Cooling Tower Efficiency Calculations
Cooling Tower Efficiency Calculations
Cooling Tower Efficiency Calculations
Or Simply
In summer the ambient air wet bulb temperature raises when compared to winter thus
limiting the cooling tower efficiency.
Cycle of Concentration
The cycle of concentration is a dimensionless number. It is a ratio between parameter in
Cooling Water to the parameter in Makeup water. It can be calculated from any the
following formulae.
B = E/ (COC-1)
COC = Cycle of Concentration. Varies from 3.0 to 7.0 depending upon Manufactures
Guidelines
E = 0.00085 x R x 1.8 x C
R= Range