types can also be connected to the device in which case a completely open slat position
corresponds to the slats in horizontal position .

Figure 13: Type 2 - Slatted Venetian blinds with oblique and horizontal slat position

Presetting the slat moving time


The measurement of the slat moving time is described in detail in chapter "Commissioning".
o Set the parameter "Slat moving time" on parameter page "O1 - Times" exactly to the value
determined in the course of the commissioning procedure.
i The slat moving time must be shorter than the preset or learnt blind travelling time.
i The configured or measured movement time extension will also be taken into account
when slats are moved into the completely open position (upward movement).

Determining and configuring the movement time extension and the switchover time
When moving upwards, Venetian blinds, roller shutters or awnings have a tendency of moving
more slowly due to their own weight or to external physical influences (e.g. temperature, wind,
etc.). The same applies to venting louvers where opening may take longer than closing.
For this reason, the device takes the configured travelling time extension into account when
moving upwards or when opening louvers. The extension is computed as a percentage of the
difference of the movement times in both directions.
The movement time extension should be determined separately during commissioning and
entered into the ETS configuration.
The measurement of the movement time extension is described in detail in chapter
"Commissioning".
Example for determining the movement time extension:

1473-1-7829 | Rev. 01 | 3.2012 Page 42 of 144


Software "Blind, input/1.1"
Functional description

- "Movement time" previously determined and configured: TOU= 20 seconds,"


- Time determined for movement from lower to upper end position: TUO= 22 seconds,
- Calculated supplementary movement time: TUO - TOU = 2 seconds ->
2 seconds out of 20 seconds are 10 %,
- Movement time extension to be configured: 10 %.
To protect the drive motors from irreparable damage, a fixed pause during movement direction
switchover can be configured. During the pause, no movement direction is active ("stop"). The
necessary parameter value can normally be found in the technical documents of the drive motor
used. The switchover time is accounted for in every state of operation of the device.

Presetting the movement time extension


o Enter the determined movement time extension (by rounding up the determined extension
value) into the parameter "Movement time extension for upward movement" on parameter
page "O1 - General".

Presetting the switchover time for movement direction changes


o Set the parameter "Switchover time for travel direction change" on parameter page
"O1 - Times" to the required switchover interval.
i In the as-delivered state of the device, the switchover time is generally preset to 1 s.

1473-1-7829 | Rev. 01 | 3.2012 Page 43 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.4.3 Positioning and feedback settings


Computing the blind height or the louver position
The device has a easy-to-use and accurate positioning function. The device calculates the
current position of the connected Venetian blind, roller shutter, awning or louver whenever these
elements are adjusted either by manual or bus control. The calculated position value is a
measure of the height of the blind or of the opening width of the venting louver (Figure 14).

Figure 14: Positions defined as a function of the type of movement

The device derives the positions from the configured travelling time since conventional drives do
not provide feedback about their positions. Thus, the travelling time configured in the ETS is the
reference for all position approaches and of basic importance for the accuracy of the position
calculations. For this reason, the travelling time should be determined with great accuracy in
order to achieve the best possible positioning results.

For positioning purposes, the device calculates the movement time required as a function of the
current position.
Example 1...
The roller shutter connected to the certain output has an overall travelling time of 20 s. The
roller shutter is in its upper end position (0 %). It is to be positioned at 25 %. The device
calculates the movement time required for approaching the desired position:
20 s × 0.25(25 %) = 5 s. The output will then lower the roller shutter for 5 s and thus position the
blind at height of 25 %.

Example 2...
The shutter connected to the certain output has an overall travelling time of 20 s. The shutter is
in the 75 % position. I It is to be positioned at 75 %. The difference between the positions is
50 %. The device calculates the movement time required for bridging the difference between
the positions: 20 s × 0.5(50 %) = 10 s. The output will then lower the roller shutter for 10 s and
thus position the blind at height of 75 %.

With all the upward movements, the configured movement time extension is automatically
added to the calculated movement time.
Example 3...
The roller shutter connected to the certain output has an overall movement time of 20 s. The
roller shutter is in the 75 % position. It is to be positioned at 25 %. The difference between the
positions is 50 %. The device calculates the unextended movement time required for bridging
the difference between the positions:

1473-1-7829 | Rev. 01 | 3.2012 Page 44 of 144


Software "Blind, input/1.1"
Functional description

20 s × 0.5(50 %) = 10 s. Taking the movement time extension into account (e.g. 10 %), the actual
raising time is: 10 s × ((100 % + 10 %(extension)) : 100 %) = 10 s × 1.1 = 11 s. The output will then
raise the roller shutter for 11 s and thus position it at a blind height of 25 %.

When the lower or upper end positions (0 % or 100 %) are approached, the movement time is
always 20 % longer than the overall movement time.
Example 4...
The shutter connected to the certain output has an overall travelling time of 20 s. The shutter is
in the 75 % position It is to be positioned at 100 %. The difference between the positions is
50 %. The device calculates the movement time required for bridging the difference between
the positions: 20 s × 0.5(50 %) = 10 s. As the movement is a limit position movement, the device
adds 20 % of the total movement time:
10 s + (20 % : 100 %) · 20 s = 14 s. The output will then lower the roller shutter for 14 s and
thus positions it safely at a blind height of 100 %.

Example 5:
The roller shutter connected to the certain output has an overall movement time of 20 s. The
roller shutter is in the 50 % position. It is to be positioned at 0 %. The difference between the
positions is 50 %. The device calculates the unextended movement time required for bridging
the difference between the positions: 20 s × 0.5(50 %) = 10 s. As the movement is a limit position
movement, the device also adds 20 % of the total movement time:
10 s + (20 % : 100 %) - 20 s = 14 s.
Taking the movement time extension into account (e.g. 10 %), the actual raising time is:
10 s × ((100 % + 10 %(extension)) : 100 %) = 10 s × 1.1 = 15.4 s. The output will then raise the
roller shutter for 15.4 s and thus position safely at 0 %.

i The device executes position approaches only if a new position deviating from the current
position is preset.
i The device stores the blind or louver positions temporarily. The device can approach newly
preset blind or louver positions only if the current positions are known. For this purpose,
each output must be given the opportunity to synchronise itself whenever the supply
voltage is switched on or after every ETS programming operation (physical address,
application program, partial download). Synchronisation is performed with the help of a
reference movement (cf. "reference movement").
i Position approaches in progress will be aborted in case of bus voltage failure. In case of
bus voltage failure, the configured behaviour will be executed.

Calculating the slat position (only with Venetian blinds)


In the "Venetian blind" operating mode, the device always calculates the slat position so that the
opening angle and thus the amount of 'light admitted into the room' by the Venetian blind can be
adjusted. A new position approach by a Venetian blind will always be followed by a positioning
movement of the slats. Thus, the slat positions last selected will be tracked or readjusted to a
new value if a position change has taken place.
In case of single-motor Venetian blind systems without a working position, the slats will be
readjusted directly by a change of the Venetian blind height. For this reason, an adjustment of
the slat position will always have an influence on the position of the Venetian blind itself
(Figure 15).

Figure 15: Example of slat positioning affecting the position of the Venetian blind
(typical of slat type 1; analogous reaction for type 2)

1473-1-7829 | Rev. 01 | 3.2012 Page 45 of 144


Software "Blind, input/1.1"
Functional description

Since a preset slat position is to remain constant until the next change, the device will not
change the height of the Venetian blind, if the calculated movement time required for a change
of position lies within the configured slat moving time.
Similarly, the device accounts for the ratio of the moving times of slat and Venetian blind and –
in case of slat position changes – always recalculates the resulting Venetian blind position. If
the position feedback objects are used (cf. "Position feedback"), the device transmits the
Venetian blind positions changed by the adaptation also to the bus.

Example (Figure 15)...


The Venetian blind position is preset to 50 %. A change of the slat angle (100 %...0 %) initiates
the calculation of a new Venetian blind position which is also tracked in the position feedback
objects. If the device is to approach a new Venetian blind position of, for example, 47 % in this
case, the device will not perform a movement as the calculated travelling time lies within the
configured slat moving time and therefore coincides with the slat movement. A change of the
Venetian blind position to 55 % in this case triggers a Venetian blind movement as the change
does not lie within the slat movement (0 to 100 %).

In each position operation, the Venetian blind setpoint position refers to a slat position of 100 %.
In the event of a slat repositioning movement (0 to 100 %), the system will therefore report a
Venetian blind position below the desired position.

Exception: The Venetian blind setpoint position of 0 % (upper end position) is assigned to the
slat position of 0 %. The readjustment of the slat position will result also in this case in a change
of the Venetian blind height (brief downward movement). Only in this case will the actuator
report back a Venetian blind position above the Venetian blind setpoint position (Figure 16).
With slat type 1, the slats are generally horizontal when the Venetian blind is in its upper end
position. For this reason, the calculated slat position with a slat type 1 corresponds to the actual
opening angle only after the first slat is completely extended (100%).

Figure 16: Example of slat positioning with the Venetian blind in upper end position
(typical of slat type 1)

Example (Figure 16)...


The Venetian blind position is preset to 0 %. After an extended movement, the Venetian blind is
safely in the upper end position. A change of the slat angle (0 %...100 %) initiates the
calculation of a new Venetian blind position which is also tracked in the position feedback
objects. If the device is to approach a new Venetian blind position of, for example, 5 % in this
case, the device will not perform a movement as the calculated travelling time lies within the
configured slat moving time and therefore coincides with the slat movement. A change of the
Venetian blind position to 15 % in this case triggers a Venetian blind movement as the change
does not lie within the slat movement (0 to 100 %).

i The device executes slat position adjustments only if a new position deviating from the
current slat position is preset.

1473-1-7829 | Rev. 01 | 3.2012 Page 46 of 144


Software "Blind, input/1.1"
Functional description

i The device stores the slat positions temporarily. The device can approach newly preset slat
positions only if the current position is known. For this purpose, the output must be given
the opportunity to synchronise itself whenever the supply voltage is switched on or after
every ETS programming run (physical address, application program, partial download). The
synchronisation is performed with the help of a reference movement for the slat or the
Venetian blind (cf. "reference movement").
i A change of the Venetian blind height will always result in a change of the slat position.
After reactivation of the supply voltage of after ETS programming, the device will in this
case generally move the slats into the 100 % position, if no position has been preset for the
slats.
i The smaller the ratio between slat moving time and Venetian blind travelling time, the more
precise the position approaches and the less marked the influence of the slat angle
adjustment on the height of the Venetian blind.

Reference movement
After ETS programming (physical address, application program, partial download) or after bus
voltage failure all current position data are unknown. Before the device can approach new
positions after bus voltage return or after programming, the positioning system must at first be
calibrated. A position calibration is possible by executing the reference movement.
A reference movement is the time required for a movement into the upper end position
increased by 20 % and additionally by the configured movement time extension (Figure 17). A
reference movement is not retriggerable.

Reference movements can be executed by the following commands...


- Uninterrupted long time operation (including also a terminated safety movement) into the
upper end position activated via the corresponding communication object,
- Positioning to the 0 % position.

Figure 17: Reference movement

In the event of slat positioning via the corresponding communication objects after bus voltage
return or after programming, a slat reference movement becomes necessary if the Venetian
blind has not been moved beforehand in the up or down directions for at least the configured
slat moving time. During a slat reference movement, the device always moves the slats for the

1473-1-7829 | Rev. 01 | 3.2012 Page 47 of 144


Software "Blind, input/1.1"
Functional description

configured slat moving time into the completely open position (0 %) and then to the desired
position. The slat position is also considered as calibrated when the Venetian blind has been
moved by a long-time command in the up or down direction during at least the configured slat
moving time.

i A terminated reference movement of the Venetian blind will also calibrate the slat position.
i If the reference movement is interrupted for instance by a short-time operation, the position
is still unknown as before.
i A long-time travel into the lower end position activated via the corresponding
communication object also calibrates the reference position.
i With the sun protection function it is moreover possible to force the actuator to perform a
reference movement before each sun protection travel even if the positions are known.
Thus, it is ensured that in case of sun protection the configured sun protection position is
always precisely approached even after repeated position approaches.
i Using the connected drives frequently for position approaches (for instance several times a
day) can result after some time in positioning inaccuracies. These deviations from the
setpoint position are mostly due to external physical influences. To achieve accurate
positioning in operation it is recommended to perform the reference movement at least
once every day. This can be achieved for instance by a central raising command
transmitted to the long-time object.

Presetting the position


The following ways of presetting positions can be distinguished…
- Direct positioning via the positioning objects (direct operation),
- Positioning by activating the sun protection function,
- Positioning using the response to bus voltage return,
- Positioning by a scene recall.
Positioning via the positioning objects:
Every Venetian blind, roller shutter, awning or louver can be positioned directly via the
"Position..." object separate for each output. An independent positioning object exists for each
of the slats. The position approached is always the position last received. The device does not
show a reaction when the set or approached position value is received multiple times in
succession.
Like the operation via short time, long time or scene recall, this form of control is also
designated as 'direct operation'. Positioning via the objects therefore has the same priority.
A position approach effected by the communication objects can be interrupted at any time by a
short- or long-time or by a scene recall. Direct operation can be overridden by a function with a
higher priority, e.g. forced position, safety or also sun protection (configurable).
The position telegrams must conform to the 1-byte data format as per
KNX datapoint type 5.001 (scaling). The device converts the value received (0...255) linearly
into a position (0...100 %) (see the table 4).

Received value Position derived from value


(0...255) (0…100 %)
0 0 % (upper end position / slat or louver opened)
↓ ↓ (all intermediate values rounded off to 1 % increments)
255 100 % lower end position / slat or louver closed)

Table 4: Data format of positioning objects with conversion into percentage position values

It is possible that new positioning telegrams are being received while a position approach is in
progress. In this case, the device immediately reverses the direction of travel, if the new position
to be approached lies in the opposite direction.
If a slat positioning command is received during a running Venetian blind position approach, the
device finishes first the Venetian blind position approach before positioning the slat. If a

1473-1-7829 | Rev. 01 | 3.2012 Page 48 of 144


Software "Blind, input/1.1"
Functional description

Venetian blind positioning command is received during a slat positioning movement, the device
interrupts the slat positioning movement and approaches the new Venetian blind position. The
device only executes the most recently receive slat positioning command after this.
In case of Venetian blind positioning, slat positioning will always be executed later. After
switching on the bus voltage or after programming with the ETS, it may be the case that the slat
position is unknown, if no long time command for the upward or downward movement with a
duration of at least the configured slat moving time has been received or no slat positioning has
taken place (no slat reference movement). In this case, the slat is moved during a Venetian
blind position approach into the completely closed position (100 %). The slat position is then
considered as calibrated.

i Optionally, the sun protection function offers the possibility of receiving the instruction of
the blind height, venting louver or slat position to be adopted during sunshine via separate
communication objects and to preset these values variably. This form of variable position
preset in the sun protection function is identical to presetting the positions via
communication objects in direct operation. The priority of the incoming telegrams in direct
operation with the sun protection activated can be additionally configured in the ETS.

Positioning by the sun protection function, the behaviour after bus voltage return or by a scene
recall:
In case of the device functions mentioned, the positions to be approached are configured
directly in the ETS depending on the operating mode. The position values can be specified
between 0 % and 100 % in 1 % increments.
With Venetian blinds, the height of the Venetian blind is positioned first in these cases. The
configured slat position is adjusted only thereafter.

i Important notes for all positioning movements: Using the connected drives frequently for
position approaches (for instance several times a day) can result after some time in
positioning inaccuracies. These deviations from the setpoint position are mostly due to
external physical influences. To achieve accurate positioning in operation it is
recommended to perform the reference movement at least once every day. This can be
achieved for instance by a central raising command transmitted to the long time object.

Position feedback messages


In addition to presetting positions via positioning objects, the device can track the current
positions values via separate feedback objects and also transmit them to the bus, if the bus
voltage is on. Thus, the preset setpoint position can be distinguished from the true actual
position of the drives activated.
The following feedback telegrams can be preset depending on the configured operating
mode...
- Feedback (1 byte) of the Venetian blind, roller shutter, awning or venting louver position,
- Feedback (1 byte) of the slat position (only with Venetian blinds).

The individual position feedback messages can be enabled in the ETS independent of one
another and have communication objects of their own.

For each movement, the device calculates the current position and tracks it in the position
feedback objects. The positions are tracked and the feedback objects updated even when the
output has been activated via short time or long time telegrams on condition that the bus
voltage is on.

1473-1-7829 | Rev. 01 | 3.2012 Page 49 of 144


Software "Blind, input/1.1"
Functional description

The feedback objects are updated after the following events...


- At the end of a drive movement – including a slat positioning movement in a Venetian
blind – when the drive stops and when the new position is reached,
- With a movement to an end position already at the time the end position is theoretically
reached, i.e. before the 20 % extension and the movement time extension have elapsed.

The feedback objects are not updated, if the position last reported back has not changed after a
movement (for instance, when the Venetian blind is repositioned, the unchanged slat position
will not be reported back a second time).

The device cannot calculate a feedback position, if the current position data after switch-on of
the bus voltage or after ETS programming are still unknown. In these cases, the system must
first perform a reference movement (cf. "reference movement") so that the position can be
calibrated. In case of unknown positions, the device automatically performs reference
movements, if new positions are preset and if these positions are to be approached. As long as
a position is unknown, the value of the feedback objects is "0".

Presetting position feedback for Venetian blind, roller shutter, awning or venting louver
positions
The feedback functions can be enabled and programmed. When feedback is enabled, the ETS
adapts the parameter texts depending on the preset operating mode
("Venetian blind position feedback", "Roller shutter/awning position feedback" or
"Venting louver position feedback"). The feedback can be used as an active message object or
as a passive status object. As an active signalling object, the position feedback information is
transmitted to the bus whenever a position value changes. As a passive status object, there is
no telegram transmission after a change. In this case, the object value must be read out. The
ETS automatically sets the object communication flags required for proper functioning.
In case of an actively transmitting signalling object, the current position can be transmitted to
the bus after bus voltage return, if the position value differs from the one last transmitted. When
the position data are known, the feedback telegram can in this case be transmitted with a time
delay to reduce the bus load, with the delay being preset globally for all outputs in common (cf.
"Delay after bus voltage return").
The feedback functions of an output must be enabled on parameter page
"O1 - Enabled functions". Only then are the parameters for the feedback functions visible.
o Set the parameter "Venetian blind position feedback",
"Roller shutter/awning position feedback" or "Venting louver position feedback" on
parameter page "O1 - Feedbacks" to "feedback object is active signalling object".
The feedback object is enabled. The position value is transmitted as soon as it changes.
No value will be actively transmitted, if the position is unknown.
o Set the parameter "Venetian blind position feedback",
"Roller shutter/awning position feedback" or "Rückmeldung Lüftungsklappenposition" on
parameter page "O1 - Feedbacks" to "feedback object is passive status object".
The feedback object is enabled. The position value will be transmitted in response only if
the feedback object is read out from by the bus. If the position is unknown, a value of "0"
will be reported back after readout.

The feedback must be set as actively transmitting.


o If a time delay after bus voltage return should be necessary, the parameter
"Time delay for feedback after bus voltage return" on parameter page "O1 - Feedbacks"
must be set to "yes".
The position feedback will be transmitted with a delay after bus voltage return. After the
end of the time delay, the position last adjusted statically will be transmitted to the bus. No
feedback telegram is transmitted during a running delay, even if a position value changes
during this delay.

1473-1-7829 | Rev. 01 | 3.2012 Page 50 of 144


Software "Blind, input/1.1"
Functional description

Presetting the position feedback for slat positions (only with Venetian blinds)
The feedback for the slat positions can be enabled and programmed separately. As with the
position feedback of the Venetian blind height, the feedback can be used as an active message
object or as a passive status object.
In case of an actively transmitting signalling object, the current slat position can be transmitted
to the bus after bus voltage return, if the position value differs from the one last transmitted.
When the position data is known, the feedback telegram can, in this case, be transmitted with a
time delay to reduce the bus load, with the delay being preset for all feedback in common
(cf. "Delay after bus voltage return").
The feedback functions of the output must be enabled on parameter page
"O1 - Enabled functions". Only then are the parameters for the slat position feedback functions
visible.
o Set the parameter "Slat position feedback" on parameter page "O1 - Feedbacks" to
"feedback object is active signalling object".
The feedback object is enabled. The position value is transmitted as soon as it changes.
No value will be actively transmitted, if the position is unknown.
o Set the parameter "Slat position feedback" to "feedback object is passive status object".
The feedback object is enabled. The position value will be transmitted in response only if
the feedback object is read out from by the bus. If the position is unknown, a value of "0"
will be reported back after readout.

The feedback must be set as actively transmitting.


o If a time delay after bus voltage return should be necessary, the parameter
"Time delay for feedback after bus voltage return" on parameter page "O1 - Feedbacks"
must be set to "yes".
The position feedback will be transmitted with a delay after bus voltage return. After the
end of the time delay, the position last adjusted statically will be transmitted to the bus.
During a running delay the affected feedback object is updated but no feedback is
transmitted actively, even if a position value changes during this delay.

i Behaviour of the position feedback on voltage failure & return:


On bus voltage return, the current position data is always written to the feedback objects.
The positions are then also transmitted to the bus, if the feedback objects transmit actively.
If the position data is unknown, the feedback objects are initialised with "0" and not
transmitted to the bus.
i In case of Venetian blind operation, any position change of the Venetian blind within the
limits of the slat adjustment (0 to 100 %) does not launch a movement and therefore no
change of the feedback position data either.

Unknown position feedback and drive movement


In addition to position data feedback, the device can also report back enlarged 1-bit status
information messages and transmit them actively to the bus, if the bus voltage is on.
The following status feedback messages can be preset...
- Feedback of an invalid position,
- Drive movement feedback,

Feedback of an invalid position:


After switch-on of the supply voltage or after programming with the ETS, all the position data of
an output is unknown. In this case – when the bus voltage is on – the device can update the
feedback object "Invalid position"(object value "1") which will then signal that the object values
of the 1-byte position feedback objects are invalid.
An invalid position feedback will be only be reversed (object value "0") after the position data for
the Venetian blind, roller shutter, awning or venting louver have been calibrated by means of a

1473-1-7829 | Rev. 01 | 3.2012 Page 51 of 144


Software "Blind, input/1.1"
Functional description

reference movement. The calibration of the slat position in a Venetian blind alone will not result
in the reversal of an 'invalid position' status message.
As an option, the object value of the status feedback message can be actively transmitted to the
bus in case of a value change.

Drive movement feedback:


The device can report back via a separate 1-bit communication object whether the connected
drive is moving, i.e. whether the output is supplying current for any of the movement directions.
The feedback object has a value of "1" when current is flowing from the output to the drive.
Likewise, a "0" is written into the object if the output concerned remains in a stop position. In
this case, the operation by which the output was activated (short time or long time operation,
positioning, etc.) is of no importance.
As an option, the object value of the status feedback message can be actively transmitted to the
bus in case of a value change.
The state of the feedback is only derived from the relay state of the device. This means that if a
drive is blocked or already in its end position, the value reported back does not correspond to
the actual state of the drive movement.

Setting feedback of an invalid position


The feedback of an invalid position can be enabled and programmed independently. When
feedback is enabled, the ETS adapts the parameter texts depending on the preset operating
mode ("Invalid Venetian blind position feedback",
"Invalid roller shutter/awning position feedback" or "Invalid venting louver position feedback").
The feedback can be used as an active message object or as a passive status object. As an
active signalling object, the status feedback information is transmitted to the bus whenever a
position value changes. As a passive status object, there is no telegram transmission after a
change. In this case, the object value must be read out. The ETS automatically sets the object
communication flags required for proper functioning.
If the object is an actively transmitting signalling object, the feedback telegram can be
transmitted after bus voltage return with a time delay to reduce the bus load, with the delay
being preset globally for all outputs in common (cf. "Delay after bus voltage return").
The feedback functions of the output must be enabled on parameter page
"O1 - Enabled functions". Only then are the parameters for the feedback functions visible.
o Set the parameter "Invalid Venetian blind position feedback",
"Invalid roller shutter/awning position feedback" or
"Invalid venting louver position feedback" on parameter page "O1 - Feedbacks" to
"feedback object is active signalling object".
The feedback object is enabled. A telegram is transmitted as soon as there is a change
(e.g. after ETS programming, after switch-on of the supply voltage or after a reference
movement).
o Set the parameter "Invalid Venetian blind position feedback",
"Invalid roller shutter/awning position feedback" or
"Invalid venting louver position feedback" on parameter page "O1 - Feedbacks" to
"Feedback object is passive status object".
The feedback object is enabled. A telegram will be transmitted in response only if the
feedback object is read out by the bus.

The feedback must be set as actively transmitting.


o If a time delay after bus voltage return should be necessary, the parameter
"Time delay for feedback after bus voltage return" on parameter page "O1 - Feedbacks"
must be set to "yes".
The feedback of an invalid position will be transmitted with a delay after bus voltage return.
After the end of the time delay, the object value state last adjusted will be transmitted to the
bus. No feedback telegram is transmitted during a running delay, even if a position value
becomes known during this delay, for example through a reference movement.

