KNX Shutter Actuator
KNX Shutter Actuator
KNX Shutter Actuator
2012
Product Manual
ABB i-bus® KNX
Contents
1 Product definition
1.1 Product catalogue
Product name: Shutter actuator 1gang with binary Inputs
Use: Actuator / sensor
Form: UP (concealed)
Art.-No. 6152/11 U-500
1.2 Function
The output (O1) allows the control of electrically-operated Venetian blinds, roller shutters,
awnings, venting louvers or similar blinds for 230 V AC mains voltage. The relay contacts for the
movement directions (up, down) are bistable, meaning that the last switching status set also
remains intact, should the mains voltage fail.
The functionalities that can be preset with the ETS for the Venetian blind output include, for
instance, separately configurable travelling times, enlarged feedback functions, assignment to
up to 5 different safety functions, an extensive sun protection function, and incorporation into
scenes or forced-position applications.
Besides the output, the device possesses three additional inputs, which can have an internal
effect on the Venetian blind output or, alternatively, affect the KNX/EIB separately, depending
on the ETS configuration. The connected potential-free switch or button contacts are
downloaded to the device via a shared reference potential. With the internal effect, inputs 1 and
2 directly operate the Venetian blind output. With the effect on the bus, the inputs can,
independently of one another, transmit telegrams for switching or dimming for Venetian blind
control or value encoder use (dimming value encoder, light scene extension).
The connection of 230 V signals or other external voltages to the extension inputs is not
permitted!
For configuration and commissioning of this device, it is necessary to use ETS3.0 from version
"d" onwards. Advantages with regard to downloading (significantly shorter loading times) and
parameter programming can be expected only if this ETS patch version or later versions are
used.
The device electronics are supplied exclusively from the bus voltage. The device is designed for
installation in concealed switch or device boxes in permanent installations.
DANGER!
When connecting the bus/extensions and mains voltage wires in a shared
appliance box, the KNX bus line may come into contact with the mains voltage.
This endangers the safety of the entire KNX installation. People at remote
devices may also receive an electric shock.
Do not place bus/extensions and mains voltage terminals in a shared
connection compartment. Use an appliance box with a fixed partition wall or
separate boxes.
o Connect the mains voltage and the Venetian blind drive using the included screwless
terminals (Figure 4).
o Connect the device to KNX. For this, use a KNX connection terminal.
o If necessary, connect potential-free contacts to the inputs (Figure 5).
i Use suitable terminals to connect potential-free contacts to the control cable.
i The reference potential "com" may only be switched together with the reference potentials
of other devices of the same type (!).
i Venting louvers must be connected in such a way that they open in travel direction "UP -
n" and close in travel direction "DOWN – o".
i Do not connect any three-phase motors.
i Insulate unused wires of the 6-pin control cable against each other and outside voltage.
i To avoid interference from EMC radiation, the cables of the extension inputs should not be
run in parallel to cables carrying voltage.
2.4 Commissioning
After installation and connection of the bus line, the mains voltage and of all electrical loads, the
device can be put into operation. For output 1 only, special commissioning steps have to be
performed prior to programming with the ETS. The following procedure is generally
recommended...
DANGER!
Electrical shock on contact with live parts in the installation environment.
Electrical shocks can be fatal.
Before working on the device, disconnect the power supply and cover up live
parts in the working environment.
i The travelling time extension can also be determined after commissioning with the ETS
(bus operation through communication objects).
i This device stores the curtain, slat or louver positions temporarily. After each bus voltage
failure or after programming with the ETS, the device therefore automatically performs a
reference movement for output 1 before a new position can be approached.
i After bus voltage return, the device generates an "invalid position" message for output 1
which can also be transmitted to the bus, if so configured. The message is withdrawn
(inverted signal value) as soon as a reference movement could be executed.
2.5 Operation
In the as-delivered state of the device, extension inputs 1 and 2 have a direct effect on Venetian
blind output 1. In this way, it is possible, for example, for a connected Venetian blind 'on the
building site' to be commissioned and operated simply by applying the bus voltage and without
using additional sensors.
After commissioning using the ETS, extension inputs 1 and 2 behaviour as they are configured
in the ETS. It is also possible to let the inputs internally effect output 1. Alternatively, these
inputs can also affect the bus and control other actuators. The extension inputs then function
like standard KNX/EIB pushbutton interfaces.
i Extension input 3 always behaves independently and, through separate communication
objects, only affects the bus. In the as-delivered state, this extension input is inactive.
If inputs 1 and 2 have an internal effect on output 1, control takes place using the two-area
principle: Input 1 controls the "UP" command and input 2 controls the "DOWN" command.
Venetian blind 1 is controlled according to Table 1...
i The times specified in Table 1 and the operating concept "Short - long - short" are preset in
the as-delivered state of the device. However, the appropriate actuation times of inputs 1
and 2 can be configured in the ETS and thus adapted to special requirements (see
page 29). The operating concept cannot be changed when inputs 1 and 2 have an internal
impact.
i After bus voltage return, the device only switches to status change of the extension signals
when the configured time for "delay after bus voltage return" has elapsed (see chapter
4.2.4.1. General functions for extension inputs). Within the delay, any pending flanks or
signals at the inputs are not evaluated and are ignored. The delay time is configured
generally for all the inputs. In the as-delivered state, the time is preset to "0 s".
3 Technical data
General
Mark of approval KNX / EIB
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
Dimensions Ø×H 53×28 mm
KNX/EIB supply
KNX medium TP 1
Commissioning mode S-mode
Rated voltage KNX DC 21 ... 32 V SELV
Power consumption KNX max. 240 mW
Connection mode KNX Connection terminal on control cable
4 Software description
4.1 Software specification
ETS search paths: Blind / Switch / Shutter actuator 1gang with binary Inputs
Application programs:
Function: Switching
Object Function Name Type DPT Flag
10, Switching object X.1 Input 1 ... 3 1 1-bit 1.001 C, W, T 2
h 11,
12
Description 1-bit object for the transmission of switching telegrams (ON, OFF)
(first switching object)
Function: Switching
Object Function Name Type DPT Flag
14, Switching object X.2 Input 1 ... 3 1 1-bit 1.001 C, W, T 2
h 15,
16
Description 1-bit object for the transmission of switching telegrams (ON, OFF)
(second switching object)
Function: Dimming
Object Function Name Type DPT Flag
10, Switching Input 1 ... 3 1 1-bit 1.001 C, W, T 2
h 11,
12
Description 1-bit object for the transmission of switching telegrams (ON, OFF) for the
dimming function.
Function: Dimming
Object Function Name Type DPT Flag
14, Dimming Input 1 ... 3 1 4-bit 3.007 C, W, T 2
h 15,
16
Description 4-bit object for change of relative brightness between 0 and 100 %.
1: The objects for inputs 1 and 2 are not available when inputs have an internal effect on the
Venetian blind output.
2: Each communication object can be read out. For reading, the R-flag must be set.
Description 2-byte object for transmission of temperature value telegrams (0 °C ... 40 °C).
Description 1-byte object for opening or saving light scenes (1 ... 64).
1: The objects for inputs 1 and 2 are not available when inputs have an internal effect on the
Venetian blind output.
2: Each communication object can be read out. For reading, the R-flag must be set.
1: The objects for inputs 1 and 2 are not available when inputs have an internal effect on the
Venetian blind output.
2: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
2: The object designation varies with the type of blind (Venetian blind, roller shutter / awning,
venting louver).
1: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
2: The object designation varies with the type of blind (Venetian blind, roller shutter / awning,
venting louver).
3: The communication flags are set automatically depending on the configuration. "T" flag for
active signalling object; "R" flat for passive status object.
1: The communication flags are set automatically depending on the configuration. "T" flag for
active signalling object; "R" flat for passive status object.
2: The object designation varies with the type of blind (Venetian blind, roller shutter / awning,
venting louver).
3: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.
o Set the parameter to "I1 & I2 internally on O1, I3 separately on the bus".
The extension inputs 1 and 2 only directly affect the internal Venetian blind output of the
device. For two-area operation, input 1 operates the "UP" command and input 2 the
"DOWN" command. Input 3 behaves independently and, through separate communication
objects, only affects the bus.
Venetian blind output 1 is controlled according to Table 2...
i The times specified in Table 2 and the operating concept "Short - long - short" are preset in
the as-delivered state of the device. However, the appropriate actuation times of inputs 1
and 2 can be configured in the ETS and thus adapted to special requirements (see
page 29). The operating concept cannot be changed when inputs 1 and 2 have an internal
impact.
i After bus voltage return, the device only switches to status change of the extension signals
when the configured time for "delay after bus voltage return" has elapsed (see chapter
4.2.4.1. General functions for extension inputs). Within the delay, any pending flanks or
signals at the inputs are not evaluated and are ignored. The delay time is configured
generally for all the inputs. In the as-delivered state, the time is preset to "0 s".
It is also possible to configure a general telegram rate limit. In this case no more telegrams
are transmitted to the bus in 17 seconds (permanently defined, cyclical time interval) than
are specified in the ETS.
The three inputs of the device affect the KNX/EIB independently of the Venetian blind
output and each other. Depending on the ETS configuration, the functions "Switching",
"Dimming", "Venetian blind" or "Value encoder" can be set (see chapter 4.2.4.3.1. Function
configuration of the extension inputs).
The "No function" setting deactivates the appropriate input. With the "Venetian blind"
setting, the input objects can be connected to the objects of the Venetian blind output using
group objects. This allows control of the device using its own inputs, even if the extensions
are affecting the bus (e.g. with group control of multiple actuators during installation).
i A telegram rate limit does not influence a configured delay after bus voltage return. These
two functions can be combined in any way.
i The delay has no effect on the behaviour of the output. Only the bus telegrams for
feedback are delayed. The output can also be controlled over the bus during the delay after
bus voltage return.
i A setting of "0" for the delay after bus voltage return deactivates the delaying function
altogether. In this case, any messages, if actively transmitted, will be transmitted to the bus
without any delay.
Figure 6: Operating concept "Short - long - short" when inputs 1 and 2 have an internal impact
With a rising flank, input 1 always operates the movement direction "UP". Input 2 operates the
movement direction "DOWN". After bus voltage return, unoperated inputs do not show any
special behaviour.
i In the as-delivered state, the times between short and long time operation and the slat
adjustment times of the inputs are matched to the time of short time operation and the
movement time (long time operation) of the Venetian blind output. If the times at the inputs
are changed, then it should be observed that, for flawless operation of the blind or venting
louver at output 1, the times of the output may also need to be adjusted.
i It is not possible to actuats the inputs simultaneously.
i After bus voltage return, the device only switches to status change of the extension signals
when the configured time for "delay after bus voltage return" has elapsed (see page 27).
Within the delay, any pending flanks or signals at the inputs are not evaluated and are
ignored. The delay time is configured generally for all the inputs. In the as-delivered state,
the time is preset to "0 s".
Switching function
For each input whose function is set to "Switching", the ETS displays two 1-bit communication
objects (switching object X.1 and X.2). It is possible to use these two objects to transmit
different switching telegrams to the bus depending on the signal flank at the input. The input
parameter on the parameter page "Ix - General " (x = 1, 2, 3) can be used to define which object
value is transmitted to the bus when there is a rising or falling flank at the input (no reaction,
ON, OFF, TOGGLE - switchover of the object value). No distinction is made between a brief or
long signal flank/actuation in the "Switching" function.
Cyclical transmission
Optionally, the object values can be transmitted cyclically to the bus for the "Switching" function.
For this, the transmission criteria must first be defined in the ETS. The "Transmit cyclically ?"
parameter on the parameter page "Ix - Transmit cyclically" (x = 1, 2, 3) specifies with which
value cyclical transmission should take place. Depending on requirements, it is possible to
transmit cyclically via both or just one switching object(s). In addition, it is possible to define the
cycle time separately for both switching objects in the ETS.
The object value entered in the switching objects by the device on a flank change or externally
by the bus is always transmitted cyclically. The object value is then also transmitted cyclically
when "no reaction" is assigned to a rising or falling flank. Cyclical transmission also takes place
directly after bus voltage return, if the reaction after bus voltage return corresponds to the
transmission criterion for cyclical transmission. During an active disable, no cyclical
transmissions take place via the disabled input.
Dimming function
For each input whose function is set to "Dimming", the ETS indicates a 1-bit "Switching" and a
4-bit "Dimming" object. In general, the device transmits a switching telegram on a short time
input signal (triggered by the rising flank of a closed contact) and a dimming telegram on a long
signal. In the standard configuration, the device transmits a telegram for stopping the dimming
action after a long signal.
The length of time the input signal (closed pushbutton or switch) must last until a long actuation
is detected can be set using the parameter "Time between switching and dimming" on the
parameter page "Ix - General" (x = 1, 2, 3).
Operating principle
The "Operation" parameter specifies the operating principle. In the presetting of the dimming
function, two-surface operation is specified here. This means that the input transmits a telegram
for switching on after a short signal length and a telegram for increasing the brightness after a
long signal length ("Brighter"). Alternatively, the device can transmit a telegram for switching off
after a short signal length and a telegram for reducing the brightness after a long signal length
("Darker").
With a single-surface dimming function, the input transmits switch-on and switch-off telegrams
("TOGGLE") in an alternating pattern for each short signal. After long signals, the device
transmits "brighter" and "darker" telegrams in an alternating pattern.
- If a falling flank is detected within the slat adjustment time, the input transmits an additional
short time telegram. This function is used for adjusting the slats of a blind. The function
permits stopping the slats in any position during their rotation.
The "slat adjusting time" should be chosen as required by the drive for a complete rotation
of the slats. If the "slat adjusting time" is selected longer than the complete running time of
the drive, a pushbutton function is possible as well. This means that the drive is active only
when a button connected to the input is kept depressed.
- If the button is kept depressed longer than T2, the input transmits no further telegram. The
drive remains on until the end position is reached.