1473-1-7829 | Rev. 01 | 3.2012 Page 52 of 144


Software "Blind, input/1.1"
Functional description

i Automatic transmission after bus voltage return only takes place if there has been an
internal change to the object state.

Setting drive movement feedback


The feedback of a drive movement can be enabled and programmed independently. The
feedback can be used as an active message object or as a passive status object. As an active
signalling object, the status feedback information is transmitted to the bus whenever a position
value changes. As a passive status object, there is no telegram transmission after a change. In
this case, the object value must be read out. The ETS automatically sets the object
communication flags required for proper functioning.
If the object is an actively transmitting signalling object, the feedback telegram can be
transmitted after bus voltage return with a time delay to reduce the bus load, with the delay
being preset globally for all outputs in common (cf. "Delay after bus voltage return").
The feedback functions of an output must be enabled on parameter page
"O1 - Enabled functions". Only then are the parameters for the feedback functions visible.
o Set the parameter "Drive movement feedback" on parameter page "O1 - Feedbacks" to
"feedback object is active signalling object".
The feedback object is enabled. A telegram is transmitted when the connected drive starts
moving or stops.
o Set the parameter "Drive movement feedback" on parameter page "O1 - Feedbacks" to
"Feedback object is passive status object".
The feedback object is enabled. A telegram representing the current travel movement will
be transmitted in response only if the feedback object is read out by the bus.

The feedback must be set as actively transmitting.


o If a time delay after bus voltage return should be necessary, the parameter
"Time delay for feedback after bus voltage return" on parameter page "O1 - Feedbacks"
must be set to "yes".
The feedback of a drive movement is transmitted after a delay on bus voltage return, for
example, when the drive starts moving on account of the set behaviour after bus voltage
return. After the end of the time delay, the object value state last adjusted will be
transmitted to the bus. No feedback telegram is transmitted during a running delay, even if
the drive stops or starts moving.

i Automatic transmission only takes place after a bus voltage return when the drive starts
moving on bus voltage return or if the bus failure has caused a change to the drive
movement.

1473-1-7829 | Rev. 01 | 3.2012 Page 53 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.4.4 Safety function settings


Safety function
The device can handle up to five different safety functions:
3 x wind alarm, 1 x rain alarm, 1 x frost alarm. Each safety function has a communication object
of its own so that the functions can be activated or deactivated independently of one another.
There are three different wind alarms available. These alarms can be used, for instance, to
protect Venetian blinds or awnings on several building facades from wind and gusts. In addition
or as an alternative, a rain alarm, for instance, as a protection for awnings, and a frost alarm as
a protection against mechanical damage to lowered Venetian blinds in low temperatures can be
activated and used. The telegram polarity of the safety objects is fixed:
"0" = No alarm / "1" = Alarm.
Usually, weather stations, which record temperature, wind speed and rain via the sensors,
control the communication objects of the safety function.
The reactions at the beginning of an alarm message ("1" telegram) or at the end of an alarm
message ("0" telegram) can be specified during the configuration in the ETS.

The communication objects for the safety alarms can be monitored for the arrival of cyclical
telegrams. If there are no telegrams within a settable monitoring time, the device activates the
safety movement for the output. The safety function is terminated as soon as a new
"0" telegram is received.
For the wind alarms, the rain alarm and the frost alarm, different monitoring times between '1
minute' and '23 hours 59 minutes' can be separately selected in the ETS. A shared time is
configured for the wind alarms. Each wind alarm has its own timer so that the wind objects are
separately checked for telegram updates.

Figure 18: Function diagram of the safety function

The output can be assigned independently to the wind alarms, the rain alarm and the frost
alarm. If the output is associated with several alarms, the preset priority decides which of the
alarms will prevail and be executed. In so doing, an alarm with a higher priority overrides the
alarms with the lower priorities. When safety alarm with the higher priority has ended, the safety
alarm with the lower priority is executed on condition that it is active.
The order of priority of the wind alarms with respect to the frost alarm or to the rain alarm can be
configured on the parameter page "O1 - Safety I". The three wind alarms have the same priority
with respect to one another (logic OR). The last telegram update to the wind alarm objects
decides which of the wind alarms will be executed. The wind alarm is completely deactivated
only after all three objects are inactive ("0").
The output in the active safety alarm state is locked, i.e. the control of the output concerned via
the bus by direct operation (short time, long time telegram, scenes, positioning) or by a sun
protection function is prevented. Only a forced position has a higher priority so that this function
may override a safety lock. At the end of a forced position, the safety reaction is re-executed if
an assigned safety alarm is still active.

1473-1-7829 | Rev. 01 | 3.2012 Page 54 of 144


Software "Blind, input/1.1"
Functional description

Presetting the safety priorities


If several safety alarms are assigned to the output, it is important to preset the priority of the
incoming safety telegrams. In so doing, an alarm with a higher priority overrides the alarms with
the lower priorities. When safety alarm with the higher priority has ended, the safety alarm with
the lower priority is executed on condition that it is active.
The safety function for an output must be enabled on parameter page "O1 - Enabled functions.
Only then are the parameters for the safety function visible.
o Set the "Priority of safety alarms" parameter on the "O1 - Safety I" parameter page in the
required order of priority.
i The three wind alarms have the same priority with respect to one another (logic OR). The
last telegram update to the wind alarm objects decides which of the wind alarms will be
executed. The wind alarm is completely deactivated only after all three objects are inactive
("0").

Presetting cyclical monitoring


If cyclical telegram monitoring of the safety objects is necessary, the individual monitoring
functions must be activated separately. The monitoring functions must be enabled and the
monitoring times preset on the "O1 - Safety II" parameter page.
The safety function for an output must be enabled on parameter page "O1 - Enabled functions.
Only then are the parameters for the safety function visible.
o If monitoring of the wind alarms is to be activated, the parameter
"Use wind alarm monitoring function ?" must be set to "yes".
The monitoring function for the wind alarm objects is now activated. As soon as the
monitoring function is activated, telegrams must be transmitted cyclically to all enabled
wind alarm objects. If only one of the wind alarm telegrams is missing within the monitoring
period, the wind alarm reaction will be executed for the output.
o Specify the required monitoring time for the wind alarm objects in the
"Wind alarm monitoring times" parameters.

o If the monitoring function is to be activated for a rain alarm, the parameter


"Use rain alarm monitoring function ?" must be set to "yes".
The monitoring function for the rain alarm object is now activated. As soon as the
monitoring function is activated, telegrams must be transmitted cyclically to the rain alarm
object.
o Specify the required monitoring time for the rain alarm object in the
"Rain alarm monitoring times" parameters.

o If the monitoring function is to be activated for a frost alarm, the parameter


"Use frost alarm monitoring function ?" must be set to "yes".
The monitoring function for the frost alarm object is now activated. As soon as the
monitoring function is activated, telegrams must be transmitted cyclically to the frost alarm
object.
o Specify the required monitoring time for the frost alarm object in the
"Frost alarm monitoring times" parameters.
i The monitoring function for the wind alarms may only be activated, if at least one wind
alarm has been activated on the "O1 - Safety I" page.

1473-1-7829 | Rev. 01 | 3.2012 Page 55 of 144


Software "Blind, input/1.1"
Functional description

i The cycle time of the transmitters should be shorter than the monitoring time configured in
the device in order to ensure that at least one telegram can be received during the
monitoring time.

Assigning safety alarms


The individual safety alarms can be assigned separately to each output. The channels are
assigned on parameter page "O1 - Safety III".
The safety function for an output must be enabled on parameter page "O1 - Enabled functions.
Only then are the parameters for the safety function visible.
o If an assignment to the wind alarms is necessary, set the parameter
"Assignment to wind alarms" to the wind alarms required.
The output is assigned to the specified wind alarms.
o If an assignment to the rain alarm is necessary, set the parameter
"Assignment to rain alarm" to "yes".
The output is assigned to the rain alarm.
o If an assignment to the frost alarm is necessary, set the parameter
"Assignment to frost alarm" to "yes".
The output is assigned to the frost alarm.

i If an output was assigned to the wind alarm and these alarms are not enabled on
parameter page "O1 - Safety I", the assignment is without effect.

Presetting the behaviour at the beginning of a safety alarm


The behaviour of the output at the beginning of a safety alarm can be configured separately for
each alarm (wind alarms in common, rain and frost alarms separately). The alarm behaviour is
preset on parameter page "O1 - Safety III". At the beginning of a safety alarm, the device locks
the output, i.e. control via the bus by direct operation (short time, long time telegram, scenes,
positioning) or by a sun protection function is prevented.
Depending on the selected operating mode, the ETS adapts the designations of the parameter
settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing the louver").
The safety function for an output must be enabled on parameter page "O1 - Enabled functions.
Only then are the parameters for the safety function visible.
The behaviour in case of a safety alarm can only be adjusted, if the output has been assigned
to the corresponding alarm. Since there is no difference between the alarm-dependent
configurations, the selection of the parameters is described below only once.
o Set the parameter "Behaviour in case of ..." to "no reaction".
At the beginning of the alarm, the output is locked and the relay of the output shows no
reaction. Any movements still in progress at this instant will still be completely finished.
o Set the parameter "Behaviour in case of ..." to "raising" or "opening the louver".
The device raises the blind or opens the venting louver at the beginning of the alarm and
locks the output thereafter.
o Set the parameter "Behaviour in case of ..." to "lowering" or "closing the louver".
The device lowers the blind or closes the venting louver at the beginning of the alarm and
locks the output thereafter.
o Set the parameter "Behaviour in case of ..." to "stop".
At the beginning of the alarm, the device switches the relays of the output to "stop" and
locks the output. A drive movement, if any, will be interrupted.

1473-1-7829 | Rev. 01 | 3.2012 Page 56 of 144


Software "Blind, input/1.1"
Functional description

i The safety movement time required by an output to move the drive into the end positions is
determined by the "Movement time" parameter on parameter page "O1 - Times". Like the
long-time operation, a safety movement is derived from the movement time. Downward
movement: movement time + 20 %; Upward movement: movement time + 20 % +
configured movement time extension. Safety movements are not retriggerable.
i Slats of blinds are not repositioned at the end of safety movements to end positions.

Presetting the behaviour at the end of all safety alarms


The device ends the safety interlock of the output only after all safety alarms assigned to the
output have become inactive. Thereafter, the output shows the configured
"Behaviour at the end of safety". The behaviour is configured on parameter page
"O1 - Safety III" in common for all alarms.
Depending on the selected operating mode, the ETS adapts the designations of the parameter
settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing the louver").
The safety function for an output must be enabled on parameter page "O1 - Enabled functions.
Only then are the parameters for the safety function visible.
o Set the parameter "Behaviour at the end of safety" to "no reaction".
At the end of all safety alarms, the output is released and the relay of the output shows no
reaction. Any movements still in progress at this instant will still be finished.
o Set the parameter "Behaviour at the end of safety" to "raising" or "opening the louver".
The device releases the output at the end of all safety alarms and raises the blind or opens
the venting louver.
o Set the parameter "Behaviour at the end of safety" to "lowering" or "closing the louver".
The device releases the output at the end of all safety alarms and lowers or closes the
venting louver.
o Set the parameter "Behaviour at the end of safety" to "stop".
At the end of all safety alarms, the output is released and the device switches the relays of
the output to "stop". A drive movement, if any, will be interrupted.
o Set the parameter "Behaviour at the end of safety" to "tracking the position".
At the end of all safety alarms, the output will be set to the state last adjusted statically
before the safety function or to the state tracked and internally stored during the safety
function. The position objects, the long time object and the scene function are tracked.
i Parameter setting "Position tracking": The device can track absolute positions after safety
release (position telegram, scene value) only if the position data is known and if the
positions have been predefined. In all other cases, no reaction takes place on release of
safety.
Position data can be tracked, if the output was in a defined position before the safety
function or if a new position telegram was received via the position objects during the
safety interlock. In the latter case, a reference movement will be executed when the safety
function is enabled, if the position before or during the safety interlock was unknown.
Known slat positions will also be tracked as described. This is also the case, when the
height of the Venetian blind is unknown.
Long time movements (movements without position preset) will, however, always be
tracked.
i The preset "Behaviour at the end of safety" will only be executed, if the output passes over
to direct operation at the end of all safety alarms. If a sun protection function is activated
(independent of the preset priority with respect to direct operation), it will be also executed.

1473-1-7829 | Rev. 01 | 3.2012 Page 57 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.4.5 Sun protection settings


Sun protection function - General information
A sun protection function can be configured and actuated for output 1 of the device. Sun
protection is generally realized with blinds, shutters or awnings and offers an intelligent method
of shading rooms, terraces or balconies during sunshine depending on the
altitude of the sun in the sky and on the intensity of the sunlight(Figure 19)

Figure 19: Sun protection principles (example)

The sun protection functions of the device can be adapted many different applications. In simple
applications as, for instance, in case of direction-dependent measurement of the sun's intensity
by means of a brightness sensor, the curtains controlled can be closed partly or completely to
prevent being disturbed by direct sunlight. In these applications, the sun protection function
merely evaluates the 1-bit sun signal from the brightness or a similar sensor (e.g. weather
station with limit value monitoring) and makes a drive open or close the controlled curtains by
moving them into fixed configured positions or into variable positions preset via the bus.

In extended applications – for instance where the degree of shading is controlled by weather
stations evaluating additionally the sun angle as a function of astro co-ordinates and presetting
the blind and also the slat positions dynamically – the sun protection function can be
supplemented by an automatic control system. In such applications, the sun protection function
evaluates additional bus communication objects allowing to enable or to disable the automatic
control while the device is in operation. This results in a large number of combination variants
with intelligent Venetian blind control systems.

Already simple sun protection applications are sufficient to permit a fixed or variable re-
adjustment of the positions of Venetian blind slats for adapting the curtain to individual shading
requirements. For such purpose, it is possible to preset a static slat offset in the ETS
parameters, for instance, for adapting the reflection of sunlight depending on the building
situation, or additionally, a dynamical slat offset via a bus communication object,
for instance, for manual re-adjustment of the slat opening by persons in the room or otherwise
by a central building services control system.

In all cases, the priority between an incoming sunshine or automatic telegram and the direct
operation of the output (short time, long time telegram, scenes, positioning) is also presettable
in the ETS. This way, a sun protection position can, for instance, be influenced by a 'manual'
operation of a pushbutton sensor in the room and the sun protection function be interrupted.
Alternatively, sun protection mode can therefore not be interrupted by a direct operation, i.e. the
output is locked.
A sun protection function can be overridden by a safety function, a forced position or also by a
manual control locally on the device itself as these functions of the device invariably have a
higher priority. At the end of one of the mentioned functions with a higher priority, the same
reaction as the one at the beginning of sun protection will be re-executed, if the sun protection
function is still active at this time.

The device can be operated with two sun protection functions. The simple sun protection or
alternatively the extended sun protection that can be enabled.

1473-1-7829 | Rev. 01 | 3.2012 Page 58 of 144


Software "Blind, input/1.1"
Functional description

Sun protection function - Simple sun protection


In the simple sun protection, shading against sunlight is activated and deactivated via the
1-bit communication object "Sunshine / shading facade". The polarity of this object can be
selected in the ETS. The sun protection is activated as soon as "sunshine" is signalled to the
object depending on the preset polarity. After ETS programming or after switch-on of the supply
voltage, the object must at first have data written into it by the bus also in case of inverted
polarity before the sun protection can be activated.

A newly received object value (sun / beginning of shading or sun / end of shading) can
optionally be evaluated with a time delay. This feature permits suppressing brief brightness
variations caused, for instance, by passing clouds or by a thunderstorm. An update (from
activated to activated) of the "Sunshine / shading facade" object causes the sun protection to be
reactivated, if it had been influenced and possibly been re-enabled beforehand by a direct
operation in acc. with the preset priority.

The reaction of the output at the beginning of shading can be preset in the ETS.
Amongst other things, this setting permits approaching fixed configured positions or positions
preset via the bus and thus variable. Variable positions for sun protection purposes can be
preset, for instance, by means of pushbutton sensors or visualisations. In addition, it is possible
in case of a defined sun protection positioning movement to have a reference movement
executed by forced control. This ensures that identical blind positions are approached
synchronously by different outputs in case of a sun protection positioning movement.
The reaction at the end of a shading task can be preset as well. In this situation, the curtain can
pass into an end position, be stopped or shown no special reaction. Tracking of positions is
possible as well.

By means of a priority setting in the ETS configuration, it can be specified whether the sun
protection function can be influenced by direct operation or whether the corresponding output is
locked by a telegram "Sunshine / shading facade" in the sun protection position. The
"Forced position" and "Safety" functions always have a higher priority so that these functions
can override, but not terminate a sun protection. Thus, the sun protection function is re-
executed at the end of a function with a higher priority, if the object "Sunshine / shading facade"
continues to signal the presence of sunshine.

i The following rules must be observed for the extended sun protection: After an ETS
programming operation, the sun protection function including automatic operation is always
deactivated.

The schematic diagram of the simple sun protection (Figure 20) and an example of how sensor
components can be integrated into a simple sun protection configuration.

1473-1-7829 | Rev. 01 | 3.2012 Page 59 of 144


Software "Blind, input/1.1"
Functional description

Figure 20: Schematic diagram illustrating the simple sun protection configuration

The function diagram (Figure 21) shows all possible functions of the simple sun protection. For
reasons of clarity, the functions with a higher priority (forced position, safety function) are not
shown in the diagram.

Figure 21: Function diagram illustrating the simple sun protection

Sun protection function - extended sun protection


The extended sun protection has the basic functional properties of the simple sun protection
function. In addition, an automatic control system can be implemented. Venetian blind control
systems for blind and slat position tracking with respect to the position of the sun as, for
instance, a weather station with combination sensor can therefore be integrated into the device
system via the bus as an added automatic function.

In the extended sun protection, shading against sunlight is activated and deactivated via the
1-bit communication object "Sunshine / shading facade". A reaction of the output to the sun
telegram can be expected only after the automatic control has been activated. In all other
cases, the sun protection function is completely deactivated.

1473-1-7829 | Rev. 01 | 3.2012 Page 60 of 144


Software "Blind, input/1.1"
Functional description

As far as the activation of the automatic control via the corresponding object is concerned, the
following two cases must be distinguished...
- Sun shading action starting immediately:
Automatic operation is activated as soon as the "Automatic" object receives a "1" telegram.
The output reacts immediately to the activation and shows the preset behaviour depending
on sunlight conditions (Sun / beginning of the shading action / Sun end of the shading
action). The sunlight conditions are derived from the "Sun / shading facade" object
according to the set polarity - if necessary after the delays have elapsed.
After an ETS programming operation or after switch-on of the supply voltage, the
"Sunshine / shading facade" object is initialised with "0" and, unlike the simple sun
protection, evaluated immediately depending on the preset polarity so that shading against
sunlight can begin immediately on activation of the automatic sun protection function. The
reception of a "0" telegram by the object "Automatic" always terminates an automatic
operation independent of the state of the "Sunshine / shading facade" object.

Application example:
Private house with winter garden. The conservatory is equipped with Venetian blinds to
shade the place against sunlight. When the conversation is used, automatic operation is
activated, for instance, with a pushbutton sensor on the wall. The device then immediately
executes the shading function, if sunshine was detected.
The device performs the behaviour configured for the end of the shading / sunshine in case
no sunshine is detected when the automatic operation is activated.

- Activation of the sun shading only on the next update:


In this configuration, the polarity of the automatic object can be preset. Automatic operation
is activated as soon as the "Automatic" object is set to 'active' in consideration of polarity. A
reaction at the output occurs, however, only after a new change of state
("0" -> "1" or "1" -> "0") has been signalled via the "Sunshine / shading facade" object. In
this case, the new state (beginning of sunshine/shading or end of sunshine/shading)
determines the behaviour of the output immediately depending on the preset polarity.
After an ETS programming operation or after switch-on of the supply voltage, the
object "Automatic" must at first have data written into it by the bus also in case of inverted
polarity before the automatic operation can be activated.
The reception of an 'Automatic deactivated' telegram by the "Automatic" object always
terminates an automatic operation independent of the
state of the "Sunshine / shading facade" object.

Application example:
An office building is equipped with several Venetian blinds to shade individual offices
against sunlight. In the early morning hours, the automatic sun protection is activated in a
central place in the building, e.g. in the porter's lodge. The Venetian blinds will, however,
not move into the shading positions unless the system has actually reported sunshine for
the building facades in question.

The behaviour at the end of automatic operation is configured separately in the ETS and is
executed whenever the automatic mode is terminated and when no function with a higher
priority is active at this time. In this situation, the curtain can pass into an end position, be
stopped or shown no special reaction. Tracking of positions is possible as well.

Disabling functions of the extended sun protection:


In the event of the sun shading action starting immediately, the automatic operation can
optionally be disabled with an additional communication object. The objects
"Automatic" and "Automatic mode disable" are logically combined (AND with feedback). When
disabling is activated, the automatic operation is reset and thus aborted. The output will then
show the behaviour at the end of automatic operation. The automatic mode can only be
reactivated, if the disabling object is enabled and if the "Automatic" object is updated again by
writing a "1" into it. Any attempt of activating the automatic mode while a disable is active will be
ignored.

Automatic operation disabling example:


An office room is equipped with Venetian blinds to shade the room against sunlight. The room is

1473-1-7829 | Rev. 01 | 3.2012 Page 61 of 144


Software "Blind, input/1.1"
Functional description

moreover equipped with a pushbutton sensor on the wall with which the automatic operation
can be activated or also deactivated. When the automatic mode is activated, the room is
immediately shaded against sunlight, if necessary. Depending on the time of day or in the event
of disturbing sunlight falling into the room, the persons in the room can therefore decide for
themselves whether automatic shading is desired or not.
If required, the automatic sun protection is disabled in a central place of the building,
for instance, in the porter's lodge. The automatic control of the Venetian blinds can then be
deactivated, if servicing work is being carried out (window cleaning or similar work). After the
end of disabling, for instance, at the end of the working hours, automatic operation can only be
restarted if it is reactivated in any of the rooms in case of need.

In addition, also the direct operation of the output can be disabled with an independent disabling
object. When disabling is active, a direct operation can – independent of the preset priority –
never override a sun protection function. In this case, direct operation is non operational
in other functions, too. During disabling, incoming direct operation telegrams are completely
ignored (positions received via the bus can then not be tracked either).
If the disabling command is received while a movement initiated by direct operation is in
progress, the movement will still be completely finished. Thereafter, direct operation is
disabled.

Direct operation disabling example:


An office building is equipped with several Venetian blinds to shade individual offices against
sunlight. During the working hours, the rooms are to be shaded automatically. Any direct
operation – e.g. by means of a simple Venetian blind pushbutton sensor on the wall – is to be
disabled during the day. For this reason, the direct operation is disabled, for instance, by the
porter or by a building services management system. Cleaners must have the possibility of
controlling the shutters directly only after the normal working hours. In this case, direct operation
can again be centrally enabled during evening and night hours.

The disabling functions for automatic and for direct operation can also be combined so that it is
possible to intervene at any time and as required by the situation in sun protection control
functions.

Sunshine signal in the extended sun protection mode:


In the sun protection mode, the system is informed about the prevailing sunshine conditions via
the "Sunshine / shading facade" communication object. The system the decides whether
shading is required or not. In the extended sun protection mode, the sunshine signal is only
evaluated when the automatic operation is activated as well.

A new value received via the "Sunshine / shading facade" object can optionally be evaluated
with a time delay. This feature permits suppressing brief brightness variations caused, for
instance, by passing clouds or by a thunderstorm. The time delay is started after an update of
the "Sunshine / shading facade" object also in those cases where the automatic operation is
deactivated so that the newly received information about the sunshine conditions may possibly
also be processed with a delay, if the automatic operation is activated later on.
Unlike in the simple sun protection mode, an update of the "Sunshine / shading facade" object
from active to active or from inactive to inactive in the extended sun protection mode shows
generally no reaction. The behaviour of the output is only influenced if a change of state is being
detected. An update of the sunshine signal alone does not result in the activation of the
automatic operation either.

When the automatic operation is active, the reaction of a specific output at the beginning of
shading can be preset separately in the ETS. This setting permits approaching fixed configured
positions or positions preset via the bus and thus variable. Positions for sun protection purposes
can be variably preset, for instance, by means of a weather station for sun position tracking.
In addition, it is possible in case of a defined sun protection positioning movement to have a
reference movement executed by forced control. This ensures that identical blind positions are
approached synchronously by different outputs in case of a sun protection positioning
movement.
At the end of sun shading when automatic operation is active, the output reaction can also be
configured separately. In this case, too, it is possible to approach fixed configured positions.

By means of a priority setting in the ETS parameters it can be specified whether the evaluation

1473-1-7829 | Rev. 01 | 3.2012 Page 62 of 144


Software "Blind, input/1.1"
Functional description

of the sunshine signal in the automatic mode can be influenced by a direct operation or whether
the automatic mode basically locks the corresponding output during sun protection. The
"Forced position" and "Safety" functions invariably have a higher priority so that these functions
can override, but not terminate a sun protection including an automatic operation. Thus, the sun
protection function is re-executed at the end of a function with a higher priority, if the automatic
sunshine protection is still active.
An update (from activated to activated) of the "Automatic" object causes the sun protection to
be reactivated, if it had been influenced and cancelled beforehand by a direct operation in
accordance with the lower priority.
The schematic diagram of the extended sun protection (Figure 22) and an example of how
sensor components can be integrated into an extended sun protection configuration.

Figure 22: Schematic diagram illustrating the extended sun protection configuration
(for reasons of simplicity without disabling functions)

The function diagram (Figure 23) shows all possible functions of the extended sun protection.
For reasons of clarity, the functions with a higher priority (forced position, safety function) are
not shown in the diagram.

1473-1-7829 | Rev. 01 | 3.2012 Page 63 of 144


Software "Blind, input/1.1"
Functional description

Figure 23: Function diagram illustrating the extended sun protection

i The following rules must be observed for the extended sun protection:
After an ETS programming operation, the sun protection function including automatic
operation is always deactivated. An activated sun protection (independent of the selected
priority with respect to direct operation) remains active even after a bus voltage failure as
long as the mains voltage supply is still on. The sun protection reaction last executed will
therefore be executed again at the end of a temporary or permanent manual control (if
enabled in case of bus failure), even if there is no bus voltage.

Presetting the type of sun protection


The type of sun protection can be preset. The setting determines whether the simple or the
extended type of sun protection is configured.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
o Set the parameter "Type of sun protection" on parameter page "O1 - Sun protection" to
"simple sun protection".
Simple sun protection is now configured. The necessary parameters and communication
objects are visible.
o Set the parameter "Type of sun protection" on parameter page "O1 - Sun protection" to
"extended sun protection".
Extended sun protection is now configured. The necessary parameters and communication
objects are visible.

1473-1-7829 | Rev. 01 | 3.2012 Page 64 of 144


Software "Blind, input/1.1"
Functional description

i When the sun protection type parameters are changed, the assignments of group
addresses to sun protection objects or other parameter settings are lost. For this reason,
the sun protection type parameter should be selected directly at the beginning of the sun
protection configuration and then not be changed anymore later on.

Presetting the priority of sun protection (for simple sun protection only)
The priority of the sun protection function can be set. In the simple sun protection, the priority
relations between the "Sunshine / shading facade" object and the objects of direct operation
(short time, long time or position telegram, scene recall) must be configured.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for simple sun protection.
o Set the parameter "Priority of sun protection with respect to direct operation" on parameter
page "O1 - Sun protection" to "same priority".
The sun protection mode can be overridden at any time by direct operation. In the same
way, the sun protection overrides the direct operation, when a new "sunshine" telegram is
received via the "Sunshine / shading facade" object and when a configured time delay, if
any, has elapsed. If the sun protection function is overridden by a direct operation, the
preset behaviour "Reaction at the end of sunshine / shading" will not be executed.
o Set the parameter "Priority of sun protection with respect to direct operation" on parameter
page "O1 - Sun protection" to "higher priority".
An active sun protection will override a direct operation. The sun protection mode can
therefore not be interrupted by a direct operation. Direct operation will be possible again
only after the sun protection function is terminated.
o Set the parameter "Priority of sun protection with respect to direct operation" on parameter
page "O1 - Sun protection" to "lower priority".
A direct operation can at any time override the sun protection mode. If the sun protection
function is overridden by a direct operation, the preset behaviour
"Reaction at the end of sunshine / shading" will not be executed. The sun protection
function can only be reactivated after an enabling movement controlled by a direct
operation has been effected and after a new "sunshine" telegram has been received via the
"Sunshine / shading facade" object. Attempts to activate the sun protection function are
ignored for as long as the enabling movement has not taken place.
On the enabling movement:
An enabling movement is an accomplished long time movement into the upper end position
which has been initiated by the object "Long time operation". An upward movement after
bus voltage return, a position approach to "0 %" or an upward movement after enabling of
forced position or safety functions have no enabling effect.
The sun protection is not enabled if the enabling movement has been interrupted. The
sunshine protection function will be also be disabled if the output has been readjusted
again by a direct operation after an accomplished enabling movement.
After an ETS programming operation or switch-on of the bus voltage, the sunshine
protection function is always enabled.

i The forced position function and the safety functions have a fixed priority higher than that of
the sun protection. The sun protection is overridden – but not terminated – by a function
with a higher priority. After the end of the function with the higher priority the reaction at the
beginning of sun protection will therefore be executed again, if the sun protection is still
active at this time.
i With the settings "same priority" or "lower priority", the sun protection can be overridden by
a direct operation only if the direct control action can be executed at once. A direct
operation will therefore not override the sun protection during an active forced position
function or an active safety function.

1473-1-7829 | Rev. 01 | 3.2012 Page 65 of 144


Software "Blind, input/1.1"
Functional description

i Parameter setting "same priority" or "lower priority": A variable preset of curtain and slat
positions or of a slat offset via the bus at the beginning of sunshine / shading shows no
reaction at the output, if the sun protection was overridden by direct operation. However,
the position data or offsets received are stored internally so that the new positions will be
approached on reactivation of the sun protection.

Presetting the priority of automatic sun protection (for extended sun protection only)
The priority of the automatic sun protection function can be set. In the extended sun protection,
the priority relations between the "Sunshine / shading facade" object and the objects of direct
operation (short time, long time or position telegram, scene recall) must be configured. The
selected priority thus affects the evaluation of the sunshine signal in the automatic mode and
not the automatic mode itself.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for extended sun protection.
o Set the parameter "Priority of automatic operation with respect to direct operation" on
parameter page "O1 - Sun protection" to "same priority".
The sunshine signal of the automatic sun protection mode and the corresponding reaction
can be overridden at any time by direct operation. In the same way, the sunshine signal
overrides the direct operation, when a new "sunshine" or "no sunshine" telegram is
received via the "Sunshine / shading facade" object and when this telegram results in a
change of state. Moreover, a configured delay time, if any, must have elapsed. When the
sunshine signal is overridden by a direct operation, the preset behaviour
"Reaction at the end of sunshine / shading" will not be executed.
o Set the parameter "Priority of automatic operation with respect to direct operation" on
parameter page "O1 - Sun protection" to "higher priority".
An active automatic mode always overrides the direct operation independent of the
sunshine signal. The sunshine signal can therefore not be interrupted by a direct operation.
Direct operation will be possible again only after the automatic mode is terminated.
o Set the parameter "Priority of automatic operation with respect to direct operation" on
parameter page "O1 - Sun protection" to "lower priority".
A direct operation can at any time override the sunshine signal. If the sunshine signal is
overridden, the preset behaviour "Reaction at the end of sunshine / shading" will not be
executed. The sunshine signal will be evaluated again only after an enabling movement
controlled by a direct operation has been effected and when a new "sunshine" or
"no sunshine" telegram is received via the "Sunshine / shading facade" object and when
this telegram results in a change of state. The sun protection function is ignored for as long
as the enabling movement has not taken place.
On the enabling movement:
An enabling movement is an accomplished long time movement into the upper end position
which has been initiated by the object "Long time operation". An upward movement after
bus voltage return, a position approach to "0 %" or an upward movement after enabling of
forced position or safety functions have no enabling effect.
The sunshine signal is not enabled if the enabling movement has been interrupted. The
sunshine signal will be also be disabled, if the output has been re-adjusted again by a
direct operation after an accomplished enabling movement.

i A direct operation never terminates the automatic mode. Irrespective of a function being
overridden by a direct operation, an activation or a deactivation of the automatic mode
(telegram update of the "Automatic" object) always re-enables the sunshine signal as well
and evaluates it when the automatic mode is active. Attention must be paid to this
behaviour especially in those cases where the "Automatic" object is cyclically overwritten
by telegrams.

1473-1-7829 | Rev. 01 | 3.2012 Page 66 of 144


Software "Blind, input/1.1"
Functional description

i The forced position function and the safety functions have a fixed priority higher than that of
the automatic sun protection. The sun protection is overridden – but not terminated – by a
function with a higher priority. After the end of the function with the higher priority the
reaction last executed by the automatic sun protection will therefore be executed again, if
the sun protection is still active at this time.
i With the settings "same priority" or "lower priority", the sunshine signal can be overridden
by a direct operation only if the direct control action can be executed at once. A direct
operation will therefore not override the sun signal during an active forced position function
or an active safety function.
i Parameter setting "same priority" or "lower priority": A variable preset of blind and slat
positions or of a slat offset via the bus at the beginning of sunshine / shading shows no
reaction at the output, if the sunshine signal was overridden by direct operation. However,
the position data or offsets received are stored internally so that the new positions can be
approached when the sensor signals that the sun is shining again.
i Irrespective of the preset priority, an update of the "Sunshine / shading facade" object from
active to active or from inactive to inactive in the extended sun protection mode shows
generally no reaction. The behaviour of the output is only influenced if a change of state is
detected.

Presetting the polarity of the "Sunshine / shading facade" object


The telegram polarity of the "Sunshine / shading facade" object can be preset. This means that
an adaptation to the signals from existing sensors or weather stations is possible in the simple
and also in the extended sun protection mode.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
o Set the parameter "Polarity of 'Sunshine / shading facade' object" on parameter page
"O1 - Sun protection" to the required telegram polarity.
The sunshine signal is evaluated in accordance with the preset priority.

i In the simple sun protection mode, an update (from activated to activated) of the
"Sunshine / shading facade" object causes the sun protection to be reactivated, if it had
been influenced and possibly been re-enabled beforehand by a direct operation in acc. with
the preset priority.
i In the extended sun protection mode, an update of the "Sunshine / shading facade" object
from active to active or from inactive to inactive shows generally no reaction. The behaviour
of the output is only influenced if a change of state is detected.

Presetting the activation of the automatic mode (for extended sun protection only)
As far as the activation of the automatic mode is concerned, two cases must be distinguished
which can be configured with the help of ETS parameters. Either a travel movement in acc. with
the reaction at the beginning or the end of sunshine is executed immediately on activation of the
automatic mode, or otherwise the system waits after activation of the automatic mode for a new
change of state in the "Sunshine / shading facade" object until the corresponding output shows
the reaction at the beginning or at the end of sunshine.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for extended sun protection.
o Set the parameter "Activation of automatic mode by..." on parameter page
"O1 - Sun protection" to "Object 'Automatic' and next change of state".

1473-1-7829 | Rev. 01 | 3.2012 Page 67 of 144


Software "Blind, input/1.1"
Functional description

Automatic operation is activated as soon as the "Automatic" object is set to 'active' in


consideration of polarity. A reaction at the output occurs, however, only after a new change
of state has been signalled via the "Sunshine / shading facade" object. In this case, the
new state (beginning of sunshine/shading or end of sunshine/shading) determines the
behaviour of the output.
o Set the parameter "Activation of automatic mode by..." on parameter page
"O1 - Sun protection" to "Object 'Automatic' & immediate tracking".
Automatic operation is activated as soon as object "Automatic" receives a "1" telegram.
The behaviour of the output (beginning of sunshine/shading or end of sunshine/shading) is
immediately determined by the state of the object "Sunshine / shading facade".

i Depending on the setting, various object numbers are created for the "Automatic" object in
the ETS. If the parameters are changed, the group address assignments for the automatic
object are lost.

Presetting the polarity of the "Automatic" object (for extended sun protection only)
If the automatic mode is to be activated via the object and only at the next change of state of the
sunshine signal (see "Presetting the activation of the automatic mode"), the telegram polarity of
the automatic object can be preset in addition.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The extended sun protection must be configured for activation of the automatic mode on next
change of state.
o Set the parameter "Polarity of 'Automatic' object" on parameter page "O1 - Sun protection"
to the required telegram polarity.
The telegram to the "Automatic" object will be evaluated depending on the selected priority.

i After an ETS programming operation or after switch-on of the supply voltage, the
object "Automatic" must at first have data written into it by the bus also in case of inverted
polarity before the automatic operation can be activated.
i The polarity of the "Automatic" object is not presettable, if the automatic mode is activated
via the object with immediate tracking. In this case, the telegram polarity is fixed:
Automatic ON = "1", Automatic OFF = "0".

Presetting the disabling function for the automatic mode (for extended sun protection
only)
Automatic mode can be deactivated at any time via a separate disabling object. After enabling
of the disabling function in the ETS parameters, the "Automatic mode disable" object becomes
visible.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The extended sun protection must be configured for activation of the automatic mode with
immediate tracking of the sunshine signal.
o Set the parameter "Disabling function for automatic mode ?" on parameter page
"O1 - Sun protection" to "yes".
The disabling function is enabled. The parameter for setting of the polarity becomes visible.
o Set the parameter "Polarity of object 'Automatic mode disable'" on parameter page
"O1 - Sun protection" to the required telegram polarity.

1473-1-7829 | Rev. 01 | 3.2012 Page 68 of 144


Software "Blind, input/1.1"
Functional description

The telegram to the "Automatic mode disable" object will be evaluated depending on the
selected priority.

i The objects "Automatic" and "Automatic mode disable" are logically combined
(AND with feedback). When disabling is activated, the automatic operation is reset and
thus aborted. The output will then show the behaviour at the end of automatic operation.
The automatic mode can only be reactivated, if the disabling object is enabled and if the
"Automatic" object is updated again by writing a "1" into it. Any attempt of activating the
automatic mode while a disable is active will be ignored.
i After an ETS programming operation or after switch-on of the supply voltage, the
objects "Automatic" and "Automatic mode disable" are always initialised with "0". If the
disabling object works with inverted polarity (setting "disabled" = "0") the disabling function
is in this case immediately active.

Presetting the disabling function for direct operation (for extended sun protection only)
The direct mode can be deactivated at any time via a separate disabling object. After enabling
of the disabling function in the ETS parameters, the "Direct operation disable" object becomes
visible.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for extended sun protection.
o Set the parameter "Disabling function for direct mode ?" on parameter page
"O1 - Sun protection" to "yes".
The disabling function is enabled. The parameter for setting of the polarity becomes visible.
o Set the parameter "Polarity of object 'Direct operation disable'" on parameter page
"O1 - Sun protection" to the required telegram polarity.
The telegram to the "Direction operation disable" object will be evaluated depending on the
selected priority.

i After an ETS programming operation or after switch-on of the supply voltage, the
"Automatic mode disable" object is always initialised with "0". If the disabling object works
with inverted polarity (setting "disabled" = "0") the disabling function is in this case
immediately active.

Presetting the reaction at the end of automatic operation (for extended sun protection
only)
When the automatic operation is being deactivated – also by the disabling function – the output
will show the preset reaction, if no function with a higher priority is active at the time of
deactivation. The preset reaction will not be executed either on termination of the automatic
operation, if the sunshine signal is overridden on account of priority settings by a direct
operation. The reaction at the end of automatic operation is preset on parameter page
"O1- Sun protection". Depending on the selected mode of operation, the ETS adapts the
designations of the parameter settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing
the louver.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for extended sun protection.
o Set the parameter "Reaction at the end of automatic operation" to "no reaction".
At the end of automatic operation the relay of the output shows no reaction. Any
movements still in progress at this instant will still be finished.

1473-1-7829 | Rev. 01 | 3.2012 Page 69 of 144


Software "Blind, input/1.1"
Functional description

o Set the parameter "Reaction at the end of automatic operation" to


"raising" or "opening the louver".
At the end of automatic operation, the device raises the blind or opens the venting louver.
o Set the parameter "Reaction at the end of automatic operation" to
"lowering" or "closing the louver".
At the end of automatic operation, the device lowers the blind or closes the venting louver.
o Set the parameter "Reaction at the end of automatic operation" to "stop".
At the end of automatic operation, the device switches the relays of the output to the "stop"
position. A drive movement, if any, will be interrupted.
o Set the parameter "Reaction at the end of automatic operation" to "position tracking".
At the end of automatic operation, the output will be set to the state last adjusted statically
before the automatic sun protection or to the state tracked and internally stored during the
automatic sun protection. The position objects, the long time object and the scene function
are tracked.

i The behaviour preset in this parameter will only be executed, if no function with a higher
priority (e.g. safety) is activated at the end of automatic operation.
i Parameter setting "Position tracking": The device can track absolute positions (position
telegram, scene value) at the end of automatic operation only if the position data is known
and if the positions have been predefined. There is otherwise no reaction at the end of
automatic operation.
Position data can be tracked, if the output was in a defined position before the automatic
sun protection function or if a new position telegram was received via the position objects
during the sun protection. In the latter case, a reference movement will be executed at the
end of automatic operation, if the position before or during the sun protection was
unknown.
Known slat positions will also be tracked as described. This is also the case, when the
height of the Venetian blind is unknown.
Long time travel movements (movements without position preset) will always be tracked.

Presetting a time delay for beginning and end of sunshine / shading


The telegram received via the object "Sunshine / shading facade" for activation or deactivation
of shading (depending on polarity) can be evaluated with a time delay. The preset delay times
are always evaluated in the simple as well as in the extended sun protection mode.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
o Set the parameter "Time delay at the beginning of sunshine / shading" on parameter page
"O1 - Beginning of sun protection" to the required delay time.
The telegram for activation of the sun shading will be evaluated with a delay corresponding
to the setting.
o Set the parameter "Time delay at the end of sunshine / shading" to the required delay time.
The telegram for deactivation of the sun protection will be evaluated with a delay
corresponding to the setting.

i A setting of "0" in the parameters deactivates the respective delay time. In this case, the
state of the sunshine signal is evaluated immediately.
i Simple sun protection mode: An update (from activated to activated) of the
"Sunshine / shading facade" object causes the sun protection to be reactivated in
consideration of the delay time, if the sun protection had been influenced or aborted
beforehand by a direct operation because of the same or a lower priority.

1473-1-7829 | Rev. 01 | 3.2012 Page 70 of 144


Software "Blind, input/1.1"
Functional description

i For extended sun protection mode: The time delay is started after an
update of the "Sunshine / shading facade" object also in those cases where the automatic
operation is deactivated so that the newly received information about the sunshine
conditions may possibly also be processed with a delay, if the automatic operation is
activated later on. Unlike in the simple sun protection mode, an update of the
"Sunshine / shading facade" object from active to active or from inactive to inactive in the
extended sun protection mode shows generally no reaction. The behaviour of the output is
only influenced if a change of state is detected. An update of the sunshine signal alone
does not result in the activation of the automatic operation either.

Presetting the reaction at the beginning of sunshine / shading


The behaviour of the output at the beginning of sunshine / shading – if applicable, after the end
of the delay time – can be configured in the ETS. In the simple sun protection mode, the
behaviour will be executed, when the sun protection function is activated after receiving a new
sunshine signal. In the extended sun protection mode, the output shows the configured
reaction, when automatic operation is activated and when a new sunshine signal
("sun is shining") is being received or was received beforehand. The reaction will not be
executed if a function with a higher priority is active at the time the sun shading is received.
The reaction at the beginning of sunshine / shading is preset on parameter page
"O1- Sun protection". Depending on the selected mode of operation, the ETS adapts the
designations of the parameter settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing
the louver. The ETS equally adapts the parameter selection depending on the preset mode of
operation.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
o Set the parameter "Reaction at the beginning of sunshine / shading" to "no reaction".
At the beginning of shading, the output switches over to sun protection while the relays of
the output show no reaction. Any movements still in progress at this instant will still be
finished.
o Set the parameter "Reaction at the beginning of sunshine / shading" to
"raising" or "opening the louver".
At the beginning of shading, the device raises the blind or opens the venting louver.
o Set the parameter "Reaction at the beginning of sunshine / shading" to
"lowering" or "closing the louver".
At the beginning of shading, the device lowers the blind or closes the venting louver.
o Set the parameter "Reaction at the beginning of sunshine / shading" to "stop".
At the beginning of shading, the device switches the relays of the output to the "stop"
position. A drive movement, if any, will be interrupted.
o Set the parameter "Reaction at the beginning of sunshine / shading" to
"internal scene recall". The number of the scene to be recalled must be specified in the
parameter "Scene number (1…8)".
At the beginning of shading, the device recalls the position value for the output which was
preset in the scene configuration. This is not a scene recall as in direct operation, but only
an approach to the corresponding scene position value.
o Set the parameter "Reaction at the beginning of sunshine / shading" to "fixed position".
At the beginning of shading, the device recalls a fixed position value output.

i In the "Venetian blinds" operating mode, the setting "fixed position" can be selected
separately for the height of the Venetian blind and for the slat position. For this reason, the
ETS adapts the parameter selection and enlarges the setting options in this operating
mode.

1473-1-7829 | Rev. 01 | 3.2012 Page 71 of 144


Software "Blind, input/1.1"
Functional description

o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"as parameter value". Thereafter, set the parameter
"Position of Venetian blind (0…100%)", "Position of roller shutter/awning (0…100%)" or
"Position of venting louver (0…100%)" to the desired position.
At the beginning of shading, the output invariably approaches the configured position value.
o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"no change of current position".
At the beginning of shading, the last set position of the Venetian blind height, the roller
shutter, awning or venting louver will be maintained.
o "Fixed position" and operating mode = "Venetian blind" only: Set the parameter
"Fixed slat position (0…100%)" to the desired position value.
At the beginning of shading, the output invariably moves the slats to the configured position
after the height of the Venetian blind has been adjusted.
o Set the parameter "Reaction at the beginning of sunshine / shading" to "variable position".
At the beginning of shading, the device recalls the variably specified position value output.
The variable specification of the Venetian blind height, the roller shutter, awning or venting
louver position takes place via the separate communication object
"...pos. sunshine / shading" (in the "Venetian blind" operating mode for the slats also using
the separate object "Slat position sunshine / shading").

i In the "Venetian blind" operating mode, the "variable position" setting can be selected
separately for the height of the Venetian blind and for the slat position. For this reason, the
ETS adapts the parameter selection and enlarges the setting options in this operating
mode.

i The behaviour preset in this parameter will only be executed, if no function with a higher
priority (e.g. safety) is activated at the time of shading.
i "Internal scene recall" setting: For this setting, the scene function of the output must be
enabled in the ETS. Otherwise, the positions approached at the beginning of sun shading
are undefined positions. The scene position values stored in the device by a scene storage
function will be approached as well. A delay configured for scene recalls has no influence
on the recall of the scene value by the sun protection function.
i "Variable position" setting: After an ETS programming operation or after switch-on of the
supply voltage, the
objects "Sunsh./shading ... position" and "Sunsh./ shading slat position" must receive
position values from the bus. Otherwise the device does not position itself at the start of
sun shading as it does not have any valid position data.
When the device is in operation, the position data can be updated at any time via the bus
even if the sun protection is active (e.g. by a weather station for the purpose of sun position
tracking). The device will then immediately approach the newly received positions if the sun
protection is active. If a function with a higher priority is active, the device stores the newly
received position values and approaches them during a later shading operation.
The position data last received are not lost in a bus voltage failure.

Presetting a forced reference movement in the sun protection mode


If needed, a reference movement can be executed by forced-control in the simple and in the
extended sun protection mode at the beginning of a shading cycle, if fixed or variable position
values or scene positions are to be approached. The execution of a reference movement by
forced control at the beginning of shading can be used in a sun protection positioning operation
to ensure that the curtains or slats are moved synchronously by different outputs to identical
positions (e.g. in a long row of windows). Without the execution of reference movement by
forced control, there might otherwise be positioning inaccuracies with a negative effect on the
overall appearance of a building facade with the blinds let down.

1473-1-7829 | Rev. 01 | 3.2012 Page 72 of 144


Software "Blind, input/1.1"
Functional description

A reference movement by forced control will always be executed in the simple sun protection
mode, when the beginning of shading is signalled for the first time via the
"Sunshine/shading facade" object. Updates of the object from 'sun is shining' to 'sun is shining'
do not initiate a reference movement if, at this time, the output is still in the sun protection
position.
A reference movement by forced control will be executed in the extended sun protection mode,
when the beginning of shading is signalled via the "Sun shading facade" object and when
automatic operation is active or is activated. Updates of the object from 'sun is shining' to
'sun is shining' will never initiate a reference movement. In this case, the sunshine signal must
first change from 'sun is not shining' to 'sun is shining' before a new reference movement can
take place.
A reference movement by forced control will always be executed for synchronisation purposes
as described and also in such cases where the position data of the blind or the slats are known.
No reference movement by forced control will be executed at the end of shading.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
o Set the parameter
"reference movement before every sun protection positioning operation ?" on parameter
page "O1 - Begin of sun protection" to "yes".
At the beginning of shading there is always a reference movement by forced control as
described. The preset position will be approached after the end of the reference movement.
o Set the parameter
"reference movement before every sun protection positioning operation ?" on parameter
page "O1 - Beginning of sun protection" to "no".
A reference movement at the beginning of sun protection will only be executed, if the
position data are unknown, for instance, after an ETS programming operation or after
switch-on of the power supply. In all other cases, the preset shading position will be
approached immediately.

i A reference movement is the time required for a travel movement into the upper end
position increased by 20 % and additionally by the configured travel time extension. A
reference travel is not retriggerable.
i Variable position preset: No reference movement will be executed, if new position values
are preset via the bus while the sun protection is active.
i "Venetian Blind" operating mode: A terminated reference movement of for the height of the
Venetian blind synchronises at the same time also the slat position.