Flank evaluation
The parameter "Command on rising flank" on the parameter page "Ix - General" (x = 1, 2, 3)
specifies the direction of movement of the short time or long time telegram. In the "TOGGLE"
setting (single-surface operation) the input switches the direction of the short and long time
telegram each time there is a new signal. Several short time telegrams in succession have the
same direction.
i If the actuator is to be controlled from several locations, a faultless single-surface actuation
requires that the all long time objects of the sensor devices are interlinked. A sensor device
would otherwise not be able to detect that the actuator has been addressed from another
sensor, in which case it would have to be actuated twice during the next use in order to
produce the desired reaction.
Table 3: Value ranges of dimming value encoder, temperature and brightness value encoder
Value adjustment for dimming value encoder, temperature and brightness value encoder
With the dimming value encoder and the temperature and brightness value encoder, the value
to be transmitted can be adjusted at any time during device operation. A value adjustment can
only be configurable in the ETS when the value is to be transmitted only on a rising flank or only
on a falling flank, i.e. a pushbutton is connected to the input.
A value adjustment is introduced by a long signal at the input (> 5 s) and continues for as long
as the signal is detected as active, i.e. the pushbutton is actuated. With the first adjustment after
commissioning, the value programmed by the ETS is increased cyclically by the step width
configured for the dimming value encoder and transmitted. The step width of the
temperature value encoder (1 °C) and the brightness value encoder (50 Lux) is permanently
defined. The previously transmitted value is saved after releasing the pushbutton. The next long
pushbutton actuation adjusts the saved value and the direction of the value adjustment
changes.
The time between two telegrams on adjusting values can be configured in the ETS.
i There is no value over- or underrun on adjustment. If, during an adjustment, the maximum
or minimum value is reached (see Table 3), no more telegrams are transmitted.
i To ensure that, during a value adjustment, for example the controlled lighting switches off
or switches on at the maximum, the limit values (e.g. the values "0" or "255") are always
transmitted when the limits of the adjustable range are reached. This also takes place
when the configured step width of these values is not immediately taken into account (see
example above: step width = 5; value "2" is transmitted, then value "0").
In this case, to ensure that the original starting value can be reset on resetting with a
change to the adjustment direction, the first value jump is not equal to the preset step width
(see example above: step width = 5; value "0" is transmitted, then values "2"; "7" etc.).
i The newly adjusted values are stored in RAM. After a device reset (bus voltage failure or
ETS programming operation), the adjusted values are replaced by the values originally
configured in the ETS.
Examples for a light scene extension with memory function (Figure 10):
1.) Only memory function = No
2.) Only memory function = Yes
Behaviour on bus voltage return for value encoder and light scene extension
After a device reset (bus voltage return or ETS programming operation), the communication
object of the value encoder or light scene extension can be initialised. For this, the "Behaviour
on bus voltage return" parameter should be configured to the required reaction. The setting is
dependent on the value encoder function and flank evaluation selected in the ETS. In the
settings "Reaction as rising flank" or "Reaction as falling flank", telegrams are transmitted
actively to the bus according to the configuration in the ETS. In the "Transmit current input
status" setting, the device evaluates the static signal status of the input and, according to this,
transmits the appropriately configured telegram to the bus (contact closed at the input =
telegram as with rising flank; contact open at input = telegram as with falling flank). This setting
can only be configured with "Transmit value on = rising and falling flank (switch)".
If, in the ETS, a delay is set for the extension inputs after bus voltage return, the device only
transmits the telegrams when the delay has elapsed.
Each input or each switching object can execute a specific independent reaction at the
beginning or end of a disable. This reaction is specified on the parameter page
"Ix - disable" (x = 1, 2, 3) in the ETS and is dependent on the flank evaluation defined for the
affected input. In so doing, it is possible to configure to "No reaction". Only in this case are
dimming or Venetian blind control operations or value adjustments completed during an active
disable and only then the input locked. In all other cases, the configured disabling command is
executed immediately at the beginning of disabling.
In the "Transmit current input status" setting, the device evaluates the current static signal
status of the input and, according to this, transmits the appropriately configured telegram to the
bus (contact closed at the input = telegram as with rising flank; contact open at input = telegram
as with falling flank).
A disabling function is activated or deactivated by the corresponding 1-bit object. The telegram
polarity can be set in the ETS for each disabling object. The disabling object is always inactive
after a device reset. Even with an inverted polarity "Disabling = 0 (Enabling = 1)", a "0" telegram
must first be received after a reset until the appropriate disabling function is activated.
i Updates to disabling objects with the same telegram polarity (disabling -> disabling or
enabling -> enabling) do not show a reaction.
i With cyclical transmission in the "Switching" function: during an active disable, cyclical
transmission does not take place via the disabled input switching object. Cyclical
transmission is continued immediately at the end of the disabling with the last object value
written to the object, providing that the transmit criterion for cyclical transmission is fulfilled
(transmit on ON, on OFF or on ON and OFF).
Behaviour in case of bus voltage failure, after bus voltage return or after programming
with the ETS
The preferred contact positions of output 1 after bus voltage return or after ETS programming
can be set. Since the device is equipped with bistable relays, the relay switching state at bus
voltage failure can be defined as well.
i At the beginning of each ETS programming cycle, the device always executes a "stop"
command for the output.
i The "Behaviour after ETS programming" as configured will be executed after every ETS
application or parameter download. A simple download of the physical address alone or
partial programming of only the group addresses has the effect that this parameter is
disregarded and that the configured "Behaviour after bus or mains voltage return" will be
executed instead.
i After programming with the ETS, the safety functions, the forced positions and the sun
protection function are always deactivated.
(upper end position / awning rolled up) to the completely closed position
(lower end position / awning completely unrolled). Not vice-versa! The movement times are to
be determined as a function of the different types of drives.
Figure 11: Determining the movement time according to the drive type
Setting the movement time of Venetian blinds, roller shutters/awnings and louvers
The measurement of the movement time is described in detail in chapter "Commissioning".
o Enter the exact movement times determined in the course of the commissioning procedure
into the parameters "Venetian blind movement time" or
"Roller shutter/awning movement time" or "Venting louver movement time" on parameter
page "O1 – Times". The maximum travelling time is '59 minutes 59 seconds. The working
principle does not allow longer movement times.
i The configured movement time extension will also be taken into account by the device for
all upward movement or all movements into the open position as the drive motors are then
generally not as fast due to the weight of the blind or external physical influences (e.g.
temperature, wind, etc.).
Determining and configuring the slat moving time (only with slatted Venetian blinds)
If Venetian blinds are controlled, the slats can be positioned independently. To enable the
device to compute slat positions and to report them back to the bus, it is necessary that the
device gets precise information about the time required for a slat rotation. The slat moving time
must in each case be determined and configured 'manually'.
The device is designed in such a way that it can control single-motor Venetian blind drives
without a working position. In this drive mode, the slats are directly adjusted by way of
mechanical linkage when the height of the Venetian blind is changed. The device assumes that
the slats are completely closed when the Venetian blind moves downwards. The actuator
assumes that the slats are completely closed when the Venetian blind moves downwards
(Figure 12). These Venetian blinds are the most common type on the market.
Figure 12: Type 1 - Slatted Venetian blinds with oblique slat position in both travel directions
There are also single-motor Venetian blind systems without a working position the slats of which
are horizontal during an upward travel and oblique during a downward travel. Such Venetian
blind types can also be connected to the device in which case a completely open slat position
corresponds to the slats in horizontal position .
Figure 13: Type 2 - Slatted Venetian blinds with oblique and horizontal slat position
Determining and configuring the movement time extension and the switchover time
When moving upwards, Venetian blinds, roller shutters or awnings have a tendency of moving
more slowly due to their own weight or to external physical influences (e.g. temperature, wind,
etc.). The same applies to venting louvers where opening may take longer than closing.
For this reason, the device takes the configured travelling time extension into account when
moving upwards or when opening louvers. The extension is computed as a percentage of the
difference of the movement times in both directions.
The movement time extension should be determined separately during commissioning and
entered into the ETS configuration.
The measurement of the movement time extension is described in detail in chapter
"Commissioning".
Example for determining the movement time extension:
The device derives the positions from the configured travelling time since conventional drives do
not provide feedback about their positions. Thus, the travelling time configured in the ETS is the
reference for all position approaches and of basic importance for the accuracy of the position
calculations. For this reason, the travelling time should be determined with great accuracy in
order to achieve the best possible positioning results.
For positioning purposes, the device calculates the movement time required as a function of the
current position.
Example 1...
The roller shutter connected to the certain output has an overall travelling time of 20 s. The
roller shutter is in its upper end position (0 %). It is to be positioned at 25 %. The device
calculates the movement time required for approaching the desired position:
20 s × 0.25(25 %) = 5 s. The output will then lower the roller shutter for 5 s and thus position the
blind at height of 25 %.
Example 2...
The shutter connected to the certain output has an overall travelling time of 20 s. The shutter is
in the 75 % position. I It is to be positioned at 75 %. The difference between the positions is
50 %. The device calculates the movement time required for bridging the difference between
the positions: 20 s × 0.5(50 %) = 10 s. The output will then lower the roller shutter for 10 s and
thus position the blind at height of 75 %.
With all the upward movements, the configured movement time extension is automatically
added to the calculated movement time.
Example 3...
The roller shutter connected to the certain output has an overall movement time of 20 s. The
roller shutter is in the 75 % position. It is to be positioned at 25 %. The difference between the
positions is 50 %. The device calculates the unextended movement time required for bridging
the difference between the positions:
20 s × 0.5(50 %) = 10 s. Taking the movement time extension into account (e.g. 10 %), the actual
raising time is: 10 s × ((100 % + 10 %(extension)) : 100 %) = 10 s × 1.1 = 11 s. The output will then
raise the roller shutter for 11 s and thus position it at a blind height of 25 %.
When the lower or upper end positions (0 % or 100 %) are approached, the movement time is
always 20 % longer than the overall movement time.
Example 4...
The shutter connected to the certain output has an overall travelling time of 20 s. The shutter is
in the 75 % position It is to be positioned at 100 %. The difference between the positions is
50 %. The device calculates the movement time required for bridging the difference between
the positions: 20 s × 0.5(50 %) = 10 s. As the movement is a limit position movement, the device
adds 20 % of the total movement time:
10 s + (20 % : 100 %) · 20 s = 14 s. The output will then lower the roller shutter for 14 s and
thus positions it safely at a blind height of 100 %.
Example 5:
The roller shutter connected to the certain output has an overall movement time of 20 s. The
roller shutter is in the 50 % position. It is to be positioned at 0 %. The difference between the
positions is 50 %. The device calculates the unextended movement time required for bridging
the difference between the positions: 20 s × 0.5(50 %) = 10 s. As the movement is a limit position
movement, the device also adds 20 % of the total movement time:
10 s + (20 % : 100 %) - 20 s = 14 s.
Taking the movement time extension into account (e.g. 10 %), the actual raising time is:
10 s × ((100 % + 10 %(extension)) : 100 %) = 10 s × 1.1 = 15.4 s. The output will then raise the
roller shutter for 15.4 s and thus position safely at 0 %.
i The device executes position approaches only if a new position deviating from the current
position is preset.
i The device stores the blind or louver positions temporarily. The device can approach newly
preset blind or louver positions only if the current positions are known. For this purpose,
each output must be given the opportunity to synchronise itself whenever the supply
voltage is switched on or after every ETS programming operation (physical address,
application program, partial download). Synchronisation is performed with the help of a
reference movement (cf. "reference movement").
i Position approaches in progress will be aborted in case of bus voltage failure. In case of
bus voltage failure, the configured behaviour will be executed.
Figure 15: Example of slat positioning affecting the position of the Venetian blind
(typical of slat type 1; analogous reaction for type 2)
Since a preset slat position is to remain constant until the next change, the device will not
change the height of the Venetian blind, if the calculated movement time required for a change
of position lies within the configured slat moving time.
Similarly, the device accounts for the ratio of the moving times of slat and Venetian blind and –
in case of slat position changes – always recalculates the resulting Venetian blind position. If
the position feedback objects are used (cf. "Position feedback"), the device transmits the
Venetian blind positions changed by the adaptation also to the bus.
In each position operation, the Venetian blind setpoint position refers to a slat position of 100 %.
In the event of a slat repositioning movement (0 to 100 %), the system will therefore report a
Venetian blind position below the desired position.
Exception: The Venetian blind setpoint position of 0 % (upper end position) is assigned to the
slat position of 0 %. The readjustment of the slat position will result also in this case in a change
of the Venetian blind height (brief downward movement). Only in this case will the actuator
report back a Venetian blind position above the Venetian blind setpoint position (Figure 16).
With slat type 1, the slats are generally horizontal when the Venetian blind is in its upper end
position. For this reason, the calculated slat position with a slat type 1 corresponds to the actual
opening angle only after the first slat is completely extended (100%).
Figure 16: Example of slat positioning with the Venetian blind in upper end position
(typical of slat type 1)
i The device executes slat position adjustments only if a new position deviating from the
current slat position is preset.
i The device stores the slat positions temporarily. The device can approach newly preset slat
positions only if the current position is known. For this purpose, the output must be given
the opportunity to synchronise itself whenever the supply voltage is switched on or after
every ETS programming run (physical address, application program, partial download). The
synchronisation is performed with the help of a reference movement for the slat or the
Venetian blind (cf. "reference movement").
i A change of the Venetian blind height will always result in a change of the slat position.
After reactivation of the supply voltage of after ETS programming, the device will in this
case generally move the slats into the 100 % position, if no position has been preset for the
slats.
i The smaller the ratio between slat moving time and Venetian blind travelling time, the more
precise the position approaches and the less marked the influence of the slat angle
adjustment on the height of the Venetian blind.
Reference movement
After ETS programming (physical address, application program, partial download) or after bus
voltage failure all current position data are unknown. Before the device can approach new
positions after bus voltage return or after programming, the positioning system must at first be
calibrated. A position calibration is possible by executing the reference movement.
A reference movement is the time required for a movement into the upper end position
increased by 20 % and additionally by the configured movement time extension (Figure 17). A
reference movement is not retriggerable.
In the event of slat positioning via the corresponding communication objects after bus voltage
return or after programming, a slat reference movement becomes necessary if the Venetian
blind has not been moved beforehand in the up or down directions for at least the configured
slat moving time. During a slat reference movement, the device always moves the slats for the
configured slat moving time into the completely open position (0 %) and then to the desired
position. The slat position is also considered as calibrated when the Venetian blind has been
moved by a long-time command in the up or down direction during at least the configured slat
moving time.
i A terminated reference movement of the Venetian blind will also calibrate the slat position.
i If the reference movement is interrupted for instance by a short-time operation, the position
is still unknown as before.
i A long-time travel into the lower end position activated via the corresponding
communication object also calibrates the reference position.
i With the sun protection function it is moreover possible to force the actuator to perform a
reference movement before each sun protection travel even if the positions are known.
Thus, it is ensured that in case of sun protection the configured sun protection position is
always precisely approached even after repeated position approaches.
i Using the connected drives frequently for position approaches (for instance several times a
day) can result after some time in positioning inaccuracies. These deviations from the
setpoint position are mostly due to external physical influences. To achieve accurate
positioning in operation it is recommended to perform the reference movement at least
once every day. This can be achieved for instance by a central raising command
transmitted to the long-time object.
Table 4: Data format of positioning objects with conversion into percentage position values
It is possible that new positioning telegrams are being received while a position approach is in
progress. In this case, the device immediately reverses the direction of travel, if the new position
to be approached lies in the opposite direction.
If a slat positioning command is received during a running Venetian blind position approach, the
device finishes first the Venetian blind position approach before positioning the slat. If a
Venetian blind positioning command is received during a slat positioning movement, the device
interrupts the slat positioning movement and approaches the new Venetian blind position. The
device only executes the most recently receive slat positioning command after this.
In case of Venetian blind positioning, slat positioning will always be executed later. After
switching on the bus voltage or after programming with the ETS, it may be the case that the slat
position is unknown, if no long time command for the upward or downward movement with a
duration of at least the configured slat moving time has been received or no slat positioning has
taken place (no slat reference movement). In this case, the slat is moved during a Venetian
blind position approach into the completely closed position (100 %). The slat position is then
considered as calibrated.
i Optionally, the sun protection function offers the possibility of receiving the instruction of
the blind height, venting louver or slat position to be adopted during sunshine via separate
communication objects and to preset these values variably. This form of variable position
preset in the sun protection function is identical to presetting the positions via
communication objects in direct operation. The priority of the incoming telegrams in direct
operation with the sun protection activated can be additionally configured in the ETS.
Positioning by the sun protection function, the behaviour after bus voltage return or by a scene
recall:
In case of the device functions mentioned, the positions to be approached are configured
directly in the ETS depending on the operating mode. The position values can be specified
between 0 % and 100 % in 1 % increments.
With Venetian blinds, the height of the Venetian blind is positioned first in these cases. The
configured slat position is adjusted only thereafter.
i Important notes for all positioning movements: Using the connected drives frequently for
position approaches (for instance several times a day) can result after some time in
positioning inaccuracies. These deviations from the setpoint position are mostly due to
external physical influences. To achieve accurate positioning in operation it is
recommended to perform the reference movement at least once every day. This can be
achieved for instance by a central raising command transmitted to the long time object.
The individual position feedback messages can be enabled in the ETS independent of one
another and have communication objects of their own.
For each movement, the device calculates the current position and tracks it in the position
feedback objects. The positions are tracked and the feedback objects updated even when the
output has been activated via short time or long time telegrams on condition that the bus
voltage is on.
The feedback objects are not updated, if the position last reported back has not changed after a
movement (for instance, when the Venetian blind is repositioned, the unchanged slat position
will not be reported back a second time).
The device cannot calculate a feedback position, if the current position data after switch-on of
the bus voltage or after ETS programming are still unknown. In these cases, the system must
first perform a reference movement (cf. "reference movement") so that the position can be
calibrated. In case of unknown positions, the device automatically performs reference
movements, if new positions are preset and if these positions are to be approached. As long as
a position is unknown, the value of the feedback objects is "0".
Presetting position feedback for Venetian blind, roller shutter, awning or venting louver
positions
The feedback functions can be enabled and programmed. When feedback is enabled, the ETS
adapts the parameter texts depending on the preset operating mode
("Venetian blind position feedback", "Roller shutter/awning position feedback" or
"Venting louver position feedback"). The feedback can be used as an active message object or
as a passive status object. As an active signalling object, the position feedback information is
transmitted to the bus whenever a position value changes. As a passive status object, there is
no telegram transmission after a change. In this case, the object value must be read out. The
ETS automatically sets the object communication flags required for proper functioning.
In case of an actively transmitting signalling object, the current position can be transmitted to
the bus after bus voltage return, if the position value differs from the one last transmitted. When
the position data are known, the feedback telegram can in this case be transmitted with a time
delay to reduce the bus load, with the delay being preset globally for all outputs in common (cf.
"Delay after bus voltage return").
The feedback functions of an output must be enabled on parameter page
"O1 - Enabled functions". Only then are the parameters for the feedback functions visible.
o Set the parameter "Venetian blind position feedback",
"Roller shutter/awning position feedback" or "Venting louver position feedback" on
parameter page "O1 - Feedbacks" to "feedback object is active signalling object".
The feedback object is enabled. The position value is transmitted as soon as it changes.
No value will be actively transmitted, if the position is unknown.
o Set the parameter "Venetian blind position feedback",
"Roller shutter/awning position feedback" or "Rückmeldung Lüftungsklappenposition" on
parameter page "O1 - Feedbacks" to "feedback object is passive status object".
The feedback object is enabled. The position value will be transmitted in response only if
the feedback object is read out from by the bus. If the position is unknown, a value of "0"
will be reported back after readout.
Presetting the position feedback for slat positions (only with Venetian blinds)
The feedback for the slat positions can be enabled and programmed separately. As with the
position feedback of the Venetian blind height, the feedback can be used as an active message
object or as a passive status object.
In case of an actively transmitting signalling object, the current slat position can be transmitted
to the bus after bus voltage return, if the position value differs from the one last transmitted.
When the position data is known, the feedback telegram can, in this case, be transmitted with a
time delay to reduce the bus load, with the delay being preset for all feedback in common
(cf. "Delay after bus voltage return").
The feedback functions of the output must be enabled on parameter page
"O1 - Enabled functions". Only then are the parameters for the slat position feedback functions
visible.
o Set the parameter "Slat position feedback" on parameter page "O1 - Feedbacks" to
"feedback object is active signalling object".
The feedback object is enabled. The position value is transmitted as soon as it changes.
No value will be actively transmitted, if the position is unknown.
o Set the parameter "Slat position feedback" to "feedback object is passive status object".
The feedback object is enabled. The position value will be transmitted in response only if
the feedback object is read out from by the bus. If the position is unknown, a value of "0"
will be reported back after readout.
reference movement. The calibration of the slat position in a Venetian blind alone will not result
in the reversal of an 'invalid position' status message.
As an option, the object value of the status feedback message can be actively transmitted to the
bus in case of a value change.
i Automatic transmission after bus voltage return only takes place if there has been an
internal change to the object state.
i Automatic transmission only takes place after a bus voltage return when the drive starts
moving on bus voltage return or if the bus failure has caused a change to the drive
movement.
The communication objects for the safety alarms can be monitored for the arrival of cyclical
telegrams. If there are no telegrams within a settable monitoring time, the device activates the
safety movement for the output. The safety function is terminated as soon as a new
"0" telegram is received.
For the wind alarms, the rain alarm and the frost alarm, different monitoring times between '1
minute' and '23 hours 59 minutes' can be separately selected in the ETS. A shared time is
configured for the wind alarms. Each wind alarm has its own timer so that the wind objects are
separately checked for telegram updates.
The output can be assigned independently to the wind alarms, the rain alarm and the frost
alarm. If the output is associated with several alarms, the preset priority decides which of the
alarms will prevail and be executed. In so doing, an alarm with a higher priority overrides the
alarms with the lower priorities. When safety alarm with the higher priority has ended, the safety
alarm with the lower priority is executed on condition that it is active.
The order of priority of the wind alarms with respect to the frost alarm or to the rain alarm can be
configured on the parameter page "O1 - Safety I". The three wind alarms have the same priority
with respect to one another (logic OR). The last telegram update to the wind alarm objects
decides which of the wind alarms will be executed. The wind alarm is completely deactivated
only after all three objects are inactive ("0").
The output in the active safety alarm state is locked, i.e. the control of the output concerned via
the bus by direct operation (short time, long time telegram, scenes, positioning) or by a sun
protection function is prevented. Only a forced position has a higher priority so that this function
may override a safety lock. At the end of a forced position, the safety reaction is re-executed if
an assigned safety alarm is still active.
i The cycle time of the transmitters should be shorter than the monitoring time configured in
the device in order to ensure that at least one telegram can be received during the
monitoring time.
i If an output was assigned to the wind alarm and these alarms are not enabled on
parameter page "O1 - Safety I", the assignment is without effect.
i The safety movement time required by an output to move the drive into the end positions is
determined by the "Movement time" parameter on parameter page "O1 - Times". Like the
long-time operation, a safety movement is derived from the movement time. Downward
movement: movement time + 20 %; Upward movement: movement time + 20 % +
configured movement time extension. Safety movements are not retriggerable.
i Slats of blinds are not repositioned at the end of safety movements to end positions.
The sun protection functions of the device can be adapted many different applications. In simple
applications as, for instance, in case of direction-dependent measurement of the sun's intensity
by means of a brightness sensor, the curtains controlled can be closed partly or completely to
prevent being disturbed by direct sunlight. In these applications, the sun protection function
merely evaluates the 1-bit sun signal from the brightness or a similar sensor (e.g. weather
station with limit value monitoring) and makes a drive open or close the controlled curtains by
moving them into fixed configured positions or into variable positions preset via the bus.
In extended applications – for instance where the degree of shading is controlled by weather
stations evaluating additionally the sun angle as a function of astro co-ordinates and presetting
the blind and also the slat positions dynamically – the sun protection function can be
supplemented by an automatic control system. In such applications, the sun protection function
evaluates additional bus communication objects allowing to enable or to disable the automatic
control while the device is in operation. This results in a large number of combination variants
with intelligent Venetian blind control systems.
Already simple sun protection applications are sufficient to permit a fixed or variable re-
adjustment of the positions of Venetian blind slats for adapting the curtain to individual shading
requirements. For such purpose, it is possible to preset a static slat offset in the ETS
parameters, for instance, for adapting the reflection of sunlight depending on the building
situation, or additionally, a dynamical slat offset via a bus communication object,
for instance, for manual re-adjustment of the slat opening by persons in the room or otherwise
by a central building services control system.
In all cases, the priority between an incoming sunshine or automatic telegram and the direct
operation of the output (short time, long time telegram, scenes, positioning) is also presettable
in the ETS. This way, a sun protection position can, for instance, be influenced by a 'manual'
operation of a pushbutton sensor in the room and the sun protection function be interrupted.
Alternatively, sun protection mode can therefore not be interrupted by a direct operation, i.e. the
output is locked.
A sun protection function can be overridden by a safety function, a forced position or also by a
manual control locally on the device itself as these functions of the device invariably have a
higher priority. At the end of one of the mentioned functions with a higher priority, the same
reaction as the one at the beginning of sun protection will be re-executed, if the sun protection
function is still active at this time.
The device can be operated with two sun protection functions. The simple sun protection or
alternatively the extended sun protection that can be enabled.
A newly received object value (sun / beginning of shading or sun / end of shading) can
optionally be evaluated with a time delay. This feature permits suppressing brief brightness
variations caused, for instance, by passing clouds or by a thunderstorm. An update (from
activated to activated) of the "Sunshine / shading facade" object causes the sun protection to be
reactivated, if it had been influenced and possibly been re-enabled beforehand by a direct
operation in acc. with the preset priority.
The reaction of the output at the beginning of shading can be preset in the ETS.
Amongst other things, this setting permits approaching fixed configured positions or positions
preset via the bus and thus variable. Variable positions for sun protection purposes can be
preset, for instance, by means of pushbutton sensors or visualisations. In addition, it is possible
in case of a defined sun protection positioning movement to have a reference movement
executed by forced control. This ensures that identical blind positions are approached
synchronously by different outputs in case of a sun protection positioning movement.
The reaction at the end of a shading task can be preset as well. In this situation, the curtain can
pass into an end position, be stopped or shown no special reaction. Tracking of positions is
possible as well.
By means of a priority setting in the ETS configuration, it can be specified whether the sun
protection function can be influenced by direct operation or whether the corresponding output is
locked by a telegram "Sunshine / shading facade" in the sun protection position. The
"Forced position" and "Safety" functions always have a higher priority so that these functions
can override, but not terminate a sun protection. Thus, the sun protection function is re-
executed at the end of a function with a higher priority, if the object "Sunshine / shading facade"
continues to signal the presence of sunshine.
i The following rules must be observed for the extended sun protection: After an ETS
programming operation, the sun protection function including automatic operation is always
deactivated.
The schematic diagram of the simple sun protection (Figure 20) and an example of how sensor
components can be integrated into a simple sun protection configuration.
Figure 20: Schematic diagram illustrating the simple sun protection configuration
The function diagram (Figure 21) shows all possible functions of the simple sun protection. For
reasons of clarity, the functions with a higher priority (forced position, safety function) are not
shown in the diagram.