1473-1-7829 | Rev. 01 | 3.2012 Page 73 of 144


Software "Blind, input/1.1"
Functional description

Slat offset in the sun protection mode (only "Venetian blind" operating mode)
An offset can be specified for the slat position at the start of sun shading, if fixed or variable slat
position values are to be approached.
If necessary, the slat offset can correct the fixed or variable nominal slat position and thus allow
the creation of an individual shading situation, when the sun protection is active. The offset can
be preset in two ways...
- The slat offset can be configured statically in the ETS. The configuration of a static offset
value allows variation of the degree of shading in those parts of the building that are not
exposed to full sunshine due to objects in front of the building. The variable slat angle
adjusted by the sun protection control or the fixed angle specified in a parameter can thus
be overridden so that the slats are always opened a bit wider than originally preset.
Alternatively, the slats can also be closed completely by means of the static offset if too
much sunlight is reflected into the room.
- The slat offset can additionally be adapted by the bus via the separate communication
object "Sunshine slat position offset". In this way, the desired slat offset can also be
adjusted during an active shading cycle and independent of a direct operation as, for
instance, the short time mode. Thus, it is possible, for instance, that persons in a room can
correct the slat angle at any time 'manually' and individually by selecting another preset
value at a touch sensor or a visualisation. An offset preset via the object overwrites the
value configured in the ETS.

The preset offset is taken into account in the simple and in the extended sun protection mode
for each positioning move during an active shading cycle (beginning of sun / shading) and
added to the predefined nominal slat position. The offset value can be varied within a range
from -100 % … 0 … 100 % so that the slats can be moved in both directions into the respective
end positions (Figure 24). At an offset of "0 %", the actual slat position is always identical with
the predefined nominal slat position for sun protection purposes.

Figure 24: Functional principle of slat offset


(example showing slat type 1 / slat type 2 identical)

The position value actually adjusted with the offset after adding the slat position value is always
between 0 and 100 %. Minimum and maximum position are thus determined by the slat end
positions. These limits cannot be exceeded by specifying an greater offset. Example
(Figure 24)...
Slat position at start of sun / shading = 90 %
Slat position offset at start of sun / shading = +30 %
-> The resulting slat position is 100% as the end position is reached.

In acc. with the KNX datapoint type 6.001 (DPT_Percent_V8) the data format of the
communication object "Sunshine slat position offset" permits presetting positive and negative
values in a range of -128 … 0 … +127. The device interprets the value received directly as an
offset in %. Values below 100 or above +100 are limited to the minimum (-100 %) and maximum
offset (+100 %) and evaluated accordingly.

An offset preset via the object overwrites the value configured in the ETS. In the event of a bus
voltage failure, an offset value received via the communication object can be stored internally in

1473-1-7829 | Rev. 01 | 3.2012 Page 74 of 144


Software "Blind, input/1.1"
Functional description

a non-volatile memory so that the offset value last received is not lost even in case the power
supply fails. As an alternative, the offset preset via the bus can be reset (0 %) in the event of a
power supply failure with the result that the value configured in the ETS is again used in
operation. The offset reaction preset in the event of bus voltage failure can be configured in the
ETS.

Configuring the slat offset in the sun protection mode (only "Venetian blind" operating
mode)
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must be configured for the "Venetian blind" operating mode.
The reaction at the beginning of sunshine/shading must be configured for fixed or variable
position preset.
o Set the parameter "Offset with fixed and variable slat position" on parameter page
"O1 - Beginning of sun protection" to "no offset".
The offset correction is deactivated. During shading (beginning of sunshine/shading), the
fixed or variable slat position will be approached without offset correction. The other
parameter relating to the offset are blanked out.
o Set the parameter "Offset with fixed and variable slat position" to "offset as configured".
The static offset correction based on the parameter preset in the ETS is activated. During
every shading operation (beginning of sunshine/shading), the nominal slat position is
always corrected by the configured offset value.
o Set the parameter "Offset with fixed and variable slat position" to
"offset as configured and via object".
The offset correction based on the parameter preset in the ETS and via the object is
activated. The slat offset is preset by a fixed value configured in the ETS and can be
adapted dynamically with a separate communication object. During every shading
operation (beginning of sunshine/shading), the nominal slat position is always corrected by
the preset offset value.
o Set the parameter "Slat offset position (-100 … 100 %)" on parameter page
"O1 - Beginning of sun protection" to the desired offset value.
The configured value defines the static offset correction of the slat position. The configured
value can be re-adjusted via the "Sunshine slat position offset" object, if the communication
object has been enabled.
o Set the "Store offset slat position via object in case of bus voltage failure ?" to "No".
The value received via the object will only be stored temporarily in volatile memory. The
received value only replaces the configured value until the device is reinitialised (bus
voltage return, if both were previously switched up). After the initialisation, the offset value
configured in the ETS will be used again.
o Set the "Store offset slat position via object in case of bus voltage failure ?" to "Yes".
The value received via the object will be stored in case of bus voltage failure in a non-
volatile memory of the device. The originally configured offset value is definitely overwritten
in the process. Only a new ETS programming operation sets the offset back to the
configured value.

i An offset value received via the bus is stored temporarily or permanently in the device and
taken into account during the next shading operation. The reception of an offset value
during an active shading phase (beginning of sunshine/shading active) results in an
immediate and 'visible' correction of the offset angle by the output.
i After an ETS programming operation, the offset is always set to the value configured in the
ETS.

1473-1-7829 | Rev. 01 | 3.2012 Page 75 of 144


Software "Blind, input/1.1"
Functional description

i Storage of the slat offset position in case of bus voltage failure: The offset value preset via
the object is stored only if the bus voltage has been available without interruption for at
least 20 seconds after the last reset (storage capacitors sufficiently charged for storage
purposes). In all other cases nothing is stored.
i The slat offset has no influence on the behaviour of an output at the end of a shading
phase (end of sunshine/shading).

Presetting the reaction at the end of sunshine / shading (for simple sun protection only)
At the end of the shading phase – if applicable, after the end of the delay time – the output will
show the preset reaction, if no function with a higher priority is active at the time of deactivation.
The preset reaction will also not be executed at the end of sun shading, if the sunshine signal is
overridden on account of priority settings by a direct operation.
The reaction at the end of sun shading is preset on parameter page "O1- Sun protection end".
Depending on the selected mode of operation, the ETS adapts the designations of the
parameter settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing the louver.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for simple sun protection.
o Set the parameter "Reaction at the end of sunshine / shading" to "no reaction".
At the end of shading, the relay of the output shows no reaction. Any movements still in
progress at this instant will still be finished.
o Set the parameter "Reaction at the end of sunshine / shading" to
"raising" or "opening the louver".
At the end of shading, the device raises the blind or opens the venting louver.
o Set the parameter "Reaction at the end of sunshine / shading" to
"lowering" or "closing the louver".
At the end of shading, the device lowers the blind or closes the venting louver.
o Set the parameter "Reaction at the end of sunshine / shading" to "stop".
At the end of shading, the device switches the relays of the output to the "stop" position. A
drive movement, if any, will be interrupted.
o Set the parameter "Reaction at the end of sunshine / shading" to "position tracking".
At the end of shading, the output will be set to the state last adjusted statically before sun
protection or to the state tracked and internally stored during sun protection. The position
objects, the long time object and the scene function are tracked.

i The behaviour preset in this parameter will only be executed, if no function with a higher
priority (e.g. safety) is activated when the sun protection is enabled or when a direct
operation has not overridden the sunshine signal on account of priority settings.
i Parameter setting "Position tracking": The device can track absolute positions (position
telegram, scene value) at the end of sun protection only if the position data are known and
if the positions have been predefined. There is otherwise no reaction at the end of sun
shading.
Position data can be tracked, if the output was in a defined position before the automatic
sun protection function or if a new position telegram was received via the position objects
during the sun protection. In the latter case, a reference movement will be executed at the
end of sun protection, if the position before or during the sun protection was unknown.
Known slat positions will also be tracked as described. This is also the case, when the
height of the Venetian blind is unknown.
Long time travel movements (movements without position preset) will always be tracked.

1473-1-7829 | Rev. 01 | 3.2012 Page 76 of 144


Software "Blind, input/1.1"
Functional description

Presetting the reaction at the end of sunshine / shading (for extended sun protection
only)
The behaviour of the output at the end of sunshine / shading – if applicable, after the end of the
delay time – can be configured in the ETS. In the extended sun protection mode, the output
shows the configured reaction, when automatic operation is activated and when a new sunshine
signal (change of state from "sun is shining" -> "sun is not shining") is being received. The
reaction will not be executed if a function with a higher priority is active at the time the sunshine
signal changes. The preset reaction will not be executed either, if the sunshine signal is
overridden on account of priority settings by a direct operation.
The reaction at the end of sunshine / shading is preset on parameter page
"O1- Sun protection end". Depending on the selected mode of operation, the ETS adapts the
designations of the parameter settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing
the louver.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for extended sun protection.
o Set the parameter "Reaction at the end of sunshine / shading" to "no reaction".
At the end of shading, the relay of the output shows no reaction. Any movements still in
progress at this instant will still be finished.
o Set the parameter "Reaction at the end of sunshine / shading" to
"raising" or "opening the louver".
At the end of shading, the device raises the blind or opens the venting louver.
o Set the parameter "Reaction at the end of sunshine / shading" to
"lowering" or "closing the louver".
At the end of shading, the device lowers the blind or closes the venting louver.
o Set the parameter "Reaction at the end of sunshine / shading" to "stop".
At the end of shading, the device switches the relays of the output to the "stop" position. A
drive movement, if any, will be interrupted.
o Set the parameter "Reaction at the end of sunshine / shading" to "internal scene recall".
The number of the scene to be recalled must be specified in the parameter
"Scene number (1…8)".
At the end of shading, the device recalls the position value for the output which was preset
in the scene configuration. This is not a scene recall as in direct operation, but only an
approach to the corresponding scene position value.
o Set the parameter "Reaction at the end of sunshine / shading" to "fixed position".
At the end of shading, the device recalls a fixed position value output.
i In the "Venetian blind" operating mode, the setting "fixed position" can only be selected in
common for the height of the Venetian blind and for the slat position.

o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"as specified by parameter". Thereafter, set the parameter
"Position of Venetian blind (0…100%)", "Position of roller shutter/awning (0…100%)" or
"Position of venting louver (0…100%)" to the desired position.
At the end of shading, the output invariably approaches the configured position value.
o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"no change of current position".
At the end of shading, the last set position of the Venetian blind height, the roller shutter,
awning or venting louver will be maintained.
o "Fixed position" and operating mode = "Venetian blind" only: Set the parameter
"Fixed slat position (0…100%)" to the desired position value.

1473-1-7829 | Rev. 01 | 3.2012 Page 77 of 144


Software "Blind, input/1.1"
Functional description

At the end of shading, the output invariably moves the slats to the configured position after
the height of the Venetian blind has been adjusted.

i The behaviour preset in this parameter will only be executed, if no function with a higher
priority (e.g. safety) is activated at the time the sunshine signal changes. The preset
reaction will not be executed either, if the sunshine signal is overridden on account of
priority settings by a direct operation.
i "Internal scene recall" setting: For this setting, the scene function of the output must be
enabled in the ETS. Otherwise, the positions approached at the end of sunshine/shading
are undefined positions. The scene position values stored in the device by a scene storage
function will be approached as well. A delay configured for scene recalls has no influence
on the recall of the scene value by the sun protection function.

1473-1-7829 | Rev. 01 | 3.2012 Page 78 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.4.6 Settings for automatic heating/cooling


Automatic heating/cooling
Automatic heating/cooling can supplement the extended sun protection so that the sun shading
of a room is available to an additional application.

When automatic heating / cooling is active, a presence signal – e.g. from a KNX / EIB presence
monitor or a detector – is evaluated in addition to the signals of the extended sun protection
function. The automatic sun protection function will then only be activated by the device when
people are in the room. The room is then shaded or not according to the sunshine signal (see
chapter 4.2.4.4.5. Sun protection settings).
If no presence is signalled, the device evaluates in addition a heating/cooling signal derived, for
instance, from a room temperature controller or from an outside thermostat. In this case, the
shading function can be used to support the heating or cooling function in a room. As no
persons are present in the room, intensive sunlight can be used, for instance, to heat up the
room by opening the slats or by raising the curtain. Similarly, the room can also be shaded
against sunlight during the absence of persons, if additional heating up of the room is not
desired.

By evaluating the three 1-bit signals "Presence", "Heating/cooling switchover" and


"Sunshine / shading facade" the telegram polarity of which can be configured independently in
the ETS, the enlarged sun protection function with automatic heating/cooling can differentiate
between the 6 states shown in Table 5 and the corresponding output reactions.

Presence Heating/ Sunshine / Reaction at output


signal cooling shading
switchover facade
persons --- (irrelevant) Sunshine signal Reaction at the beginning of sunshine/shading
present active
persons --- (irrelevant) Sunshine signal Reaction at the end of sunshine/shading
present inactive
No people Heating active Sunshine signal Reaction at the beginning of sunshine/shading
present active with heating
No people Heating active Sunshine signal Reaction at the end of sunshine/shading with
present inactive heating
No people Cooling active Sunshine signal Sunshine signal active reaction at the
present active beginning of sunshine/shading with cooling
No people Cooling active Sunshine signal Reaction at the end of sunshine/shading with
present inactive cooling

Table 5: States of the extended sun protection function with heating/cooling switchover
As described for the extended sun protection without automatic heating/cooling, the sunshine
signal will be delayed, if a delay is configured in the ETS for this signal. In the same way, the
presence signal can be evaluated independently after a delay, for example in order to
'debounce' short time changes to the signal state.
The schematic diagram (Figure 25) shows the interaction of the different communication objects
of the extended sun protection function in combination with the
automatic heating/cooling function. The diagram moreover illustrates the principle of
incorporating sensor components into the automatic heating/cooling system.

1473-1-7829 | Rev. 01 | 3.2012 Page 79 of 144


Software "Blind, input/1.1"
Functional description

Figure 25: Schematic diagram of automatic heating/cooling


(for reasons of simplicity shown without disabling functions of the automatic or direct operation)

In accordance with the schematic diagram, the automatic heating/cooling function is only active
when the automatic sun protection is active, too. Like in the extended sun protection mode
without automatic heating/cooling, the automatic sun protection is activated via the
object "Automatic" depending on the configuration either immediately or only after a change of
state has been detected for one of the signals "Presence", "Heating/cooling switchover" and
"Sunshine / shading facade" (cf. "Sun protection function – extended sun protection").
After an ETS programming operation or after switch-on of the bus voltage supply), the
corresponding communication objects of the signals "Presence", "Heating/cooling switchover"
and "Sunshine / shading facade" are initialised with "0". In accordance with the preset polarity,
the state of the sunshine and of the presence signal as well as the heating/cooling state will be
determined and the corresponding reaction executed provided the automatic sun protection
function is active. When the automatic sun protection is active, any change of state of the
presence signal or any change in the heating/cooling signal will be evaluated immediately and
the corresponding reaction executed.

The schematic function diagram (Figure 26) shows all possible functions of the extended sun
protection with automatic heating/cooling. For reasons of clarity, the functions with a higher
priority (manual control, forced position, safety function) are not shown in the diagram.

1473-1-7829 | Rev. 01 | 3.2012 Page 80 of 144


Software "Blind, input/1.1"
Functional description

Figure 26: Schematic function diagram of automatic heating/cooling

Enabling automatic heating/cooling


Automatic heating/cooling can be preset separately in the ETS. When automatic heating/cooling
is enabled, the extended sun protection function will be supplemented by the necessary
communication objects and parameters.
The sun protection function must be enabled on parameter page "O1 - Enabled functions".
Moreover, the function must have been configured for extended sun protection.
o Set the parameter "Automatic heating/cooling" on parameter page
"O1 - Automatic heating/cooling" to "enabled".
The automatic heating/cooling function is enabled. The necessary parameters and
communication objects are visible.
o Set the parameter "Automatic heating/cooling" on parameter page
"O1 - Automatic heating/cooling" to "disabled".

1473-1-7829 | Rev. 01 | 3.2012 Page 81 of 144


Software "Blind, input/1.1"
Functional description

The automatic heating/cooling function is deactivated. The corresponding parameters and


objects are hidden. Only the extended sun protection without evaluation of the heating/
cooling and of the presence signal is now configured.

i If the automatic heating/cooling activation parameters are changed, the group address
assignments and the parameter settings are lost. For this reason, the automatic heating/
cooling parameters should be selected directly at the beginning of configuration and then
not be changed anymore later on.

Presetting the polarity of the "Heating/cooling switchover" object


The telegram polarity of the "Heating / cooling switchover" object can be preset. This means
that an adaptation to the signals from existing room temperature controllers or from outside
thermostats is possible.
For the parameters to be visible, automatic heating/cooling must be enabled on parameter page
"O1 - Automatic heating/cooling".
o Set the parameter "Polarity of 'Heating/cooling switchover' object" to the required telegram
polarity.
The heating/cooling signal is evaluated in accordance with the preset priority.

i An update of the "Heating / cooling switchover" object from active to active or from inactive
to inactive shows generally no reaction. The behaviour of the output is only influenced if a
change of state is detected.
i After switch-on of the bus supply voltage, the heating/cooling switchover function is
initialised with an object value of "0".

Presetting the polarity of the "Heating/cooling presence" object


The telegram polarity of the "Heating / cooling presence" object can be preset. This means that
an adaptation to the signals from existing KNX/EIB presence monitors or detectors is possible.
For the parameters to be visible, automatic heating/cooling must be enabled on parameter page
"O1 - Automatic heating/cooling".
o Set the parameter "Polarity of 'Heating / cooling presence" object to the required telegram
polarity.
The presence signal is evaluated in accordance with the preset priority.

i An update of the "Heating / cooling presence" object from active to active or from inactive
to inactive shows generally no reaction. The behaviour of the output is only influenced if a
change of state is detected.
i After presence control of the bus supply voltage, the heating/cooling switchover function is
initialised with an object value of "0".

Presetting a time delay for beginning and end of presence


The telegram received via the object "Heating / cooling presence" for transmission of the
presence state (depending on polarity) can be evaluated with a time delay separately for the
output.
For the parameters to be visible, automatic heating/cooling must be enabled on parameter page
"O1 - Automatic heating/cooling".
o Set the parameter "Time delay at the beginning of presence" to the required delay time.

1473-1-7829 | Rev. 01 | 3.2012 Page 82 of 144


Software "Blind, input/1.1"
Functional description

The telegram for activation of the presence mode will be evaluated with a delay
corresponding to the setting.
o Set the parameter "Time delay at the end of presence" to the required delay time.
The telegram for deactivation of the presence mode will be evaluated with a delay
corresponding to the setting.

i A setting of "0" in the parameters deactivates the respective delay time. In this case, the
presence state is evaluated immediately on reception of a telegram.
i An update of the "Heating / cooling presence" object from active to active or from inactive
to inactive shows generally no reaction. The behaviour of the output is only influenced if a
change of state is detected. An update of the presence signal alone does not result in the
activation of automatic operation either.
i The time delay is started after an update of the "Heating / cooling presence" object also in
those cases where the automatic operation is deactivated so that the newly received
presence state may possibly also be processed with a delay, if the automatic operation is
activated later on.

Presetting the reaction of automatic heating/cooling


The behaviour of the output when automatic heating/cooling is active can be configured in the
ETS. A distinction is made between four states in the evaluation of the three 1-bit signals
"Presence", "Heating/cooling switchover" and "Sunshine / shading facade"...

- "Reaction at the beginning of sunshine / shading with heating",


- "Reaction at the end of sunshine / shading with heating",
- "Reaction at the beginning of sunshine / shading with cooling",
- "Reaction at the end of sunshine / shading with cooling".

The reaction of the output can be set separately in the ETS for each of the named states. There
is no difference between the parameter settings for the individual states. For this reason, the
following section only describes the possible configuration as an example.
The reaction at the end of automatic heating/cooling is set on parameter page
"O1 - Automatic heating/cooling". Depending on the selected mode of operation, the ETS
adapts the designations of the parameter settings ("raising" ↔ "opening the louver" / "lowering"
↔ "closing the louver.
For the parameters to be visible, automatic heating/cooling must be enabled on parameter page
"O1 - Automatic heating/cooling".
o Set the parameter "Reaction at the ... of sunshine / shading" to "no reaction".
During automatic heating/cooling, the relays of the output show no reaction. Any
movements still in progress will still be finished.
o Set the parameter "Reaction at the ... of sunshine / shading" to
"raising" or "opening the louver".
During automatic heating/cooling, the device raises the blind or opens the venting louver.
o Set the parameter "Reaction at the ... of sunshine / shading" to
"lowering" or "closing the louver".
During automatic heating/cooling, the device lowers the blind or closes the venting louver.
o Set the parameter "Reaction at the ... of sunshine / shading" to "stop".
During automatic heating/cooling, the device switches the relays of the output to the "stop"
position. A drive movement, if any, will be interrupted.
o Set the parameter "Reaction at the ... of sunshine / shading" to "internal scene recall". The
number of the scene to be recalled must be specified in the parameter
"Scene number (1…8)".
During automatic heating/cooling, the device recalls the position value preset in the scene
configuration for the output. This is not a scene recall as in direct operation, but only an
approach to the corresponding scene position value.

1473-1-7829 | Rev. 01 | 3.2012 Page 83 of 144


Software "Blind, input/1.1"
Functional description

o Set the parameter "Reaction at the ... of sunshine / shading" to "fixed position".
During automatic heating/cooling, the device recalls the fixed position value for the output.

i In the "Venetian blind" operating mode, the setting "fixed position" can only be selected in
common for the height of the Venetian blind and for the slat position.

o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"as specified by parameter". Thereafter, set the parameter
"Position of Venetian blind (0…100%)", "Position of roller shutter/awning (0…100%)" or
"Position of venting louver (0…100%)" to the desired position.
During automatic heating/cooling, the output invariably approaches the configured position
value.
o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"no change of current position".
With automatic heating/cooling, the last set position of the Venetian blind height, the roller
shutter, awning or venting louver will be maintained.
o "Fixed position" and operating mode = "Venetian blind" only: Set the parameter
"Fixed slat position (0…100%)" to the desired position value".
During automatic heating/cooling, the output invariably moves the slats to the configured
position after the height of the Venetian blind has been adjusted.

i The configured reactions will not be executed if a function with a higher priority is active
during automatic heating/cooling (e.g. safety function, forced position). The preset reaction
will not be executed either, if the automatic sun protection is overridden on account of
priority settings by a direct operation.
i "Internal scene recall" setting: For this setting, the scene function of the output must be
enabled in the ETS. Otherwise, the positions approached during automatic heating/cooling
are undefined positions. The scene position values stored in the device by a scene storage
function will be approached as well. A delay configured for scene recalls has no influence
on the recall of the scene value by the automatic heating/cooling function.

1473-1-7829 | Rev. 01 | 3.2012 Page 84 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.4.7 Scene function settings


Light scene function
A device can hold up to 8 scenes for output 1 and store scene position values for the height of a
Venetian blind, roller shutter or awning or the position of a venting louver. In the 'Venetian
blinds' mode, the user can also preset slat positions. The scene values are recalled or stored
via a separate scene extension object by means of extension telegrams. A scene recall can
optionally take place after a delay.
The datapoint type of the extension object permits addressing a maximum of 64 scenes. This
means that, in the configuration of a scene, it is possible to specify which scene number (1...64)
contacts the internal scene (1...8).

The scene function must be enabled on parameter page "O1 - Enabling functions", for the
required communication objects and parameters (on the parameter page "O1 - Scenes") to be
visible.

Like the output control via short time, long time or position telegrams, the scene function should
be assigned to direct operation. For this reason, a recalled scene position can at any time be
overridden by a forced position or a safety function. The scene position last recalled can also be
readjusted by other telegrams of the direct operation mode. The priority of direct operation and
also of the scene function can be configured with respect to the sun protection function (see
chapter 4.2.4.4.5. Sun protection settings).