In the extended sun protection, shading against sunlight is activated and deactivated via the
1-bit communication object "Sunshine / shading facade". A reaction of the output to the sun
telegram can be expected only after the automatic control has been activated. In all other
cases, the sun protection function is completely deactivated.
As far as the activation of the automatic control via the corresponding object is concerned, the
following two cases must be distinguished...
- Sun shading action starting immediately:
Automatic operation is activated as soon as the "Automatic" object receives a "1" telegram.
The output reacts immediately to the activation and shows the preset behaviour depending
on sunlight conditions (Sun / beginning of the shading action / Sun end of the shading
action). The sunlight conditions are derived from the "Sun / shading facade" object
according to the set polarity - if necessary after the delays have elapsed.
After an ETS programming operation or after switch-on of the supply voltage, the
"Sunshine / shading facade" object is initialised with "0" and, unlike the simple sun
protection, evaluated immediately depending on the preset polarity so that shading against
sunlight can begin immediately on activation of the automatic sun protection function. The
reception of a "0" telegram by the object "Automatic" always terminates an automatic
operation independent of the state of the "Sunshine / shading facade" object.
Application example:
Private house with winter garden. The conservatory is equipped with Venetian blinds to
shade the place against sunlight. When the conversation is used, automatic operation is
activated, for instance, with a pushbutton sensor on the wall. The device then immediately
executes the shading function, if sunshine was detected.
The device performs the behaviour configured for the end of the shading / sunshine in case
no sunshine is detected when the automatic operation is activated.
Application example:
An office building is equipped with several Venetian blinds to shade individual offices
against sunlight. In the early morning hours, the automatic sun protection is activated in a
central place in the building, e.g. in the porter's lodge. The Venetian blinds will, however,
not move into the shading positions unless the system has actually reported sunshine for
the building facades in question.
The behaviour at the end of automatic operation is configured separately in the ETS and is
executed whenever the automatic mode is terminated and when no function with a higher
priority is active at this time. In this situation, the curtain can pass into an end position, be
stopped or shown no special reaction. Tracking of positions is possible as well.
moreover equipped with a pushbutton sensor on the wall with which the automatic operation
can be activated or also deactivated. When the automatic mode is activated, the room is
immediately shaded against sunlight, if necessary. Depending on the time of day or in the event
of disturbing sunlight falling into the room, the persons in the room can therefore decide for
themselves whether automatic shading is desired or not.
If required, the automatic sun protection is disabled in a central place of the building,
for instance, in the porter's lodge. The automatic control of the Venetian blinds can then be
deactivated, if servicing work is being carried out (window cleaning or similar work). After the
end of disabling, for instance, at the end of the working hours, automatic operation can only be
restarted if it is reactivated in any of the rooms in case of need.
In addition, also the direct operation of the output can be disabled with an independent disabling
object. When disabling is active, a direct operation can – independent of the preset priority –
never override a sun protection function. In this case, direct operation is non operational
in other functions, too. During disabling, incoming direct operation telegrams are completely
ignored (positions received via the bus can then not be tracked either).
If the disabling command is received while a movement initiated by direct operation is in
progress, the movement will still be completely finished. Thereafter, direct operation is
disabled.
The disabling functions for automatic and for direct operation can also be combined so that it is
possible to intervene at any time and as required by the situation in sun protection control
functions.
A new value received via the "Sunshine / shading facade" object can optionally be evaluated
with a time delay. This feature permits suppressing brief brightness variations caused, for
instance, by passing clouds or by a thunderstorm. The time delay is started after an update of
the "Sunshine / shading facade" object also in those cases where the automatic operation is
deactivated so that the newly received information about the sunshine conditions may possibly
also be processed with a delay, if the automatic operation is activated later on.
Unlike in the simple sun protection mode, an update of the "Sunshine / shading facade" object
from active to active or from inactive to inactive in the extended sun protection mode shows
generally no reaction. The behaviour of the output is only influenced if a change of state is being
detected. An update of the sunshine signal alone does not result in the activation of the
automatic operation either.
When the automatic operation is active, the reaction of a specific output at the beginning of
shading can be preset separately in the ETS. This setting permits approaching fixed configured
positions or positions preset via the bus and thus variable. Positions for sun protection purposes
can be variably preset, for instance, by means of a weather station for sun position tracking.
In addition, it is possible in case of a defined sun protection positioning movement to have a
reference movement executed by forced control. This ensures that identical blind positions are
approached synchronously by different outputs in case of a sun protection positioning
movement.
At the end of sun shading when automatic operation is active, the output reaction can also be
configured separately. In this case, too, it is possible to approach fixed configured positions.
By means of a priority setting in the ETS parameters it can be specified whether the evaluation
of the sunshine signal in the automatic mode can be influenced by a direct operation or whether
the automatic mode basically locks the corresponding output during sun protection. The
"Forced position" and "Safety" functions invariably have a higher priority so that these functions
can override, but not terminate a sun protection including an automatic operation. Thus, the sun
protection function is re-executed at the end of a function with a higher priority, if the automatic
sunshine protection is still active.
An update (from activated to activated) of the "Automatic" object causes the sun protection to
be reactivated, if it had been influenced and cancelled beforehand by a direct operation in
accordance with the lower priority.
The schematic diagram of the extended sun protection (Figure 22) and an example of how
sensor components can be integrated into an extended sun protection configuration.
Figure 22: Schematic diagram illustrating the extended sun protection configuration
(for reasons of simplicity without disabling functions)
The function diagram (Figure 23) shows all possible functions of the extended sun protection.
For reasons of clarity, the functions with a higher priority (forced position, safety function) are
not shown in the diagram.
i The following rules must be observed for the extended sun protection:
After an ETS programming operation, the sun protection function including automatic
operation is always deactivated. An activated sun protection (independent of the selected
priority with respect to direct operation) remains active even after a bus voltage failure as
long as the mains voltage supply is still on. The sun protection reaction last executed will
therefore be executed again at the end of a temporary or permanent manual control (if
enabled in case of bus failure), even if there is no bus voltage.
i When the sun protection type parameters are changed, the assignments of group
addresses to sun protection objects or other parameter settings are lost. For this reason,
the sun protection type parameter should be selected directly at the beginning of the sun
protection configuration and then not be changed anymore later on.
Presetting the priority of sun protection (for simple sun protection only)
The priority of the sun protection function can be set. In the simple sun protection, the priority
relations between the "Sunshine / shading facade" object and the objects of direct operation
(short time, long time or position telegram, scene recall) must be configured.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for simple sun protection.
o Set the parameter "Priority of sun protection with respect to direct operation" on parameter
page "O1 - Sun protection" to "same priority".
The sun protection mode can be overridden at any time by direct operation. In the same
way, the sun protection overrides the direct operation, when a new "sunshine" telegram is
received via the "Sunshine / shading facade" object and when a configured time delay, if
any, has elapsed. If the sun protection function is overridden by a direct operation, the
preset behaviour "Reaction at the end of sunshine / shading" will not be executed.
o Set the parameter "Priority of sun protection with respect to direct operation" on parameter
page "O1 - Sun protection" to "higher priority".
An active sun protection will override a direct operation. The sun protection mode can
therefore not be interrupted by a direct operation. Direct operation will be possible again
only after the sun protection function is terminated.
o Set the parameter "Priority of sun protection with respect to direct operation" on parameter
page "O1 - Sun protection" to "lower priority".
A direct operation can at any time override the sun protection mode. If the sun protection
function is overridden by a direct operation, the preset behaviour
"Reaction at the end of sunshine / shading" will not be executed. The sun protection
function can only be reactivated after an enabling movement controlled by a direct
operation has been effected and after a new "sunshine" telegram has been received via the
"Sunshine / shading facade" object. Attempts to activate the sun protection function are
ignored for as long as the enabling movement has not taken place.
On the enabling movement:
An enabling movement is an accomplished long time movement into the upper end position
which has been initiated by the object "Long time operation". An upward movement after
bus voltage return, a position approach to "0 %" or an upward movement after enabling of
forced position or safety functions have no enabling effect.
The sun protection is not enabled if the enabling movement has been interrupted. The
sunshine protection function will be also be disabled if the output has been readjusted
again by a direct operation after an accomplished enabling movement.
After an ETS programming operation or switch-on of the bus voltage, the sunshine
protection function is always enabled.
i The forced position function and the safety functions have a fixed priority higher than that of
the sun protection. The sun protection is overridden – but not terminated – by a function
with a higher priority. After the end of the function with the higher priority the reaction at the
beginning of sun protection will therefore be executed again, if the sun protection is still
active at this time.
i With the settings "same priority" or "lower priority", the sun protection can be overridden by
a direct operation only if the direct control action can be executed at once. A direct
operation will therefore not override the sun protection during an active forced position
function or an active safety function.
i Parameter setting "same priority" or "lower priority": A variable preset of curtain and slat
positions or of a slat offset via the bus at the beginning of sunshine / shading shows no
reaction at the output, if the sun protection was overridden by direct operation. However,
the position data or offsets received are stored internally so that the new positions will be
approached on reactivation of the sun protection.
Presetting the priority of automatic sun protection (for extended sun protection only)
The priority of the automatic sun protection function can be set. In the extended sun protection,
the priority relations between the "Sunshine / shading facade" object and the objects of direct
operation (short time, long time or position telegram, scene recall) must be configured. The
selected priority thus affects the evaluation of the sunshine signal in the automatic mode and
not the automatic mode itself.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for extended sun protection.
o Set the parameter "Priority of automatic operation with respect to direct operation" on
parameter page "O1 - Sun protection" to "same priority".
The sunshine signal of the automatic sun protection mode and the corresponding reaction
can be overridden at any time by direct operation. In the same way, the sunshine signal
overrides the direct operation, when a new "sunshine" or "no sunshine" telegram is
received via the "Sunshine / shading facade" object and when this telegram results in a
change of state. Moreover, a configured delay time, if any, must have elapsed. When the
sunshine signal is overridden by a direct operation, the preset behaviour
"Reaction at the end of sunshine / shading" will not be executed.
o Set the parameter "Priority of automatic operation with respect to direct operation" on
parameter page "O1 - Sun protection" to "higher priority".
An active automatic mode always overrides the direct operation independent of the
sunshine signal. The sunshine signal can therefore not be interrupted by a direct operation.
Direct operation will be possible again only after the automatic mode is terminated.
o Set the parameter "Priority of automatic operation with respect to direct operation" on
parameter page "O1 - Sun protection" to "lower priority".
A direct operation can at any time override the sunshine signal. If the sunshine signal is
overridden, the preset behaviour "Reaction at the end of sunshine / shading" will not be
executed. The sunshine signal will be evaluated again only after an enabling movement
controlled by a direct operation has been effected and when a new "sunshine" or
"no sunshine" telegram is received via the "Sunshine / shading facade" object and when
this telegram results in a change of state. The sun protection function is ignored for as long
as the enabling movement has not taken place.
On the enabling movement:
An enabling movement is an accomplished long time movement into the upper end position
which has been initiated by the object "Long time operation". An upward movement after
bus voltage return, a position approach to "0 %" or an upward movement after enabling of
forced position or safety functions have no enabling effect.
The sunshine signal is not enabled if the enabling movement has been interrupted. The
sunshine signal will be also be disabled, if the output has been re-adjusted again by a
direct operation after an accomplished enabling movement.
i A direct operation never terminates the automatic mode. Irrespective of a function being
overridden by a direct operation, an activation or a deactivation of the automatic mode
(telegram update of the "Automatic" object) always re-enables the sunshine signal as well
and evaluates it when the automatic mode is active. Attention must be paid to this
behaviour especially in those cases where the "Automatic" object is cyclically overwritten
by telegrams.
i The forced position function and the safety functions have a fixed priority higher than that of
the automatic sun protection. The sun protection is overridden – but not terminated – by a
function with a higher priority. After the end of the function with the higher priority the
reaction last executed by the automatic sun protection will therefore be executed again, if
the sun protection is still active at this time.
i With the settings "same priority" or "lower priority", the sunshine signal can be overridden
by a direct operation only if the direct control action can be executed at once. A direct
operation will therefore not override the sun signal during an active forced position function
or an active safety function.
i Parameter setting "same priority" or "lower priority": A variable preset of blind and slat
positions or of a slat offset via the bus at the beginning of sunshine / shading shows no
reaction at the output, if the sunshine signal was overridden by direct operation. However,
the position data or offsets received are stored internally so that the new positions can be
approached when the sensor signals that the sun is shining again.
i Irrespective of the preset priority, an update of the "Sunshine / shading facade" object from
active to active or from inactive to inactive in the extended sun protection mode shows
generally no reaction. The behaviour of the output is only influenced if a change of state is
detected.
i In the simple sun protection mode, an update (from activated to activated) of the
"Sunshine / shading facade" object causes the sun protection to be reactivated, if it had
been influenced and possibly been re-enabled beforehand by a direct operation in acc. with
the preset priority.
i In the extended sun protection mode, an update of the "Sunshine / shading facade" object
from active to active or from inactive to inactive shows generally no reaction. The behaviour
of the output is only influenced if a change of state is detected.
Presetting the activation of the automatic mode (for extended sun protection only)
As far as the activation of the automatic mode is concerned, two cases must be distinguished
which can be configured with the help of ETS parameters. Either a travel movement in acc. with
the reaction at the beginning or the end of sunshine is executed immediately on activation of the
automatic mode, or otherwise the system waits after activation of the automatic mode for a new
change of state in the "Sunshine / shading facade" object until the corresponding output shows
the reaction at the beginning or at the end of sunshine.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for extended sun protection.
o Set the parameter "Activation of automatic mode by..." on parameter page
"O1 - Sun protection" to "Object 'Automatic' and next change of state".
i Depending on the setting, various object numbers are created for the "Automatic" object in
the ETS. If the parameters are changed, the group address assignments for the automatic
object are lost.
Presetting the polarity of the "Automatic" object (for extended sun protection only)
If the automatic mode is to be activated via the object and only at the next change of state of the
sunshine signal (see "Presetting the activation of the automatic mode"), the telegram polarity of
the automatic object can be preset in addition.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The extended sun protection must be configured for activation of the automatic mode on next
change of state.
o Set the parameter "Polarity of 'Automatic' object" on parameter page "O1 - Sun protection"
to the required telegram polarity.
The telegram to the "Automatic" object will be evaluated depending on the selected priority.
i After an ETS programming operation or after switch-on of the supply voltage, the
object "Automatic" must at first have data written into it by the bus also in case of inverted
polarity before the automatic operation can be activated.
i The polarity of the "Automatic" object is not presettable, if the automatic mode is activated
via the object with immediate tracking. In this case, the telegram polarity is fixed:
Automatic ON = "1", Automatic OFF = "0".
Presetting the disabling function for the automatic mode (for extended sun protection
only)
Automatic mode can be deactivated at any time via a separate disabling object. After enabling
of the disabling function in the ETS parameters, the "Automatic mode disable" object becomes
visible.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The extended sun protection must be configured for activation of the automatic mode with
immediate tracking of the sunshine signal.
o Set the parameter "Disabling function for automatic mode ?" on parameter page
"O1 - Sun protection" to "yes".
The disabling function is enabled. The parameter for setting of the polarity becomes visible.
o Set the parameter "Polarity of object 'Automatic mode disable'" on parameter page
"O1 - Sun protection" to the required telegram polarity.
The telegram to the "Automatic mode disable" object will be evaluated depending on the
selected priority.
i The objects "Automatic" and "Automatic mode disable" are logically combined
(AND with feedback). When disabling is activated, the automatic operation is reset and
thus aborted. The output will then show the behaviour at the end of automatic operation.
The automatic mode can only be reactivated, if the disabling object is enabled and if the
"Automatic" object is updated again by writing a "1" into it. Any attempt of activating the
automatic mode while a disable is active will be ignored.
i After an ETS programming operation or after switch-on of the supply voltage, the
objects "Automatic" and "Automatic mode disable" are always initialised with "0". If the
disabling object works with inverted polarity (setting "disabled" = "0") the disabling function
is in this case immediately active.
Presetting the disabling function for direct operation (for extended sun protection only)
The direct mode can be deactivated at any time via a separate disabling object. After enabling
of the disabling function in the ETS parameters, the "Direct operation disable" object becomes
visible.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for extended sun protection.
o Set the parameter "Disabling function for direct mode ?" on parameter page
"O1 - Sun protection" to "yes".
The disabling function is enabled. The parameter for setting of the polarity becomes visible.
o Set the parameter "Polarity of object 'Direct operation disable'" on parameter page
"O1 - Sun protection" to the required telegram polarity.
The telegram to the "Direction operation disable" object will be evaluated depending on the
selected priority.
i After an ETS programming operation or after switch-on of the supply voltage, the
"Automatic mode disable" object is always initialised with "0". If the disabling object works
with inverted polarity (setting "disabled" = "0") the disabling function is in this case
immediately active.
Presetting the reaction at the end of automatic operation (for extended sun protection
only)
When the automatic operation is being deactivated – also by the disabling function – the output
will show the preset reaction, if no function with a higher priority is active at the time of
deactivation. The preset reaction will not be executed either on termination of the automatic
operation, if the sunshine signal is overridden on account of priority settings by a direct
operation. The reaction at the end of automatic operation is preset on parameter page
"O1- Sun protection". Depending on the selected mode of operation, the ETS adapts the
designations of the parameter settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing
the louver.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for extended sun protection.
o Set the parameter "Reaction at the end of automatic operation" to "no reaction".
At the end of automatic operation the relay of the output shows no reaction. Any
movements still in progress at this instant will still be finished.
i The behaviour preset in this parameter will only be executed, if no function with a higher
priority (e.g. safety) is activated at the end of automatic operation.
i Parameter setting "Position tracking": The device can track absolute positions (position
telegram, scene value) at the end of automatic operation only if the position data is known
and if the positions have been predefined. There is otherwise no reaction at the end of
automatic operation.
Position data can be tracked, if the output was in a defined position before the automatic
sun protection function or if a new position telegram was received via the position objects
during the sun protection. In the latter case, a reference movement will be executed at the
end of automatic operation, if the position before or during the sun protection was
unknown.
Known slat positions will also be tracked as described. This is also the case, when the
height of the Venetian blind is unknown.
Long time travel movements (movements without position preset) will always be tracked.
i A setting of "0" in the parameters deactivates the respective delay time. In this case, the
state of the sunshine signal is evaluated immediately.
i Simple sun protection mode: An update (from activated to activated) of the
"Sunshine / shading facade" object causes the sun protection to be reactivated in
consideration of the delay time, if the sun protection had been influenced or aborted
beforehand by a direct operation because of the same or a lower priority.
i For extended sun protection mode: The time delay is started after an
update of the "Sunshine / shading facade" object also in those cases where the automatic
operation is deactivated so that the newly received information about the sunshine
conditions may possibly also be processed with a delay, if the automatic operation is
activated later on. Unlike in the simple sun protection mode, an update of the
"Sunshine / shading facade" object from active to active or from inactive to inactive in the
extended sun protection mode shows generally no reaction. The behaviour of the output is
only influenced if a change of state is detected. An update of the sunshine signal alone
does not result in the activation of the automatic operation either.
i In the "Venetian blinds" operating mode, the setting "fixed position" can be selected
separately for the height of the Venetian blind and for the slat position. For this reason, the
ETS adapts the parameter selection and enlarges the setting options in this operating
mode.
o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"as parameter value". Thereafter, set the parameter
"Position of Venetian blind (0…100%)", "Position of roller shutter/awning (0…100%)" or
"Position of venting louver (0…100%)" to the desired position.
At the beginning of shading, the output invariably approaches the configured position value.
o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"no change of current position".
At the beginning of shading, the last set position of the Venetian blind height, the roller
shutter, awning or venting louver will be maintained.
o "Fixed position" and operating mode = "Venetian blind" only: Set the parameter
"Fixed slat position (0…100%)" to the desired position value.
At the beginning of shading, the output invariably moves the slats to the configured position
after the height of the Venetian blind has been adjusted.
o Set the parameter "Reaction at the beginning of sunshine / shading" to "variable position".
At the beginning of shading, the device recalls the variably specified position value output.
The variable specification of the Venetian blind height, the roller shutter, awning or venting
louver position takes place via the separate communication object
"...pos. sunshine / shading" (in the "Venetian blind" operating mode for the slats also using
the separate object "Slat position sunshine / shading").
i In the "Venetian blind" operating mode, the "variable position" setting can be selected
separately for the height of the Venetian blind and for the slat position. For this reason, the
ETS adapts the parameter selection and enlarges the setting options in this operating
mode.
i The behaviour preset in this parameter will only be executed, if no function with a higher
priority (e.g. safety) is activated at the time of shading.
i "Internal scene recall" setting: For this setting, the scene function of the output must be
enabled in the ETS. Otherwise, the positions approached at the beginning of sun shading
are undefined positions. The scene position values stored in the device by a scene storage
function will be approached as well. A delay configured for scene recalls has no influence
on the recall of the scene value by the sun protection function.
i "Variable position" setting: After an ETS programming operation or after switch-on of the
supply voltage, the
objects "Sunsh./shading ... position" and "Sunsh./ shading slat position" must receive
position values from the bus. Otherwise the device does not position itself at the start of
sun shading as it does not have any valid position data.
When the device is in operation, the position data can be updated at any time via the bus
even if the sun protection is active (e.g. by a weather station for the purpose of sun position
tracking). The device will then immediately approach the newly received positions if the sun
protection is active. If a function with a higher priority is active, the device stores the newly
received position values and approaches them during a later shading operation.
The position data last received are not lost in a bus voltage failure.
A reference movement by forced control will always be executed in the simple sun protection
mode, when the beginning of shading is signalled for the first time via the
"Sunshine/shading facade" object. Updates of the object from 'sun is shining' to 'sun is shining'
do not initiate a reference movement if, at this time, the output is still in the sun protection
position.
A reference movement by forced control will be executed in the extended sun protection mode,
when the beginning of shading is signalled via the "Sun shading facade" object and when
automatic operation is active or is activated. Updates of the object from 'sun is shining' to
'sun is shining' will never initiate a reference movement. In this case, the sunshine signal must
first change from 'sun is not shining' to 'sun is shining' before a new reference movement can
take place.
A reference movement by forced control will always be executed for synchronisation purposes
as described and also in such cases where the position data of the blind or the slats are known.
No reference movement by forced control will be executed at the end of shading.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
o Set the parameter
"reference movement before every sun protection positioning operation ?" on parameter
page "O1 - Begin of sun protection" to "yes".
At the beginning of shading there is always a reference movement by forced control as
described. The preset position will be approached after the end of the reference movement.
o Set the parameter
"reference movement before every sun protection positioning operation ?" on parameter
page "O1 - Beginning of sun protection" to "no".
A reference movement at the beginning of sun protection will only be executed, if the
position data are unknown, for instance, after an ETS programming operation or after
switch-on of the power supply. In all other cases, the preset shading position will be
approached immediately.
i A reference movement is the time required for a travel movement into the upper end
position increased by 20 % and additionally by the configured travel time extension. A
reference travel is not retriggerable.
i Variable position preset: No reference movement will be executed, if new position values
are preset via the bus while the sun protection is active.
i "Venetian Blind" operating mode: A terminated reference movement of for the height of the
Venetian blind synchronises at the same time also the slat position.
Slat offset in the sun protection mode (only "Venetian blind" operating mode)
An offset can be specified for the slat position at the start of sun shading, if fixed or variable slat
position values are to be approached.
If necessary, the slat offset can correct the fixed or variable nominal slat position and thus allow
the creation of an individual shading situation, when the sun protection is active. The offset can
be preset in two ways...
- The slat offset can be configured statically in the ETS. The configuration of a static offset
value allows variation of the degree of shading in those parts of the building that are not
exposed to full sunshine due to objects in front of the building. The variable slat angle
adjusted by the sun protection control or the fixed angle specified in a parameter can thus
be overridden so that the slats are always opened a bit wider than originally preset.
Alternatively, the slats can also be closed completely by means of the static offset if too
much sunlight is reflected into the room.
- The slat offset can additionally be adapted by the bus via the separate communication
object "Sunshine slat position offset". In this way, the desired slat offset can also be
adjusted during an active shading cycle and independent of a direct operation as, for
instance, the short time mode. Thus, it is possible, for instance, that persons in a room can
correct the slat angle at any time 'manually' and individually by selecting another preset
value at a touch sensor or a visualisation. An offset preset via the object overwrites the
value configured in the ETS.
The preset offset is taken into account in the simple and in the extended sun protection mode
for each positioning move during an active shading cycle (beginning of sun / shading) and
added to the predefined nominal slat position. The offset value can be varied within a range
from -100 % … 0 … 100 % so that the slats can be moved in both directions into the respective
end positions (Figure 24). At an offset of "0 %", the actual slat position is always identical with
the predefined nominal slat position for sun protection purposes.
The position value actually adjusted with the offset after adding the slat position value is always
between 0 and 100 %. Minimum and maximum position are thus determined by the slat end
positions. These limits cannot be exceeded by specifying an greater offset. Example
(Figure 24)...
Slat position at start of sun / shading = 90 %
Slat position offset at start of sun / shading = +30 %
-> The resulting slat position is 100% as the end position is reached.
In acc. with the KNX datapoint type 6.001 (DPT_Percent_V8) the data format of the
communication object "Sunshine slat position offset" permits presetting positive and negative
values in a range of -128 … 0 … +127. The device interprets the value received directly as an
offset in %. Values below 100 or above +100 are limited to the minimum (-100 %) and maximum
offset (+100 %) and evaluated accordingly.
An offset preset via the object overwrites the value configured in the ETS. In the event of a bus
voltage failure, an offset value received via the communication object can be stored internally in
a non-volatile memory so that the offset value last received is not lost even in case the power
supply fails. As an alternative, the offset preset via the bus can be reset (0 %) in the event of a
power supply failure with the result that the value configured in the ETS is again used in
operation. The offset reaction preset in the event of bus voltage failure can be configured in the
ETS.
Configuring the slat offset in the sun protection mode (only "Venetian blind" operating
mode)
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must be configured for the "Venetian blind" operating mode.
The reaction at the beginning of sunshine/shading must be configured for fixed or variable
position preset.
o Set the parameter "Offset with fixed and variable slat position" on parameter page
"O1 - Beginning of sun protection" to "no offset".
The offset correction is deactivated. During shading (beginning of sunshine/shading), the
fixed or variable slat position will be approached without offset correction. The other
parameter relating to the offset are blanked out.
o Set the parameter "Offset with fixed and variable slat position" to "offset as configured".
The static offset correction based on the parameter preset in the ETS is activated. During
every shading operation (beginning of sunshine/shading), the nominal slat position is
always corrected by the configured offset value.
o Set the parameter "Offset with fixed and variable slat position" to
"offset as configured and via object".
The offset correction based on the parameter preset in the ETS and via the object is
activated. The slat offset is preset by a fixed value configured in the ETS and can be
adapted dynamically with a separate communication object. During every shading
operation (beginning of sunshine/shading), the nominal slat position is always corrected by
the preset offset value.
o Set the parameter "Slat offset position (-100 … 100 %)" on parameter page
"O1 - Beginning of sun protection" to the desired offset value.
The configured value defines the static offset correction of the slat position. The configured
value can be re-adjusted via the "Sunshine slat position offset" object, if the communication
object has been enabled.
o Set the "Store offset slat position via object in case of bus voltage failure ?" to "No".
The value received via the object will only be stored temporarily in volatile memory. The
received value only replaces the configured value until the device is reinitialised (bus
voltage return, if both were previously switched up). After the initialisation, the offset value
configured in the ETS will be used again.
o Set the "Store offset slat position via object in case of bus voltage failure ?" to "Yes".