Presetting a scene recall delay for the scene function


Each scene recall of the output can optionally also be delayed. With this feature, dynamical
scene sequences can be configured if several outputs are combined with cyclical scene
telegrams.
The scene function must be enabled on parameter page "O1 - Enabled functions".
o Set the parameter "Delay scene recall?" on parameter page "O1 - Scenes" to "yes".
The delay time is now activated and can be configured separately. The delay only
influences the scene recall of the output. The delay time is started on arrival of a recall
telegram. The corresponding scene will be recalled and the output set to the respective
scene position value only after this time has elapsed.

i Each scene recall telegram restarts the delay time and retriggers it. If a new scene recall
telegram is received while a delay is active (scene recall not yet executed), the old (and not
yet recalled scene) will be rejected and only the scene last received executed.
i The scene recall delay has no influence on the storage of scene values. A scene storage
telegram within a scene recall delay terminates the delay and thus the scene recall.
i In case of bus voltage failure, all time functions will be stopped. Therefore, all scene recalls
that are still in the delay stage will be aborted. A scene recall received shortly before bus
voltage failure is then lost, if the corresponding delay has not yet elapsed. A delayed scene
recall will also be aborted, if a function with a higher priority (forced position, safety, sun
protection, if the priority is the same as or higher than that of direct operation) is activated.
The scene recall is nevertheless stored internally so that the scene positions last recalled
can be tracked at the end of a higher-ranking function.

Presetting the ETS download behaviour for the scene function


During storage of a scene, the scene values are stored permanently in the device
(cf. "Presetting the storage behaviour for scene functions"). To prevent the stored values from
being replaced during ETS programming of the application or of the parameters by the originally
programmed scene position values, the device can inhibit overwriting of the scene values. As
an alternative, the original values can be reloaded into the device during each programming run
of the ETS.

1473-1-7829 | Rev. 01 | 3.2012 Page 85 of 144


Software "Blind, input/1.1"
Functional description

The scene function must be enabled on parameter page "O1 - Enabled functions".
o Set the parameter "Overwrite the values values in the device during ETS download ?" to
"Yes".
During each ETS programming of the application or of the parameters, the scene values
configured in the ETS for the output will be programmed into the device. Scene values
stored in the device by means of a storage function will be overwritten, if any.
o Set the parameter "Overwrite the values values in the device during ETS download ?" to
"No".
Scene values stored in the device with a storage function will be maintained. If no scene
values have been stored, the position values last programmed in the ETS remain valid.

i When the device is put into operation for the first time, this parameter should be set to
"yes" so that the output is initialised with valid scene values. In the device as delivered, the
scene positions are internally set to default values as in the ETS product database.

Presetting scene numbers


The datapoint type of the scene extension object permits addressing of up to 64 scenes max.
For this reason, the scene number (1...8) with which the scene is addressed, i.e. recalled or
stored, must be determined for each internal scene (1...64) of the output.
The scene function must be enabled on parameter page "O1 - Enabled functions".
o Set the parameter "Scene y activatable by scene number" (y = number of the scene (1…8))
on parameter page "O1 - Scenes" for each scene to the numbers with which the scenes
are to be addressed.
A scene can be addressed with the configured scene number. A setting of "0" deactivates
the corresponding scene so that neither recalling nor storage is possible.

i If the same scene number is configured for several scenes, only the scene with the lowest
internal scene number (1...8) will be addressed. The other internal scenes will be ignored in
this case.

Presetting scene positions


Moreover, the position value (Venetian blind, roller shutter, awning, venting louver position) to
be set for the output in case of a scene recall must be specified as well. In the
"Venetian blind" mode, the height of the Venetian blind and the slat position can be preset.
The scene function must be enabled on parameter page "O1 - Enabled functions".
o Set the parameter "Position ... for scene y" (y = number of the scene (1…8) on
parameter page "O1 - Scenes" for each scene to the desired position (0 %...100 %).
In case of a scene recall, the output is set to the configured position.

i The configured position values are adopted in the device during programming with the ETS
only if the parameter "Overwrite values stored in the device during ETS download ?" is set
to "yes".
i Before approaching the required scene position, the device may perform a reference
movement, if the current position data is unknown (e.g. after an ETS programming
operation or after switch-on of the bus voltage).

1473-1-7829 | Rev. 01 | 3.2012 Page 86 of 144


Software "Blind, input/1.1"
Functional description

Presetting the storage behaviour for the scene function


The current position value of a Venetian blind, roller shutter, awning, venting louver and also of
a slat can be stored internally via the extension object on reception of a scene storage telegram.
The position value can be influenced before storage by all functions of the output (e.g. short-
time and long-time operation or scene recall telegram, safety and sun protection function).
The scene function must be enabled on parameter page "O1 - Enabled functions".
o Set the parameter "Storage function for scene y" (y = number of the scene (1…8)) on
parameter page "O1 - Scenes" for each scene to "yes".
The storage function is activated for the scene in question. On reception of a storage
telegram via the "Scene extension" object, the current position value will be internally
stored.
o Set the parameter "Storage function for scene y" (y = number of the scene (1…8)) on
parameter page "O1 - Scenes" for each scene to "no".
The storage function is deactivated for the scene in question. A storage telegram received
via the "scene extension" object will be rejected.

i The following rules apply for the position data to be stored:


The current blind, slat and louver positions are stored. With Venetian blinds, the height to
be stored is always referred to a slat position of 100 %. A position temporarily approached
will also be stored for that output that are involved in a travel movement at the time of data
storage.
On account of the fact that position data is stored as integer percentage values
(rounding to 0...100), a minor deviation from the set positions on a later scene recall cannot
be avoided.
The data is only stored if the bus voltage has been available before without interruption for
at least 20 seconds after the last reset (storage capacitors sufficiently charged for storage
purposes). The data will not be stored, if the position data is unknown.

1473-1-7829 | Rev. 01 | 3.2012 Page 87 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.4.8 Forced position settings


Forced position function
The forced position function can be enabled for the output 1. The forced position has the
highest priority. An active forced position therefore overrides the safety function, the sun
protection function and the direct operation (short time, long time telegram, scenes, positioning).
During a forced-position state, the output is locked so that it can no longer be controlled with
functions of a lower priority.

The forced position function possesses a separate 2-bit communication object. The state of the
output in case of a forced position function is directly determined by the forced position
telegram. The first bit (bit 0) of the "Forced position" object specifies the travel direction to be
forced onto the output as in long time operation. The second bit (bit 1) activates or deactivates
the forced-position state (cf. table 6).

Bit 1 Bit 0 Function


0 x Forced position not active normal control
0 x Forced position not active normal control
1 0 Forced position active, raising / opening the louver
1 1 Forced position active, lowering / closing the louver

Table 6: Bit coding of forced position


The behaviour of an output at the end of the forced-position function can be configured. In
addition, the forced object can be initialised on bus voltage return.

i The forced movement time required by an output to move the drive into the end positions is
determined by the "Movement time" parameter on parameter page "O1 - Times". Like long
time operation, a forced-position movement is derived from the travel time. Downward
movement: movement time + 20 %; Upward movement: movement time + 20 % +
configured movement time extension. Forced movements are not retriggerable.
i The slats of blinds are not repositioned at the end of forced movements into the end
positions.
i Updates of the forced position object from "forced position active" to "forced position active"
while maintaining the forced movement direction or from "forced position inactive" to
"forced position inactive" show no reaction.
i After programming of the application or of the parameters with the ETS, the forced position
is always cancelled.
i The current state of the forced position function will be stored in case of bus voltage failure.

Enabling the forced position function


The forced position function can be enabled.
o Set the parameter "Forced position function" on parameter page "O1 - Enabled functions"
to "enabled".
The forced position function is enabled. The corresponding communication object is
created and the respective parameters on parameter page "O1 - Forced position" become
visible.

1473-1-7829 | Rev. 01 | 3.2012 Page 88 of 144


Software "Blind, input/1.1"
Functional description

Presetting the behaviour at the end of the forced position function


The behaviour of the output at the end of the forced position function can be configured. The
behaviour is configured on parameter page "O1 - Forced position".
The forced position function of the output must be enabled on parameter page
"O1 - Enabled functions". Only then are the parameters for the forced position function visible.
o Set the parameter "Behaviour at the end of the forced position function" to
"position tracking".
At the end of a forced position function, the output will be set to the state adjusted statically
before the forced position function or to the state tracked and internally stored during the
forced position function. The position objects, the long time object and the scene function
are tracked.
o Set the parameter "Behaviour at the end of the forced position function" to "no change".
At the end of forced position function, the state last adjusted will not be changed.
Thereafter, the output is again enabled. Any movements still in progress at this instant will
still be finished.

i Parameter setting "Position tracking": The device can track absolute positions (position
telegram, scene value) during activated forced control only if the position data are known
and if positions have been predefined. If this is not the case, no reaction takes place at the
time forced control is enabled.
Position data can be tracked, if the output has been in a defined position before the forced
position function or if a new position telegram has been received via the position objects
while the forced position function was interlocked. In the latter case, a reference movement
will be executed when the forced position function is enabled, if the position was unknown
before or during the safety interlock.
Known slat positions will also be tracked as described. This is also the case, when the
height of the Venetian blind is unknown.
Long time movements (movements without position preset) will, however, always be
tracked.
i The preset "Behaviour at the end of the forced position function" will only be executed, if
the output passes over to direct operation at the end of the forced position function. If a
safety function or a sun protection function is activated (independent of the preset priority
with respect to direct operation), the function with the next lower priority will be executed.
The configured behaviour is not executed when the forced position is terminated by a
specification on bus voltage return. The parameter "Behaviour after bus voltage return" will
in this case be evaluated.

Presetting the behaviour of the forced position function after bus voltage return
The forced position communication object can be initialised after bus voltage return. In this way,
an output can be influenced and locked on bus initialisation when the forced position function is
being activated.
The behaviour of the forced position after bus voltage return is configured separately on the
parameter pages "O1 - Forced position".
Depending on the selected operating mode, the ETS adapts the designations of the parameter
settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing the louver").
After bus voltage return, the configured state is transferred to the "Forced position"
communication object.
The forced position function of the output must be enabled on parameter page
"O1 - Enabled functions". Only then are the channel-related parameters for the forced position
function visible.
o Set the parameter "Behaviour after bus voltage return" to "no forced position active".
The forced position is deactivated after bus voltage return. In this case, the parameter
"Behaviour after bus voltage return" will be evaluated on bus voltage return.
o Set the parameter "Behaviour after bus voltage return" to
"forced position function ON, raising" or "forced position function ON, opening the louver".

1473-1-7829 | Rev. 01 | 3.2012 Page 89 of 144


Software "Blind, input/1.1"
Functional description

After bus voltage return, the forced position is activated and the blind raised or the venting
louver opened. The output is interlocked by forced control until an enable signal is received
via the bus. In this case, the parameter "Behaviour after bus voltage return" will not be
evaluated for the output.
o Set the parameter "Behaviour after bus voltage return" to
"forced position function ON, lowering" or "forced position function ON, closing the louver".
After bus voltage return, the forced position is activated and the blind lowered or the
venting louver closed. The output is interlocked by forced control until an enable signal is
received via the bus. In this case, the parameter "Behaviour after bus voltage return" will
not be evaluated for the output.
o Set the parameter "Behaviour after bus voltage return" to
"state of forced position before bus failure".
After bus voltage return, the forced position state last selected and internally stored before
bus voltage failure will be tracked. An ETS programming operation deletes the stored state
(reaction in that case same as with "no forced position active"). If the tracked state
corresponds to "no forced position active", the parameter
"Behaviour after bus voltage return" will be executed on return of bus voltage.

i Setting or tracked state "no forced position active": The reaction of the output after return of
bus voltage is defined by the parameter "Behaviour after bus voltage return".
i After programming of the application or of the parameters with the ETS, the forced position
is always cancelled.

1473-1-7829 | Rev. 01 | 3.2012 Page 90 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.4.9 Fabric stretching settings


Fabric-stretching function
In the roller shutter/awning operating mode, the fabric stretching function can be activated. The
fabric stretching function permits 'smoothing' the fabric of an awning tight after lowering. The
fabric stretching function can also be used with roller shutters to reopen the slits of the shutter
curtain after a downward movement into the lower end position.

If activated in the ETS parameters, fabric stretching is executed during each downward
movement after stopping and after the configured switchover delay has elapsed. The curtain is
then 'stretched' by moving briefly into the opposite movement direction (Figure 27).

Figure 27: Fabric stretching in an awning

The downward movement can be triggered by any of the following events: Long time, short time
or position telegram, forced position, safety or sun protection function or scene recall.

Fabric stretching is never effected in upward movements.

i Fabric stretching affects the determination of positions and the position feedback since a
fabric stretching movement changes the position of a shutter or an awning. In a positioning
move into the lower end position (100 %), the position value reported back after the fabric
stretching operation will always be a smaller one.
i Fabric stretching cannot be configured in the Venetian blind or louver modes of operation.

Activating the fabric stretching function


The fabric stretching function can be activated on parameter page "O1 - Enabled functions".
The operating mode selected must be the "Roller shutter/awning" mode.
o Set the parameter "Fabric stretching function" to "enabled".
Parameter page "O1 - Fabric stretching" is enabled and the fabric stretching function is
activated.

i Fabric stretching cannot be configured in the Venetian blind or louver modes of operation.

Presetting the fabric stretching function


The fabric stretching function can be configured independently for each roller shutter or awning
output on parameter page "O1 - Fabric stretching". The movement time required for fabric
stretching by means of a movement in opposite direction can be configured.
The fabric stretching function must be activated.

1473-1-7829 | Rev. 01 | 3.2012 Page 91 of 144


Software "Blind, input/1.1"
Functional description

o Select the desired value for the "Time for fabric stretching" parameter.
After the end of a downward movement the blind stops and – after the switchover delay
has elapsed – moves backwards in opposite direction for a period corresponding to the
configured fabric stretching time.

i Set the time for fabric stretching to less than the configured or measured movement time of
the roller shutter or awning. Otherwise, there is the risk of malfunction.
i Fabric stretching will only be effected if the downward movement lasts longer than the
configured fabric stretching time.

1473-1-7829 | Rev. 01 | 3.2012 Page 92 of 144


Software "Blind, input/1.1"
Functional description

4.2.4.5 Priorities for the output


The device distinguishes between different functions that can have an effect on the output. In
order to prevent conflicting states, each available function has a certain priority. The function
with the higher priority overrides the one with the lower priority.

For output 1 there are the following priorities...


- 1nd priority: forced position
- 2rd priority: safety function(s)
Priority levels 3 and 4 can be parameterized in the ETS. The options are then...
- 3th priority: sun protection function
- 4rd priority: direct operation via the bus (short time/long time operation, positioning,
scenes),
or...
- 3rd priority: direct operation via the bus (short time/long time operation, positioning,
scenes),
- 4th priority: sun protection function
or...
- 3rd priority: sun protection function and direct operation via the bus (short time/long time
operation, positioning, scenes).

1473-1-7829 | Rev. 01 | 3.2012 Page 93 of 144


Software "Blind, input/1.1"
Delivery state

4.2.5 Delivery state


Delivery state
In the state as delivered, the device is passive, i.e. no telegrams are transmitted to the bus. The
device can be programmed and put into operation via the ETS. The physical address is preset
to 15.15.255
Moreover the device has been configured at the factory with the following characteristics...

For output 1 (Venetian blind output)...


- Operating mode: Venetian blind
- Duration of short time operation: 0.5 seconds
- Movement time (continuous run): 1 minute
- Movement time (slat): 4 seconds
- Movement time extension: 2 %
- Break during movement direction changeover: 1 s
- Behaviour in case of bus voltage failure: no reaction
- Response to bus voltage return: stop
For inputs 1...3 (extension inputs)...
- Direction of action: I1 and I2 internally on Venetian blind output / I3 no function
- Operation concept: short - long - short
- Function: I1 UP / I2 DOWN
- Time between short and long time operation: 0.4 seconds
- Slat moving time: 2.5 seconds
- Response to bus voltage return: no reaction
- Delay after bus voltage return, 0 seconds

1473-1-7829 | Rev. 01 | 3.2012 Page 94 of 144


Software "Blind, input/1.1"
Parameters

4.2.6 Parameters

4.2.6.1 General parameters

Description Values Comment


h General
Output (O1)...
Delay after bus voltage 0...59 To reduce telegram traffic on the bus
return line after bus voltage activation (bus
Minutes (0...59) reset), after connection of the device to
the bus line or after programming with
the ETS, it is possible to delay all
actively transmitted feedback telegrams
of the actuator output. For this purpose
a channel-independent delay time can
be defined here for output 1. Only after
the configured time elapses are
feedback telegrams for initialisation
transmitted to the bus.

Setting of the delay time minutes for the


actuator output.
Seconds (0...59) 0...17…59 Setting of the delay time seconds for the
actuator output.

Extension inputs (I1, I2,


I3)...
Effect of the extension The device possesses extension inputs,
inputs which can have an internal effect on the
Venetian blind output or, alternatively,
affect the KNX/EIB separately,
depending on this parameter.
I1, I2 & I3 separately on the With the effect on the bus, the inputs
bus can, independently of one another,
transmit telegrams for switching or
dimming for Venetian blind control or
value encoder use (dimming value
encoder, light scene extension). They
then function like a pushbutton interface.
I1 & I2 internally on O1, I3 With the internal effect, inputs 1 and 2
separately on the bus directly operate the Venetian blind
output (O1). This configuration also
corresponds to the as-delivered status
(unprogrammed device). In this way, it is
possible, for example, for a connected
Venetian blind 'on the building site' to be
commissioned and operated simply by
applying the bus voltage and without
using additional sensors.
In this setting, extension input 3 also
affects the bus.

Debounce time 10...30...255 This parameter specifies the time for


(10...255 ms) software debounce for all the extension
inputs. A signal flank at the input is

1473-1-7829 | Rev. 01 | 3.2012 Page 95 of 144


Software "Blind, input/1.1"
Parameters

evaluated after a delay according to the


time set here.

Delay after bus voltage 0...59 It is possible to specify separately for


return each input whether a reaction should
Minutes (0...59) take place after a device reset (bus
voltage return or ETS programming
operation). This means that a defined
telegram can be transmitted to the bus
according to the input signal or with
forced control. The delay time for the
extension inputs configurable at this
point must have elapsed fully by the
time the set reaction is executed. Within
the delay, any pending flanks or signals
at the inputs are not evaluated and are
ignored.

Minute setting of the delay time for the


extension inputs.
Seconds (0...59) 0...17…59 Second setting of the delay time for the
extension inputs.

Telegram rate disabled Here it is possible to configure a general


limit Enabled telegram rate limit. If the telegram rate
limit is enabled, no more telegrams are
transmitted to the bus in 17 seconds
(permanently defined, cyclical time
interval) than is specified by the
parameter "Telegrams per 17 s". This
avoids fast flank changes at the inputs
causing an unpermissibly high bus load.
Telegrams per 17 s 30, 60, 100, 127 Setting the telegram rate (telegrams in
17 s) for the telegram rate limit.
Only visible on "Telegram rate limit =
enabled".

1473-1-7829 | Rev. 01 | 3.2012 Page 96 of 144


Software "Blind, input/1.1"
Parameters

4.2.6.2 Parameters for the extension inputs

Description Values Comment


h Input X - General (x = 1, 2, 3)
Function input x No function The basic function of the appropriate
(X = 1...3) Switching extension input is defined here.
Dimming It should be noted that the extension
Venetian blind inputs 1 and 2 can optionally affect the
Value transmitter internal Venetian blind output of the
device. In this case, inputs 1 and 2 do
not have separate communication
objects and are permanently configured
to the Venetian blind function in the
ETS. These inputs can only be given a
limited configuration.
In the "No function" setting, the
extension input is deactivated.

The following parameters are visible for the function "Switching"...


Command on rising No reaction This parameter can be used to define
flank ON which object value is transmitted first to
Switching object 1.1 OFF the bus via the first communication
TOGGLE object of the input when there is a rising
flank (TOGGLE - switchover of the
object value).

Command on falling No reaction This parameter can be used to define


flank ON which object value is transmitted first to
Switching object 1.1 OFF the bus via the first communication
TOGGLE object of the input when there is a falling
flank (TOGGLE - switchover of the
object value).

Command on rising No reaction This parameter can be used to define


flank ON which object value is transmitted first to
Switching object 1.2 OFF the bus via the second communication
TOGGLE object of the input when there is a rising
flank (TOGGLE - switchover of the
object value).

Command on falling No reaction This parameter can be used to define


flank ON which object value is transmitted first to
Switching object 1.2 OFF the bus via the second communication
TOGGLE object of the input when there is a falling
flank (TOGGLE - switchover of the
object value).

Behaviour after bus After a device reset (bus voltage return


voltage or ETS programming operation), the
return communication objects of the input can
be initialised. If, in the ETS, a delay is
set for the extension inputs after bus

1473-1-7829 | Rev. 01 | 3.2012 Page 97 of 144


Software "Blind, input/1.1"
Parameters

voltage return, the device only transmits


the telegrams when the delay has
elapsed.
No reaction After a device reset, no reaction takes
place automatically (no telegram is
transmitted to the bus).
Send ON telegram In this configuration, an "ON" telegram is
actively transmitted to the bus after a
device reset.
Send OFF telegram In this configuration, an "OFF" telegram
is actively transmitted to the bus after a
device reset.
Transmit current input In this setting, the device evaluates the
status static signal status of the input and,
according to this, transmits the
appropriately configured telegram to the
bus (contact closed at the input =
telegram as with rising flank; contact
open at input = telegram as with falling
flank). If, in this case, the flank
command dependent on the current
status is configured to "No reaction", the
device does not transmit a telegram to
the bus on initialisation.

The following parameters are visible for the function "Dimming"...


Operation This parameter specifies the reaction to
a rising flank at the input.
Single-surface operation: With a short signal length at the input,
Brighter / darker (TOGGLE) the object value of the switching object
is toggled and an appropriate telegram
transmitted. With a long signal length, a
dimming telegram (brighter / darker).
The dimming direction is only stored
internally and switched on sequential
dimming operations.
Two button operation: With a short signal length at the input,
Brighter (ON) an ON telegram is triggered and, if there
is a long signal length, a dimming
telegram (brighter) is triggered.
Two button operation: With a short signal length at the input,
Darker (OFF) an OFF telegram is triggered and, if
there is a long signal length, a dimming
telegram (darker) is triggered.
Two button operation: With a short signal length at the input,
Brighter (TOGGLE) the object value of the switching object
is toggled and an appropriate telegram
transmitted, if there is a long signal
length, a dimming telegram (brighter) is
triggered.
Two button operation: With a short signal length at the input,
Darker (TOGGLE) the object value of the switching object
is toggled and an appropriate telegram
transmitted, if there is a long signal

1473-1-7829 | Rev. 01 | 3.2012 Page 98 of 144


Software "Blind, input/1.1"
Parameters

length, a dimming telegram (darker) is


triggered.

Time between switching 0...59 Time from which the dimming function
and dimming ("long signal length") is executed.
Seconds (0...59) Sets the time seconds.
Milliseconds (4...9 x 4...9 Sets the time milliseconds.
100)

Behaviour after bus After a device reset (bus voltage return


voltage or ETS programming operation), the
return communication object "Switching" of the
input can be initialised. If, in the ETS, a
delay is set for the extension inputs after
bus voltage return, the device only
transmits the telegrams when the delay
has elapsed.
No reaction After a device reset, no reaction takes
place automatically (no telegram is
transmitted to the bus).
Send ON telegram In this configuration, an "ON" telegram is
actively transmitted to the bus after a
device reset.
Send OFF telegram In this configuration, an "OFF" telegram
is actively transmitted to the bus after a
device reset.

Increase brightness by 100 % A dimming telegram can increase


50 % brightness by a maximum of X %. This
25 % parameter determines the maximum
12.5 % dimming increments for a dimming
6% telegram. This parameter depends on
3% the set operation.
1.5 %

Reduce brightness by 100 % A dimming telegram can increase


50 % darkness by a maximum of X %. This
25 % parameter determines the maximum
12.5 % dimming increments for a dimming
6% telegram. This parameter depends on
3% the set operation.
1.5 %

Transmit stop telegram? No One or no telegram is transmitted on


yes releasing a pushbutton at the input
(falling flank).

Telegram No It is possible to use this parameter to


repeat? Yes determine whether the dimming
telegram should be repeated cyclically
for a long signal length (actuation of a
pushbutton at the input).

1473-1-7829 | Rev. 01 | 3.2012 Page 99 of 144


Software "Blind, input/1.1"
Parameters

Time between two 0...1...59 Time between two telegrams when


telegrams telegram repetition is active. A new
Seconds (0...59) dimming telegram is transmitted after
this time has elapsed.
Sets the time seconds.
Milliseconds (5...9 x 5...9 Sets the time milliseconds.
100)

The following parameters are visible for the function "Venetian Blind"...
Command on rising This parameter specifies the reaction to
flank a rising flank at the input.
No function The input is deactivated.
UP A short time telegram (UP) is triggered
by a short signal length and a long time
telegram (high) is triggered by a long
signal length.
DOWN A short time telegram (DOWN) is
triggered by a short signal length and a
long time telegram (low) is triggered by
a long signal length.
TOGGLE With this setting, the direction is
switched over internally long signal
length (MOVE). If a short time signal
transmits a STEP telegram, then this
STEP is always switched in the opposite
direction of the last MOVE. Several
STEP telegrams transmitted
successively are switched in the same
direction.