The value received via the object will be stored in case of bus voltage failure in a non-
volatile memory of the device. The originally configured offset value is definitely overwritten
in the process. Only a new ETS programming operation sets the offset back to the
configured value.
i An offset value received via the bus is stored temporarily or permanently in the device and
taken into account during the next shading operation. The reception of an offset value
during an active shading phase (beginning of sunshine/shading active) results in an
immediate and 'visible' correction of the offset angle by the output.
i After an ETS programming operation, the offset is always set to the value configured in the
ETS.
i Storage of the slat offset position in case of bus voltage failure: The offset value preset via
the object is stored only if the bus voltage has been available without interruption for at
least 20 seconds after the last reset (storage capacitors sufficiently charged for storage
purposes). In all other cases nothing is stored.
i The slat offset has no influence on the behaviour of an output at the end of a shading
phase (end of sunshine/shading).
Presetting the reaction at the end of sunshine / shading (for simple sun protection only)
At the end of the shading phase – if applicable, after the end of the delay time – the output will
show the preset reaction, if no function with a higher priority is active at the time of deactivation.
The preset reaction will also not be executed at the end of sun shading, if the sunshine signal is
overridden on account of priority settings by a direct operation.
The reaction at the end of sun shading is preset on parameter page "O1- Sun protection end".
Depending on the selected mode of operation, the ETS adapts the designations of the
parameter settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing the louver.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for simple sun protection.
o Set the parameter "Reaction at the end of sunshine / shading" to "no reaction".
At the end of shading, the relay of the output shows no reaction. Any movements still in
progress at this instant will still be finished.
o Set the parameter "Reaction at the end of sunshine / shading" to
"raising" or "opening the louver".
At the end of shading, the device raises the blind or opens the venting louver.
o Set the parameter "Reaction at the end of sunshine / shading" to
"lowering" or "closing the louver".
At the end of shading, the device lowers the blind or closes the venting louver.
o Set the parameter "Reaction at the end of sunshine / shading" to "stop".
At the end of shading, the device switches the relays of the output to the "stop" position. A
drive movement, if any, will be interrupted.
o Set the parameter "Reaction at the end of sunshine / shading" to "position tracking".
At the end of shading, the output will be set to the state last adjusted statically before sun
protection or to the state tracked and internally stored during sun protection. The position
objects, the long time object and the scene function are tracked.
i The behaviour preset in this parameter will only be executed, if no function with a higher
priority (e.g. safety) is activated when the sun protection is enabled or when a direct
operation has not overridden the sunshine signal on account of priority settings.
i Parameter setting "Position tracking": The device can track absolute positions (position
telegram, scene value) at the end of sun protection only if the position data are known and
if the positions have been predefined. There is otherwise no reaction at the end of sun
shading.
Position data can be tracked, if the output was in a defined position before the automatic
sun protection function or if a new position telegram was received via the position objects
during the sun protection. In the latter case, a reference movement will be executed at the
end of sun protection, if the position before or during the sun protection was unknown.
Known slat positions will also be tracked as described. This is also the case, when the
height of the Venetian blind is unknown.
Long time travel movements (movements without position preset) will always be tracked.
Presetting the reaction at the end of sunshine / shading (for extended sun protection
only)
The behaviour of the output at the end of sunshine / shading – if applicable, after the end of the
delay time – can be configured in the ETS. In the extended sun protection mode, the output
shows the configured reaction, when automatic operation is activated and when a new sunshine
signal (change of state from "sun is shining" -> "sun is not shining") is being received. The
reaction will not be executed if a function with a higher priority is active at the time the sunshine
signal changes. The preset reaction will not be executed either, if the sunshine signal is
overridden on account of priority settings by a direct operation.
The reaction at the end of sunshine / shading is preset on parameter page
"O1- Sun protection end". Depending on the selected mode of operation, the ETS adapts the
designations of the parameter settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing
the louver.
For the sun protection parameters to be visible, the sun protection function must be enabled on
parameter page "O1 - Enabled functions".
The function must have been configured for extended sun protection.
o Set the parameter "Reaction at the end of sunshine / shading" to "no reaction".
At the end of shading, the relay of the output shows no reaction. Any movements still in
progress at this instant will still be finished.
o Set the parameter "Reaction at the end of sunshine / shading" to
"raising" or "opening the louver".
At the end of shading, the device raises the blind or opens the venting louver.
o Set the parameter "Reaction at the end of sunshine / shading" to
"lowering" or "closing the louver".
At the end of shading, the device lowers the blind or closes the venting louver.
o Set the parameter "Reaction at the end of sunshine / shading" to "stop".
At the end of shading, the device switches the relays of the output to the "stop" position. A
drive movement, if any, will be interrupted.
o Set the parameter "Reaction at the end of sunshine / shading" to "internal scene recall".
The number of the scene to be recalled must be specified in the parameter
"Scene number (1…8)".
At the end of shading, the device recalls the position value for the output which was preset
in the scene configuration. This is not a scene recall as in direct operation, but only an
approach to the corresponding scene position value.
o Set the parameter "Reaction at the end of sunshine / shading" to "fixed position".
At the end of shading, the device recalls a fixed position value output.
i In the "Venetian blind" operating mode, the setting "fixed position" can only be selected in
common for the height of the Venetian blind and for the slat position.
o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"as specified by parameter". Thereafter, set the parameter
"Position of Venetian blind (0…100%)", "Position of roller shutter/awning (0…100%)" or
"Position of venting louver (0…100%)" to the desired position.
At the end of shading, the output invariably approaches the configured position value.
o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"no change of current position".
At the end of shading, the last set position of the Venetian blind height, the roller shutter,
awning or venting louver will be maintained.
o "Fixed position" and operating mode = "Venetian blind" only: Set the parameter
"Fixed slat position (0…100%)" to the desired position value.
At the end of shading, the output invariably moves the slats to the configured position after
the height of the Venetian blind has been adjusted.
i The behaviour preset in this parameter will only be executed, if no function with a higher
priority (e.g. safety) is activated at the time the sunshine signal changes. The preset
reaction will not be executed either, if the sunshine signal is overridden on account of
priority settings by a direct operation.
i "Internal scene recall" setting: For this setting, the scene function of the output must be
enabled in the ETS. Otherwise, the positions approached at the end of sunshine/shading
are undefined positions. The scene position values stored in the device by a scene storage
function will be approached as well. A delay configured for scene recalls has no influence
on the recall of the scene value by the sun protection function.
When automatic heating / cooling is active, a presence signal – e.g. from a KNX / EIB presence
monitor or a detector – is evaluated in addition to the signals of the extended sun protection
function. The automatic sun protection function will then only be activated by the device when
people are in the room. The room is then shaded or not according to the sunshine signal (see
chapter 4.2.4.4.5. Sun protection settings).
If no presence is signalled, the device evaluates in addition a heating/cooling signal derived, for
instance, from a room temperature controller or from an outside thermostat. In this case, the
shading function can be used to support the heating or cooling function in a room. As no
persons are present in the room, intensive sunlight can be used, for instance, to heat up the
room by opening the slats or by raising the curtain. Similarly, the room can also be shaded
against sunlight during the absence of persons, if additional heating up of the room is not
desired.
Table 5: States of the extended sun protection function with heating/cooling switchover
As described for the extended sun protection without automatic heating/cooling, the sunshine
signal will be delayed, if a delay is configured in the ETS for this signal. In the same way, the
presence signal can be evaluated independently after a delay, for example in order to
'debounce' short time changes to the signal state.
The schematic diagram (Figure 25) shows the interaction of the different communication objects
of the extended sun protection function in combination with the
automatic heating/cooling function. The diagram moreover illustrates the principle of
incorporating sensor components into the automatic heating/cooling system.
In accordance with the schematic diagram, the automatic heating/cooling function is only active
when the automatic sun protection is active, too. Like in the extended sun protection mode
without automatic heating/cooling, the automatic sun protection is activated via the
object "Automatic" depending on the configuration either immediately or only after a change of
state has been detected for one of the signals "Presence", "Heating/cooling switchover" and
"Sunshine / shading facade" (cf. "Sun protection function – extended sun protection").
After an ETS programming operation or after switch-on of the bus voltage supply), the
corresponding communication objects of the signals "Presence", "Heating/cooling switchover"
and "Sunshine / shading facade" are initialised with "0". In accordance with the preset polarity,
the state of the sunshine and of the presence signal as well as the heating/cooling state will be
determined and the corresponding reaction executed provided the automatic sun protection
function is active. When the automatic sun protection is active, any change of state of the
presence signal or any change in the heating/cooling signal will be evaluated immediately and
the corresponding reaction executed.
The schematic function diagram (Figure 26) shows all possible functions of the extended sun
protection with automatic heating/cooling. For reasons of clarity, the functions with a higher
priority (manual control, forced position, safety function) are not shown in the diagram.
i If the automatic heating/cooling activation parameters are changed, the group address
assignments and the parameter settings are lost. For this reason, the automatic heating/
cooling parameters should be selected directly at the beginning of configuration and then
not be changed anymore later on.
i An update of the "Heating / cooling switchover" object from active to active or from inactive
to inactive shows generally no reaction. The behaviour of the output is only influenced if a
change of state is detected.
i After switch-on of the bus supply voltage, the heating/cooling switchover function is
initialised with an object value of "0".
i An update of the "Heating / cooling presence" object from active to active or from inactive
to inactive shows generally no reaction. The behaviour of the output is only influenced if a
change of state is detected.
i After presence control of the bus supply voltage, the heating/cooling switchover function is
initialised with an object value of "0".
The telegram for activation of the presence mode will be evaluated with a delay
corresponding to the setting.
o Set the parameter "Time delay at the end of presence" to the required delay time.
The telegram for deactivation of the presence mode will be evaluated with a delay
corresponding to the setting.
i A setting of "0" in the parameters deactivates the respective delay time. In this case, the
presence state is evaluated immediately on reception of a telegram.
i An update of the "Heating / cooling presence" object from active to active or from inactive
to inactive shows generally no reaction. The behaviour of the output is only influenced if a
change of state is detected. An update of the presence signal alone does not result in the
activation of automatic operation either.
i The time delay is started after an update of the "Heating / cooling presence" object also in
those cases where the automatic operation is deactivated so that the newly received
presence state may possibly also be processed with a delay, if the automatic operation is
activated later on.
The reaction of the output can be set separately in the ETS for each of the named states. There
is no difference between the parameter settings for the individual states. For this reason, the
following section only describes the possible configuration as an example.
The reaction at the end of automatic heating/cooling is set on parameter page
"O1 - Automatic heating/cooling". Depending on the selected mode of operation, the ETS
adapts the designations of the parameter settings ("raising" ↔ "opening the louver" / "lowering"
↔ "closing the louver.
For the parameters to be visible, automatic heating/cooling must be enabled on parameter page
"O1 - Automatic heating/cooling".
o Set the parameter "Reaction at the ... of sunshine / shading" to "no reaction".
During automatic heating/cooling, the relays of the output show no reaction. Any
movements still in progress will still be finished.
o Set the parameter "Reaction at the ... of sunshine / shading" to
"raising" or "opening the louver".
During automatic heating/cooling, the device raises the blind or opens the venting louver.
o Set the parameter "Reaction at the ... of sunshine / shading" to
"lowering" or "closing the louver".
During automatic heating/cooling, the device lowers the blind or closes the venting louver.
o Set the parameter "Reaction at the ... of sunshine / shading" to "stop".
During automatic heating/cooling, the device switches the relays of the output to the "stop"
position. A drive movement, if any, will be interrupted.
o Set the parameter "Reaction at the ... of sunshine / shading" to "internal scene recall". The
number of the scene to be recalled must be specified in the parameter
"Scene number (1…8)".
During automatic heating/cooling, the device recalls the position value preset in the scene
configuration for the output. This is not a scene recall as in direct operation, but only an
approach to the corresponding scene position value.
o Set the parameter "Reaction at the ... of sunshine / shading" to "fixed position".
During automatic heating/cooling, the device recalls the fixed position value for the output.
i In the "Venetian blind" operating mode, the setting "fixed position" can only be selected in
common for the height of the Venetian blind and for the slat position.
o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"as specified by parameter". Thereafter, set the parameter
"Position of Venetian blind (0…100%)", "Position of roller shutter/awning (0…100%)" or
"Position of venting louver (0…100%)" to the desired position.
During automatic heating/cooling, the output invariably approaches the configured position
value.
o "Fixed position" only: Set the parameter "Fixed position of Venetian blind",
"Fixed position of roller shutter/awning" or "Fixed position of venting louver" to
"no change of current position".
With automatic heating/cooling, the last set position of the Venetian blind height, the roller
shutter, awning or venting louver will be maintained.
o "Fixed position" and operating mode = "Venetian blind" only: Set the parameter
"Fixed slat position (0…100%)" to the desired position value".
During automatic heating/cooling, the output invariably moves the slats to the configured
position after the height of the Venetian blind has been adjusted.
i The configured reactions will not be executed if a function with a higher priority is active
during automatic heating/cooling (e.g. safety function, forced position). The preset reaction
will not be executed either, if the automatic sun protection is overridden on account of
priority settings by a direct operation.
i "Internal scene recall" setting: For this setting, the scene function of the output must be
enabled in the ETS. Otherwise, the positions approached during automatic heating/cooling
are undefined positions. The scene position values stored in the device by a scene storage
function will be approached as well. A delay configured for scene recalls has no influence
on the recall of the scene value by the automatic heating/cooling function.
The scene function must be enabled on parameter page "O1 - Enabling functions", for the
required communication objects and parameters (on the parameter page "O1 - Scenes") to be
visible.
Like the output control via short time, long time or position telegrams, the scene function should
be assigned to direct operation. For this reason, a recalled scene position can at any time be
overridden by a forced position or a safety function. The scene position last recalled can also be
readjusted by other telegrams of the direct operation mode. The priority of direct operation and
also of the scene function can be configured with respect to the sun protection function (see
chapter 4.2.4.4.5. Sun protection settings).
i Each scene recall telegram restarts the delay time and retriggers it. If a new scene recall
telegram is received while a delay is active (scene recall not yet executed), the old (and not
yet recalled scene) will be rejected and only the scene last received executed.
i The scene recall delay has no influence on the storage of scene values. A scene storage
telegram within a scene recall delay terminates the delay and thus the scene recall.
i In case of bus voltage failure, all time functions will be stopped. Therefore, all scene recalls
that are still in the delay stage will be aborted. A scene recall received shortly before bus
voltage failure is then lost, if the corresponding delay has not yet elapsed. A delayed scene
recall will also be aborted, if a function with a higher priority (forced position, safety, sun
protection, if the priority is the same as or higher than that of direct operation) is activated.
The scene recall is nevertheless stored internally so that the scene positions last recalled
can be tracked at the end of a higher-ranking function.
The scene function must be enabled on parameter page "O1 - Enabled functions".
o Set the parameter "Overwrite the values values in the device during ETS download ?" to
"Yes".
During each ETS programming of the application or of the parameters, the scene values
configured in the ETS for the output will be programmed into the device. Scene values
stored in the device by means of a storage function will be overwritten, if any.
o Set the parameter "Overwrite the values values in the device during ETS download ?" to
"No".
Scene values stored in the device with a storage function will be maintained. If no scene
values have been stored, the position values last programmed in the ETS remain valid.
i When the device is put into operation for the first time, this parameter should be set to
"yes" so that the output is initialised with valid scene values. In the device as delivered, the
scene positions are internally set to default values as in the ETS product database.
i If the same scene number is configured for several scenes, only the scene with the lowest
internal scene number (1...8) will be addressed. The other internal scenes will be ignored in
this case.
i The configured position values are adopted in the device during programming with the ETS
only if the parameter "Overwrite values stored in the device during ETS download ?" is set
to "yes".
i Before approaching the required scene position, the device may perform a reference
movement, if the current position data is unknown (e.g. after an ETS programming
operation or after switch-on of the bus voltage).
The forced position function possesses a separate 2-bit communication object. The state of the
output in case of a forced position function is directly determined by the forced position
telegram. The first bit (bit 0) of the "Forced position" object specifies the travel direction to be
forced onto the output as in long time operation. The second bit (bit 1) activates or deactivates
the forced-position state (cf. table 6).
i The forced movement time required by an output to move the drive into the end positions is
determined by the "Movement time" parameter on parameter page "O1 - Times". Like long
time operation, a forced-position movement is derived from the travel time. Downward
movement: movement time + 20 %; Upward movement: movement time + 20 % +
configured movement time extension. Forced movements are not retriggerable.
i The slats of blinds are not repositioned at the end of forced movements into the end
positions.
i Updates of the forced position object from "forced position active" to "forced position active"
while maintaining the forced movement direction or from "forced position inactive" to
"forced position inactive" show no reaction.
i After programming of the application or of the parameters with the ETS, the forced position
is always cancelled.
i The current state of the forced position function will be stored in case of bus voltage failure.
i Parameter setting "Position tracking": The device can track absolute positions (position
telegram, scene value) during activated forced control only if the position data are known
and if positions have been predefined. If this is not the case, no reaction takes place at the
time forced control is enabled.
Position data can be tracked, if the output has been in a defined position before the forced
position function or if a new position telegram has been received via the position objects
while the forced position function was interlocked. In the latter case, a reference movement
will be executed when the forced position function is enabled, if the position was unknown
before or during the safety interlock.
Known slat positions will also be tracked as described. This is also the case, when the
height of the Venetian blind is unknown.
Long time movements (movements without position preset) will, however, always be
tracked.
i The preset "Behaviour at the end of the forced position function" will only be executed, if
the output passes over to direct operation at the end of the forced position function. If a
safety function or a sun protection function is activated (independent of the preset priority
with respect to direct operation), the function with the next lower priority will be executed.
The configured behaviour is not executed when the forced position is terminated by a
specification on bus voltage return. The parameter "Behaviour after bus voltage return" will
in this case be evaluated.
Presetting the behaviour of the forced position function after bus voltage return
The forced position communication object can be initialised after bus voltage return. In this way,
an output can be influenced and locked on bus initialisation when the forced position function is
being activated.
The behaviour of the forced position after bus voltage return is configured separately on the
parameter pages "O1 - Forced position".
Depending on the selected operating mode, the ETS adapts the designations of the parameter
settings ("raising" ↔ "opening the louver" / "lowering" ↔ "closing the louver").
After bus voltage return, the configured state is transferred to the "Forced position"
communication object.
The forced position function of the output must be enabled on parameter page
"O1 - Enabled functions". Only then are the channel-related parameters for the forced position
function visible.
o Set the parameter "Behaviour after bus voltage return" to "no forced position active".
The forced position is deactivated after bus voltage return. In this case, the parameter
"Behaviour after bus voltage return" will be evaluated on bus voltage return.
o Set the parameter "Behaviour after bus voltage return" to
"forced position function ON, raising" or "forced position function ON, opening the louver".
After bus voltage return, the forced position is activated and the blind raised or the venting
louver opened. The output is interlocked by forced control until an enable signal is received
via the bus. In this case, the parameter "Behaviour after bus voltage return" will not be
evaluated for the output.
o Set the parameter "Behaviour after bus voltage return" to
"forced position function ON, lowering" or "forced position function ON, closing the louver".
After bus voltage return, the forced position is activated and the blind lowered or the
venting louver closed. The output is interlocked by forced control until an enable signal is
received via the bus. In this case, the parameter "Behaviour after bus voltage return" will
not be evaluated for the output.
o Set the parameter "Behaviour after bus voltage return" to
"state of forced position before bus failure".
After bus voltage return, the forced position state last selected and internally stored before
bus voltage failure will be tracked. An ETS programming operation deletes the stored state
(reaction in that case same as with "no forced position active"). If the tracked state
corresponds to "no forced position active", the parameter
"Behaviour after bus voltage return" will be executed on return of bus voltage.
i Setting or tracked state "no forced position active": The reaction of the output after return of
bus voltage is defined by the parameter "Behaviour after bus voltage return".
i After programming of the application or of the parameters with the ETS, the forced position
is always cancelled.
If activated in the ETS parameters, fabric stretching is executed during each downward
movement after stopping and after the configured switchover delay has elapsed. The curtain is
then 'stretched' by moving briefly into the opposite movement direction (Figure 27).
The downward movement can be triggered by any of the following events: Long time, short time
or position telegram, forced position, safety or sun protection function or scene recall.
i Fabric stretching affects the determination of positions and the position feedback since a
fabric stretching movement changes the position of a shutter or an awning. In a positioning
move into the lower end position (100 %), the position value reported back after the fabric
stretching operation will always be a smaller one.
i Fabric stretching cannot be configured in the Venetian blind or louver modes of operation.
i Fabric stretching cannot be configured in the Venetian blind or louver modes of operation.
o Select the desired value for the "Time for fabric stretching" parameter.
After the end of a downward movement the blind stops and – after the switchover delay
has elapsed – moves backwards in opposite direction for a period corresponding to the
configured fabric stretching time.
i Set the time for fabric stretching to less than the configured or measured movement time of
the roller shutter or awning. Otherwise, there is the risk of malfunction.
i Fabric stretching will only be effected if the downward movement lasts longer than the
configured fabric stretching time.
4.2.6 Parameters
Time between switching 0...59 Time from which the dimming function
and dimming ("long signal length") is executed.
Seconds (0...59) Sets the time seconds.
Milliseconds (4...9 x 4...9 Sets the time milliseconds.
100)
The following parameters are visible for the function "Venetian Blind"...
Command on rising This parameter specifies the reaction to
flank a rising flank at the input.
No function The input is deactivated.
UP A short time telegram (UP) is triggered
by a short signal length and a long time
telegram (high) is triggered by a long
signal length.
DOWN A short time telegram (DOWN) is
triggered by a short signal length and a
long time telegram (low) is triggered by
a long signal length.
TOGGLE With this setting, the direction is
switched over internally long signal
length (MOVE). If a short time signal
transmits a STEP telegram, then this
STEP is always switched in the opposite
direction of the last MOVE. Several
STEP telegrams transmitted
successively are switched in the same
direction.
Time between step and 0...59 Time after which the function of a long
move operation actuation is executed.
Seconds (0...59) Only visible with
"Operation concept = "Short – Long – S-
hort".
Sets the time seconds.
Milliseconds (4...9 x 4...9 Sets the time milliseconds.
100)
Slat moving time 0...2...59 Time during which a long time telegram
Seconds (0...59) for slat adjustment can be terminated by
a falling flank at the input.
Sets the time seconds.
Milliseconds (0...9 x 0...9 Sets the time milliseconds.
100)
The following parameters are visible for the function "Value encoder"...
Function as Dimming value encoder This parameter specifies the value
transmitter function to be executed. The
Scene recall without data format of the value object is
storage function dependent on the set function of the
value encoder.
Scene recall with storage
function
Temperature value
transmitter
Brightness value
transmitter
Transmit value / light rising flank (pushbutton This parameter specifies the flank which
scene number on as NO contact) starts signal evaluation in the device.
The setting "rising and falling flank
Light scene number on 1...64 This parameter specifies the light scene
rising flank number transmitted on a rising flank.
(1...64) Only visible with "Light scene recall" and
"Transmit value on = rising flank
(pushbutton as NO contact)" and
"Transmit value on = rising and falling
flank (switch)".
Light scene number on 1...64 This parameter specifies the light scene
falling flank number transmitted on a falling flank.
(1...64) Only visible with "Light scene recall" and
"Transmit value on = falling flank
(pushbutton as NC contact)" and
"Transmit value on = rising and falling
flank (switch)".
Value on rising flank 0 Lux...200 Lux...1.500 Lux This parameter specifies the brightness
value transmitted on a rising flank.
Only visible with "Brightness value
encoder" and "Transmit value on =
rising flank (pushbutton as NO contact)"
and "Transmit value on = rising and
falling flank (switch)".
Value on falling flank 0 Lux...1,500 Lux This parameter specifies the brightness
value transmitted on a falling flank.
Only visible with "Brightness value
encoder" and "Transmit value on =
falling flank (pushbutton as NC contact)"
and "Transmit value on = rising and
falling flank (switch)".
Adjustment via long No With the dimming value encoder and the
actuation Yes temperature and brightness value
encoder, the value to be transmitted can
be adjusted at any time during device
operation. A value adjustment can only
be configurable here when the value is
Polarity of the disabling Disable = 1 (Enable = 0) This parameter defines the polarity of
object Disable = 0 (Enable = 1) the disabling object.
Behaviour at the end of No reaction With an active disable, the first switching
the disabling function ON object is disabled. This parameter
Switching object 1.1 OFF specifies the command transmitted via
Transmit current input this object at the end of the disabling.
status "TOGGLE" switches over the current
object value. In the "Transmit current
input status" setting, the device
evaluates the current static signal status
of the input and, according to this,
transmits the appropriately configured
telegram to the bus (contact closed at
the input = telegram as with rising flank;
contact open at input = telegram as with
falling flank).
Polarity of the disabling Disable = 1 (Enable = 0) This parameter defines the polarity of
object Disable = 0 (Enable = 1) the disabling object.
Polarity of the disabling Disable = 1 (Enable = 0) This parameter defines the polarity of
object Disable = 0 (Enable = 1) the disabling object.
Polarity of the disabling Disable = 1 (Enable = 0) This parameter defines the polarity of
object Disable = 0 (Enable = 1) the disabling object.
Polarity of the disabling Disable = 1 (Enable = 0) This parameter defines the polarity of
object Disable = 0 (Enable = 1) the disabling object.
h Output 1 - Times
Short time operation This parameter can be used to configure
the reaction to a received short-time
telegram.
No (only stop) The drive will only be stopped if it is
executing a travel movement at the time
of telegram reception. There is no
reaction if no movement is in progress.
yes Short-time operation is started on
reception of a short-time telegram when
the drive is stationary. If the drive is in
motion at the time of telegram reception,
it will be stopped.
Time for short time 0...59 This parameter defines the duration of
operation short-time operation.
Seconds (0...59)
Sets the monitoring time seconds.
Milliseconds (0...99 x 0...99 Sets the monitoring time milliseconds.
10) The duration of short-time operation
should in no case exceed half the slat
adjusting time. This parameter is only
visible, if the parameter
"Short-time operation" is set to "yes".
h Output 1 - Feedbacks
Venetian blind position The current Venetian blind position of
feedback the output can be reported separately
back to the bus.
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).
This parameter is visible only in the
'Venetian blind' operating mode.
Roller shutter/awning
position feedback
Time delay for feedback Yes (delay time under The feedback telegram can be
telegram after bus "General"!) transmitted to the bus with a delay after
voltage bus voltage return or after programming
return ? No with the ETS. Setting "Yes" activates the
delay time of the feedback in case of
bus voltage return. The delay time is
configured under "General".
This parameter is only visible in case of
an actively transmitting feedback object.
Time delay for feedback Yes (delay time under The feedback telegram can be
telegram after bus "General"!) transmitted to the bus with a delay after
voltage bus voltage return or after programming
return ? No with the ETS. Setting "Yes" activates the
delay time of the feedback in case of
bus voltage return. The delay time is
configured under "General".
This parameter is only visible in case of
an actively transmitting feedback object.
Invalid Venetian blind The device can report to the bus that the
position feedback current blind position is unknown (e.g.
after an initialisation, when no reference
movement has been executed as yet).
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).
This parameter is visible only in the
'Venetian blind' operating mode.