Behaviour after bus After a device reset (bus voltage return


voltage or ETS programming operation), the
return communication object "Long time
operation" of the input can be initialised.
If, in the ETS, a delay is set for the
extension inputs after bus voltage
return, the device only transmits the
telegrams when the delay has elapsed.
No reaction After a device reset, no reaction takes
place automatically (no telegram is
transmitted to the bus).
Up In this configuration, an "UP" telegram is
actively transmitted to the bus after a
device reset.
Down In this configuration, an "DOWN"
telegram is actively transmitted to the
bus after a device reset.

Operation concept This parameter specifies the telegram


sequence after actuation (rising flank).

1473-1-7829 | Rev. 01 | 3.2012 Page 100 of 144


Software "Blind, input/1.1"
Parameters

Short - long - short A STEP is transmitted with a rising flank


and the "Time between short and long
time operation" started. This STEP
serves the purpose of stopping a
continuous movement. If, within the
started time, a falling flank is detected,
the input does not transmit an additional
telegram. If no falling flank was detected
during the time, a MOVE is transmitted
automatically after the time has elapsed
and the "slat adjustment time" is started.
If a falling flank is detected within the
slat adjustment time, the input transmits
a STEP. This function is used for slat
adjustment.
Long - short A MOVE is transmitted when there is a
rising flank at the input and the "slat
adjustment time" started. If a falling flank
is detected within the started time, the
input transmits a STEP. This function is
used for slat adjustment.

Time between step and 0...59 Time after which the function of a long
move operation actuation is executed.
Seconds (0...59) Only visible with
"Operation concept = "Short – Long – S-
hort".
Sets the time seconds.
Milliseconds (4...9 x 4...9 Sets the time milliseconds.
100)

Slat moving time 0...2...59 Time during which a long time telegram
Seconds (0...59) for slat adjustment can be terminated by
a falling flank at the input.
Sets the time seconds.
Milliseconds (0...9 x 0...9 Sets the time milliseconds.
100)

The following parameters are visible for the function "Value encoder"...
Function as Dimming value encoder This parameter specifies the value
transmitter function to be executed. The
Scene recall without data format of the value object is
storage function dependent on the set function of the
value encoder.
Scene recall with storage
function

Temperature value
transmitter

Brightness value
transmitter

Transmit value / light rising flank (pushbutton This parameter specifies the flank which
scene number on as NO contact) starts signal evaluation in the device.
The setting "rising and falling flank

1473-1-7829 | Rev. 01 | 3.2012 Page 101 of 144


Software "Blind, input/1.1"
Parameters

falling flank (pushbutton as (switch)" cannot be selected with the


NC contact) value encoder function "Light scene
recall with memory function".
rising and falling flank
(switch)

Value on rising flank 0...100...255 This parameter specifies the value


(0...255) transmitted on a rising flank.
Only visible with "Dimming value
encoder" and "Transmit value on =
rising flank (pushbutton as NO contact)"
and "Transmit value on = rising and
falling flank (switch)".

Value on falling flank 0...255 This parameter specifies the value


(0...255) transmitted on a falling flank.
Only visible with "Dimming value
encoder" and "Transmit value on =
falling flank (pushbutton as NC contact)"
and "Transmit value on = rising and
falling flank (switch)".

Light scene number on 1...64 This parameter specifies the light scene
rising flank number transmitted on a rising flank.
(1...64) Only visible with "Light scene recall" and
"Transmit value on = rising flank
(pushbutton as NO contact)" and
"Transmit value on = rising and falling
flank (switch)".

Light scene number on 1...64 This parameter specifies the light scene
falling flank number transmitted on a falling flank.
(1...64) Only visible with "Light scene recall" and
"Transmit value on = falling flank
(pushbutton as NC contact)" and
"Transmit value on = rising and falling
flank (switch)".

Value on rising flank 0 °C...20 °C...40 °C This parameter specifies the


temperature value transmitted on a
rising flank.
Only visible with "Temperature value
encoder" and "Transmit value on =
rising flank (pushbutton as NO contact)"
and "Transmit value on = rising and
falling flank (switch)".

Value on falling flank 0 °C...18 °C...40 °C This parameter specifies the


temperature value transmitted on a
falling flank.
Only visible with "Temperature value
encoder" and "Transmit value on =
falling flank (pushbutton as NC contact)"
and "Transmit value on = rising and

1473-1-7829 | Rev. 01 | 3.2012 Page 102 of 144


Software "Blind, input/1.1"
Parameters

falling flank (switch)".

Value on rising flank 0 Lux...200 Lux...1.500 Lux This parameter specifies the brightness
value transmitted on a rising flank.
Only visible with "Brightness value
encoder" and "Transmit value on =
rising flank (pushbutton as NO contact)"
and "Transmit value on = rising and
falling flank (switch)".

Value on falling flank 0 Lux...1,500 Lux This parameter specifies the brightness
value transmitted on a falling flank.
Only visible with "Brightness value
encoder" and "Transmit value on =
falling flank (pushbutton as NC contact)"
and "Transmit value on = rising and
falling flank (switch)".

Behaviour after bus After a device reset (bus voltage return


voltage or ETS programming operation), the
return communication object of the value
encoder or light scene extension can be
initialised. If, in the ETS, a delay is set
for the extension inputs after bus voltage
return, the device only transmits the
telegrams when the delay has elapsed.
No reaction After a device reset, no reaction takes
place automatically (no telegram is
transmitted to the bus).
Reaction as rising flank In this configuration, a telegram is
actively transmitted to the bus after a
device reset in accordance with the
configuration for the rising flank.
Reaction as falling flank In this configuration, a telegram is
actively transmitted to the bus after a
device reset in accordance with the
configuration for the falling flank.
Transmit current input In this setting, the device evaluates the
status static signal status of the input and,
according to this, transmits the
appropriately configured telegram to the
bus (contact closed at the input =
telegram as with rising flank; contact
open at input = telegram as with falling
flank).
This setting can only be configured with
"Transmit value on = rising and falling
flank (switch)".

Adjustment via long No With the dimming value encoder and the
actuation Yes temperature and brightness value
encoder, the value to be transmitted can
be adjusted at any time during device
operation. A value adjustment can only
be configurable here when the value is

1473-1-7829 | Rev. 01 | 3.2012 Page 103 of 144


Software "Blind, input/1.1"
Parameters

to be transmitted only on a rising flank or


only on a falling flank, i.e. a pushbutton
is connected to the input. A value
adjustment is introduced by a long
signal at the input (> 5 s) and continues
for as long as the signal is detected as
active, i.e. the pushbutton is actuated.
With the first adjustment after
commissioning, the value programmed
by the ETS is increased cyclically by the
step width configured for the dimming
value encoder and transmitted. The step
width of the temperature value encoder
(1 °C) and the brightness value encoder
(50 Lux) is permanently defined. The
previously transmitted value is saved
after releasing the pushbutton. The next
long pushbutton actuation adjusts the
saved value and the direction of the
value adjustment changes.
Only visible with "Transmit value on =
rising flank (pushbutton as NO contact)"
and "Transmit value on = falling flank
(pushbutton as NC contact)".

Time between two 0...1...59 The time between two telegrams on


telegrams adjusting values can be configured here.
Seconds (0...59) Only visible on "Adjustment via long
actuation = Yes".
Sets the time seconds.
Milliseconds (5...9 x 5...9 Sets the time milliseconds.
100)

Level size (1...10) 1...10 Increments by which the adjusted value


is increased or decreased with long
actuation.
Only visible on "Function as = Dimming
value encoder".

h Input x - disable (X = 1, 2, 3) - Only for "Switching" function!


Disabling function disabled The extension inputs can be separately
switching object 1.1 Enabled disabled via the bus using 1-bit objects.
With the "Switching" function, it is
possible to disable the two switching
objects of an input independently of
each other. With an active disabling
function, signal flanks at the input are
ignored by the device related to the
affected objects.
This parameter enables the disabling
function of the first communication
object.

Polarity of the disabling Disable = 1 (Enable = 0) This parameter defines the polarity of
object Disable = 0 (Enable = 1) the disabling object.

1473-1-7829 | Rev. 01 | 3.2012 Page 104 of 144


Software "Blind, input/1.1"
Parameters

Behaviour at the No reaction With an active disable, the first switching


beginning of the ON object is disabled. This parameter
disabling function OFF specifies the command transmitted via
Switching object 1.1 TOGGLE this object at the beginning of the
disabling. "TOGGLE" switches over the
current object value.

Behaviour at the end of No reaction With an active disable, the first switching
the disabling function ON object is disabled. This parameter
Switching object 1.1 OFF specifies the command transmitted via
Transmit current input this object at the end of the disabling.
status "TOGGLE" switches over the current
object value. In the "Transmit current
input status" setting, the device
evaluates the current static signal status
of the input and, according to this,
transmits the appropriately configured
telegram to the bus (contact closed at
the input = telegram as with rising flank;
contact open at input = telegram as with
falling flank).

Disabling function disabled The extension inputs can be separately


switching object 1.2 Enabled disabled via the bus using 1-bit objects.
With the "Switching" function, it is
possible to disable the two switching
objects of an input independently of
each other. With an active disabling
function, signal flanks at the input are
ignored by the device related to the
affected objects.
This parameter enables the disabling
function of the second communication
object.

Polarity of the disabling Disable = 1 (Enable = 0) This parameter defines the polarity of
object Disable = 0 (Enable = 1) the disabling object.

Behaviour at the No reaction With an active disable, the second


beginning of the ON switching object is disabled. This
disabling function OFF parameter specifies the command
Switching object 1.2 TOGGLE transmitted via this object at the
beginning of the disabling. "TOGGLE"
switches over the current object value.

Behaviour at the end of No reaction With an active disable, the second


the disabling function ON switching object is disabled. This
Switching object 1.2 OFF parameter specifies the command
Transmit current input transmitted via this object at the end of
status the disabling. "TOGGLE" switches over
the current object value. In the "Transmit
current input status" setting, the device
evaluates the current static signal status

1473-1-7829 | Rev. 01 | 3.2012 Page 105 of 144


Software "Blind, input/1.1"
Parameters

of the input and, according to this,


transmits the appropriately configured
telegram to the bus (contact closed at
the input = telegram as with rising flank;
contact open at input = telegram as with
falling flank).

h Input x - disable (X = 1, 2, 3) - Only for "Dimming" function!


Disabling function disabled The extension inputs can be separately
Enabled disabled via the bus using 1-bit objects.
With an active disabling function, signal
flanks at the input are ignored by the
device related to the affected objects.
This parameter enables the disabling
function of the input.

Polarity of the disabling Disable = 1 (Enable = 0) This parameter defines the polarity of
object Disable = 0 (Enable = 1) the disabling object.

Behaviour at the No reaction With an active disable, the input is


beginning of the ON disabled. This parameter specifies the
disabling function OFF command transmitted via the
TOGGLE "Switching" object at the beginning of
the disabling. "TOGGLE" switches over
the current object value.

Behaviour at the end of No reaction With an active disable, the input is


the disabling function OFF disabled. This parameter specifies the
command transmitted via the
"Switching" object at the end of the
disabling.

h Input x - disable (X = 1, 2, 3) - Only for "Venetian blind" function!


Disabling function disabled The extension inputs can be separately
Enabled disabled via the bus using 1-bit objects.
With an active disabling function, signal
flanks at the input are ignored by the
device related to the affected objects.
This parameter enables the disabling
function of the input.

Polarity of the disabling Disable = 1 (Enable = 0) This parameter defines the polarity of
object Disable = 0 (Enable = 1) the disabling object.

Behaviour at the No reaction With an active disable, the input is


beginning of the Up disabled. This parameter specifies the
disabling function Down command transmitted via the "Long time
Toggle operation" object at the beginning of the
disabling. "TOGGLE" switches over the

1473-1-7829 | Rev. 01 | 3.2012 Page 106 of 144


Software "Blind, input/1.1"
Parameters

current object value.

Behaviour at the end of No reaction With an active disable, the input is


the disabling function Up disabled. This parameter specifies the
Down command transmitted via the "Long time
Toggle operation" object at the end of the
disabling. "TOGGLE" switches over the
current object value.

h Input x - disable (X = 1, 2, 3) - Only for "Value encoder" function!


Disabling function disabled The extension inputs can be separately
Enabled disabled via the bus using 1-bit objects.
With an active disabling function, signal
flanks at the input are ignored by the
device related to the affected objects.
This parameter enables the disabling
function of the input.

Polarity of the disabling Disable = 1 (Enable = 0) This parameter defines the polarity of
object Disable = 0 (Enable = 1) the disabling object.

Behaviour at the No reaction With an active disable, the input is


beginning of the disabled. This parameter specifies the
disabling function Reaction as rising flank command transmitted via the value
object at the beginning of the disabling.
Reaction as falling flank In the "Transmit current input status"
Transmit current input setting, the device evaluates the static
status signal status of the input and, according
to this, transmits the appropriately
configured telegram to the bus (contact
closed at the input = telegram as with
rising flank; contact open at input =
telegram as with falling flank).
The selection of the settings of this
parameter depends on the configured
flank evaluation of the input.

Behaviour at the end of No reaction With an active disable, the input is


the disabling function disabled. This parameter specifies the
Reaction as rising flank command transmitted via the value
object at the end of the disabling.
Reaction as falling flank In the "Transmit current input status"
setting, the device evaluates the static
Transmit current input signal status of the input and, according
status to this, transmits the appropriately
configured telegram to the bus (contact
closed at the input = telegram as with
rising flank; contact open at input =
telegram as with falling flank).
The selection of the settings of this
parameter depends on the configured
flank evaluation of the input.

1473-1-7829 | Rev. 01 | 3.2012 Page 107 of 144


Software "Blind, input/1.1"
Parameters

h Input x - Transmit cyclically (X = 1, 2, 3) - Only for "Switching" function!


Cyclical transmission ? Optionally, the object values can be
transmitted cyclically to the bus for the
"Switching" function. For this, the
transmission criteria must first be
defined in the ETS. This parameter
specifies with which value cyclical
transmission should take place.
The object value entered in the
switching objects by the device on a
flank change or externally by the bus is
always transmitted cyclically. The object
value is then also transmitted cyclically
when "no reaction" is assigned to a
rising or falling flank. Cyclical
transmission also takes place directly
after bus voltage return, if the reaction
after bus voltage return corresponds to
the transmission criterion for cyclical
transmission. During an active disable,
no cyclical transmissions take place via
the disabled input.
No cyclical transmission There is no cyclical transmission.
Repeat on ON Transmission takes place cyclically
when the object value is "ON".
Repeat on OFF Transmission takes place cyclically
when the object value is "OFF".
Repeat on ON and OFF Transmission takes place cyclically
irrespective of the object value.

Cyclical transmission yes Here, it is possible to specify whether


Switching object 1.1 ? No cyclical transmission should take place
via the first switching object of the input.

Time for cyclical 0...23 If cyclical transmission should take place


transmission via the first switching object of the input,
Hours (0...23) then the cycle time can be configured
here.
Sets the cycle time hours.
Minutes (0...59) 0...59 Sets the cycle time minutes.
Seconds (0...59) 0...30...59 Sets the cycle time seconds.

Cyclical transmission Yes Here, it is possible to specify whether


Switching object 1.2 ? No cyclical transmission should take place
via the second switching object of the
input.

Time for cyclical 0...23 If cyclical transmission should take place


transmission via the second switching object of the
Hours (0...23) input, then the cycle time can be
configured here.
Sets the cycle time hours.

1473-1-7829 | Rev. 01 | 3.2012 Page 108 of 144


Software "Blind, input/1.1"
Parameters

Minutes (0...59) 0...59 Sets the cycle time minutes.


Seconds (0...59) 0...30...59 Sets the cycle time seconds.

1473-1-7829 | Rev. 01 | 3.2012 Page 109 of 144


Software "Blind, input/1.1"
Parameters

4.2.6.3 Parameters for the Venetian blind output

Description Values Comment


h Output 1 - General
Operating mode Venetian blind The device can control various drive
(Please set first!) systems. This parameter defines which
Roller shutter / awning type of drive or which type of curtain is
connected to Output 1.
Venting louver The ETS adapts all of the following
parameters (designations, visible/non
visible, etc.) dynamically to the
respective "operating mode" parameter.
For this reason, the "Operating mode"
parameter should be adjusted before all
other parameters of an output.

Behaviour after ETS The device permits setting the preferred


programming relay contact position after ETS
programming.
Raising / opening the After programming with the ETS, the
louver device raises the blind or opens the
venting louver.
Lowering / closing the After programming with the ETS, the
louver device lowers blind or closes the venting
louver.
Stop After programming with the ETS, the
device switches the relays of the output
to the "stop" position. A drive movement,
if any, will be interrupted.

Behaviour in case of The device permits setting the preferred


bus voltage failure relay contact position in case of bus
voltage failure.
Stop In case of bus voltage failure, the device
switches the relays of the output to the
"stop" position. A drive movement, if
any, will be interrupted.
No reaction In the event of bus voltage failure, the
relay of the output shows no reaction.
Any drive movements still in progress at
the time of failure will be completely
finished.

Response to bus The device permits setting the preferred


voltage return relay contact position after bus voltage
return.
Stop In case of bus voltage return, the device
switches the relays of the output to the
"stop" position. A drive movement, if
any, will be interrupted.
Raising / opening the
louver

1473-1-7829 | Rev. 01 | 3.2012 Page 110 of 144


Software "Blind, input/1.1"
Parameters

After bus voltage return, the device


raises the blind or opens the venting
louver.
Lowering / closing the After bus voltage return, the device
louver lowers the blind or closes the venting
louver.
Position on bus failure After bus voltage return, the forced-
position state last selected and internally
stored before bus voltage failure will be
tracked.
Approaching a position In case of bus voltage return, the
connected drive can approach a position
specified by further parameters.

Position of Venetian 0...100 This parameter specifies the blind


blind on bus voltage position to be approached in case of bus
return voltage return.
(0...100%) This parameter is only visible, if
"Behaviour in case of bus voltage retur-
n" is set to "approach position". This
parameter is visible only in the 'Venetian
blind' operating mode.

Position of slat on bus 0...100 This parameter specifies the slat


voltage position to be approached in case of bus
return voltage return after the blind has been
(0...100%) positioned at the desired height.
This parameter is only visible, if
"Behaviour in case of bus voltage retur-
n" is set to "approach position". This
parameter is visible only in the 'Venetian
blind' operating mode.

Roller shutter/awning 0...100 This parameter specifies the roller


position on bus voltage shutter or awning position to be
return approached in case of bus voltage
(0...100%) return.
i This parameter is only visible, if
"Behaviour in case of bus voltage r-
eturn" is set to "approach position".
i This parameter is visible only in the
"Roller Shutter / Awning" operating
mode.

Position of venting 0...100 This parameter specifies the venting


louver on bus voltage louver position to be approached in case
return of bus voltage return.
(0...100%) This parameter is only visible, if
"Behaviour in case of bus voltage retur-
n" is set to "approach position". This
parameter is visible only in the 'Venting
louver' operating mode.

1473-1-7829 | Rev. 01 | 3.2012 Page 111 of 144


Software "Blind, input/1.1"
Parameters

Travelling time 2% The device extends all the up


extension for upward 3% movements or all venting louver
travel 4% movements into the opened position of
5% Venetian blind outputs using the
6% extension configured here. The time
7% extension expressed in percent is the
8% difference between the measured travel
9% time needed to reach the lower end
10 % position (completely closed position) and
12.5 % the time needed to reach the upper end
position (completely open position).

h Output 1 - Times
Short time operation This parameter can be used to configure
the reaction to a received short-time
telegram.
No (only stop) The drive will only be stopped if it is
executing a travel movement at the time
of telegram reception. There is no
reaction if no movement is in progress.
yes Short-time operation is started on
reception of a short-time telegram when
the drive is stationary. If the drive is in
motion at the time of telegram reception,
it will be stopped.

Time for short time 0...59 This parameter defines the duration of
operation short-time operation.
Seconds (0...59)
Sets the monitoring time seconds.
Milliseconds (0...99 x 0...99 Sets the monitoring time milliseconds.
10) The duration of short-time operation
should in no case exceed half the slat
adjusting time. This parameter is only
visible, if the parameter
"Short-time operation" is set to "yes".

Venetian blind travelling 0...1...59 This parameter defines the travelling


time time of the Venetian blind. The time
Minutes (0...19) needed for a complete travel from the
upper into the lower end position must
be determined.

Sets the minutes of the Venetian blind


travelling time.
Seconds (0...59) 0...59 Sets the seconds of the Venetian blind
travelling time.
The travelling time must be determined
precisely. These parameters are visible
only in the 'Blind' mode of operation.

Roller shutter/awning 0...1...59 This parameter defines the travelling


travelling time time of the roller shutter or awning. The
Minutes (0...59) time needed for a complete travel from

1473-1-7829 | Rev. 01 | 3.2012 Page 112 of 144


Software "Blind, input/1.1"
Parameters

the upper into the lower end position


must be determined.

Sets the minutes of the roller shutter/


awning moving time.
Seconds (0...59) 0...59 Sets the seconds of the roller shutter/
awning moving time.
The travelling time must be determined
precisely. These parameter are visible
only in the "Roller Shutter / Awning"
operating mode.

Venting louver travelling 0...1...59 This parameter defines the travelling


time time of the venting louver. The time
Minutes (0...59) needed for a complete travel from the
completely open into the completely
closed position must be determined.

Sets the minutes of the venting louver


travelling time.
Seconds (0...59) 0...59 Sets the seconds of the venting louver
travelling time.
The travelling time must be determined
precisely. These parameters are visible
only in the 'Venting louver' mode of
operation.

Slat travelling time 0...59 This parameter defines the travelling


Minutes (0...59) time of the slats. The time needed for a
complete movement from the completely
open slat position into the completely
closed slat position (downward direction)
must be determined.

Sets the minutes of the slat moving time.


Seconds (0...59) 0...4...59 Sets the seconds of the slat moving
time.
The travelling time must be determined
precisely. The slat moving time must be
selected shorter than the blind travelling
time. These parameters are visible only
in the 'Blind' mode of operation.

Switchover time for 0.5 s Specifies the break in a travel direction


travel direction change 1s change (switchover time).
2s
5s

h Output 1 - Enabled functions


Feedback functions disabled This parameter can be used to disable
or to enable the feedback functions.
Enabled When the function is enabled, the
required parameters will be displayed
under "O1 –Feedbacks".

1473-1-7829 | Rev. 01 | 3.2012 Page 113 of 144


Software "Blind, input/1.1"
Parameters

Safety functions disabled This parameter can be used disable or


to enable the safety functions. When the
Enabled function is enabled, the required
parameters will be displayed under
"O1 –Safety I...III".

Sun protection functions disabled This parameter can be used disable or


to enable the sun protection functions.
Enabled When the function is enabled, the
corresponding parameters will be
displayed under "O1 - Sun protection"
and the necessary objects enabled.

Light scene function disabled This parameter can be used disable or


to enable the scene function. When the
Enabled function is enabled, the corresponding
parameters will be displayed under
"O1 - Scenes" and the necessary object
enabled.

Forced position function disabled This parameter can be used to disable


or to enable the forced position function.
Enabled When the function is enabled, the
corresponding parameters will be
displayed under "O1 - Forced position"
and the necessary object enabled.

Fabric-stretching disabled This parameter can be used disable or


function to enable the fabric-stretching function.
Enabled When the function is enabled, the
required parameters will be displayed
under "O1 – Fabric stretching".

h Output 1 - Feedbacks
Venetian blind position The current Venetian blind position of
feedback the output can be reported separately
back to the bus.
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).
This parameter is visible only in the
'Venetian blind' operating mode.

Roller shutter/awning
position feedback

1473-1-7829 | Rev. 01 | 3.2012 Page 114 of 144


Software "Blind, input/1.1"
Parameters

The current roller shutter or awning


position of the output can be reported
separately back to the bus.
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).
This parameter is visible only in the
"Roller Shutter / Awning" operating
mode.

Venting louver position The current venting louver position of


feedback the output can be reported separately
back to the bus.
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).
This parameter is visible only in the
'Venting louver' operating mode.

Time delay for feedback Yes (delay time under The feedback telegram can be
telegram after bus "General"!) transmitted to the bus with a delay after
voltage bus voltage return or after programming
return ? No with the ETS. Setting "Yes" activates the
delay time of the feedback in case of
bus voltage return. The delay time is
configured under "General".
This parameter is only visible in case of
an actively transmitting feedback object.

Slat position feedback The current slat position of the output


can be reported separately back to the
bus.
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).

1473-1-7829 | Rev. 01 | 3.2012 Page 115 of 144


Software "Blind, input/1.1"
Parameters

This parameter is visible only in the


'Venetian blind' operating mode.

Time delay for feedback Yes (delay time under The feedback telegram can be
telegram after bus "General"!) transmitted to the bus with a delay after
voltage bus voltage return or after programming
return ? No with the ETS. Setting "Yes" activates the
delay time of the feedback in case of
bus voltage return. The delay time is
configured under "General".
This parameter is only visible in case of
an actively transmitting feedback object.