Invalid roller shutter- The device can report to the bus that the
awning position current roller shutter/awning position is
feedback unknown (e.g. after an initialisation,
when no reference movement has been
executed as yet).
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).
This parameter is visible only in the
"Roller Shutter / Awning" operating
mode.
Invalid venting louver The device can report to the bus that the
position feedback current venting louver position is
unknown (e.g. after an initialisation,
when no reference movement has been
executed as yet).
Time delay for feedback Yes (delay time under The feedback telegram can be
telegram after bus "General"!) transmitted to the bus with a delay after
voltage bus voltage return or after programming
return ? No with the ETS. Setting "Yes" activates the
delay time of the feedback in case of
bus voltage return. The delay time is
configured under "General".
This parameter is only visible in case of
an actively transmitting feedback object.
Drive movement The device can report to the bus that the
feedback connected drive is active, i.e. the output
is supplying power to the drive for a
travel direction.
no feedback No feedback object available for the
output. Feedback deactivated.
Feedback object is active Feedback and the object are activated.
signalling object The object transmits actively (telegram
transmission after change).
Feedback object is passive Feedback and the object are activated.
status object The object is passive (telegram
transmission only as a response to
'Read' request).
Time delay for feedback Yes (delay time under The feedback telegram can be
telegram after bus "General"!) transmitted to the bus with a delay after
voltage bus voltage return or after programming
return ? No with the ETS. Setting "Yes" activates the
delay time of the feedback in case of
bus voltage return. The delay time is
configured under "General".
This parameter is only visible in case of
an actively transmitting feedback object.
h Output 1 - Safety I
Wind alarm 1 disabled This parameter can be used to enable
the first wind alarm and thus to enable
Enabled the communication object
(setting: "disabled"). If the first wind
alarm is deactivated
Priority of safety alarms Wind -> rain -> frost This parameter defines the priority
Wind -> frost -> rain ranking of the individual safety alarms.
Rain -> wind -> frost Interpretation:
Rain -> frost -> wind High -> medium -> low.
Frost -> rain -> wind The three wind alarms have the same
Frost -> wind -> rain priority with respect to one another.
h Output 1 - Safety II
Use wind alarm Yes If the wind alarms enabled under
monitoring function ? "O1 - Safety I" are to be monitored
(only if wind alarms are No cyclically for incoming telegrams to the
enabled!) safety objects, the monitoring function
must be enabled here (setting: "yes").
Otherwise (setting: "No") there is no
Time for monitoring rain 0...23 The rain alarm monitoring time is
alarm configured here.
Hours (0...23)
Sets the monitoring time hours.
Minutes (1...59) 1...2...59 Sets the monitoring time minutes.
The cycle time of the transmitter should
be less than half the configured
monitoring time of the device. The times
can only be set if rain alarm monitoring
is activated.
Wind alarm 2
Wind alarm 3
Wind alarm 1 + 2
Wind alarm 1 + 3
Wind alarm 2 + 3
Wind alarm 1 + 2 + 3
Behaviour in case of This parameter defines the behaviour of
wind alarm the output at the beginning of a wind
alarm.
The behaviour preset in this parameter
will be executed when one of the
assigned wind alarms is activated. This
parameter is only visible if the output
has been assigned to at least one wind
alarm.
No reaction At the beginning of the wind alarm or
wind alarms, the output is interlocked
and the relay of the output shows no
reaction. Any movements in progress at
this instant will still be completely
finished.
Raising / opening the The device raises the blind or opens the
louver venting louver at the beginning of the
wind alarm or wind alarms and locks the
output thereafter.
Lowering / closing the The device lowers the blind or closes
louver the venting louver at the beginning of
the wind alarm or wind alarms and locks
the output thereafter.
Stop At the beginning of the wind alarm or
wind alarms, the device switches the
The reception of a
telegram 'Automatic mode inactive' at
the "Automatic" object immediately ends
the automatic mode in both cases. The
behaviour is in this case defined by the
parameter
"Reaction at the end of automatic opera-
tion".
parameter
"Activation of automatic operation via..."
is set to
"object automatic & immediate tracking".
Polarity of "Automatic Automatic mode: enabled = This parameter defines the polarity of
mode disable" object 1; disabled = 0 the automatic mode disable object.
Disabling is active when a telegram with
Automatic mode: enabled polarity 'disabled' is received.
= 0; disabled = 1 This parameter is only visible, if the
parameter
"Disabling function for automatic mode -
?" is set to "yes".
Disabling function for Yes Direct operation can be disabled. When
direct operation ? disabling is active, a direct operation
No can – independent of the preset
priority – never override a sun protection
function. In this case, direct operation is
disabled in other functions, too.
The "Yes" setting enables the disabling
function and makes the disabling object
visible.
Direct operation =
long-time/short-time operation;
Positioning via objects, scenes
Polarity of "Direct Automatic mode: enabled = This parameter defines the polarity of
operation disable" 1; disabled = 0 the disabling object for direct operation.
object Disabling is active when a telegram with
Automatic mode: enabled polarity 'disabled' is received.
= 0; disabled = 1 This parameter is only visible, if the
parameter "Direct operation disable?" is
set to "yes".
Venetian blind position 0...50…100 This parameter sets the fixed position of
(0...100 %) the Venetian blind to be approached at
the beginning of shading.
This parameter is only visible, if the
parameter "Fixed position of Venetian
blind" is set to "as specified by
parameter". This parameter is visible
only in the 'Venetian blind' operating
mode.
Fixed slat position 0...50…100 This parameter sets the fixed position of
(0...100 %) the slat to be approached at the
beginning of shading and, as the case
may be, after positioning of the Venetian
blind.
This parameter is only visible, if the slat
is to approach a fixed position at the
beginning of shading. This parameter is
visible only in the 'Venetian blind'
operating mode.
Position of roller shutter 0...50…100 This parameter sets the fixed position of
/ awning the roller shutter or awning to be
(0...100 %) approached at the beginning of shading.
This parameter is only visible, if the
parameter "Fixed position of shutter /
awning" is set to "as specified by
Offset slat position -100…0...100 This parameter is used for setting the
(-100..100 %) slat offset. The value specified in this
parameter is added at the beginning of
shading to the current slat angle.
Even with offset correction, the 0...100%
slat position limits cannot be
overstepped. It should be noted that the
configured offset value can be
overwritten by the object after reception
of a dynamic value. This parameter is
only visible, if the parameter "Offset with
fixed and variable slat position" is set to
"Offset as configured" or to "Offset as
configured and via object". This
parameter is visible only in the 'Venetian
blind' operating mode.
Store offset slat position If the offset is preset via the object, this
via object in case of bus parameter defines whether the received
voltage failure ? value is to be stored in the device's NV
memory.
This parameter is only visible, if the
parameter "Offset with fixed and
variable slat position" is set to "offset as
configured and via object". This
parameter is visible only in the 'Venetian
blind' operating mode.
yes The value received via the object will be
stored in case of bus voltage failure in a
non-volatile memory of the device. The
originally configured offset value is
definitely overwritten in the process.
No The value received via the object will
only be stored temporarily in volatile
memory. This only replaces the
configured value until the device is
reinitialised. After the initialisation, the
offset value configured in the ETS will
be used again.
Time delay at end of 0...59 The telegram received via the object
sunshine / shading "Sunshine / shading facade" for
Minutes (0...59) deactivation of shading (depending on
polarity) can be evaluated with a time
delay..
Venetian blind position 0...50…100 This parameter sets the fixed position of
(0...100 %) the Venetian blind to be approached at
the end of shading.
0...50…100
Position of roller shutter 0...50…100 This parameter sets the fixed position of
/ awning the roller shutter or awning to be
(0...100 %) approached at the end of shading.
This parameter is only visible, if the
parameter "Fixed position of shutter /
awning" is set to "as specified by
parameter". This parameter is visible
only in the "Roller Shutter / Awning"
operating mode.
Time delay at the 0...59 The telegram received via the object
beginning of presence "Heating/cooling presence" for activation
Minutes (0...59) of the presence function (in acc. with
polarity) can be evaluated with a time
delay. A time setting of "0" in the
parameters deactivates the respective
delay time. In this case, the state of the
presence object is evaluated
immediately.
Time delay at the end of 0...59 The telegram received via the object
presence "Heating/cooling presence" for
Minutes (0...59) deactivation of the presence function (in
acc. with polarity) can be evaluated with
a time delay. A time setting of "0" in the
parameters deactivates the respective
delay time. In this case, the state of the
presence object is evaluated
immediately.
End on heating *
No reaction The relays of the output show no
reaction. Any movements still in
progress at this instant will still be
finished.
Raising The device raises the blind.
Lowering The device lowers the blind.
Internal scene recall An internal scene of the device is
recalled.
End on heating *
No reaction The relays of the output show no
reaction. Any movements still in
progress at this instant will still be
finished.
Raising The device raises the blind.
Lowering The device lowers the blind.
Internal scene recall An internal scene of the device is
recalled.
Fixed roller shutter / awning The output moves to a configured fixed
position roller shutter or awning position.
*: The parameter settings for heating or
cooling or beginning or end must be
configured separately. The setting
options - also for the follow-up
parameters - are identical in all cases.
End on heating *
No reaction The relays of the output show no
reaction. Any movements still in
progress at this instant will still be
finished.
Opening the louver The device opens the venting louver.
Closing the louver The device closes the venting louver.
Internal scene recall An internal scene of the device is
recalled.
Venetian blind position 0...50…100 This parameter sets the fixed position of
(0...100 %) the Venetian blind to be approached in
case of automatic heating/cooling.
This parameter is only visible, if the
parameter "Fixed position of Venetian
blind" is set to "as specified by
parameter". In addition, this parameter
is visible only in the 'Venetian blind'
operating mode.
Fixed slat position 0...50…100 This parameter sets the fixed position of
(0...100 %) the slat to be approached in case of
automatic heating/cooling and, as the
case may be, after positioning of the
Venetian blind.
This parameter is only visible, if the slat
is to approach a fixed position with
automatic heating/cooling. In addition,
this parameter is visible only in the
'Venetian blind' operating mode.
Position of roller shutter 0...50…100 This parameter sets the fixed position of
/ awning the Venetian blind to be approached
(0...100 %) with automatic heating/cooling.
This parameter is only visible, if the
parameter "Fixed position of shutter /
awning" is set to "as specified by
parameter". In addition, this parameter
is visible only in the "Roller Shutter /
Awning" operating mode.
h Output 1 - Scenes
Delay scene recall ? Yes A scene is recalled via the scene
extension object. If needed, the scene
No recall on the device can be made with a
delay after reception of a recall telegram
(setting: "Yes"). The recall is
alternatively made immediately on
reception of the telegram (setting: "No").
A recall delay has no influence on the
storage of scene values.
Slat position for scene X 0*...100 This parameter is used for configuring
the slat position which is executed when
*: The predefined position the scene is recalled.
X =depending on the value is dependent on the This parameter is visible only in the
scene (1...8) scene (1...8). 'Venetian blind' operating mode.
Forced position on, raising / After bus voltage return, the forced
opening the louver position is activated and the blind raised
or the venting louver opened.
Forced position on, After bus voltage return, the forced
lowering / closing the louver position is activated and the blind
lowered or the venting louver closed.
State of forced position After bus voltage return, the forced
before bus failure position state last selected and internally
stored before bus voltage failure will be
tracked. An ETS programming operation
deletes the stored state (reaction in that
case same as with "no forced position
active").
h Output 1 - Fabric stretching (only in the "Roller Shutter / Awning" operating mode)
Time for fabric 0...59 This parameter can be used to specify
stretching the time for fabric stretching. After the
Seconds (0...59) end of a downward travel the awning
stops and – after elapsing of the
switchover delay – moves backwards in
opposite direction for a period
corresponding to the fabric stretching
time configured here.
Setting of the fabric stretching time in
seconds.
Milliseconds 4...9 Setting of the fabric stretching time in
(4...9 x 100) milliseconds.
The time for fabric stretching must be
less than the movement time of the
roller shutter/awning.
5 Appendix
5.1 Index
A P
application program.. ............................. 17 Performing a reference movement .. 10
Automatic heating/cooling.. ................... 79 (optional)
Position feedback messages.. ............... 49
B Presetting the position.. ......................... 48
blind height.. .......................................... 44 priority.. .................................................. 93
bus voltage failure.. ............................... 37
bus voltage return.. ................................ 37 R
Reference movement.. .......................... 47
C
Commissioning.. .................................... 10 S
communication objects.. ........................ 18 Safe-state mode.. .................................. 17
Computing.. ........................................... 44 Safety function.. ..................................... 54
Short time operation.. ............................ 40
D Simple sun protection.. .......................... 59
Delay after bus voltage return.. ......... 27-28 slat moving time.. ................................... 41
Delivery state.. ....................................... 94 Slat offset.. ............................................. 74
Device components.. ............................. 5 slat position.. .......................................... 45
Dimming function.. ................................. 30 Sun protection function.. ........................ 58
direct operation.. .............................. 40, 48 Switching function.. ................................ 29
disabling function.. ................................. 36 switchover time.. .................................... 42
drive movement.. ................................... 51
T
E Telegram rate limit.. ............................... 27
effect .. ................................................... 29
Effect.. ................................................... 26 U
ETS programming.. ............................... 37 Unknown position.. ................................ 51
ETS search paths.. ................................ 14 Unloading the application program.. ...... 17
extended sun protection.. ...................... 60
V
F Value transmitter function.. .................... 33
Fabric-stretching function.. .................... 91 Venetian blind function.. ........................ 31
functionalities.. ....................................... 3
L
Light scene function.. ............................. 85
long time operation.. .............................. 40
louver position.. ..................................... 44
M
Measuring the slat moving time.. ........... 10
Measuring the travelling time .. 9
extension
Measuring the travelling times.. ............. 9
movement time extension.. .................... 42
O
operating mode.. .................................... 37
Operating mode.. ................................... 37