Invalid Venetian blind The device can report to the bus that the
position feedback current blind position is unknown (e.g.
after an initialisation, when no reference
movement has been executed as yet).
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).
This parameter is visible only in the
'Venetian blind' operating mode.

Invalid roller shutter- The device can report to the bus that the
awning position current roller shutter/awning position is
feedback unknown (e.g. after an initialisation,
when no reference movement has been
executed as yet).
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).
This parameter is visible only in the
"Roller Shutter / Awning" operating
mode.

Invalid venting louver The device can report to the bus that the
position feedback current venting louver position is
unknown (e.g. after an initialisation,
when no reference movement has been
executed as yet).

1473-1-7829 | Rev. 01 | 3.2012 Page 116 of 144


Software "Blind, input/1.1"
Parameters

no feedback No feedback object available for the


output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).
This parameter is visible only in the
'Venting louver' operating mode.

Time delay for feedback Yes (delay time under The feedback telegram can be
telegram after bus "General"!) transmitted to the bus with a delay after
voltage bus voltage return or after programming
return ? No with the ETS. Setting "Yes" activates the
delay time of the feedback in case of
bus voltage return. The delay time is
configured under "General".
This parameter is only visible in case of
an actively transmitting feedback object.

Drive movement The device can report to the bus that the
feedback connected drive is active, i.e. the output
is supplying power to the drive for a
travel direction.
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).

Time delay for feedback Yes (delay time under The feedback telegram can be
telegram after bus "General"!) transmitted to the bus with a delay after
voltage bus voltage return or after programming
return ? No with the ETS. Setting "Yes" activates the
delay time of the feedback in case of
bus voltage return. The delay time is
configured under "General".
This parameter is only visible in case of
an actively transmitting feedback object.

h Output 1 - Safety I
Wind alarm 1 disabled This parameter can be used to enable
the first wind alarm and thus to enable
Enabled the communication object
(setting: "disabled"). If the first wind
alarm is deactivated

1473-1-7829 | Rev. 01 | 3.2012 Page 117 of 144


Software "Blind, input/1.1"
Parameters

(setting: "disabled"), the configured


assignment of the Venetian blind output
to wind alarm 1 is not operational.

Wind alarm 2 disabled This parameter can be used to enable


the second wind alarm and thus to
Enabled enable the communication object
(setting: "disabled"). If the second wind
alarm is deactivated
(setting: "disabled"), the configured
assignment of the Venetian blind output
to wind alarm 2 is not operational.

Wind alarm 3 disabled This parameter can be used to enable


the third wind alarm and thus to enable
Enabled the communication object
(setting: "enabled"). If the third wind
alarm is deactivated
(setting: "disabled"), the configured
assignment of the Venetian blind output
to wind alarm 3 is not operational.

Rain alarm disabled This parameter can be used to enable


the rain alarm and thus to enable the
Enabled communication object
(setting: "enabled"). If the rain alarm is
deactivated (setting: "disabled"), any
configured assignment of the Venetian
blind output to the rain alarm is not
operational.
Frost alarm disabled This parameter can be used to enable
the frost alarm and thus to enable the
Enabled communication object
(setting: "enabled"). If the frost alarm is
deactivated (setting: "disabled"), any
configured assignment of the Venetian
blind output to the frost alarm is not
operational.

Priority of safety alarms Wind -> rain -> frost This parameter defines the priority
Wind -> frost -> rain ranking of the individual safety alarms.
Rain -> wind -> frost Interpretation:
Rain -> frost -> wind High -> medium -> low.
Frost -> rain -> wind The three wind alarms have the same
Frost -> wind -> rain priority with respect to one another.

h Output 1 - Safety II
Use wind alarm Yes If the wind alarms enabled under
monitoring function ? "O1 - Safety I" are to be monitored
(only if wind alarms are No cyclically for incoming telegrams to the
enabled!) safety objects, the monitoring function
must be enabled here (setting: "yes").
Otherwise (setting: "No") there is no

1473-1-7829 | Rev. 01 | 3.2012 Page 118 of 144


Software "Blind, input/1.1"
Parameters

cyclical monitoring of the objects.


As soon as the monitoring function is
activated here, telegrams must be
transmitted cyclically to all enabled wind
alarm objects. The monitoring function
may only be activated, if at least one
wind alarm has been activated under
"O1 - Safety I".

Time for monitoring 0...23 The wind alarm monitoring time is


wind alarm configured here.
Hours (0...23)
Sets the monitoring time hours.
Minutes (1...59) 1...25...59 Sets the monitoring time minutes.
The cycle time of the transmitter should
be less than half the configured
monitoring time of the device. The times
can only be set, if wind alarm monitoring
is activated.

Use rain alarm Yes If the rain alarm enabled under


monitoring function ? "O1 - Safety I" is to be monitored
No cyclically for incoming telegrams to the
safety object, the monitoring function
must be enabled here (setting: "yes").
Otherwise (setting: "No") there is no
cyclical monitoring of the object.
As soon as the monitoring function is
activated, telegrams must be transmitted
cyclically to the enabled rain alarm
object. The parameter is only visible, if
the rain alarm has been enabled under
"O1 - Safety I".

Time for monitoring rain 0...23 The rain alarm monitoring time is
alarm configured here.
Hours (0...23)
Sets the monitoring time hours.
Minutes (1...59) 1...2...59 Sets the monitoring time minutes.
The cycle time of the transmitter should
be less than half the configured
monitoring time of the device. The times
can only be set if rain alarm monitoring
is activated.

Use frost alarm Yes If the frost alarm enabled under


monitoring function ? "O1 - Safety I" is to be monitored
No cyclically for incoming telegrams to the
safety object, the monitoring function
must be enabled here (setting: "yes").
Otherwise (setting: "No") there is no
cyclical monitoring of the object.
As soon as the monitoring function is
activated, telegrams must be transmitted
cyclically to the enabled frost alarm
object. The parameter is only visible, if

1473-1-7829 | Rev. 01 | 3.2012 Page 119 of 144


Software "Blind, input/1.1"
Parameters

the frost alarm has been enabled under


"O1 - Safety I".

Time for monitoring 0...23 The frost alarm monitoring time is


frost alarm configured here.
Hours (0...23)
Sets the monitoring time hours.
Minutes (1...59) 1...2...59 Sets the monitoring time minutes.
The cycle time of the transmitter should
be less than half the configured
monitoring time of the device. The times
can only be set, if frost alarm monitoring
is activated.

h Output 1 - Safety III


Assignment to wind No This parameter defines whether the
alarms output responds to a wind alarm and to
Wind alarm 1 which of the alarms.

Wind alarm 2

Wind alarm 3

Wind alarm 1 + 2

Wind alarm 1 + 3

Wind alarm 2 + 3

Wind alarm 1 + 2 + 3
Behaviour in case of This parameter defines the behaviour of
wind alarm the output at the beginning of a wind
alarm.
The behaviour preset in this parameter
will be executed when one of the
assigned wind alarms is activated. This
parameter is only visible if the output
has been assigned to at least one wind
alarm.
No reaction At the beginning of the wind alarm or
wind alarms, the output is interlocked
and the relay of the output shows no
reaction. Any movements in progress at
this instant will still be completely
finished.
Raising / opening the The device raises the blind or opens the
louver venting louver at the beginning of the
wind alarm or wind alarms and locks the
output thereafter.
Lowering / closing the The device lowers the blind or closes
louver the venting louver at the beginning of
the wind alarm or wind alarms and locks
the output thereafter.
Stop At the beginning of the wind alarm or
wind alarms, the device switches the

1473-1-7829 | Rev. 01 | 3.2012 Page 120 of 144


Software "Blind, input/1.1"
Parameters

relays of the output to "stop" and locks


the output. A drive movement, if any, will
be interrupted.

Assignment to rain Yes This parameter defines whether the


alarm output responds to the rain alarm.
No

Behaviour in case of This parameter defines the behaviour of


rain alarm the output at the beginning of the rain
alarm.
This parameter is only visible, if the
output has been assigned to the rain
alarm.
No reaction At the beginning of the rain alarm, the
output is locked and the relay of the
output shows no reaction. Any
movements in progress at this instant
will still be completely finished.
Raising / opening the The device raises the blind or opens the
louver venting louver at the beginning of the
rain alarm and locks the output
thereafter.
Lowering / closing the The device lowers the blind or closes
louver the venting louver at the beginning of
the alarm and locks the output
thereafter.
Stop At the beginning of the rain alarm, the
deviceswitches the relays of the output
to "stop" and locks the output. A drive
movement, if any, will be interrupted.

Assignment to frost Yes This parameter defines whether the


alarm output responds to the frost alarm.
No

Behaviour in case of This parameter defines the behaviour of


frost alarm the output at the beginning of the frost
alarm.
This parameter is only visible, if the
output has been assigned to the frost
alarm.
No reaction At the beginning of the frost alarm, the
output is interlocked and the relay of the
output shows no reaction. Any
movements in progress at this instant
will still be completely finished.
Raising / opening the The device raises the blind or opens the
louver venting louver at the beginning of the
frost alarm and locks the output
thereafter.
Lowering / closing the The device lowers the blind or closes
louver the venting louver at the beginning of

1473-1-7829 | Rev. 01 | 3.2012 Page 121 of 144


Software "Blind, input/1.1"
Parameters

the frost alarm and locks the output


thereafter.
Stop At the beginning of the frost alarm, the
device switches the relays of the output
to "stop" and locks the output. A drive
movement, if any, will be interrupted.

Behaviour at the end of This parameter defines the behaviour of


safety the output at the end of all safety
(Wind, rain, frost) functions.
The behaviour preset in this parameter
will only be executed, if the output
passes over to direct operation at the
end of safety. Direct operation will be
executed when a sun protection function
is active.
No reaction At the end of the safety functions, the
output is unlocked and the relay of the
output shows no reaction. Any
movements still in progress at this
instant will still be finished.
Raising / opening the The device unlocks the output at the end
louver of all safety alarms and raises the blind
or opens the venting louver.
Lowering / closing the The device unlocks the output at the end
louver of the safety functions and lowers the
blind or closes the venting louver.
Stop At the end of the safety functions, the
output is unlocked and the device
switches the relays of the output into the
"stop" position. A drive movement, if
any, will be interrupted.
Tracking the position At the end of safety, the output will be
set to the state last adjusted before the
safety function or to the state tracked
and internally stored during the safety
function. The position objects, the long
time object and the scene function are
tracked.

h Output 1 - Sun protection


Type of sun protection This parameter defines the scope of sun
protection functions.
simple sun protection Reduced scope of functions with
standard configuration possibilities.
enlarged sun protection Enlarged scope of functions including
mode the possibilities of the simple sun
protection. In addition, the connected
drive can be integrated in shading
control systems depending on the
position of the sun.
Automatic heating/cooling can also be
implemented.

1473-1-7829 | Rev. 01 | 3.2012 Page 122 of 144


Software "Blind, input/1.1"
Parameters

Priority of sun protection This parameter defines the priority of the


with respect to direct sun protection function with respect to
operation direct operation.
same priority The sun protection can be overridden by
direct operation and vice versa. Only
after the next reception of a
"sun is shining" signal will the sun
protection mode be activated again.
higher priority The sun protection has the higher
priority and cannot be aborted by a
direct operation.
Lower priority The direct operation has the higher
priority and cannot be aborted by sun
protection. The sun protection can be
activated only after an enabling
movement into the upper end position
initiated by a direct operation has
occurred without interruption.
This parameter is only visible in the
simple sun protection. Direct operation
= long-time/short-time operation;
Positioning via objects, scenes

Priority of automatic This parameter defines the priority of


operation with respect automatic operation with respect to
to direct operation direct operation. The selected priority
affects the evaluation of the sunshine
signal in the automatic mode and not the
automatic mode itself.
same priority The evaluation of the sunshine signal in
the automatic mode can be overridden
by a direct operation. In the same way, a
direct operation is overridden by the
reception of a new sunshine telegram.
higher priority The automatic mode has the higher
priority and cannot be aborted by a
direct operation irrespective of the state
of the sunshine signal. A direct
operation will be possible again only
after the automatic mode is terminated.
Lower priority The direct operation has the higher
priority and cannot be aborted by a
sunshine signal in the automatic mode.
The sunshine signal is evaluated again
only after an enabling movement into
the upper end position initiated by a
direct operation has occurred without
interruption and only if the automatic
mode is activated and not disabled at
this time.
This parameter is only visible in the
extended sun protection. Direct
operation =
long-time/short-time operation;
Positioning via objects, scenes

1473-1-7829 | Rev. 01 | 3.2012 Page 123 of 144


Software "Blind, input/1.1"
Parameters

Polarity of the sunshine = 1; no This parameter defines the polarity of


"Sunshine / shading fac- sunshine = 0 the input object
ade" object "Sunshine / shading facade" of the sun
Sunshine = 0; no sunshine protection.
=1

Activation of automatic This parameter defines how to activate


operation via... the automatic mode and the reactions
resulting from such activation.
Object "Automatic" & next Automatic operation is activated as soon
change of state as the "Automatic" object is set to
'active' in consideration of polarity. A
reaction at the output occurs, however,
only after a new change of state has
been signalled via the
"Sunshine / shading facade" object. In
this case, the new state (beginning of
sun protection or end of sun protection)
determines the behaviour of the output.
object "Automatic" & Automatic operation is activated as soon
immediate tracking as the "Automatic" object receives a
"1" telegram. The state of the object
"Sunshine / shading facade"
immediately determines the behaviour of
the output (beginning of sun protection,
end of sun protection).

The reception of a
telegram 'Automatic mode inactive' at
the "Automatic" object immediately ends
the automatic mode in both cases. The
behaviour is in this case defined by the
parameter
"Reaction at the end of automatic opera-
tion".

Polarity of "Automatic" automatic mode: This parameter defines the polarity of


object activated = 1; deactivated the automatic object.
=0 This parameter is only visible if the
parameter
Automatic mode: activated "Activation of automatic operation via..."
= 0; deactivated = 1 is set to
"automatic" & next change of state".

Disabling function for Yes The automatic mode can be disabled.


automatic mode ? When disabling is active, the automatic
No mode is aborted. It can only be
reactivated, if a "1" is written into the
"Automatic" object. The objects
"Automatic" and
"Automatic mode disable" are logically
combined (AND with feedback).
The "Yes" setting enables the disabling
function and makes the disabling object
visible.
This parameter is only visible, if the

1473-1-7829 | Rev. 01 | 3.2012 Page 124 of 144


Software "Blind, input/1.1"
Parameters

parameter
"Activation of automatic operation via..."
is set to
"object automatic & immediate tracking".
Polarity of "Automatic Automatic mode: enabled = This parameter defines the polarity of
mode disable" object 1; disabled = 0 the automatic mode disable object.
Disabling is active when a telegram with
Automatic mode: enabled polarity 'disabled' is received.
= 0; disabled = 1 This parameter is only visible, if the
parameter
"Disabling function for automatic mode -
?" is set to "yes".
Disabling function for Yes Direct operation can be disabled. When
direct operation ? disabling is active, a direct operation
No can – independent of the preset
priority – never override a sun protection
function. In this case, direct operation is
disabled in other functions, too.
The "Yes" setting enables the disabling
function and makes the disabling object
visible.
Direct operation =
long-time/short-time operation;
Positioning via objects, scenes

Polarity of "Direct Automatic mode: enabled = This parameter defines the polarity of
operation disable" 1; disabled = 0 the disabling object for direct operation.
object Disabling is active when a telegram with
Automatic mode: enabled polarity 'disabled' is received.
= 0; disabled = 1 This parameter is only visible, if the
parameter "Direct operation disable?" is
set to "yes".

Reaction at the end of This parameter defines the behaviour of


automatic operation the output at the end of automatic
operation and also at the beginning of
an automatic operation disable.
The behaviour preset in this parameter
will only be executed, if no function with
a higher priority (e.g. safety) is activated
at the end of automatic operation.
No reaction At the end of automatic operation, the
sun protection function is ended and the
relay of the output shows no reaction.
Any movements still in progress at this
instant will still be finished.
Raising / opening the At the end of automatic operation, the
louver device terminates the sun protection and
raises the blind or opens the venting
louver.
Lowering / closing the At the end of automatic operation, the
louver device terminates the sun protection and
lowers the blind or closes the venting
louver.
Stop At the end of automatic operation the
sun protection is terminated and the
device switches the relays of the output

1473-1-7829 | Rev. 01 | 3.2012 Page 125 of 144


Software "Blind, input/1.1"
Parameters

to "stop". A drive movement, if any, will


be interrupted.
Tracking the position At the end of automatic operation, the
output will be set to the state last
adjusted before the automatic sun
protection or to the state tracked and
internally stored during the automatic
sun protection. The position objects, the
long time object and the scene function
are tracked.

h Output 1 - Beginning of sun protection


Time delay beginning of 0...59 The telegram received via the object
sunshine / shading "Sunshine / shading facade" for
Minutes (0...59) activation of shading (depending on
polarity) can be evaluated with a time
delay..

Setting the delay time minutes.


Seconds (0...59) 0...30...59 Setting the delay time seconds.
A time setting of "0" in the parameters
deactivates the respective delay time. In
this case, the state of shading is
evaluated immediately.

Reaction at the This parameter defines the behaviour of


beginning of sunshine / the output at the beginning of shading –
shading if applicable, after the end of the delay
time.
This parameter is visible only in the
'Venetian blind' operating mode.
No reaction At the beginning of shading, the output
switches over to sun protection while the
relays of the output show no reaction.
Any movements still in progress at this
instant will still be finished.
Raising At the beginning of shading, the device
raises the blind.
Lowering At the beginning of shading, the device
lowers the blind.
Stop At the beginning of shading, the device
switches the relays of the output to the
"stop" position. A drive movement, if
any, will be interrupted.
Internal scene recall At the beginning of shading, the device
recalls the position values for the
affected output which were preset in the
scene configuration. This is not a scene
recall as in direct operation, but only an
approach of the corresponding scene
position values.
Venetian blind or slat
position fixed

1473-1-7829 | Rev. 01 | 3.2012 Page 126 of 144


Software "Blind, input/1.1"
Parameters

At the beginning of shading, the output


controls the approach to a configured
fixed Venetian blind and slat position.
Venetian blind position At the beginning of shading, the output
fixed / slat position variable controls the approach to a configured
fixed Venetian blind position and to slat
position preset by a separate object and
thus variable.
Slat position fixed / At the beginning of shading, the output
Venetian blind position controls the approach to a configured
variable fixed slat position and to a Venetian
blind position preset by a separate
object and thus variable.
Venetian blind and slat At the beginning of shading, the output
position variable controls the approach to the Venetian
blind and slat positions preset by two
separate objects and thus variable.

Reaction at the This parameter defines the behaviour of


beginning of sunshine / the output at the beginning of shading –
shading if applicable, after the end of the delay
time.
This parameter is visible only in the
"Roller Shutter / Awning" operating
mode.
No reaction At the beginning of shading, the output
switches over to sun protection while the
relays of the output show no reaction.
Any movements still in progress at this
instant will still be finished.
Raising At the beginning of shading, the device
raises the blind.
Lowering At the beginning of shading, the device
lowers the blind.
Stop At the beginning of shading, the device
switches the relays of the output to the
"stop" position. A drive movement, if
any, will be interrupted.
Internal scene recall At the beginning of shading, the device
recalls the position values for the
affected output which were preset in the
scene configuration. This is not a scene
recall as in direct operation, but only an
approach of the corresponding scene
position values.
shutter / awning position At the beginning of shading, the output
fixed controls the approach to a configured
fixed roller shutter / awning position.
Roller shutter / awning At the beginning of shading, the output
position variable controls the approach to the roller
shutter / awning position preset by a
separate object and thus variable.

1473-1-7829 | Rev. 01 | 3.2012 Page 127 of 144


Software "Blind, input/1.1"
Parameters

Reaction at the This parameter defines the behaviour of


beginning of sunshine / the output at the beginning of shading –
shading if applicable, after the end of the delay
time.
This parameter is visible only in the
"Venting louver" operating mode.
No reaction At the beginning of shading, the output
switches over to sun protection while the
relays of the output show no reaction.
Any movements still in progress at this
instant will still be finished.
Opening the louver At the beginning of shading, the device
opens the venting louver.
Closing the louver At the beginning of shading, the device
closes the venting louver.
Stop At the beginning of shading, the device
switches the relays of the output to the
"stop" position. A drive movement, if
any, will be interrupted.
Internal scene recall At the beginning of shading, the device
recalls the position values for the
affected output which were preset in the
scene configuration. This is not a scene
recall as in direct operation, but only an
approach of the corresponding scene
position values.
Fixed position of venting At the beginning of shading, the output
louver controls the approach to a configured
fixed venting louver position.
Venting louver position At the beginning of shading, the output
variable controls the approach to the venting
louver position preset by a separate
object and thus variable.

Scene number (1...8) 1...8 This parameter defines the number of


the internal scene which is recalled at
the beginning of shading.
This parameter is only visible, if the
parameter "Reaction at the beginning of
sunshine / shading" is set to "internal
scene recall".

Fixed position of The fixed Venetian blind position at the


Venetian blind beginning of shading can either be
preset statically by a separate
parameter or basically adjusted to the
value prevailing at the time of shading
activation, i.e. remain unchanged.
Same as configured value At the beginning of shading, the
configured Venetian blind position value
will be approached.
No change in current At the beginning of shading, the current
position position of the Venetian blind will be
maintained. In this case, the output

1473-1-7829 | Rev. 01 | 3.2012 Page 128 of 144


Software "Blind, input/1.1"
Parameters

behaves as if only the slat were


positioned as a result of shading.
This parameter is only visible, if the
Venetian blind is to approach a fixed
position at the beginning of shading.
This parameter is visible only in the
'Venetian blind' operating mode.

Venetian blind position 0...50…100 This parameter sets the fixed position of
(0...100 %) the Venetian blind to be approached at
the beginning of shading.
This parameter is only visible, if the
parameter "Fixed position of Venetian
blind" is set to "as specified by
parameter". This parameter is visible
only in the 'Venetian blind' operating
mode.

Fixed slat position 0...50…100 This parameter sets the fixed position of
(0...100 %) the slat to be approached at the
beginning of shading and, as the case
may be, after positioning of the Venetian
blind.
This parameter is only visible, if the slat
is to approach a fixed position at the
beginning of shading. This parameter is
visible only in the 'Venetian blind'
operating mode.

Fixed position of roller The fixed position of the roller shutter or


shutter / awning awning at the beginning of shading can
either be preset statically by a separate
parameter or basically adjusted to the
value prevailing at the time of shading
activation, i.e. remain unchanged.
Same as configured value At the beginning of shading, the
configured roller shutter or awning
position will be approached.
No change in current At the beginning of shading, the current
position position of the roller shutter or awning
will be maintained. Any movements in
progress at the time of shading
activation will be finished.
This parameter is only visible, if the
shutter or awning is to approach a fixed
position at the beginning of shading.
This parameter is visible only in the
"Roller Shutter / Awning" operating
mode.

Position of roller shutter 0...50…100 This parameter sets the fixed position of
/ awning the roller shutter or awning to be
(0...100 %) approached at the beginning of shading.
This parameter is only visible, if the
parameter "Fixed position of shutter /
awning" is set to "as specified by

1473-1-7829 | Rev. 01 | 3.2012 Page 129 of 144


Software "Blind, input/1.1"
Parameters

parameter". This parameter is visible


only in the "Roller Shutter / Awning"
operating mode.

Fixed position of venting The fixed venting louver position at the


louver beginning of shading can either be
preset statically by a separate
parameter or basically adjusted to the
value prevailing at the time of shading
activation, i.e. remain unchanged.
Same as configured value At the beginning of shading, the
configured venting louver position will be
approached.
No change in current At the beginning of shading, the current
position position of the venting louver will be
maintained. Any movements in progress
at the time of shading activation will be
finished.
This parameter is only visible if the
venting louver is to approach a fixed
position at the beginning of shading.
This parameter is visible only in the
"Venting louver" mode of operation.

Position of venting 0...50…100 This parameter sets the fixed position of


louver the venting louver to be approached at
(0...100 %) the beginning of shading.
This parameter is only visible, if the
parameter "Fixed position of venting
louver" is set to "as specified by
parameter". This parameter is visible
only in the "Venting louver" mode of
operation.

Reference movement Yes A forced reference movement of the


before each sun drive is performed before sun protection
protection No positioning (setting "yes"). A reference
positioning operation ? movement is a positioning movement
into the upper end position or into the
completely open position. By means of a
forced reference movement, drives
connected to different outputs can be
synchronised. If no synchronising
movement is forced (setting "no"), the
device performs a reference movement
only once after return of the power
supply.

Offset with fixed and For 'manual' readjustment of the slat


variable slat position angle during a shading or sun position
tracking operation, a slat offset can be
preset. The offset corrects the preset
slat angle in positive or in negative
direction. The lighting conditions in a
room can thus be individually adapted
by persons present in the room.

1473-1-7829 | Rev. 01 | 3.2012 Page 130 of 144


Software "Blind, input/1.1"
Parameters

This parameter is only visible, if the slat


is to approach a fixed or a variable
position at the beginning of shading.
This parameter is visible only in the
'Venetian blind' operating mode.
no offset The offset correction is deactivated.
Offset as configured The slat offset is statically preset by
means of a fixed parameter value.
Offset as configured and The slat offset is preset by a fixed
via object parameter value and can be dynamically
adapted via a separate communication
object.

Offset slat position -100…0...100 This parameter is used for setting the
(-100..100 %) slat offset. The value specified in this
parameter is added at the beginning of
shading to the current slat angle.
Even with offset correction, the 0...100%
slat position limits cannot be
overstepped. It should be noted that the
configured offset value can be
overwritten by the object after reception
of a dynamic value. This parameter is
only visible, if the parameter "Offset with
fixed and variable slat position" is set to
"Offset as configured" or to "Offset as
configured and via object". This
parameter is visible only in the 'Venetian
blind' operating mode.

Store offset slat position If the offset is preset via the object, this
via object in case of bus parameter defines whether the received
voltage failure ? value is to be stored in the device's NV
memory.
This parameter is only visible, if the
parameter "Offset with fixed and
variable slat position" is set to "offset as
configured and via object". This
parameter is visible only in the 'Venetian
blind' operating mode.
yes The value received via the object will be
stored in case of bus voltage failure in a
non-volatile memory of the device. The
originally configured offset value is
definitely overwritten in the process.
No The value received via the object will
only be stored temporarily in volatile
memory. This only replaces the
configured value until the device is
reinitialised. After the initialisation, the
offset value configured in the ETS will
be used again.

h Output 1 - End of sun protection

1473-1-7829 | Rev. 01 | 3.2012 Page 131 of 144


Software "Blind, input/1.1"
Parameters

Time delay at end of 0...59 The telegram received via the object
sunshine / shading "Sunshine / shading facade" for
Minutes (0...59) deactivation of shading (depending on
polarity) can be evaluated with a time
delay..

Setting the delay time minutes.


Seconds (0...59) 0...30...59 Setting the delay time seconds.
A time setting of "0" in the parameters
deactivates the respective delay time. In
this case, the state of shading is
evaluated immediately.

Reaction at the end of This parameter defines the behaviour of


sunshine / shading the output at the end of shading – if
applicable, after the end of the delay
time.
The behaviour preset in this parameter
will only be executed if no function with
a higher priority (e.g. safety) is activated
at the end of shading. This parameter is
only visible in the simple sun protection.
No reaction At the end of shading, the output quits
the sun protection mode and the relays
of the output show no reaction. Any
movements still in progress at this
instant will still be finished.
Raising / opening the At the end of shading, the device raises
louver the blind or opens the venting louver.
Lowering / closing the At the end of shading, the device lowers
louver the blind or closes the venting louver.
Stop At the end of shading, the device
switches the relays of the output to the
"stop" position. A drive movement, if
any, will be interrupted.
Tracking the position At the end of shading, the output will be
set to the state last adjusted before sun
protection or to the state tracked and
internally stored during sun protection.
The position objects, the long time
object and the scene function are
tracked.

Reaction at the end of This parameter defines the behaviour of


sunshine / shading the output at the end of shading – if
applicable, after the end of the delay
time.
This parameter is only visible in the
extended sun protection and in
"Venetian blind" mode. This parameter
does not define the behaviour of the
output at the end of automatic operation
(cf. parameter "Reaction at the end of
automatic operation")!
No reaction At the end of shading, the relays of the
output show no reaction. Any

1473-1-7829 | Rev. 01 | 3.2012 Page 132 of 144


Software "Blind, input/1.1"
Parameters

movements still in progress at this


instant will still be finished.
Raising At the end of shading, the device raises
the blind.
Lowering At the end of shading, the device lowers
the blind.
Stop At the end of shading, the device
switches the relays of the output to the
"stop" position. A drive movement, if
any, will be interrupted.
Internal scene recall At the end of shading, an internal scene
of the device is recalled.
Venetian blind or slat At the end of shading, the output moves
position fixed to a configured fixed Venetian blind and
slat position.

Reaction at the end of This parameter defines the behaviour of


sunshine / shading the output at the end of shading – if
applicable, after the end of the delay
time.
This parameter is only visible in the
extended sun protection and in "Roller
shutter / awning" mode. This parameter
does not define the behaviour of the
output at the end of automatic operation
(cf. parameter "Reaction at the end of
automatic operation")!
No reaction At the end of shading, the relays of the
output show no reaction. Any
movements still in progress at this
instant will still be finished.
Raising At the end of shading, the device raises
the blind.
Lowering At the end of shading, the device lowers
the blind.
Stop At the end of shading, the device
switches the relays of the output to the
"stop" position. A drive movement, if
any, will be interrupted.
Internal scene recall At the end of shading, an internal scene
of the device is recalled.
shutter / awning position At the end of shading, the output moves
fixed to a configured fixed roller shutter /
awning position.

Reaction at the end of This parameter defines the behaviour of


sunshine / shading the output at the end of shading – if
applicable, after the end of the delay
time.
This parameter is only visible in the
extended sun protection and in "Venting
louver" mode. This parameter does not
define the behaviour of the output at the

1473-1-7829 | Rev. 01 | 3.2012 Page 133 of 144


Software "Blind, input/1.1"
Parameters

end of automatic operation (cf.


parameter "Reaction at the end of
automatic operation")!
No reaction At the end of shading, the relays of the
output show no reaction. Any
movements still in progress at this
instant will still be finished.
Opening the louver At the end of shading, the device opens
the venting louver.
Closing the louver At the end of shading, the device closes
the venting louver.
Stop At the end of shading, the device
switches the relays of the output to the
"stop" position. A drive movement, if
any, will be interrupted.
Internal scene recall At the end of shading, an internal scene
of the device is recalled.
Fixed position of venting At the end of shading, the output moves
louver to a configured fixed venting louver
position.

Scene number (1...8) 1...8 This parameter defines the number of


the internal scene which is recalled at
the end of shading.
This parameter is only visible, if the
parameter "Reaction at the end of
sunshine / shading" is set to "internal
scene recall".
Fixed position of The fixed Venetian blind position at the
Venetian blind end of shading can either be preset
statically by a separate parameter or
basically remain at the value set or
tracked by the shading operation.
This parameter is only visible, if the
Venetian blind is to approach a fixed
position at the end of shading. This
parameter is visible only in the 'Venetian
blind' operating mode.
Same as configured value At the end of shading, the configured
Venetian blind position will be
approached.
No change in current At the end of shading, the current
position position of the Venetian blind will be
maintained. In this case, the output
behaves as if only the slat were
positioned as a result of the end of
shading.

Venetian blind position 0...50…100 This parameter sets the fixed position of
(0...100 %) the Venetian blind to be approached at
the end of shading.

0...50…100

1473-1-7829 | Rev. 01 | 3.2012 Page 134 of 144


Software "Blind, input/1.1"
Parameters

Fixed slat position This parameter sets the fixed position of


(0...100 %) the slat to be approached at the end of
shading and, as the case may be, after
positioning of the Venetian blind.
This parameter is only visible, if the slat
is to approach a fixed position at the
beginning of shading. This parameter is
visible only in the 'Venetian blind'
operating mode.

Fixed position of roller The fixed position of the roller shutter or


shutter / awning awning at the end of shading can either
be preset statically by a separate
parameter or basically adjusted to the
value prevailing at the time of shading
activation, i.e. remain unchanged.
This parameter is only visible, if the
shutter or awning is to approach a fixed
position at the end of shading. This
parameter is visible only in the "Roller
Shutter / Awning" operating mode.
Same as configured value At the end of shading, the configured
roller shutter or awning position will be
approached.
No change in current At the end of shading, the current
position position of the roller shutter or awning
will be maintained. Any movements in
progress at the time of shading
activation will be finished.

Position of roller shutter 0...50…100 This parameter sets the fixed position of
/ awning the roller shutter or awning to be
(0...100 %) approached at the end of shading.
This parameter is only visible, if the
parameter "Fixed position of shutter /
awning" is set to "as specified by
parameter". This parameter is visible
only in the "Roller Shutter / Awning"
operating mode.

Fixed position of venting The fixed venting louver position at the


louver end of shading can either be preset
statically by a separate parameter or
basically adjusted to the value prevailing
at the time of shading activation, i.e.
remain unchanged.
This parameter is only visible if the
venting louver is to approach a fixed
position at the end of shading. This
parameter is visible only in the "Venting
louver" mode of operation.
Same as configured value At the end of shading, the configured
venting louver position will be
approached.
No change in current At the end of shading, the current
position position of the venting louver will be

1473-1-7829 | Rev. 01 | 3.2012 Page 135 of 144


Software "Blind, input/1.1"
Parameters

maintained. Any movements in progress


at the time of shading activation will be
finished.

Position of venting 0...50…100 This parameter sets the fixed position of


louver the venting louver to be approached at
(0...100 %) the end of shading.
This parameter is only visible, if the
parameter "Fixed position of venting
louver" is set to "as specified by
parameter". This parameter is visible
only in the "Venting louver" mode of
operation.

h Output 1 - Automatic heating/cooling


Automatic heating/ disabled This parameter can be used to activate
cooling the automatic heating/cooling function.
Enabled The automatic heating/cooling function
adds a presence detection function to
the extended sun protection mode. If a
person is present, the extended sun
protection is executed as described. If
nobody is present, however, the
Venetian blinds, roller shutters, awnings
or venting louvers can be operated in
such a way that these devices support
the heating or cooling function of the
building.
When the function is enabled, the other
parameters and objects are visible.
The automatic heating/cooling function
can only be activated in the extended
sun protection mode. Moreover, the
automatic heating/cooling function is
only active when the automatic mode of
the extended sun protection function is
activated.

Polarity of "Heating/ Cooling = 0; This parameter defines the polarity of


cooling presence" Heating = 1 the object for heating/cooling
object switchover.
Cooling = 1; This object is linked, for instance, with
Heating = 0 room temperature controllers or outside
thermometers.
After the return of the power supply of
the device, the heating/cooling
switchover function is initialised with an
object value of "0" and the set polarity.
This parameter is visible only if
automatic heating/cooling is enabled.

Polarity of "Heating/ No presence = 0; This parameter defines the polarity of


cooling presence" Presence = 1 the object for presence control in case of
object automatic heating/cooling.
No presence = 1; This object is linked, for example, with
Presence = 0 presence detectors.

1473-1-7829 | Rev. 01 | 3.2012 Page 136 of 144


Software "Blind, input/1.1"
Parameters

After the return of the power supply of


the device, the heating/cooling presence
controller is initialised with an object
value of "0" and the set polarity. This
parameter is visible only if automatic
heating/cooling is enabled.

Time delay at the 0...59 The telegram received via the object
beginning of presence "Heating/cooling presence" for activation
Minutes (0...59) of the presence function (in acc. with
polarity) can be evaluated with a time
delay. A time setting of "0" in the
parameters deactivates the respective
delay time. In this case, the state of the
presence object is evaluated
immediately.

Setting the delay time minutes.


Seconds (0...59) 0...30...59 Setting the delay time seconds.
These parameters are visible only if
automatic heating/cooling is enabled.

Time delay at the end of 0...59 The telegram received via the object
presence "Heating/cooling presence" for
Minutes (0...59) deactivation of the presence function (in
acc. with polarity) can be evaluated with
a time delay. A time setting of "0" in the
parameters deactivates the respective
delay time. In this case, the state of the
presence object is evaluated
immediately.

Setting the delay time minutes.


Seconds (0...59) 0...30...59 Setting the delay time seconds.
These parameters are visible only if
automatic heating/cooling is enabled.

Reaction to sunshine / This parameter defines the behaviour of


shading the output at the end / at the beginning
of sunshine / shading with heating /
Start on cooling * cooling – if applicable, after the end of
the delay time.
End on cooling * This parameter is visible only in the
"Venetian blind" mode if automatic
Start on heating * heating/cooling is enabled.

End on heating *
No reaction The relays of the output show no
reaction. Any movements still in
progress at this instant will still be
finished.
Raising The device raises the blind.
Lowering The device lowers the blind.
Internal scene recall An internal scene of the device is
recalled.

1473-1-7829 | Rev. 01 | 3.2012 Page 137 of 144


Software "Blind, input/1.1"
Parameters

Venetian blind or slat The output moves to a configured fixed


position fixed Venetian blind and slat position.
*: The parameter settings for heating or
cooling or beginning or end must be
configured separately. The setting
options - also for the follow-up
parameters - are identical in all cases.

Reaction to sunshine / This parameter defines the behaviour of


shading the output at the end / at the beginning
of sunshine / shading with heating /
Start on cooling * cooling – if applicable, after the end of
the delay time.
End on cooling * This parameter is visible only in the
"Roller shutter / awning" mode if
Start on heating * automatic heating/cooling is enabled.

End on heating *
No reaction The relays of the output show no
reaction. Any movements still in
progress at this instant will still be
finished.
Raising The device raises the blind.
Lowering The device lowers the blind.
Internal scene recall An internal scene of the device is
recalled.
Fixed roller shutter / awning The output moves to a configured fixed
position roller shutter or awning position.
*: The parameter settings for heating or
cooling or beginning or end must be
configured separately. The setting
options - also for the follow-up
parameters - are identical in all cases.

Reaction to sunshine / This parameter defines the behaviour of


shading the output at the end / at the beginning
of sunshine / shading with heating /
Start on cooling * cooling – if applicable, after the end of
the delay time.
End on cooling * This parameter is visible only in the
"Venting louver" mode if automatic
Start on heating * heating/cooling is enabled.

End on heating *
No reaction The relays of the output show no
reaction. Any movements still in
progress at this instant will still be
finished.
Opening the louver The device opens the venting louver.
Closing the louver The device closes the venting louver.
Internal scene recall An internal scene of the device is
recalled.

1473-1-7829 | Rev. 01 | 3.2012 Page 138 of 144


Software "Blind, input/1.1"
Parameters

Venting louver position The output moves to a configured fixed


fixed venting louver position.
*: The parameter settings for heating or
cooling or beginning or end must be
configured separately. The setting
options - also for the follow-up
parameters - are identical in all cases.

Scene number (1...8) 1...8 This parameter defines the number of


the internal scene which is recalled.
This parameter is only visible, if the
parameter "Reaction in case of sunshine
/ shading" of the automatic heating/
cooling function is set to "internal scene
recall".

Fixed position of The fixed Venetian blind position in case


Venetian blind of automatic heating/cooling can either
be preset statically by a separate
parameter or basically remain at the
current value.
This parameter is only visible, if the
Venetian blind is to approach a fixed
position in case of automatic heating/
cooling. In addition, this parameter is
visible only in the 'Venetian blind'
operating mode.
Same as configured value The configured position of the Venetian
blind will be approached.
No change in current The current position of the Venetian
position blind will be maintained. In this case, the
output behaves as if only the slat were
positioned.

Venetian blind position 0...50…100 This parameter sets the fixed position of
(0...100 %) the Venetian blind to be approached in
case of automatic heating/cooling.
This parameter is only visible, if the
parameter "Fixed position of Venetian
blind" is set to "as specified by
parameter". In addition, this parameter
is visible only in the 'Venetian blind'
operating mode.

Fixed slat position 0...50…100 This parameter sets the fixed position of
(0...100 %) the slat to be approached in case of
automatic heating/cooling and, as the
case may be, after positioning of the
Venetian blind.
This parameter is only visible, if the slat
is to approach a fixed position with
automatic heating/cooling. In addition,
this parameter is visible only in the
'Venetian blind' operating mode.

1473-1-7829 | Rev. 01 | 3.2012 Page 139 of 144


Software "Blind, input/1.1"
Parameters

Fixed position of roller The fixed roller shutter/awning position


shutter / awning in case of automatic heating/cooling can
either be preset statically by a separate
parameter or basically remain at the
current value.
This parameter is only visible, if the
roller shutter or awning is to approach a
fixed position in case of automatic
heating/cooling. In addition, this
parameter is visible only in the "Roller
Shutter / Awning" operating mode.
Same as configured value The configured roller shutter or awning
position is approached.
No change in current The current roller shutter / awning
position position will be maintained.

Position of roller shutter 0...50…100 This parameter sets the fixed position of
/ awning the Venetian blind to be approached
(0...100 %) with automatic heating/cooling.
This parameter is only visible, if the
parameter "Fixed position of shutter /
awning" is set to "as specified by
parameter". In addition, this parameter
is visible only in the "Roller Shutter /
Awning" operating mode.

Fixed position of venting The fixed venting louver position in case


louver of automatic heating/cooling can either
be preset statically by a separate
parameter or basically remain at the
current value.
This parameter is only visible, if the
venting louver is to approach a fixed
position in case of automatic heating/
cooling. In addition, this parameter is
visible only in the "Venting louver"
operating mode.
Same as configured value The configured venting louver position
will be approached.
No change in current The current position of the venting
position louver will be maintained.

Position of venting 0...50…100 This parameter sets the fixed position of


louver the venting louver to be approached in
(0...100 %) case of automatic heating/cooling.
This parameter is only visible, if the
parameter "Fixed position of venting
louver" is set to "as specified by
parameter". In addition, this parameter
is visible only in the "Venting louver"
operating mode.

1473-1-7829 | Rev. 01 | 3.2012 Page 140 of 144


Software "Blind, input/1.1"
Parameters

h Output 1 - Scenes
Delay scene recall ? Yes A scene is recalled via the scene
extension object. If needed, the scene
No recall on the device can be made with a
delay after reception of a recall telegram
(setting: "Yes"). The recall is
alternatively made immediately on
reception of the telegram (setting: "No").
A recall delay has no influence on the
storage of scene values.

Delay time 0...59 This parameter is used for programming


Minutes (0...59) the duration of the switch-on time for a
scene recall.
The delay time parameters are only
visible, if the parameter "Delay scene
recall ?" is configured to "Yes".

Switch-on time minutes setting.


Seconds (0...59) 0...10...59 Switch-on time seconds setting.

Overwrite values stored yes During storage of a scene, the scene


in the device during values (current states of the output) are
ETS download ? No stored internally in the device. To
prevent the stored values from being
replaced during an ETS programming
operation by the originally programmed
scene states, the device can inhibit
overwriting of the scene values (setting:
"No"). As an alternative, the original
values can be reloaded into the device
during each ETS programming
operation (setting: "Yes").

Scene X activatable by 0…1*...64 The device distinguishes between up to


scene number (scene 8 different scenes which are recalled via
number "0" = scene *: The predefined scene the scene extension object or stored.
deactivated) number is dependent on The datapoint type of the extension
the scene (1...8). object, however, permits addressing a
X =depending on the maximum of 64 scenes. This parameter
scene (1...8) defines the scene number (1...64) which
is used to address the internal scene
(1...8). A setting of "0" deactivates the
corresponding scene.

Venetian blind position 0*...100 This parameter is used for


for scene X parameterizing the blind position which
*: The predefined position is executed when the scene is recalled.
X =depending on the value is dependent on the This parameter is visible only in the
scene (1...8) scene (1...8). 'Venetian blind' operating mode.

Slat position for scene X 0*...100 This parameter is used for configuring
the slat position which is executed when
*: The predefined position the scene is recalled.

1473-1-7829 | Rev. 01 | 3.2012 Page 141 of 144


Software "Blind, input/1.1"
Parameters

X =depending on the value is dependent on the This parameter is visible only in the
scene (1...8) scene (1...8). 'Venetian blind' operating mode.

Roller shutter/awning 0*...100 This parameter is used for configuring


position for scene X the roller shutter or awning position
*: The predefined position which is executed when the scene is
X =depending on the value is dependent on the recalled.
scene (1...8) scene (1...8). This parameter is visible only in the
"Roller Shutter / Awning" operating
mode.

Position of venting 0*...100 This parameter is used for configuring


louver for scene X the venting louver position which is
*: The predefined position executed when the scene is recalled.
X =depending on the value is dependent on the This parameter is visible only in the
scene (1...8) scene (1...8). "Venting louver" operating mode.

Storage function for Yes Setting "yes" enables the storage


scene X function of the scene. If the function is
No enabled, the current position (0...100 %)
X =depending on the can be stored internally via the
scene (1...8) extension object on reception of a
storage telegram. If "no" is selected, the
storage telegrams are rejected.

h Output 1 - Forced position


Behaviour at the end of The behaviour of the output at the
the forced position beginning of a forced position function is
function directly determined by the forced
position telegram. The behaviour of the
output at the end of the forced position
function can be configured.
Tracking the position At the end of the forced position state,
the output will be set to the position last
existing before the forced position
function or to the one tracked internally
while the forced position function was
active.
No change At the end of forced position state, the
position last adjusted will not be
changed. Thereafter, the output is again
enabled.

Behaviour after bus The forced position communication


voltage object can be initialised after bus voltage
return return.
This parameter is evaluated even after
an ETS download of the application or of
parameters.
no forced position active The forced position is deactivated after
bus voltage return.

1473-1-7829 | Rev. 01 | 3.2012 Page 142 of 144


Software "Blind, input/1.1"
Parameters

Forced position on, raising / After bus voltage return, the forced
opening the louver position is activated and the blind raised
or the venting louver opened.
Forced position on, After bus voltage return, the forced
lowering / closing the louver position is activated and the blind
lowered or the venting louver closed.
State of forced position After bus voltage return, the forced
before bus failure position state last selected and internally
stored before bus voltage failure will be
tracked. An ETS programming operation
deletes the stored state (reaction in that
case same as with "no forced position
active").

h Output 1 - Fabric stretching (only in the "Roller Shutter / Awning" operating mode)
Time for fabric 0...59 This parameter can be used to specify
stretching the time for fabric stretching. After the
Seconds (0...59) end of a downward travel the awning
stops and – after elapsing of the
switchover delay – moves backwards in
opposite direction for a period
corresponding to the fabric stretching
time configured here.
Setting of the fabric stretching time in
seconds.
Milliseconds 4...9 Setting of the fabric stretching time in
(4...9 x 100) milliseconds.
The time for fabric stretching must be
less than the movement time of the
roller shutter/awning.

1473-1-7829 | Rev. 01 | 3.2012 Page 143 of 144


 
Appendix

5 Appendix
5.1 Index

A P
application program.. ............................. 17 Performing a reference movement .. 10
Automatic heating/cooling.. ................... 79 (optional)
Position feedback messages.. ............... 49
B Presetting the position.. ......................... 48
blind height.. .......................................... 44 priority.. .................................................. 93
bus voltage failure.. ............................... 37
bus voltage return.. ................................ 37 R
Reference movement.. .......................... 47
C
Commissioning.. .................................... 10 S
communication objects.. ........................ 18 Safe-state mode.. .................................. 17
Computing.. ........................................... 44 Safety function.. ..................................... 54
Short time operation.. ............................ 40
D Simple sun protection.. .......................... 59
Delay after bus voltage return.. ......... 27-28 slat moving time.. ................................... 41
Delivery state.. ....................................... 94 Slat offset.. ............................................. 74
Device components.. ............................. 5 slat position.. .......................................... 45
Dimming function.. ................................. 30 Sun protection function.. ........................ 58
direct operation.. .............................. 40, 48 Switching function.. ................................ 29
disabling function.. ................................. 36 switchover time.. .................................... 42
drive movement.. ................................... 51
T
E Telegram rate limit.. ............................... 27
effect .. ................................................... 29
Effect.. ................................................... 26 U
ETS programming.. ............................... 37 Unknown position.. ................................ 51
ETS search paths.. ................................ 14 Unloading the application program.. ...... 17
extended sun protection.. ...................... 60
V
F Value transmitter function.. .................... 33
Fabric-stretching function.. .................... 91 Venetian blind function.. ........................ 31
functionalities.. ....................................... 3

L
Light scene function.. ............................. 85
long time operation.. .............................. 40
louver position.. ..................................... 44

M
Measuring the slat moving time.. ........... 10
Measuring the travelling time .. 9
extension
Measuring the travelling times.. ............. 9
movement time extension.. .................... 42

O
operating mode.. .................................... 37
Operating mode.. ................................... 37

1473-1-7829 | Rev. 01 | 3.2012 Page 144 of 144


Contact us

A member of the ABB Group Notice


We reserve the right to at all times make technical
changes as well as changes to the contents of this
Busch-Jaeger Elektro GmbH document without prior notice.
The detailed specifications agreed to at the time
PO box
of ordering apply to all orders. ABB accepts no
58505 Lüdenscheid responsibility for possible errors or incompleteness
in this document.

Freisenbergstraße 2 We reserve all rights to this document and the topics


58513 Lüdenscheid and illustrations contained therein. The document
Germany and its contents, or extracts thereof,
must not be reproduced, transmitted or reused by third
parties without prior written consent by ABB.
www.BUSCH-JAEGER.de
[email protected] Copyright© 2012 Busch-Jaeger Elektro GmbH
All rights reserved
Central sales service:
Phone.: +49 (0) 180 5 669900
Fax: +49 (0) 180 5 669909

You might also like